Installer's Guide
Ultra-Low NOx Series
Single Packaged Gas Heating/Electric Cooling
13.4 SEER 2 / 81% AFUE, 2 - 5 Ton Units
Models:
- 4YCL4024B1055A
- 4YCL4030B1070A
- 4YCL4036B1070A
- 4YCL4042B1100A
- 4YCL4048B1100A
- 4YCL4060B1100A
Note: Graphics in this document are for representation only. Actual model may differ in appearance. ⚠ SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
June 2024
18-EB42D1-1B-EN ⚠ WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. • Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Installation and service must be performed by a qualified installer, service agency or the gas supplier. DO NOT DESTROY THIS MANUAL. READ ALL INSTRUCTIONS IN THIS MANUAL AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE. Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage. ⚠ WARNING: ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. Improper servicing could result in dangerous operation, serious injury, death or property damage. ⚠ WARNING: These units are fully charged with R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be attempted by qualified, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation service personnel to service this type of equipment. Under no circumstances should the homeowner attempt to install and/or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death. ⚠ WARNING: Do not place combustible material on or against the unit cabinet. Do not place combustible materials, including gasoline and any other flammable vapors and liquids, in the vicinity of the unit. ⚠ WARNING: PROPOSITION 65 WARNING: This product contains fiberglass wool, a product known to the state of California to cause cancer. Disturbing the insulation of this product during installation, maintenance, or repair will expose you to fiberglass wool. ⚠ WARNING: The information listed below and on the next page must be followed during the installation, service, and operation of this unit. Unqualified individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious personal injury or death. This single package gas heating / electric cooling unit is designed only for outdoor rooftop or ground level slab installations and can be readily connected to the high static duct system of a home. This unit has been tested for capacity and efficiency in accordance with AHRI standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained. With regular maintenance, this unit will operate satisfactorily year after year. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards. To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain tools and mechanical skills. Diagram Description: Figure 1 shows clearance requirements. It illustrates a unit with minimum required clearances to combustibles marked as 36 inches on the sides and 1 inch on the top, with the top of the unit needing to be unobstructed. This unit should be sized to provide the design heating load requirement. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air Conditioning Engineers; or other approved engineering methods. For installations above 2,000 ft., the unit should have a sea level input rating large enough that it will meet the heating load after deration for altitude. ⚠ WARNING: CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed with each individual appliance connected to the venting system being placed in operation, while all other appliances connected to the venting system are not in operation: General Information ⚠ WARNING: Installation methods other than those described in the following sections must comply with the National Fuel Gas Code and all applicable local codes for providing sufficient combustion air to the unit. ⚠ WARNING: Combustible air must not be drawn from a contaminated atmosphere. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Vent Termination This unit has been equipped with an integral venting system and designed to operate only with this venting system. No additional venting shall be used. This unit must be vented to the outdoors. ⚠ WARNING: This unit is intended for outdoor installation only. Do not vent the unit through a conventional venting system. A vent cover assembly has been supplied with the unit. and can be found secured to the gas controls within the control area of this unit. The vent cover assembly must be installed to assure proper operation of the unit. Diagram Description: Figure 2 illustrates the proper installation of the vent cover assembly over the vent outlet on the exterior of the corner panel. Fasteners for the vent cover are included in the owner's package. The text lists requirements for vent system termination locations, including minimum distances from meters, inlets, windows, doors, and grade, and avoiding obstruction by snow. ⚠ WARNING: Products of combustion must not be allowed to enter the return air ductwork or the circulating air supply. Failure to prevent products of combustion from being circulated into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death. All return ductwork must be adequately sealed, all joints must be taped, and the ductwork must be secured to the unit with sheet metal screws. When return air is provided through the bottom of the unit, the joint between the unit and the return air plenum must be air tight. The roof curb or cement pad on which the unit is mounted must provide sound physical support of the unit with no gaps, cracks, or sagging between the unit and the curb or pad. Return air and circulating air ductwork must not be connected to any other heat producing device such as a fireplace insert, stove, etc. Doing so may result in fire, explosion, carbon monoxide poisoning, personal injury, or property damage. This unit is designed only for use with a supply and return duct. Air ducts should be installed in accordance with the standards of the National Fire Protection Association "Standard for Installation of Air Conditioning Systems" (NFPA 90A), "Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems" (NFPA 90B), and all applicable local codes. NFPA publications are available by writing to: National Fire Protection Association, Batterymarch Park, Quincy, ME 02269 or visit www.NFPA.org on the web. An air filter is not supplied with this package unit as shipped from the factory. The installer must provide a high velocity filter that is appropriately sized to the return air duct opening or internal filter rack. The filters must comply with ANSI/UL 900 or CAN/ULC-S111. ⚠ WARNING: Never operate the unit without a filter in place. Dust and lint could accumulate on internal parts, resulting in loss of efficiency, equipment damage and possible fire. NOTE TO INSTALLER: After installing or replacing the filtration system for this unit, add the following statement on or adjacent to the filter service panel: "Replace filter(s) installed in your system only with the same dimensional size filters that are being replaced." Unconditioned Spaces All duct work passing through unconditioned space must be properly insulated to minimize duct losses and prevent condensation. Use insulation with an outer vapor barrier. Refer to local codes for insulation material requirements. Acoustical Duct Work Certain installations may require the use of acoustical lining inside the supply duct work. Table 1. Recommended External Air Filter Sizes * Based on velocity of 300 ft/min for disposable filters. Remove the shipping carton and User's Manual from the equipment. For rooftop installations, remove and discard the two supports attached beneath the unit. ⚠ WARNING: To avoid the risk of property damage, personal injury, or death, it is the rigger's responsibility to ensure that whatever means are used to hoist the unit are safe and adequate: These units are certified as combination heating and cooling equipment for outdoor rooftop or ground level installations. Units may be installed on combustible flooring or Class A, B, or C roofing material when used with bottom supply and return air ducts as long as the following requirements are met: Rooftop installations must be located according to local building codes or ordinances and these requirements: Ground level installations must be located according to local building codes or ordinances and these requirements: the unit's weight. The slab height must be a minimum of 2" (5cm) above grade and with adequate drainage. See Figure 4 (page 10). Remove and discard the horizontal Supply and Return duct covers located on the rear of the unit. Form duct attachment flanges by bending the sheet metal outward 90 degrees along the perforated lines. Firmly attach ductwork directly to these flanges with screws or other approved mechanical connections and not to the Supply/Return air panels to avoid damage to internal components of the equipment. Once completed use approved duct sealing methods to ensure an air and watertight seal is achieved. The unit is shipped ready for horizontal duct connections. If down flow ducts are required, the unit must be converted following the steps below for both the supply and return ducts. Condensate is removed from the unit through the 3/4" female pipe fitting located on the front side of the unit. See Figure 5 (page 10). Install a 2 inch condensate trap in the drain line of the same size and prime with water. When connecting rigid drain line, hold the female fitting with a wrench to prevent twisting. Do not over tighten! Refer to local codes and restrictions for proper condensate disposal requirements. Diagram Description: Figure 3 shows a rooftop installation. Figure 4 shows a ground level installation. Figure 5 indicates the locations of refrigerant service ports and the condensate drain. ⚠ WARNING: ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. Improper servicing could result in dangerous operation, serious injury, death or property damage. IMPORTANT NOTE: If replacing any of the original wires supplied with the furnace, the replacement wire must be copper wiring having the same guage, voltage, and temperature rating. ⚠ WARNING: The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. Do not use gas piping as an electrical ground! This unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical Code. Grounding of the unit is accomplished by using the grounding lug provided in the control box. The blower speed is preset at the factory for fan only, heating, and cooling operation. These factory settings are listed in Table 6 (page 19) and Table 7 (page 20). For optimum system performance and comfort, it may be necessary to change the factory set speed. ⚠ CAUTION: To avoid personal injury or property damage, make sure the motor leads do not come into contact with any uninsulated metal components of the unit. The furnace control board provides output terminals for an optional electronic air cleaner (EAC) that can be installed in the return air duct of your system. THE EAC output is energized any time the HEAT or COOL blower speed is energized. Control ratings are 1.0 Amp. @ 240 VAC. Output connections are made via board terminals labeled EAC and NEUTRAL. Table 2. Copper Wire Size NOTE: Wire Size based on N.E.C. for 60° type copper conductors. Figure 6. Typical Thermostat Connection (Field Supplied) for 1-Stage Cool / 1-Stage Heat Diagram Description: Figure 6 shows a typical thermostat connection for a 1-stage cool/1-stage heat system, illustrating wiring terminals for R, C, Y1, G, W1, Y2, and A1, connecting to an indoor thermostat sub-base and the furnace board. ⚠ WARNING: FIRE OR EXPLOSION HAZARD This unit only has right side gas entry. When connecting the gas, provide clearance between the gas supply line and the entry hole in the unit's casing to avoid unwanted noise and/ or damage to the unit. A typical gas service hookup is shown in Figure 7. Table 8 (page 21) lists gas pipe capacities for standard pipe sizes as a function of length in typical applications based on nominal pressure drop in the line. ⚠ WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life. After the gas piping to the unit is complete, all connections must be tested for gas leaks. This includes pipe connections at the main gas valve, emergency shutoff valve and other gas connectors. A soap and water solution can be applied on each joint or union using a small paintbrush. If any bubbling is observed, the connection is not sealed adequately and must be retightened. Repeat the tightening and soap check process until bubbling ceases. For installations between zero and 5000 ft above sea level, the factory installed gas orifice should be used. High altitude conversion with this furnace depends on the installation altitude and the heating value of the gas. Installation of this furnace at altitudes above 2,000 feet shall be in accordance with local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1/NFPA 54. Please consult your local code authority. ⚠ WARNING: The reduction of input rating necessary for high altitude installation may only be accomplished with factory supplied orifices. Do not attempt to drill out orifices in the field. Improperly drilled orifices may cause fire, explosion, carbon monoxide poisoning, personal injury or death. The furnaces are shipped from the factory with orifices and gas regulator settings for natural gas operation up to 5000 ft. At 2,000 feet, the NFGC requires that this appliance be derated 4% for each 1,000 feet of altitude. For example, at 2,000 feet the input needs to be reduced 8%, at 3,000 feet (12%), etc. This deration is in reference to the input rate and gas heating value at sea level. Diagram Description: Figure 7 illustrates a typical gas hookup showing the right side entry, including a shut-off valve with a plugged tap, automatic gas valve, drip leg, and ground joint union. ⚠ WARNING: If this unit is equipped with crankcase heaters, allow 24 hrs for heating of the refrigerant compressor crankcase prior to start up or anytime the power has been removed for more than 12 hrs. Failure to comply may result in damage or cause premature failure of the system. Leave the thermostat system mode on OFF, and set the fan mode to ON. Blower should run continuously. Check the air delivery at the supply registers and adjust register openings for balanced air distribution. Examine ductwork for leaks or obstruction if insufficient air is detected. Set the thermostat fan mode to AUTO. The blower should stop running. Verify the temperature rise through the unit is within the range specified on the unit data label. Temperature rises outside the specified range could result in premature heat exchanger failure. NOTE: For typical duct systems, the temperature rise will fall within the range specified on the data label (with the blower speed at the factory recommended setting) shown in Table 6 (page 19) or Table 7 (page 20). If the measured temperature rise falls outside the specified range, it may be necessary to change the blower speed. Lowering the blower speed increases the temperature rise and a higher speed decreases the temperature rise. ⚠ CAUTION: Do not re-drill the burner orifices. If the orifice size must be changed, use only new orifices. The firing rate must be verified for each installation to prevent over-firing of the unit. The firing rate must not exceed the rate shown on the unit data label. To determine the firing rate, follow the steps below: Example: 7. Adjust the manifold pressure if necessary. See Manifold Pressure Adjustment below. For additional information about elevations above 2,000 feet, see page 12. The manifold pressure must be set to the appropriate value for your installation. To adjust the manifold pressure: NOTE: The values listed in the tables are based on sea level values. At higher altitudes, the heating value of gas is lower than the sea level heating value. NOTE: Turning the screw clockwise increases the pressure and turning the screw counter-clockwise decreases the pressure. To prevent backing the screw all the way out from the valve, turn the screw slowly. Diagram Description: Figure 8 shows the locations of the regulator capscrew and tap, including the inlet pressure tap, manifold pressure tap, and the ON/OFF switch. NOTE: The over-temperature limit control should turn off the gas valve within approximately four minutes (exact time depends on the efficiency of the close-off when blocking the return air). The circulating air and combustion blowers should continue to run when the over-temperature limit control switch opens. ⚠ CAUTION: The door over the burners may only be open for inspection purposes only. The door must be installed during unattended operation. A properly functioning limit switch should turn off the gas valve when the return is blocked (time depends on how well the return air is blocked). The circulating air and combustion blowers should continue to run when the limit switch opens. Table 3. Manifold Pressure Setting (In WC) for Natural Gas The operating sequences for the heating, cooling, and fan modes are described below. Refer to the field and unit wiring diagram. See Figure 12 (page 23) and Figure 13 (page 24). ⚠ WARNING: ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. Improper servicing could result in dangerous operation, serious injury, death or property damage. ⚠ CAUTION: Use care when removing parts from this unit. Personal injury can result from sharp metal edges present in all equipment of sheet metal construction. Proper maintenance is important to achieve optimum performance from the system. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance. Consult your local dealer about the availability of maintenance contracts. Routine maintenance should include the following: ⚠ CAUTION: The unit should never be operated without a filter in the return air system. Replace disposable filters with the same type and size. Heat Exchanger & Burner Maintenance - The furnace should operate for many years without soot buildup in the flue passageways, however, the flue and vent system should be inspected and cleaned (if required) by a qualified service technician annually to ensure continued safe operation. Pay attention to any deterioration from corrosion or other sources. Lubrication - The bearings in the blower motor and inducer blower used in these furnaces are pre-lubricated and sealed by the manufacturer. No further oiling of the bearings is required for the life of the motor. Cleaning of Flame Sensor - If the flame sensor is suspect for Loss of Flame fault code, the sensor can be cleaned to see if that remedies the issue. Follow steps 1 - 10. See Figure 14 (page 26) for component location. ⚠ CAUTION: Due to igniter/flame sensor assembly location, a new gasket should be on hand before servicing this part. One new gasket is provided in the furnace extra parts package. Failure to re-seal the assembly after service can result in abnormal furnace operation. 7. Lift the assembly and bracket straight up out of the burner box and off the HX panel. NOTE: Use of a flat blade screwdriver between assembly bracket and top of burner mounting bracket to help leverage bracket off may be required. See Figure 9. 8. Clean the flame sensor using steel wool being careful not to damage the igniter. 9. Replace old gasket with new gasket ensuring correct orientation, with adhesive side to the bracket. 10.Replace igniter/flame sense assembly in reverse order they were removed. Vent System - Check the vent pipe and/or chimney for corrosion or debris. Any corroded section of vent pipe must be replaced, and any obstruction or blockage must be removed prior to operating the furnace. ⚠ WARNING: Holes in the vent pipe or heat exchanger can cause combustion products to enter the home. Replace the vent pipe or heat exchanger if leaks are found. Failure to prevent the circulation of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death. Diagram Description: Figure 9 shows the Ignitor Flame Sensor Bracket and details the removal of screws and the access cover plate. If the unit does not operate in the cooling mode, check the following: IMPORTANT NOTE: The furnace will lock out after 5 failed attempts for ignition and will try again every hour if the call for heat remains. Table 4. Diagnostic Codes Diagram Description: Figure 10 shows the unit dimensions from top, back, and side views, including measurements for duct openings, entry points, and overall dimensions. Table 5 lists unit shipping weights and center of gravity data for various models. Table 6. Nominal Heating Airflow Rates & Temperature Rises (° F) ** Denotes factory set heating speed Tap 1 is factory set fan speed Data is ACFM Table 7. Nominal Cooling Airflow Rates & Temperature Rises (° F) * Denotes factory set cooling speed Tap 1 is factory set fan speed Data is with a dry coil Table 8. Gas Pipe Capacities Cubic Feet Per Hour Required = Input To Furnace (Btu/hr) / Heating Value of Gas (Btu/Cu. Ft.) NOTE: The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas flow required by the furnace. To determine the cubic feet per hour of gas flow required by the furnace, divide the input rate of the furnace by the heating value (from gas supplier) of the gas. Table 9. Gas Flow Rates WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or move by hand, do not try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. TO TURN OFF GAS TO APPLIANCE Diagram Description: Figure 11 shows the Gas Valve Label with a diagram of the gas valve, including the switch for ON/OFF positions. Diagram Description: Figure 12 provides the wiring diagram for a 230V / 60 Hz unit, detailing connections for the compressor, outdoor fan motor, pressure switches, limit switches, gas valve, ignitor, inducer, blower motor, and auto transformer. It also includes a legend for field wiring, low voltage, and high voltage, and a diagnostic code table with LED indicators. Diagram Description: Figure 13 provides the wiring diagram for a 230V / 60 Hz unit with an ECM Outdoor Motor, similar to Figure 12 but with specific ECM motor connections. Table 10. Electrical Data. NOTE: FLA = Full Load Amps; LRA = Lock Rotor amps; RLA = Rated Load Amps. ⚠ WARNING: These units are shipped fully charged with R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be done by qualified, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation/service personnel to service this type of equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death. ⚠ CAUTION: This unit uses R-410A refrigerant. DO NOT use any other refrigerant in this unit. Use of another refrigerant may damage the unit. The system refrigerant charge can be checked and adjusted through the service ports provided at the front panel. Use only gauge lines which have a "Schrader" depression device present to actuate the valve. Draw a vacuum on gauge lines to remove air before attaching them to the service ports on the unit. Refrigerant charging must be done by qualified personnel familiar with safe and environmentally responsible refrigerant handling procedures. This equipments cooling system contains refrigerant under high pressure, always use safe practices when servicing the unit. Always review the factory literature and safety warnings prior to servicing. These units are shipped from the factory with the proper amount and type of refrigerant. Always inspect the unit rating label to determine the units information prior to working on the system. Do not mix different refrigerants or charge the unit with a refrigerant not listed on the unit rating label. The charging tables are valid for a variety of indoor, return air conditions and are most highly influenced by the outdoor ambient temperature, outdoor fan operation and the unit operating voltage. Before referencing the charts, always make sure that the compressor circuit is energized on nominal speed (Y1 energized) and has stable operation. As can be seen in the charging charts, the ideal system sub-cooling can vary over the range of operation. Always reference the charts to determine the ideal amount of sub-cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit efficiency (EER). To inspect a systems operation, using quality instruments, match the measured liquid temperature to the units chart. The measured liquid pressure reading should be within 3% of the value shown for most installations. For systems operating with more than a 5% deviation, inspect the unit for leaks. Always use safe and environmentally sound methods for refrigerant handling. When repairing system leakages, always utilize a nitrogen (inert) gas to protect the refrigerant system and pressure check the repair before recharging. Always replace the filter-dryers when performing any repair to the refrigeration system. After completing the repairs, evacuate the system to 350-500 microns and weigh in the refrigerant to the amount specified on the unit rating label. The descriptions below are various functional components that affect the operation and shutting down of this furnace. Some of these components and their locations are shown in Figure 14. If any component of the furnace must be replaced, use only factory authorized replacement parts specified in the Replacement Parts List. Diagram Description: Figure 14 shows the locations of various furnace components including the Autotransformer, Transformer, Capacitor, Air/Fuel Mixing Tube, Combustion Air Orifice Plate, Compressor, Limit Switch, Gas Valve, Inducer Assembly, Collector Box, Terminal Strip, Furnace Control Board, Autotransformer Fuse, Contactor, Ignitor Relay, Ground Lug, Sight Glass, Gas Burner Head, Primary Air Limit Switch, Pressure Switch, and Ignitor/Flame Sensor Assembly Access. INSTALLATION ADDRESS: CITY: STATE: UNIT MODEL # UNIT SERIAL # Unit Installed Minimum clearances per Figure 1 (page 5)? YES NO INSTALLER NAME: CITY: STATE: Has the owner's information been reviewed with the customer? YES NO Has the Literature Package been left with the unit? YES NO Electrical connections tight? YES NO Line voltage polarity correct? YES NO Rated Voltage (VOLTS): L1-L2 Volts: Has the thermostat been calibrated? YES NO Is the thermostat level? YES NO Is the heat anticipator setting correct? (If Applicable) YES NO Is the vent hood installed? YES NO Is vent hood free from restrictions YES NO Filter(s) secured in place? YES NO Filter(s) clean? YES NO ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product. Safety should always be the deciding factor when installing this product and using common sense plays an important role as well. Pay attention to all safety warnings and any other special notes highlighted in the manual. Improper installation of the unit or failure to follow safety warnings could result in serious injury, death, or property damage. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Gas Type: (circle one) Natural Gas Propane Gas pipe connections leak-tested? YES NO Gas Line Pressure (in - W.C.): Is there adequate fresh air supply for combustion and ventilation? YES NO Installation Altitude (FT.): Deration Percentage: Unit Input (Btuh): Supply Air Temperature (° F): Return Air Temperature (° F): Temperature Rise (° F): Manifold pressure (in - W.C.): Was unit given 24 hr warm up period for crankcase heaters (if equipped)? YES NO Stage-1 Liquid Pressure (high side): Stage-1 Suction Pressure (low side): Replacement parts are available through your distributor. Please have the complete model and serial number of the unit when ordering replacement parts. 1043684A (Replaces 10436840) Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com. The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. Trane 6200 Troup Hwy Tyler, Texas 75707 18-EB42D1-1B-EN 21Jun 2024 Supersedes 18-EB42D1-1A-EN (Aug 2022) For more information, contact your local dealer (distributor). ©2024WHAT TO DO IF YOU SMELL GAS
IMPORTANT SAFETY INFORMATION
REQUIREMENTS & CODES
Combustion & Ventilation Air
Duct Systems
Electrical Connections
Gas Piping & Gas Pipe Pressure Testing
General Installation
Safety
GENERAL INFORMATION
Before you install this unit
Locating the Equipment
Heating Load
COMBUSTION AIR & VENTING REQUIREMENTS
CIRCULATING AIR SUPPLY
Air Ducts
NOMINAL COOLING (TONNAGE) EXTERNAL FILTER SIZES APPROXIMATE AIR FLOW RANGE (CFM) APPROXIMATE FILTER AREA (SQ. IN.)* FILTER SIZE (IN. X IN.) 2.0 20 x 25 600-900 450 2.5 20 x 30 750-1200 550 3.0 25 x 25 1100-1300 625 3.5 24 x 30 1200-1600 750 4.0 18 x 24 (2 required) 1400-1800 850 5.0 20 x 25 (2 required) 1700-2200 1000 CABINET HEIGHT OUTDOOR FAN DIAMETER INTERNAL FILTER SIZES APPROXIMATE AIR FLOW RANGE (CFM) APPROXIMATE FILTER AREA (SQ. IN.)* FILTER SIZE (IN. X IN.) 30" 20" (2) 14"x25" 700 - 1300 700 24" (1) 12"x20" and (1) 16"x25" 34" 20" (2) 16"x25" 900 - 1400 640 24" (1) 12"x20" and (2) 10"x25" 38" 20" (2) 18"x25" 1100 - 1600 800 24" (1) 12"x20" and (2) 12"x25" 42" 20" (2) 20"x25" 1300 - 1800 740 24" (1) 12"x20" and (2) 14"x25" UNIT INSTALLATION
Packaging Removal
Rigging & Hoisting
Clearances to Combustible Materials
Rooftop
Ground Level
Horizontal to Downflow Conversion
Condensate Drain
ELECTRICAL WIRING
Pre-Electrical Checklist
Grounding
Line Voltage
Thermostat / Low Voltage Connections
Checking Heat Anticipator Settings
Blower Speed
5-Speed ECM Motor
Optional Furnace Control Board Connections
Electronic Air Cleaner
SUPPLY WIRE LENGTH-FEET COPPER WIRE SIZE -- AWG (1% VOLTAGE DROP) SUPPLY CIRCUIT AMPACITY 200 150 100 50 6 8 10 14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 GAS SUPPLY & PIPING
WHAT TO DO IF YOU SMELL GAS
Leak Check
High Altitude Conversion - Natural Gas
START UP & ADJUSTMENTS
Pre-Start Check List
Start-Up Procedure
Air Circulation
System Cooling
System Heating
Verifying & Adjusting Temperature Rise
Verifying & Adjusting Firing Rate
Manifold Pressure Adjustment
Verifying Over-Temperature Limit Control Operation
Verifying Burner Operation
Verify Operation of the Supply Air Limit Switch
ALTITUDE ABOVE SEA LEVEL HEATING VALUE BTU/CU. FT ORIFICE 800 TO 899 900 TO 999 1,000 TO 1,100 ZERO TO 5,000 FT. 3.5 3.5 3.5 FACTORY INSTALLED OPERATING SEQUENCE
Heating Cycle
Cooling Cycle
Fan Mode
EQUIPMENT MAINTENANCE
TROUBLESHOOTING
DIAGNOSTIC DESCRIPTION GREEN LED RED LED Control Fault (No Power) Off Off L1/Neutral Polarity Fault Flash Flash 1 Hour Lockout Alternating Flash Normal Operation On On Pressure Switch Closed Fault On Flash Pressure Switch Open Fault Flash On Open Limit Switch Fault Flash Off DIAGNOSTIC DESCRIPTION YELLOW LED Low Flame Sensor Signal Continuous Flash Flame Present On FIGURES & TABLES
MODEL NUMBER HEATING RISE RANGE MOTOR TAP EXTERNAL STATIC PRESSURE DROP - INCHES WATER COLUMN 0.1 (ACFM) (F) RISE 0.2 (ACFM) (F) RISE 0.3 (ACFM) (F) RISE 0.4 (ACFM) (F) RISE 0.5 (ACFM) (F) RISE 0.6 (ACFM) (F) RISE 0.7 (ACFM) (F) RISE 0.8 (ACFM) (F) RISE 4YCL4024B1055A 35-65 Tap T1** 996 41 898 46 800 52 750 55 726 57 632 65 552 75 470 88 Tap T2 Tap T3 Tap T4 Tap T5 4YCL4030B1070A 35-65 Tap T1 1243 42 1158 45 1076 49 984 53 906 58 845 62 782 67 762 69 Tap T2** 1393 38 1310 40 1255 42 1172 45 1099 48 1021 51 955 55 899 58 4YCL4036B1070A 35-65 Tap T3 Tap T4 Tap T5 4YCL4042B1100A 35-65 Tap T1 1098 68 1020 74 954 79 886 85 814 92 765 98 691 109 620 121 Tap T2 1453 52 1384 54 1326 57 1267 59 1204 62 1137 66 1095 68 1031 73 Tap T3** 1663 45 1605 47 1541 49 1489 50 1425 53 1366 55 1321 57 1260 60 Tap T4 Tap T5 4YCL4048B1100A 35-65 Tap T1 1153 65 1071 70 1002 75 930 81 855 88 803 93 726 103 651 115 Tap T2** 1684 45 1597 47 1529 49 1467 51 1397 54 1323 57 1245 60 1171 64 Tap T3 Tap T4 Tap T5 4YCL4060B1100A 35-65 Tap T1 1589 47 1498 50 1391 54 1271 59 1165 64 1063 71 995 75 899 83 Tap T2** 1803 42 1710 44 1621 46 1513 50 1416 53 1320 57 1241 60 1146 65 Tap T3 Tap T4 Tap T5 MODEL NUMBER MOTOR TAP EXTERNAL STATIC PRESSURE DROP - INCHES WATER COLUMN 0.1 SCFM 0.2 SCFM 0.3 SCFM 0.4 SCFM 0.5 SCFM 0.6 SCFM 0.7 SCFM 0.8 SCFM 4YCL4024B1055A Tap T1 810 730 650 610 590 514 449 382 Tap T2 970 895 819 747 680 611 554 488 Tap T3 1112 1050 987 903 837 776 707 641 Tap T4* 1160 1105 1053 991 908 840 797 720 Tap T5 1472 1411 1350 1295 1228 1164 1097 1051 4YCL4030B1070A Tap T1 1036 965 897 820 755 704 652 635 Tap T2 1161 1092 1046 977 916 851 796 749 Tap T3 1294 1231 1178 1127 1066 1005 936 887 Tap T4* 1333 1268 1213 1161 1098 1035 964 913 Tap T5 1920 1872 1836 1785 1728 1699 1645 1592 4YCL4036B1070A Tap T1 1036 965 897 820 755 704 652 635 Tap T2 1161 1092 1046 977 916 851 796 749 Tap T3 1333 1268 1213 1161 1098 1035 964 913 Tap T4* 1439 1392 1340 1295 1250 1200 1145 1090 Tap T5 1920 1872 1836 1785 1728 1699 1645 1592 4YCL4042B1100A Tap T1 1098 1020 954 886 814 765 691 620 Tap T2 1450 1380 1326 1267 1204 1137 1095 1031 Tap T3* 1527 1469 1418 1357 1289 1243 1190 1132 Tap T4 1950 1884 1842 1790 1743 1687 1637 1571 Tap T5 2031 1992 1921 1871 1820 1770 1711 1650 4YCL4048B1100A Tap T1 1098 1020 954 886 814 765 691 620 Tap T2 1604 1521 1456 1397 1330 1260 1186 1115 Tap T3 1663 1605 1541 1489 1425 1366 1231 1260 Tap T4* 1871 1806 1747 1693 1631 1575 1509 1449 Tap T5 2031 1992 1921 1871 1820 1770 1711 1650 4YCL4060B1100A Tap T1 1292 1218 1131 1033 947 864 809 731 Tap T2 1466 1390 1318 1230 1151 1073 1009 932 Tap T3 1774 1719 1661 1599 1529 1448 1384 1306 Tap T4* 2024 1973 1919 1857 1798 1731 1668 1600 Tap T5 2144 2087 2028 1962 1911 1849 1785 1718 Gas Information
NOMINAL PIPE DIAMETER (IN.) CAPACITY OF BLACK IRON GAS PIPE (CU. FT. PER HOUR) FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60) 10 20 30 40 50 60 70 80 1/2 130 90 75 65 55 50 45 40 3/4 280 190 150 130 115 105 95 90 1 520 350 285 245 215 195 180 170 1 1/4 1,050 730 590 500 440 400 370 350 1 1/2 1,600 1,100 890 760 670 610 TIME FOR ONE REVOLUTION (SECONDS) CUBIC FEET PER REVOLUTION OF GAS METER CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 1 5 10 10 360 1,800 3,600 66 55 273 545 12 300 1,500 3,000 68 53 265 529 14 257 1,286 2,571 70 51 257 514 16 225 1,125 2,250 72 50 250 500 18 200 1,000 2,000 74 49 243 486 20 180 900 1,800 76 47 237 474 22 164 818 1,636 78 46 231 462 24 150 750 1,500 80 45 225 450 26 138 692 1,385 82 44 220 439 28 129 643 1,286 84 43 214 429 30 120 600 1,200 86 42 209 419 32 113 563 1,125 88 41 205 409 34 106 529 1,059 90 40 200 400 36 100 500 1,000 92 39 196 391 38 95 474 947 94 38 191 383 40 90 450 900 96 38 188 375 42 86 429 857 98 37 184 367 44 82 409 818 100 36 180 360 46 78 391 783 102 35 176 353 48 75 375 750 104 35 173 346 50 72 360 720 106 34 170 340 52 69 346 692 108 33 167 333 54 67 333 667 110 33 164 327 56 64 321 643 112 32 161 321 58 62 310 621 114 32 158 316 60 60 300 600 116 31 155 310 62 58 290 581 118 31 153 305 64 56 281 563 120 30 150 300 FOR YOUR SAFETY READ BEFORE OPERATING
WHAT TO DO IF YOU SMELL GAS
OPERATING INSTRUCTIONS
Wiring Diagram & Electrical Data
MODEL NUMBER HEATING INPUT (BTUH) NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER AMPS INDUCER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAXIMUM OVER-CURRENT PROTECTION MIN. MAX. RLA LRA 024K 55,000 230-60-1 196 253 12.8 58.3 1.0 3.8 0.7 20.8 30 030K 70,000 230-60-1 196 253 14.1 73 1.46 5.4 0.7 24.5 35 036K 70,000 230-60-1 196 253 16.7 79 1.46 5.4 0.7 27.7 40 042K 100,000 230-60-1 196 253 19.8 110 3.8 5.4 0.7 34.0 50 048K 100,000 230-60-1 196 253 21.8 117 1.46 5.4 0.7 34.1 50 X60K 100,000 230-60-1 196 253 26.3 134 1.46 7.0 0.7 41.3 60 REFRIGERANT CHARGING
Application Notes & Charging Charts (Cooling Mode Only)
FURNACE COMPONENTS
INSTALLATION CHECKLIST
ELECTRICAL SYSTEM
VENTING SYSTEM
GAS SYSTEM
DURING UNIT OPERATION:
REFRIGERATION SYSTEM
REPLACEMENT PARTS
ELECTRICAL:
MOTORS:
COMPONENTS:
About Trane and American Standard Heating and Air Conditioning