Airam Sono III Luminaires: Installation and Mounting Instructions
This document provides comprehensive installation and configuration guidelines for the Airam Sono III series of luminaires, designed for recessed mounting and featuring advanced sensor technologies.
Product Overview
The Airam Sono III series offers a range of versatile luminaires with robust construction (IP54, IK10), electronic ballasts, and integrated sensor options (microwave, PIR, radar) for intelligent lighting control. These luminaires are suitable for general use and provide efficient illumination.
Available Models and Key Specifications
The following models are part of the Sono III series:
Model Code | Model Name | Lumens | Weight (kg) | GTIN | E-NR |
---|---|---|---|---|---|
4116462 | SONO III IP54 15W/835 | 1300 lm | 0.57 | 6435200216403 | 7502636 |
4116464 | SONO III 15W/835 RA 10-100 | 1300 lm | 0.57 | 6435200216427 | 7502638 |
4116465 | SONO III IP54 15W/835 RA M-S | 1300 lm | 0.57 | 6435200216434 | 7502743 |
4116463 | SONO III IP54 15W/835 PIR M-S | 1300 lm | 0.57 | 6435200216410 | 7502637 |
4126204 | SONO III 420 IP54 21W/835 | 1800 lm | 1.20 | 6435200234582 | 7503683 |
4126213 | SONO III 420 21W/835 RA M-S | 1800 lm | 1.25 | 6435200234773 | 7503684 |
General Dimensions: Standard models feature a circular luminaire body with a diameter of 295 mm and a height of 77.7 mm. The mounting plate dimensions are approximately 169 mm x 169 mm. A larger circular model is available with a diameter of 420 mm. Cable entry points require 8-10 mm clearance. The 'E' symbol indicates the earth connection point for continuity or termination of earth wires.
Connections: Standard wiring uses -o-3 x 2.5 mm² terminals, while specific models (e.g., RA) use RA -o- 4 x 2.5 mm² terminals.
Important Safety Note: Installation must be performed by a qualified electrician. Use only the rated voltage and frequency specified on the luminaire/driver. Always switch off the power supply before installation or maintenance. These instructions must be kept available for future reference. The light source is not user-replaceable; the entire fixture must be replaced if the light source fails.
General Installation Guidelines
When selecting an installation location, consider the following:
- Radar sensors can detect movement through thin walls or glass.
- The luminaire must be mounted on a stable, vibration-free surface.
- Large metal surfaces may affect the detection area's size and shape.
- Lux values provided are for reference only.
Installation Steps
- Switch off the power supply.
- Unscrew and remove the diffuser (PC-kupu).
- Mark the mounting hole locations on the ceiling or wall.
- Connect the supply wires to the terminal block according to the wiring diagram.
- Secure the luminaire to the mounting surface using screws through the base mounting holes.
- Re-attach the diffuser using the screws.
Model Specifics & Settings
Airam Sono III RA 10-100 (Microwave Sensor)
This model integrates a microwave sensor for motion detection.
Microwave Sensor Specifications
Parameter | Specification |
---|---|
HF Operating Frequency | 5.8 GHz ±75 MHz ISM wave band |
HF Radiated Power | <0.5mW max. |
Detection Range | Detection surface radius 1-7 m (at 3m installation height) |
Hold Time | 5 s, 30 s, 90 s, 6 min, 20 min |
Stand-by Period | 0 s, 10 min, 60 min, +∞ |
Detection Area | 100%, 75%, 50%, 10% |
Daylight Sensor | 10 lux, 25 lux, 50 lux, 150 lux, 2000 lux |
Mounting Height | Ceiling mounting 3-6 m, 6 m max |
Detection Angle | 150° (Wall mounting), 360° (Ceiling mounting) |
Operating Temperature/Humidity | -25 °C ~ 50 °C, 85% humidity (non-condensing) |
IP Rating | IP20 |
Wiring Diagram Description
The wiring diagram illustrates connections for AC IN (L, N), DC OUT, and sensor inputs. It shows the placement of the microwave sensor module, daylight sensor, and a work light indicator (Green LED).
Detection Patterns
Ceiling Mounting Pattern: A polar graph illustrating detection coverage in meters. The suggested installation height is 1-1.8 meters.
Wall Mounting Pattern: A polar graph illustrating detection coverage in meters. The suggested installation height is 1-7 meters.
Functionality
The sensor activates the light when motion is detected in insufficient ambient light. After the hold time expires, the light switches off if no motion is detected. If no new motion is detected after the hold time, the sensor may dim the light to a low level before switching off.
Sensor Settings (DIP Switches)
Settings are configured using DIP switches:
Detection Area (Switches 1-3)
SW1 | SW2 | SW3 | Detection Area |
---|---|---|---|
ON | ON | ON | 100% |
ON | ON | OFF | 75% |
ON | OFF | ON | 50% |
ON | OFF | OFF | 25% |
OFF | ON | ON | 10% |
Hold Time (Switches 4-6)
SW4 | SW5 | SW6 | Hold Time |
---|---|---|---|
ON | ON | ON | 5 s |
ON | ON | OFF | 30 s |
ON | OFF | ON | 90 s |
ON | OFF | OFF | 3 min |
OFF | ON | ON | 6 min |
OFF | ON | OFF | 20 min |
OFF | OFF | ON | 30 min |
Daylight Sensor (Switches 7-9)
SW7 | SW8 | SW9 | Daylight Sensor Setting |
---|---|---|---|
ON | ON | ON | 10/75 lux |
ON | ON | OFF | 25/100 lux |
ON | OFF | ON | 50/150 lux |
ON | OFF | OFF | 150/300 lux |
OFF | ON | ON | 2000 lux |
OFF | OFF | OFF | Disable |
Airam Sono III PIR/M-S (PIR Sensor)
This model features a Passive Infrared (PIR) motion sensor.
Specifications
Specification | Value |
---|---|
Power Source | 220-240V/AC, 50Hz |
Ambient Light | 3-2000 lux (adjustable) |
Time-Delay | min: 15 s ± 8 s, max: 8 min ± 2 min |
Rated Load | 1200 W (incandescent lamp), 300 W (energy-saving lamp) |
Detection Distance | 2-8 m (adjustable, at <24°C) |
Detection Range | 120° |
Working Temperature | -20 ~ 40 °C |
Working Humidity | <93%RH |
Installation Height | 2-3 m |
Power Consumption | 0.45W (work), 0.1W (static) |
Detection Motion Speed | 0.6 - 1.5 m/s |
Functionality
The PIR sensor can identify day and night by adjusting the ambient light threshold. It can operate in daylight or darkness. Sensitivity (SENS) is adjustable for different room sizes, offering a detection distance of 2m for low sensitivity and up to 8m for high sensitivity. The time-delay function accumulates; receiving a new motion signal resets the timer.
Airam Sono III RADAR M-S (Radar Sensor)
This model utilizes a microwave radar sensor for motion detection.
Microwave Sensor Specifications
Parameter | Specification |
---|---|
Power Supply | 220-240 Vac, 50 Hz |
Rated Load | 400 W (inductive), 800 W (resistive) |
HF System | 5.8 GHz ± 75 MHz, ISM band |
Transmitting Power | <0.5 mW |
Power Consumption | ≤0.5 W (standby), <1 W (operation) |
Detection Zone | Max. (D x H): 12 m x 6 m |
Detection Sensitivity | 10%, 25%, 50%, 75%, 100% |
Hold Time | 5 s, 30 s, 90 s, 3 min, 20 min, 30 min |
Daylight Sensor | 2 lux, 10 lux, 25 lux, 50 lux, Disable |
Mounting Height | Max 6 m |
Motion Detection Speed | 0.5-3 m/s |
Detection Angle | 150° (wall installation), 360° (ceiling installation) |
Temperature Range | -20°C ~ 60°C |
IP Rating | IP20 |
Wiring Scheme Description
The wiring scheme illustrates connections for power input (L, N), output control, and sensor modules. It shows how to connect multiple luminaires (maximum of 3) and details the placement of control gear.
Detection Patterns
Ceiling Mounting Pattern: A polar graph illustrating detection coverage in meters. The suggested installation height is 1-1.5 meters.
Wall Mounting Pattern: A polar graph illustrating detection coverage in meters. The suggested installation height is 2.5-6 meters.
Settings (DIP Switches)
Detection Area
Adjustable via DIP switches 1-3. Combinations determine the detection area size, allowing for precise fitting to specific applications.
SW1 | SW2 | SW3 | Detection Area |
---|---|---|---|
ON | ON | ON | 100% |
ON | ON | OFF | 75% |
ON | OFF | ON | 50% |
ON | OFF | OFF | 25% |
OFF | ON | ON | 10% |
Hold Time
Determines how long the lamp remains at 100% illumination after no motion is detected. Configured using DIP switches 4-6.
SW4 | SW5 | SW6 | Hold Time |
---|---|---|---|
ON | ON | ON | 5 s |
ON | ON | OFF | 30 s |
ON | OFF | ON | 90 s |
ON | OFF | OFF | 3 min |
OFF | ON | ON | 6 min |
OFF | ON | OFF | 20 min |
OFF | OFF | ON | 30 min |
Daylight Sensor
Allows the lamp to illuminate only when ambient brightness falls below a defined threshold. Configured using DIP switches 7-9. When set to 'Disable' mode, the sensor activates the lamp regardless of ambient light level upon detecting motion.
SW7 | SW8 | SW9 | Daylight Sensor Setting |
---|---|---|---|
ON | ON | ON | 2 lux |
ON | ON | OFF | 10 lux |
ON | OFF | ON | 25 lux |
ON | OFF | OFF | 50 lux |
OFF | OFF | OFF | Disable |
Troubleshooting
This section addresses common malfunctions and provides potential causes and remedies.
Malfunction | Cause | Remedy |
---|---|---|
The load will not work | Wrong light-control setting selected. | Adjust setting. |
The load will not work | Load faulty. | Change load. |
The load will not work | Main switch OFF. | Switch ON. |
The load works always. | Continuous movement in the detection zone. | Check zone setting. |
The load works always. | Sensor not mounted reliably. | Securely mount enclosure. |
The load works without any identifiable movement. | Movement occurred but not identified by the sensor (e.g., behind wall, small objects near lamp). | Check zone setting. |
The load will not work despite movement. | Rapid movements suppressed to minimize malfunctioning, or detection zone is too small. | Check zone setting. |