VLT® AutomationDrive FC 360

90–315 kW, Enclosure Sizes J8–J9

1 Introduction

This operating guide provides necessary information for qualified personnel to install and commission the AC drive. Read and follow the instructions to use the drive safely and professionally.

Do not dispose of equipment containing electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation.

2 Safety

Pay particular attention to the safety instructions and general warnings to avoid the risk of death, serious injury, and equipment or property damage.

WARNING

3 Installation

3.1 Mechanical Dimensions

Illustration 1: Mechanical Dimensions, Enclosure Sizes J8–J9

Table 1: Power Ratings, Dimensions, and Weights for Enclosure Sizes J8–J9
Enclosure size (IP20)Power [kW (hp)] 3x380–480 VHeight [mm (in)]Width [mm (in)]
AA(1)aBbb1
J8110–160 (150–250)889 (35.0)909 (35.8)844 (33.2)250 (9.8)180 (7.1)200 (7.9)
J9200–315 (300–450)1096 (43.1)1122 (44.2)1051 (41.4)350 (13.8)280 (11.0)271 (10.7)
Enclosure size (IP20)Depth [mm (in)]Mounting hole [mm (in)]Center of gravity [mm (in)]Maximum weight [kg (lb)]
CDEFG
J8375 (14.8)11 (0.4)128 (5.0)495 (19.5)148 (5.8)98 (216)
J9375 (14.8)11 (0.4)176 (6.9)611 (24.1)148 (5.8)164 (362)

Note: (1) Including decoupling plate.

3.2 Removing the Front Cover

Procedure:

  1. Step 1: Loosen and remove the 2 screws on the front cover.
  2. Step 2: Disconnect the front cover from the hooks.

Illustration 2: Removing the Front Cover

3.3 Connecting to Mains, Motor, Control Terminals, and Relays

Illustration 3: Connecting to Mains, Motor, Control Terminals, and Relays

3.4 Control Terminals

Illustration 4: Control Terminals

4 Specifications

Table 2: Electrical Data for Normal Overload, Mains Supply 3x380–480 V AC
DriveEnclosure sizeNormal overload=110% current during 60 sTypical shaft output at 400 V [kW]Typical shaft output at 460 V [hp]Output current (3-phase)Continuous (at 400 V) [A]Intermittent (60 s overload) (at 400 V) [A]Continuous (at 460 V) [A]Intermittent (60 s overload) (at 460 V) [A]Continuous kVA (at 400 V) [kVA]Continuous kVA (at 460 V) [kVA]Maximum input currentContinuous (at 400 V) [A]Continuous (at 460 V) [A]Maximum number and size of cables per phaseMains and motor [mm² (AWG)]Maximum external mains fuses [A]Estimated power loss at 400 V [W]Estimated power loss at 460 V [W]Efficiency [%]Output frequency [Hz]Heat sink overtemperature trip [°C (°F)]Control card overtemperature trip [°C (°F)]
Q110J81101502122331902091471512041832x95 (2x3/0)31525592261980–590110 (230)75 (167)
Q132J81322002602862402641801912512312x95 (2x3/0)350295427240–590110 (230)75 (167)
Q160J81602503153473023322182413042912x95 (2x3/0)400377036280–590110 (230)75 (167)
Q200J92003003954353613972742883813482x185 (2x350 mcm)550411635690–590110 (230)80 (176)
Q250J92503504805284434873333534634272x185 (2x350 mcm)630513745660–590110 (230)80 (176)
Q315J93154505886475355894074265675162x185 (2x350 mcm)800667457140–590110 (230)80 (176)
Table 3: Electrical Data for High Overload, Mains Supply 3x380–480 V AC
DriveEnclosure sizeHigh overload=150% current during 60 sTypical shaft output at 400 V [kW]Typical shaft output at 460 V [hp]Output current (3-phase)Continuous (at 400 V) [A]Intermittent (60 s overload) (at 400 V) [A]Continuous (at 460 V) [A]Intermittent (60 s overload) (at 460 V) [A]Continuous kVA (at 400 V) [kVA]Continuous kVA (at 460 V) [kVA]Maximum input currentContinuous (at 400 V) [A]Continuous (at 460 V) [A]Maximum number and size of cables per phaseMains and motor [mm² (AWG)]Maximum external mains fuses [A]Estimated power loss at 400 V [W]Estimated power loss at 460 V [W]Efficiency [%]Output frequency [Hz]Heat sink overtemperature trip [°C (°F)]Control card overtemperature trip [°C (°F)]
H90KJ8901251772661602401231271711542x95 (2x3/0)31520311828980–590110 (230)75 (167)
H110J81101502123181902851471512041832x95 (2x3/0)350228920510–590110 (230)75 (167)
H132J81322002603902403601801912512312x95 (2x3/0)400292320890–590110 (230)75 (167)
H160J91602503154733024532182413042912x185 (2x350 mcm)550309328720–590110 (230)80 (176)
H200J92003003955933615422742883813482x185 (2x350 mcm)630403935750–590110 (230)80 (176)
H250J92503504807204436653333534634272x185 (2x350 mcm)800500444580–590110 (230)80 (176)

5 Ambient Conditions

Ambient Conditions for J8–J9 enclosure size
ParameterValue
IP RatingIP20/Chassis
Vibration test (standard)0.7 g
Relative humidity5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
Aggressive environment (IEC 60068-2-43) H₂S testClass Kd
Aggressive gases (IEC 60721-3-3)Class 3C3
Test method according to IEC 60068-2-43H₂S (10 days)
Ambient temperature (at SFAVM switching mode)- with derating: Maximum 55 °C (131 °F)
- with full output power of typical EFF2 motors (up to 90% output current): Maximum 50 °C (122 °F)
- at full continuous FC output current: Maximum 45 °C (113 °F)
Minimum ambient temperature during full-scale operation-15 °C (5 °F)
Minimum ambient temperature at reduced speed performance-20 °C (-4 °F)
Temperature during storage/transport-25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating1000 m (3281 ft)
Maximum altitude above sea level with derating3000 m (9842 ft)
Energy efficiency classIE2

6 Mounting Clearance

Enclosure size J8 and J9

Minimum mounting clearance [Maximum temperature 50 °C (122 °F)]:

7 EMC Compatibility and Motor Cable Length

8 Programming

8.1 Local Control Panel (LCP)

Illustration 5: Local Control Panel (LCP 21 and LCP 23)

Functional Section A: Display

Table 4: Display Function
NumberFunction
1The setup number shows the active setup and the edit setup. For LCP 21: The setup number shows the active setup and the edit setup. If the same setup acts as both active and edit setup, only that setup number is shown (factory setting). For LCP 23, the setup number shows on the upper right corner in the status mode. For example, "1(2)" means the active setup is "1" and the editing setup is "2".
2LCP 21 shows only parameter number. LCP 23 shows both parameter number and name.
3Parameter value.
4Motor direction indicated by a small arrow pointing either clockwise or counterclockwise. For LCP 23, it only shows in status menu on the upper right corner of the screen.
5The triangle indicates if the LCP is in Status, Quick Menu, or Main Menu.

Functional Section B: Menu Key

Press [Menu] to select among Status, Quick Menu, or Main Menu.

Functional Section C: Indicator Lights (LEDs) and Navigation Keys

Table 5: Indicator Lights (LEDs)
NumberIndicator LightFunction
6On (Green)Turns on when the drive receives power from the mains voltage, a DC bus terminal, or a 24 V external supply.
7Warn. (Yellow)Turns on when warning conditions are met. Text is shown in the display area identifying the warning.
8Alarm (Red)Flashes when a fault condition occurs. Text is shown in the display area identifying the alarm.
Table 6: Navigation Keys
NumberKeyFunction
9/13Up/Down(1) Switches among parameter groups, parameters, and within parameters. (2) Increases or decreases parameter values. (3) Sets local reference.
10[Back]Moves to the previous step or layer in the navigation structure.
11RightMoves from left to right within the parameter value to change each digit individually.
12[OK]Selects a parameter and accepts changes to parameter settings.

Functional Section D: Operation Keys and Indicator Lights (LEDs)

Table 7: Operation Keys and Indicator Lights (LEDs)
NumberKeyFunction
14[Hand On](1) Starts the drive in local control. (2) An external stop signal via control input or serial communication overrides the local hand on command.
15[Off/Reset](1) Stops the motor but does not remove power to the drive. (2) Resets the drive manually after a fault has been cleared. (3) In alarm mode, the alarm is reset when the alarm condition is removed.
16[Auto On]Puts the system in remote operational mode, in which the drive only responds to an external start command via control terminals or bus communication.

NOTICE

[2] Coast inverse is the default option for parameter 5-12 Terminal 27 Digital Input. If there is no 24 V supply to terminal 27, [Hand On] does not start the motor. Connect terminal 12 to terminal 27.

8.2 Automatic Motor Adaptation (AMA)

Procedure:

  1. Set motor data in parameter group 1-Load and Motor according to the motor nameplate.
  2. Connect terminal 27 to terminal 12 (24 V voltage) or choose [0] No operation in parameter 5-12 Terminal 27 Digital Input.
  3. Set [1] Enable Complete AMA or [2] Enable Reduced AMA for parameter 1-29 Automatic Motor Adaptation (AMA).
  4. Press the [Hand On] key, the test runs automatically and the main display indicates when it is completed.

9 Troubleshooting

Table 8: Warning and Alarm Code List
NumberDescriptionWarningAlarmTrip lockCause
2Live zero errorXXSignal on terminal 53 or 54 is less than 50% of the values set in parameter 6-10 Terminal 53 Low Voltage, parameter 6-12 Terminal 53 Low Current, parameter 6-20 Terminal 54 Low Voltage, and parameter 6-22 Terminal 54 Low Current.
3No motorXXXNo motor has been connected to the output of the drive, or 1 motor phase is missing.
4Mains phase loss(1)XXXMissing phase on the supply side, or the voltage imbalance is too high. Check the supply voltage.
7DC overvoltage(1)XXDC-link voltage exceeds the limit.
8DC undervoltage(1)XXDC-link voltage drops below the voltage warning low limit.
9Inverter overloadedXXMore than 100% load for too long.
10Motor ETR overtemperatureXXMotor is too hot due to more than 100% load for too long.
11Motor thermistor overtemperatureXXThermistor or thermistor connection is disconnected, or the motor is too hot.
12Torque limitXXTorque exceeds value set in either parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode.
13OvercurrentXXXInverter peak current limit is exceeded. For J1–J6 units, if this alarm occurs on power-up, check whether power cables are mistakenly connected to the motor terminals.
14Ground faultXXDischarge from output phases to ground.
16Short circuitXXShort circuit in motor or on motor terminals. For J7 units, if this alarm occurs on power-up, check whether power cables are mistakenly connected to the motor terminals.
17Control word timeoutXXNo communication to the drive.
18Start failedXX
25Brake resistor short-circuitedXXBrake resistor is short-circuited, thus the brake function is disconnected.
26Brake overloadXXThe power transmitted to the brake resistor over the last 120 s exceeds the limit. Possible corrections: Decrease brake energy via lower speed or longer ramp time.
27Brake IGBT/Brake chopper short-circuitedXXBrake transistor is short-circuited, thus brake function is disconnected.
28Brake checkXBrake resistor is not connected/working.
30U phase lossXXMotor phase U is missing. Check the phase.
31V phase lossXXMotor phase V is missing. Check the phase.
32W phase lossXXMotor phase W is missing. Check the phase.
34Fieldbus faultXXPROFIBUS communication issues have occurred.
35Option faultXXFieldbus or option B detects internal faults.
36Mains failureXXThis warning/alarm is only active if the supply voltage to the drive is lost and parameter 14-10 Mains Failure is NOT set to [0] No Function.
38Internal faultXXContact the local supplier.
40Overload T27XCheck the load connected to terminal 27 or remove short-circuit connection.
41Overload T29XCheck the load connected to terminal 29 or remove short-circuit connection.
46Gate drive voltage faultXX
4724 V supply lowXXX24 V DC may be overloaded.
50AMA calibrationXX
51AMA check Unom and InomXXWrong setting for motor voltage and/or motor current.
52AMA low InomXXMotor current is too low. Check the settings.
53AMA big motorXXThe power size of the motor is too large for the AMA to operate.
54AMA small motorXXThe power size of the motor is too small for the AMA to operate.
55AMA parameter rangeXXThe parameter values of the motor are outside of the acceptable range. AMA does not run.
56AMA interruptXXThe AMA is interrupted.
57AMA timeoutXX
58AMA internalXXContact the local supplier.
59Current limitXXXThe drive is overloaded.
60External InterlockXX
61Encoder lossXXA feedback fault is detected by option B.
63Mechanical brake lowXXActual motor current has not exceeded release brake current within start delay time window.
65Control card tempXXXThe cutout temperature of the control card is 80 °C (176 °F).
67Option module configuration has changedXXOne or more options have either been added or removed since the last power-down. To apply the change, enable option layout changes in parameter 14-89 Option Detection. Alternatively, restore the correct option configuration.
69Power card tempXXX
70Illegal FC configXX
80Drive initialized to default valueXXAll parameter settings are initialized to default settings.
87Auto DC brakeXXOccurs in IT mains when the drive coasts and the DC voltage is higher than 830 V. Energy on DC-link is consumed by the motor. This function can be enabled/disabled in parameter 0-07 Auto DC Braking.
88Option detectionXXA change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen configuration and the option layout has been changed. To apply the change, enable option layout changes in parameter 14-89 Option Detection. Alternatively, restore the correct option configuration.
90Feedback monitorXX
95Broken beltXX
99Locked rotorXX
101Flow/pressure information missingXX
120Position control faultXX
124Tension limitXX
126Motor rotatingXX
127Back EMF too highXXTry to start PM motor which is rotating in an abnormal high speed.
250New spare partXX
251New type codeXX

Note: (1) These faults may be caused by mains distortions. Installing a Danfoss line filter may rectify this problem. (2) An (X) marked in the above table indicates that the warning or alarm has occurred. A warning precedes an alarm.

10 Accessories and Spare Parts

Accessories and spare parts
Accessories and spare partsCode number
(1) VLT® PROFIBUS DP MCA 101134B6778
(2) VLT® PROFINET MCA 120134B6779
(3) VLT® encoder input MCB 102132B0282
(4) VLT® resolver input MCB 103132B0283
(5) VLT® 24 V DC supply MCB 107130B1208
(6) VLT® graphical control panel LCP 23132B0801
(7) VLT® numeric control panel LCP 21132B0254
(8) Remote mounting kit for LCP with cable, 3 m132B0102
(9) LCP remote mounting cable, 3 m132B0132
(10) Control card for FC 360 J8-J9132G0279

Note: (1) - (9) are accessories, and (10) is spare part. For more spare parts, contact Danfoss.

11 Technical Documentation

Scan the QR code to access more technical documents for the drive. Or, after scanning the QR code, click Global English on the website to select your local region's website, search FC 360 to find the documents with your own languages.

Models: FC360 J8-J9_OG, e30bv159.10, e30bv154.10, e30bv161.10, VLT AutomationDrive FC 360 Frequency Inverter, FC 360 Frequency Inverter, Frequency Inverter, Inverter

File Info : application/pdf, 2 Pages, 6.12MB

PDF preview unavailable. Download the PDF instead.

AQ458833512974en-000101

References

Danfoss A/S

Related Documents

PreviewDanfoss VLT AutomationDrive FC 360 Operating Guide
This operating guide provides essential information for the safe and professional installation and commissioning of the Danfoss VLT AutomationDrive FC 360 AC drive, covering specifications, safety, troubleshooting, and accessories for models 90-315 kW in enclosure sizes J8-J9.
PreviewVLT AutomationDrive FC 360 Operating Guide
Comprehensive operating guide for the Danfoss VLT AutomationDrive FC 360 AC drive, covering installation, safety, specifications, and troubleshooting for models ranging from 0.37 to 90 kW.
PreviewDanfoss VLT Safe Torque Off Operating Guide
This operating guide provides comprehensive information on the Safe Torque Off (STO) function for Danfoss VLT FC Series frequency converters, covering installation, commissioning, safety, and application examples.
PreviewDanfoss VLT® AutomationDrive FC 302 Enclosed Drives: Design Guide for 90-710 kW Applications
This design guide from Danfoss provides comprehensive technical information for the integration, installation, and operation of the VLT® AutomationDrive FC 302 enclosed drives, covering power ratings from 90 to 710 kW. It details features, specifications, safety, and electrical considerations for optimal system design and performance.
PreviewDanfoss VLT® AutomationDrive FC 302 Design Guide (315-1200 kW)
Comprehensive design guide for the Danfoss VLT® AutomationDrive FC 302 series (315-1200 kW), detailing product features, specifications, safety, approvals, installation, and accessories for industrial motor control applications.
PreviewDanfoss VLT® Adjustable Frequency Drive Safe Torque Off (STO) Instruction Manual
Comprehensive instruction manual for Danfoss VLT® Adjustable Frequency Drives featuring the Safe Torque Off (STO) function. Covers installation, commissioning, safety, technical data, and compliance with EN ISO 13849-1, IEC 61508, and EN 60204-1 standards.
PreviewDanfoss VLT Frequency Converters: Safe Torque Off Operating Guide
This operating guide from Danfoss details the Safe Torque Off (STO) function for VLT® Frequency Converters. It covers essential information on installation, commissioning, safety protocols, application examples, and technical specifications, ensuring safe operation and compliance with industry standards like EN ISO 13849-1 and IEC 61508.
PreviewDanfoss VFD Drives: Overview, Comparisons, and Repair Options
An in-depth look at Danfoss Variable Frequency Drives (VFDs), including product lines, comparisons with other brands like ABB and Yaskawa, and guidance on repair versus upgrade decisions. Learn about VFD benefits, energy efficiency, and industry standards.