LCN Senior Swing Control Box Installation Instructions

Model Numbers: 2800 Overhead Concealed Series, 9500 Surface Applied Series

Important Safety Information

IMPORTANT: These instructions are presented in step-by-step sequence. It is very important that installation begins with "1. Pre-Installation Site and Product Check" (page 3) and continues as directed after each section.

WARNING: Always disconnect main power to the operator prior to replacing. Control box contains no serviceable parts inside.

Table of Contents

General Information

The Senior Swing Control Box is for use with the Senior Swing Power Operator System. The system can operate a single door (2810, 9530, and 9540 Series), a simultaneous pair of doors (2850 and 9550 Series), or an independent pair of doors (2860 and 9560 Series).

ANSI/BHMA A156.19 Compliance: The Senior Swing Power Operator System is a low energy product and must conform to the latest version of ANSI/BHMA A156.19 (American National Standard for Power Assist and Low Energy Power Operated Doors).

Installation Instructions: All installation instructions are valuable references and should be given to the building owner or maintenance supervisor after installation is complete. The Senior Swing Control Box installation instructions and the manufacturer's instruction manual accompanying any sensor must be referenced to ensure proper installation, setup, and operation.

Electrical Specifications

AC input voltage120 VAC
AC fuse120 VAC, 2.5 A time-delay fuse
Motor protectionSolid state failure detection and shutdown
Activate inputsdry NO contacts (close contacts to open door)
Safety inputsdry NO contacts (closed contacts indicate an obstruction)
Breakaway inputdry NC contacts (open contacts indicate breakaway)
3-position switch inputdry 3-position switch
Power Boost disable inputdry NO contacts (close contacts to disable Power Boost)
Lock outputForm C dry relay contacts rated 8 A, 30 VDC maximum
Accessory power output24 VDC, 1A (protected by resettable thermal fuse)
Logic power output5 V, 50 mA (protected by resettable thermal fuse)

1 Pre-Installation Site and Product Check

IMPORTANT:

TypeWidth per LeafMaximum Weight per Leaf
Single Door36" to 48"200 lb. (36 in. @ 400 lbs.)
Simultaneous Pair30" to 48"200 lb. (36 in. @ 400 lbs.)

1a. All required installation steps listed before "8. Control Box Installation" in the Senior Swing installation instructions should be completed before installing the Senior Swing control box.

1b. Check that the control box model (indicated on control box label; Figure 1-1) is correct for the application.

1c. Check that the available AC voltage matches the control box voltage requirement (120 VAC).

1d. Check that all accessories required for the application are on hand.

Figure 1-1: Control Box Label

Diagram showing the LCN Senior Swing control box panel with labels indicating model, settings, and various input/output connectors (P1-P10). Key settings like Opening Speed, Backcheck Speed, Hold-Open Delay, etc., are listed with their corresponding setting codes and default values.

2 Installation

To install the Senior Swing Control Box, follow the Senior Swing installation instructions beginning with "8. Control Box Installation" on page 12 of those instructions.

CAUTION: Improper installation or set up may result in personal injury or property damage. Follow instructions carefully. For answers to questions, call 1-877-671-7011.

3 Wiring

CAUTION: When joining or separating a plug and receptacle, do not push or pull on wires. This may cause a wire to be pulled loose from a terminal, which may result in a malfunction.

Diagram illustrating wiring connections for single and dual door setups.

Diagram shows two door configurations. For a single door, the operator's motor power cable connects to the control box's Master Motor Power. For a dual door setup, the master operator connects to the Master Motor Power, and the companion operator connects to the Companion Motor Power receptacle (P5) on the control box power board. Both diagrams indicate the 'Approach side' and 'Safety side' of the doors.

Figure 3-2: Control box power board connectors.

Diagram shows the power board of the control box with connections for AC fuse (120 VAC, 2.5 A time-delay), AC power, Companion motor power (P5), and Master motor power.

Figure 3-3: Control box logic board connectors.

Diagram shows the logic board of the control box with connections for Breakaway, 3-position switch, and references Figure 3-4 for a closer look at logic board connectors.

Figure 3-4: Closeup of control box logic board connectors.

Diagram provides a detailed view of the logic board connectors, labeling various inputs and outputs such as DMSS (companion and master, approach and safety sides), Activate, Bodyguard (safety side), Locking Interface and Power Boost disable input, and Retrofit Accessories.

Figure 3-5: Wiring Diagram for Logic and Power Boards

Detailed wiring diagram illustrating connections between the Logic Board (P1-P8, P10) and Power Board (P5) to various components like DMSS sensors, Activate inputs, Breakaway switch, 3-Position Switch, Locking Interface, Companion Motor Power, Master Motor Power, and AC Input. Specific cable part numbers and wire color codes are provided for each connection.

Figure 3-6: Sample Wiring for a Fail Safe Electric Strike Locking Device

Diagram shows wiring for a fail-safe electric strike. It connects the control box locking interface (P10) to the electric strike using Cable 761465. The diagram illustrates the polarity of the diode and the connections for the COM and NO (normally open) terminals of the strike. The keypad EL (electric lock) setting should be SA (fail safe).

Figure 3-7: Sample Wiring for a Fail Secure EL (Electric Latch Retraction) Locking Device

Diagram shows wiring for a fail-secure electric latch retraction (EL) device, such as the Von Duprin PS914 x 900-2RS. It connects the control box locking interface (P10) using Cable 761465. The diagram specifies using 12 AWG stranded wire for outputs 01 and 02. The keypad EL (electric lock) setting should be SE (fail secure).

4 Keypad Settings

Settings for the Senior Swing Power Operator System are adjusted using keypad pushbuttons and an alphanumeric display on the control box (Figures 4-1 and 4-2). Close speed is adjusted using dials on the control box.

CAUTION: Adjust the operator for the slowest operation practical in accordance with the latest revisions of Americans with Disabilities Act, ANSI/BHMA A156.19 (American National Standard for Power Assist and Low Energy Power Operated Doors), and local codes.

Figure 4-1: Control Box Panel with Keypad

Diagram of the control box panel showing the keypad, setting display, value display, close speed dials, and various setting selection and value selection pushbuttons. Labels indicate functions like OPENING SPEED, BACKCHECK SPEED, HOLD-OPEN DELAY, etc.

Figure 4-2: Closeup of Control Box Keypad

A closer view of the control box keypad, highlighting the setting display, value display, setting selection pushbuttons (UP/DOWN), value selection pushbuttons (UP/DOWN), and the DEFAULT pushbutton. It lists various settings with their corresponding codes (e.g., 05: OPENING SPEED, 65: BACKCHECK SPEED).

To change setting values:

  1. Set the 3-position switch, if used, to OFF.
  2. Apply AC power. The POWER light will illuminate and the display will remain blank.
  3. Press any two pushbuttons at the same time for 1 second to turn on the keypad. The display will illuminate.
  4. Press the UP or DOWN setting selection pushbutton to select the desired setting. The setting is shown in the SETTING display, and the current value for that setting is shown in the VALUE display.
  5. Press the UP or DOWN value selection pushbutton to select the desired value for the displayed setting. The value for the setting is indicated in the VALUE display.
  6. The keypad will automatically turn off after 5 minutes of inactivity.

To reset all values to default:

  1. Set the 3-position switch, if used, to OFF.
  2. Apply AC power. The POWER light will illuminate, and the display will remain blank.
  3. Press any two pushbuttons at the same time for 1 second to turn on the keypad. The display will illuminate.
  4. Press the DEFAULT pushbutton for 4 seconds.
  5. The values are set to default, and the display will indicate the opening speed setting and value.
  6. The keypad will automatically turn off after 5 minutes of inactivity.
Figure 4-3: Door Position Definitions

Diagram illustrating key door positions during opening and closing cycles, including Back check speed, Back check position, Opening speed, Closing speed, Latch position, and Deceleration to fully closed position.

Table 4-1. Control Box Settings and Selectable Values

SettingSetting DisplaySelectable ValuesValues as DisplayedDescription
Opening Speed0501 = slow, 02 = medium, 03 = fast (default = 01)01, 02, 03Controls opening speed of any normal weight and size door
Back Check Speed6501 = slow, 02 = medium (default = 01)01, 02Controls speed of door near full open position to prevent door slamming open
Back Check Position6P45-80 degrees (default = 70)45-80Approximate angle at which door begins to decelerate near the full open position
Hold Open Delayhd01-32 seconds (default = 05)01-32Amount of time (in seconds) door remains fully open following an activate signal
Latch PositionLP00-23 degrees (default = 13)00-23Approximate angle at which door begins to decelerate near the full closed position
Auto Reverse ClosingACoff, on (default = off)OF, OnWhen on, door will re-open upon hitting an obstruction
Electric LockELoff, SA = fail safe, SE = fail secure (default = off)OF, SA, SETo turn on, set to SA (fail safe) or SE (fail secure) to match locking device connected to control box locking interface receptacle (P10); when on, causes a 1 second delay between activate signal and door opening to allow time for most electric locks to disengage before operator opens door
Power BoostPboff, 1 sec, 2 sec, 3 sec, 4 sec, 5 sec, continuous (default = off)OF, 01, 02, 03, 04, 05, СпWhen on, increases closing force of door from 9 lbs to 18 lbs to close door against high winds or stack pressure; turns on for seconds or continuously after door reaches latch position during closing cycle; disabled by Power Boost disable input
Push 'N' GoP6off, on, fd (default = off)OF, On, FdWhen set to On or Fd, pushing door open 5 degrees causes operator to open door remainder of way and hold open. Hold open time is same as hd setting when set to On. Hold open time is 1 second when set to Fd.
Alternate ActivateAAoff, on (default = off)OF, OnWhen on, door stays open until a second activate signal is received.
Safety Slow/Stop55slow, stop (default = slow)SL, SPDetermines response to a DMSS on the safety side of the door; if SL (slow), door goes to back check speed; if SP (stop), door stops for 5 seconds, then continues opening at back check speed
Special5doff, 30-85 (default = off)OF, 30-85Deactivate the Door Mounted Safety Sensor (DMSS) on safety side of door to eliminate nuisance detection of a wall or guard rail.
Status AnnouncementSAReservedReservedReserved

5 System Test

WARNING: KEEP HANDS, CLOTHING, WIRES, TOOLS, LADDERS, ETC. AWAY FROM THE DOOR WHEN THE OPERATOR IS INITIALLY TURNED ON.

If control box does not operate as expected during system test, see section 6 for troubleshooting tips.

5a. With the door closed, set the 3-position switch, if used, to AUTO and turn on all AC power. For applications using companion door, try to get both doors to open same amount of degrees before hitting hard stop (either internal gearbox stop or rubber bumper on wall).

5b. Activate the operator using an activation device. The operator should perform one sizing cycle. Sizing cycle: Occurs when the door is activated for the first time after power is turned on. During the sizing cycle, the door opens and closes once.

If the door sizes properly, go to step No. 5.3.

If the door does not open at all during the sizing cycle:

If the door does not open fully during the sizing cycle, check door for binds, obstructions, or items that could activate safety sensors.

5c. After the sizing cycle is complete and the door is closed, apply a maintained activation signal and check that the door remains open while the activation signal is applied. Then release the activate signal and verify door closes after the open time delay expires.

5d. To check the function of the door safety device:

  1. Activate the door and then activate the approach side safety device while the door is open. The door should not close while the safety device is activated. Next, deactivate the safety device. The door should close after the hold open time delay expires.
  2. With the door closed, activate the safety side safety device, then activate the door. The door should not open while the safety device is activated. Next, deactivate the safety device. The door should open when activated.

5e. Set the 3-position switch, if used, to HOLD. Verify that the door opens and stays open.

5f. Set the 3-position switch, if used, to OFF. Verify that the door closes. Verify that an activate signal does not open the door.

5g. If a Breakaway switch is connected, set the 3-position switch, if used, to AUTO, then break open the door. Verify that an activate signal does not cause the door to move. Re-latch the door after testing.

5h. Do not release the system for service until it is operating properly.

6 Troubleshooting

6a. Identify all switch and sensor inputs that are currently active:

  1. Remove breakaway jumper to enter diagnostic mode. Note: When in diagnostic mode, controller will not open door.
  2. Keypad display shows each active input signal for 1 second. See table below:
Input StatusDisplay Code
(Key switch) set to Auto OR is not presentSA80
(Key switch) set to OFFSA81
(Key switch) set to HOLDSA82
(Activate) input is ONSA83
(DMSS approach) activate input is ONSA84
(DMSS safety) slowdown input is ONSA85
(Carpet Safety) input is ONSA86
(Bodyguard) input is ONSA87
(Power Boost Disable) input is ONSA88

For example, if key switch is set to Auto, Activate button is pressed, and DMSS sees something on the safety side, then display will repeat the sequence SA80, SA83, SA85 continuously until breakaway jumper is replaced.

3. After completing diagnostics, reinstall breakaway jumper for normal operation.

6b. If control box does not function and the error message Er## flashes on the control box Setting and Value displays, turn AC power off and on to reset the control box. The following are common errors and suggested fixes:

If problem cannot be corrected by using suggested fixes, contact 1-877-671-7011.

7 Release for Service

7a. Remove all tools, installation equipment, and debris from the vicinity of the door.

7b. Install all safety, traffic control, and instruction decals on the door as required by the latest revision of ANSI/BHMA A156.19. This is very important! Failure to do this leaves the installer LIABLE for any accident that might occur. This must be done!

7c. Verbally instruct the owner or person in charge of the proper operation of the door.

7d. Instruct the owner or person in charge to routinely inspect the door for the following:

7e. Instruct the owner or person in charge who and where to call for service when required.

IMPORTANT: Make sure to install all safety, traffic control, and instruction decals on the door as required.

Customer Service: 1-877-671-7011

Website: www.allegion.com/us

Allegion 2018

Printed in U.S.A.

72937 Rev. 10/18-a

Models: Senior Swing Control Box

File Info : application/pdf, 12 Pages, 2.69MB

PDF preview unavailable. Download the PDF instead.

LCN 2800 Series and 9500 Series Senior Swing Control Box Instruction Sheet 107510

References

Adobe PDF Library 15.0

Related Documents

PreviewLCN Benchmark III Swing Operator Installation Instructions (Models 9130, 9140, 9150)
Comprehensive installation guide for the LCN Benchmark III automatic electromechanical swinging door operator, covering models 9130, 9140, and 9150. Includes pre-installation checks, wiring, adjustment, and operational procedures.
PreviewLCN 4640 Series Electrohydraulic Automatic Door Operator - Features, Mounting, and Accessories
Detailed overview of the LCN 4640 Series electrohydraulic low-energy automatic door operator, including features, technical specifications, mounting instructions, and available accessories for enhanced accessibility.
PreviewLCN 1000 Series Surface Mounted Door Closers Catalog
Explore the LCN 1000 Series of surface-mounted door closers with this comprehensive catalog. Discover features, specifications, product configurations, and detailed mounting instructions for models including 1250, 1260, 1450, 1450T, 1460, and 1460T series, designed for reliable door control.
PreviewLCN SEM7800 Series Electrically Controlled Door Holding Magnets
Detailed information on LCN SEM7800 Series heavy-duty, electrically controlled door holding magnets. Covers features, certifications, electrical data, mounting options, and available accessories for fire and life safety applications.
PreviewLCN Closers & Automatic Operators Parts Manual
A comprehensive parts manual for LCN closers and automatic operators, detailing components, part numbers, and ordering information for various series including 4000, 1000, Concealed, Fire-Life Safety, High Security, and Automatic Operators.
PreviewLCN 8310-2300 Series Touchless Actuator Installation Instructions
Detailed installation instructions for the LCN 8310-2300 Series battery-powered touchless actuator, covering descriptions, technical specifications, mounting, wiring, setup, and troubleshooting.
PreviewLCN High Security Series Vandal Resistant Door Closers - Product Catalog
Comprehensive catalog detailing LCN's High Security Series of vandal-resistant door closers, including the 2210, 4210, 4210T, 4510, and 4510T series. Features, specifications, applications, mounting details, and ordering information for correctional, institutional, and high-traffic environments.
PreviewLCN Special Template Chart for Door Closers
A comprehensive chart detailing LCN special templates for various door closer series, including 4040XP, 2210, 4000, 1460, 5030, 2030, 3130, 4116, 4000T, 1460T, 2310ME, 4310ME, 4050T, 1260, and 4020 series. The chart specifies application types, mounting details, and necessary components or modifications for each special template.