XL-Trace Edge

Self-regulating heating cable for pipe freeze protection and flow maintenance

PRODUCT OVERVIEW Heating cable construction
Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket Tinned-copper braid Modified polyolefin inner jacket Self-regulating conductive core Nickel-plated copper bus wire

nVent RAYCHEM XL-Trace Edge is designed for pipe freeze protection and flow maintenance in the following applications: · Freeze protection of general water piping
(aboveground and buried) · Freeze protection of fire sprinkler system piping,
including sprinklers · Flow maintenance of greasy waste lines
(aboveground and buried) · Flow maintenance of fuel lines (aboveground)
The heating element in the XL-Trace Edge heating cable consists of a continuous core of conductive polymer extruded between two copper bus wires. The XL-Trace Edge heating cable regulates its power output in response to pipe temperature changes. This self-regulating technology allows XL-Trace Edge heating cable to be overlapped or installed on plastic pipes without overheating.
Low total installed cost
The XL-Trace Edge heating cable's parallel circuitry allows it to be cut to the exact length required, with no wasted cable. Its flexibility allows it to be wrapped around complex fittings and valves.
All of these characteristics simplify and streamline the design of a heat-tracing system. Installation is quick and simple.
Low total operating cost
Building operators are assured of optimal energy efficiency and low maintenance costs when an XL-Trace Edge system is specified.
The same features that make an XL-Trace Edge system easy to install the first time also simplify additions or changes to the system during building renovations.
For additional information, contact your nVent representative or call (800) 545-6258.

RAYCHEM-DS-H51349-XLTraceEdge-EN-2302

nVent.com/RAYCHEM | 1

Catalog Number

3XLE1-CR

3XLE2-CR

5XLE1-CR/CT 5XLE2-CR/CT 8XLE1-CR/CT 8XLE2-CR/CT 12XLE2-CR/CT

Voltage

120 V

208­277 V 120 V

208­277 V 120 V

208­277 V 208­277 V

Maximum Operating Temperature

154°F (68°C) 154°F (68°C) 154°F (68°C) 154°F (68°C) 154°F (68°C) 154°F (68°C) 150°F (65°C)

Maximum Exposure Temperature

185°F (85°C)1 185°F (85°C)1 185°F (85°C)1 185°F (85°C)1 185°F (85°C)1 185°F (85°C)1 185°F1 (85°C)1

Minimum Installation Temperature

0°F (­18°C) 0°F (­18°C) 0°F (­18°C) 0°F (­18°C) 0°F (­18°C) 0°F (­18°C) 0°F (­18°C)

Minimum Bend Radius

1/2 in (12 mm)

1/2 in (12 mm)

1/2 in (12 mm)

1/2 in (12 mm)

1/2 in (12 mm)

1/2 in (12 mm)

1/2 in (12 mm)

1 When the design requires 185°F (85°C) exposure temperature, all connections must be installed off the pipe.

MAXIMUM CIRCUIT LENGTH IN FEET

40°F / 110°F Maintain*

Start-up

3XLE1 5XLE1 8XLE1 3XLE2

5XLE2

8XLE2

tem- CB

perature size

(°F)

(A) 120 V 120 V 120 V 208 V 240 V 277 V 208 V 240 V 277 V 208 V 240 V

­20°F 15 134 96 75 258 250 247 201 209 221 138 116

20 179 129 100 344 334 329 268 279 294 210 180

30 269 193 150 517 501 494 402 419 441 316 341

40 335 207 151 689 668 644 469 474 487 339 359

0°F 15 156 112 84 307 298 294 227 237 250 170 142

20 209 149 113 410 397 392 303 316 333 236 239

30 313 223 169 615 596 587 455 474 499 354 382

277 V 99 148 370 384 120 190 414

40 368 245 173 696 732 708 535 544 558 384 407 435

20°F 15 189 132 98 376 365 359 262 273 288 200 185

20 252 176 131 501 486 479 349 364 383 267 288

30 368 264 196 696 729 718 523 546 575 400 432

40 368

287

205

696

732

776

535

584 642

407/ 452/ 442 467

40°F 15 242 160 117 492 478 471 311 324 342 232 250

20 323 214 156 656 637 628 414 432 456 309 334

30 368

287

223

696

732

776

535

584 642

407/ 452/ 464 500

40 368

287

223

696

732

776

535

584 642

407/ 452/ 526 555

50°F 15 ­ ­ ­ ­ ­ ­ ­ ­ ­ 253 273

20 ­ ­ ­ ­ ­ ­ ­ ­ ­ 337 364

30 ­ ­ ­ ­ ­ ­ ­ ­ ­ 506 546

40 ­ ­ ­ ­ ­ ­ ­ ­ ­ 586 617

65°F 15 ­ ­ ­ ­ ­ ­ ­ ­ ­ 296 319

20 ­ ­ ­ ­ ­ ­ ­ ­ ­ 395 426

30 ­ ­ ­ ­ ­ ­ ­ ­ ­ 592 639

40 ­ ­ ­ ­ ­ ­ ­ ­ ­ 686 756

* When maximum circuit length is listed in: - black type, the value is for applications with a 40°F maintain - red type, the value is for applications with a 110°F maintain

154 276 469
499
221 362 504/ 543 504/ 591 296 395 592 656 347 462 693 801

12XLE2

208 V 127 169 253 338 129 172 258 340/ 344 144 192 287 340/ 383 162 216

240 V 129 171 257 343 131 175 262
349
146 194 292 360/ 389 165 219

324 329

340/ 430 173 231 346 430 192 256 384 430

360/ 439 176 234 352 460 195 260 390 460

277 V 130 174 260 347 133 177 265
354
148 197 296 380/ 394 167 222
333
380/ 444 178 237 356 475 197 263 395 490

RAYCHEM-DS-H51349-XLTraceEdge-EN-2302

nVent.com/RAYCHEM | 2

MAXIMUM CIRCUIT LENGTH IN METERS

4°C / 43°C Maintain*

Start-up

3XLE1 5XLE1 8XLE1 3XLE2

5XLE2

8XLE2

12XLE2

tem-

CB

perature size

(°C)

(A) 120 V 120 V 120 V 208 V 240 V 277 V 208 V 240 V 277 V 208 V 240 V 277 V 208 V 240 V 277 V

­29°C 15 41 29 23 79 76 75 61 64 67 42 35 30 39 39 40

20 55 39 30 105 102 100 82 85 90 64 55 45 52 52 53

30 82 59 46 158 153 151 123 128 134 96 104 113 77 78 79

40 102 63 46 210 204 196 143 145 148 103 109 117 103 105 106

­18°C 15 48 34 26 94 91 90 69 72 76 52 43 37 39 40 41

20 64 45 34 125 121 120 92 96 102 72 73 58 52 53 54

30 95 68 52 188 182 179 139 145 152 108 116 126 79 80 81

40 112 75

53

212

223 216 163

166

170 117

124 133

104/ 105

106

108

­7°C 15 58 40 30 115 111 109 80 83 88 61 56 47 44 45 45

20 77 54 40 153 148 146 106 111 117 81 88 84 59 59 60

30 112 80 60 212 222 219 159 166 175 122 132 143 88 89 90

40 112 88

63

212 223 237 163 178

196

124/ 135

138/ 142

152

104/ 110/ 117 119

116/ 120

4°C

15 74 49 36 150 146 144 95 99 104 71 76 67 49 50 51

20 98 65 48 200 194 191 126 132 139 94 102 110 66 67 68

30 112 88

68

212 223 237 163 178

196

124/ 138/ 154/ 160 169 180

99

100 102

40 112 88

68

212 223 237 163 178

196

124/ 138/ 154/ 104/ 110/ 160 169 180 131 134

116/ 135

10°C 15 ­ ­ ­ ­ ­

­­

­

­ 77 83 90 53 54 54

20 ­ ­ ­ ­ ­

­­

­

­ 103 111 120 70 71 72

30 ­ ­ ­ ­ ­

­­

­

­ 154 166 180 105 107 109

40 ­ ­ ­ ­ ­

­­

­

­ 179 188 200 131 140 145

18°C 15 ­ ­ ­ ­ ­

­­

­

­ 90 97 106 59 59 60

20 ­ ­ ­ ­ ­

­­

­

­ 120 130 141 78 79 80

30 ­ ­ ­ ­ ­

­­

­

­ 180 195 211 117 119 120

40 ­ ­ ­ ­ ­

­­

­

­ 209 230 244 131 140 149

* When maximum circuit length is listed in: - black type, the value is for applications with a 40°F maintain - red type, the value is for applications with a 110°F maintain

NOMINAL POWER OUTPUT ON METAL PIPES AT 120 V/240 V

Power W/ft

14
12 D
10
8 C
6 B 4 A
2
0 30 40 (­1) (5)

50 60 70 80 90 100 110 120 130 (10) (15) (21) (27) (32) (38) (43) (49) (54)
Pipe temperature

140 150 °F (60) (65) (°C)

A

3XLE1-CR (120 V) 3XLE2-CR (240 V)

B

5XLE1-CR and 5XLE1-CT (120 V) 5XLE2-CR and 5XLE2-CT (240 V)

C

8XLE1-CR and 8XLE1-CT (120 V) 8XLE2-CR and 8XLE2-CT (240 V)

D 12XLE2-CR and 12XLE2-CT (240 V)

RAYCHEM-DS-H51349-XLTraceEdge-EN-2302

nVent.com/RAYCHEM | 3

BUS WIRES 16 AWG nickel-plated copper

BRAID/OUTER JACKET Tinned-copper braid with modified polyolefin jacket (-CR) or fluoropolymer jacket (-CT)

DIMENSIONS
Maximum width Maximum thickness

3XLE, 5XLE and 8XLE 0.56 in (14 mm) 0.24 in (6 mm)

12XLE 0.62 in (16 mm) 0.24 in (6 mm)

NOMINAL WEIGHT

92 lb/1000 ft

104 lb/1000 ft

CONNECTION KITS
nVent RAYCHEM RayClic or FTC connection kits must be used with XL-Trace Edge heating cables. Refer to the Pipe Freeze Protection and Flow Maintenance Design Guide (H55838) for proper connection kit selection.

APPROVALS

Refer to the Pipe Freeze Protection and Flow Maintenance Design Guide (H55838) and the Fire Sprinkler Freeze Protections Design Guide (H58489) for specific product approval details.
Note: The XL-Trace Edge system is not UL listed for plastic fire sprinkler pipes.
GROUND FAULT PROTECTION
To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent, agency certifications, and national electrical codes, ground fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection. Many nVent RAYCHEM control and monitoring systems meet the ground fault protection requirement.

North America
Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nVent.com

Our powerful portfolio of brands:
©2023 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice. RAYCHEM-DS-H51349-XLTraceEdge-EN-2302

nVent.com/RAYCHEM | 4

