Introducing Lossnay The concept of sensible heat and latent heat exchange using Lossnay core Lossnay is a complete heat exchange ventilation system

Lossnay-Heat-Recovery-Ventilation-Brochure
Introducing Lossnay
Lossnay is a complete heat exchange ventilation system that uses a paper core to perform temperature (sensible heat) and humidity (latent heat) exchange.
The diagram below provides an overview of how this process takes place inside of the Lossay system.

The concept of sensible heat and latent heat exchange using Lossnay core
Outside Inside

Outside exhaust air outlet (EA) Outside air intake (OA)

Inside return air (RA) Inside supply air (SA)

2

Contents

Line Up

4

The Need for Ventilation 5

Mitsubishi Electric

Air Management

6

LGH Series

8

Control

10

Energy Saving Features 12

GUF Series

13

Remote Controllers

18

Optional Parts

19

Specifications

20

3

Line Up
Lossnay by Mitsubishi Electric is an advanced Fresh Air Heat Recovery Ventilation System that captures and filters fresh outdoor air to replace indoor stale air for an all-round healthier, drier and warmer home. But what makes Lossnay so different from other ventilation systems is our patented Heat Exchanger, which is the source of the heat recovery capabilities of the Lossnay ventilation unit and provides several important benefits.
LGH-RVX Series
This commercially oriented system can be utilised virtually anywhere with high performance functions.
LGH-RVXT Series
Thin large air volume models in LGH series with high performance functions.

GUF Series
Heat recovery with heating and cooling system using the heat resource of City Multi outdoor unit.
VL-220CZGV-E
Centralised ventilation for residential use with sensible heat exchange.

Application

Model

Air Volume 150 CMH

LGH-RVX Series

3

250 CMH
3

350 CMH
3

500 CMH

650 CMH

800 CMH

1000 CMH

1500 CMH

2000 CMH

2500 CMH

3

3

3

3

3

3

Commercial Use LGH-RVXT Series

3

3

3

GUF Series

3

3

Residential Use VL-220CZGV-E

3

*While every effort has been made to represent product colours herein accurately, slight deviations from actual colour may be noted due to the printing process.
4

The Need for Ventilation

The Need for Fresh Air
Poor air quality can be attributed to many problems arising in the workplace and in the home. It is believed to contribute to a significant loss in productivity, low morale and higher rates of sickness. Providing good ventilation in residential and commercial buildings is to provide conditions under which people can live and work comfortably and safely.

Effect of oxygen deficiency on the human body

0

5

10

Normal air concentration

Oxygen concentration (%)

15

20

21%

Safe limit

18%

Breathing / Pulse increases headaches, nausea, vomiting

Dizziness, nausea, muscle weakness (leading to death)

12%

16%

Facial pallor, unconscious vomiting 10%

Lapse into a coma and die in 8 minutes

8%

Respiratory arrest, convulsion, death

6%

Source: SE Series "Safety of New Construction" Author: "Oxygen Deficiency" Doctor of Medicine/ Hiroshi Yamaguchi, issued by Research Institute for Safety Engineering

What can be improved by introducing Lossnay? Ventilation with maximised comfort.
In Summer: Air similar to the conditions of the cooled (dehumidified) indoor air is supplied.

The Need for Appropriate Humidity Management
Viruses such as influenza are found to be active and the survival rate is high in low humidity and dry environments.
In general, the survival rate is said to decrease significantly when the relative humidity (RH) is 50% or more when the temperature is 20°C. During the winter, keeping an appropriate humidity and heating temperature can help prevent influenza.

Influenza virus survival rate

Survival Rate of Virus (%)

70

60

50

50%

40

RH

30

20 80% 10 RH

0

10

22 Temperature (°C)

20% RH
32

Source: Survival rate after 6 hours by G.J. Harper, Takehito Takano and other "Health Housing Science Seminar"

Activity range of microorganisms by humidity range Optimum range for human health Size of Energy

Bacteria

Virus

Mold

Mite

10 20 30 40 50 60 70 80 90 Humidity (%)

Source: ASHRAE Trans. 91 - 1B (1985)

In Winter: Air similar to the conditions of the heated (humidified) indoor air is supplied.

Supply Air

Lossnay

Sensible Conventional HRV Unit HRV Unit

Dry Bulb Temperature (°C)

28

28

33

Absolute humidity (g/kg'(DA)) Relative humidity (%) Enthalpy (kJ/kg(DA))

13.3

20.1

20.1

56

84

63

62.1

79.5

84.6

Total energy recovery (kW) Outdoor air load (kW)

7.5

1.7

0

3.1

8.9

10.6

Outdoor air load ratio (%)

29

84

100

Room Air

Dry Bulb Temperature (°C)

26ºC

Air Conditioner

Absolute Humidity Relative Humidity

10.5g/kg'(DA) 50%

Enthalpy

52.9kJ/kg(DA)

Exhaust Air

Outdoor Air

Dry Bulb Temperature (°C)

33ºC

Absolute Humidity

20.1g/kg'(DA)

Relative Humidity

63%

Enthalpy

84.6kJ/kg(DA)

Supply Air

Lossnay

Sensible Conventional HRV Unit HRV Unit

Dry Bulb Temperature (°C)

16

16

0

Absolute humidity (g/kg'(DA))

5.2

1.9

1.9

Relative humidity (%)

46

17

50

Enthalpy (kJ/kg(DA))

29.2

20.9

4.7

Total energy recovery (kW) Outdoor air load (kW)

8.2

5.5

0

3.1

5.8

11.3

Outdoor air load ratio (%)

28

51

100

Room Air

Dry Bulb Temperature (°C)

20ºC

Air Conditioner

Absolute Humidity Relative Humidity

7.3g/kg'(DA) 50%

Enthalpy

38.5kJ/kg(DA

Exhaust Air

Outdoor Air

Dry Bulb Temperature (°C)

0ºC

Absolute Humidity

1.9g/kg'(DA)

Relative Humidity

50%

Enthalpy

4.7kJ/kg(DA)

Heat Recovery Calculation

Indoor Supply Air Temperature (°C)

=

Outdoor Temperature (°C)

-

{

Outdoor Temperature

(°C)

-

Indoor Temperature

(°C)

}

x

Temp Recovery Efficiency (%)

Calculation example: 28°C=33°C-(33°C-26°C)x72%

*The above applies to the case of LGH-100RVX (fan speed 4).

Heat Recovery Calculation

Indoor Supply Air Temperature (°C)

=

{

Indoor Temperature

(°C) -

Outdoor Temperature

(°C)

}

x

Temp Recovery Efficiency (%)

+

Indoor Temperature (°C)

Calculation example: 16°C=(20°C-0°C)x80%+0°C

*The above applies to the case of LGH-100RVX (fan speed 4).

5

Mitsubishi Electric Air Management
For a healthier, more comfortable workplace and home.
OUR SOLUTIONS FOR BETTER AIR MANAGEMENT
Mitsubishi Electric has developed the Lossnay in order to better manage the air in highly populated indoor environments such as workplaces and homes. These areas require complex systems in order to move fresh comfortable air throughout. However each of these are distinctly different in their requirements.

LGH-RVXT Series

VL-220CZGV-E

WORKPLACE BENEFITS
The Lossnay Fresh Air Energy Recovery Systems set a new standard in ventilation by recovering heat from the air inside your office and transferring it to fresh, dry air introduced from outside. Not only providing energy recovery savings in summer by cooling the warmer fresh air to an acceptable level but also providing excellent energy efficiency in winter. Lossnay heat exchangers have an efficiency of approximately 82%* thereby eliminating the need for additional electric elements.

Easy Installation
· Installable in tight ceiling spaces.

Energy Efficiency
· Heat recovery ventilation.
· Scheduled ventilation programs.

*Refer to calculations on the bottom of the page 5.
6

Improve Indoor Air Quality
· Ventilation on demand.
· Simultaneous air supply and exhaust.

FEATURES
Below are some key features of the Lossnay system as a whole, followed by an outline of benefits as they pertain to both the workplace and home environments.

Energy Saving
A highly efficient EC motor operates at a lower energy consumption. Heat recovery ventilators also help to reduce the load on air conditioning system.

Comfort
Heat Recovery ventilation and low noise operation assures a comfortable indoor environment.

Clean
Ventilation and clean, fresh air contribute to a healthy living environment.

HOUSEHOLD BENEFITS
Lossnay is the ultimate home ventilation system that provides fresh clean air. Featuring the new advanced Diamond Heat Exchanger, heat is recovered from both outgoing stale air as well as from damp areas such as kitchens and bathrooms. This heat is utilised to pre-heat incoming fresh air so your heating system is not required to work as hard to maintain desired room temperature.

Quiet and Comfortable Operation
· Quieter operation*. · Minimises temperature difference. · Filter cuts pollen and dust for fresh clean air. *Measured on the lowest fan speed.

Save on Energy Costs
· Minimise energy consumption.
· Heat recovery ventilation.

Maintain a Healthy Living Environment
· 24 hours ventilation. · Simultaneous air supply and exhaust.
7

LGH Series
IMPROVED AIR VOLUME RANGE
Wide Range Air Volume
The LGH-RVX/RVXT are equipped with four fan speeds. In addition, each speed has a range setting of 25, 50, 75 and 100%, allowing much finer air volume control.
When used in combination with the CO2 sensor or timer function, the air volume can be controlled according to conditions that produce better performance and reduce power consumption.
LGH-RVX/RVXT Series Model Characteristic Curves
Offers a wide range of airflow variations, from fine to large volume

Air Volume Control by CO2 Sensor
An external CO2 sensor can be connected directly to the Lossnay RVX/RVXT units, allowing the fan speed to vary according to the CO2 levels detected. When the CO2 concentration is low, the unit can operate at a lower air volume compared to previous models and this improves total heat exchange efficiency and contributes to energy saving.
Fan Speed 4
Fan speed 4
High CO2 density CO2Sensor

Static pressure

25%

50%

75%

100%

Fan speed 1

Fan speed

Fan speed

2

3

Air volume

Fan speed 4

Weekly Timer
The operation pattern for each day of the week, On/Off and air volume can be set using the weekly timer function (up to eight zones per day).

Compared to previous models, much finer operation control contributes to enhanced energy saving operation. With a wider range of air volumes the Lossnay RVX/RVXT units enable optimised ventilation not just at different times of the day, but for different days of the week as well, enabling further energy savings.

LGH-RVX/RVXT Series Model

8:00 9:00 12:00 13:00

Monday

to Thursday

2*

4*

2*

Friday

8:00 9:00 12:00 13:00

2*

4*

2*

17:00

19:00 22:00

3*

2*

1*

17:00
3*

22:00
1*

8:00
Saturday to Sunday

1* *Fan Speed

22:00

Total Power Consumption in a Week
32.5 kWh

Previous Model

12.6 kWh

60% OFF

Current Model

*Comparison of LGH-100RX5-E and LGH-100RVX-E.
8

Fan Speed 1

Fan speed 1

Low CO2 density

CO2 Sensor

Static pressure

P-Q Curve Image

default +1 +2 +3 +4

Improved External Static Pressure
External static pressure has been improved compared to previous models.
By increasing the external static pressure, flexible duct work installation is possible thus, allowing flexibility with existing installations.

Fan speed 1

Fan speed

Fan speed

2

3

Air volume

Fan speed 4

Fan Speed Adjustment Function
The default fan speed value can be adjusted slightly. Use the PZ-61DR-E remote controller to reset the speed.
1. The fan speed will be adjusted automatically after a given period of time to allow for increased filter static.
2. After the unit is installed, if the air volume is slightly lower than the desired airflow, it is possible to make fine adjustments from the unit's dip switches.

IMPROVED INSTALLATION
Connect ducts in two different directions (OA, EA side)
Ducts can be connected in two different directions to the outdoor vents, thanks to collars and aperture plates that can be interchangeably placed in two different positions. This flexibility allows for installations close to the surface of a wall and helps avoid cases where the stale air exhaust vent would be blocked by an obstruction of some kind. This makes both planning and installation that much simpler.

Standard installation
A space is necessary to prevent the influx of rainwater.

EA

OA

Flange

Plate

Installation with duct direction changed

Can be installed close to the surface of the wall.
EA Changing the duct direction
Exchangeable

Avoid installations where the stale air exhaust aperture would be blocked by lighting or air conditioning units.

Lighting etc.

OA

EA

OA

Remove the flange (factory-standard direction) and the side panel plate and switch their placements.
They are both equipped with screw stoppers making the switch extremely simple.
The direction of the ducts can only be changed on the outside (OA and EA).
The inside cannot be changed (SA and RA).

OA/EA square duct (LGH-150 / 200RVX-E)
OA/EA is a square duct. This simplifies installation and reduces total installation time.
Thin new series (LGH-RVXT-E)
The LGH-RVXT-E series have a large air volume of 417 - 694 L/s, with a thin body at 500mm. Installing the unit behind the ceiling is easy.

Ceiling

500mm

9

Control

SIMPLE CONTROL WITH THE PZ-61DR-E REMOTE CONTROLLER

Interlocked with Air Conditioners

City Multi

Mr Slim

M-NET Transmission Line

Lossnay Independent
Lossnay RVX/RVXT (Max 15 units)

City Multi

Lossnay RVX/RVXT

Lossnay Remote Controller PZ-61DR-E can be connected.

(PZ-43SMF-E can be connected however function is limited)

Mr. Slim

Lossnay RVX/RVXT

Option 1: Slim-Lossnay Connection Cable (Impossible to use Lossnay Remote Controller)

Option 2: PAC-SF40RM-E (Possible to use Lossnay Remote Controller)

Lossnay Remote Controller PZ-61DR-E
(PZ-43SMF-E can be connected however function is limited)

CENTRALISED CONTROLLER SYSTEM

Centralised Controller AE-200E

Outdoor Unit

Indoor Unit
Network Remote Controller

Lossnay RVX/RVXT
Lossnay Remote Controller PZ-61DR-E

Interlocked with City Multi indoor units

Indoor Unit
Network Remote Controller

Lossnay units only

Lossnay RVX/RVXT
Lossnay Remote Controller PZ-61DR-E

Lossnay RVX/RVXT
Lossnay Remote Controller PZ-61DR-E

Lossnay RVX/RVXT
Lossnay Remote Controller PZ-61DR-E

Ext. Signal Source

Interlocked with external devices

M-NET Adapter

Mr. Slim Outdoor Unit

Mr. Slim Indoor Unit

Lossnay RVX/RVXT

Interlocked with Mr. Slim indoor units

Mr. Slim

10

Remote Controller

M-NET

Switching Hub

M-NET

adapter

FEATURESL(1AO0N0BFASEC-TX)ENTRALISED CONTROLML-NEET R "AE-200E" A Control

In an easy and flexible manner, an optimum system can be established according to the scale of the facilities.

ControlRuepmtoote50 indoor units of air conditioning equipmAeEn-2t.0B0Ey using three units of expansion controller "AE-50E", the centralised control is capable of controlling

a mamxoimniutomrinogf 2PC00 units. Connection with PC allows implementation of control on more than 200 indoor units via Web Browser. *

Remote monitoring

Power Supply Unit

*Pvleiaasae Wcoenbtabctroyowusrelor cal distributor for when the fea(tPuAreCis-SreCq5u1irKedU.A)

General Equipment

DIDO Controller (PAC-YG66DCA)

System Structure

Hub Hub

M-NET

Temp/Humidity sensor AI Controller (PAC-YG63MCA)

Lights Ventilation

Central Control PC (TG-2000A)
*Ver. 6.50 or later

AE-200E
VPN Modem Router

Internet

Watt hour meter
PI Controller (PAC-YG60MCA) Service company / Sales office

Modem

VPN Router

Mobile phone of service person

Remote monitoring PC
Remote monitoring via a Web browser

: Each unit

: Each group : Each block

: Each floor

: Collective

: Not available

Note: Use a security device such as a VPN router when connecting the AG-150/AE200E to the Internet to prevent unauthorised access.

Function

: Each unit

: Each group

: Each block

: Each floor

: Collective

: Not available

Item

Description

Controllable number of unit Up to 50 units/50 groups

On/Off Operation mode Temperature setting Fan speed setting

ON and OFF operation for the air conditioning units and general equipment. (To operate general equipment, PAC-YG66DCA is required.)
Switches between several operation modes depending on the air conditioning unit. Air conditioning unit : Cool/Dry/Auto(*)/Fan/Heat LOSSNAY unit : Heat Recovery/Bypass/Auto CAHV, Air To Water (PWFY) units : Heating, Heating ECO, Hot Water, Anti-freeze, Cooling(**) * Auto mode is for CITY MULTI R2 and WR2 series only. ** Only PWFY
Cool/Dry : 19°C -35°C [14°C -30°C] Heat : 4.5°C -28°C [17°C -28°C] Auto : 19°C -28°C [17°C -28°C] The range of temperature depends on the air conditioning unit. [ ] in case of using middle-temperature on PDFY, PEFY-VML/VMR/VMS/VMH-by setting DipSW7-1 to ON. PEFY-P-VMH-E-F is excluded.
Models with 4 air flow speed settings : Hi/Mid-2/Mid-1/Low Models with 3 air flow speed settings : Hi/Mid/Low Models with 2 air flow speed settings : Hi/Low Fan speed setting (including Auto) varies depending on the model.

Air flow direction setting Air flow direction angles, 4-angles or 5-angles Swing, Auto (Louver cannot be set).

Schedule operation
Permit/prohibit local operation Indoor unit intake temperature Error

Weekly schedule can be set by groups based on daily operation pattern. Individually prohibits operation of each local remote controller function. (On/Off, Operation mode, Set temperature, Filter sign reset, Air Direction*, Fan Speed*, Timer*) * This function depends on the model.
Measures the intake temperature of the indoor unit only when the indoor unit is operating.
When an error is currently occurring on an air conditioning unit, the afflicted unit and the error code are displayed.

Test run

This operates air conditioning units in test run mode.

Ventilation interlock

The ventilation unit (LOSSNAY) is able to automatically start its operation when operation of the interlocked indoor unit starts.

External input/output
Energy Management Advanced HVAC Controller (AHC) Smart ME controller

By using optional external input/output adapter (PAC-YG10HA-E) you can set and monitor the following. Input : By level signal : "Batch On/Off", "Batch emergency stop" By pulse signal : "Batch On/Off", "Enable/disable local remote controller" Output : "On/Off", "Error/Normal"
Bar Graph : Indoor unit Electric Energy, FAN operation time, Thermo-ON time (TOTAL, Cooling, Heating) can be displayed hourly, daily and monthly.
Line Graph : Outdoor temp., Room temp., Set temp. (Heating, Cooling) Input from PAC-YG63MCA and temp. From AHC.
The status of AHC can only be monitored.
The status of sensor on this controller can be monitored.

Smartphone/Tablet

The specified Web browser on iOS and Android OS can monitor and operate AE-200E. *2

New Web design

The web screen design is renewed for user friendly interface. *2

Initial setting software Apportionment of power consumption BACnet® communication

The initial setting can be configured without the connection of AE-200E. *2 Apportionment of power consumption can be calculated on AE-200 without TG-2000A. *2 ANSI/ASHRAE 135-2010 (ISO16484-5) is supported and approved by the BTL. *2

Operations Display

*2 Please contact your local distributor for when the feature is required.

11

Energy Saving Features

FLEXIBILITY IN SETTING NIGHT PURGE AND AUTO VENTILATION HAVE IMPROVED

Night Purge
During the summer season, the Night Purge mode draws cooler outside air into the room at night. This energy conservation mode reduces the load when the air conditioning is started up the next morning. With new models, it is possible to manually engage and set* the night purge operation.
* Settings can only be made using the PZ-61DR-E.

Current Model Operating Time
Possible to set to any time.

Start Condition
(inside-outside temperature difference)
Can be set to between 0°C and 7°C
(1°C increments)

Fan Speed
Select from Fan Speed 1 to 4

VENTILATION MODE SWITCHING

With operation from PZ-61DR-E, it is possible to select manual switching or automatic switching between "Lossnay ventilation (with heat exchange)" and "Bypass ventilation (without heat exchange)". With the previous model, the auto ventilation mode was based on the initial programmed setting; however, with the new model it is possible to set three setting points, as shown in the table on the right.

* Settings can only be made using the PZ-61DR-E.
What is Lossnay Ventilation?
Room air is discharged to outside via Lossnay core. Heat exchanged outside air is supplied to the room. In summer and winter, air conditioning energy can be recovered by Lossnay unit.

Stale Exhaust Air
Fresh Air from Outside

What is Bypass Ventilation?
Stale room air is discharged to outside without passing through the Lossnay core. In spring and autumn when air conditioning is not necessary, the unit operates in bypass ventilation mode.

Stale Exhaust Air
Fresh Air from Outside

Damper Plate
Stale Room Air Extracted
Fresh Air Supply to the Room
Lossnay Core
Damper Plate
Stale Room Air Extracted
Fresh Air Supply to the Room
Lossnay Core

Outdoor temperature( )

Bypass/Lossnay Ventilation map in automatic ventilation mode

40

38

Lossnay ventilation area

36

34

Setting item A

32

30

When Lossnay is connected

28

with Mr Slim or City Multi setting

26

temp will be the min limit of

24

bypass ventilation

22

20

Setting item B

18

Bypass ventilation area

16

14

12

10

8

Setting item C

8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

Indoor temperature( )

Improved Control with a BMS System
Using a 0-10V signal from the Building Management System, the air volume of the Lossnay unit can be changed.

Connection example: BMS (Building Management System)

Input voltage [VDC]

Fan Speed

Fan Speed Changing from Remote Controller

0 -1.0

-

Available

1.5 - 2.5

1

Not Available

3.5 - 4.5

2

5.5 - 7.0

3

8.5 - 10.0

4

Not Available Not Available Not Available

PC BMS

Lossnay

Air Conditioning

Lighting System

Surveillance

Camera System

12

GUF Series

VENTILATION AND AIR CONDITIONING
The OA (Outdoor air) Processing Unit creates an optimum environment while providing substantial energy savings. The OA Processing Unit comprises forced air ventilation, heat recovery, heating and cooling, and air purification. This total air conditioning system keeps indoor air fresh and comfortable all year round, and keeps it free of contaminants. Inside the OA Processing Unit is the Lossnay core, a heat exchange unit that transfers heat efficiently, cutting ventilation load by as much as 70%.
A remarkable product found nowhere else, this special combination of functionality and performance contained within a single unit ensures users ample comfort, good health, and energy savings.

GUF-RD type

OA (Outdoor air) Fresh, outdoor air in a quantity required for ventilation is drawn in by the supply fan.

EA (Exhaust air) Heat from the indoor air (both sensible and latent) is recovered by the Lossnay core and vented outside by the exhaust fan.

The exhaust fan High efficiency filters (Option) The supply fan

Heat recovery unit (Lossnay core) Temperature and humidity are exchanged between the supply air and the exhaust air.
Maintenance cover
Air filter Prevents clogs in the Lossnay core.
DX Heat exchanger Cools or heats the drawn in outdoor air.

RA (Return air) The exhaust fan draws in contaminated indoor air.
SA (Supply air) The processed, fresh outdoor air is vented to the indoor rooms.

GUF-RDH type

OA (Outdoor air) Fresh, outdoor air in a quantity required for ventilation is drawn in by the supply fan.

EA (Exhaust air) Heat from the indoor air (both sensible and latent) is recovered by the Lossnay core and vented outside by the exhaust fan.

The exhaust fan High efficiency filters (Option) The supply fan

Heat recovery unit (Lossnay core) Temperature and humidity are exchanged between the supply air and the exhaust air.
Maintenance cover
Air filter Prevents clogs in the Lossnay core.
DX Heat exchanger Cools or heats the drawn in outdoor air.

RA (Return air) The exhaust fan draws in contaminated indoor air.
SA (Supply air) The processed, fresh outdoor air is vented to the indoor rooms.
Permeable-film humidifier Humidifies the drawn in outdoor air as is necessary to produce a comfortable indoor environment.

13

PERMEABLE FILM HUMIDIFIER (GUF-RDH ONLY)
Comfortable Level of Humidity for Exceptional Air Quality
The OA Processing Unit is equipped with a permeable film humidifier developed by Mitsubishi Electric. Steam transmission efficiency has been improved by lowering the resistance of the material. By providing an optimum level of humidity, the OA Processing Unit creates a comfortable interior environment which may prevent irritations such as dried out eyes or a parched throat that can be caused by insufficiently low levels of humidity in the air.
Highly Efficient Humidification
Improvements in the system of airflow patterns and water injection techniques have resulted in a substantial increase in humidifying volume. The system also controls the humidity level of the air that is exhausted, ensuring an efficient, environmentally friendly manner of operation.
Note: In the case in which the level of residual impurities exceeds 100mg/ please use a water purifier.

DUAL-FAN SYSTEM
Reliable Ventilation
The OA Processing Unit utilises a dual-fan configuration for the intake and exhaust of air from a building. A forced air method is incorporated for the simultaneous supply and exhaust of air to support effective ventilation even in highly insulated airtight rooms. The Lossnay core is designed in such a way that the passages for air being drawn into and exhausted from a building are entirely separate. This setup prevents the mixing of indoor and outdoor air for safe, reliable ventilation.
FREE COOLING
When the air conditioning system is operating in its cooling mode and the temperature of the air outdoors drops below the temperature indoors (e.g. a summer night), the OA Processing Unit detects this and automatically switches to a mode of operation which bypasses the heat recovery unit. Bringing in cool air from outside serves to help reduce the air conditioner's cooling load.
HEAT PROCESSING
A direct expansion heat exchanger is incorporated to compensate for any heat loss that may occur during ventilation. It also improves the efficiency of humidification in the winter.
VARIABLE DUCT POSITIONS
The connection position of the outside duct is variable allowing for more complicated duct installations.

Standard installation
A space is necessary to prevent the influx of rainwater.

Installation with duct direction changed

Can be installed close to the surface of the wall.

Avoid installations where the stale air exhaust aperture would be blocked by lighting or air conditioning units.

Lighting etc.

EA

OA

*There is no pressure loss with a change in the duct position.

EA

OA

EA

OA

14

VL Series

SMART VENTILATION
More comfortable!
· Minimises temperature difference. · Reduces outside noise. · Filter cuts pollen and dust for fresh clean air.
More energy saving!
2F · 86% maximum exchange efficiency. · Reduces load on air conditioning (heating and cooling).
One Lobesdsronoamy unit providbeedsro2om4 hours ventilation for the entire house from the living areas to the bathroom. The heat recovery system provides fresh air at a comfortable air temperature. The energy saved by using Lossnay contributes directly towards loweribnegd rhooemating or coolinbgatheroxopmenses. The sensible heat exchanger type is effective for ddeowcnreasing excess humidity in the winter.

 

1F
porch

2F

dining room

bed room

bed room

up SA

living room

toilet

kitchen

bed room

bath room down

EA OA

 

1F

1F

2F porch

dining room

PRODUCT MERITS up
living room
Newly Developed Heat Exchanger toilet kitchen
· During ventilation, Lossnay recovers warmth in the winter and keeps air cool in the summer.
· Reducing heating and cooling loads with a maximum exchange efficiency of 86%.

RA SA

Normal Square Heat Exchanger
Simple structure contributes to minimise pressure loss and reduce power consumption.

2F
bed
bed
1F
por
living

Wider Wider

Length Length

New Diamond Heat Exchanger
Due to the diamond design, air passages are longer and help realise higher exchange efficiency.

Quiet
· At an ultra quiet 14dB, it is the quietest product in its class*.
· Blocks outside noise for a more comfortable environment.
*On lowest fan speed.

Energy Efficient
· The highest energy saving in its class. (8.5W minimum input power)
· Saves heating and cooling costs by minimising energy loss occurring during ventilation.

15

Static pressure Static pressure

FAN SPEED SETTING
Widely Adjustable Fan Speed
This model can operate at four main fan speeds. In addition, each speed has a range setting of approximately 25, 50, 75 and 100%, allowing optimum air volume control.
When used in combination with the CO2 sensor or timer function, the air volume can be controlled according to conditions that realise better performance and reduce power consumption.

Fan speed precise adjustment function
Each main fan speed value can be further adjusted slightly. Use the PZ-61DR-E remote controller to adjust the speed.
1. Considering the total hours of Lossnay operation (filter clogging), the fan power can be adjusted automatically after a given period of time.
2. After the unit is installed, if the air volume is slightly lower or higher than the desired airflow, it is possible to make fine adjustments. (Fan speed 4 is available only 1down and 2down)

VL-220CZGV-E Characteristic Curves
Offers a wide range of airflow variations, from fine to large volume

P-Q Curve Image

Q

g

+2 +1 Original -1 -2

25%
Fan speed 1

50%

75%

Fan speed

Fan speed

2

3

Air volume

100%
Fan speed 4

Fan speed 1

Fan speed

Fan speed

2

3

Air volume

Fan speed 4

MAINTENANCE
To keep the Lossnay unit in optimal condition, clean dirt and dust from the filters and the drain pan periodically (at least once every six months or more, depending on the operating environment).

1. Draw out filters after unlocking the fix knobs

Supply air filter case
It holds the supply air filter or High efficiency supply air filter.

Supply air filter fixing knob
Release it to remove the supply air filter case (3 locations).

2. Remove the air filters from the filter cases

Supply air filter case

Exhaust air filter case

Supply air filter

Exhaust air filter

3. Clean at least once every six months Lightly tap or remove dust with a vacuum cleaner

Drain pan
Drain pan (supply air side) It holds dew condensation water that occurs inside the Lossnay unit.

Supply air filter
It removes insects, pollen, dirt, dust, and other particles
from the outside air that is taken into the room.

4. The Drain pan can be cleaned with a vacuum cleaner Drain pan
(Supply air side)

16

CONTROL

Multi Ventilation (Power Supply/Exhaust) Mode
This mode allows the air supply/exhaust balance to be varied dynamically. The supply/exhaust balance can be selected to suit the usage environment.

Normal Mode

Power Supply Mode

Power Exhaust Mode

Relax time

Adjust the indoor pressure balance in case a separate exhaust is installed

Increase indoor pressure to prevent unfiltered drafts from coming in

Keeps steam only inside the shower room

Prevent odours from spreading

Weekly Timer
The operation pattern for each day of the week. On/Off and air volume can be set using the weekly timer function (up to eight zones per day). This function contributes to enhanced energy saving operation.

0:00
MoMtnodoanyday FrtiodaFyriday

Fan speed
1

5:00

8:00

Fan speed
3

Fan speed
1

17:00

19:00

21:00

23:59

Fan speed Fan speed

3

4

Fan speed
1

0:00
SatSuradtauyrday

sleeping time
Fan speed
1

breakfast time

go to working place

8:00

10:00 11:00

13:00

Fan speed Fan speed Fan speed

3

2

3

dinner time
Fan speed
1

shower time

sleeping time

21:00 22:00

23:59

Fan speed Fan speed

4

1

0:00
SuSnudnayday

sleeping time
Fan speed
1

breakfast relax

time

time

lunch time

shopping time

shower sleeping

time

time

8:00

10:00 11:00

13:00

Fan speed Fan speed Fan speed

3

2

3

Fan speed
1

17:00

19:00

21:00

23:59

Fan speed Fan speed

3

4

Fan speed
1

Outdoor temperature (°C)

sleeping time

breakfast relax

time

time

lunch time

go out in the family

dinner time

shower time

sleeping time

Free Cooling Mode
During the summer season, the free cooling mode draws cooler outside air into the room. This mode contributes to reduced loads on air conditioning. For this operation, an optional bypass damper P-133DUE-E is required. The user is able to set the OA temp. Depending on the preference between 10°C to 30°C.

40

38

36

Heat recovery ventilation area

34

32

30

28

26

Default Setting (Factory Setting)

24

22°C to 28°C

22

20

18

16

Bypass ventilation area

14

12

10

8

Heat recovery ventilation area

8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
Indoor temperature (°C)

P-133DUE-E attached to VL-220CZGV-E

The remote controller PZ-61DR-E can set the free cooling temp. zone: Max: 30°C, Min: 10°C

PipiPnigpinEgxaexmamplpele

Outdoor

EA

side

(Exhaust Air)

Indoor side

SA (Supply air)
RA3

Lossnay

OA (Outdoor Air)

RA2

Kitchen/dining room

Motorised damper (option)

17

Remote Controllers

PZ-61DR-E

PZ-43SMF-E

120

19

70

15

Lower case

120 120

Unit (mm)

Unit (mm)

Function (Communicating Mode) Fan speed selection
Ventilation mode selection
Night purge (time) Night purge (fan speed) Function setting from RC
Bypass temp. free setting
Heater-On temp. free setting Fan power change after installation On/Off timer Auto-Off timer Weekly timer Operation restrictions (On/Off, ventilation mode, fan speed) Operation restrictions (fan speed skip setting) Screen contrast adjustment Language selection Initialising remote controller Filter cleaning sign Lossnay core cleaning sign Error indication Error history

PZ-61DR-E

LGH-RVX/RVXT

VL-220CZGV-E

4 fan speeds Energy recovery / Bypass / Auto
Anytime schedule

4 fan speeds
Heat recovery / Bypass / Auto (available with
optional parts P-133DUE-E)
No

Selectable from 4 fan speeds

No

Yes

Yes

Yes (available with

Yes

optional parts

P-133DUE-E)

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes (ventilation mode is

Yes

available with optional parts

P-133DUE-E)

Yes

Yes

Yes Yes (8 languages)
Yes Yes Yes Yes Yes

Yes Yes (8 languages)
Yes Yes No Yes Yes

PZ-43SMF-E

LGH-RVX/RVXT

VL-220CZGV-E

2 of 4 fan speeds
Energy recovery / Bypass / Auto
No

2 of 4 fan speeds
Heat recovery / Bypass / Auto (available with
optional parts P-133DUE-E)
No

No

No

No

No

No

No

No

No

No

No

Yes

Yes

No

No

No

No

No

No

No
No No (English Only)
No Yes No Yes No

No
No No (English Only)
No Yes No Yes No

18

Optional Parts

Standard filter
Replacement components for the standard air filter supplied with the Lossnay LGH main unit.

B

A

C

Unit (mm)

Model
PZ-15RF8-E PZ-25RF8-E PZ-35RF8-E PZ-50RF8-E PZ-65RF8-E PZ-80RF8-E
PZ-100RF8-E

Dimension (mm)

A

BC

557 130 20

333 156 15

399 183 20

470 183 15

433 218 15

451 243 15

565 243 15

Number of filters per set Supply Exhaust

Applicable model

Filter material

1 1 LGH-15RVX-E

2 2 LGH-25RVX-E

2 2 LGH-35RVX-E

2

2

LGH-50RVX-E Nonwoven

GUF-50RD(H)4

filter

2

2 LGH-65RVX-E Filtration

2

2

LGH-80RVX-E LGH-150RVX-E(2sets)

efficiency (EU-G3)

LGH-100RVXE

2 2 GUF-100RD(H)4

LGH-200RVX-E(2sets)

Model

Air

Supply PZ-150RTF-E
Exhaust

Dimension (mm)
AB

Number of filters per set

655 290

2

655 250

2

Applicable model
LGH-150RVXT-E

Supply 985 290

2

PZ-250RTF-E

Exhaust 985 250

2

LGH-200RVXT-E LGH-250RVXT-E

Filter material
Nonwoven filter
Filtration efficiency (EU-G3)

High-efficiency Filter
This high-efficiency filter (with 65% colorimetricity EU-F7:EN779: 2002) can be incorporated inside the Lossnay unit without the need to attach parts from other systems, as done to date.

B

A

25

Unit (mm)

Optional Parts for VL-220CZGV-E
Bypass damper

Model
PZ-15RFM-E PZ-25RFM-E PZ-35RFM-E PZ-50RFM-E PZ-65RFM-E PZ-80RFM-E
PZ-100RFM-E

Dimension (mm)

A

B

553

123

327

149

393

175

464

175

427

209

446

236

559

236

Number of filters per set 1 2 2 2 2 2
2

Applicable model
LGH-15RVX-E LGH-25RVX-E LGH-35RVX-E LGH50RVX-E GUF-50RD(H)4 LGH-65RVX-E LGH-80RVX-E LGH-150RVX-E(2 sets) LGH-100RVX-E GUF-100RD(H)4 LGH-200RVX-E(2 sets)

Filter material
Noncombustible fiber (polyester polyolefin) (EU-F7:EN 779:2002)

Filter type

High Efficiency Supply Air filter

Medium Efficiency

Standard

Exhaust Air Filter Replacement Filter

9

360

9

344

57

17

11

2- 3.5 Mounting bracket mounting hole

2- 3.5 Mounting bracket mounting hole
410

Model Classification (EN779:2012)

P-220SHF-E M6

Approximate Service Life

1 year (replacement) Cannot be cleaned

P-220EMF-E

P-220F-E

G4

G3

2 year (replacement) Clean approximately once every 6 months

Replace when broken Can be washed with water
and reused 4 times. Clean approximately once every 6 months.

Certain ratings and specifications may change due to product improvements or modifications, refer to product manuals for safety precautions.

200 18

125

152

108

124

134

4- 3.5 Duct connecting flange

mounting hole

125

125

203

Unit (mm)

19

SPECIFICATIONS LGH-15/25RVX-E

Model

LGH-15RVX-E

LGH-25RVX-E

Electrical power supply

220-240V/50Hz, 220V/60Hz

220-240V/50Hz, 220V/60Hz

Ventilation mode

Heat recovery mode

Bypass mode

Heat recovery mode

Bypass mode

Fan speed

SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1

Running current (A)

0.40 0.24 0.15 0.10 0.41 0.25 0.15 0.10 0.48 0.28 0.16 0.10 0.48 0.29 0.16 0.11

Input power (W)

49 28 14 7 52 28 14 8 62 33 16 7.5 63 35 17 9

Air volume

(m3/h) (L/s)

150 113 75 42 31 21

38 150 113 75 10 42 31 21

38 250 188 125 63 250 188 125 63 10 69 52 35 17 69 52 35 17

External static pressure (Pa)

95 54 24 6 95 54 24 6 85 48 21 5 85 48 21 5

Temperature exchange efficiency (%)

80.0 81.0 83.0 84.0 - - - - 79.0 80.0 82.0 86.0 - - - -

Enthalpy exchange efficiency (%)

Heating Cooling

73.0 75.5 78.0 79.0 71.0 74.5 78.0 79.0

-

-

-

- 69.5 72.0 76.0 83.0 - 68.0 70.0 74.5 83.0 -

-

-

-

Noise (dB)

(Measured at 1.5m under the centre of unit in an anechoic chamber)

28.0

24.0

19.0

17.0

29.0

24.0

19.0

18.0

27.0

22.0

20.0

17.0

27.5

23.0

20.0

17.0

Weight (kg)

20

23

Specific energy consumption class

A

A

*The Air outlets noise (45 angle,1.5 metres in front of the unit) is about 13dB(LGH-15RVX-E) / 15dB(LGH-25RVX-E) greater than the indicated value (at Fan speed 4). *The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230V/50Hz. *For the specification at the other frequency contact your dealer. *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

Static pressure (Pa) Exchange efficiency (%)
Static pressure (Pa) Exchange efficiency (%)

Characteristic Curve of the LGH-15RVX-E

100mm dia straight pipe length

250

200 150

EEntnhtahlaplyTpeyemxecpxhecahranagtnuegreeefeefixfcfciiechineacnnycgy(eC(eoHfofeilcianiteginn)gc)y

20m 15m

90

80 10m
70

SP4 100

5m 60

SP3

50

SP2

50

SP1

00

50

100

150

200

250

0

10

20

30

40

50

60

70

Air volume

40 300 (m3/h) 80 (L/s)

Dimensions of the LGH-15RVX-E

119 Air exhaust fan

Position where duct direction change is possible

Bypassdamper plate Ceiling suspension fixture (4-13 X 20 oval)

768

65

EA (Exhaust air)

RA (Return air)

Characteristic Curve of the LGH-25RVX-E

250

150mm dia straight pipe length 90

200 150

ETnetmhEaplenprtyhaateulxprceyheeaxxnccghheaanengfgfeieceieeffnfficicciyeien(nCccyoyo(Hlinega)ting)

80
40m 70
30m

100

SP4

20m 60

SP3

50 SP2

10m 50

SP1

00

40

100

200

300

400 (m3/h)

0 10 20 30 40 50 60 70 80 90 100 110 (L/s) Air volume

Dimensions of the LGH-25RVX-E

Air exhaust fan 102

Position where duct direction change is possible Bypass damper plate Ceiling suspension fixture(4-13X 20 oval)

768

65

EA (Exhaust air)

RA (Return air)

782

530

735

658

450

610

115

115

OA (Outdoor air) Maintenance space for Lossnay core, air filters, fan, high efficiency filter

More than 600

150 to 250

SA (Supply air)

20

119

Inspection

opening

450 x 450

or more

65

Air supply fan 50

Control box Maintenance cover

289

Power supply cable opening

Lossnay core

High efficiency filter (sold separately) attachment position

54

780

54

20

Position where duct direction change is possible

Air filters

97.5

110

Unit (mm)

*Certain ratings and specifications may change due to product improvements or modifications. *Refer to the product manuals for safety precautions.

OA (Outdoor air) Maintenance space for Lossnay core, air filters, fan, high efficiency filter

More than 600

150 to 250

SA (Supply air)

20

102 Inspection opening 450 x 450 or more

Air supply fan 65 Control box Maintenance cover

30 289

Power supply cable opening

Lossnay core

High efficiency filter (sold separately) attachment position

64

780

64

Position where duct direction change is possible

Air filters

142

160

Unit (mm)

LGH-35/50RVX-E

Model

LGH-35RVX-E

LGH-50RVX-E

Electrical power supply

220-240V/50Hz, 220V/60Hz

220-240V/50Hz, 220V/60Hz

Ventilation mode

Heat recovery mode

Bypass mode

Heat recovery mode

Bypass mode

Fan speed

SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1

Running current (A)

0.98 0.54 0.26 0.12 0.98 0.56 0.28 0.13 1.15 0.59 0.26 0.13 1.15 0.59 0.27 0.13

Input power (W)

140 70 31 11 145 72 35 13 165 78 32 12 173 81 35 14

Air volume

(m3/h) (L/s)

350 263 175 88 350 263 175 88 500 375 250 125 500 375 250 125 97 73 49 24 97 73 49 24 139 104 69 35 139 104 69 35

External static pressure (Pa)

160 90 40 10 160 90 40 10 120 68 30 8 120 68 30 8

Temperature exchange efficiency (%)

80.0 82.5 86.0 88.5 - - - - 78.0 81.0 83.5 87.0 - - - -

Enthalpy exchange efficiency (%)

Heating Cooling

71.5 74.0 78.5 83.5 71.0 73.0 78.0 82.0

-

-

-

- 69.0 71.0 75.0 82.5 - 66.5 68.0 72.5 82.0 -

-

-

-

Noise (dB)

(Measured at 1.5m under the centre of unit in an anechoic chamber)

32.0

28.0

20.0

17.0

32.5

28.0

20.0

18.0

34.0

28.0

19.0

18.0

35.0

29.0

20.0

18.0

Weight (kg)

30

33

*The Air outlets noise (45 angle,1.5 metres in front of the unit) is about 12dB(LGH-35RVX-E) / 18dB(LGH-50RVX-E) greater than the indicated value (at Fan speed 4). *The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230V/50Hz. *For the specification at the other frequency contact your dealer. *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

Static pressure (Pa) Exchange efficiency (%)
Static pressure (Pa) Exchange efficiency (%)

Characteristic Curve of the LGH-50RVX-E

350 300 250

150mm dia straight pipe

EntEhnatlphyalTepexymcehpxaecnrhgaaetnugereeffieceixfefcinchcieaynn(cgCyeo(eoHflifenicagite)inngc)y

40m

length
30m
20m

90 80 70

200

SP4

60

150 100
50 00 0

SP3

SP2 SP1

100

200

20 40 60

300

400

500

80 100 120 140 Air volume

50 10m
40

30

20

600

(m3/h)

160 180 (L/s)

Dimensions of the LGH-35RVX-E

Air exhaust fan 124

Position where duct direction change is possible Bypass damper plate Ceiling suspension fixture (4-13 X 20 oval)
875 85

EA (Exhaust air)

RA (Return air)

Characteristic Curve of the LGH-35RVX-E

300 250 200 150

200mm dia straight
EnEthnatlhpTayelpmeyxpceehxraacnhtugarenegeeeffxieccifhefiancnicegyne(cCyeof(foHicleiineagnt)icnyg)

pipe

length
60m

90 80 70 60

SP4

40m

100

SP3

50

50

SP2

20m 40

SP1

00

30

100

200

300

400

500

600

700 (m3/h)

0 20 40 60 80 100 120 140 160 180 Air volume

(L/s)

Dimensions of the LGH-50RVX-E

Air exhaust fan 124

Position where duct direction change is possible
Bypass damper plate Ceiling suspension fixture (4-13 X 20 oval) 875
85

EA (Exhaust air)

RA (Return air)

1063

1016 745

921

650

874

115

OA (Outdoor air)

SA (Supply air)

20

More than 600

Maintenance space for Lossnay core, air filters, fan, high efficiency filter

150 to 250

124
Lossnay core 64

Inspection opening 450 x 450 or more
888

85

Air supply fan

Control box

55

Maintenance cover 331

Power supply cable opening

High efficiency filter (sold separately) attachment position 64

160

142

Position where duct direction change is possible

Air filters

Unit (mm)

*Certain ratings and specifications may change due to product improvements or modifications. *Refer to the product manuals for safety precautions.

115

OA (Outdoor air)

SA (Supply air)

20

More than 600 150 to 250

Maintenance space for Lossnay core,

124

air filters,

fan,

high efficiency filter

Lossnay core 79

Inspection opening 450 x 450 or more

85 Air supply fan 30

Control box

331

Maintenance cover

Power supply cable opening

High efficiency filter (sold separately) attachment position

888

79

Position where duct direction change is possible

Air filters

192

208

Unit (mm)

21

SPECIFICATIONS LGH-65/80RVX-E

Model

LGH-65RVX-E

LGH-80RVX-E

Electrical power supply

220-240V/50Hz, 220V/60Hz

220-240V/50Hz, 220V/60Hz

Ventilation mode

Heat recovery mode

Bypass mode

Heat recovery mode

Bypass mode

Fan speed

SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1

Running current (A)

1.65 0.90 0.39 0.15 1.72 0.86 0.38 0.16 1.82 0.83 0.36 0.15 1.97 0.86 0.40 0.15

Input power (W)

252 131 49 15 262 131 47 17 335 151 60 18 340 151 64 20

Air volume

(m3/h) (L/s)

650 488 325 163 650 488 325 163 800 600 400 200 800 600 400 200 181 135 90 45 181 135 90 45 222 167 111 56 222 167 111 56

External static pressure (Pa)

120 68 30 8 120 68 30 8 150 85 38 10 150 85 38 10

Temperature exchange efficiency (%)

77.0 81.0 84.0 86.0 - - - - 79.0 82.5 84.0 85.0 - - - -

Enthalpy exchange efficiency (%)

Heating Cooling

68.5 71.0 76.0 82.0 66.0 69.5 74.0 81.0

-

-

-

- 71.0 73.5 78.0 81.0 - 70.0 72.5 78.0 81.0 -

-

-

-

Noise (dB)

(Measured at 1.5m under the centre of unit in an anechoic chamber)

34.5

29.0

22.0

18.0

35.5

29.0

22.0

18.0

34.5

30.0

23.0

18.0

36.0

30.0

23.0

18.0

Weight (kg)

38

48

*The Air outlets noise (45 angle,1.5 metres in front of the unit) is about 16dB(LGH-65RVX-E) / 24dB(LGH-80RVX-E) greater than the indicated value (at Fan speed 4). *The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230V/50Hz. *For the specification at the other frequency contact your dealer. *Use this unit with static pressure 240Pa or less at Fan speed 4. Otherwise the noise level might be large. (Only LGH-80RVX-E) *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

Static pressure (Pa) Exchange efficiency (%)
Static pressure (Pa) Exchange efficiency (%)

Characteristic Curve of the LGH-65RVX-E

200mm dia straight pipe length

350 300 250 200

EnEthnathTlpeaymlpeypxecerhxaactnhugareengeeexffciechfifeaicnnicegynec(eCyfof(iHocileeinangtci)nyg)

60m 90 80
40m 70 60

SP4

150 SP3
100

50 20m
40

SP2

50

30

SP1

00

20 100 200 300 400 500 600 700 800 900 1000(m3/h)

0 20 40 60 80 100 120 140 160 180 200 220 240 260 Air volume

(L/s)

Dimensions of the LGH-65RVX-E

Air exhaust fan 124

Position where duct direction change is possible

Bypass damper plate Ceiling suspension fixture (4-13 X 20 oval)

895

70

EA (Exhaust air)

RA (Return air)

Characteristic Curve of the LGH-80RVX-E

250mm dia straight pipe length

350 300 250

TEenEmtnhptahelapralyptyeuxreecxhecahxncaghneagneegffeiecffieiecfnifeiccnyice(ynCc(oHyoeliantgin) g)

90
80 100m
70 80m

200

60

SP4

60m

150

50

SP3 100

40m 40

SP2

50

30

SP1

00

20

200

400

600

800

1000 1200 (m3/h)

0

50

100 150 200 250 300 350 (L/s)

Air volume

Dimensions of the LGH-80RVX-E

Air exhaust fan 165

Position where duct direction change is possible
Bypass damper plate Ceiling suspension fixture (4-13X20 oval) 1131
77

EA (Exhaust air)

RA (Return air)

1051

1004 690

1001

692

954

115

OA (Outdoor air)

SA (Supply air)

20

More than 600

Maintenance space for Lossnay core, air filters, fan, high efficiency filter

150 to 250

124

Inspection

opening

450 x 450

or more

Air supply fan 70

Control box

404

Maintenance cover

Power supply cable opening

Lossnay core 79

High efficiency filter (sold separately) attachment position

908

79

208

192

22

Position where duct direction change is possible

Air filters

Unit (mm)

*Certain ratings and specifications may change due to product improvements or modifications. *Refer to the product manuals for safety precautions.

More than 600 150 to 250

OA (Outdoor air)

Maintenance space for

Lossnay core,

165

air filters,

fan,

high efficiency filter

Lossnay core 79

SA (Supply air)

20

115

Inspection opening 450 x 450 or more

Air supply fan 77 Control box Maintenance cover

40 404

Power supply cable opening

High efficiency filter (sold separately) attachment position

1144

79

258

242

Position where duct direction change is possible

Air filters

Unit (mm)

LGH-100/150RVX-E

Model

LGH-100RVX-E

LGH-150RVX-E

Electrical power supply

220-240V/50Hz, 220V/60Hz

220-240V/50Hz, 220V/60Hz

Ventilation mode

Heat recovery mode

Bypass mode

Heat recovery mode

Bypass mode

Fan speed

SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1

Running current (A)

2.50 1.20 0.50 0.17 2.50 1.20 0.51 0.19 3.71 1.75 0.70 0.29 3.85 1.78 0.78 0.30

Input power (W)

420 200 75 21 420 200 75 23 670 311 123 38 698 311 124 44

Air volume

(m3/h) (L/s)

1000 750 500 250 1000 750 500 250 1500 1125 750 375 1500 1125 750 375 278 208 139 69 278 208 139 69 417 313 208 104 417 313 208 104

External static pressure (Pa)

170 96 43 11 170 96 43 11 175 98 44 11 175 98 44 11

Temperature exchange efficiency (%)

80.0 83.0 86.5 89.5 - - - - 80.0 82.5 84.0 85.0 - - - -

Enthalpy exchange efficiency (%)

Heating Cooling

72.5 74.0 78.0 87.0 71.0 73.0 77.0 85.5

-

-

-

- 72.0 73.5 78.0 81.0 - 70.5 72.5 78.0 81.0 -

-

-

-

Noise (dB)

(Measured at 1.5m under the centre of unit in an anechoic chamber)

37.0

31.0

23.0

18.0

38.0

32.0

24.0

18.0

39.0

32.0

24.0

18.0

40.5

33.0

26.0

18.0

Weight (kg)

54

98

*The Air outlets noise (45 angle,1.5 metres in front of the unit) is about 21dB(LGH-100RVX-E) / 22dB(LGH-150RVX-E) greater than the indicated value (at Fan speed 4). *The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230V/50Hz. *For the specification at the other frequency contact your dealer. *Use this unit between static pressure 60Pa and 240Pa at Fan speed 4. Otherwise the motor protection may work and reduce its output or the noise level might be larger. (Only LGH-100RVX-E) *Use this unit with static pressure 250Pa or less at Fan speed 4. Otherwise the noise level might be larger (Only LGH-150RVX-E) *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

115

Static pressure (Pa) Exchange efficiency (%)
Static pressure (Pa) Exchange efficiency (%)

Characteristic Curve of the LGH-100RVX-E

350 300 250

250mm dia straight pipe
EnthaElnptyheaxlpcyTheeamxncgpheeareanftgfuiecreieefneficxcycieh(naCcnoygo(elHineegfaf)itciniegn)cy

length
100m
80m

90 80 70

60m

200

SP4

60

150 100
50 00 0

40m 50 SP3
40

SP2 SP1
500

1000

30 20 1500(m3/h)

50 100 150 200 250 300 350 400 (L/s) Air volume

Dimensions of the LGH-100RVX-E

Air exhaust fan

Position where duct direction change is possible

165

Bypass damper plate Ceiling suspension fixture (4-13X20 oval)

1131

77

40

EA (Exhaust air)

RA (Return air)

1278

1231 917

More than 600 150 to 250

OA (Outdoor air)

Maintenance space for

Lossnay core,

165

air filters,

fan,

high efficiency filter

Lossnay core 79

Inspection opening 450 x 450 or more
1144

SA (Supply air)

20

77

Air supply fan

40

Control box Maintenance cover

404

Power supply cable opening

High efficiency filter (sold separately) attachment position 79

Characteristic Curve of the LGH-150RVX-E

350

90

300 250 200

TeEmEnpnthetharlaapltypuyreexecxehcxahcnahgnaegnegefeefifcefiiefcfinieccineycn(yCc(yoHoeliantgin)g)

80 70 60

SP4

150

50

100 50 00 0

SP3

SP2

SP1

500

1000

1500

2000

2500

100 200 300 400 500 600 700 Air volume

40
30 20 3000(m3/h) 800 (L/s)

Dimensions of the LGH-150RVX-E

Bypass damper plate

Air exhaust fan

1010

270

EA (Exhaust air)

Ceiling suspension fixture (4-15 X 30 oval)

40

40

RA (Return air)

1045

690

690

1004

270

OA (Outdoor air)

More than 600 150 to 250

Maintenance space for Lossnay core, air filters, fan, high efficiency filter

Lossnay core 44

115

Inspection opening 450 x 450 or more

SA (Supply air)

26

Air supply fan

404 808

Control box

Maintenance cover

Power supply cable opening

High efficiency filter (sold separately) attachment position

1144

79

242 242 258 258

700 40

258

242

Position where duct direction change is possible

Air filters

Unit (mm)

*Certain ratings and specifications may change due to product improvements or modifications. *Refer to the product manuals for safety precautions.

Air filters

Unit (mm)
23

SPECIFICATIONS LGH-200RVX-E

Model

LGH-200RVX-E

Electrical power supply

220-240V/50Hz, 220V/60Hz

Ventilation mode

Heat recovery mode

Bypass mode

Fan speed

SP4

SP3

SP2

SP1

SP4

SP3

SP2

Running current (A)

4.88

2.20

0.88

0.33

4.54

2.06

0.87

Input power (W)

850

400

153

42

853

372

150

Air volume

(m3/h)

2000

1500

1000

500

2000

1500

1000

(L/s)

556

417

278

139

556

417

278

External static pressure (Pa)

150

84

38

10

150

84

38

Temperature exchange efficiency (%)

80.0

83.0

86.5

89.5

-

-

-

Enthalpy exchange efficiency (%)

Heating Cooling

72.5 71.0

74.0 73.0

78.0 77.0

87.0 85.5

-

-

-

Noise (dB)

(Measured at 1.5m under the centre of unit in an anechoic chamber)

40.0

36.0

28.0

18.0

41.0

36.0

27.0

Weight (kg)

110

*The Air outlets noise (45 angle,1.5 metres in front of the unit) is about 21dB greater than the indicated value (at Fan speed 4). *The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230V/50Hz. *For the specification at the other frequency contact your dealer. *Use this unit between static pressure 50Pa and 220Pa at Fan speed 4. Otherwise the motor protection may work and reduce its output or the noise level might be large. *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

SP1 0.35 49 500 139 10 -
19.0

Static pressure (Pa) Exchange efficiency (%)

Characteristic Curve of the LGH-200RVX-E
350 300 250 200 150

90

EnEtnhtaThelpamylppeyexercaxhtcuahrnaegneegxeecfhefiacffniiecgnieecnyecf(yfCic(oiHeonelicanytgin)g)

80 70

60

SP4

50

SP3

100

40

SP2

50

30

SP1

00

20

500

1000

1500

2000

2500

3000(m3/h)

0

100 200 300 400 500 600 700 800 (L/s)

Air volume

Dimensions of the LGH-200RVX-E

Bypass damper plate

Air exhaust fan

1010

270

EA (Exhaust air)

Ceiling suspension fixture (4-15 X 30 oval)

40

40

RA (Return air)

1272

917

917

1231

270

OA (Outdoor air)
Maintenance space for Lossnay core, air filters, fan, high efficiency filter
Lossnay core 44

More than 600 150 to 250

115

Inspection opening 450 x 450 or more

SA (Supply air)

26

404

Air supply fan

808

Control box

Maintenance cover

Power supply cable opening

High efficiency filter (sold separately) attachment position

1144

79

242 242 258 258

700 40

24

Air filters
*Certain ratings and specifications may change due to product improvements or modifications. *Refer to the product manuals for safety precautions.

Unit (mm)

LGH-150/200RVXT-E

Model

LGH-150RVXT-E

LGH-200RVXT-E

Electrical power supply

220-240V/50Hz, 220V/60Hz

220-240V/50Hz, 220V/60Hz

Ventilation mode

Heat recovery mode

Bypass mode

Heat recovery mode

Bypass mode

Fan speed

SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1

Running current (A)

4.30 2.40 1.10 0.36 3.40 1.80 0.77 0.31 5.40 2.70 1.10 0.39 5.00 2.20 0.85 0.34

Input power (W) Air volume

(m3/h) (L/s)

792 421 176 1500 1125 750 417 313 208

48 625 334 134 375 1500 1125 750 104 417 313 208

37 1000 494 197 56 916 407 150 45 375 2000 1500 1000 500 2000 1500 1000 500 104 556 417 278 139 556 417 278 139

External static pressure (Pa)

Supply 175 98 44 11 175 98 44 11 175 98 44 11 175 98 44 11 Return 100 56 25 6 100 56 25 6 100 56 25 6 100 56 25 6

Temperature exchange efficiency (%)

80.0 80.5 81.0 81.5 - - - - 80.0 81.0 82.5 84.0 - - - -

Enthalpy exchange efficiency (%)

Heating Cooling

70.0 71.0 73.0 75.0 69.0 70.0 72.0 74.0

-

-

-

- 72.5 73.5 77.0 83.0 - 70.0 71.0 74.5 80.5 -

-

-

-

Noise (dB)

39.5 35.5 29.5 22.0 39.0 33.0 26.5 20.5 39.5 35.5 28.0 22.0 40.5 34.5 27.0 20.5

Weight (kg)

156

159

*The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230V/50Hz. *For the specification at the other frequency contact your dealer. *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

90 750 255 750 1980
945.7 945.7 945.7 945.7 115 750 250 750 116 210 560 440 560 90 750 255 750
1980 945.7 945.7 945.7 945.7 115 750 250 750 116 210 560 440 560

Static pressure (Pa) Exchange efficiency (%)
Static pressure (Pa) Exchange efficiency (%)

Characteristic Curve of the LGH-150RVX-E

450

90

Temperature exchange efficiency

400 350

Enthalpy exchange efficiency (Heating) Enthalpy exchange efficiency (Cooling)

80 70

300

60

250

200

SP4

SP3 150

Supply Return

100

SP2

50

SP1

00

500

1000

1500

2000

2500(m3/h)

0

100

200

300

400

500

600

Air volume

(L/s)

Dimensions of the LGH-150RVX-E

Bypass damper plate

60 250

OA (Outdoor air)

RA (Return air)

Flange 1500

215 250

Lossnay cores Control box

Bypass damper plate

50

1450

Air exhaust fan (Outside) Air exhaust fan (Inside) Ceiling suspension fixture(6-15 X 30 oval)

Flange EA (Exhaust air)

287

58

227

Exhaust

Pipe guide

SA (Supply air)
Flange Air supply fan (Inside) Air supply fan (Outside)

Supply

Power supply cable opening

250 132
424 500

242 258
When using 250 duct

RA air filters OA air filters

Unit (mm)

*Certain ratings and specifications may change due to product improvements or modifications. *Refer to the product manuals for safety precautions.

Characteristic Curve of the LGH-200RVX-E

450

90

Temperature exchange efficiency

400

Enthalpy exchange efficiency (Heating)

80

350

Enthalpy exchange efficiency (Cooling)

70

300

60

250

Supply

200

Return

SP4

150

SP3

100

SP2

50

SP1

00

500

1000

1500

2000

2500

3000(m3/h)

0

200

400

600

800 (L/s)

Air volume

Dimensions of the LGH-200RVX-E

Bypass damper plate

60 250

OA (Outdoor air)

RA (Return air)

Flange 1500

215 250

Lossnay cores Control box

Bypass damper plate

50

1450

Air exhaust fan (Outside) Air exhaust fan (Inside) Ceiling suspension fixture(6-15 X 30 oval)

Flange EA (Exhaust air)

287

58

227

Exhaust

Pipe guide

SA (Supply air)
Flange Air supply fan (Inside) Air supply fan (Outside)

Supply

Power supply cable opening

250 132
424 500

242 258 When using
250 duct

RA air filters OA air filters

Unit (mm)

25

SPECIFICATIONS LGH-250RVXT-E

Model

LGH-250RVXT-E

Electrical power supply

220-240V/50Hz, 220V/60Hz

Ventilation mode

Heat recovery mode

Bypass mode

Fan speed

SP4

SP3

SP2

SP1

SP4

SP3

SP2

SP1

Running current (A)

7.60

3.60

1.40

0.57

6.90

3.10

1.30

0.49

Input power (W) Air volume

1446

687

244

82

1298

587

212

69

(m3/h)

2500

1875

1250

625

2500

1875

1250

625

(L/s)

694

521

347

174

694

521

347

174

External static pressure (Pa)

Supply

175

Return

100

98 56

44 25

11

175

98

6

100

56

44 25

11 6

Temperature exchange efficiency (%)

77.0

79.0

80.5

82.5

-

-

-

-

Enthalpy exchange efficiency (%)

Heating Cooling

68.0 65.5

71.5 69.0

74.0 71.5

79.0 76.5

-

-

-

-

Noise (dB)

43.0

39.0

32.0

24.0

44.0

38.5

31.0

22.5

Weight (kg)

198

*The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230V/50Hz. *For the specification at the other frequency contact your dealer. *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

Static pressure (Pa) Exchange efficiency (%)

Characteristic Curve of the LGH-250RVXT-E

450

90

400 350 300

Temperature exchange efficiency EEntnhtahlaplypyexecxhcahnagnegeefefifcfiiceinecnycy(H(Ceaootinlingg) )

80 70 60

250

Supply

200

Return

SP4

150

SP3

100

SP2

50

SP1

00

1000

2000

3000

4000(m3/h)

0

200

400

600

800

1000

(L/s)

Air volume

Dimensions of the LGH-250RVXT-E

Bypass damper plate

60 250

OA (Outdoor air)

RA (Return air)

Flange 1500

215 250

Lossnay cores Control box

Bypass damper plate

50

1450

90 750 255 750 1980
945.7 945.7 945.7 945.7 115 750 250 750 116 210 560 440 560

Air exhaust fan (Outside) Air exhaust fan (Inside) Ceiling suspension fixture(6-15 X 30 oval)

Flange EA (Exhaust air)

287

58

227

Exhaust

Pipe guide

SA (Supply air)
Flange Air supply fan (Inside) Air supply fan (Outside)

Supply

Power supply cable opening

250 132
424 500

242 258
When using  250 duct

26

RA air filters OA air filters
*Certain ratings and specifications may change due to product improvements or modifications. *Refer to the product manuals for safety precautions.

Unit (mm)

GUF-50/100RD4

Model

GUF-50RD4

GUF-100RD4

Electrical power supply

220-240V/50Hz

220-240V/50Hz

Ventilation mode

Heat recovery mode

Bypass mode

Heat recovery mode

Bypass mode

Fan speed

High

Low

High

Low

High

Low

High

Low

Running current (A)

1.15

0.70

1.15

0.70

2.20

1.73

2.25

1.77

Input power (W) Air volume

(m3/h) (L/s)

235-265 500 139

150-165 400 111

235-265 500 139

150-165 400 111

480-505 1000 278

370-395 800 222

490-515 1000 278

385-410 800 222

External static pressure (Pa)

140

90

140

90

140

90

140

90

Temperature exchange efficiency (%)

77.5

80

-

-

79.5

81.5

-

-

Enthalpy exchange efficiency (%)

Heating Cooling

68 65

71 67

-

-

71 69

74 71

-

-

Cooling capacity (kW)

5.57(1.94)

11.44(4.12)

Heating capacity (kW)

6.21(2.04)

12.56(4.26)

Capacity equivalent to the indoor unit

P32

P63

Noise (dB)

(Measured at 1.5m under the centre of the unit)

33.5-34.5

29.5-30.5

35-36

29.5-30.5

38-39

34-35

38-39

35-36

Weight (kg)

48

82

*Cooling/Heating capacity indicates the maximum value at operation under the following conditions. Cooling: Indoor: 27cDB/19cWB Outdoor: 35cDB/24cWB Heating: Indoor: 20cDB/13.8cWB Outdoor: 7cDB/6cWB *The figures in( ) indicates heat recovering capacity of heat exchange core. *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

Characteristic Curve of the GUF-50RD4

Exchange efficiency (%)

90 80 70 60 400 50
300

TEenEtmhnatphlpaeylrpaeyxteucxhrceahnaegnxegceehfefaicffniiecgineecnycey(fCf(ioHcoeielainntignc)gy)

200mm dia
pipe length 100
80

High

60

200 Low
100

40 20

Static pressure (Pa)

00

200

400

600

800(m3/h)

0 20 40 60 80 100 120 140 160 180 200 220 (L/s) Air volume

Dimensions of the GUF-50RD4

Air exhaust fan 124 EA (Exhaust air)

Position where duct direction change is possible

Bypass damper plate Ceiling suspension fixture

1185

Air supply fan

RA (Return air)

435

372.5

1048

1016

745

OA (Outdoor
air)

SA (Supply air)

20

100

22

More than 600 150 to 250

Maintenance cover

124

Control box

Inspection Inspection Power supply cable opening

opening

opening

Maintenance space for heat exhanger

450 Maintenance space for Lossnay core air filters, fan, high efficiency filter

158.5 317

Lossnay core 79
124

High efficiency filter 1288 (Optional parts) 79
266

Heat exchanger Maintenance cover

60

192 208

Ceiling suspension fixture Position where duct direction change is possible

Air filters

135

30

347
Drain discharge hole (VP25 connection)

Gas pipe (Flare 12.7) Liquid pipe (Flare 6.35) Unit (mm)

*Certain ratings and specifications may change due to product improvements or modifications. *Refer to the product manuals for safety precautions.

Characteristic Curve of the GUF-100RD4

Exchange efficiency (%)

90 80 70 500 60 400 50 300

EnthalpyTEeenxmtchhpaaelpnryageetuxercefhfiaceinxegcnehcyaenf(fCgiceoieonelicfnfyigc)(iHenecayting) High

250mm dia
pipe length
100

Static pressure (Pa)

200 Low
100

80 60 40 20

00 200 400 600 800 1000 1200 1400 (m3/h)

0 50 100 150 200 250 300 350 400 (L/s) Air volume

GUF-100RD4
149 Air exhaust fan
EA (Exhaust
air)

Position where duct direction change is possible

Bypass damper plate Ceiling suspension fixture

1465

Air supply fan

RA (Return air)

670

460

1271

1231

920

OA (Outdoor
air)

SA (Supply air)

100

20

16

More than 600 150 to 250

Maintenance cover

149 Inspection

Inspection Power supply cable opening

opening

opening Maintenance space for

600

Control box heat exhanger

199 398

Maintenance space for Lossnay core air filters, fan, high efficiency filter

Lossnay core

High efficiency filter

(Optional parts)

79

1580

79

149

280

Heat exchanger Maintenance cover

60

242 258

Ceiling suspension fixture

Position where duct direction

change is possible

Air filters

169

30

361
Drain discharge hole (VP25 connection)

Gas pipe (Flare 15.88) Liquid pipe (Flare 9.52)
Unit (mm)

27

SPECIFICATIONS GUF-50/100RDH4

28

Model

GUF-50RDH4

GUF-100RDH4

Electrical power supply

Ventilation mode

Fan speed

Running current (A)

Input power (W)

Air volume

(m3/h) (L/s)

External static pressure (Pa)

Temperature exchange efficiency (%)

Enthalpy exchange efficiency (%)

Heating Cooling

Cooling capacity (kW)

Heating capacity (kW)

Capacity equivalent to the indoor unit

Humidifying

Humidifier Humidifying capacity(kg/h)

Water supply pressure

Noise (dB)

(Measured at 1.5m under the centre of the unit)

Weight (kg)

220-240V/50Hz

220-240V/50Hz

Heat recovery mode

Bypass mode

Heat recovery mode

Bypass mode

High

Low

High

Low

High

Low

High

Low

1.15

0.70

1.15

0.70

2.20

1.76

2.25

1.77

235-265 150-165 235-265 150-165 480-505 385-400 490-515 385-410

500

400

500

400

1000

800

1000

800

139

111

139

111

278

222

278

222

125

80

125

80

135

86

135

86

77.5

80

-

-

79.5

81.5

-

-

68

71

-

-

71

74

-

-

65

67

-

-

69

71

-

-

5.57(1.94)

11.44(4.12)

6.21(2.04)

12.56(4.26)

P32

P63

Permeable film humidifier

2.7(heating)

5.4(heating)

Minimum pressure : 2.0 × 104Pa Maximum pressure : 49.0 × 104Pa

33.5-34.5 29.5-30.5

35-36

29.5-30.5

38-39

34-35

38-39

35-36

51(filled with water 55)

88(filled with water 96)

*Cooling/Heating capacity indicates the maximum value at operation under the following conditions. Cooling: Indoor: 27cDB/19cWB Outdoor: 35cDB/24cWB Heating: Indoor: 20cDB/13.8cWB Outdoor: 7cDB/6cWB *The figures in( ) indicates heat recovering capacity of heat exchange core. *Figures in the chart are measured according to Japan Industrial Standard (JIS B 8628). Characteristic Curves are measured by chamber method.

Characteristic Curve of the GUF-50RDH4

Exchange efficiency (%)

90 80 70 60 50
300

EnTtehEamnlptphyaeelrpxayctheuaxrncegheaenxegfcfeihceiaeffnniccgiyeen(Cceyoffo(iHclineiegan)tincgy)

200mm dia
pipe length 100
80

High

60

200 40

100

Low

20

Static pressure (Pa)

00

200

400

600

800 (m3/h)

0 20 40 60 80 100 120 140 160 180 200 220 (L/s) Air volume

Characteristic Curve of the GUF-100RDH4

Exchange efficiency (%)

90 80 70 60
300 200 100

EnthalpyTEeenxmthcphaalepnryageteuxrecefhfiaecnixegcnehcaeynf(fgiCceioeonelcifnfyigc()iHenecayting) High

250mm dia
pipe length
100

80

60 Low
40

20

Static pressure (Pa)

00 200 400 600 800 1000 1200 1400 (m3/h)

0 50 100 150 200 250 300 350 400 (L/s) Air volume

Dimensions of the GUF-50RDH4

Air exhaust fan 124 EA (Exhaust air)
OA (Outdoor
air)

1016

Position where duct direction change is possible Bypass damper plate Ceiling suspension fixture

1185

Air supply fan

RA (Return air) Solenoid valve unit with pressure requlator

372.5

1048

SA (Supply air)

100

20

745

435

22

More than 600 150 to 250

Maintenance cover

124 Inspection opening

Control box

Inspection opening

Power supply cable opening Maintenance space for heat exhanger

450

permeable-film humidifier Maintenance space for Lossnay core

air filters, fan, high efficiency filter

158.5 317

Lossnay core

High efficiency filter Heat exchanger

79

1288 (Optional parts) 79

Permeable-film humidifier

124

79 266

Maintenance cover(humidifier)

60

192 208

Ceiling suspension fixture Position where duct direction change is possible

Air filters

Water intake strainer (R1/2 of External thread)

30 99 135

347
Drain discharge hole (VP25 connection)

Gas pipe (Flare 12.7) Liquid pipe (Flare 6.35) Unit (mm)

Dimensions of the GUF-100RDH4

149 Air exhaust fan
EA (Exhaust
air)

Position where duct direction change is possible Bypass damper plate Airsupply fan Ceiling suspension fixture

1465

Solenoid valve unit with pressure requlator

RA (Return air)

670

460

1271

1231

920

OA (Outdoor
air)

SA (Supply air)

100

20

16

More than 600 150 to 250

Maintenance cover

149

Inspection Inspection Power supply cable opening

opening

opening Maintenance space for

600

Control box

heat exhanger permeable-film humidifier

199 398

Maintenance space for Lossnay core

air filters, fan, high efficiency filter

Lossnay core

High efficiency filter

Heat exchanger

79 149 Ceiling suspension fixture

60

(Optional parts)

1580

79

79 280

Permeable-film humidifier Maintenance cover(humidifier)

242 258

Position where duct direction

change is possible

Air filters

Water intake strainer (R1/2 of External thread)

169

30 110

361
Drain discharge hole (VP25 connection)

Gas pipe (Flare 15.88) Liquid pipe (Flare 9.52)
Unit (mm)

VL-220CZGV-E

Model

Electrical power supply

Ventilation mode

Fan speed

Running current

Input power (W)

Air volume

(m3/h) (L/s)

External static pressure (Pa)

Temperature exchange efficiency (%)

Noise (dB)

Weight (kg)

Specific energy consumption class

Fan speed 4 0.60 80 230 64 164 82.0 31.0

VL-220CZGV-E

220-240V/50Hz 220V/60Hz

Heat recovery mode

Fan speed 3

Fan speed 2

0.29

0.18

35

18.5

165

120

46

33

84

44

84.0

85.0

25.0

19.0

31

A

Fan speed 1 0.11 8.5 65 18 13 86.0 14.0

Characteristic Curve of the VL-220CZGV-E

125mm dia straight pipe length

400

90

35m

300

Temperature exchange efficiency

25m 80

Exchange efficiency (%)

Static pressure (Pa)

Fan Speed 4

15m

200

70

Fan Speed 3 100
Fan Speed 2

Fan Speed 1

00

100

200

0

20

40

60

Air volume

300

80

100

60
40050(m3/h) (L/s)

Dimensions of the VL-220CZGV-E
143 Power supply cable opening Ceiling suspension Fixture
Duct connecting flange (SA)
SA (Supply air)

174 119 33 Drain outlet

116

86
RA1 (Return air)

850

20 848(Ceiling suspension fixture)

229

271

EA (Exhaust air)
Duct connecting flange (EA) 139

8

8

720 775(Ceiling suspension fixture)
815
151 Exhaust air filter case

OA (Outdoor air)
199

31

80

295

234

Duct connecting flange (RA1)
Auxiliary fixture
Duct connecting flange (OA)

146 124 98
885

31 320 362

Drain pan

Supply air filter case

Unit (mm)

29

NOTES
30

NOTES
31

For more information contact
www.mitsubishielectric.com.au Call 1300 722 228
Distributed and guaranteed throughout Australia by MITSUBISHI ELECTRIC AUSTRALIA PTY. LTD. (Incorporated in New South Wales) A.B.N. 58 001 215 792
Please refer to the specifications before installation and servicing of these products. The purchaser must ensure that the person and/ or companies are suitably licensed and experienced, are permitted to install, service and repair the air conditioners. Suitable access for warranty and service is required. Specifications, designs and other content appearing in this brochure are current at the time of printing, and is subject to change without notice. Images are representational for illustration purposes. New publication, effective April 2015. Superseding L-179-6-C7458-F SI 1204. PRINTED: JANUARY 2018.

