Pressure switch and thermostat, type KP and KPI

Pressure switch and thermostat, type KP and KPI - Danfoss

Figure 1: Key sketch of KP pressure switch oss 60-973.13.10 O=14mm oss 60-972.13.10 Figure 2: Key sketch of KPI pressure switch oss 60-776.17.10 O=14mm

Pressure switch and Thermostat Type KP ...

Pressure switch and Thermostat Type KP and KPI

AI000086439001en-001001
Data Sheet
Pressure switch and Thermostat Type KP and KPI

For industrial applications

The KP and KPI pressure switches and thermostats are used for control, monitoring and alarm systems in a wide variety of industry applications. KP pressure switches are mainly used for gaseous fluid whereas KPI pressure switches are more for liquid and gaseous fluid. The products are available in IP30 enclosure as well as IP55 enclosure. The KP pressure range include special designed pressure switches and limiters for steam boilers and other heating applications. For water pump control and protection (dry run) the dual pressure switch KP44 is suitable and secure improved life time of the water pump.

AI000086439001en-001001

Pressure switch and Thermostat, Type KP and KPI
Features
Features · Wide setting range · Shock and impact resistant · Snap action electrical contacts minimize chatter, bounce, and wear, and ensure long term electrical and
mechanical reliability · Small dimensions - space saving and easy to install in panels · Electrical connection from front of the unit makes rack mounting easier and also saves space · Suitable for alternating current and direct current · Single pressure switches and thermostats are fitted with a single pole double throw contact system (SPDT) · Can be used for both liquids and gases (KPI) · Manual trip function enables electrical connections verification without any tools or pressure changes in the
application · Versions with automatic and manual reset available · For demineralized water, there are special KP models with wetted parts made of stainless steel (AISI 316L)

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 2

Danfoss 60-973.13.10
Danfoss 60-972.13.10
Danfoss 60-776.17.10 Danfoss 60-974.12.10

Pressure switch and Thermostat, Type KP and KPI
Functions KP and KPI Pressure switch
Figure 1: Key sketch of KP pressure switch

Figure 2: Key sketch of KPI pressure switch

O=14mm
Figure 3: Key sketch of KP pressure switch, boiler version
3

O=14mm

Danfoss 60-1356.11.10 Danfoss 60-1355.11.10

1 Setting spindle 2 Differential setting spindle 3 Main arm 4 Main spring 5 Differential spring 6 Bellows 7 Pressure connector

8 Contact system 9 Connection terminals 10 Earth terminal 11 Cable entry 12 Omega spring (KPI) 12 Tumbler (KP) 13 Locking screw 14 Manual reset

The contact system in KP pressure switches has a snap function. This means that the bellows is active only when the cut-in or cut out value is reached. The bellows is connected to the pressure of the controlled plant via the connector. Danfoss KPI pressure switches are designed so that the bellows moves in the same proportion as the pressure switches change. To ensure a snap function on contact change over, an omega spring is located between bellows and contact system.

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 3

Pressure switch and Thermostat, Type KP and KPI
KP 44 pressure switch
Figure 4: Key sketch of KP 44 pressure switch

Danfoss 60-1175.12.10

O=14mm
1 Lefthand pressure setting spindle 2 Differential setting spindle 3 Main arm 4 Righthand pressure setting spindle 5 Main spring 6 Differential spring 7 Bellows 8 Pressure connections

9 Contact system 10 Terminal 11 Earth terminal 12 Cable entry 13 Tumbler 14 Locking plate 15 Impulse lever

Water supply from reservoir or well The contact system in the KP 44 has a snap-action function and allows the bellows moves only when the cut-in or cut-out value is reached. If water is running short in the well or reservoir, the pump will no longer be able to increase the pressure to the cutout value. Consequently the pump will keep running - perhaps without water. However, the KP 44 pressure switch will stop the pump as soon as the righthand bellows pressure drops below the safety cut-out setting. The pump can be started again by lifting the impulse lever. The pump will continue to operate when the impulse lever is released, provided that the righthand bellows pressure is higher than the safety cut-out setting plus a fixed differential of 1 bar. If this is not the case, the pump will cut-out again indicating insufficient water supply. Pressurized water supply direct to pump When water supply fails on the inlet side, the pump will no longer be able to boost the pressure to the cut-out value. Consequently the pump will keep running - perhaps without water. However, the KP 44 pressure switch will stop the pump as soon as the pressure in the pump suction line drops below the safety cut-out setting. The pump will automatically start again when the pump suction pressure has reached the level of 1 bar above the safety cut-out setting. Automatic start-up will only take place if the righthand bellows is connected to the pump suction line. Air pockets should be avoided to prevent the pump from starting up on air pressure rise, without the presence of water.

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 4

Pressure switch and Thermostat, Type KP and KPI

In a hydrophore system where water is pumped from a well or an open tank, both bellows are connected to a pressure outlet on the air side in the pump pressure line, if possible.

In a booster system receiving pressurized water the righthand bellows is connected · to the low pressure side of the pump forautomatic start-up · to the high pressure side of the pump for manual start-up The lefthand bellows is always connected to the high pressure side of the pump.
KP thermostat
Figure 5: Key sketch of KP thermostat, types KP 78, KP 79, KP 81 12 8

4

5

4

12

9

5

8

10

6

6

11

11 7

7

Danfoss 60-971.13.10
Danfoss 60-970.12.10

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 5

Pressure switch and Thermostat, Type KP and KPI
1 Temperature setting spindle 2 Differential setting spindle 3 Main arm 4 Main spring 5 Differential spring 6 Bellows Figure 6: KP 75 room sensor

7 Sensor 8 Contact system 9 Connection terminals 10 Earth terminal 11 Cable entry 12 Tumbler

7

Danfoss 60-904.12.10

The contact system in KP thermostats has a snap function. This means that the bellows is active only when the cutin or cut-out value is reached.

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 6

Pressure switch and Thermostat, Type KP and KPI

Product specification

Technical Data

Single pressure switch

Table 1: Single pressure switch

Description

Ambient temperature [°C] Media temperature [°C] Fluid

Parts in contact with fluid

Bellows Pressure connector

KP 35, KP 36

KPI 35, KPI 36

KPI 38

KP 34, KP 35, KP 36, KP 37 boiler version

-40 ­ 65 °C (for max. 2 hours up to 80 °C)

-40 ­ 100 °C

Gaseous media

Gaseous media and liquids

Steam, air, gaseous media & liquids

Phosphor bronze or Stainless steel

Phosphor bronze

Stainless steel

Free-cutting steel (nickel plated) or Stainless steel

Brass

Free-cutting steel (nickel plated)

Contact system

Contact load, Silver
Contact load, Gold plated contact set Enclosure, IP30 grade Enclosure, IP44 grade Enclosure, IP55 grade Cable entry Mounted on back plate / wall bracket Mounted on angle bracket

Single-pole double throw (SPDT)

Alternating current: AC-1: 16 A, 400 V AC-3: 16 A, 400 V AC-15: 10 A, 400 V

Alternating current: AC-1: 10 A, 440 V AC-3: 6 A, 440 V AC-15: 4 A, 440 V

Alternating current: AC-1 : 16 A, 400 V AC-3 : 16 A, 400 V AC-15 : 10 A, 400 V

Direct current: DC-13: 12 W, 220 V

Direct current: DC-13: 12 W, 220 V

Direct current: DC-13: 12 W, 220 V

See Table 6

Unit must be mounted on a flat surface / a flat fitting and all unused holes covered

Mounted as IP30 plus fitting of top cover, code no. 060-109766

Unit mounted in a special IP55 enclosure, code no. 060-033066 or 060-062866

Rubber cable gland entry for 6 ­ 14 mm diameter cables

Vibration proof in the range 0 ­ 1000 Hz, 4 g [1g = 9.81 m/s2]

Not recommended in areas where vibrations occur

Table 2: Contact system and application

Switch type ­ single pole double throw

Switch action

Application

Terminal 1­ 4 close high and open low Terminal 1 ­2 can be used as low pressure alarm

Low pressure cut-out

SPDT
Figure 7: Setting

Terminal 1 ­ 2 open high and close low Terminal 1 ­ 4 can be used as high pressure alarm

High pressure cut-out

Diff. Range

Cut-in and cut-out pressures of the system should always be checked with an accurate pressure gauge. Pressure setting for switches with automatic reset.

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 7

Pressure switch and Thermostat, Type KP and KPI

· Set the cut-in pressure on the "CUT-IN" scale (range scale). · Set the differential on the "DIFF" scale.

The cut-out pressure must be above absolute vacuum (pe = -1 bar). For high pressure switches the restart pressure is equal to cut-out pressure minus differential.

Pressure switches with manual reset Set the cut-out presure on the "CUT-OUT" scale (range scale).

High pressure limiters can be manually reset when the pressure is equal to the stop pressure minus the differential.

 NOTE: For low pressure switches the restart pressure is equal to cut-out pressure plus differential value.

Dual pressure switch

Table 3: Dual pressure switch
Temperature Ambient temperature [°C] Media temperature [°C] Fluid
Parts in contact with fluid

Range -40 ­ 65 °C (for max. 2 hours up to 80 °C) Max. 100 °C Liquids Bellows Pressure connector

Phosphor bronze, CuSn6 Free-cutting steel (nickel plated)

Contact system

Contact load, Silver
IP level Cable entry Mounted on backplate or wall bracket Mounting on angle bracket

Alternating current: AC-1: 16 A, 400 V AC-3: 16 A, 400 V AC-15: 10 A, 400 V
Direct current: DC-13: 12 W, 220 V
IP22
Rubber cable gland entry for 6 ­ 14 mm diameter cables
Vibration-proof in the range 0 ­ 1000 Hz, 4 g [1g = 9.81 m/s2]
Not recommended for areas where vibration occurs

Safety cut-out setting The righthand bellows will automatically cut-out the pump at the safety cut-out setpoint. Automatic start-up, if any, will take place when the pressure has reached the level of 1 bar above the setpoint. Manual cut-in is made by lifting the impulse lever and releasing it again when the pressure has increased by min. 1 bar. The safety cut-out setpoint is normally determined by the static pressure (the water column). However, in order to avoid disturbing signal interaction, care should be taken to ensure that the safety cut-out setting is at least 1.5 bar lower than the control pressure cut-in setting. See table with pressure setting examples below

Table 4: Pressure settings
Required tap water pressure Control pressure cut-out setting Differential Control pressure cut-in setting Max. safety cut-out setting

 2.3 bar 3.0 bar 0.7 bar 2.3 bar 0.8 bar

 4.0 bar 5.0 bar 1.0 bar 4.0 bar 2.5 bar

 5.0 bar 8.0 bar 3.0 bar 5.0 bar 3.5 bar

 8.0 bar 12 bar 4.0 bar 8.0 bar 6.0 (1)bar

(1) 6.0 bar is the normal max. setpoint
Control pressure settings Control pressure cut-out setpoint is set on the lefthand pressure setting scale. The differential is set between 0.7 and 4 bar. The control pressure cut-in setting will be the cut-out control pressure less the differential.

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 8

Pressure switch and Thermostat, Type KP and KPI

Thermostat
Table 5: Thermostat
Temperature Ambient temperature [°C] Sensor material

Range -40 ­ 65 °C (for max. 2 hours up to 80 °C) Tinned copper Cu/Sn5

Contact system

Contact load, Silver
Contact load, Gold plated contact set Enclosure, IP30 grade Enclosure, IP44 grade Enclosure, IP55 grade Cable entry Mounted on backplate or wall bracket Mounted on angle bracket
Charges Figure 8: Charges

Single-pole double throw (SPDT) Alternating current: AC-1: 16 A, 400 V AC-3: 16 A, 400 V AC-15: 10 A, 400 V Direct current: DC-13: 12 W, 220 V See Table 6 Unit must be mounted on a flat surface / a flat fitting and all unused holes covered Mounted as IP30 plus fitting of top cover, code no. 060-109766 Unit mounted in a special IP55 enclosure, code no. 060-033066 or 060-062866. Exception: KP 75 Entry for 6 ­ 14 mm diameter cable Vibration-proof in the range 0 ­ 1000 Hz, 4 g [1 g = 9.81 m/s2] Not recommended for areas where vibration occurs
6 Bellows 7 Sensor 13 Capillary tube

6

13

Danfoss 60-909.11.10

17
Absorption charge The charge consists partly of a superheated gas and partly of a solid substance with a large absorption surface. The solid substance is concentrated in the sensor, and consequently it is always the sensor that comprises the temperature-regulating part of the thermostatic element. The sensor can be placed both warmer or colder than the thermostat housing and capillary tube. However, placing it in an ambient temperature higher or lower than 20 °C can affect the accuracy of the scale.

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 9

Pressure switch and Thermostat, Type KP and KPI

Setting

Thermostats with automatic reset Set the upper limit temperature on the range scale. Then set the differential on the DIFF scale. The temperature set on the range scale is also the temperature at which contact changeover re-occurs on rising temperature. The contacts changeover when the temperature has fallen to a value lower than that set on the DIFF scale.

If at lower settings the plant will not start/stop, the reason might be that the differential has been set too high.

Thermostats with minimum reset Set the temperature on the range scale. The differential setting is fixed.

Min. reset units will restart after the temperature at the thermostat sensor has risen by a value greater than that of the fixed differential.

Thermostats with maximum reset Set the stop temperature on the range scale. The differential setting is fixed.

Max. reset units will restart after the temperature at the thermostat sensor has fallen by a value greater than that of the fixed differential.

Dimensions [mm] and weights [kg]

Single pressure switch, type KP and KPI

Figure 9: KP 35, 36, KPI 35, 36, 38, Net weight 0.3 kg

Figure 10: IP55 enclosure

84

44

61

Danfoss 60-9059.10

28 ­ 30

O=14mm

Figure 11: Wall bracket

Figure 12: Angle bracket

Danfoss 60-221.13

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 10

Pressure switch and Thermostat, Type KP and KPI

Single pressure switch, type KP (Boiler version)

Figure 13: KP 35, 36 (net weight approx. 0.34 kg)

Figure 14: KP 34 (net weight approx. 0.43 kg)

Danfoss 60-1358.11

O=24
Dual pressure switch, type KP 44
Figure 15: KP 44 (net weight 0.5 kg)

Danfoss 60-1357.11

Danfoss 60-1178.12

Thermostat, type KP
Figure 16: KP 75, 78, 79, 81 (net weight 0.4 kg) 84

Figure 17: IP55 enclosure

14

61

Danfoss 60-298.16

44 © Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 11

Pressure switch and Thermostat, Type KP and KPI Figure 18: KP 75 Sensor: Tinned copper Cu/Sn 5 Figure 19: KP 78, 79, 81 Sensor: Tinned copper Cu/Sn 5

Danfoss 60-435.13
Danfoss 60-663.11

Figure 20: Wall bracket

Figure 21: Angle bracket

Danfoss 60-221.13

Danfoss 60-969

General information gold contacts

Table 6: Gold contacts
Contact material

Gold-plated silver
SPDT 4

Contact system

Line 1 2

Contact load (when Au surface is burnt away)

Single-pole double throw (SPDT) Alternating current: Ohmic load: AC-1: 10 A, 440 V Inductive load: AC-3: 6 A, 440 V and AC-15: 4 A, 440 V
Direct current: DC-13: 12 W, 220 V

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 12

Pressure switch and Thermostat, Type KP and KPI

Figure 22: Contact load

A Gives the maximum load B Acceptable load for the gold plating of the contact (DC-13)

Terminology
Range setting / Set point The pressure range within which the unit will give a signal (contact changeover). Differential The difference between contact changeover on rising and falling pressure. The differential is a condition for stable automatic plant operation. Manual reset A unit with manual reset can only be restored to operational mode by activation of the external reset button. Min. reset units will restart after the pressure has risen by a value greater than that of the fixed differential. Max. reset units will restart after the pressure has fallen by a value greater than that of the fixed differential. Automatic reset Units with automatic reset restart automatically after stop. Permissible operating pressure The highest permissible constant pressure or pressure variation the unit can be exposed to. Maximum test pressure The maximum pressure applied in strength or leakage tests on heating system or components thereof. Maximum working pressure The maximum permissible pressure for safe functioning of a heating system or any of its parts. Snap function A specific contact force is maintained until snap is initiated. The time over which contact force reaches zero is a few milliseconds; therefore, contact bounce cannot occur as a result, for example, of slight vibrations before cut-out. The snap-action contact system will continue to function even when micro-welds are created between the contacts during cut-in. The force created to separate the contacts is strong, and instantly shears off all contact surface welds that have been created as the result of cut-in action. These design features ensure that the cut-out point of the KP control remains very accurate and completely independent of the magnitude of the current load. Current ratings:

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 13

Pressure switch and Thermostat, Type KP and KPI

AC ­ 1
AC ­ 3 AC ­ 15 DC ­ 13

The alternating current rating, in amperes, of the non-inductive, slightly inductive loads or resistive furnaces The alternating current rating, in amperes, of the squirrel-cage motors: starting, plugging, inching The alternating current rating, in amperes, of electromagnetic loads (>72VA) The direct current rating, in amperes, of electromagnets

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 14

Pressure switch and Thermostat, Type KP and KPI

Ordering

Pressure switch, type KP and KPI

Table 7: Pressure switch, types KP 35 and KP 36

Type

Setting range Pe [bar]

Differential [bar]

Permissible oper- ating pressure Pe
[bar]

-0.2 ­ 7.5

0.7 ­ 4.0

17

KP 35

-0.2 ­ 7.5

0.7 ­ 4.0

17

-0.2 ­ 7.5

0.7 ­ 4.0

17

-0.2 ­ 7.5

0.7 ­ 4.0

17

2.0­ 14.0

0.7 ­ 4.0

17

KP 36

2.0­ 14.0

0.7 ­ 4.0

17

2.0 - 14.0

0.7 - 4.0

17

2.0­ 14.0

0.7 ­ 4.0

17

4.0 ­ 12.0

0.5 ­ 1.6

17

4.0 ­ 12.0

0.5 ­ 1.6

17

Max. test pres- sure [bar]
22
22 22 22
22
22 22 22 22 22

Pressure connec- tion

Contact material

G 1/4 A
G 1/4 A G 1/4 A G 1/4 A
G 1/4 A
G 1/4 A G 1/4 A G 1/4 A G 1/4 A G 1/4 A

silver
gold-plated silver silver
silver
gold silver silver silver gold

Code no.
060-113366 060-113391 (1) 060-504766 060-538666 (2) 060-450366 (3) 060-110866 060-110891 060-113766 060-450166(3) 060-538766(2) 060-122166 060-114466

(1) Available only in Asia market (2) IP55 transparent enclosure (3) Stainless steel version, IP55 non-transparent enclosure

Table 8: Pressure switch, types KPI 35 ­ KPI 38

Type KPI 35 KPI 36 KPI 38

Setting range Pe
[bar] -0.2 ­ 8.0 -0.2 ­ 8.0 -0.2 ­ 8.0 -0.2 ­ 8.0 4 .0­ 12.0 4 .0­ 12.0 2.0 ­ 12.0 2.0 ­ 12.0 8.0 ­ 28.0 8.0 ­ 28.0

Differential
[bar] 0.4 ­ 1.5 0.4 ­ 1.5 0.5 ­ 2.0 0.4 ­ 1.5 0.5 ­ 1.6 0.5 ­ 1.6 0.5 ­ 1.6 0.5 ­ 1.6 1.8 ­ 6.0 1.8 ­ 6.0

Permissible oper- ating pressure Pe
[bar] 18 18 18 18 18 18 18 18 30 30

Max. test pres- sure [bar] 18 18 18 18 18 18 18 18 30 30

Pressure connec- tion

Contact material

G ¼ A G ¼ A G ¼ A G ¼ A G ¼ A G ¼ A G ¼ A G ¼ A G ¼ A G ¼ A

silver gold-plated
silver silver silver gold-plated silver silver silver silver

Code no.
060-121766 060-316466 060-121966 060-315766 (4) 060-118966 060-113866 060-316966 060-319366 (5) 060-508166 060-541866

(4) IP55 transparent enclosure (5) IP55 non-transparent enclosure

Table 9: Pressure switch, types KP 34 ­ KP 37, boiler version

Type KP 34 KP 35 KP 36 KP 37

Setting range pe
[bar] 0.1 ­ 1.0 0.1 ­ 1.0 0.4 ­ 3.4 0.4 ­ 3.4 1.0 ­ 10.0 1.0 ­ 10.0 4.0 ­ 20.0 4.0 ­ 20.0

Differential
[bar] 0.1 ­ 0.4
0.2 0.4 ­ 2.2
0.5 0.7 ­ 4.0
0.7 1.8 ­ 3.1
3.0

Reset
Automatic Manual
Automatic Manual
Automatic Manual
Automatic Manual

Pressure connec- tion [bar] G 1/2 A G 1/2 A G 1/2 A G 1/2 A G 1/2 A G 1/2 A G 1/2 A G 1/2 A

Max. test pres- sure [bar] 4.0 4.0 10 10 17 17 28 28

Contact material
silver silver silver silver silver silver silver silver

Code no.
060-216466 060-216366 060-216666 060-216566 060-215966 060-216066 060-216166 060-216266

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 15

Pressure switch and Thermostat, Type KP and KPI

Table 10: Pressure switch, type KP 44

Pressure range

Differential

Control [bar]

Safety [bar]

Control [bar]

Safety [bar]

2.0 ­ 12.0

0.5 ­ 6.0

0.7 ­ 4.0

1.0

Permissible operating pressure pe [bar]
Left side: 17 Right side: 17

Max. test pressure [bar]
Left side: 25 Right side: 19

Pressure con- Contact mate-

nection

rial

Code no.

2 × G ¼ A

Silver

060-001366

Thermostat, type KP

Table 11: Thermostat, types KP 75 ­ KP 81

Type

Setting range [°C]

Differential [°C]

KP 75 KP 75 KP 78 KP 79 KP 81 KP 81 KP 81 KP 81 (max. reset)

0 ­ 40 0 ­ 40 30 ­ 90 50 ­ 100 80 ­ 150 80 ­ 150 80 ­ 150 80 ­ 150

3 ­ 10 3 ­ 10 5 ­ 15 5 ­ 15 7 ­ 20 7 ­ 20 7 ­ 20 8 (max. reset)

Max. sensor temperature
[°C] 80 80 150 150 200 200 200 200

Capillary tube length
[m] Room sensor Room sensor
2 2 2 3 5 2

Contact material
silver gold-plated
silver silver silver silver silver silver

Code no.
060L121266 060L117166 060L118466 060L112666 060L112566 060L118366 060L117066 060L115566

Accessories for KP pressure switches

Table 12: KP pressure switches

Part

Symbol

Brackets with mounting screws and washers

Description Wall bracket for KP
Angle bracket for KP

Total Code no

1

060-105566

1

060-105666

Screwed cable entry

PG 13.5 with special nut For 6 ­14 mm diameter cables

1

060-105966

Sealing screw Top cover
Protective cap IP55 nontransparent enclosure IP55 transparent enclosure

For sealing the setting on KP

2

060-105766

If a bracket is mounted on the backplate of the housing, the KP thermostats will have an IP44 grade of enclosure. The cover pro- 1 tects the setting spindles

060-109766

Protective cap for KP pressure switches and thermostats. To protect

the unit against rain and humidity. Grade of enclosure: IP44 Material: Polyethylene Max. ambient temperature: 65 °C Min. ambient

1

temperature: -40 °C

060-003166

If the unit risk being exposed to heavy water influence a better grade of enclosure can be achieved when mounting product in a 1 special IP55 enclosure If the unit risk being exposed to heavy water influence a better grade of enclosure can be achieved when mounting product in a 1 special IP55 enclosure

060-033066 060-062866

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 16

Pressure switch and Thermostat, Type KP and KPI

Accessories for KP 44 pressure switches

Table 13: KP 44 pressure switches

Part

Symbol

Brackets with mounting screws and washers

Description Wall bracket
Angle bracket

Total 1
1

Code no. 060-105566
060-105666

Screwed cable entry

PG 13.5 with special nut for 6 ­ 14 mm diameter cables

1

060-105966

Sealing screw

For sealing the setting on KP

Accessories for KP thermostats

Table 14: Accessories
Part

Symbol

Brackets with mounting screws and washers

Description Wall bracket for KP
Angle bracket for KP

2

060-105766

Total 1
1

Code no. 060-105566
060-105666

Sensor holder Screwed cable entry Sealing screw Top cover Protective cap

Sensor holder for wall mounting with four capillary tube clips and 9-off 12 mm pins

1

PG 13.5 with special nut For 6 ­ 14 mm diameter cables A

standard Pg 16 cable entry can be used for 8 ­16 mm diame-

1

ter cables

For sealing the setting on KP

2

If a bracket is mounted on the backplate of the housing, the

KP thermostats will have an IP44 grade of enclosure. The cover

1

protects the setting spindles

Protective cap for KP pressure switches and thermostats.

To protect the unit against rain and humidity.

Grade of enclosure: IP44 Material: Polyethylene

1

Max. ambient temperature: 65 °C

Min. ambient temperature: -40 °C

017-420166 060-105966 060-105766 060-109766 060-003166

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 17

Pressure switch and Thermostat, Type KP and KPI

Part Sensor pocket

Symbol

Brass

Stainless steel

Description

Total

Code no.

For all KP thermostats with cylindrical remote sensor. Sensor pocket, gasket and union for screwing into G½ connectors welded onto tubes, containers, etc.

Int. diameter 9.6 mm, insert depth 112 mm (brass). Ext. diameter 11 mm.

1

017-437066

Int. diameter 9.6 mm, insert depth 112 mm (st 18/8). Ext. diameter 11 mm.

1

017-436966

Int. diameter 9.6 mm, insert depth 465 mm (brass). Ext. diameter 11 mm.

1

017-421666

Heat-conductive aluminium paste

Media temperature for sensor: 250 °C This temperature can be increased by applying a different gasPermissible pressure of sensor pipe ket material
medium

Tube

For KP and RT thermostats with sensor mounted in a sensor pocket. Temperature range: -20 ­ 150 °C (short-lived 220 °C)

1

041E0115

Danfoss 41E9000

Tube with 6 g aluminium paste

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 18

Pressure switch and Thermostat, Type KP and KPI

Certificates, declarations, and approvals

The list contains all certificates, declarations, and approvals for this product type. Individual code number may have some or all of these approvals, and certain local approvals may not appear on the list.

Some approvals may change over time. You can check the most current status at danfoss.com or contact your local Danfoss representative if you have any questions.

Table 15: Certificates, declaration and approvals

Document name

Document type

BK_W_0862_01_2018

Food and Health - Performance Certificate

RU -DK.02..03367

EAC Declaration

RU C-DK.08..00063_18

Electrical - Safety Certificate

ELE-086320XG-003

Marine - Safety Certificate

UA.1O146.D.00075-19

UA Declaration

Document topic
EMC EMC/LVE
EMCD/LVD

Approval authority PZH EAC EAC RINA LLC CDC EURO TYSK

· CE-marked in accordance with LVD 2014/35/EU: EN 60947-1, EN 60947-4-1, EN 60947-5-1 · Underwriters Laboratories Inc., UL · China Compulsory Certificate, CCC (excluding boiler versions)

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 19

Online support
Danfoss offers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below. The Danfoss Product Store
The Danfoss Product Store is your one-stop shop for everything product related--no matter where you are in the world or what area of the cooling industry you work in. Get quick access to essential information like product specs, code numbers, technical documentation, certifications, accessories, and more. Start browsing at store.danfoss.com.
Find technical documentation Find the technical documentation you need to get your project up and running. Get direct access to our official collection of data sheets, certificates and declarations, manuals and guides, 3D models and drawings, case stories, brochures, and much more. Start searching now at www.danfoss.com/en/service-and-support/documentation.
Danfoss Learning Danfoss Learning is a free online learning platform. It features courses and materials specifically designed to help engineers, installers, service technicians, and wholesalers better understand the products, applications, industry topics, and trends that will help you do your job better. Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.
Get local information and support Local Danfoss websites are the main sources for help and information about our company and products. Find product availability, get the latest regional news, or connect with a nearby expert--all in your own language. Find your local Danfoss website here: www.danfoss.com/en/choose-region.

© Danfoss | Climate Solutions | 2022.05

AI000086439001en-001001 | 20


Danfoss A/S