VT8300 Series Installation Guide
24 Vac Low Voltage
Commercial and Hotel/Lodging HVAC Fan Coil Applications

CONTENTS

Installation

2

Terminal Identification & Function

3

Terminal identification

3

Wiring

4

Typical Applications

5

2 pipe systems cooling and/or heating

6

4 pipe systems cooling and heating

7

2 pipe systems cooling or heating with reheat

8

Remote Sensor Accessories

8

Home Screen Display

9

How to Enter Setup Screen

10

Appendix

11

2
INSTALLATION
Location
· Do not install on outside wall. · Do not install in areas with direct heat source. · Do no install near any air discharge grill. · Do not install in areas exposed to direct sunlight · Ensure Controller has sufficient air circulation. · Ensure wall surface is flat and clean.
Installation
1. Remove security screw (if any) on bottom of Room Controller cover.
2. Open unit by pulling on bottom side of Room Controller (Figure 1). 3. Read FCC ID and IC label installed in cover before installing any
wireless product. 4. Ensure correct side of base faces up. 5. Pull cables 6in (15cm) out from wall. 6. Align base and mark location of two mounting holes on wall (Figure 2). 7. Install anchors in wall. 8. Insert cable in central hole of base. 9. Insert screws in mounting holes on each side of base. 10. Strip each wire 1/4in (0.6cm) from end. 11. Insert each wire and screw according to wiring chart (see following
pages). 12. Gently push excess wiring back into hole. 13. Gently align cover to top of base and snap in place from bottom
(Figure 3). 14. Install security screw.

Installation Guide VT8300 Series
Figure-1 Open the cover

· If replacing an existing Line Voltage FCU Controller, label wires before removal of Room Controller.
· Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing Controller.
· A short circuit or wrong wiring may permanently damage Room Controller or equipment.
· All VT8300 series controls are designed for use as operating controls only and are not safety devices. Tampering with the devices or unintended application of the devices will result in a void of warranty.
· This device must be installed to provide a separation distance of at least 8in (20cm) from all persons and must not be collocated or operating in conjunction with any other antenna or transmitter.

Figure-2 Install the base Figure-3 Reinstall cover

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

Installation Guide VT8300 Series TERMINAL IDENTIFICATION AND FUNCTION

Terminal identification
VT83xxU Description / Application
Internal Temperature Internal Humidity
1- BO1 2- BO2 3- BO3 4- BO4 5- RC / 24 V~ Hot 6- C / 24 V~ Com
7- RH 8- BO8 9- UO9 10- UO10 11- UO11 12- UO12
13- RS485 + 14- RS485 15- RS485 Ref 16- UI16 17- UI17 18- Scom
19- UI19 20- UI20 21- Scom 22- UI22 23- UI23 24- UI24

2 & 4 Pipe Control Type = On/Off
X Model Dependent
Not used Fan-L Fan-M Fan-H
24 V~ Hot 24 V~ Com
Aux Heat Aux Heat Normally Close Cool Valve Normally Close Heat Valve Normally Open Cool Valve Normally Open Heat Valve
BACnet MS-TP + BACnet MS-TP BACnet MS-TP Ref
UI16 Function UI17 Function
Common
UI19 Function Remote Room Sensor
Common Remote Supply Sensor
Not used Not used

Used in applications
2 & 4 Pipe Control Type = Floating
X Model Dependent
Not used Fan-L Fan-M Fan-H
24 V~ Hot 24 V~ Com
Aux Heat Aux Heat Close Cool Valve Close Heat Valve Open Cool Valve Open Heat Valve
BACnet MS-TP + BACnet MS-TP BACnet MS-TP Ref
UI16 Function UI17 Function
Common
UI19 Function Remote Room Sensor
Common Remote Supply Sensor
Not used Not used

3
2 & 4 Pipe Control Type = Analog
X Model Dependent
Not used Fan-L Fan-M Fan-H
24 V~ Hot 24 V~ Com
Aux Heat Aux Heat Not used Not used Analog Heat valve Analog Cool Valve
BACnet MS-TP + BACnet MS-TP BACnet MS-TP Ref
UI16 Function UI17 Function
Common
UI19 Function Remote Room Sensor
Common Remote Supply Sensor
Not used Not used

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

4
Wiring
Power and Fan (All Models) 3 Speed
LOW
MED
HIGH

2 Speed
LOW
HIGH

Installation Guide VT8300 Series Single Speed

HIGH

24 Vac

Transformer

BO8 Auxilliary Output Wiring Dry contact to end device 24 V~ maximum
RC (24 Vac) C (Common)
R
RH BO8 - Aux Heat

24 Vac power to relay

RC (24 Vac) C (Common)

RH

BO8 - Aux Heat

R

Main Outputs Wiring 22PPipipeeAAppplpicliactaiotinosns

Control type = On-Off

44 PPi4pipePeiApApeppAplipclipacltaiicotainotsinosns

UO9 UO11

Heating / Cooling valve

Com

OR

24Vac

Floating control

CCCooommm

UO10 NC UO12 NO

OR

222444VVVaaaC2cccC24oC24Vom4oVamVmacacc

Heating valve

CCCooommm

UO11 NO UO11 NC

OR

222444VVVaaaC2cccC24oC24Vom4oVamVmacacc

Cooling valve

UO11 UO9

Heating / Cooling valve CCCooommm OCOCOClplpoolpoeessesnneeCOCneCOColpCOCoolpmeosolpomenesmesnene

Analog control

UO12 UO10 UO11 UO9

CCCooommm COCCOCCOColoplpooolpmomeesmsesnneeCOCneCOColpCOCoolpmeosolpomenesmesnene OCOCOClplpoolpoeessesnneeCOCneCOColpCOCoolpmeosolpomenesmesnene

Heating valve Cooling valve

UO12

Heating / Cooling valve CCCooommm 202020-4-4-411VV10V0aa0VaVC20cVccdd-C204odC201cc-4Vocm-401oVa1mVV0mac0VadcVcdcdcc

UO11 UO12

CCCooommm C02C02C02--44o1-o14o100mmV0VmVVVaaV0C2dadcdc-0C2c4cc1o0C2c-401-om4V1o0VmVa0mVdVacVcdacdccc 202020--441-14100V0VVVVaaVC20dadcdc-C20c4cc1oC20c-401-om4V1o0VmVa0mVdVacVcdacdccc

Heating valve Cooling valve

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

Installation Guide VT8300 Series

TYPICAL APPLICATIONS

Schematic

3 Speed Fan

Normally Closed On/Off

Cooling / Heating

Sensor

Valve

Wiring
2 pipe system cooling and/or heating Control type = On / Off

2

BO2 - Fan L

3

BO3 - Fan M

4

BO4 - Fan H

5

RC (24 Vac)

6

C (Common)

24 Vac fan relays LOW MED HIGH

7

RH

8

BO8 - Aux Heat

9

UO9 NC

10

UO10

11

UO11

12

UO12

24 Vac Transformer Normally Closed

Room Temperature Control Thermostat

3 Speed Fan

Modulating Floating

Cooling / Heating

Sensor

Valve

Room Temperature Control Thermostat

18 Common 19 UI 19

Optional supply water temperature sensor

2 pipe system cooling and/or heating Control type = Floating

2

BO2 - Fan L

24 Vac fan relays LOW

3

BO3 - Fan M

4

BO4 - Fan H

5

RC (24 Vac)

MED HIGH

6

C (Common)

7

RH

24 Vac Transformer

8

BO8 - Aux Heat

9

UO9

10

UO10

11

UO11

12

UO12

Normally Closed

18 Common 19 UI19

Optional supply water temperature sensor

5
Settings
Mandatory · Pipe no = 2 pipes · CntrltTyp = On/Off · Fan Menu = (L-M-H) · FL time = N/A
If cooling only set:: · SeqOpera = Cooling only
If heating only set: · SeqOpera = Heating only
If heat / cool auto-changeover with a local water temperature sensor set: · SeqOpera = Cooling only · UI19 = COS
Mandatory · Pipe no = 2 pipes · CntrltTyp = Floating · Fan Menu = 0 (L-M-H) · FL time = as per actuator
If cooling only set: · SeqOpera = Cooling only
If heating only set: · SeqOpera = Heating only
If heat / cool auto-changeover with a local water temperature sensor set: · SeqOpera = Cooling only · UI19 = COS

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

6

Installation Guide VT8300 Series

Schematic

3 Speed Fan

Modulating Analog

Cooling / Heating

Sensor

Valve

Room Temperature Control Thermostat

Wiring
2 pipe system cooling and/or heating Control type = Analog

2

BO2 - Fan L

24 Vac fan relays LOW

3

BO3 - Fan M

4

BO4 - Fan H

5

RC (24 Vac)

MED HIGH

6

C (Common)

7

RH

24 Vac Transformer

8

BO8 - Aux Heat

9

UO9

10

UO10

11

UO11

12

UO12

0 to 10 Vdc
Normally Closed

18 Common 19 UI 19

Optional supply water temperature sensor

Settings
Mandatory · Pipe no = 2 pipes · CntrltTyp = Analog · Fan Menu = (L-M-H) · RA/DA = as per actuator
If cooling only set: · SeqOpera = Cooling only
If heating only set: · SeqOpera = Heating only
If heat / cool auto-changeover with a local water temperature sensor set: · SeqOpera = Cooling only · UI19 = COS

4 pipe system cooling and heating Control type = On / Off

3 Speed Fan

Normally Closed On/Off

Cooling Heating Valve Valve
Room Temperature Control Thermostat

2

BO2 - Fan L

24 Vac fan relays LOW

3

BO3 - Fan M

MED

4

BO4 - Fan H

HIGH

5

RC (24 Vac)

6

C (Common)

7

RH

8

BO8 - Aux Heat

9

UO9 NC

24 Vac Transformer

Mandatory · Pipe no = 4 pipes · CntrltTyp = On/Off · Fan Menu = (L-M-H) · SeqOpera = Cool/Heat

10

UO10

11

UO11 NC

12

UO12

Heating Normally Closed

Cooling

4 pipe system cooling and heating Control type = Floating

3 Speed Fan Modulating Floating

2

3

BO2 - Fan L BO3 - Fan M

24 Vac fan relays LOW
MED

Cooling Heating Valve Valve

4

BO4 - Fan H

5

RC (24 Vac)

6

C (Common)

7

RH

8

BO8 - Aux Heat

9

UO9

10

UO10

HIGH
Mandatory · Pipe no = 4 pipes · CntrltTyp = Floating
24 Vac Transformer
· Fan Menu = (L-M-H) · FL time = as per actuator · SeqOpera = Cool/Heat

11

UO11

Room Temperature Control Thermostat

12

UO12

Heating Cooling

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

Installation Guide VT8300 Series

7

Schematic
3 Speed Fan Modulating Analog
Cooling Heating Valve Valve
Room Temperature Control Thermostat

3 Speed Fan

Modulating Floationg

Cooling / Heating

Valve

Electric Reheat

Sensor

Room Temperature Control Thermostat

Wiring
4 pipe system cooling and heating Control type = Analog

Settings

2

BO2 - Fan L

24 Vac fan relays LOW

3

BO3 - Fan M

4

BO4 - Fan H

5

RC (24 Vac)

6

C (Common)

7

RH

8

BO8 - Aux Heat

9

UO9

10

UO10

MED

HIGH

24 Vac Transformer

Mandatory · Pipe no = 4 pipes · CntrltTyp = Analog · Fan Menu = (L-M-H) · RA/DA = as per actuator · SeqOpera = Cool/Heat

11

UO11

12

UO12

0 to 10 Vdc
Heating

0 to 10 Vdc
Cooling

2 pipe system cooling or heating with reheat Control type = Floating

2

BO2 - Fan L

24 Vac fan relays LOW

3

BO3 - Fan M

MED

4

BO4 - Fan H

HIGH

5

RC (24 Vac)

6

C (Common)

7

RH

8

BO8 - Aux Heat

9

UO9

10

UO10

11

UO11

12

UO12

Electric Reheat

24 Vac Transformer Normally Closed

Mandatory · Pipe no = 2 pipes · CntrltTyp = Floating · Fan Menu = (L-M-H) · FL time = as per actuator · SeqOpera = Cool/Reheat · UI19 = COS

18 SCom 19 UI 19

Optional supply water temperature sensor

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

8
REMOTE SENSOR ACCESSORIES

Installation Guide VT8300 Series

Model no. S3010W1000 S3020W1000

Description Wall mounted temperature sensor Wall mounted temperature sensor with override button and occupancy status
LED

The VT8300 Room Controller is compatible with remote mount temperature sensors using 10K type 2 NTC thermistors.
Note: If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Disconnecting the sensor(s) in the RS terminal will re-activate the internal sensor.
Features: · Each sensor can be configured for various averaging combinations · Optional occupancy led · Optional override key

VT8300
Series Controller

Wiring example of single remote room sensor

S3020W1000
Remote wiring 1 sensor S2-1= On, S2-2=On

S3010W1000
Remote wiring 1 sensor S2-1= On, S2-2=On

Common UI 20

SCom
OR
RS

SCom RS

BO8

Aux

24 Vac Com

C

UI17

DI

Dip switch setting for: 1 sensor

ON 12

S2-1 = ON S2-2 = ON

Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10K±3%, B25/85°C = 3975K±1.5%)

ºC ºF

Kohm

ºC ºF

Kohm

ºC ºF

Kohm

ºC ºF

Kohm

ºC ºF

-40 -40 324.3197

-20 -4 94.5149

0 32 32.1910

20 68 12.4601

40 104

-35 -31 234.4009

-15 5 71.2430

5 41 25.1119

25 77 10.0000

45 113

-30 -22 171.3474

-10 14 54.1988

10 50 19.7390

30 86 8.0694

50 122

-25 -13 126.6109

-5 23 41.5956

15 59 15.6286

35 95 6.5499

55 131

Kohm
5.3467 4.3881 3.6202 3.0016

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

Installation Guide VT8300 Series

9

HOME SCREEN DISPLAY

Hospitality User Interface Shown

Date Occupancy Status
Indoor Temperature
Indoor Humidity Outdoor Temperature
System Mode Short Network
Message

Time System Status
Fan Status
Up Arrow Increase Temperature Setpoint
Actual Setpoint
Down Arrow Decrease Temperature Setpoint Help

Fan Mode

Language Selection

Temperature Units

Note: User HMI is configurable and allows display functions such as Date, Time, Humidity, Outdoor Temperature, Setpoint, and others to be enabled or disabled by setting various parameters.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

10
HOW TO ENTER SET-UP SCREEN

Installation Guide VT8300 Series

Touch and hold this point for 3 seconds to enter set-up mode
Note: If a configuration/installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt shows to prevent access to device configuration components.

For more information on using and configuring the functions of the HMI, refer to the VT8300 User Interface Guide

SET-UP SCREEN DISPLAY
1/2 Setup
Network Configuration Setpoints - Display Service View Test Outputs Language Selection

Enter BACnet® & ZigBee® network settings Enter parameter configuration menu Enter setpoint & display settings Enter status and service view Enter output testing mode Enter language selection

Return to home screen

Discover Mode The Controller becomes discoverable on the wireless ZigBee® network for 1 minute (this button is hidden if ZigBee® settings are not configured)

General Note:
Adjustable parameter Non-adjustable parameter

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0429-03

www.viconics.com | sales@viconics.com

April 2016

Installation Guide VT8300 Series

11

APPENDIX A TERMINAL CORRESPONDANCE
The terminals of a VT8300 are identified differently and have a wider range of possible functions compared to those of any of the VT7300 series Room Controllers. Nonetheless, there is a direct correspondance of functions between the terminals of the VT7300 series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7300 Room Controller with a VT8300 Room Controller.

VT7300

Terminal name

Terminal ID

Binary Input 1

BI1

Binary Input 2

BI2

Universal Input 3

UI3

Sensor Common

Scom

Remote Sensor

RS

Sensor Common

Scom

Mix/Supply Sensor

MS

VT8300

Terminal name

Terminal ID

Universal Input 16

UI16

Universal Input 17

UI17

Universal Input 19

UI19

Terminal 18 Common COM

Universal Input 20

UI20 - RS

Terminal 21 Common COM

Universal Input 22

UI22 - SS

APPENDIX B POWER OUTAGE CLOCK RESET
In the event of a power outage, VT8300 Room Controllers retain the correct time as long as the duration of the power outage is not prolonged. Depending on the duration of the power outage, the Room Controllers internal clock may need to be updated or reset completely. The following table gives an indication of the expected clock performance after a power outage.

Outage duration 0 - 24 hours 24 - 36 hours 36 - 72 hours 72+ hours

Room Controller behaviour Clock functions are normal
Clock accuracy not guaranteed, time may need to be adjusted
Clock no longer increments and must adjusted when power is restored Clock functions are fully reset, and must be reinitialized as per a new installation

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150