Installer's Guide

Ultra-Low NOx Series

Single Packaged Gas Heating/Electric Cooling

13.4 SEER 2 / 81% AFUE, 2 - 5 Ton Units

Models:

Note: Graphics in this document are for representation only. Actual model may differ in appearance.

⚠ SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

June 2024

18-EB42D1-1B-EN

⚠ WARNING:

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Installation and service must be performed by a qualified installer, service agency or the gas supplier.

DO NOT DESTROY THIS MANUAL. READ ALL INSTRUCTIONS IN THIS MANUAL AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

IMPORTANT SAFETY INFORMATION

Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.

⚠ WARNING:

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

Improper servicing could result in dangerous operation, serious injury, death or property damage.

⚠ WARNING:

These units are fully charged with R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be attempted by qualified, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation service personnel to service this type of equipment. Under no circumstances should the homeowner attempt to install and/or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death.

⚠ WARNING:

Do not place combustible material on or against the unit cabinet. Do not place combustible materials, including gasoline and any other flammable vapors and liquids, in the vicinity of the unit.

⚠ WARNING:

PROPOSITION 65 WARNING: This product contains fiberglass wool, a product known to the state of California to cause cancer. Disturbing the insulation of this product during installation, maintenance, or repair will expose you to fiberglass wool.

⚠ WARNING:

The information listed below and on the next page must be followed during the installation, service, and operation of this unit. Unqualified individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious personal injury or death.

REQUIREMENTS & CODES

Combustion & Ventilation Air

Duct Systems

Electrical Connections

Gas Piping & Gas Pipe Pressure Testing

General Installation

Safety

GENERAL INFORMATION

This single package gas heating / electric cooling unit is designed only for outdoor rooftop or ground level slab installations and can be readily connected to the high static duct system of a home. This unit has been tested for capacity and efficiency in accordance with AHRI standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained. With regular maintenance, this unit will operate satisfactorily year after year. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.

To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain tools and mechanical skills.

Before you install this unit

Locating the Equipment

Diagram Description: Figure 1 shows clearance requirements. It illustrates a unit with minimum required clearances to combustibles marked as 36 inches on the sides and 1 inch on the top, with the top of the unit needing to be unobstructed.

Heating Load

This unit should be sized to provide the design heating load requirement. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air Conditioning Engineers; or other approved engineering methods. For installations above 2,000 ft., the unit should have a sea level input rating large enough that it will meet the heating load after deration for altitude.

COMBUSTION AIR & VENTING REQUIREMENTS

⚠ WARNING:

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed with each individual appliance connected to the venting system being placed in operation, while all other appliances connected to the venting system are not in operation:

  1. Seal any unused openings in the venting system.
  2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
  3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
  4. Close fireplace dampers.
  5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
  6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
  7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
  8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
  9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.

General Information

⚠ WARNING:

Installation methods other than those described in the following sections must comply with the National Fuel Gas Code and all applicable local codes for providing sufficient combustion air to the unit.

⚠ WARNING:

Combustible air must not be drawn from a contaminated atmosphere. Excessive exposure to contaminated combustion air will result in safety and performance related problems.

Vent Termination

This unit has been equipped with an integral venting system and designed to operate only with this venting system. No additional venting shall be used. This unit must be vented to the outdoors.

⚠ WARNING:

This unit is intended for outdoor installation only. Do not vent the unit through a conventional venting system.

A vent cover assembly has been supplied with the unit. and can be found secured to the gas controls within the control area of this unit. The vent cover assembly must be installed to assure proper operation of the unit.

Diagram Description: Figure 2 illustrates the proper installation of the vent cover assembly over the vent outlet on the exterior of the corner panel. Fasteners for the vent cover are included in the owner's package. The text lists requirements for vent system termination locations, including minimum distances from meters, inlets, windows, doors, and grade, and avoiding obstruction by snow.

CIRCULATING AIR SUPPLY

⚠ WARNING:

Products of combustion must not be allowed to enter the return air ductwork or the circulating air supply. Failure to prevent products of combustion from being circulated into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.

All return ductwork must be adequately sealed, all joints must be taped, and the ductwork must be secured to the unit with sheet metal screws. When return air is provided through the bottom of the unit, the joint between the unit and the return air plenum must be air tight.

The roof curb or cement pad on which the unit is mounted must provide sound physical support of the unit with no gaps, cracks, or sagging between the unit and the curb or pad.

Return air and circulating air ductwork must not be connected to any other heat producing device such as a fireplace insert, stove, etc. Doing so may result in fire, explosion, carbon monoxide poisoning, personal injury, or property damage.

Air Ducts

This unit is designed only for use with a supply and return duct. Air ducts should be installed in accordance with the standards of the National Fire Protection Association "Standard for Installation of Air Conditioning Systems" (NFPA 90A), "Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems" (NFPA 90B), and all applicable local codes. NFPA publications are available by writing to: National Fire Protection Association, Batterymarch Park, Quincy, ME 02269 or visit www.NFPA.org on the web.

An air filter is not supplied with this package unit as shipped from the factory. The installer must provide a high velocity filter that is appropriately sized to the return air duct opening or internal filter rack. The filters must comply with ANSI/UL 900 or CAN/ULC-S111.

⚠ WARNING:

Never operate the unit without a filter in place. Dust and lint could accumulate on internal parts, resulting in loss of efficiency, equipment damage and possible fire.

NOTE TO INSTALLER: After installing or replacing the filtration system for this unit, add the following statement on or adjacent to the filter service panel: "Replace filter(s) installed in your system only with the same dimensional size filters that are being replaced."

Unconditioned Spaces

All duct work passing through unconditioned space must be properly insulated to minimize duct losses and prevent condensation. Use insulation with an outer vapor barrier. Refer to local codes for insulation material requirements.

Acoustical Duct Work

Certain installations may require the use of acoustical lining inside the supply duct work.

Table 1. Recommended External Air Filter Sizes

NOMINAL COOLING (TONNAGE)EXTERNAL FILTER SIZESAPPROXIMATE AIR FLOW RANGE (CFM)APPROXIMATE FILTER AREA (SQ. IN.)*
FILTER SIZE (IN. X IN.)
2.020 x 25600-900450
2.520 x 30750-1200550
3.025 x 251100-1300625
3.524 x 301200-1600750
4.018 x 24 (2 required)1400-1800850
5.020 x 25 (2 required)1700-22001000
CABINET HEIGHTOUTDOOR FAN DIAMETERINTERNAL FILTER SIZESAPPROXIMATE AIR FLOW RANGE (CFM)APPROXIMATE FILTER AREA (SQ. IN.)*
FILTER SIZE (IN. X IN.)
30"20"(2) 14"x25"700 - 1300700
24"(1) 12"x20" and (1) 16"x25"
34"20"(2) 16"x25"900 - 1400640
24"(1) 12"x20" and (2) 10"x25"
38"20"(2) 18"x25"1100 - 1600800
24"(1) 12"x20" and (2) 12"x25"
42"20"(2) 20"x25"1300 - 1800740
24"(1) 12"x20" and (2) 14"x25"

* Based on velocity of 300 ft/min for disposable filters.

UNIT INSTALLATION

Packaging Removal

Remove the shipping carton and User's Manual from the equipment. For rooftop installations, remove and discard the two supports attached beneath the unit.

Rigging & Hoisting

⚠ WARNING:

To avoid the risk of property damage, personal injury, or death, it is the rigger's responsibility to ensure that whatever means are used to hoist the unit are safe and adequate:

Clearances to Combustible Materials

These units are certified as combination heating and cooling equipment for outdoor rooftop or ground level installations. Units may be installed on combustible flooring or Class A, B, or C roofing material when used with bottom supply and return air ducts as long as the following requirements are met:

Rooftop

Rooftop installations must be located according to local building codes or ordinances and these requirements:

Ground Level

Ground level installations must be located according to local building codes or ordinances and these requirements:

the unit's weight. The slab height must be a minimum of 2" (5cm) above grade and with adequate drainage. See Figure 4 (page 10).

Remove and discard the horizontal Supply and Return duct covers located on the rear of the unit. Form duct attachment flanges by bending the sheet metal outward 90 degrees along the perforated lines.

Firmly attach ductwork directly to these flanges with screws or other approved mechanical connections and not to the Supply/Return air panels to avoid damage to internal components of the equipment. Once completed use approved duct sealing methods to ensure an air and watertight seal is achieved.

Horizontal to Downflow Conversion

The unit is shipped ready for horizontal duct connections. If down flow ducts are required, the unit must be converted following the steps below for both the supply and return ducts.

  1. Remove the horizontal duct cap.
  2. Locate the duct cap inside the duct openings and remove the screw holding it in place.
  3. Lift the cap out of the unit. (Hint: The cap can be pushed up from the bottom by reaching through the fork slot).
  4. Cover the horizontal duct opening with the horizontal duct cap. The insulation will be on the indoor side.
  5. Fasten the cover with screws to seal.
  6. Remove and discard the two wood supports beneath the unit.

Condensate Drain

Condensate is removed from the unit through the 3/4" female pipe fitting located on the front side of the unit. See Figure 5 (page 10).

Install a 2 inch condensate trap in the drain line of the same size and prime with water. When connecting rigid drain line, hold the female fitting with a wrench to prevent twisting. Do not over tighten! Refer to local codes and restrictions for proper condensate disposal requirements.

Diagram Description: Figure 3 shows a rooftop installation. Figure 4 shows a ground level installation. Figure 5 indicates the locations of refrigerant service ports and the condensate drain.

ELECTRICAL WIRING

⚠ WARNING:

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

Improper servicing could result in dangerous operation, serious injury, death or property damage.

IMPORTANT NOTE:

If replacing any of the original wires supplied with the furnace, the replacement wire must be copper wiring having the same guage, voltage, and temperature rating.

Pre-Electrical Checklist

Grounding

⚠ WARNING:

The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. Do not use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical Code. Grounding of the unit is accomplished by using the grounding lug provided in the control box.

Line Voltage

Thermostat / Low Voltage Connections

Checking Heat Anticipator Settings

Blower Speed

The blower speed is preset at the factory for fan only, heating, and cooling operation. These factory settings are listed in Table 6 (page 19) and Table 7 (page 20). For optimum system performance and comfort, it may be necessary to change the factory set speed.

⚠ CAUTION:

To avoid personal injury or property damage, make sure the motor leads do not come into contact with any uninsulated metal components of the unit.

5-Speed ECM Motor

Optional Furnace Control Board Connections

Electronic Air Cleaner

The furnace control board provides output terminals for an optional electronic air cleaner (EAC) that can be installed in the return air duct of your system. THE EAC output is energized any time the HEAT or COOL blower speed is energized. Control ratings are 1.0 Amp. @ 240 VAC. Output connections are made via board terminals labeled EAC and NEUTRAL.

Table 2. Copper Wire Size

SUPPLY WIRE LENGTH-FEETCOPPER WIRE SIZE -- AWG (1% VOLTAGE DROP)SUPPLY CIRCUIT AMPACITY
20015010050
68101415
4681220
4681025
4461030
346835
346840
234645
234650
234655
123460

NOTE: Wire Size based on N.E.C. for 60° type copper conductors.

Figure 6. Typical Thermostat Connection (Field Supplied) for 1-Stage Cool / 1-Stage Heat

Diagram Description: Figure 6 shows a typical thermostat connection for a 1-stage cool/1-stage heat system, illustrating wiring terminals for R, C, Y1, G, W1, Y2, and A1, connecting to an indoor thermostat sub-base and the furnace board.

GAS SUPPLY & PIPING

⚠ WARNING:

FIRE OR EXPLOSION HAZARD

WHAT TO DO IF YOU SMELL GAS

This unit only has right side gas entry. When connecting the gas, provide clearance between the gas supply line and the entry hole in the unit's casing to avoid unwanted noise and/ or damage to the unit. A typical gas service hookup is shown in Figure 7.

Table 8 (page 21) lists gas pipe capacities for standard pipe sizes as a function of length in typical applications based on nominal pressure drop in the line.

Leak Check

⚠ WARNING:

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.

After the gas piping to the unit is complete, all connections must be tested for gas leaks. This includes pipe connections at the main gas valve, emergency shutoff valve and other gas connectors. A soap and water solution can be applied on each joint or union using a small paintbrush. If any bubbling is observed, the connection is not sealed adequately and must be retightened. Repeat the tightening and soap check process until bubbling ceases.

High Altitude Conversion - Natural Gas

For installations between zero and 5000 ft above sea level, the factory installed gas orifice should be used. High altitude conversion with this furnace depends on the installation altitude and the heating value of the gas. Installation of this furnace at altitudes above 2,000 feet shall be in accordance with local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1/NFPA 54. Please consult your local code authority.

⚠ WARNING:

The reduction of input rating necessary for high altitude installation may only be accomplished with factory supplied orifices. Do not attempt to drill out orifices in the field. Improperly drilled orifices may cause fire, explosion, carbon monoxide poisoning, personal injury or death.

The furnaces are shipped from the factory with orifices and gas regulator settings for natural gas operation up to 5000 ft. At 2,000 feet, the NFGC requires that this appliance be derated 4% for each 1,000 feet of altitude. For example, at 2,000 feet the input needs to be reduced 8%, at 3,000 feet (12%), etc. This deration is in reference to the input rate and gas heating value at sea level.

Diagram Description: Figure 7 illustrates a typical gas hookup showing the right side entry, including a shut-off valve with a plugged tap, automatic gas valve, drip leg, and ground joint union.

START UP & ADJUSTMENTS

Pre-Start Check List

Start-Up Procedure

⚠ WARNING:

If this unit is equipped with crankcase heaters, allow 24 hrs for heating of the refrigerant compressor crankcase prior to start up or anytime the power has been removed for more than 12 hrs. Failure to comply may result in damage or cause premature failure of the system.

Air Circulation

Leave the thermostat system mode on OFF, and set the fan mode to ON. Blower should run continuously. Check the air delivery at the supply registers and adjust register openings for balanced air distribution. Examine ductwork for leaks or obstruction if insufficient air is detected. Set the thermostat fan mode to AUTO. The blower should stop running.

System Cooling

  1. Set the thermostat's system mode to COOL and the fan mode to AUTO. Gradually lower the thermostat temperature setpoint below room temperature and verify the compressor, fan and indoor blower energize.
  2. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
  3. Allow the cooling system to operate for several minutes and then set the temperature selector above room temperature. Verify the fan and compressor cycle off with the thermostat. NOTE: The blower will also stop after a 60 second delay.

System Heating

  1. Set the thermostat to the lowest setting.
  2. Follow the procedures given on the operating instruction label, this manual or attached inside the louvered control access panel.
  3. Set the thermostat above room temperature and verify the Operating Sequence. See page 16.
  4. Verify that the compressor and outdoor fan motor are not energized.
  5. After the unit has run for approximately five minutes, set the thermostat below room temperature and verify the shutdown sequence; steps 10, 11, & 12 in the Operating Sequence section on page 16.

Verifying & Adjusting Temperature Rise

Verify the temperature rise through the unit is within the range specified on the unit data label. Temperature rises outside the specified range could result in premature heat exchanger failure.

  1. Place thermometers in the return and supply air stream as close to the unit as possible. The thermometer on the supply air side must be shielded against direct radiation from the heat exchanger to avoid false readings.
  2. Adjust all registers and duct dampers to the desired position. Run the unit for 10 to 15 minutes before taking any temperature readings. The temperature rise is the difference between the supply and return air temperatures.

NOTE: For typical duct systems, the temperature rise will fall within the range specified on the data label (with the blower speed at the factory recommended setting) shown in Table 6 (page 19) or Table 7 (page 20). If the measured temperature rise falls outside the specified range, it may be necessary to change the blower speed. Lowering the blower speed increases the temperature rise and a higher speed decreases the temperature rise.

Verifying & Adjusting Firing Rate

⚠ CAUTION:

Do not re-drill the burner orifices. If the orifice size must be changed, use only new orifices.

The firing rate must be verified for each installation to prevent over-firing of the unit. The firing rate must not exceed the rate shown on the unit data label. To determine the firing rate, follow the steps below:

  1. Obtain the gas heating value (HHV) from the gas supplier.
  2. Shut off all other gas fired appliances.
  3. Start the unit in heating mode and allow it to run for at least 3 minutes.
  4. Measure the time (in seconds) required for the gas meter to complete one revolution.
  5. Convert the time per revolution to cubic feet of gas per hour using Table 9 (page 21).
  6. Multiply the gas flow rate in cubic feet per hour by the heating value of the gas in Btu per cubic foot to obtain the firing rate in Btu per hour. See Example.

Example:

7. Adjust the manifold pressure if necessary. See Manifold Pressure Adjustment below. For additional information about elevations above 2,000 feet, see page 12.

Manifold Pressure Adjustment

The manifold pressure must be set to the appropriate value for your installation. To adjust the manifold pressure:

  1. Obtain the required manifold pressure setting

NOTE: The values listed in the tables are based on sea level values. At higher altitudes, the heating value of gas is lower than the sea level heating value.

  1. Remove the regulator capscrew (Figure 8) from the INLET side of the regulator.
  2. Slowly turn the adjustment screw inside the regulator to obtain the appropriate manifold pressure.

NOTE: Turning the screw clockwise increases the pressure and turning the screw counter-clockwise decreases the pressure. To prevent backing the screw all the way out from the valve, turn the screw slowly.

  1. Replace and tighten the regulator capscrew over the adjustment screw.

Diagram Description: Figure 8 shows the locations of the regulator capscrew and tap, including the inlet pressure tap, manifold pressure tap, and the ON/OFF switch.

Verifying Over-Temperature Limit Control Operation

  1. Verify the louvered control access panel is in place and that there is power to the unit.
  2. Block the return airflow to the unit by installing a close-off plate in place of or upstream of the filter.
  3. Set the thermostat above room temperature and verify the units operating sequence on page 16.

NOTE: The over-temperature limit control should turn off the gas valve within approximately four minutes (exact time depends on the efficiency of the close-off when blocking the return air). The circulating air and combustion blowers should continue to run when the over-temperature limit control switch opens.

  1. Remove the close-off plate immediately after the over-temperature limit control opens. If the unit operates for more than four minutes with no return air, set the thermostat below room temperature, shut off power to the unit, and replace the over-temperature limit control.

Verifying Burner Operation

⚠ CAUTION:

The door over the burners may only be open for inspection purposes only. The door must be installed during unattended operation.

  1. Remove the burner compartment door and note the location of the sightglass on burner head.
  2. Set the thermostat above room temperature and observe the ignition sequence. NOTE: The burner flame should be present by seeing a glow through the sightglass.
  1. After validating the flame, change the thermostat setting to below room temperature.
  2. Verify the burner flame is completely extinguished.
  3. Replace the burner compartment door.

Verify Operation of the Supply Air Limit Switch

A properly functioning limit switch should turn off the gas valve when the return is blocked (time depends on how well the return air is blocked). The circulating air and combustion blowers should continue to run when the limit switch opens.

  1. Verify the blower door is securely mounted in place and that there is power to the furnace.
  2. Block the return airflow to the furnace by installing a close-off plate in place of or upstream of the filter(s).
  3. Set the thermostat above room temperature and observe the Operating Sequence.
  4. Remove the close-off immediately after the limit switch opens. If the furnace continues to operate with no return air, set the thermostat below room temperature, shut off power to the furnace, and replace the limit switch.

Table 3. Manifold Pressure Setting (In WC) for Natural Gas

ALTITUDE ABOVE SEA LEVELHEATING VALUE BTU/CU. FTORIFICE
800 TO 899900 TO 9991,000 TO 1,100
ZERO TO 5,000 FT.3.53.53.5FACTORY INSTALLED

OPERATING SEQUENCE

The operating sequences for the heating, cooling, and fan modes are described below. Refer to the field and unit wiring diagram. See Figure 12 (page 23) and Figure 13 (page 24).

Heating Cycle

  1. The thermostat calls for heat by energizing the W terminal with 24VAC.
  2. The control verifies the safety circuit pressure switch is open and high temperature limit switch circuit is closed.
  3. If the pressure switch is open, the control energizes the inducer and waits for the pressure switch to close. The pressure switch must close within 10 seconds.
  4. The control runs the inducer for a 30 second pre-purge.
  5. The control energizes the igniter output for a 30 second warm-up period.
  6. The control energizes the main gas valve for 3 seconds.
  7. If the flame is proved after igniting the gas, the control de-energizes the igniter. The gas valve and inducer remain energized. The control goes to blower on delay.
  8. If flame is present, the control energizes the blower on the selected HEAT speed 30 seconds after the gas valve opened. The gas valve remains energized while the inducer ramps to Max. RPM over a programmed time period.
  9. When the thermostat demand for heat is satisfied, the control de-energizes the gas valve. The inducer output remains on for a 90 second post-purge period.
  10. Blower off timing of 60, 90, 120, & 180 seconds (depending on the movable jumper setting) begins when the thermostat is satisfied. See Figure 14 (page 16). The control will operate at the selected HEAT speed of 60 seconds, then change to FAN speed for the remaining off delay time. If the blower off delay jumper is not present, the fan should still operate for 120 seconds at the selected HEAT speed. The indoor blower motor is de-energized after a blower off delay as selected by the movable jumper.

Cooling Cycle

  1. The thermostat calls for cooling by energizing the Y & G terminal with 24VAC.
  2. The control energizes the blower in the cooling speed and sends 24VAC to the contactor in the condensing section.
  3. When the thermostat removes the call for cooling, the contactor in the outdoor condensing section is de-energized and the control continues to run the fan for a period of 60 seconds.

Fan Mode

EQUIPMENT MAINTENANCE

⚠ WARNING:

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

Improper servicing could result in dangerous operation, serious injury, death or property damage.

⚠ CAUTION:

Use care when removing parts from this unit. Personal injury can result from sharp metal edges present in all equipment of sheet metal construction.

Proper maintenance is important to achieve optimum performance from the system. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance. Consult your local dealer about the availability of maintenance contracts. Routine maintenance should include the following:

⚠ CAUTION:

The unit should never be operated without a filter in the return air system. Replace disposable filters with the same type and size.

Heat Exchanger & Burner Maintenance - The furnace should operate for many years without soot buildup in the flue passageways, however, the flue and vent system should be inspected and cleaned (if required) by a qualified service technician annually to ensure continued safe operation. Pay attention to any deterioration from corrosion or other sources.

Lubrication - The bearings in the blower motor and inducer blower used in these furnaces are pre-lubricated and sealed by the manufacturer. No further oiling of the bearings is required for the life of the motor.

Cleaning of Flame Sensor - If the flame sensor is suspect for Loss of Flame fault code, the sensor can be cleaned to see if that remedies the issue. Follow steps 1 - 10. See Figure 14 (page 26) for component location.

⚠ CAUTION:

Due to igniter/flame sensor assembly location, a new gasket should be on hand before servicing this part. One new gasket is provided in the furnace extra parts package. Failure to re-seal the assembly after service can result in abnormal furnace operation.

  1. Shut off gas supply to the furnace at the meter or at a manual valve in the supply piping.
  2. Turn off all power to the furnace and set the thermostat to its lowest setting.
  3. Remove the louvered door from the unit.
  4. Turn the gas control switch to the OFF position.
  5. Remove the 2 screws securing the combustion air orifice plate to the air/fuel mixing tube (if needed to access the ignitor/flame sensor assembly cover on smaller models).
  6. Remove 8 screws from perimeter of access cover plate.

7. Lift the assembly and bracket straight up out of the burner box and off the HX panel. NOTE: Use of a flat blade screwdriver between assembly bracket and top of burner mounting bracket to help leverage bracket off may be required. See Figure 9.

8. Clean the flame sensor using steel wool being careful not to damage the igniter.

9. Replace old gasket with new gasket ensuring correct orientation, with adhesive side to the bracket.

10.Replace igniter/flame sense assembly in reverse order they were removed.

Vent System - Check the vent pipe and/or chimney for corrosion or debris. Any corroded section of vent pipe must be replaced, and any obstruction or blockage must be removed prior to operating the furnace.

⚠ WARNING:

Holes in the vent pipe or heat exchanger can cause combustion products to enter the home. Replace the vent pipe or heat exchanger if leaks are found. Failure to prevent the circulation of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.

Diagram Description: Figure 9 shows the Ignitor Flame Sensor Bracket and details the removal of screws and the access cover plate.

TROUBLESHOOTING

If the unit does not operate in the cooling mode, check the following:

IMPORTANT NOTE: The furnace will lock out after 5 failed attempts for ignition and will try again every hour if the call for heat remains.

Table 4. Diagnostic Codes

DIAGNOSTIC DESCRIPTIONGREEN LEDRED LED
Control Fault (No Power)OffOff
L1/Neutral Polarity FaultFlashFlash
1 Hour LockoutAlternating Flash
Normal OperationOnOn
Pressure Switch Closed FaultOnFlash
Pressure Switch Open FaultFlashOn
Open Limit Switch FaultFlashOff
DIAGNOSTIC DESCRIPTIONYELLOW LED
Low Flame Sensor SignalContinuous Flash
Flame PresentOn

FIGURES & TABLES

Diagram Description: Figure 10 shows the unit dimensions from top, back, and side views, including measurements for duct openings, entry points, and overall dimensions. Table 5 lists unit shipping weights and center of gravity data for various models.

Table 6. Nominal Heating Airflow Rates & Temperature Rises (° F)

MODEL NUMBERHEATING RISE RANGEMOTOR TAPEXTERNAL STATIC PRESSURE DROP - INCHES WATER COLUMN
0.1 (ACFM)(F) RISE0.2 (ACFM)(F) RISE0.3 (ACFM)(F) RISE0.4 (ACFM)(F) RISE0.5 (ACFM)(F) RISE0.6 (ACFM)(F) RISE0.7 (ACFM)(F) RISE0.8 (ACFM)(F) RISE
4YCL4024B1055A35-65Tap T1**9964189846800527505572657632655527547088
Tap T2
Tap T3
Tap T4
Tap T5
4YCL4030B1070A35-65Tap T11243421158451076499845390658845627826776269
Tap T2**1393381310401255421172451099481021519555589958
4YCL4036B1070A35-65Tap T3
Tap T4
Tap T5
4YCL4042B1100A35-65Tap T110986810207495479886858149276598691109620121
Tap T2145352138454132657126759120462113766109568103173
Tap T3**166345160547154149148950142553136655132157126060
Tap T4
Tap T5
4YCL4048B1100A35-65Tap T1115365107170100275930818558880393726103651115
Tap T2**168445159747152949146751139754132357124560117164
Tap T3
Tap T4
Tap T5
4YCL4060B1100A35-65Tap T11589471498501391541271591165641063719957589983
Tap T2**180342171044162146151350141653132057124160114665
Tap T3
Tap T4
Tap T5

** Denotes factory set heating speed

Tap 1 is factory set fan speed

Data is ACFM

Table 7. Nominal Cooling Airflow Rates & Temperature Rises (° F)

MODEL NUMBERMOTOR TAPEXTERNAL STATIC PRESSURE DROP - INCHES WATER COLUMN
0.1 SCFM0.2 SCFM0.3 SCFM0.4 SCFM0.5 SCFM0.6 SCFM0.7 SCFM0.8 SCFM
4YCL4024B1055ATap T1810730650610590514449382
Tap T2970895819747680611554488
Tap T311121050987903837776707641
Tap T4*116011051053991908840797720
Tap T514721411135012951228116410971051
4YCL4030B1070ATap T11036965897820755704652635
Tap T2116110921046977916851796749
Tap T3129412311178112710661005936887
Tap T4*133312681213116110981035964913
Tap T519201872183617851728169916451592
4YCL4036B1070ATap T11036965897820755704652635
Tap T2116110921046977916851796749
Tap T3133312681213116110981035964913
Tap T4*14391392134012951250120011451090
Tap T519201872183617851728169916451592
4YCL4042B1100ATap T110981020954886814765691620
Tap T214501380132612671204113710951031
Tap T3*15271469141813571289124311901132
Tap T419501884184217901743168716371571
Tap T520311992192118711820177017111650
4YCL4048B1100ATap T110981020954886814765691620
Tap T216041521145613971330126011861115
Tap T316631605154114891425136612311260
Tap T4*18711806174716931631157515091449
Tap T520311992192118711820177017111650
4YCL4060B1100ATap T11292121811311033947864809731
Tap T21466139013181230115110731009932
Tap T317741719166115991529144813841306
Tap T4*20241973191918571798173116681600
Tap T521442087202819621911184917851718

* Denotes factory set cooling speed

Tap 1 is factory set fan speed

Data is with a dry coil

Gas Information

Table 8. Gas Pipe Capacities

NOMINAL PIPE DIAMETER (IN.)CAPACITY OF BLACK IRON GAS PIPE (CU. FT. PER HOUR) FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60)
1020304050607080
1/213090756555504540
3/42801901501301151059590
1520350285245215195180170
1 1/41,050730590500440400370350
1 1/21,6001,100890760670610

Cubic Feet Per Hour Required = Input To Furnace (Btu/hr) / Heating Value of Gas (Btu/Cu. Ft.)

NOTE: The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas flow required by the furnace. To determine the cubic feet per hour of gas flow required by the furnace, divide the input rate of the furnace by the heating value (from gas supplier) of the gas.

Table 9. Gas Flow Rates

TIME FOR ONE REVOLUTION (SECONDS)CUBIC FEET PER REVOLUTION OF GAS METERCUBIC FEET PER REVOLUTION OF GAS METER
15101510
103601,8003,6006655273545
123001,5003,0006853265529
142571,2862,5717051257514
162251,1252,2507250250500
182001,0002,0007449243486
201809001,8007647237474
221648181,6367846231462
241507501,5008045225450
261386921,3858244220439
281296431,2868443214429
301206001,2008642209419
321135631,1258841205409
341065291,0599040200400
361005001,0009239196391
38954749479438191383
40904509009638188375
42864298579837184367
448240981810036180360
467839178310235176353
487537575010435173346
507236072010634170340
526934669210833167333
546733366711033164327
566432164311232161321
586231062111432158316
606030060011631155310
625829058111831153305
645628156312030150300

FOR YOUR SAFETY READ BEFORE OPERATING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.

A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or move by hand, do not try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

OPERATING INSTRUCTIONS

  1. STOP! Read the safety information above on this label.
  2. Set the thermostat to the lowest setting.
  3. Turn off all electrical power to the appliance.
  4. The appliance's ignition device automatically lights the burner. Do not try to light burner by hand.
  5. Remove the control access door/panel (upper door if two-door model).
  6. Move the gas control switch to the "OFF" position. (See Figure 1)
  7. Wait fi ve (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in above information. If you don't smell gas, go to the next step.
  8. Move the gas control switch to the "ON" position. (See Figure 1)
  9. Replace the control access door/panel (upper door if two door model).
  10. Turn on all electrical power to the appliance.
  11. Turn the thermostat to a desired setting.
  12. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.

TO TURN OFF GAS TO APPLIANCE

  1. Set the thermostat to the lowest setting.
  2. Turn off all electrical power to the appliance if service is to be performed.
  3. Remove the control access door/panel (upper door if two-door model).
  4. Move the gas control switch to the "OFF" position. Do not use force. (See Figure 1)
  5. Replace the control access door/panel (upper door if two-door model).

Diagram Description: Figure 11 shows the Gas Valve Label with a diagram of the gas valve, including the switch for ON/OFF positions.

Wiring Diagram & Electrical Data

Diagram Description: Figure 12 provides the wiring diagram for a 230V / 60 Hz unit, detailing connections for the compressor, outdoor fan motor, pressure switches, limit switches, gas valve, ignitor, inducer, blower motor, and auto transformer. It also includes a legend for field wiring, low voltage, and high voltage, and a diagnostic code table with LED indicators.

Diagram Description: Figure 13 provides the wiring diagram for a 230V / 60 Hz unit with an ECM Outdoor Motor, similar to Figure 12 but with specific ECM motor connections.

Table 10. Electrical Data.

MODEL NUMBERHEATING INPUT (BTUH)NOMINAL ELECTRICAL SUPPLYVOLTAGE RANGECOMPRESSORFAN AMPSBLOWER AMPSINDUCER MOTOR AMPSMINIMUM CIRCUIT AMPACITYMAXIMUM OVER-CURRENT PROTECTION
MIN.MAX.RLALRA
024K55,000230-60-119625312.858.31.03.80.720.830
030K70,000230-60-119625314.1731.465.40.724.535
036K70,000230-60-119625316.7791.465.40.727.740
042K100,000230-60-119625319.81103.85.40.734.050
048K100,000230-60-119625321.81171.465.40.734.150
X60K100,000230-60-119625326.31341.467.00.741.360

NOTE: FLA = Full Load Amps; LRA = Lock Rotor amps; RLA = Rated Load Amps.

REFRIGERANT CHARGING

⚠ WARNING:

These units are shipped fully charged with R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be done by qualified, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation/service personnel to service this type of equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.

⚠ CAUTION:

This unit uses R-410A refrigerant. DO NOT use any other refrigerant in this unit. Use of another refrigerant may damage the unit.

The system refrigerant charge can be checked and adjusted through the service ports provided at the front panel. Use only gauge lines which have a "Schrader" depression device present to actuate the valve. Draw a vacuum on gauge lines to remove air before attaching them to the service ports on the unit. Refrigerant charging must be done by qualified personnel familiar with safe and environmentally responsible refrigerant handling procedures.

Application Notes & Charging Charts (Cooling Mode Only)

This equipments cooling system contains refrigerant under high pressure, always use safe practices when servicing the unit. Always review the factory literature and safety warnings prior to servicing.

These units are shipped from the factory with the proper amount and type of refrigerant. Always inspect the unit rating label to determine the units information prior to working on the system. Do not mix different refrigerants or charge the unit with a refrigerant not listed on the unit rating label.

The charging tables are valid for a variety of indoor, return air conditions and are most highly influenced by the outdoor ambient temperature, outdoor fan operation and the unit operating voltage. Before referencing the charts, always make sure that the compressor circuit is energized on nominal speed (Y1 energized) and has stable operation. As can be seen in the charging charts, the ideal system sub-cooling can vary over the range of operation. Always reference the charts to determine the ideal amount of sub-cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit efficiency (EER).

To inspect a systems operation, using quality instruments, match the measured liquid temperature to the units chart. The measured liquid pressure reading should be within 3% of the value shown for most installations.

For systems operating with more than a 5% deviation, inspect the unit for leaks. Always use safe and environmentally sound methods for refrigerant handling. When repairing system leakages, always utilize a nitrogen (inert) gas to protect the refrigerant system and pressure check the repair before recharging. Always replace the filter-dryers when performing any repair to the refrigeration system. After completing the repairs, evacuate the system to 350-500 microns and weigh in the refrigerant to the amount specified on the unit rating label.

FURNACE COMPONENTS

The descriptions below are various functional components that affect the operation and shutting down of this furnace. Some of these components and their locations are shown in Figure 14. If any component of the furnace must be replaced, use only factory authorized replacement parts specified in the Replacement Parts List.

Diagram Description: Figure 14 shows the locations of various furnace components including the Autotransformer, Transformer, Capacitor, Air/Fuel Mixing Tube, Combustion Air Orifice Plate, Compressor, Limit Switch, Gas Valve, Inducer Assembly, Collector Box, Terminal Strip, Furnace Control Board, Autotransformer Fuse, Contactor, Ignitor Relay, Ground Lug, Sight Glass, Gas Burner Head, Primary Air Limit Switch, Pressure Switch, and Ignitor/Flame Sensor Assembly Access.

INSTALLATION CHECKLIST

INSTALLATION ADDRESS:

CITY: STATE:

UNIT MODEL #

UNIT SERIAL #

Unit Installed Minimum clearances per Figure 1 (page 5)? YES NO

INSTALLER NAME:

CITY: STATE:

Has the owner's information been reviewed with the customer? YES NO

Has the Literature Package been left with the unit? YES NO

ELECTRICAL SYSTEM

Electrical connections tight? YES NO

Line voltage polarity correct? YES NO

Rated Voltage (VOLTS): L1-L2 Volts:

Has the thermostat been calibrated? YES NO

Is the thermostat level? YES NO

Is the heat anticipator setting correct? (If Applicable) YES NO

VENTING SYSTEM

Is the vent hood installed? YES NO

Is vent hood free from restrictions YES NO

Filter(s) secured in place? YES NO

Filter(s) clean? YES NO

ATTENTION INSTALLERS:

It is your responsibility to know this product better than your customer. This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product. Safety should always be the deciding factor when installing this product and using common sense plays an important role as well. Pay attention to all safety warnings and any other special notes highlighted in the manual. Improper installation of the unit or failure to follow safety warnings could result in serious injury, death, or property damage. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment.

GAS SYSTEM

Gas Type: (circle one) Natural Gas Propane

Gas pipe connections leak-tested? YES NO

Gas Line Pressure (in - W.C.):

Is there adequate fresh air supply for combustion and ventilation? YES NO

Installation Altitude (FT.): Deration Percentage:

Unit Input (Btuh):

Supply Air Temperature (° F):

Return Air Temperature (° F):

Temperature Rise (° F):

DURING UNIT OPERATION:

Manifold pressure (in - W.C.):

REFRIGERATION SYSTEM

Was unit given 24 hr warm up period for crankcase heaters (if equipped)? YES NO

Stage-1 Liquid Pressure (high side):

Stage-1 Suction Pressure (low side):

REPLACEMENT PARTS

Replacement parts are available through your distributor. Please have the complete model and serial number of the unit when ordering replacement parts.

ELECTRICAL:

MOTORS:

COMPONENTS:

1043684A (Replaces 10436840)

About Trane and American Standard Heating and Air Conditioning

Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

Trane

6200 Troup Hwy

Tyler, Texas 75707

18-EB42D1-1B-EN 21Jun 2024

Supersedes 18-EB42D1-1A-EN (Aug 2022)

For more information, contact your local dealer (distributor).

©2024

Models: 4YCL4024B1055A, 4YCL4030B1070A, 4YCL4036B1070A, 4YCL4042B1100A, 4YCL4048B1100A, 4YCL4060B1100A, Ultra-Low NOx Series Single Packaged Gas Heating, Ultra-Low NOx Series, Single Packaged Gas Heating, Packaged Gas Heating, Gas Heating, Heating

PDF preview unavailable. Download the PDF instead.

18-EB42D1-1B-EN 06212024 Acrobat Distiller 24.0 (Windows)

Related Documents

PreviewTrane A801X060BM4SC Single Stage Gas Furnace: Specifications and Features
Detailed specifications, features, and airflow data for the Trane A801X060BM4SC single-stage, non-condensing gas-fired furnace. Includes dimensions, ratings, and operational benefits for residential applications.
PreviewTrane TCONT602AF22MA Programmable Comfort Control Installation Instructions
Installation instructions for the Trane TCONT602AF22MA Programmable Comfort Control, detailing system application, pre-installation checks, wallplate and wiring setup, installer configuration, system testing, and troubleshooting.
PreviewTrane BAYOSAH Fresh Air Kit Installation Guide
Official installer's guide for Trane and American Standard BAYOSAH fresh air kits, providing installation instructions, model compatibility, dimensions, and important safety information for HVAC systems.
PreviewTrane Packaged Terminal Air Conditioners & Heat Pumps - Product Overview and Specifications
Detailed product information for Trane Packaged Terminal Air Conditioners (PTACs) and Heat Pumps, including features, benefits, technical specifications, performance data, dimensions, and warranty.
PreviewTrane Down Discharge Economizer and Rain Hood Installer's Guide | BAYECON105A/106A
Detailed installation, wiring, checkout, and troubleshooting guide for Trane's Down Discharge Economizer and Rain Hood (models BAYECON105A, BAYECON106A) used with various HVAC units. Includes safety warnings and technical specifications.
PreviewTrane 4YCC Series: 13 SEER Single Packaged Convertible Gas/Electric Systems Product Data
Detailed product data for Trane's 4YCC series of single-packaged convertible gas/electric HVAC systems, featuring 13 SEER efficiency, dual fuel heating and cooling capabilities, and specifications for models 4YCC3018 through 4YCC3060.
PreviewTrane Top Mount Hydronic Coil Accessory Installer's Guide
Comprehensive installer's guide for the Trane Top Mount Hydronic Coil Accessory, designed for Hyperion™ and ForeFront™ air handler models. Covers essential safety precautions, installation steps, piping guidelines, performance tables, and operational configurations for HVAC professionals.
PreviewInstaller's Guide: Extreme Condition Curb Mounting Kit MAYEXMK002A/003A
Installation guide for Trane and American Standard Extreme Condition Curb Mounting Kit (MAYEXMK002A/003A) for 2-5 Ton Double Deck Gas Units. Includes safety warnings, kit contents, and step-by-step installation procedures with diagram descriptions.