Installation Guide for DEVI models including: 316 Electronic Thermostat, 316, Electronic Thermostat, Thermostat

DEVIreg™ 316

DEVIreg™ 316 - Danfoss

DEVIreg™ 316 applies to the control of room temperature, floor ... Max 16A / 3680W @ 230V cos φ= 0.3 max 1A. Sensing units. NTC 15 kOhm at 25 °C.

PDF preview unavailable. Download the PDF instead.

AQ119286461476en-020406
Installation Guide
DEVIregTM 316
Electronic Thermostat
www.DEVI.com

The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC)

DEVIregTM 316

Table of Contents

1

Introduction . . . . . . . . . . . . . . . . . . . . . 3

1.1 Technical Speci cations . . . . . . . . . . . 4

1.2 Safety Instructions . . . . . . . . . . . . . . . 5

2

Mounting Instructions . . . . . . . . . . . . . . . 6

3

Settings . . . . . . . . . . . . . . . . . . . . . . . . 7

3.1 Hysteresis . . . . . . . . . . . . . . . . . . . . 7

3.2 Minimum Temperature Limiter . . . . . . . 8

3.3 Temperature Set-back . . . . . . . . . . . . 9

4

Warranty. . . . . . . . . . . . . . . . . . . . . . . 10

5

Disposal Instruction . . . . . . . . . . . . . . . 13

1 Introduction
DEVIregTM 316 is an electronic thermostat to be installed in electric cabinets with DIN rail attachment. The thermostat must be installed via an all-pole disconnection switch. DEVIregTM 316 applies to the control of room temperature,
oor temperature, ventilation, cooling or to the control of snow melting in gutters and similar installations.
For measuring purposes either a wire sensor or an external air sensor is used.

Installation Guide

3

DEVIregTM 316
The thermostat has a button to adjust the temperature setting with a scale from -10°C to +50°C . An LED indicator shows standby periods and heating periods (red light).
More information on this product can also be found at: devireg.devi.com.

1.1 Technical Speci cations

Operation voltage

220 - 240V~, 50Hz

Standby power consumption

Max 0.25W

Relay:
Resistive load Inductive load

Max 16A / 3680W @ 230V cos = 0.3 max 1A

Sensing units

NTC 15 kOhm at 25 °C

Sensing values:
0 °C 25 °C 50 °C

42 kOhm 15 kOhm 6 kOhm

Hysteresis

0 ° to 6 °C

Ambient temperature

-10 °C to +45 °C

Lowering in economy periods

0 ° to 8 °C

Temperature range

-10 ° to +50 °C

Minimum temperature range

-10 °C to +5 °C

Cable speci cation max

1 x 4 mm or 2 x 2,5 mm

Ball pressure temperature

75 °C

4

Installation Guide

DEVIregTM 316

Pollution degree Type Storage temperature IP class Protection class Dimensions Weight

2 (domestic use) 1B -20 °C to +65 °C 30 Class II 86 x 36 x 58 mm 180 g

The product complies with the EN/IEC Standard "Automatic electrical controls for household and similar use":

· EN/IEC 60730-1 (general) · EN/IEC 60730-2-9 (thermostat)

1.2 Safety Instructions Make sure the mains supply to the thermostat is turned o before installation.

IMPORTANT: When the thermostat is used to control a oor heating element in connection with a wooden oor or
similar material, always use a oor sensor and never set the maximum oor temperature to more than 35°C.
Please also note the following:
· The installation of the thermostat must be done by an authorized and quali ed installer according to local regulations.

Installation Guide

5

DEVIregTM 316
· The thermostat must be connected to a power supply via an all-pole disconnection switch.
· Always connect the thermostat to continuous power supply.
· Do not expose the thermostat to moisture, water, dust, and excessive heat.
2 Mounting Instructions
Please observe the following placement guidelines:
· Install the thermostat in an electric cabinet with DIN rail attachment or a separate DIN attachment according to local regulation on IP classes.
· Do not place the thermostat in a way that it will be exposed to direct sunlight.
Follow the steps below to mount the thermostat: 1. Click the thermostat on to the DIN rail attachment.
2. Connect the thermostat according to the connection diagram.

Min. Sensor

7 8 9 10 11 12

NL
1 2 3 45 6

250V~ 16 (1) A

Mains 220-240V~

Danfoss A/S Ulvehavevej 61 7100 Vejle Denmark

IP20 -10T50

D316

6

Installation Guide

DEVIregTM 316
The screen of the heating cable must be connected to the earth conductor of the power supply cable by using a separate connector.
Note: When you use the wire sensor for oor heating, always install the sensor in a conduit.
3. Turn on the power supply.
Protective separation The thermostat is designed so that the sensor circuit is galvanically separated from the high voltage part which means that the sensor part is regarded as a low voltage part.

3 Settings

A Night set-back
B Minimum temperature limiter
C Hysteresis

3.1 Hysteresis When the thermostat is used to apply with either heating systems or refrigerating systems, and the requested

Installation Guide

7

DEVIregTM 316
temperature is between -10°C to +50°C, then it is recommendable also to adjust the hysteresis (C) according to the requested regulating range.
As an example if the temperature is set at 18°C and the hysteresis at 3°C the thermostat will switch on at 18°C and o at 21°C.
For controlling of room temperature the Hysteresis is recommended to the set point of 1°C.
3.2 Minimum Temperature Limiter When the thermostat is used in connection with snow and ice melting systems, it is recommendable also to use and adjust the minimum temperature limiter (B) which ensures both an upper and lower temperature range in between which the thermostat allows the system to heat.
The requested maximum temperature range has to be between -10°C to +50°C and the requested minimum temperature range has to be between -10°C to +5°C.
An link between terminal 9+10 must be connected to activate the use of the minimum temperature feature when the thermostat controls snow and ice melting in gutters, valley gutters and down pipes, where the waste of unnecessary energy must be avoided. In particular by extremely cold weather where owing water or moisture does not occur.

8

Installation Guide

DEVIregTM 316
When the temperature drops below the minimum temperature set value, the thermostat stops heating and the LED indicator turns yellow.
When the temperature exceeds the maximum temperature setting, the thermostat stops heating and both the indicator for minimum and maximum temperature disappears.
3.3 Temperature Set-back By connecting an external timer to terminals 4 and 6, the thermostat can be set to reduce the temperature by 0°C to 8°C (A).

Installation Guide

9

DEVIregTM 316
4 Warranty
A 2-year product warranty is valid for: · thermostats: DEVIregTM 316.
Should you, against all expectations, experience a problem with your DEVI product, you will nd that Danfoss o ers DEVIwarranty valid from the date of purchase on the following conditions: During the warranty period Danfoss shall o er a new comparable product or repair the product if the product is found to be faulty by reason of defective design, materials or workmanship. The repair or replacement.
The decision to either repair or replace will be solely at the discretion of Danfoss. Danfoss shall not be liable for any consequential or incidental damages including, but not limited to, damages to property or extra utility expenses. No extension of the warranty period following repairs undertaken is granted.
The warranty shall be valid only if the WARRANTY CERTIFICATE is completed correctly and in accordance with the instructions, the fault is submitted to the installer or the seller without undue delay and proof of purchase is provided. Please note that the WARRANTY CERTIFICATE must be lled in, stamped and signed by the authorized installer performing the installation (Installation date must be indicated). After the installation is performed, store and keep the WARRANTY CERTIFICATE and purchase documents (invoice, receipt or similar) during the whole warranty period.
DEVIwarranty shall not cover any damage caused by incorrect conditions of use, incorrect installation or if installation has been carried out by non-authorized electricians. All work will be invoiced in full if Danfoss is required to inspect or repair faults that have arisen as a result of any of the above. The DEVIwarranty shall not extend to products which have not been paid in full. Danfoss will, at all times, provide a rapid and e ective response to all complaints and inquiries from our customers.
The warranty explicitly excludes all claims exceeding the above conditions.
For full warranty text visit www.devi.com. devi.danfoss.com/en/warranty/

10

Installation Guide

DEVIregTM 316

Installation Guide

WARRANTY CERTIFICATE
The DEVIwarranty is granted to:

Address

Stamp

Purchase date

Serial number of the product

Product

Art. No.

*Connected output [W]
Installation Date & Signature *Not mandatory

Connection Date & Signature

11

DEVIregTM 316

12

Installation Guide

DEVIregTM 316 5 Disposal Instruction

Installation Guide

13

DEVIregTM 316

14

Installation Guide

DEVIregTM 316

Danfoss A/S Nordborgvej 81 6430 Nordborg, Syddanmark Denmark
8095512 & AQ119286461476en-020405

© Danfoss | 2024.03

DEVIregTM 316 -10<>+50°
140F1075 EN

88009955551122

Electronic thermostat 220-240V~ 50-60Hz -10°C to +50°C 16A/3680W@230V~

Product documentation

dMk
For UK customer only: Importer: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB

Designed in Denmark for Danfoss A/S
5 703466 209240


Danfoss A/S GPL Ghostscript 9.55.0