OVERHEAD DOOR

TRADE MARK

the original since 1921

Overhead Door Corp.
Pennsylvania Division
23 Industrial Park Road
Lewistown, PA 17044
Phone 800-929-2553
717-248-0131
Fax 717-248-6447

OWNER'S MANUAL

MODELS

FIRE SENTINEL FSXPBB

FIRE SENTINEL FSXPBBVB

EXTENDED PERFORMANCE RELEASE DEVICE

Diagram Description: A schematic illustration shows a fire door system. On the left, a rolling fire door is depicted with a release unit mounted above it. A chain extends from the release unit to the fire door. An eyebolt is shown near the release unit, connected to a fuse link system. The fuse links are connected to a turnbuckle, which is part of the chain system. A smoke detector is positioned near the release unit, and an annunciator is shown below the fire door. On the right, a detailed inset shows the Fire Sentinel release device itself, a rectangular enclosure with a mechanical reset plunger on top and connection points.

The UL (Underwriters Laboratories) and ULC (Underwriters Laboratories of Canada) certification marks are visible.

TABLE OF CONTENTS

▲ WARNING

Mechanical

▲ WARNING

Electrical

CAUTION

When you see these Safety Symbols and Signal Words on the following pages, they will alert you to the possibility of serious injury or death if you do not comply with the warnings that accompany them. The hazard may come from something mechanical or from electric shock. Read the warnings carefully.

When you see this Signal Word on the following pages, it will alert you to the possibility of damage to your door and/or the door operator if you do not comply with the cautionary statements that accompany it. Read them carefully.

IMPORTANT NOTES:

  • BEFORE attempting to install, operate or maintain the release device, you must read and fully understand this manual and follow all safety instructions.
  • DO NOT attempt repair or service of your release device unless you are an Authorized Service Technician.

INTRODUCTION

  • General Description
  • Agency Requirements
  • Specifications
  • Preparation

INSTALLATION

  • Important Installation Warnings
  • Mount the Release Device

WIRING

  • Wiring Instructions
  • Wire Routing
  • Wiring Diagram
  • Connections of Initiating Devices and Accessories
  • Optional Connections

TESTING

  • Test Procedures

TROUBLESHOOTING

  • Operational Checklist

MAINTENANCE

  • Maintenance Requirements
  • Enclosure Mounted LEDs Status Indicators

ACCESSORIES AND REPAIR PARTS

APPENDIX

INTRODUCTION

GENERAL DESCRIPTION

The Fire Sentinel FSXPBB and Fire Sentinel FSXPBBVB Release Devices are UL/ULC listed normally energized fail-safe devices designed for use on rolling doors, single-slide, and center-parting level and inclined track doors. All models are normally energized fail-safe releasing devices incorporating state-of-the-art electronic control circuitry. The release devices respond to emergency conditions generated from an automatic initiating device and are used in conjunction with a temperature fuse link system.

The release device can be powered from 120Vac, 24 Vac, or 24Vdc line voltage or 24Vdc received from an approved UL 1481 regulated power supply with battery backup. The devices can be activated via a smoke detector or an alarm relay from the panel's Form C dry contact relay. The release device features include a 10-, 20-, 30- or 60-second delay on alarm, closed door detection capabilities, Form C relay outputs for the transmission of alarm and trouble signals transmitted to the fire alarm control panel, an audible trouble sounder, and diagnostic feedback LEDs.

The release device is provided with a battery management system that can provide 24Vdc power for up to four smoke detectors and two horn strobes, as well as provide battery backup for the release device and accessories. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications and used with fuse link systems.

AGENCY REQUIREMENTS

Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).

▲ WARNING

To prevent possible SERIOUS INJURY or DEATH:

  • DO NOT use this device without fuse links installed.
  • Test every 90 days to assure proper operation of release device.

SPECIFICATIONS

ELECTRICAL SPECIFICATIONS

VOLTAGE RATING:120Vac, 60Hz; 24Vac, 60Hz; 24Vdc
STANDBY CURRENT.06A, .3A, .2A
ALARM CURRENT.06A, .3A, .25A
BATTERY RATING:12V 4.5AH Sealed Lead Acid Battery, Maximum charge current .150Amps
BATTERY STANDBY TIME:Fire Sentinel FSXPBB, 72 Hours
Fire Sentinel FSXPBBVB, 24 Hours
FUSES:3A @ 250V, 2AG Slo-Blo Type
INITIATING DEVICE:Maximum line impedance 20 ohm; Maximum current not to exceed .010A.; Maximum voltage 24Vdc
AUXILIARY POWER:24Vdc @ .5A Maximum
COMMON ALARM AND TROUBLE RELAYS: (MAX. CONTACT RATING).5A 125Vac 60Hz
1A 24Vdc Resistive

MECHANICAL SPECIFICATIONS

LOAD RATING:Support and Release 40 lbs. Max.
PHYSICAL DIMENSIONS:9.7" x 7.5" x 5" (h x w x d)
WEIGHT: (INCLUDING BATTERIES)Approximately 18 lbs.

PREPARATION

It is imperative that the wall or mounting surface provide adequate support for the release device.

Refer to the door manufacturer's recommendations for use of this product with specific door being utilized. Use only hardware approved or recognized by the appropriate testing and listing agencies in conjunction with the installation of this product.

Additional items may be required to complete the installation:

  • Concrete anchors or fasteners
  • Sash chain or 1/16 cable
  • Eyebolts-hook
  • Fuse links
  • Turnbuckles
  • Smoke detectors (up to 4 may be installed with this device)

Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices shall be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay.

Diagram Description: This diagram illustrates the components of a fire door release system. A rolling fire door is shown on the right. Above it, the 'Releasing Unit' is mounted. A 'Chain End Link' connects the releasing unit to a 'Chain' that goes down to the fire door. An 'Eyebolt' is shown connected to 'Fuse Links', which are in turn connected to a 'Turnbuckle'. The turnbuckle is part of the chain system. A 'Smoke Detector' is positioned near the eyebolt. An 'Annunciator' is located below the fire door.

INSTALLATION

IMPORTANT INSTALLATION INSTRUCTIONS

▲ ▲ WARNING

To reduce the risk of SEVERE INJURY or DEATH:

  1. READ AND FOLLOW ALL INSTALLATION WARNINGS AND INSTRUCTIONS.
  2. NEVER connect release device to power source until instructed to do so.
  3. DO NOT install this device on a motorized door without an electric safety edge.
  4. DO NOT use this device without fuse links installed.
  5. Concrete anchors MUST be used if mounting release device into masonry.
  6. DO NOT exceed maximum pull rating of 40 lbs. on releasing device.

Classification:

Releasing device as defined by Underwriters Laboratories.

Installation Requirements:

Intended for "Indoor Dry” locations; all wiring must be performed in accordance with the most current version of NFPA 72 - National Fire Alarm Code and the National Electric Code.

Figure 1: A diagram showing the front of the release device with a 'Mechanical Reset Plunger' on top and an 'End Link' extending from the side. The 'Electronic Reset Button' and 'Test Button' are located on the bottom of the release device, along with three LEDs: Red (Line Power Present), Green (Battery Backup Power Present), and Yellow (Close Door Detection/Release Disabled).

MOUNT THE RELEASE DEVICE

Installation procedures vary according to door types. Refer to door manufacturer's recommendation that applies to your door.

  1. Mount the release device on a vertical surface with chain end link exiting side of enclosure.
  2. Secure the release device enclosure with fasteners (#10 is the minimum size recommended). If installing in masonry, use concrete anchors (not provided).
  3. Install hardware (sash chain or 1/16 cable, eyebolts-hook, fuse links, turnbuckles—not provided) according to door manufacturer's recommendations. NOTE: The end link direction of pull must be perpendicular to the side of the release device enclosure. Install an eyebolt a minimum distance of 12" from the release device to adequately redirect sash chain pull.
  4. Install end link by pressing mechanical reset to allow insertion of end link. Push end link completely in and release mechanical reset to latch end link.
  5. Remove sash chain or cable slack by adjusting turnbuckle.

Diagram Description: This diagram illustrates the components of a fire door release system, similar to the previous one, but with more detail on the release unit's connection. A rolling fire door is shown on the right. Above it, the 'Releasing Unit' is mounted, with a 'Mechanical Reset Plunger' on its top. A 'Chain End Link' connects the releasing unit to a 'Chain' that goes down to the fire door. An 'Eyebolt' is shown connected to 'Fuse Links', which are in turn connected to a 'Turnbuckle'. The turnbuckle is part of the chain system. A 'Smoke Detector' is positioned near the eyebolt. An 'Annunciator' is located below the fire door. The diagram also shows the 'End Link' extending from the side of the release unit.

WIRING

▲ ▲ WARNING

To reduce the risk of SEVERE INJURY or DEATH:

  • ALL electrical connections MUST be made by a qualified individual.
  • Disconnect power at the fuse box BEFORE proceeding. Release device MUST be properly grounded and connected in accordance with local electrical codes.
  • Installation of ALL wiring and connections, including Class 1 and Class 2 circuits, shall be performed in accordance with, but not limited to, the latest NFPA, UL and N.E.C. standards and codes. In addition, ALL installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods.
  • ALL power wiring should be on a dedicated circuit and well protected. The location of the power disconnect should be visible and clearly labeled.
  • ALL power and control wiring MUST be run in separate conduit.
  • 120Vac should ONLY be attached to the 3-position terminal block mounted within the enclosure.
  • DO NOT disconnect battery or remove battery fuse while unit is under power, the door will drop.

CAUTION

To prevent DAMAGE to the circuit board, ALL connections from terminals 3 through 16 MUST be dry contact type.

WIRING INSTRUCTIONS

Verify wiring configuration with that recommended by door manufacturer for use of this product with specific door and accessories being utilized. 18-gauge wire is recommended.

  1. Turn off power supply sources for the release device as well as the door operator, if applicable, before beginning.
  2. Verify voltage rating of release device to power source being utilized. Voltage is indicated on the side of the unit. Verify that power is disconnected before proceeding.
  3. When powering the device from 120Vac line voltage, locate the 3-position terminal block mounted within the device enclosure. Connect 120Vac (single phase) power source inputs to terminals L1 (line) and L2 (neutral) of the terminal block (Figure 1). The third position is used for earth ground.
  4. When powering the device from 24Vac or 24Vdc power, connect to terminal board positions 1 and 2 (Figure 2). Observe proper polarity. 24Vdc power input from an approved UL 1481 regulated power supply with battery backup may be used in lieu of direct line voltage.
  5. Do not connect line power or battery until all field wiring is complete per the following pages. The battery provides backup power in the event of a loss of line voltage and prevents the release of the fusible link assembly and the resulting door closure. A pulsing sounder occurs when the battery is disconnected or when replacement is required. The battery also provides power to the various ancillary devices (i.e., smoke detectors, horn/strobes, etc.).

Figure 1: An internal view of the release device showing the main circuit board and terminal blocks. A 'Mechanical Reset Plunger' is at the top. A 'Power Strip' is visible. Connections for 'Ground', 'L2', and 'L1' are shown on a 3-position terminal block. An 'Option DIP Switch' is also indicated.

Figure 2: A diagram illustrating the 24Vac or 24Vdc power input connections. Terminals 1 (+) and 2 (-) are shown, indicating where 24Vac or 24Vdc from a line voltage or an approved UL 1481 Regulated Power Supply with Battery Backup should be connected.

WIRE ROUTING

Diagram Description: An open view of the release device enclosure showing the routing of different wiring types. A 'Mechanical Reset Plunger' is at the top. A 'Power Strip' is visible. 'High Voltage Wiring' is shown connected to L1 and L2 terminals. 'Low Voltage Wiring' is routed through a grommet. 'Annunciator Wiring with Sleeve' and 'Voice Board Wiring' are also shown routed through designated openings, illustrating the separation of different voltage wires within the enclosure.

WIRING DIAGRAM

Diagram Description: A comprehensive wiring schematic for the Fire Sentinel release device. Key components include:

  • Solenoid: Connected to the main circuit board.
  • Battery: A 12V, 4.5 AHr battery with a 2 Amp maximum current fuse (F1: 3 Amp, 250 V, 3AG Slo-Blo) connected to the board.
  • Input Power: Options for 120 VAC (Hot, Neutral, Ground) and +24V AC/DC.
  • Auxiliary Common Relay Connections: Terminals for Trouble NO, Trouble Com, Trouble NC, Alarm NO, Alarm Com, Alarm NC.
  • 2-Wire Detector Initiation Loop (1) (3): Terminals with connections for In/Out, requiring a 10 kOhm EOL Resistor between 5 & 6 if unused.
  • Normally Closed Initiation Loop (1) (3): Terminals with connections for In/Out, requiring a jumper between 3 & 4 if unused, and external power.
  • N.O. Closed Door Proximity Switch (2) (optional): Terminals for NC and COM.
  • Annunciator Loop (4): Terminals for +Horn, Horn, +Strobe, Strobe, requiring a 10 kOhm EOL resistor between 9 & 10 if unused.
  • Speaker - Voice board model only: Connections for + Speaker and Speaker.

Notes on the diagram specify:

  • Batteries should be replaced every 2 years.
  • Field wiring should consist of 22-18 AGW wiring.
  • Use only 250Vac, 3 Amp, 3 AG, Slo-Blo fuses.
  • Supervised, power limited circuit, 20 Ohm maximum line impedance.
  • Unsupervised power limited circuit, 20 Ohm maximum line impedance.
  • Maximum of 4 Class B Style A detectors.
  • Maximum of 2 Class B Style W notification appliances. 0.5 Amp at 24 Vdc maximum. Supervised non-power limited circuit.

CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES

▲ WARNING

To prevent possible SERIOUS INJURY or DEATH:

  • End-of-line devices MUST be installed for supervision of electrical power to 4-wire smoke detector.
  • DO NOT install this device on a motorized door without an electric safety edge.

A maximum of 4 smoke detectors may be installed with this device. Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices must be installed for supervision of electrical power to 4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a UL/ULC listed end-of-line relay.

NOTE: For low voltage wiring #18 AWG is recommended.

Normally Open "2-Wire,” Class B Style A Initiating Devices

Connect wiring from N/O initiating device loop to positions 3 and 4. Place the supervisory resistor (10k ohm @ 1/2 watt) contained within the accessory pack. (Figure 3). Observe proper polarity, 3 (+), 4 (-) when attaching to the release device's terminal board. NOTE: Make certain that the factory-installed jumper between terminal positions 5 and 6 remains in place. This option is a supervised, current-limited circuit.

Figure 3: Diagram showing connections for a Normally Open "2-Wire" Class B Style A Initiating Device. 24Vdc Power from Terminal Strip connects to terminals 3 (+) and 4 (-). A 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) is connected across the input. This method is for LM2W-B, LM2WT-B, or other 2-wire 24Vdc smoke detectors.

OR

Normally Open “4-Wire,” Class B Style A Initiating Devices

Connect wiring from N/O 4-Wire initiating device loop to positions 3 and 4, making sure an end-of-line supervisory resistor (10k ohm @ 1/2 watt) is installed as shown in Figure 4 or 5, depending upon the type of smoke detector being used. Observe proper polarity, 3 (+), 4 (−) when attaching to the release device's terminal board. NOTE: Make certain that the factory-installed jumper between terminal positions 5 and 6 remains in place. This option is a supervised, current-limited circuit.

Figure 4: Diagram showing connections for a Normally Open "4-Wire" Class B Style A Initiating Device. Power from Control Panel connects to terminals 3 (+) and 4 (-). An LMEOLR1224 12/24 Vdc EOL Relay and a 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) are shown in the circuit. This method is for LM4W-B, LM4WT-B, or other N/O 4-wire smoke detectors.

Figure 5: Diagram showing an alternative connection method for a Normally Open "4-Wire" Class B Style A Initiating Device. Power from Control Panel connects to terminals 3 (+) and 4 (-). An LMEOLR1224 12/24 Vdc EOL Relay and a 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) are shown in the circuit. This method is for LM1424, LM1412, or other N/O 4-wire smoke detectors.

OR

Normally Closed “4-Wire,” Class B Style A Initiating Devices

After removing the factory-installed jumper between terminal positions 5 and 6, connect wiring from N/C 4-Wire initiating device loop to positions 5 and 6 (Figure 6). This option is a supervised, current-limited circuit. NOTE: Make certain that the factory-installed resistor between positions 3 and 4 remains in place.

NOTE: End-of-line devices must be installed adjacent and after the last initiating device. Initiating device loops are supervised and cannot be direct series or paralleled between multiple release devices or shared with other alarm equipment. For proper wiring configurations from multiple smoke detectors or signaling for simultaneous closure on multiple doors, call technical support, 1-800-929-2553. Incorrect wiring between devices may cause damage to the release control circuit and void warranty.

Figure 6: Diagram showing connections for a Normally Closed "4-Wire" Class B Style A Initiating Device. Power from Control Panel connects to terminals 5 (+) and 6 (-). N/C (Normally Closed) contacts are shown, with a 'Purple' wire connection. An LMEOLR1224 12/24 Vdc EOL Relay is part of the circuit. This figure shows a generic version of a N/C 4-wire smoke detector.

IMPORTANT: When using 4-wire smoke detectors with this device, the smoke detectors must be powered from a source other than the release device, such as an approved UL 1481 regulated power supply providing battery backup support.

OR

Relay Module Installation

In lieu of smoke detectors, the release device may be put into alarm by the fire alarm control panel. Most commonly, a relay module is used as an interface between the fire alarm control panel and the release device. The relay module must provide Form C dry contacts for connection to the appropriate terminals on the release device (Figure 7).

NOTE: When choosing a relay module to activate the release device in an alarm condition, always select one that provides Form C dry contact relays. Do not use any relay module providing or passing any (control) voltage through the contacts into the release device. The passage of voltage through such a relay module into the release device will cause problems with the operation of the device and may damage the device's terminals and/or circuit board.

Figure 7: Diagram showing Relay Module connections. A 'Relay Module' has 'Common' and 'Normally Closed' contacts. 'Red' wire connects to 'Common' and 'Black' wire connects to 'Normally Closed' on the 'Fire Alarm Control Panel'. These connections are made to terminals 5 and 6 on the release device's terminal strip.

OPTIONAL CONNECTIONS

CLOSE DOOR DETECTION OPTION

Connect wiring from N/O electrical loop, using a proximity switch or other similar device with dry contacts, to 7 and 8 (Figure 8). The switch should be placed to engage when the door is in the closed position and so that it will toggle states from its N/O condition (switch closed when door is closed) to a closed condition indicating that the door edge has made contact with desired down position. When the switch is closed by contact from the door, the release device will not activate on alarm, thereby eliminating nuisance gravity drops through the inadvertent release of the fusible link assembly. This option only works as long as power is available to unit. Fail-safe operation is maintained under all operating conditions, and if power is not available to the unit, the fusible link assembly will be released. This is a power-limited, unsupervised circuit. This proximity switch must be mounted in the same room as the release device.

Figure 8: Diagram showing connections for the Close Door Detection Option. Terminal 7 connects to 'Attach to Common on N/O Proximity Switch' and Terminal 8 connects to 'Attach to N/O Position on Proximity Switch'. A 'Proximity Switch Part No. LM56A' is indicated.

RELAY AND TROUBLE OUTPUTS OPTION

Connect wiring from the Alarm Relay Outputs (#11 N/C or #13 N/O and #14 Common) to the appropriate inputs on the fire alarm control panel to provide a signal at the panel when the release device is in an alarm state. Connect wiring from the Trouble Relay Outputs (#14 N/C or #16 N/O and #15 Common) to the appropriate inputs on the fire alarm control panel to provide a signal at the panel that the release device is in a trouble state (Figure 9). If these features are desired, coordinate the interconnection between the Release Device and the Fire Alarm Control Panel with the fire alarm installer.

Figure 9: Diagram showing Relay and Trouble Output connections. Terminals 11, 12, 13 are for 'N/C Alarm Relay Output', 'Common', and 'N/O Alarm Relay Output' respectively. Terminals 14, 15, 16 are for 'N/C Trouble Output', 'Trouble Common', and 'N/O Trouble Output' respectively. These connections are made to the Fire Alarm Panel as required by project specifications and Authority Having Jurisdiction.

ANNUNCIATOR OPTION

To power one or two (maximum) horn/strobes or similar annunciators, connect wiring to terminals 9 and 10 (Figure 10). Route wires through the non-conductive sleeving (provided) covering any exposed bare wires. Maximum distance of wire run within conduit not to exceed 20' total This is a supervised, non power-limited circuit.

NOTE: If installing two visual annunciators, they must be installed on opposite sides of wall.

Figure 10: Diagram showing Annunciator connections. Terminals 9 and 10 are connected to 'Horn/Strobe' units. A 'Non-conductive sleeve' is indicated for wire routing. A 10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10) is shown in the circuit. The diagram notes that a maximum of two annunciators may be installed.

VOICE BOARD OPTION

The voice board provides one of two verbal warnings that the fire door is closing. Typically, depending on the length of the delay chosen on the release device, a warning tone will occur prior to the message, which is approximately 10 seconds in length (for example, a 20 second delay setting on the release device will result in a 10 second warning tone followed by the verbal warning message). There are two messages that may be selected:

  • Message 1: Warning tone followed by the message, “Warning! An emergency condition exists and this fire door is about to close; please remove any obstructions from its path and stand clear."
  • Message 2: Warning tone followed by the message, “Warning! This fire door will close in 10 seconds... 5 seconds... the fire door is now closing; please remove any obstructions from its path and stand clear."

The release device has an 4-position DIP Switch mounted on the circuit board, and the switch at position #3 permits selection of either message. In the “ON” position, Message 1 is activated; in the "OFF" position, Message 2 is activated.

The voice board can drive up to two 70.7V speakers (Model LM8SP) or speaker inputs to speaker strobes (Model LMPSTR2475ADA). Maximum delivered power is 5 watts.

A potentiometer (VR1) is mounted on the board and rotation counterclockwise increases the volume (clockwise to decrease volume) (Figure 11).

Figure 11: Diagram showing the 'Volume Control' potentiometer (CCW for Max volume) and 'Wire to Speaker' connections on the voice board.

DIP SWITCH SELECTION

The release device will provide a factory default delay of 10 seconds (to minimize nuisance alarms) before releasing the fusible link chain upon alarm or power loss. A 4-position DIP Switch found on the PC board within the release device can be used to adjust the length of the delay to one of four preset delays. The optional delay settings are as follows:

Figure 12: Diagram of a 4-position DIP Switch. The default setting shows all switches in the OFF position, corresponding to a 10-second delay. NOTE: Position 4 is unused and should remain in the OFF position. Position 3 is used to select one of the two available voice messages.

Delay SettingSwitch Position
1234
10 SecondsOffOffOffOff
20 SecondsOffOnOffOff
30 SecondsOnOffOffOff
60 SecondsOnOnOffOff
NOTE: Set all DIP switch options before applying power to the system.

TESTING

▲ WARNING

To prevent possible SERIOUS INJURY or DEATH:

  • Clear fire door opening and prohibit ALL traffic through door opening while testing.
  • Test every 90 days to assure proper operation of release device.

TEST PROCEDURES

TO BE PERFORMED BY FACTORY AUTHORIZED PERSONNEL ONLY! CLEAR FIRE DOOR OPENING AND PROHIBIT TRAFFIC THROUGH DOOR OPENING WHILE TESTING!

Testing does not affect normal operation of alarm system when connected to release device/control panel. Testing of the release device is independent of, and shall in no way be interpreted as an alternative method of, testing of a central fire alarm system, motorized operator and/or any other system component employed on the fire door or counter fire door installation. Complete testing and normal operation can only be accomplished with power applied to unit.

Door must be in open position with power applied to unit to begin testing. The following procedures describe testing of all options. Verify options ordered and installed with unit. All tests may not apply. Refer to Figure 1 for location of all the LEDs and switches mentioned in this section.

Figure 1: A diagram showing the front of the release device with a 'Mechanical Reset Plunger' on top and an 'End Link' extending from the side. The 'Electronic Reset Button' and 'Test Button' are located on the bottom of the release device, along with three LEDs: Red (Line Power Present), Green (Battery Backup Power Present), and Yellow (Close Door Detection/Release Disabled).

INITIAL POWER UP

  1. Connect black battery wire to the black terminal on the battery. Connect the red battery wire to the red terminal.
  2. Apply line power to the unit.
  3. Power LED (red) and battery LED (green) will be lit on the bottom of the release device.

MECHANICAL RELEASE

  1. Depress and continue to hold test button on side of release device. After the selected delay expires, the device will release the end link and allow door to drop. Release test button.
  2. Reset the door per door manufacturer's instructions. Raise door and then reset the release device by pushing downward on the mechanical reset button at the top of the device. Fully insert the end link through the side opening on the device and release the reset button in order to latch end link.

CLOSE DOOR DETECTION (OPTIONAL)

  1. Using the chain hoist or motor operator, lower the door to fully closed position.
  2. Verify that Close Door Detection LED (yellow) is lit indicating door closure. Depress and continue to hold test button on side of release device for 10 seconds. Close Door Detection logic will prohibit the release device from energizing and releasing the end link. Reset the test button.
  3. Raise door to fully open position.

SUSPENSION OF POWER

  1. Make sure door is in fully open position. Turn off all power to release device and disconnect battery. Immediately upon loss of power (line voltage and battery backup) to the release device, a mechanical release will be initiated.
  2. Reset the door per door manufacturer's instructions. Raise the door and then reset the release device by pushing downward on the mechanical reset button at the top of the device. Fully insert the end link through the side opening on the device and release the reset button in order to latch end link. Press the "Reset" button on the side of the device to reset the alarm loop.

After completing all tests, make sure the door is in its normal position (open or closed) and all power required for normal operation is restored to unit. The release device is designed to operate with power applied.

NOTE: Testing shall be performed and witnessed for proper operation.

TROUBLESHOOTING

OPERATIONAL CHECKLIST

POWER

Is the red LED, labeled “Power,” located on the bottom of the enclosure lit?

Is the Red LED Lit?
YesMove on.
NoCheck power connections at terminal board positions 1 and 2. Check voltage; voltage should be 24Vdc received from an approved UL 1481 regulated power supply.

CHECK THE ALARM

Are the alarm (smoke detection) inputs correct? If not, the release device will not release the fusible link assembly in a fire condition. Conversely, the release device will always release the fusible link assembly when powered or reset.

Are the Alarm Inputs correct?
YesMove on.
NoCheck that it is a dry contact input. There should not be any voltage on the alarm lines when they are disconnected from the unit. Check to see if it is tied into an addressable relay module of an alarm panel. At times, noise can be picked up from these modules.

CHECK THE CLOSE DOOR DETECTION

Is the Yellow LED on the bottom of the enclosure lit? If lit, the close limit is active and the device is disabled and will not release the tension on the door spring as the door is in the closed position, activating the proximity switch. If not lit, check wiring instructions in Figure 8.

CHECK THE BATTERY CONNECTIONS

Is the Green LED on the bottom of the enclosure lit? If so, the battery is connected properly. If the LED does not light, the battery is not functioning properly and a trouble sounder will annunciate. Check the following:

  1. Are the battery leads properly connected or do the leads have a defective connector?
  2. Do the battery connections observe correct polarity — Red (+) and Black (-)?
  3. Is the battery discharged? If so, allow 10 minutes for the battery management system to recharge the battery. If the sounder does not stop after this time, then the battery needs to be replaced. Refer to the “Replacement Parts and Accessories" section of this manual for ordering instructions.

Battery Performance Inconsistencies

Does the unit go into alarm and release the fusible link as soon as power is applied? If so, then check the wiring and connections on the smoke detector loop, focusing especially on the presence and the correct placement of the end-of-line resistor. Also, if N/O smoke detectors are being used, make certain that the jumper between positions 5 and 6 on the release device's terminal strip is in place.

CIRCUIT BOARD DIAGNOSTIC LEDS

View diagnostic LEDs present on the circuit board located behind the terminal board. Refer to the table below for the status LED indications.

LED LabelLED ColorDescription
N/O Detector TroubleYellow (LED 6)If lit, indicates a trouble condition (a short) within the N/O 2-wire (or 4-wire) smoke detector loop (emanating from terminal board positions 3 and 4), resulting from either incorrect wiring or incorrect placement of the end-of-line resistor, and the smoke detector loop is inactive. Refer to the Smoke Detector Installation section on pages 7 and 8 of this manual for correct wiring instructions.
N/O Detector AlarmRed (LED 5)If lit, indicates that the N/O 2-wire (or 4-wire) smoke detector loop (emanating from terminal board positions 3 and 4) is in alarm. When lit during testing, press the Auxiliary Reset Button at the bottom of the release device to reset the loop.
N/C Detector TroubleRed (LED 4)If lit, indicates an open circuit within the N/C 4-wire smoke detector loop (emanating from terminal board positions 5 and 6), resulting from either incorrect wiring or incorrect placement of the end-of-line relay or the detector(s) are in alarm. If in alarm, cycle power off and then on to the smoke detectors to reset, then depress the auxiliary reset button to reset the release device. Refer to the Smoke Detector Installation section on pages 7 and 8 of this manual for correct wiring instructions.
Close Door DetectionGreen (LED 2)If lit, indicates that the fire door or shutter is closed and activating the proximity switch. If not lit, refer to the Close Door Detection section of this manual for correct wiring instructions.
Annunciator TroubleYellow (LED 9)If lit, indicates a trouble condition (a short) within the annunciator loop (emanating from terminal board positions 9 and 10), resulting from either incorrect wiring or incorrect placement of the end-of-line resistor. Refer to the Annunciator section of this manual for correct wiring instructions.
Ground FaultYellow (LED 3)If lit, indicates that one of the ancillary devices/loops (smoke detector, annunciator, etc.) is not grounded properly, and a short to earth ground exists.

MAINTENANCE

▲ ▲ WARNING

To avoid SERIOUS PERSONAL INJURY or DEATH from electrocution, disconnect ALL electric and battery power BEFORE performing ANY maintenance.

MAINTENANCE REQUIREMENTS

The release device has no scheduled maintenance requirements. The unit has been designed and tested for use in dry, indoor locations. Testing of the unit at least once every 90 days is recommended, but test intervals shall ultimately be subject to criteria established by the Authority Having Jurisdiction (AHJ).

FUSE REPLACEMENT PROCEDURE AND REPAIR PARTS

One serviceable fuse, a 3 Amp, 3AG, slo-blo fuse, is required for proper operation and protection of the circuit board. The release device is shipped with the fuse in place and two replacement fuses are provided in a separate parts bag. The fuse is located on the circuit board near the battery cable connection.

Refer to page 13 for replacement parts.

BATTERY MAINTENANCE/TESTING

No maintenance or testing is required for the battery. An audible warning tone, generated by the trouble annunciator mounted to the side of the release device, will sound when the battery is approaching the minimum operating threshold. This indicates the need to replace the battery.

Refer to page 13 for replacement parts.

BATTERY DISPOSAL

Spent batteries must be treated as hazardous waste and disposed of in accordance with State, Local and Federal Regulations.

Figure 1: A diagram showing the front of the release device with a 'Mechanical Reset Plunger' on top and an 'End Link' extending from the side. The 'Electronic Reset Button' and 'Test Button' are located on the bottom of the release device, along with three LEDs: Red (Line Power Present), Green (Battery Backup Power Present), and Yellow (Close Door Detection/Release Disabled).

ENCLOSURE MOUNTED LEDS STATUS INDICATORS

LED LabelLED ColorDescriptionAction Required
BatteryGreenIf the Green LED is lit, then the battery is connected properly and charged above the minimum acceptable level.If the LED does not light, check that the leads are connected to the battery as shown on the wiring diagram on page 6 of this manual.
DisableYellowThe Yellow LED will light when the door reaches the close limit and activates a proximity switch attached to terminal positions 7 and 8 on the release device. This configuration results in the device not releasing the fusible link assembly in alarm or power loss situations and should only be used when the fire door is kept in a constant closed position.If the LED does not light when the door reaches the close limit and activates the proximity switch, then check that the proximity switch has been activated and that the switch is set to normally open (N.O.). Check to make certain that the switch is attached to terminal positions 7 and 8 on the release device.
PowerRedIf the Red LED is lit, then the line power is connected and switched "on."If the LED does not light when power is applied, check that power is connected as described in the installation manual electrical connections.

ACCESSORIES AND REPLACEMENT PARTS

ACCESSORIES

ITEMPART #DESCRIPTIONITEMPART #DESCRIPTION
1LM8100Smoke Detector - 120V Photo12LMEH1224ADAHorn - 12/24Vdc
2LM8100TSmoke Detector - 120V Photo with Thermal13LMPSTR2475ADASpeaker Strobe - 24Vdc
3LM8100ISmoke Detector - 120V Ion14LML2475ADAStrobe - 24Vdc
4LM2W-BSmoke Detector - 12/24Vdc 2-Wire Photo15LMHS2475ADAHorn/Strobe - 24Vdc
5LM2WT-BSmoke Detector - 12/24Vdc 2-Wire Photo with Thermal16LMEH1224ADAHorn - 24Vdc
6LM4W-BSmoke Detector - 12/24Vdc 4-Wire Photo17LMPSTR1V75ADASpeaker Strobe - 120Vac
7LM4WT-BSmoke Detector - 12/24Vdc 4-Wire Photo with Thermal and Form C Relay18LML1V750ADAStrobe - 120Vac
8LM1424Smoke Detector - 24Vdc Ion19LMHS1V75ADAHorn/Strobe - 120Vac
9LM1412Smoke Detector - 12Vdc Ion20LMEH120ADAHorn - 120Vac
10LMTH135Heat Detector - 135 Degree Fixed Temperature21LM8SPSpeaker 8"
11LMTH194Heat Detector - 194 Degree Fixed Temperature22LMEOLR1224End-of-Line Relay - 12/24Vdc
23LMEOLR120End-of-Line Relay - 120Vac

REPLACEMENT PARTS

ITEMPART #DESCRIPTION
1LMRKReset Knob
2LMELHEnd Link
301-32051Owner's Manual
4LM2AG3AMPFuse - 3Amp
5LMEOLRES-10End-of-Line Resistor, 10 kOhm
6LM4AH12Battery
NOTE: Certain accessories above will require a separate power source. Refer to product manual.

HOW TO ORDER REPAIR PARTS

OUR LARGE SERVICE ORGANIZATION SPANS AMERICA

Installation and service information call our TOLL FREE number:

1-800-929-2553

APPENDIX

ACCESSORY COMPATIBILITY GUIDE

SMOKE DETECTORS

MODEL NO.DESCRIPTIONSYSTEM SENSOR MODEL NO.
LM2W-B24Vdc 2-Wire Photo2W-B
LM2WT-B24Vdc 2-Wire Photo with Thermal2WT-B
LM4W-B24Vdc 4-Wire Photo4W-B
LM4WT-B24Vdc 4-Wire Photo with Thermal & Form C Relay4WT-B
LM142424Vdc Ion#1424

HEAT DETECTORS

MODEL NO.DESCRIPTIONSYSTEM SENSOR MODEL NO.CHEMTRONICS MODEL NO.EDWARDS SYSTEM TECHNOLOGY (EST) MODEL NO.
LMTH135135 Degree Fixed Temperature#5603#603#283B-PL
LMTH194194 Degree Fixed Temperature#5604#604#284B-PL

NOTIFICATION DEVICES

MODEL NO.DESCRIPTIONSYSTEM SENSOR MODEL NO.
LMPSTR2475ADA24Vdc Speaker StrobeSP2R1224MC
LML2475ADA24Vdc StrobeS1224MC
LMHS2475ADA24Vdc Horn/StrobeP1224MC
LMEH1224ADA24Vdc HornH12/24
LM8SPSpeakerSP201R

END-OF-LINE DEVICE

MODEL NO.DESCRIPTIONSYSTEM SENSOR MODEL NO.SPACE AGE ELECTRONICS NO.LIFTMASTER NO.
LMEOLRES-1010 kOhm End-of-Line ResistorLMEOLRES-10
LMEOLR1224End-of-Line RelayEOLR-1
LMEOLR120End-of-Life RelayPAM-1
NOTE: Certain accessories above will require a separate power source. Refer to product manual.

PDF preview unavailable. Download the PDF instead.

fire-sentinel-FSXPBB-FSXPBBVB-owner-manual Acrobat Distiller 6.0.1 for Macintosh

Related Documents

PreviewOverhead Door Legacy 1029 & 2029 Garage Door Opener Operation & Maintenance Manual
Comprehensive operation and maintenance manual for Overhead Door Legacy 1029 and 2029 garage door openers. Covers safety, features, programming, troubleshooting, and warranty information.
PreviewOverhead Door Legacy Series Garage Door Opener Programming, Operation & Maintenance Manual
This manual provides comprehensive programming, operation, and maintenance instructions for Overhead Door Legacy 650 (Model 1029) and Legacy 850 (Model 2029) belt and chain drive garage door openers. It includes safety information, feature descriptions, troubleshooting guides, and warranty details.
PreviewOverhead Door RapidFLEX® 995 Extreme Exterior High Speed Rubber Door
Detailed information on the Overhead Door RapidFLEX® 995, an extreme exterior high-speed rubber door designed for manufacturing, mining, and warehouse applications. Features include rugged construction, low maintenance, high cycle performance, and advanced safety features.
PreviewOHD Anywhere™ Smart Garage Door Opener Installation Guide | Overhead Door
Step-by-step instructions for installing the OHD Anywhere™ smart garage door opener controller from Overhead Door. Learn how to connect, program, and secure your smart garage.
PreviewOverhead Door Battery Back-Up Installation Instructions
Comprehensive installation guide for the Overhead Door Battery Back-Up system for residential garage door openers, including safety warnings, requirements, and step-by-step mounting and wiring instructions.
PreviewOverhead Door Legacy 650 Garage Door Opener (Model 1129) with OHD Anywhere
Explore the Overhead Door Legacy 650 (Model 1129) garage door opener. This brochure highlights its OHD Anywhere Wi-Fi connectivity, quiet DC motor, advanced security features, and choice of belt or chain drive for residential sectional doors.
PreviewOverhead Door 4-Button Universal Remote: FAQs and Programming Guide
Frequently asked questions and answers about the Overhead Door 4-Button Universal Remote, covering compatibility, programming methods, battery replacement, and troubleshooting for garage door openers and gate receivers.
PreviewOverhead Door Standard Drive 650 & Legacy 850 Garage Door Opener Operation & Maintenance Manual
Comprehensive operation and maintenance manual for Overhead Door Standard Drive 650 and Legacy 850 belt and chain drive garage door openers. Includes safety, features, programming, troubleshooting, and warranty information.