INTRODUCTION
GENERAL DESCRIPTION
The Fire Sentinel FSXPBB and Fire Sentinel FSXPBBVB Release Devices are UL/ULC listed normally energized fail-safe devices designed for use on rolling doors, single-slide, and center-parting level and inclined track doors. All models are normally energized fail-safe releasing devices incorporating state-of-the-art electronic control circuitry. The release devices respond to emergency conditions generated from an automatic initiating device and are used in conjunction with a temperature fuse link system.
The release device can be powered from 120Vac, 24 Vac, or 24Vdc line voltage or 24Vdc received from an approved UL 1481 regulated power supply with battery backup. The devices can be activated via a smoke detector or an alarm relay from the panel's Form C dry contact relay. The release device features include a 10-, 20-, 30- or 60-second delay on alarm, closed door detection capabilities, Form C relay outputs for the transmission of alarm and trouble signals transmitted to the fire alarm control panel, an audible trouble sounder, and diagnostic feedback LEDs.
The release device is provided with a battery management system that can provide 24Vdc power for up to four smoke detectors and two horn strobes, as well as provide battery backup for the release device and accessories. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications and used with fuse link systems.
AGENCY REQUIREMENTS
Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).
▲ WARNING
To prevent possible SERIOUS INJURY or DEATH:
- DO NOT use this device without fuse links installed.
- Test every 90 days to assure proper operation of release device.
SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
| VOLTAGE RATING: | 120Vac, 60Hz; 24Vac, 60Hz; 24Vdc |
|---|
| STANDBY CURRENT | .06A, .3A, .2A |
| ALARM CURRENT | .06A, .3A, .25A |
| BATTERY RATING: | 12V 4.5AH Sealed Lead Acid Battery, Maximum charge current .150Amps |
| BATTERY STANDBY TIME: | Fire Sentinel FSXPBB, 72 Hours Fire Sentinel FSXPBBVB, 24 Hours |
| FUSES: | 3A @ 250V, 2AG Slo-Blo Type |
| INITIATING DEVICE: | Maximum line impedance 20 ohm; Maximum current not to exceed .010A.; Maximum voltage 24Vdc |
| AUXILIARY POWER: | 24Vdc @ .5A Maximum |
| COMMON ALARM AND TROUBLE RELAYS: (MAX. CONTACT RATING) | .5A 125Vac 60Hz 1A 24Vdc Resistive |
MECHANICAL SPECIFICATIONS
| LOAD RATING: | Support and Release 40 lbs. Max. |
|---|
| PHYSICAL DIMENSIONS: | 9.7" x 7.5" x 5" (h x w x d) |
| WEIGHT: (INCLUDING BATTERIES) | Approximately 18 lbs. |
PREPARATION
It is imperative that the wall or mounting surface provide adequate support for the release device.
Refer to the door manufacturer's recommendations for use of this product with specific door being utilized. Use only hardware approved or recognized by the appropriate testing and listing agencies in conjunction with the installation of this product.
Additional items may be required to complete the installation:
- Concrete anchors or fasteners
- Sash chain or 1/16 cable
- Eyebolts-hook
- Fuse links
- Turnbuckles
- Smoke detectors (up to 4 may be installed with this device)
Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices shall be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay.
Diagram Description: This diagram illustrates the components of a fire door release system. A rolling fire door is shown on the right. Above it, the 'Releasing Unit' is mounted. A 'Chain End Link' connects the releasing unit to a 'Chain' that goes down to the fire door. An 'Eyebolt' is shown connected to 'Fuse Links', which are in turn connected to a 'Turnbuckle'. The turnbuckle is part of the chain system. A 'Smoke Detector' is positioned near the eyebolt. An 'Annunciator' is located below the fire door.
WIRING
▲ ▲ WARNING
To reduce the risk of SEVERE INJURY or DEATH:
- ALL electrical connections MUST be made by a qualified individual.
- Disconnect power at the fuse box BEFORE proceeding. Release device MUST be properly grounded and connected in accordance with local electrical codes.
- Installation of ALL wiring and connections, including Class 1 and Class 2 circuits, shall be performed in accordance with, but not limited to, the latest NFPA, UL and N.E.C. standards and codes. In addition, ALL installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods.
- ALL power wiring should be on a dedicated circuit and well protected. The location of the power disconnect should be visible and clearly labeled.
- ALL power and control wiring MUST be run in separate conduit.
- 120Vac should ONLY be attached to the 3-position terminal block mounted within the enclosure.
- DO NOT disconnect battery or remove battery fuse while unit is under power, the door will drop.
CAUTION
To prevent DAMAGE to the circuit board, ALL connections from terminals 3 through 16 MUST be dry contact type.
WIRING INSTRUCTIONS
Verify wiring configuration with that recommended by door manufacturer for use of this product with specific door and accessories being utilized. 18-gauge wire is recommended.
- Turn off power supply sources for the release device as well as the door operator, if applicable, before beginning.
- Verify voltage rating of release device to power source being utilized. Voltage is indicated on the side of the unit. Verify that power is disconnected before proceeding.
- When powering the device from 120Vac line voltage, locate the 3-position terminal block mounted within the device enclosure. Connect 120Vac (single phase) power source inputs to terminals L1 (line) and L2 (neutral) of the terminal block (Figure 1). The third position is used for earth ground.
- When powering the device from 24Vac or 24Vdc power, connect to terminal board positions 1 and 2 (Figure 2). Observe proper polarity. 24Vdc power input from an approved UL 1481 regulated power supply with battery backup may be used in lieu of direct line voltage.
- Do not connect line power or battery until all field wiring is complete per the following pages. The battery provides backup power in the event of a loss of line voltage and prevents the release of the fusible link assembly and the resulting door closure. A pulsing sounder occurs when the battery is disconnected or when replacement is required. The battery also provides power to the various ancillary devices (i.e., smoke detectors, horn/strobes, etc.).
Figure 1: An internal view of the release device showing the main circuit board and terminal blocks. A 'Mechanical Reset Plunger' is at the top. A 'Power Strip' is visible. Connections for 'Ground', 'L2', and 'L1' are shown on a 3-position terminal block. An 'Option DIP Switch' is also indicated.
Figure 2: A diagram illustrating the 24Vac or 24Vdc power input connections. Terminals 1 (+) and 2 (-) are shown, indicating where 24Vac or 24Vdc from a line voltage or an approved UL 1481 Regulated Power Supply with Battery Backup should be connected.
WIRE ROUTING
Diagram Description: An open view of the release device enclosure showing the routing of different wiring types. A 'Mechanical Reset Plunger' is at the top. A 'Power Strip' is visible. 'High Voltage Wiring' is shown connected to L1 and L2 terminals. 'Low Voltage Wiring' is routed through a grommet. 'Annunciator Wiring with Sleeve' and 'Voice Board Wiring' are also shown routed through designated openings, illustrating the separation of different voltage wires within the enclosure.
WIRING DIAGRAM
Diagram Description: A comprehensive wiring schematic for the Fire Sentinel release device. Key components include:
- Solenoid: Connected to the main circuit board.
- Battery: A 12V, 4.5 AHr battery with a 2 Amp maximum current fuse (F1: 3 Amp, 250 V, 3AG Slo-Blo) connected to the board.
- Input Power: Options for 120 VAC (Hot, Neutral, Ground) and +24V AC/DC.
- Auxiliary Common Relay Connections: Terminals for Trouble NO, Trouble Com, Trouble NC, Alarm NO, Alarm Com, Alarm NC.
- 2-Wire Detector Initiation Loop (1) (3): Terminals with connections for In/Out, requiring a 10 kOhm EOL Resistor between 5 & 6 if unused.
- Normally Closed Initiation Loop (1) (3): Terminals with connections for In/Out, requiring a jumper between 3 & 4 if unused, and external power.
- N.O. Closed Door Proximity Switch (2) (optional): Terminals for NC and COM.
- Annunciator Loop (4): Terminals for +Horn, Horn, +Strobe, Strobe, requiring a 10 kOhm EOL resistor between 9 & 10 if unused.
- Speaker - Voice board model only: Connections for + Speaker and Speaker.
Notes on the diagram specify:
- Batteries should be replaced every 2 years.
- Field wiring should consist of 22-18 AGW wiring.
- Use only 250Vac, 3 Amp, 3 AG, Slo-Blo fuses.
- Supervised, power limited circuit, 20 Ohm maximum line impedance.
- Unsupervised power limited circuit, 20 Ohm maximum line impedance.
- Maximum of 4 Class B Style A detectors.
- Maximum of 2 Class B Style W notification appliances. 0.5 Amp at 24 Vdc maximum. Supervised non-power limited circuit.
CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES
▲ WARNING
To prevent possible SERIOUS INJURY or DEATH:
- End-of-line devices MUST be installed for supervision of electrical power to 4-wire smoke detector.
- DO NOT install this device on a motorized door without an electric safety edge.
A maximum of 4 smoke detectors may be installed with this device. Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices must be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay.
NOTE: For low voltage wiring #18 AWG is recommended.
Normally Open "2-Wire,” Class B Style A Initiating Devices
Connect wiring from N/O initiating device loop to positions 3 and 4. Place the supervisory resistor (10k ohm @ 1/2 watt) contained within the accessory pack. (Figure 3). Observe proper polarity, 3 (+), 4 (-) when attaching to the release device's terminal board. NOTE: Make certain that the factory-installed jumper between terminal positions 5 and 6 remains in place. This option is a supervised, current-limited circuit.
Figure 3: Diagram showing connections for a Normally Open "2-Wire" Class B Style A Initiating Device. 24Vdc Power from Terminal Strip connects to terminals 3 (+) and 4 (-). A 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) is connected across the input. This method is for LM2W-B, LM2WT-B, or other 2-wire 24Vdc smoke detectors.
OR
Normally Open “4-Wire,” Class B Style A Initiating Devices
Connect wiring from N/O 4-Wire initiating device loop to positions 3 and 4, making sure an end-of-line supervisory resistor (10k ohm @ 1/2 watt) is installed as shown in Figure 4 or 5, depending upon the type of smoke detector being used. Observe proper polarity, 3 (+), 4 (−) when attaching to the release device's terminal board. NOTE: Make certain that the factory-installed jumper between terminal positions 5 and 6 remains in place. This option is a supervised, current-limited circuit.
Figure 4: Diagram showing connections for a Normally Open "4-Wire" Class B Style A Initiating Device. Power from Control Panel connects to terminals 3 (+) and 4 (-). An LMEOLR1224 12/24 Vdc EOL Relay and a 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) are shown in the circuit. This method is for LM4W-B, LM4WT-B, or other N/O 4-wire smoke detectors.
Figure 5: Diagram showing an alternative connection method for a Normally Open "4-Wire" Class B Style A Initiating Device. Power from Control Panel connects to terminals 3 (+) and 4 (-). An LMEOLR1224 12/24 Vdc EOL Relay and a 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) are shown in the circuit. This method is for LM1424, LM1412, or other N/O 4-wire smoke detectors.
OR
Normally Closed “4-Wire,” Class B Style A Initiating Devices
After removing the factory-installed jumper between terminal positions 5 and 6, connect wiring from N/C 4-Wire initiating device loop to positions 5 and 6 (Figure 6). This option is a supervised, current-limited circuit. NOTE: Make certain that the factory-installed resistor between positions 3 and 4 remains in place.
NOTE: End-of-line devices must be installed adjacent and after the last initiating device. Initiating device loops are supervised and cannot be direct series or paralleled between multiple release devices or shared with other alarm equipment. For proper wiring configurations from multiple smoke detectors or signaling for simultaneous closure on multiple doors, call technical support, 1-800-929-2553. Incorrect wiring between devices may cause damage to the release control circuit and void warranty.
Figure 6: Diagram showing connections for a Normally Closed "4-Wire" Class B Style A Initiating Device. Power from Control Panel connects to terminals 5 (+) and 6 (-). N/C (Normally Closed) contacts are shown, with a 'Purple' wire connection. An LMEOLR1224 12/24 Vdc EOL Relay is part of the circuit. This figure shows a generic version of a N/C 4-wire smoke detector.
IMPORTANT: When using 4-wire smoke detectors with this device, the smoke detectors must be powered from a source other than the release device, such as an approved UL 1481 regulated power supply providing battery backup support.
OR
Relay Module Installation
In lieu of smoke detectors, the release device may be put into alarm by the fire alarm control panel. Most commonly, a relay module is used as an interface between the fire alarm control panel and the release device. The relay module must provide Form C dry contacts for connection to the appropriate terminals on the release device (Figure 7).
NOTE: When choosing a relay module to activate the release device in an alarm condition, always select one that provides Form C dry contact relays. Do not use any relay module providing or passing any (control) voltage through the contacts into the release device. The passage of voltage through such a relay module into the release device will cause problems with the operation of the device and may damage the device's terminals and/or circuit board.
Figure 7: Diagram showing Relay Module connections. A 'Relay Module' has 'Common' and 'Normally Closed' contacts. 'Red' wire connects to 'Common' and 'Black' wire connects to 'Normally Closed' on the 'Fire Alarm Control Panel'. These connections are made to terminals 5 and 6 on the release device's terminal strip.
OPTIONAL CONNECTIONS
CLOSE DOOR DETECTION OPTION
Connect wiring from N/O electrical loop, using a proximity switch or other similar device with dry contacts, to 7 and 8 (Figure 8). The switch should be placed to engage when the door is in the closed position and so that it will toggle states from its N/O condition (switch closed when door is closed) to a closed condition indicating that the door edge has made contact with desired down position. When the switch is closed by contact from the door, the release device will not activate on alarm, thereby eliminating nuisance gravity drops through the inadvertent release of the fusible link assembly. This option only works as long as power is available to unit. Fail-safe operation is maintained under all operating conditions, and if power is not available to the unit, the fusible link assembly will be released. This is a power-limited, unsupervised circuit. This proximity switch must be mounted in the same room as the release device.
Figure 8: Diagram showing connections for the Close Door Detection Option. Terminal 7 connects to 'Attach to Common on N/O Proximity Switch' and Terminal 8 connects to 'Attach to N/O Position on Proximity Switch'. A 'Proximity Switch Part No. LM56A' is indicated.
RELAY AND TROUBLE OUTPUTS OPTION
Connect wiring from the Alarm Relay Outputs (#11 N/C or #13 N/O and #14 Common) to the appropriate inputs on the fire alarm control panel to provide a signal at the panel when the release device is in an alarm state. Connect wiring from the Trouble Relay Outputs (#14 N/C or #16 N/O and #15 Common) to the appropriate inputs on the fire alarm control panel to provide a signal at the panel that the release device is in a trouble state (Figure 9). If these features are desired, coordinate the interconnection between the Release Device and the Fire Alarm Control Panel with the fire alarm installer.
Figure 9: Diagram showing Relay and Trouble Output connections. Terminals 11, 12, 13 are for 'N/C Alarm Relay Output', 'Common', and 'N/O Alarm Relay Output' respectively. Terminals 14, 15, 16 are for 'N/C Trouble Output', 'Trouble Common', and 'N/O Trouble Output' respectively. These connections are made to the Fire Alarm Panel as required by project specifications and Authority Having Jurisdiction.
ANNUNCIATOR OPTION
To power one or two (maximum) horn/strobes or similar annunciators, connect wiring to terminals 9 and 10 (Figure 10). Route wires through the non-conductive sleeving (provided) covering any exposed bare wires. Maximum distance of wire run within conduit not to exceed 20' total This is a supervised, non power-limited circuit.
NOTE: If installing two visual annunciators, they must be installed on opposite sides of wall.
Figure 10: Diagram showing Annunciator connections. Terminals 9 and 10 are connected to 'Horn/Strobe' units. A 'Non-conductive sleeve' is indicated for wire routing. A 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) is shown in the circuit. The diagram notes that a maximum of two annunciators may be installed.
VOICE BOARD OPTION
The voice board provides one of two verbal warnings that the fire door is closing. Typically, depending on the length of the delay chosen on the release device, a warning tone will occur prior to the message, which is approximately 10 seconds in length (for example, a 20 second delay setting on the release device will result in a 10 second warning tone followed by the verbal warning message). There are two messages that may be selected:
- Message 1: Warning tone followed by the message, “Warning! An emergency condition exists and this fire door is about to close; please remove any obstructions from its path and stand clear."
- Message 2: Warning tone followed by the message, “Warning! This fire door will close in 10 seconds... 5 seconds... the fire door is now closing; please remove any obstructions from its path and stand clear."
The release device has an 4-position DIP Switch mounted on the circuit board, and the switch at position #3 permits selection of either message. In the “ON” position, Message 1 is activated; in the "OFF" position, Message 2 is activated.
The voice board can drive up to two 70.7V speakers (Model LM8SP) or speaker inputs to speaker strobes (Model LMPSTR2475ADA). Maximum delivered power is 5 watts.
A potentiometer (VR1) is mounted on the board and rotation counterclockwise increases the volume (clockwise to decrease volume) (Figure 11).
Figure 11: Diagram showing the 'Volume Control' potentiometer (CCW for Max volume) and 'Wire to Speaker' connections on the voice board.
DIP SWITCH SELECTION
The release device will provide a factory default delay of 10 seconds (to minimize nuisance alarms) before releasing the fusible link chain upon alarm or power loss. A 4-position DIP Switch found on the PC board within the release device can be used to adjust the length of the delay to one of four preset delays. The optional delay settings are as follows:
Figure 12: Diagram of a 4-position DIP Switch. The default setting shows all switches in the OFF position, corresponding to a 10-second delay. NOTE: Position 4 is unused and should remain in the OFF position. Position 3 is used to select one of the two available voice messages.
| Delay Setting | Switch Position |
|---|
| 1 | 2 | 3 | 4 |
|---|
| 10 Seconds | Off | Off | Off | Off |
| 20 Seconds | Off | On | Off | Off |
| 30 Seconds | On | Off | Off | Off |
| 60 Seconds | On | On | Off | Off |
NOTE: Set all DIP switch options before applying power to the system.
MAINTENANCE
▲ ▲ WARNING
To avoid SERIOUS PERSONAL INJURY or DEATH from electrocution, disconnect ALL electric and battery power BEFORE performing ANY maintenance.
MAINTENANCE REQUIREMENTS
The release device has no scheduled maintenance requirements. The unit has been designed and tested for use in dry, indoor locations. Testing of the unit at least once every 90 days is recommended, but test intervals shall ultimately be subject to criteria established by the Authority Having Jurisdiction (AHJ).
FUSE REPLACEMENT PROCEDURE AND REPAIR PARTS
One serviceable fuse, a 3 Amp, 3AG, slo-blo fuse, is required for proper operation and protection of the circuit board. The release device is shipped with the fuse in place and two replacement fuses are provided in a separate parts bag. The fuse is located on the circuit board near the battery cable connection.
Refer to page 13 for replacement parts.
BATTERY MAINTENANCE/TESTING
No maintenance or testing is required for the battery. An audible warning tone, generated by the trouble annunciator mounted to the side of the release device, will sound when the battery is approaching the minimum operating threshold. This indicates the need to replace the battery.
Refer to page 13 for replacement parts.
BATTERY DISPOSAL
Spent batteries must be treated as hazardous waste and disposed of in accordance with State, Local and Federal Regulations.
Figure 1: A diagram showing the front of the release device with a 'Mechanical Reset Plunger' on top and an 'End Link' extending from the side. The 'Electronic Reset Button' and 'Test Button' are located on the bottom of the release device, along with three LEDs: Red (Line Power Present), Green (Battery Backup Power Present), and Yellow (Close Door Detection/Release Disabled).
ENCLOSURE MOUNTED LEDS STATUS INDICATORS
| LED Label | LED Color | Description | Action Required |
|---|
| Battery | Green | If the Green LED is lit, then the battery is connected properly and charged above the minimum acceptable level. | If the LED does not light, check that the leads are connected to the battery as shown on the wiring diagram on page 6 of this manual. |
| Disable | Yellow | The Yellow LED will light when the door reaches the close limit and activates a proximity switch attached to terminal positions 7 and 8 on the release device. This configuration results in the device not releasing the fusible link assembly in alarm or power loss situations and should only be used when the fire door is kept in a constant closed position. | If the LED does not light when the door reaches the close limit and activates the proximity switch, then check that the proximity switch has been activated and that the switch is set to normally open (N.O.). Check to make certain that the switch is attached to terminal positions 7 and 8 on the release device. |
| Power | Red | If the Red LED is lit, then the line power is connected and switched "on." | If the LED does not light when power is applied, check that power is connected as described in the installation manual electrical connections. |