https://resources.kohler.com/power/kohler/industrial/pdf/tp6834

Kohler Automatic Transfer Switch Manual

PDF preview unavailable. Download the PDF instead.

tp6834
Operation and Installation
Automatic Transfer Switches
Models:
KSS/KSP
40 to 1000 Amperes
TP-6834 4/14

Product Identification Information

Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Transfer Switch Identification Numbers
Record the product identification numbers from the transfer switch nameplate.
Model Designation Serial Number
Accessories
- Alarm Board - Battery Module - Controller Disconnect Switch - Digital Meter - Heater - I/O Module, Standard (max. 4) qty: - I/O Module, High Power (max. 4) qty: - Load Shed - Line-Neutral Monitoring - Seismic Certification - Supervised Transfer Switch - Surge Protection Device (SPD) -

Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice.
Controller Description

Table of Contents
Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 List of Related Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Section 1 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.2 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.3 Model Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Section 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.2 Receipt of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.2.2 Lifting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.2.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.2.4 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.4 Seismic Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 2.5 Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.5.1 Manual Operation, Model KSS Standard-Transition Switches . . . . . . . . 14 2.5.2 Manual Operation, Model KSP Programmed-Transition Switches . . . . 16 2.6 Controller Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.6.1 Controller Input and Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.6.2 Harness Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.6.3 Controller Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.7 Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.7.1 Source and Load Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.7.2 Engine Start Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 2.7.3 Auxiliary Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 2.8 Communication and Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 2.9 Functional Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Section 3 Communication and Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.2 Communication Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.2.1 USB Port SiteTech Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.2.2 Modbus Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.2.3 Ethernet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 3.3 Accessory Modules (MPAC 1200 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 3.3.1 Accessory Module Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 3.3.2 Input/Output (I/O) Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 3.3.3 External Battery Supply Module (EBSM) . . . . . . . . . . . . . . . . . . . . . . . . . . 31 3.3.4 Alarm Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 3.4 Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 3.5 Load Shed (Forced Transfer to OFF, KSP with MPAC 1200 only) . . . . . . . . . . . . . 36 3.6 Programmable Exerciser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 3.7 Other Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

TP-6834 4/14

Table of Contents 3

Table of Contents, continued
Section 4 Functional Tests and Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 4.2 Manual Operation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 4.3 Voltage Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 4.4 Automatic Operation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 4.5 System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 4.6 Exerciser Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 4.7 User Interface Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 4.8 Startup Notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Appendix A Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

4 Table of Contents

TP-6834 4/14

Safety Precautions and Instructions

IMPORTANT SAFETY INSTRUCTIONS.

Electromechanical

equipment,

including generator sets, transfer

switches, switchgear, and accessories,

can cause bodily harm and pose

life-threatening danger when

improperly installed, operated, or

maintained. To prevent accidents be

aware of potential dangers and act

safely. Read and follow all safety

precautions and instructions. SAVE

THESE INSTRUCTIONS.

This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.

DANGER
Danger indicates the presence of a hazard that will cause severe personal injury, death, or substantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.

Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
(Decision-Makerr 3+ and 550 Generator Set Controllers)
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
(RDC, DC, RDC2, DC2, Decision-Makerr 3000, 3500 and 6000 Generator Set Controllers)

Hazardous Voltage/ Moving Parts
DANGER

Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.
DANGER

Hazardous voltage. Will cause severe injury or death.
Only authorized personnel should open the enclosure.

Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.

Short circuits.

Hazardous

voltage/current can cause severe

injury or death. Short circuits can

cause bodily injury and/or equipment

damage. Do not contact electrical

connections with tools or jewelry while

making adjustments or repairs.

Remove all jewelry before servicing the

equipment.

Making line or auxiliary connections. Hazardous voltage can cause severe injury or death. To prevent electrical shock deenergize the normal power source before making any line or auxiliary connections.

TP-6834 4/14

Safety Precautions and Instructions 5

Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Move all generator set master controller switches to the OFF position. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
(Decision-Makerr 3+ and 550 Generator Set Controllers)
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
(RDC, DC, RDC2, DC2, Decision-Makerr 3000, 3500 and 6000 Generator Set Controllers)

Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically. (600 volts and under)
WARNING
Airborne particles. Can cause severe injury or blindness. Wear protective goggles and clothing when using power tools, hand tools, or compressed air.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage. Use adequate lifting capacity. Never leave the transfer switch standing upright unless it is securely bolted in place or stabilized.

Notice
NOTICE
Improper operator handle usage. Use the manual operator handle on the transfer switch for maintenance purposes only. Return the transfer switch to the normal position. Remove the manual operator handle, if used, and store it in the place provided on the transfer switch when service is completed.
NOTICE
Foreign material contamination. Cover the transfer switch during installation to keep dirt, grit, metal drill chips, and other debris out of the components. Cover the solenoid mechanism during installation. After installation, use the manual operating handle to cycle the contactor to verify that it operates freely. Do not use a screwdriver to force the contactor mechanism.
NOTICE
Electrostatic discharge damage. Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short, to ground.

6 Safety Precautions and Instructions

TP-6834 4/14

Introduction

This manual provides operation and installation instructions for the following Kohlerr Automatic Transfer Switches (ATS):
D Model KSS standard-transition specific breaker ATS equipped with the Decision-Makerr MPAC 750 controller.
D Model KSS standard-transition specific breaker ATS equipped with the Decision-Makerr MPAC 1200 controller.
D Model KSP programmed-transition specific breaker ATS equipped with the Decision-Makerr MPAC 1200 controller.
A separate manual provided with the transfer switch covers the transfer switch controller operation. See List of Related Materials for the document part number.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this literature and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.

The equipment service requirements are very important to safe and efficient operation. Inspect parts often and perform required service at the prescribed intervals. See the controller Operation manual for the service schedule. Obtain service from an authorized service distributor/ dealer to keep equipment in top condition.

List of Related Materials
A separate manual covers the transfer switch controller and related accessories. Separate manuals contain service and parts information for transfer switch power switching devices and electrical controls.
The following table lists the part numbers for related literature.

Literature Item
Specification Sheet, Decision-Makerr MPAC 750 Controller
Specification Sheet, Decision-Makerr MPAC 1200 Controller
Specification Sheet, Model KSS/KSP
Operation Manual, Decision-Makerr MPAC 750 Controller
Operation Manual, Decision-Makerr MPAC 1200 Controller
Parts Catalog, Transfer Switch and Controller
Service Manual, Model KSS/KSP/KGS/KGP

Part Number
G11-126
G11-127 G11-130 TP-6865
TP-6866 TP-6433 TP-6921

TP-6834 4/14

Introduction 7

Service Assistance
For professional advice on generator power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading Generators--Electric.
D Visit the Kohler Power Systems website at KOHLERPower.com.
D Look at the labels and stickers on your Kohler product or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems Netherlands B.V. Kristallaan 1 4761 ZC Zevenbergen The Netherlands Phone: (31) 168 331630 Fax: (31) 168 331631
Asia Pacific Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455

China North China Regional Office, Beijing Phone: (86) 10 6518 7950 (86) 10 6518 7951 (86) 10 6518 7952 Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka India Regional Office Bangalore, India Phone: (91) 80 3366208 (91) 80 3366231 Fax: (91) 80 3315972
Japan, Korea North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131

8 Service Assistance

TP-6834 4/14

Section 1 Product Description

1.1 Purpose
An automatic transfer switch (ATS) transfers electrical loads from a normal (preferred) source of electrical power to an emergency (standby) source when the normal source falls outside the acceptable electrical parameters.
When the normal (preferred) source fails, the ATS signals the emergency (standby) source generator set to start. When the emergency (standby) source reaches acceptable levels and stabilizes, the ATS transfers the load from the normal (preferred) source to the emergency (standby) source. The ATS continuously monitors the normal (preferred) source and transfers the load back when the normal (preferred) source returns and stabilizes. After transferring the load back to the normal (preferred) source, the ATS removes the generator start signal, allowing the generator set to shut down.
Figure 1-2 shows a typical installation block diagram.

Normal (Utility) Power

Emergency

(Generator)

Power

Generator

Start Generator

Power Switching Device

Electrical Controls
Automatic Transfer Switch

To Load
Figure 1-2 Typical ATS Block Diagram

TS-003

1.2 Nameplate
A nameplate attached to the controller cover on the inside of the enclosure door includes a model designation, a serial number, ratings, and other information about the transfer switch. See Figure 1-3. The serial number is also shown on a label inside the transfer switch enclosure.
Copy the model designation, serial number, and accessory information from the nameplate to the spaces provided in the Product Identification Information section inside the front cover of this manual for use when requesting service or parts.

Figure 1-1 Automatic Transfer Switch
TP-6834 4/14

GM21291
Figure 1-3 Typical Transfer Switch Nameplate
Section 1 Product Description 9

1.3 Model Designation

Model Mechanism Transition Controls Voltage

Poles Enclosure

Current Rating

Connections

Record the transfer switch model designation in the boxes. The transfer switch model designation defines characteristics and ratings as explained below.
Sample Model Designation: KSS-JCNA-0100S

Model K: Kohler
Mechanism S: Standard (Specific-Breaker)
Transition S: Standard P: Programmed

Number of Poles/Wires N: 2 Poles / 3 Wires, Solid Neutral T: 3 Poles / 4 Wires, Solid Neutral V: 4 Poles / 4 Wires, Switched Neutral

Enclosure A: NEMA 1 B: NEMA 12 C: NEMA 3R

D: NEMA 4 F: NEMA 4X G: Open Unit

Controller A: Decision-Makerr MPAC 1200, Automatic B: Decision-Makerr MPAC 1200, Non-Automatic J: Decision-Makerr MPAC 750, Automatic

Voltage/Frequency C: 208 Volts / 60 Hz D: 220 Volts / 50 Hz F: 240 Volts / 60 Hz G: 380 Volts / 50 Hz H: 400 Volts / 50 Hz

J: 416 Volts / 50 Hz K: 440 Volts / 60 Hz M: 480 Volts / 60 Hz P: 380 Volts / 60 Hz R: 220 Volts / 60 Hz

Current, Amps 0040 0080 0100 0150

0200 0225 0260 0400

600 800 1000

Connections S: Standard

Note: Some selections are not available for every model.
Contact your Kohler distributor for availability.

10 Section 1 Product Description

TP-6834 4/14

Section 2 Installation

2.1 Introduction
Kohlerr transfer switches are shipped factory-wired, factory-tested, and ready for installation. Have the equipment installed only by trained and qualified personnel. Verify that the installation complies with applicable codes and standards. Installation includes the following steps:
D Unpack and inspect the transfer switch upon receipt.
D Verify that the transfer switch voltage and frequency ratings match the voltages and frequencies of the sources.
D Install the transfer switch.
D Check the manual operation.
D Connect the controller harness and ground lead.
D Connect the generator set engine start leads.
D Connect the normal power source (utility), emergency power source (generator set), and load circuits.
D Connect accessories, if provided.
D Check voltages and operation.
Protect the switch against damage before and during installation.
Note: An approved protective device such as a molded-case circuit breaker or fused disconnect switch MUST be installed on both sources of incoming power for circuit protection and used as a disconnect device.
The functional tests in Section 4 are a necessary part of the installation. Be sure to perform the functional tests, which include voltage checks and operation tests, before putting the transfer switch into service.

2.2 Receipt of Unit

2.2.1 Inspection
At the time of delivery, inspect the packaging and the transfer switch for signs of shipping damage. Unpack the transfer switch as soon as possible and inspect the exterior and interior for shipping damage. If damage and/or rough handling is evident, immediately file a damage claim with the transportation company.

2.2.2 Lifting

WARNING

Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Use adequate lifting capacity. Never leave the transfer switch standing upright unless it is securely bolted in place or stabilized.

See Figure 2-1 or the dimension drawing for the approximate weight of the transfer switch. Use a spreader bar to lift the transfer switch. Attach the bar only to the enclosure's mounting holes or lifting brackets; do not lift the unit any other way. Close and latch the enclosure door before moving the unit.

Weight kg (lb.)

Model Amps 2-Pole

3-Pole

4-Pole

40--225 28 (62) 30 (65)

31 (68)

260--400 52 (115) 56 (123)

59 (131)

KSS

600 179 (395) 183 (403)

800

N/A

226 (498)

186 ( 410) 236 (520)

1000

N/A

231 (509) 241 ( 531)

100--200 52 (115)

56 (123)

59 (131)

KSP

400

52 (115)

56 (123)

59 (131)

600 179 (395) 183 (403) 186 ( 410)

Figure 2-1 Approximate Transfer Switch Weights, NEMA Type 1 and 3R Enclosures

TP-6834 4/14

Section 2 Installation 11

2.2.3 Storage
Store the transfer switch in its protective packing until final installation. Protect the transfer switch at all times from moisture, construction grit, and metal chips. Avoid storage in low-temperature and high-humidity areas where moisture could condense on the unit. See Figure 2-2 for acceptable storage temperatures.

Item

Specification

Storage temperature

--40C to 70C (--40F to 158F)

Operating temperature

--20C to 85C (--4F to 185F)

Humidity

5% to 95% noncondensing

Figure 2-2 Environmental Specifications

2.2.4 Unpacking
Allow the equipment to warm to room temperature for at least 24 hours before unpacking to prevent condensation on the electrical apparatus. Use care when unpacking to avoid damaging transfer switch components. Remove dirt and packing material that may have accumulated in the transfer switch or any of its components.
Note: Do not use compressed air to clean the switch. Cleaning with compressed air can cause debris to lodge in the components and damage the switch.

2.3 Installation
NOTICE
Foreign material contamination. Cover the transfer switch during installation to keep dirt, grit, metal drill chips, and other debris out of the components. Cover the solenoid mechanism during installation. After installation, use the manual operating handle to cycle the contactor to verify that it operates freely. Do not use a screwdriver to force the contactor mechanism.
Hardware damage. The transfer switch may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
Check the system voltage and frequency. Compare the voltage and frequency shown on the transfer switch nameplate to the source voltage and frequency. Do not install the transfer switch if the system voltage and frequency are different from the nominal normal (utility) source voltage and frequency or the nominal emergency source voltage and frequency shown on the generator set nameplate.

Plan the installation. Use the dimensions given on the enclosure dimension (ADV) drawings. Select a mounting site that complies with local electrical code restrictions for the enclosure type. Mount the transfer switch as close to the load and power sources as possible. Allow adequate space to fully open the enclosure and to service the switch. Provide cable bending space and clearance to live metal parts.
Outdoor installations. Transfer switches with NEMA 3R, 4, or 4X enclosures can be installed outdoors. In locations with very high ambient temperatures, installation in a shaded area or a location with the enclosure door facing away from direct sunlight is recommended.
Prepare the foundation. Ensure that the supporting foundation for the enclosure is level and straight. For bottom cable entry, if used, install conduit stubs in the foundation. Refer to the enclosure dimension drawing for the conduit stub locations. When pouring a concrete floor, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Installation of seismically certified transfer switches. See Section 2.4 and the transfer switch dimension (ADV) drawings for additional installation requirements.
Install the ATS. Mount 40- through 400-amp transfer switches to a wall or other rigid vertical supporting structure. Clearance holes through the back of each enclosure are provided for mounting. Level the enclosure and use shims if needed to plumb the enclosure. Verify that the door hinges are vertical to avoid distortion of the enclosure or door.
Bolt 600- through 1000-amp automatic transfer switches directly to floor mounting pads. Use shims if needed to plumb the enclosure. Verify that the door hinges are vertical to avoid distortion of the enclosure or door.

12 Section 2 Installation

TP-6834 4/14

2.4 Seismic Certification
Automatic transfer switches with seismic certification must be installed according to the instructions in this section. Also refer to the Certificate of Compliance and the installation drawings for the transfer switch.
Abbreviations:
ACI: American Concrete Institute
IBC: International Building Coder
SDS: Design spectral response acceleration at short period, as determined in Section 1615.1.3 of the IBC
Rp: Equipment response modification factor
Ip: Equipment importance factor
ap: In-structure equipment amplification factor
Refer to the International Building Coder for more information.
General Seismic Installation Notes:
1. Anchors used for seismic installation must be designed in accordance with ACI 355.2--04. Suggested manufacturers include Simpson, Ramset, and Hilti.
2. Anchors must be installed to a minimum embedment of 8x the anchor diameter.
3. Anchors must be installed in minimum 4000 psi compressive strength normal weight concrete. Concrete aggregate must comply with ASTM C33. Installation in structural lightweight concrete is not permitted unless otherwise approved by the structural engineer of record.
4. Anchors must be installed to the required torque specified by the anchor manufacturer to obtain maximum loading.
5. Anchors must be installed with spacing and edge distance required to obtain maximum load unless otherwise approved by the structural engineer of record.
6. Anchors used for seismic installation must be designed and rated to resist seismic loading in accordance with ACI 355.2--04 and documented in

a report by a reputable testing agency (ex. the Evaluation Service Report issued by the International Code Council).
7. Wide washers must be installed at each anchor location between the anchor head and equipment for tension load distribution. See applicable ADV drawing for specific anchor information and washer dimensions.
8. Equipment installed on a housekeeping pad requires the housekeeping pad thickness to be at least 1.5x the anchor embedment depth.
9. All housekeeping pads must be seismically designed and dowelled or cast into the building structure as approved by the structural engineer of record.
10. Rebar reinforcing in the housekeeping pad is required for all installations.
11. Rebar reinforcement in concrete must be designed in accordance with ACI 318--05.
12. Wall mounted equipment must be installed to a rebar reinforced structural concrete wall that is seismically designed and approved by the engineer of record to resist the added seismic loads from components being anchored to the wall.
13. Floor mounted equipment (with or without a housekeeping pad) must be installed to a rebar reinforced structural concrete floor that is seismically designed and approved by the engineer of record to resist the added seismic loads from components being anchored to the floor.
14. When installing to a floor or wall, rebar interference must be considered.
15. Equipment attached to any structural floor other than those constructed of structural concrete and designed to accept the seismic loads from the mounted equipment are beyond the scope of this specification.
16. Installation to light-weight concrete over steel decking is beyond the scope of this specification.
17. Installation to concrete block or cinder block walls is beyond the scope of this specification.

TP-6834 4/14

Section 2 Installation 13

2.5 Manual Operation
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
NOTICE
Improper operator handle usage. Use the manual operator handle on the transfer switch for maintenance purposes only. Return the transfer switch to the normal position. Remove the manual operator handle, if used, and store it in the place provided on the transfer switch when service is completed.
A manual operation handle is provided with the transfer switch for maintenance purposes only. Use the manual operation handle to check the manual operation before energizing the transfer switch. Use the following manual operation procedures to verify that the contactor operates smoothly without binding.
Note: A contactor in normal and serviceable condition operates smoothly without binding. Do not place the transfer switch into service if the contactor does not operate smoothly; contact an authorized distributor/dealer to service the contactor.

2.5.1 Manual Operation, Model KSS Standard-Transition Switches
Note: Never use the maintenance handle to transfer the load with the power connected. Disconnect both power sources before manually operating the switch.
1. Disable the generator set to prevent starting and disconnect all power sources before manually operating the transfer switch.
2. Remove the maintenance handle from its storage location inside the enclosure. See Figure 2-3 through Figure 2-5.
3. Attach the maintenance handle:
a. 40--600 Amp switches: Insert the maintenance handle into the hole in the shaft on the left side of the operator as shown in Figure 2-3 or Figure 2-4.
b. 800--1000 Amp switches: Slide the maintenance handle over the square shaft on the left side of the operator as shown in Figure 2-5.
4. Move the maintenance handle up or down as shown in the corresponding figure to manually operate the transfer switch. It should operate smoothly without any binding. If it does not, check for shipping damage or construction debris.
5. Return the transfer switch to the Normal position.
6. Remove the maintenance handle and return it to the storage location.

14 Section 2 Installation

TP-6834 4/14

1
1 2 2

1. Handle storage location 2. Insert handle here for manual operation
Figure 2-3 Manual Operation, 40--260 Amp Standard-Transition Switches

tp6225

1. Handle storage location 2. Insert handle here for manual operation
Figure 2-4 Manual Operation, 400--600 Amp Standard-Transition Switches

tp6225

1

2

3

1. Handle storage location inside enclosure 2. Shaft (attach handle here) 3. Move maintenance handle down and release to manually operate
Figure 2-5 Manual Operation, 800--1000 Amp Standard-Transition Switches

tp6447

TP-6834 4/14

Section 2 Installation 15

2.5.2 Manual Operation, Model KSP Programmed-Transition Switches
Note: Never use the manual operation handle to transfer the load with the power connected. Disconnect both power sources before manually operating the switch.
1. Disable the generator set to prevent starting and disconnect all power sources before manually operating the transfer switch.
2. Check the contactor position, indicated by the A and B position indicators. See Figure 2-6. One position indicator will display ON to indicate the source position. If both indicators display OFF, the transfer switch is in the OFF position.
1
2
3 4
5

See Figure 2-6. Check that both position indicators display OFF.
4. Slide the manual operating handle (provided with the switch) over the shaft on the left side of the switch. See Figure 2-6.
5. Move the switch to the A (Source 1) or B (Source 2) position as follows:
a. To move the switch to position A (Source 1), move the manual operation handle up and then release the handle. Verify that the A position indicator displays ON.
b. To move the switch to position B (Source 2), use a screwdriver or other tool to push the SELECT button. Hold the SELECT button in and move the manual operation handle up and then release the handle. Verify that the B position indicator displays ON.
Note: Always move the manual operation handle UP and then release it.
6. Remove the manual operation handle and store it in a convenient location.
Move handle up and then release.

1. Shaft (attach handle here) 2. Trip button 3. Select button 4. Source 1 (A) position indicator (ON/OFF) 5. Source 2 (B) position indicator (ON/OFF)

tp6225

Figure 2-6 Manual Operation, ProgrammedTransition Switches (handle not shown)

3. If the transfer switch is not in the OFF position, use a screwdriver or other tool to push the TRIP button.

6225
Figure 2-7 Manual Operating Handle, ProgrammedTransition Switches

16 Section 2 Installation

TP-6834 4/14

2.6 Controller Connections
DANGER
Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.
NOTICE
Electrostatic discharge damage. Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short, to ground.
2 1

The controller is mounted in a plastic housing on the inside of the transfer switch enclosure door. Figure 2-8 shows the locations of the connectors on the controller. It is not necessary to open the cover to access the Ethernet, Modbusr, and input/output connectors. Opening the cover. If necessary, open the plastic housing by pushing up on the latch on the bottom of the cover and swinging the cover up and out. The cover is hinged at the top. Lift the cover off the hinges to remove it completely, if necessary. Note: Always replace the cover before energizing the
transfer switch controls.
34 5

8
1. Standard input/output connection 2. RS-485 connection TB2 3. Connection for optional current sensing kit 4. Optional I/O board connection P16
Figure 2-8 Controller

6
7
5. Access openings to optional RJ-45 connector 6. Latch 7. Ground wire 8. Contactor harness connection

GM85884

Modbus is a registered trademark of Schneider Electric. TP-6834 4/14

Section 2 Installation 17

2.6.1 Controller Input and Output Connections
The controller provides connections for two programmable inputs and two programmable outputs. See Figure 2-8 for the connector location.
Each input has a signal and a return connection. The outputs are C form contacts with ratings of 500 mA @ 120 VAC. See Figure 2-10 for connections. Use #12--24 AWG wire and tighten the connections to 0.5 Nm (4.4 in. lbs.).
See the transfer switch controller operation manual for instructions to assign inputs and outputs.
Transfer switches equipped with the MPAC 750 controller may also include the optional programmable exerciser. This accessory uses one input connection, which must be assigned to Remote Test. Refer to the instructions provided with the exerciser kit for more information.
Transfer switches equipped with the MPAC 1200 controller can use optional input/output modules for additional input and output connections. See Section 3.3 for instructions.

Main Board I/O Specifications

Output contact type

Isolated form C (SPDT)

Output contact rating

1 amp @ 30 VDC, 500 mA @120 VAC

I/O terminals wire size

#12--24 AWG

Figure 2-9 Main Board I/O Specifications

2.6.2 Harness Connection
Verify that the contactor harness is connected at the controller base (or at the controller disconnect switch, if equipped). See Figure 2-11.
Note: Verify that the power is disconnected before connecting or disconnecting the contactor harness.
2.6.3 Controller Ground
Verify that the grounding wire is connected from the controller's lower left mounting stud to the enclosure. This connection provides proper grounding that does not rely upon the door hinges.

Output 1 NO Output 1 C
Output 1 NC
Input 1B Input 1A

6

TB1

12

Output 2 NO Output 2 C Output 2 NC
Input 2B Input 2A

7

1

NC = normally closed

NO = normally open

C = common

6866

Figure 2-10 Input and Output Connections

1

2

GM85844

1. Contactor Harness Connection 2. Ground Connection
Figure 2-11 Contactor Harness and Controller Ground Connections

18 Section 2 Installation

TP-6834 4/14

2.7 Electrical Wiring
The transfer switch is factory-wired and tested. Field installation includes connecting the sources, loads, generator start circuit(s), and auxiliary circuits, if used.
Note: An approved protective device such as a molded-case circuit breaker or fused disconnect switch MUST be installed on both sources of incoming power for circuit protection and used as a disconnect device.
Refer to the wiring diagrams provided with the transfer switch. Observe all applicable national, state, and local electrical codes during installation.
Install DC, control, and communication system wiring in separate conduit from AC power wiring.
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.

DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Making line or auxiliary connections. Hazardous voltage can cause severe injury or death. To prevent electrical shock deenergize the normal power source before making any line or auxiliary connections.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
NOTICE
Foreign material contamination. Cover the transfer switch during installation to keep dirt, grit, metal drill chips, and other debris out of the components. Cover the solenoid mechanism during installation. After installation, use the manual operating handle to cycle the contactor to verify that it operates freely. Do not use a screwdriver to force the contactor mechanism.
2.7.1 Source and Load Connections
Determine the cable size. Refer to the transfer switch dimension drawing to determine the size and number of conductors that can be used. Make sure that the cables are suitable for use with the transfer switch lugs. Watertight conduit hubs may be required for outdoor use.
Drill the entry holes. Cover the internal components of the ATS to protect them from metal chips and construction grit. Then drill entry holes for the conductors at the locations shown on the enclosure drawings. Remove debris from the enclosure with a vacuum cleaner.
Note: Do not use compressed air to clean the switch. Cleaning with compressed air can cause debris to lodge in the components and damage the switch.

TP-6834 4/14

Section 2 Installation 19

Install and test the power cables. Leave sufficient slack in the power leads to reach all of the power connecting lugs on the power switching device. Test the power conductors before connecting them to the transfer switch. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. Pulling cables can damage insulation and stretch or break the conductor's strands.
Test the cables after pulling them into position and before they are connected to verify that they are not defective and that they were not damaged during installation.
Connect the cables. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Clean cables with a wire brush to remove surface oxides before connecting them to the terminals. Apply joint compound to the connections of any aluminum conductors.
Refer to the wiring diagram provided with the switch. The connection points on the contactor are labeled Normal, Emergency, and Load. Be sure to follow the phase markings (A, B, C, and N). For single-phase systems, connect to A and C.

Note: Connect the source and load phases as indicated by the markings and drawings to prevent short circuits and to prevent phasesensitive load devices from malfunctioning or operating in reverse.
Tighten the lugs. Verify that all connections are consistent with drawings before tightening the lugs. Tighten all lug connections to the torque values shown in Figure 2-12. Carefully wipe off any excess joint compound after tightening the terminal lugs.

Bolt Torque

Socket Size Across Flats, in.

Nm

1/8

5

Ft. lb. 4

5/32

11

8

3/16

14

10

7/32

16

12

1/4

23

17

5/16

31

23

3/8

42

31

1/2

57

42

9/16

68

50

Figure 2-12 Tightening Torque for Lugs

2.7.2 Engine Start Connection
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Prevent the generator set from starting by pressing the OFF button on the generator controller; disconnecting power to the generator engine start battery charger, if installed; and disconnecting all generator engine start battery cables, negative (--) leads first.
Connect the generator set remote starting circuit to the engine start terminals located on the transfer switch contactor assembly. See Figure 2-14 through Figure 2-19 for the locations of the engine start terminals, which are labeled on the unit with a red decal. Refer to the generator set installation manual for wire size specifications.
The engine start contact ratings are shown in Figure 2-13.

20 Section 2 Installation

TP-6834 4/14

2.7.3 Auxiliary Contacts
Connect the auxiliary contacts to customer-supplied alarms, remote indicators, or other devices. Auxiliary contacts provide contacts that close when the transfer switch is in the Normal position and contacts that close when the transfer switch is in the Emergency position.

Refer to the schematic diagram provided with the transfer switch to identify which auxiliary contacts are closed on Normal and which are closed on Emergency.
The auxiliary contact ratings are shown in Figure 2-13. Figure 2-14 through Figure 2-19 show the locations of the auxiliary contacts for different models.

Contacts
Engine Start Contacts Auxiliary Contacts, KSS (40--600A) Auxiliary Contacts, KSS (800--1000A)

Resistive Load
2 A @ 30 VDC 15 A @ 250 VAC 15 A @ 480 VAC

Auxiliary Contacts, KSP

15 A @ 480 VAC

Figure 2-13 Contact Ratings

Inductive Load
N/A N/A 15 A @ 250 VAC; 6 A @ 500 VAC
15 A @ 250 VAC; 6 A @ 500 VAC

Motor Load

NC

NO

N/A

N/A

N/A

N/A

5 A @ 125 VAC; 3 A @ 250 VAC; 1.5 A @ 500 VAC

2.5 A @ 125 VAC; 1.5 A @ 250 VAC; 0.75 A @ 500 VAC

5 A @ 125 VAC; 3 A @ 250 VAC; 1.5 A @ 500 VAC

2.5 A @ 125 VAC; 1.5 A @ 250 VAC; 0.75 A @ 500 VAC

2 2

1
1. Engine start terminal location 2. Auxiliary contacts

tp6225

Figure 2-14 Engine Start and Auxiliary Contact Locations, 40--225 Amp Standard-Transition Switches

1

1. Engine start terminal location 2. Auxiliary contacts

tp6225

Figure 2-15 Engine Start and Auxiliary Contact Locations, 400--600 Amp Standard-Transition Switches

TP-6834 4/14

Section 2 Installation 21

2 1
2
1
adv6906
1. Engine start contacts 2. Auxiliary contacts
Figure 2-17 Engine Start and Auxiliary Contact Locations, 100--200 Amp Programmed-Transition Switches
1 2

2

1. Engine start connection 2. Auxiliary contacts

tp6447

Figure 2-16 Engine Start and Auxiliary Contact Locations, 800--1000 Amp Standard-Transition Switches

1. Engine start contacts 2. Auxiliary switches

adv6907

Figure 2-18 Engine Start and Auxiliary Contact Locations, 400 Amp Programmed-Transition Switches

22 Section 2 Installation

TP-6834 4/14

2.8 Communication and

1

Accessory Connections

See Section 3 for accessory and communication connection instructions.
2

2.9 Functional Tests
After completion of the mechanical installation and all electrical connections, perform the functional tests described in Section 4. The procedures in Section 4 are required to complete the installation and startup of the transfer switch.

1. Engine start contacts 2. Auxiliary contacts

adv6908

Figure 2-19 Engine Start and Auxiliary Contact Locations, 600 Amp Programmed-Transition Switches

TP-6834 4/14

Section 2 Installation 23

Notes

24 Section 2 Installation

TP-6834 4/14

Section 3 Communication and Accessory Connections

3.1 Introduction
This section explains the connection of communication cables and factory-installed accessories.
Also refer to the following documentation for instructions to install, connect, and operate optional accessories.
D Transfer switch wiring diagrams.
D Installation instructions or diagrams provided with loose accessory kits.
3.2 Communication Connections
The Decision-Makerr MPAC 750 and MPAC 1200 controllers are equipped with a USB port and a Modbus port with an RS-485 connector. An Ethernet communication board is optional.
3.2.1 USB Port SiteTech Connection
A personal computer and Kohlerr SiteTecht software can be used for changing controller settings. Use a USB cable to connect the controller to a personal computer.
See Figure 3-1 for the USB port location on the front of the controller assembly. Remove the small port cover and use a USB cable with a mini-B connector to connect the controller's USB port to the computer.
See TP-6701, SiteTech Software Operation Manual, for instructions to use the software. Disconnect the USB cable from the controller and replace the port cover when finished.
1

1. USB connection (below port cover)

GM85888

Figure 3-1 USB Connection for SiteTech (MPAC 1200 controller shown)

3.2.2 Modbus Connection
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
See Figure 3-2 for the RS-485 Modbus connector location.
Use serial connections to TB2 on the controller to connect the transfer switch to a personal computer for system monitoring, the optional remote annunciator, or a Modbus network. See Figure 3-4.
Notice that a 121 ohm terminating resistor is recommended on the last device in a network. If there is only one device, a terminating resistor may be required depending on the cable distance and communication speed. Long cables and high speeds will increase the need for a terminating resistor.
The serial port is an isolated RS-485 port with connection speeds of 9.6, 19.2, and 57.6 kbps. Use shielded twisted-pair cable to connect to the RS-485 connectors on the controller's terminal strip TB2 for serial connections. For connection to a PC, use a USB to RS-485 converter.
Connect the Modbus input and output to the terminals shown in Figure 3-3. Use #12-24 AWG shielded, twisted-pair wire. Belden cable #9841 or equivalent is recommended. Connect one end of the shield to ground. Leave the other end of the shield disconnected. Tighten the connections to 0.5 Nm (4.4 in. lb.).

TP-6834 4/14

Section 3 Communication and Accessory Connections 25

Use Modbus RTU (remote terminal unit) protocol for communication through the serial port. A map of the Modbus codes for this controller is available. Contact your local distributor/dealer.
Note: Modbusr applications require a Modbus software driver written by a trained and qualified systems programmer.
1

USB port

RS-485 *

USB to RS-485 port converter
PC
Terminating resistor may be required [
(121 Ohms)

In Device Out

USB port

RS-485 *

2

USB to RS-485 port converter

In Device Out

PC

RS-485 *

1. RS-485 Modbus connections 2. Access opening for RS-485 cables

GM85884

Figure 3-2 Modbus Connections (controller cover removed for illustration only)

Input

Cable shield

GND1 B1 (+) A1 (--)

1

3

TB2

4

6

In Device Out
In Last Out Device
Terminating resistor [, (121 Ohms)
* Use Belden #9841 or equivalent shielded, twisted-pair communication cable for RS-485 connections. Ground one end of the cable shield. Leave the other end of the cable shield disconnected.
[ Long cables and high communication speeds will require a terminating resistor. Use 121 ohm resistor X-6058-27.
Figure 3-4 Serial Connections

RS-485 *

GND1 B1 (+) A1 (--)

Cable shield

Output

Customer connections
Figure 3-3 Modbus RS-485 Connections

26 Section 3 Communication and Accessory Connections

TP-6834 4/14

3.2.3 Ethernet Connection
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
The Ethernet communication accessory board is required for connection to the Ethernet. The Ethernet communication board is an optional accessory for the MPAC 750 and MPAC 1200 controllers. The communication board connects to the controller board as shown in Figure 3-5.
1

The Ethernet communication accessory board allows the transfer switch to be connected to a building's Ethernet network to communicate with personal computers connected to the same subnet.
Note: For an ethernet connection, obtain an IP address and subnet mask number from the local system administrator.
Ethernet Port. The ethernet port is a standard RJ-45 jack. See Figure 3-5 for the location of the Ethernet port. Use Category 5e or better cable to connect the controller to the building's network.
Use the controller's Setup menus or a personal computer connected to the controller's USB port and Kohler SiteTech software to set the communication parameters. The Ethernet communication board may have a default IP address assigned at the factory for test purposes. See Figure 3-6. Change the IP address to an address owned by the user. See the controller operation manual for instructions to set the communication parameters.
The transfer switch controller does not operate as a Modbus-to-Ethernet converter for other devices in a network. For multiple device networks connected to the personal computer through the Ethernet, use a Modbus-to-Ethernet converter for the other devices in the network. See Figure 3-7 and instruction sheet TT-1405, provided with the converter, for connection instructions.
The controller can communicate with up to five (5) simultaneous TCP/IP (ethernet) connections. These five connections do not include the RS-485 serial port. In the extreme case, five users may be communicating with the controller via TCP/IP network connections and another may be communicating through the serial port, for a total of six (6) communication channels. As the controller is asked to communicate with more and more outside devices, the communication will slow down.

12
GM85884
1. Ethernet communication board with RJ-45 connector 2. Access opening for Ethernet cable
Figure 3-5 Ethernet Board (controller cover removed for illustration only)

TP-6834 4/14

Section 3 Communication and Accessory Connections 27

Modbusr TCP/IP Category 5e

Ethernet Network

Modbusr TCP/IP Category 5e

PC IP xx.xx.xx.02

Note: The PC and the ATS must be on the same subnet.
Note: A crossover cable can be used to connect the PC to the ATS controller through the Ethernet port.

Figure 3-6 Remote Network (Ethernet) Connection

MPAC Controller with Ethernet comm.
board IP xx.xx.xx.03

Modbusr TCP/IP
PC IP xx.xx.xx.02

Modbusr TCP/IP

Ethernet Network

Modbusr TCP/IP Category 5e

MPAC Controller with Ethernet comm.
board IP xx.xx.xx.03

Modbusr TCP/IP Category 5e

Modbusr RTU
RS-485

Converter, Modbusr/Ethernet
IP xx.xx.xx.05

Device RS-485

Device

PC IP xx.xx.xx.01
Figure 3-7 Ethernet Connections to Multiple-Device Network

Terminating resistor (121 Ohms)

RS-485 Last device

28 Section 3 Communication and Accessory Connections

TP-6834 4/14

3.3 Accessory Modules (MPAC 1200 only)
DANGER

Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.

Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
Accessory modules are available with the MPAC 1200 controller. This section provides specifications and field connection information for factory-installed accessory modules. If the modules are not factory-installed, follow the instructions provided with the kits to install the mounting assembly and modules.
The transfer switch uses a standard bus system for connecting accessory modules to the controller. This bus incorporates a standard serial communication interface for passing data back and forth between the main logic board and the assemblies on the expansion bus.
The module mounting kit holds up to five optional modules. Add the current draw for all modules installed to determine the total current draw. See Figure 3-8. The total current drawn by all modules must not exceed 300 mA. If an External Battery Module is installed and connected to a battery, there is no current restriction. The External Battery Module, if used, must be the last board on the bus.

Module Current Draw Specifications, mA

Alarm Module

75

Standard I/O Module

75

High Power I/O Module

100

Note: EBSM required if total current is higher than 300 mA.

Figure 3-8 Module Current Requirements

TP-6834 4/14

3.3.1 Accessory Module Mounting
Mount the accessory modules on the module mounting plate. Starting at the end of the module mounting assembly nearest the cable connection, install any I/O modules first, then install the alarm board, if used. The external battery module, if used, must be the last module. See Figure 3-9. The alarm board has a fixed Modbus address = 5.
Note: Some models may have the I/O module assembly installed with the cable connection end pointing to the side or the bottom. Regardless of the actual orientation of the assembly, the I/O modules must be installed closest to the cable connection, followed by the alarm module and then the external battery module, if used.
1

2 2 2 3

4

5

GM46258

1. Cable connection (defined as the TOP regardless of orientation)
2. I/O modules (if equipped) 3. Alarm module (if equipped) 4. External battery module (must be last, if equipped) 5. Mounting plate
Figure 3-9 Module Mounting

Section 3 Communication and Accessory Connections 29

3.3.2 Input/Output (I/O) Modules
Two types of input/output modules are available. The standard I/O Module has two inputs and six outputs. The high-power I/O module has two inputs and three outputs. See Figure 3-10 through Figure 3-13 for I/O module illustrations and specifications.
1
2

1

2

3

3

4
1. Input LEDs 7 and 8 for inputs 1 and 2 2. Input connector (see Figure 3-14) 3. Output connector 4. Output LEDs 1--6

GM41093

Figure 3-10 Standard Input/Output Module

Inputs

Available Inputs

2

Input Definition

Contact Closure

Current

5 mA Max

Connection Type

Terminal Strip

Wire Size

#14-24 AWG

Max Distance
Outputs

700 feet

Outputs Available Contact Type

6 Form C (SPDT)

Contact Voltage Rating

2 A @ 30 VDC 500 mA @ 125 VAC

Connection Type Wire Size

Terminal Strip #14-24 AWG

Figure 3-11 Standard I/O Module Specifications

4
1. Input LEDs 1 and 2 2. Input connector (see Figure 3-14) 3. Output connector 4. Output LEDs 3--5 for outputs 1, 2, and 3

GM42186

Figure 3-12 High-Power Input/Output Module

Inputs

Available Inputs

2

Input Definition

Contact Closure

Current

5 mA Max

Connection Type

Terminal Strip

Wire Size

#14-24 AWG

Max Distance

700 feet

Outputs

Outputs Available

3

Contact Type

Form C (SPDT)

Contact Voltage Rating

12 A @ 24 VDC 12 A @ 250 VAC 10 A @ 277 VAC 2 A @ 480 VAC

Connection Type

Terminal Strip

Wire Size

#14-24 AWG

Environmental Specifications

Temperature

--40C to 85C (--40F to 185F)

Humidity

35% to 85% noncondensing

Figure 3-13 High-Power I/O Module Specifications

30 Section 3 Communication and Accessory Connections

TP-6834 4/14

Use 14-24 AWG cable to connect to inputs and outputs. See Figure 3-14.
LEDs on the module circuit board light to indicate that each input or output is active.
Note: Each I/O module must have unique address.
Use the address DIP switches on the I/O module to assign a unique (different) address to each module as shown in Figure 3-15. Assign addresses in order from 1 to 4. An LED for each DIP switch lights to indicate that the switch is closed.
The alarm module's fixed address is 5. The battery module's fixed address is 6.
See the controller operation manual for instructions to assign functions to each input and output. Inputs and outputs can also be assigned using a personal computer with Kohlerr SiteTecht software or over Modbus. See TP-6701, SiteTech Operation Manual, or TP-6113, Modbus Protocol Manual.

INPUT 2

INPUT 1

refGM41093
Figure 3-14 I/O Module Input Connections (TB1 or TB10)

3.3.3 External Battery Supply Module (EBSM)
The external battery supply module kit allows connection to the generator set engine start battery(ies) or other batteries to provide 12 VDC power to the ATS controller. The external battery supply module kit is required for the following applications:
D Systems using extended engine start time delays. The EBSM provides power to the ATS controller during extended time delays longer than 15 seconds, when neither the Normal nor the Emergency source is available.
D Installations with frequent utility power outages. The EBSM provides power to the ATS controller when neither source is available, preserving the controller's backup battery.
D Transfer switches equipped with multiple accessory modules that require a total of more than 300 mA current. See Figure 3-8.
The EBSM produces 2 amps at 12 VDC with 9--36 VDC input. The EBSM input is reverse-polarity protected. The EBSM outputs a low battery voltage signal when the external battery voltage falls below 11 VDC for a 12-volt system or 22 VDC for a 24-volt system. The module is shown in Figure 3-16.
1

Both switches OFF 3
Address=1 shown

DIP Switch

1

2

Off

Off

On

Off

Off

On

On

On

Address
1 2 3 4

Figure 3-15 Address DIP Switch Settings

4

2

1. Connector P20

GM42227-A

2. LED indicators

3. Battery input connection terminal block TB13

4. 12/24 volt DIP switch SW11-1. OFF=12 VDC, ON = 24 VDC

Figure 3-16 External Battery Supply Module

TP-6834 4/14

Section 3 Communication and Accessory Connections 31

The external battery supply module kit includes one external battery supply circuit board and the circuit board mounting components. A module mounting kit is required for installation of the external battery supply module. See Section 3.3.1. Obtain a module mounting kit if one is not already installed and follow the instructions provided with the kits to install the mounting assembly and modules.

The battery voltage selection DIP switch SW11-1 allows selection between 12-volt and 24-volt systems for low battery voltage sensing and indication. Connect one or two batteries to the external battery supply module. Use a battery charger to maintain the battery(ies) connected to the EBSM.

DIP Switch SW11-1 Setting

Battery Voltage

OFF

12 VDC

ON

24 VDC

Figure 3-17 Battery Voltage Selection

EBSM Connection and Voltage Setting
1. Use #14-28 AWG wire to connect one or two batteries to terminal block TB13. (A second battery can be connected but is not required.) Follow the marking on the board for the positive (+) and negative (--) connections. See Figure 3-16 and Figure 3-17.
Note: If the battery connections are reversed, red LED1 or LED2 will light. See Figure 3-16.
2. Set voltage selector switch SW11-1 to 12 or 24VDC. See Figure 3-16 and Figure 3-17. Switch SW11-2 is not used.
Note: The EBSM has no address switches but must be the last board on the bus.

3.3.4 Alarm Module
See Figure 3-18 for the optional alarm module. A module mounting kit is required for installation of the alarm module. See Section 3.3.1. The functions provided by this board are: D 90 dB Audible alarm (any alarm function can be
programmed to trigger the audible alarm) D Chicago alarm operation D Preferred source selection D Supervised transfer control (supervised transfer
control switch required) D Connection for external alarm The alarm board has a fixed address = 5.
1
2

4

3

1. Supervised Transfer Switch Connection, P22 2. External Alarm Connection, TB 14 3. Alarm Indicator, LED1 4. DIP Switches
Figure 3-18 Alarm Module

GM40764

32 Section 3 Communication and Accessory Connections

TP-6834 4/14

Alarm Board DIP Switches

There are four DIP switches on the alarm module board. Some of the switches are not used. See Figure 3-19. To enable the preferred source selection, set DIP switch 1 to ON. If the supervised transfer switch is installed on the ATS, set DIP switch 2 to ON.

DIP Switch Function

1

Preferred source selection

2

Supervised transfer enable

3

Not used

4

Not used

Figure 3-19 Alarm Board DIP Switches

Preferred Source Selection
The alarm module is required for preferred source selection. To enable the preferred source selection, set DIP switch 1 to ON. Then see the controller operation manual for instructions to select Source N or Source E as the preferred source.

External Alarm
A customer-supplied external alarm horn can be connected to the alarm module at terminal block TB14. Connect to the normally open or normally closed contact as recommended by the alarm manufacturer's instructions. See Figure 3-20.

Item

Specification

Wire Size

#12-22 AWG Cu

Contact Voltage Rating

500 mA @ 120 VAC 250 mA @ 240 VAC

Figure 3-20 External Alarm Connection Specifications

Audible Alarm Setup
The alarm board is equipped with a 90 dB audible alarm. The audible alarm can be set to sound under selected fault conditions. Use the Common Alarms Setup menu to assign functions to the audible alarm. See the controller operation manual for instructions to set Audible Alarm: Y for each function that should trigger the alarm.
Alarm Operation, Normal Mode
In Normal Mode, the horn sounds anytime a fault event happens in the system. The horn continues to sound unless the alarm silence button is pressed. When the fault is cleared, the alarm silence is ended and reset for the next alarm.
Alarm Operation, Chicago Alarm Mode
Chicago Alarm mode requires the horn to sound and a lamp or LED to light when the switch is in the emergency (non-preferred) position. The horn continues to sound unless the alarm silence button is pressed. When the fault is cleared, the alarm silence is ended and reset for the next alarm.
For Chicago Alarm Mode, use the Common Alarm Setup menu to assign the necessary faults and conditions to the audible alarm. See the controller operation manual for instructions to assign common faults. Be sure to assign the Contactor in Standby condition to trigger the audible alarm.
A remote alarm or indicator light can also be connected to the alarm board to indicate the alarm condition, as described previously. See External Alarm.

TP-6834 4/14

Section 3 Communication and Accessory Connections 33

Alarm Silence Mode
In Alarm Silence Mode, the horn is disabled. Alarm Silenced appears on the display and the system alert LED lights.
The Alarm Silenced condition can be assigned to a programmable output. See the controller operation manual for instructions to assign outputs.

Instructions to Silence the Alarm in Normal and Chicago Alarm Modes
When the alarm is activated, the word Alarm appears on the main display menu above the first button. See Figure 3-21. Press the Alarm button to open the Reset menu. Then press the button labeled Reset to silence the alarm.

System Ready LD Exer 12/14 @ 16:00 Norm 480V Emer 480V
Alarm View Set Test

Reset To Silence Alarm

B

Y Reset Main

Reset

Status or Fault Description Alarm Silenced

B

Y Reset Main

Figure 3-21 Alarm Silence

3.4 Heater
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
An anti-condensation heater kit is available. The strip heater is controlled by a hygrostat to raise the temperature inside the enclosure above the dew point to prevent condensation. Figure 3-22 shows a typical location of the heater kit components inside the enclosure.
The installer must connect 120 VAC power to the terminal block near the hygrostat. See Figure 3-23 and Figure 3-24. The heater and hygrostat are connected to power through a 15-amp circuit breaker.
The relative humidity setting on the hygrostat is adjustable from 35% to 95%. A setting of 65% is recommended.
Because of space limitations in the smaller enclosures, 30--225 Amp Model KSS switches can include either an enclosure heater or a surge protection device (SPD), but not both.

34 Section 3 Communication and Accessory Connections

TP-6834 4/14

HYGROSTAT
1
CIRCUIT BREAKER

2

TERMINAL BLOCK

HEATER

120 VAC ONLY CUSTOMER SUPPLIED

Right Side View
1. Hygrostat assembly, see Figure 3-23 2. Strip heater with guard
Figure 3-22 Heater Location, Typical

GM69824

Figure 3-24 Heater Connections

1

GM71278

2

3

1. 120 VAC power connection terminal block 2. Circuit breaker 3. Relative humidity adjustment control
Figure 3-23 Hygrostat Assembly, Typical

GM71056

TP-6834 4/14

Section 3 Communication and Accessory Connections 35

3.5 Load Shed (Forced Transfer to OFF, KSP with MPAC 1200 only)
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (--) leads first. Reconnect negative (--) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
The load shed (forced transfer to OFF) accessory must be factory-installed. The load shed accessory is available only on programmed-transition transfer switches with the MPAC 1200 controller. See Figure 3-25 for an illustration of the load shed acessory.
The load shed function requires an external signal (contact closure) to initiate transfer to the OFF position.

Connect the external contact to input #1 (if available) or input #2 on connector TB1 on the main logic board. See Figure 3-26. Use #12--24 AWG wire and tighten to 0.5 Nm (4.4 in. lb.).
Use the Input/Output setup menu or Kohler SiteTech software to assign the connected input (Main Board Input #1 or #2) to the forced transfer to off function. If the external contact is connected to a different input connection on an optional I/O module, assign the forced transfer to off function to that input.

Figure 3-25 Load Shed Accessory (for identification)

GM23469

36 Section 3 Communication and Accessory Connections

TP-6834 4/14

1
TB1

12

6

MLB Input 1

MLB Input 2 (alternate connection)

7

1

#12--24 AWG wire 0.5 Nm (4.4 in. lb.)
1. Input/output terminal strip TB1

MPAC Controller Circuit Board

Figure 3-26 Forced Transfer to Off Input Connection (for factory-installed load shed kits)

GM89713

TP-6834 4/14

Section 3 Communication and Accessory Connections 37

3.6 Programmable Exerciser
An optional programmable exerciser is available for transfer switches equipped with the Decision-Makerr MPAC 750 controller.
The optional programmable exerciser is a 7-day timer that allows programming of up to 8 on/off events per day. See Figure 3-27. Use the exercise timer to schedule weekly loaded or unloaded exercise runs in addition to the exercise time set through the ATS controller. The timer is installed inside the ATS enclosure.
The programmable exerciser uses the Remote Test input to the transfer switch controller. Refer to the instruction sheet provided with the exerciser for installation, connection, loaded/unloaded test selection, and programming instructions. See Section 2.6.1 for input connection information.
A personal computer and Kohlerr SiteTecht software are required to set up the remote exerciser. SiteTech software is available to Kohler-authorized distributors and dealers.

3.7 Other Accessories
Refer to the following documentation for instructions to install, connect, and operate optional accessories.
D Transfer switch wiring diagrams.
D Installation instructions provided with loose accessory kits.
D Controller Operation Manual. See List of Related materials in the Introduction section of this manual for document numbers.

Figure 3-27 Programmable Exerciser

38 Section 3 Communication and Accessory Connections

TP-6834 4/14

Section 4 Functional Tests and Setup

4.1 Introduction
Be sure to perform all of the functional tests described in this section before putting the transfer switch into operation.
The functional tests include the following checks:
D Manual Operation Test D Voltage Checks D Automatic Operation Test
Note: Perform these checks in the order presented to avoid damaging the ATS.
Read all instructions on the labels affixed to the automatic transfer switch before proceeding.
To complete the installation, follow the instructions in this section to:
D Set the time, date, and exercise schedule on the controller.
D Perform the system startup procedures listed on the startup form.
D Register the unit using the Kohlerr online Warranty Processing System.
4.2 Manual Operation Test
If you have not already done so, test the contactor manual operation before proceeding to the voltage check and electrical operation test.
Note: Disable the generator set and disconnect the power by opening the circuit breakers or switches for both sources before manually operating the transfer switch.
Follow the instructions in the Installation Section to check the transfer switch manual operation.
A contactor in normal and serviceable condition transfers smoothly without binding when operated manually. Do not place the transfer switch into service if the contactor does not operate smoothly without binding; contact an authorized distributor/dealer to service the contactor.

4.3 Voltage Check
The voltage, frequency, and phasing of the transfer switch and the power sources must be the same to avoid damage to loads and the transfer switch. Compare the voltage and frequency ratings of the utility source, transfer switch, and generator set, and verify that the ratings are all the same.
Use the voltage check procedure explained in this section to verify that the voltages and phasing of all power sources are compatible with the transfer switch before connecting the power switching device and controller wire harnesses together.
Follow the instructions provided with the generator set to prepare the generator set for operation.
Read and understand all instructions on installation drawings and labels on the switch. Note any optional accessories that have been furnished with the switch and review their operation.
Note: Source N is the source connected to the normal side of the contactor. Source E is the source connected to the emergency side of the contactor. Verify that the source leads are connected to the correct lugs before proceeding.
The voltage check procedure requires the following equipment:
D A digital voltmeter (DVM) with electrically insulated probes capable of measuring the rated voltage and frequency
D A phase rotation meter

TP-6834 4/14

Section 4 Functional Tests and Setup 39

DANGER
Hazardous voltage. Will cause severe injury or death.
Only authorized personnel should open the enclosure.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically. (600 volts and under)
Voltage Check Procedure
1. If Source N is a generator set, move the generator set master switch to the RUN position. The generator set should start.
2. Close the Source N circuit breaker or switch.
3. Use a voltmeter to check the Source N (normal) phase-to-phase and phase-to-neutral (if applicable) terminal voltages and frequency.
a. If Source N is the utility and the measured input does not match the voltage and frequency shown on the transfer switch nameplate, STOP! Do not proceed further in installation because the transfer switch is not designed for the application--call your distributor/dealer to order the correct transfer switch.
b. If Source N is a generator set and the generator set output voltage and frequency do not match the nominal system voltage and frequency shown on the transfer switch nameplate, follow the manufacturer's instructions to adjust the generator set. The automatic transfer switch will only function with the rated system voltage and frequency specified on the nameplate.

4. Use a phase rotation meter to check the phase rotation at the Source N (normal) terminals. Rewire the transfer switch Source N terminals to obtain the correct phase sequence if necessary.
Note: The default setting for the phase rotation on the controller is ABC. If the application uses a phase rotation of BAC, refer to the controller Operation Manual for instructions to change the phase rotation setting on the controller.
5. If the source is a generator set, stop the generator set by moving the master switch to the OFF position.
6. Disconnect Source N by opening upstream circuit breakers or switches.
7. Repeat steps 1 through 5 for Source E. Then proceed to step 8.
8. Disconnect both sources to the transfer switch by opening the circuit breakers or switches.
9. Close and lock the transfer switch enclosure door.
10. Reconnect both power sources by closing the circuit breakers or switches.
11. Move the generator set master switch to the AUTO position.
Note: If the engine cooldown time delay setting is not set to zero (default setting), the generator set may start and run until the Engine Cooldown Time Delay ends.
12. Perform the lamp test and then proceed to the automatic operation test.
4.4 Automatic Operation Test
Check the transfer switch's automatic control system immediately after the voltage check. Refer to the controller Operation Manual for instructions to run the automatic operation test.
Note: Close and lock the enclosure door before starting the test procedure.

40 Section 4 Functional Tests and Setup

TP-6834 4/14

4.5 System Setup
Set the controller's current time and date. See the controller Operation Manual for instructions.
The transfer switch is factory-set with default settings for time delays and other parameters. See the controller Operation Manual for instructions to view and change settings, if necessary.
Note: Use caution when changing transfer switch settings. The source voltage and frequency settings must match the values shown on the transfer switch nameplate.
4.6 Exerciser Setup
Set the exerciser to start and run the generator set at least once a week. See the controller Operation Manual for instructions.
Transfer switches equipped with the Decision-Makerr MPAC 750 controller may also use the optional programmable exerciser. Refer to the instructions provided with the exerciser to schedule additional loaded or unloaded exercise runs.

4.7 User Interface Cover
The gasket-sealed, hinged user interface cover prevents unauthorized access to the transfer switch controls and protects the user interface from harsh environmental conditions. The cover is available as an optional accessory for NEMA 1 enclosures. NEMA 3R enclosures include the cover as standard equipment.
Use a customer-supplied padlock to lock the cover.
4.8 Startup Notification
Perform the system startup procedure explained on the Startup Notification Form. The Startup Notification Form covers all equipment in the power system. Complete the Startup Notification Form and register the power system using the Kohlerr online Warranty Processing System.

TP-6834 4/14

Section 4 Functional Tests and Setup 41

Notes

42 Section 4 Functional Tests and Setup

TP-6834 4/14

Appendix A Abbreviations

The following list contains abbreviations that may appear in this publication.

A, amp ABDC AC A/D ADC
adj. ADV
Ah AHWT
AISI
ALOP alt. Al ANSI
AO APDC API approx. APU AQMD AR AS
ASE ASME
assy. ASTM
ATDC ATS auto. aux. avg. AVR AWG AWM bat. BBDC BC
BCA BCI BDC BHP blk.
blk. htr. BMEP bps br. BTDC Btu Btu/min. C cal. CAN CARB CAT5 CB CC cc CCA ccw. CEC cert. cfh

ampere after bottom dead center alternating current analog to digital advanced digital control; analog to digital converter adjust, adjustment advertising dimensional drawing amp-hour anticipatory high water temperature American Iron and Steel Institute anticipatory low oil pressure alternator aluminum American National Standards Institute (formerly American Standards Association, ASA) anticipatory only Air Pollution Control District American Petroleum Institute approximate, approximately Auxiliary Power Unit Air Quality Management District as required, as requested as supplied, as stated, as suggested American Society of Engineers American Society of Mechanical Engineers assembly American Society for Testing Materials after top dead center automatic transfer switch automatic auxiliary average automatic voltage regulator American Wire Gauge appliance wiring material battery before bottom dead center battery charger, battery charging battery charging alternator Battery Council International before dead center brake horsepower black (paint color), block (engine) block heater brake mean effective pressure bits per second brass before top dead center British thermal unit British thermal units per minute Celsius, centigrade calorie controller area network California Air Resources Board Category 5 (network cable) circuit breaker crank cycle cubic centimeter cold cranking amps counterclockwise Canadian Electrical Code certificate, certification, certified cubic feet per hour

cfm

cubic feet per minute

CG

center of gravity

CID

cubic inch displacement

CL

centerline

cm

centimeter

CMOS complementary metal oxide

substrate (semiconductor)

com

communications (port)

coml

commercial

Coml/Rec Commercial/Recreational

conn. connection

cont.

continued

CPVC chlorinated polyvinyl chloride

crit.

critical

CSA

Canadian Standards

Association

CT

current transformer

Cu

copper

cUL

Canadian Underwriter's

Laboratories

CUL

Canadian Underwriter's

Laboratories

cu. in. cubic inch

cw.

clockwise

CWC city water-cooled

cyl.

cylinder

D/A

digital to analog

DAC

digital to analog converter

dB

decibel

dB(A) decibel (A weighted)

DC

direct current

DCR

direct current resistance

deg.,  degree

dept.

department

dia.

diameter

DI/EO dual inlet/end outlet

DIN

Deutsches Institut fur Normung

e. V. (also Deutsche Industrie

Normenausschuss)

DIP

dual inline package

DPDT double-pole, double-throw

DPST double-pole, single-throw

DS

disconnect switch

DVR

digital voltage regulator

E2PROM, EEPROM

electrically-erasable

programmable read-only

memory

E, emer. emergency (power source)

ECM

electronic control module,

engine control module

EDI

electronic data interchange

EFR

emergency frequency relay

e.g.

for example (exempli gratia)

EG

electronic governor

EGSA Electrical Generating Systems

Association

EIA

Electronic Industries

Association

EI/EO end inlet/end outlet

EMI

electromagnetic interference

emiss. emission

eng.

engine

EPA

Environmental Protection

Agency

EPS

emergency power system

ER

emergency relay

ES

engineering special,

engineered special

ESD

electrostatic discharge

est.

estimated

E-Stop emergency stop

etc.

et cetera (and so forth)

exh. ext. F FHM fl. oz. flex. freq. FS ft. ft. lb. ft./min. ftp g ga. gal. gen. genset GFI

exhaust external Fahrenheit, female flat head machine (screw) fluid ounce flexible frequency full scale foot, feet foot pounds (torque) feet per minute file transfer protocol gram gauge (meters, wire size) gallon generator generator set ground fault interrupter

GND, ground

gov.

governor

gph

gallons per hour

gpm

gallons per minute

gr.

grade, gross

GRD

equipment ground

gr. wt. gross weight

H x W x D height by width by depth

HC

hex cap

HCHT high cylinder head temperature

HD

heavy duty

HET

high exhaust temp., high

engine temp.

hex

hexagon

Hg

mercury (element)

HH

hex head

HHC

hex head cap

HP

horsepower

hr.

hour

HS

heat shrink

hsg.

housing

HVAC heating, ventilation, and air

conditioning

HWT

high water temperature

Hz

hertz (cycles per second)

IBC

International Building Code

IC

integrated circuit

ID

inside diameter, identification

IEC

International Electrotechnical

Commission

IEEE

Institute of Electrical and

Electronics Engineers

IMS

improved motor starting

in.

inch

in. H2O inches of water in. Hg inches of mercury

in. lb. inch pounds

Inc.

incorporated

ind.

industrial

int.

internal

int./ext. internal/external

I/O

input/output

IP

internet protocol

ISO

International Organization for

Standardization

J

joule

JIS

Japanese Industry Standard

k

kilo (1000)

K

kelvin

kA

kiloampere

KB

kilobyte (210 bytes)

KBus Kohler communication protocol

kg

kilogram

TP-6834 4/14

Appendix 43

kg/cm2 kilograms per square

centimeter

kgm

kilogram-meter

kg/m3 kilograms per cubic meter

kHz

kilohertz

kJ

kilojoule

km

kilometer

kOhm, k kilo-ohm

kPa

kilopascal

kph

kilometers per hour

kV

kilovolt

kVA

kilovolt ampere

kVAR kilovolt ampere reactive

kW

kilowatt

kWh

kilowatt-hour

kWm

kilowatt mechanical

kWth

kilowatt-thermal

L

liter

LAN

local area network

L x W x H length by width by height

lb.

pound, pounds

lbm/ft3 pounds mass per cubic feet

LCB

line circuit breaker

LCD

liquid crystal display

LED

light emitting diode

Lph

liters per hour

Lpm

liters per minute

LOP

low oil pressure

LP

liquefied petroleum

LPG

liquefied petroleum gas

LS

left side

Lwa LWL

sound power level, A weighted low water level

LWT

low water temperature

m

meter, milli (1/1000)

M

mega (106 when used with SI

m3 m3/hr. m3/min.

units), male cubic meter cubic meters per hour cubic meters per minute

mA

milliampere

man.

manual

max.

maximum

MB

megabyte (220 bytes)

MCCB molded-case circuit breaker

MCM one thousand circular mils

meggar megohmmeter

MHz

megahertz

mi.

mile

mil

one one-thousandth of an inch

min.

minimum, minute

misc.

miscellaneous

MJ

megajoule

mJ

millijoule

mm

millimeter

mOhm, mmilliohm

MOhm, Mmegohm

MOV

metal oxide varistor

MPa

megapascal

mpg

miles per gallon

mph

miles per hour

MS

military standard

ms

millisecond

m/sec. meters per second

mtg.

mounting

MTU

Motoren-und Turbinen-Union

MW

megawatt

mW

milliwatt

F

microfarad

N, norm. normal (power source)

NA

not available, not applicable

nat. gas natural gas

NBS

National Bureau of Standards

NC

normally closed

NEC

National Electrical Code

NEMA National Electrical Manufacturers Association

NFPA

National Fire Protection Association

Nm

newton meter

NO

normally open

no., nos. number, numbers

NPS

National Pipe, Straight

NPSC National Pipe, Straight-coupling

NPT

National Standard taper pipe thread per general use

NPTF National Pipe, Taper-Fine

NR

not required, normal relay

ns

nanosecond

OC

overcrank

OD

outside diameter

OEM

original equipment manufacturer

OF

overfrequency

opt.

option, optional

OS

oversize, overspeed

OSHA Occupational Safety and Health

Administration

OV

overvoltage

oz.

ounce

p., pp. page, pages

PC

personal computer

PCB

printed circuit board

pF

picofarad

PF

power factor

ph.,  phase

PHC

Phillipsr head Crimptiter (screw)

PHH

Phillipsr hex head (screw)

PHM

pan head machine (screw)

PLC

programmable logic control

PMG

permanent magnet generator

pot

potentiometer, potential

ppm

parts per million

PROM programmable read-only memory

psi

pounds per square inch

psig

pounds per square inch gauge

pt.

pint

PTC

positive temperature coefficient

PTO

power takeoff

PVC

polyvinyl chloride

qt.

quart, quarts

qty.

quantity

R

replacement (emergency)

power source

rad.

radiator, radius

RAM

random access memory

RDO

relay driver output

ref.

reference

rem.

remote

Res/Coml Residential/Commercial

RFI

radio frequency interference

RH

round head

RHM

round head machine (screw)

rly.

relay

rms

root mean square

rnd.

round

RO

read only

ROM

read only memory

rot.

rotate, rotating

rpm

revolutions per minute

RS

right side

RTDs Resistance Temperature

Detectors

RTU RTV RW SAE
scfm SCR s, sec. SI
SI/EO sil. SMTP SN SNMP
SPDT SPST spec specs sq. sq. cm sq. in. SMS SS std. stl. tach. TB TCP TD TDC TDEC TDEN
TDES TDNE
TDOE TDON temp. term. THD TIF tol. turbo. typ.
UF UHF UIF UL UNC UNF univ. URL
US UV V VAC VAR VDC VFD VGA VHF W WCR w/ WO w/o wt. xfmr

remote terminal unit room temperature vulcanization read/write Society of Automotive Engineers standard cubic feet per minute silicon controlled rectifier second Systeme international d'unites, International System of Units side in/end out silencer simple mail transfer protocol serial number simple network management protocol single-pole, double-throw single-pole, single-throw specification specification(s) square square centimeter square inch short message service stainless steel standard steel tachometer terminal block transmission control protocol time delay top dead center time delay engine cooldown time delay emergency to normal time delay engine start time delay normal to emergency time delay off to emergency time delay off to normal temperature terminal total harmonic distortion telephone influence factor tolerance turbocharger typical (same in multiple locations) underfrequency ultrahigh frequency user interface Underwriter's Laboratories, Inc. unified coarse thread (was NC) unified fine thread (was NF) universal uniform resource locator (web address) undersize, underspeed ultraviolet, undervoltage volt volts alternating current voltampere reactive volts direct current vacuum fluorescent display video graphics adapter very high frequency watt withstand and closing rating with write only without weight transformer

44 Appendix

TP-6834 4/14

Notes

TP-6834 4/14

45

Notes

46

TP-6834 4/14

TP-6834 4/14
E 2014 by Kohler Co. All rights reserved.

KOHLER CO. Kohler, Wisconsin 53044 Phone 920-457-4441, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455


Acrobat Distiller 10.1.7 (Windows)