N1030 Temperature Controller
Instructions Manual – V1.0x J
Brand: Novus Automation The symbols below are used on the equipment and throughout this document to draw the user's attention to important operational and safety information. Read the manual thoroughly before installing and operating the equipment. All safety-related instructions that appear in the manual must be observed to ensure personal safety and to prevent damage to either the instrument or the system. If the instrument is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. The controller must be fastened on a panel, following the sequence of steps described below: Figure 01 shows the electrical terminals of the controller: Table 01 shows the sensor types accepted and their respective codes and ranges. Access the parameter 'EYPE' in the INPUT level to select the appropriate sensor. The input type should be the first parameter configured. Modifications automatically change other related parameters. Verify configuration after any input type change. The controller has two outputs. Configure these outputs as Control Output (Ctrl) or Alarm Output (AL). The control strategy can be ON/OFF (when Pb = 0.0) or PID. PID parameters can be automatically determined using the auto-tuning function (Atun). The controller has 2 alarms assignable to any output channel. Alarm functions are described in Table 02. Important Note: Alarms configured with Hi, d IF, and d IFH also trigger their output on sensor fault. For example, a High Alarm (Hi) output will operate if the SPAL value is exceeded or if the sensor is broken. This option inhibits alarms if an alarm condition is present upon energization or transition from RUN YES to NO. The alarm is enabled only after a non-alarm condition followed by a new alarm occurrence. This is useful for minimum value alarms at start-up. Initial blocking is disabled for the 'iErr' (sensor break) function. Allows fine adjustments to the PV reading for compensation of sensor error. The controller's front panel is shown in Figure 02: Display of PV / Programming: Top display (red) shows the current Process Variable (PV). In configuration mode, it shows parameter names. Display of SP / Parameters: Bottom display (green) shows the Setpoint (SP). In configuration mode, it shows parameter values. TUNE Indicator: Lit when the controller is in the tuning process. OUT Indicator: Shows the actual state of the relay or pulse control output. A1 and A2 Indicators: Signal alarm situations. P Key: Used to navigate through menu parameters. Increment [up arrow] and Decrement [down arrow] Keys: Alter parameter values. Back Key: Used to go back to previous parameters. Upon power-up, the controller displays its firmware version for 3 seconds, then starts normal operation showing PV and SP values, with outputs enabled. For proper operation, parameters must be configured according to system requirements. Parameters are grouped into three levels: Pressing and holding the 'P' key for 2 seconds cycles through the levels (PV >> Atun >> Type >> PASS >> PV). Release 'P' to enter a level. Short presses of 'P' navigate within a level. The ':' key goes back. Parameters are displayed with a prompt (upper display) and value/condition (lower display). Protected levels are preceded by 'PASS'. PV + SP: Displays the measured variable (PV) on the higher display (red) and the control setpoint (SP) on the lower display (green). Enables auto-tuning for PID parameters (Pb, ir, dt). Defines the control strategy: Value of the P term in PID control, as a percentage of the input span. Adjustable from 0 to 500.0%. Setting to 0 enables ON/OFF control. Value of the I term in PID, in repetitions per minute (Reset). Adjustable from 0 to 99.00. Displayed only if proportional band is not zero. Value of the D term in PID, in seconds. Adjustable from 0 to 300.0 seconds. Displayed only if proportional band is not zero. Pulse Width Modulation (PWM) period in seconds. Adjustable from 0.5 to 100.0 seconds. Displayed only if proportional band is not zero. Hysteresis for ON/OFF control (in temperature units). Used only when the controller is in ON/OFF mode (Pb=0). Selects the input signal type. Refer to Table 01. Selects the decimal point position for PV and SP display. Offset value added to PV to compensate sensor error. Default: zero. Defines SP upper and lower limits for PV indication range. Does not limit Alarm SP configuration. Defines alarm functions from Table 02. Value defining the activation point for alarm outputs. For Differential alarms, represents deviations. No meaning for 'iErr' alarm. Defines the difference between PV values for alarm triggering and turning off. Inputs are factory calibrated. Recalibration requires a specialized professional. Do not alter parameters if unfamiliar. Protects parameters from unauthorized modifications. The 'Prot' parameter in the Calibration level determines protection strategy (access to levels). Protected levels require an Access Password. If no password is entered, parameters can only be viewed. The password is set via 'Pasc' and defaults to 1111. The system blocks access to protected parameters for 10 minutes after 5 consecutive incorrect password attempts. Allows defining a new password if forgotten. It only grants access to the 'Pasc' parameter. The master password is formed by the last three digits of the serial number plus 9000 (e.g., serial 07154321 -> master password 9321). Controller serial number is displayed by pressing [P] for 3 seconds. Auto-tuning determines PID parameters automatically. The process involves system oscillations and output switching. It may take several minutes. The 'TUNE' indicator remains lit during tuning. Wait for completion before use. If tuning is unsatisfactory, refer to Table 04 for manual adjustment guidelines. For further details on PID tuning, visit: www.novusautomation.com. Common errors are connection issues and inadequate programming. Reviewing these can prevent issues. The controller displays messages to help identify problems: Other error messages may indicate hardware problems requiring service. Inputs are factory calibrated. Recalibration requires qualified personnel. Do not attempt if unfamiliar. Note for Pt100 calibration: Ensure the simulator's minimum excitation current is compatible with the controller's 0.170 mA. The model is identified by a code (e.g., N1030-PR, N1030-RR) and power supply type (e.g., Blank for standard, 24V for 24V models). Warranty conditions are available on the Novus Automation website: www.novusautomation.com/warranty.Safety Alerts
Caution
Caution or Danger: Electrical Shock Hazard
Installation and Connections
Recommendations for Installation
Electrical Connections
Features
Input Type Selection
TYPE CODE RANGE OF MEASUREMENT Thermocouple J EcJ -110 to 950 °C (-166 to 1742 °F) Thermocouple K Pk -150 to 1370 °C (-238 to 2498 °F) Thermocouple T ct -160 to 400 °C (-256 to 752 °F) Pt100 PE -200 to 850 °C (-328 to 1562 °F) Outputs
Control Output (Ctrl)
Alarm Output (AL)
Function Description OFF Output is not used as alarm. Lo Alarm of Absolute Minimum Value. Triggers when the value of measured PV is below the value defined for alarm Setpoint (SPAL). Hi Alarm of Absolute Maximum Value. Triggers when the value of measured PV is above the value defined for alarm Setpoint (SPAL). d IF Alarm of Differential. In this function the parameters, SPAL represent the deviation of PV in relation to the SP of CONTROL. d IFL Alarm of Minimum Differential Value. It triggers when the value of PV is below the defined point by SP-SPAL. d IFH Alarm of Maximum Differential. Triggers when the value of PV is above the defined point by SP+SPAL. iErr Alarms of the Sensor Break. Activated when the Input presents problems such as interrupted sensor, bad connection, etc. Initial Blocking of Alarm
Offset
Operation
Controller Startup
Parameter Configuration
Parameters Description
Indication Screen
Tuning Cycle
Atun (AUTO-TUNE)
Pb (Proportional Band)
ir (Integral Rate)
dt (Derivative Time)
t (Level Time)
Hyst (Control Hysteresis)
A(t (Action Control)
Out1, Out2 (Output Assignment)
Input Cycle
Type (Input Type
dP.po (Decimal Point Position
Uni t (Units)
Offs (Sensor Offset
Sp.ll, Sphl (SP Limits)
Fval (Functions of Alarms)
Sp.al (Alarm SP)
Blal (Blocking Alarm)
Hyal (Hysteresis of Alarm)
Calibration Level
Configuration Protection
PROTECTION LEVEL PROTECTION LEVELS 1 Only the Calibration level is protected. 2 Calibration and Input levels. 3 Calibration, Input and Tuning levels. 4 All levels are protected, including SP. Access Password
Protection Access Password
Master Password
Determination of PID Parameters
Auto-Tuning Steps:
PARAMETER VERIFIED PROBLEM SOLUTION Band Proportional Slow answer Decrease Great oscillation Increase Rate Integration Slow answer Increase Great oscillation Decrease Derivative Time Slow answer or instability Decrease Great oscillation Increase Maintenance
Problems with the Controller
Process Variable Input Calibration
Specifications
Environmental Conditions:
Input:
Outputs:
Front Panel:
Electromagnetic Compatibility:
Safety:
Identification
Warranty