Important Information
IMPORTANT: Prior to installation, please read this manual carefully to avoid mistakes that can lead to malfunction or damage to the equipment. Changes, modifications, or repairs not authorized by the manufacturer shall void your rights under the warranty.
SATEL aims to continually improve product quality, which may result in changes to technical specifications and software. Current information about these changes is available on the SATEL website. Please visit: https://support.satel.pl
The declaration of conformity may be consulted at www.satel.pl/ce
The following symbols may be used in this manual:
- ? note
- ⚠️ caution
Product Overview
The TSD-1 multisensor detector can detect the early stages of fire development when there is visible smoke and/or a temperature rise. This manual applies to detectors with electronics version 1.7 or higher.
1. Features
- Selection of detector operating mode:
- smoke and heat detection
- smoke detection
- heat detection
- EN54-7 compliant visible smoke sensor.
- EN54-5 compliant heat sensor.
- Alarm memory option.
- Selection of alarm output type:
- NO (Normally Open)
- NC (Normally Closed)
- 2EOL/NO
- 2EOL/NC
- Configuration of detector parameters via DIP-switches.
- Detection of optical chamber fouling.
- Red LED indicator.
2. Description
Smoke detection
An optical method is used for detecting visible smoke. When the concentration of smoke in the optical chamber exceeds a given threshold, an alarm is triggered. The smoke sensor's operating parameters are modified based on temperature changes recorded by the heat sensor (thermistor). The detector automatically compensates for gradual changes in the optical chamber caused by dust deposition.
Heat detection
The heat sensor operates according to the requirements of Class A1R (EN 54-5). An alarm is triggered when the temperature exceeds 54°C or if there is a too fast temperature rise, as detailed in Table 1.
Air temperature rise velocity | Lower limit of response time | Upper limit of response time |
---|---|---|
1°C/min | 29 min | 40 min 20 s |
3°C/min | 7 min 13 s | 13 min 40 s |
5°C/min | 4 min 9 s | 8 min 20 s |
10°C/min | 1 min | 4 min 20 s |
20°C/min | 30 s | 2 min 20 s |
30°C/min | 20 s | 1 min 40 s |
Alarm signaling
In the event of an alarm, the detector's output is activated, and the LED lights up.
Alarm memory
If alarm memory is disabled, the detector signals the alarm until the cause no longer exists. If alarm memory is enabled, the detector signals the alarm until it is reset (e.g., by power reset).
Alarm output
The detector features a relay output activated during an alarm. The relay contacts can be selected as normally open (NO) or normally closed (NC) in the normal state. When connecting to a SATEL control panel, the detector's built-in EOL resistors (2 x 1.1 kΩ) can be used. The control panel input should be programmed as 2EOL. Removing the detector's cover or cutting wires in this configuration will trigger a tamper alarm.
Detection of optical chamber soiling
The detector monitors the optical chamber's condition. Dust deposition can lead to malfunctioning. When the optical chamber requires cleaning, this state is indicated by the LED.
LED indicator
The red LED indicates:
- Alarm: ON
- Optical chamber soiling: one flash every 30 seconds
- Incorrectly configured settings: flashing
3. Selecting a Mounting Location
The detector is designed for indoor installation.
- Install the detector close to the building/apartment exit (e.g., in the hall or lobby). Refer to Figures 1 and 2 for typical placement.
- For typical home or office applications, install the detector on the ceiling, as close as possible to the center of the room, at least 0.5 meters from walls or other objects. Refer to Figure 3 for correct placement.
- Do not install the detector in areas with high concentrations of dust, or where water steam may form or condense.
- Do not install the detector near heaters, cookers, fans, or air-conditioner outlets.
- Do not install the detector in locations with obstructed airflow (e.g., in recesses or niches).
Diagram Description (Figures 1 & 2): These figures illustrate typical detector placements in residential layouts. Detector placement is indicated by numbered circles: 1 - living room, 2 - room, 3 - hall/lobby, 4 - kitchen, 5 - basement. Different locations are marked as basic or additional for detector installation.
Diagram Description (Figure 3): This figure shows correct and incorrect detector placement relative to walls. A green checkmark indicates correct placement at least 0.5 meters from a wall, while a red cross indicates incorrect placement too close to a wall.
4. Installation
Disconnect power before making any electrical connections.
- Remove the plastic dust cap.
- Turn the cover counter-clockwise and remove it. (Refer to Figures 8 and 9 for removal steps).
- Secure the enclosure base to the wall using appropriate wall plugs (anchors) and screws, selected for the specific mounting surface (e.g., concrete, brick, plaster).
- Configure the detector using the DIP-switches. Refer to the "Configuring the detector" section.
- Connect the wires to the corresponding terminals in the enclosure base. Refer to the "Connecting wires" section.
- Replace the detector cover and turn it clockwise.
- If work is being carried out in the premises that may cause soiling of the optical chamber, cover the detector with a plastic dust cover and leave it until the work is finished.
? It is recommended to keep the dust cap for future repair work.
Diagram Description (Figures 8-15): These figures illustrate the physical steps for installation and maintenance, including removing the detector cover, releasing and removing the electronics module, removing the optical chamber cover, and removing the thermistor element.
4.1 Configuring the detector
Detector settings are configured using the DIP-switches shown in Figures 4 and 5.
DIP-switch number | Parameter | DIP-switch position | |
---|---|---|---|
OFF | ON | ||
1 | relay type | NO | NC |
2 | alarm memory | disabled | enabled |
3 | heat detection | disabled | enabled |
4 | smoke detection | disabled | enabled |
? If smoke detection and heat detection are disabled, the detector's LED will flash to indicate an error.
Output configuration | DIP-switch number | |
---|---|---|
1 | 2 | |
without EOL resistors | OFF | ON |
with EOL resistors (2EOL) | ON | OFF |
4.2 Connecting wires
The terminals in the enclosure base are numbered:
- 1: common ground
- 2 and 3: alarm output
- 4: power input +12 V DC
- 5: additional terminal
Figures 6 and 7 show examples of connecting the detector to a control panel. (OUTx – power output; COM – common ground; Zx – zone programmed as fire; Zy – zone programmed as tamper). In Figure 7, the additional terminal (5) is used to connect the tamper circuit; interrupting this circuit triggers a tamper alarm.
Diagram Description (Figures 6 & 7): These diagrams illustrate wiring configurations. Figure 6 shows connections without EOL resistors, while Figure 7 shows connections with EOL resistors (2EOL) and a tamper circuit connection to a control panel.
5. Maintenance
The detector should undergo regular checks for correct functioning. Periodic checks should be performed at least every 6 months.
6. Cleaning the optical chamber
It is recommended to clean the optical chamber at least once a year. Cleaning is necessary when the LED indicates chamber fouling (one flash every 30 seconds).
- Turn the cover counter-clockwise and remove it. (Refer to Figures 8 and 9).
- Pull the release lever to unlock the electronics module and turn it counter-clockwise. (Refer to Figures 10 and 11).
- Remove the electronics module with the optical chamber. (Refer to Figure 12).
- Remove the plastic element with the thermistor from the optical chamber cover. (Refer to Figure 13).
- Release the mounting catch and remove the optical chamber cover. (Refer to Figure 14 and 15).
- Using a soft brush or compressed air, clean the labyrinth in the cover and the base of the optical chamber, paying attention to the recesses where the LEDs are installed.
- Replace the optical chamber cover.
- Replace the plastic element with the thermistor on the optical chamber.
- Secure the electronics module with the optical chamber in the cover and turn it clockwise.
- Replace the detector cover and turn it clockwise.
7. Specifications
Supply voltage | 12 VDC ±15% |
Standby current consumption | 0.25 mA |
Maximum current consumption | 24 mA |
Alarm output (relay, resistive load) | 40 mA / 16 V DC |
Class according to EN 54-5 (heat sensor) | A1R |
Static response temperature | 54°C |
Environmental class according to EN50130-5 | II |
Operating temperature range | -10°C...+55°C |
Maximum humidity | 93±3% |
Enclosure dimensions | Ø108 x 61 mm |
Weight | 164 g |
The TSD-1 smoke and heat detector conforms to the essential requirements of the EU Regulations and Directives:
- CPR 305/2011 Regulation of the European Parliament and of the Council of 9 March 2011 laying down harmonized conditions for the marketing of construction products and repealing the Council Directive 89/106/EEC on construction products.
- EMC 2014/30/UE Electromagnetic Compatibility Directive.
The CNBOP-PIB Certification Body in Józefów issued the Certificate of Constancy of Performance 1438-CPR-0687 for the construction product TSD-1 smoke and heat detector, confirming its compliance with the requirements of EN 54-5:2000+A1:2002 and EN 54-7:2000+A1:2002+A2:2006.
The Certificate and the Declaration of Performance can be downloaded from the www.satel.pl website.
Product Identification:
- SATEL Sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdańsk • POLAND
- Certificate Number: 1438
- CPR Certificate: 1438-CPR-0687
- Declaration of Performance: DOP/CPR/0687
- Standards: EN 54-5, EN 54-7
- Product Description: TSD-1 conventional spot type multisensor heat and smoke detector, operating on light scattering principle, fixed temperature / rate-of-rise, for fire alarm systems used in buildings.
- Application: fire safety.
- Technical specifications: please refer to this manual.