Samsung Air Conditioner Installation Manual

Model: AC***RNCDKG

Document Number: DB68-08133A-04

Thank you for purchasing this Samsung air conditioner. Before operating this unit, please read this manual carefully and retain it for future reference.

Safety Information

⚠️ WARNING: Hazards or unsafe practices that may result in severe personal injury or death.

❗ CAUTION: Hazards or unsafe practices that may result in minor personal injury or property damage.

Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.

General Information

⚠️ WARNING

Always disconnect the air conditioner from the power supply before servicing it or accessing its internal components.

⚠️ WARNING

Carefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order to be able to use it as reference after installation.

Installing the unit

⚠️ WARNING

IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines.

Power supply line, fuse or circuit breaker

⚠️ WARNING

❗ CAUTION

Installation Procedure

Step 1 Checking and preparing accessories

The following accessories are supplied with the indoor unit.

AC052/071RNCDKG

AccessoryQuantity
Pattern sheet(1)
User manual(1)
Installation manual(1)
Plate Hanger(2)
Cable-Tie(5)
Wireless Remote Controller(1)
Remote Controller Holder(1)
Batter(2)
M4 X 16 Tapped Screw(2)

AC100/120/140RNCDKG

AccessoryQuantity
Pattern sheet(2)
Insulation cover pipe A(1)
Insulation cover pipe B(1)
Insulation drain(1)
Flexible hose clamp(1)
Flexible hose(1)
Cable-tie(8)
User manual(1)
Installation manual(1)
Insulation(3)
Rubber(4)

Step 2 Choosing the installation location

❗ CAUTION: This product must be installed on the ceiling. (Do not make it stand up for use.)

Installation location requirements

⚠️ WARNING

If appliances contain R-32 refrigerant, then the floor area of the room in which the appliances are installed, operated and stored must be larger than the minimum floor area defined in table below A (m²).

Minimum required room area (A, m²)
m (kg)Ceiling-mounted type
≤ 1.842No requirement
1.8433.64
1.93.75
2.03.95
2.24.34
2.44.74
2.65.13
2.85.53
3.05.92
3.26.48
3.47.32
3.68.20
3.89.14
4.010.1
4.211.2
4.412.3
4.613.4
4.814.6
5.015.8
5.217.1

m: Total refrigerant charge in the system

A: Minimum required room area

? NOTE: It's important to consider either the table 1 or taking into consideration the local law regarding the minimum living space of the premises.

Minimum installation height of indoor unit is 0.6 m for floor mounted, 1.8 m for wall, 2.2 m for ceiling.

❗ CAUTION

Do not install the air conditioner in following places.

Step 3 Installing the indoor unit

Ceiling installation (AC052/071RNCDKG)

Spacing requirements:

Diagram description: Shows a side view of the indoor unit mounted on a ceiling, with dimensions indicating 300 mm clearance from the front and 50 mm from the rear.

  1. Select pipe directions.
  2. Drill holes for anchor bolts according to the distance and mount them. ? NOTE: Use the pattern sheet.
  3. Install the unit onto the ceiling. Be sure to arrange the drain hose so that it is leveled lower than the drain hose connecting port of the indoor unit. ? NOTE: For proper drainage of condensate, give a 1° or less slant to the side of the unit which will be connected with the drain hose as shown in the figure. (The gap between the lower end of the indoor unit and the ceiling should be 12 mm or less.)

Diagram description: Shows a side view of the indoor unit on a ceiling, with a drain hose sloping downwards. Indicates a 1° or less slant for the connection pipe and drain hose.

❗ CAUTION: Ensure that the ceiling is strong enough to support the weight of the indoor unit.

? NOTE: The gap between the lower end of the indoor unit and the ceiling should be 1° (16 mm) or less.

Ceiling installation (AC100/120/140RNCDKG)

Spacing requirements:

Diagram description: Shows a side view of the indoor unit mounted on a ceiling, with dimensions indicating 300 mm clearance from the front and 50 mm from the rear. Also shows wall clearance requirements: 50 mm from wall, 300 mm or more from other walls.

  1. Select pipe directions. When the directions are selected, drill 3-1/8"-(100mm, for pipe and cables) and 1-3/4"-(40mm, for drain hose) diameter holes on the wall so that it slants slightly downwards toward the outdoor for smooth water flow. ? NOTE: Use the pattern sheet to select pipe directions.
  2. Drill holes for anchor bolts according to the distance and mount them. ? NOTE: Use the pattern sheet.
  3. Insert bolt anchors. Use existing ceiling supports or construct a suitable support as shown in figure.

Diagram description: Shows how to insert bolt anchors into a ceiling, with labels for "Hole in anchor", "Hole in plug", "Concrete", "Insert", and "Suspension bolt (M8) field supply".

  1. Install the suspension bolts depending on the ceiling type.
  2. Screw eight nuts to the suspension bolts making space for hanging the indoor unit. ? NOTE: You must install all the suspension rods.
  3. When Hanging the set, firstly unscrew the screws from the both of sides, and then disassemble the Case-sides, or else the case-side will be damaged by disassembling it directly.

Diagram description: Shows unscrewing two screws from the both sides of the unit.

  1. Reassemble the Case-sides, tightening the screws after hanging the set.

Diagram description: Shows removing the Case-sides from the both of sides.

  1. Hang the indoor unit to the suspension bolts between two nuts.

Diagram description: Shows the indoor unit being hung on suspension bolts with rubber and bracket components.

❗ CAUTION: Piping must be laid and connected inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the piping into position for connection to the unit before placing the unit inside the ceiling.

  1. Screw the nuts to suspend the unit.

❗ CAUTION: Ensure that the ceiling is strong enough to support the weight of the indoor unit. Before hanging the unit, test the strength of each attached suspension bolt.

Step 4 Purging inert gas from the indoor unit

The indoor unit comes with nitrogen gas (inert gas) charged at the factory. Therefore, all inert gas must be purged before connecting the assembly piping.

Unscrew the pinch pipe at the end of each refrigerant pipe.

Diagram description: Shows the indoor unit with refrigerant pipes and pinch pipes to be unscrewed.

Diagram description: Shows the indoor unit with refrigerant pipes, side cover, and pinch pipes.

? NOTE: To prevent dirt or foreign objects from getting into the pipes during installation, do not remove the pinch pipe completely until you are ready to connect the piping. The designs and shape are subject to change according to the model.

Step 5 Cutting and flaring the pipes

1 Make sure that you have the required tools available: pipe cutter, reamer, flaring tool, and pipe holder.

2 If you wish to shorten the pipes, cut them with a pipe cutter, ensuring that the cut edge remains at a 90° angle to the side of the pipe. Refer to the illustrations below for examples of edges cut correctly and incorrectly.

Diagram description: Shows correct and incorrect pipe cuts: Correct (90° angle), Inclined, Damaged Surface, Cracked, Uneven Thickness.

Diagram description: Shows pipe cutting with a pipe cutter, and examples of pipe edges: Oblique, Rough, Burr.

3 To prevent any gas from leaking out, remove all burrs at the cut edge of the pipe, using a reamer.

4 Slide a flare nut on to the pipe and modify the flare.

Diagram description: Shows a pipe with a flare nut, and a detailed view of the flare with dimensions: 90° ±2°, 45° ±2°, R 0.4 to 0.8 mm.

Flare dimensions
Outer Diameter (D)Depth (A)Flare dimension (L)
Ø6.35 mm1.3 mm8.7 to 9.1 mm
Ø9.52 mm1.8 mm12.8 to 13.2 mm
Ø12.70 mm2.0 mm16.2 to 16.6 mm
Ø15.88 mm2.2 mm19.3 to 19.7 mm
Ø19.05 mm2.2 mm23.6 to 24.0 mm

5 Check that the flaring is correct, referring to the illustrations below for examples of incorrect flaring.

Step 6 Connecting the assembly pipes to the refrigerant pipes

There are two refrigerant pipes of different diameters:

1 Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, first manually and then with a torque wrench, a spanner applying the following torque.

Outer diameter (mm)Torque (N•m)
06.3514 to 18
09.5234 to 42
012.7049 to 61
015.8868 to 82
019.05100 to 120

(1 N•m=10 kgf.cm)

Diagram description: Shows a spanner and torque wrench tightening a union with a flare nut. Illustrates the connection of pipes.

? NOTE: If the pipes must be shortened, see Step 5 Cutting and flaring the pipes on page 11.

❗ CAUTION: Connect the indoor and outdoor units using pipes with flared connections (not supplied). For the lines, use insulated, unwelded, degreased and deoxidized copper pipe (Cu DHP type to ISO 1337 or UNI EN 12735-1), suitable for operating pressures of at least 4.2 MPa and for a burst pressure of at least 20.7 MPa. Copper pipe for hydro-sanitary applications is completely unsuitable.

Step 7 Performing the gas leak test

LEAK TEST WITH NITROGEN (before opening valves): In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-32, it's responsible of installer to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 40 bar (gauge).

LEAK TEST WITH R-32 (after opening valves): Before opening valves, discharge all the nitrogen into the system and create vacuum. After opening valves check leaks using a leak detector for refrigerant R-32.

Diagram description: Shows the AC052/071RNCDKG unit with a leak check point indicated on the refrigerant pipe.

Diagram description: Shows the AC100/120/140RNCDKG unit with a leak check point indicated on the refrigerant pipe.

? NOTE: The designs and shape are subject to change according to the model.

Step 8 Insulating the refrigerant pipes

Once you have checked that there are no leaks in the system, you can insulate the piping and hose.

1 To avoid condensation problems, place Acrylonitrile Butadien Rubber separately around each refrigerant pipe.

Diagram description: Shows cross-sections of pipes with 'No gap' and 'NBR' labels, indicating proper insulation.

Diagram description: Shows a hanger with refrigerant pipe insulation and additional insulation, with dimensions 'a' and 'a x 3'.

? NOTE: Always make the seam of pipes face upwards.

2 Wind insulating tape around the pipes and drain hose avoiding compressing the insulation too much.

Diagram description: Shows indoor unit with insulation cover pipe and insulation pipe, with a note to "Be sure to overlap the insulation".

❗ CAUTION: Be sure to wrap insulation tightly without any gaps.

3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit.

4 The pipes and electrical cables connecting the indoor unit with the outdoor unit must be fixed to the wall with suitable ducts.

❗ CAUTION: Make sure that all refrigerant connection must be accessible for easy maintenance and detachment.

5 Select the insulation of the refrigerant pipe.

Insulation type (heating/cooling)
PipePipe sizeStandard (Less than 30°C, 85%)High humidity (Over 30°C, 85%)Remarks
EPDM, NBREPDM, NBR
Liquid pipe06.35 to 09.529t9tThe internal temperature is higher than 120°C.
Ø12.7 to 019.0513t13t
Gas pipe06.3513t19t
09.5219t25t
012.70
015.88
019.05

Step 9 Installing the drain hose and drain pipe

Care must be taken when installing the drain hose for the indoor unit to ensure that any condensation water is correctly drained outside.

? NOTE:

Diagram description: Shows the indoor unit with a flexible hose clamp of the drain hose, joint of drain hose, drain hose, and wrap thermal sleeve hose. A-A' cross-section is shown.

When installing insulation in the places and conditions below, use the same insulation that is used for high humidity conditions.

<Geological condition>

High humidity locations such as shorelines, hot springs, lake or riversides, and ridges (when part of the building is covered by earth and sand)

<Operation purpose condition>

Restaurant ceiling, sauna, swimming pool etc.

<Building construction condition>

Ceilings frequently exposed to moisture and cooling are not covered. For example, pipes installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently.

Places (where the pipes are installed) that are highly humid due to a lack of ventilation.

  1. Insert the drain hose to bottom of the outfall of water basin.
  2. Lock flexible hose clamp of the drain hose according to the figure.
  3. Wind and wrap flexible hose clamp and drain hose fully with thermal insulation sponge; fix both ends of external layer with ribbon for thermal insulation.
  4. After being installed, drain hose must be insulated fully by heat insulating material. (To be provided at site.)

Diagram description: Shows tightening the flexible hose clamp of the drain hose and attaching insulation after tightening.

Diagram description: Shows ceiling installation with a wall and hole. Illustrates correct and incorrect drain hose routing: No grade, No slack, No in the water.

Step 10 Optional: Installing DPM

? NOTE: To find DPM allowable indoor unit models according to outdoor unit models, refer to outdoor installation manual.

❗ CAUTION: When installing DPM, only one external controller can be connected.

Diagram description: Shows how to extend the drain pipe by connecting an extra drain pipe. Also shows how to close the piping connection hole after installation using insulation.

Step 11 Optional: Installing interface module

AC100/120/140RNCDKG

Accessories (Interface module: MIM-B14)

External ControlPCB Case
Haness Wire (2P)Haness Wire (4P)
Screw
  1. Fix the case at with bolts on the side of the control box in the indoor unit. (See the picture)

Diagram description: Shows the interface module PCB being attached to the case in the control box of the indoor unit.

  1. Attach the Interface module PCB to the case in the control box of the indoor unit, then connect the power and the communication cable between the Interface module and the indoor unit;
  2. If you install a Interface module to an indoor unit, every outdoor unit which is connected to an indoor unit can be controlled simultaneously.
  3. Each indoor unit connected to the same centralized controller has its own Interface module.

Step 12 Connecting the power and communication cables

❗ CAUTION: Always remember to connect the refrigerant pipes before performing the electric connections. When disconnecting the system, always disconnect the electric cables before disconnecting the refrigerant pipes.

❗ CAUTION: Always remember to connect the air conditioner to the grounding system before performing the electric connections. Use a crimp ring terminal at the end of each wire.

The indoor unit is powered through the outdoor unit by means of a H07 RN-F connection cable (or a more power model), with insulation in synthetic rubber and a jacket in polychloroprene (neoprene), in accordance with the requirements specified in the standard EN 60335-2-40.

1 phase (**100/120/140**)

Diagram description: Shows the wiring for a 1-phase connection (100/120/140) for the Indoor Unit, including Indoor Power, Main power cable, Communication cable, and Cable clamp.

  1. Remove the screw on the electrical component box and remove the cover plate.
  2. Route the connection cord through the side of the indoor unit and connect the cable to the terminals refer to the figure below.
  3. Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.
  4. Reassemble the electrical component box cover, carefully tightening the screw.

1 phase (**052/071**)

Diagram description: Shows the wiring for a 1-phase connection (052/071) for the Indoor Unit and Outdoor Unit, including Wired Remote Controller (Optional), Cable clamp, Indoor Power, Main power cable, and Communication cable.

3 phase (**100/120/140**)

Diagram description: Shows the wiring for a 3-phase connection (100/120/140) for the Indoor Unit, including Indoor Power, Main power cable, Communication cable, Cable clamp, and 3 Phase 4 Wires power cable (AC 380V).

Indoor power supply
Power supplyMax/Min(V)Indoor power cable
220 to 240V, 50 Hz±10%0.75 mm², 3 wires
Communication cable
Communication cable
0.75 mm², 2 wires

Step 13 Optional: Extending the power cable

1 Prepare the following tools.

ToolsSpecShape
Crimping pliersMH-14
Connection sleeve (mm)20x06.5 (HxOD)
Insulation tapeWidth 19 mm

Diagram description: Shows contraction tube dimensions (70x08.0 LXOD) and AC power/Communication screw sizes.

Tightening torque (kgf.cm)

8.0 to 12.012.0 to 18.0
M3.5
M4

1 N-m = 10 kgf.cm

❗ CAUTION: For information about the power cable specifications for indoor and outdoor units, refer to the installation manual.

❗ CAUTION: When installing the indoor unit in a computer room or a server room, use the double shielded communication cable (tape aluminum / polyester braid + copper) of FROHH2R type.

Diagram description: Shows power cable routing with dimensions and a pre-installed tube for the power cable.

2 As shown in the figure, peel off the shields from the rubber and wire of the power cable.

3 Insert both sides of core wire of the power cable into the connection sleeve.

Diagram description: Shows Method 1 and Method 2 for connecting core wires into a connection sleeve.

4 Using a crimping tool, compress the two points and flip it over and compress another two points in the same location.

Diagram description: Shows the compression dimension should be 8.0. After compressing, pull both sides of the wire to make sure it is firmly pressed.

Diagram description: Shows Method 1 and Method 2 for compressing the connection sleeve, with 4 compressions each.

5 Apply heat to the contraction tube to contract it.

Diagram description: Shows Method 1 and Method 2 with contraction tube and insulation tape.

6 Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape. Three or more layers of insulation are required.

Diagram description: Shows Method 1 and Method 2 with insulation tape applied over the contraction tube, with dimensions 40 mm and 35 mm.

7 After tube contraction work is completed, wrap it with the insulation tape to finish.

Diagram description: Shows Method 1 and Method 2 with final insulation tape wrapping.

❗ CAUTION: Make sure that the connection parts are not exposed to outside.

⚠️ WARNING: In case of extending the electric wire, please DO NOT use a round-shaped Pressing socket. Incomplete wire connections can cause electric shock or a fire.

Step 14 Setting the indoor unit addresses and the installation options

Set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice when setting indoor unit address and installation option.

Please use the proper wireless remote controller which can set 24 digit option code.

Please refer to the wired remote controller installation manual for setting with the wired remote controller.

Common steps for setting the addresses and options

Diagram description: Shows the remote control display and buttons for entering mode for setting option and option setting mode. Buttons include Mode, Temp Up/Down, Fan Up/Down, Timer, SET, and directional arrows.

1 Enter the mode for setting the options:

  1. Remove the batteries from the remote control, and then insert them again.
  2. While holding down the ⬆️ (High Temp) and ⬇️ (Low Temp) buttons simultaneously, insert the batteries into the remote control.
  3. Make sure that you are entered to the mode for setting the options:

Diagram description: Shows the remote control display showing "On 00 Auto".

2 Set the option values.

❗ CAUTION: The total number of available options are 24: SEG1 to SEG24. Because SEG1, SEG7, SEG13, and SEG19 are the page options used by the previous remote control models, the modes to set values for these options are skipped automatically.

Set a 2-digit value for each option pair in the following order: SEG2 and SEG3 → SEG4 and SEG5 → SEG6 and SEG8 → SEG9 and SEG10 → SEG11 and SEG12 → SEG14 and SEG15 → SEG16 and SEG17 → SEG18 and SEG20 → SEG21 and SEG22 → SEG23 and SEG24

Option Code Table
SEG1SEG2SEG3SEG4SEG5SEG6
0XXXXX
SEG7SEG8SEG9SEG10SEG11SEG12
1XXXXX
SEG13SEG14SEG15SEG16SEG17SEG18
2XXXXX
SEG19SEG20SEG21SEG22SEG23SEG24
3XXXXX

On (SEG1 to SEG12)

Diagram description: Shows remote display "On 00 Auto".

Off (SEG13 to SEG24)

Diagram description: Shows remote display "Off 00 Auto".

Take the steps presented in the following table:

  1. Setting SEG2, SEG3 option: Press Low Fan button ⬇️ to enter SEG2 value. Press High Fan button ⬆️ to enter SEG3 value. Each time you press the button, 01–E–F will be selected in rotation.
  2. Setting Cool mode: Press Mode button to be changed to Cool mode in the ON status.
  3. Setting SEG4, SEG5 option: Press Low Fan button ⬇️ to enter SEG4 value. Press High Fan button ⬆️ to enter SEG5 value. Each time you press the button, 01–E–F will be selected in rotation.
Status
SEG2SEG3
On0080
AutoCool
SEG4SEG5
On8080
CoolCool

Step 14 Setting the indoor unit addresses and the installation options

Set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice when setting indoor unit address and installation option.

Please use the proper wireless remote controller which can set 24 digit option code.

Please refer to the wired remote controller installation manual for setting with the wired remote controller.

Common steps for setting the addresses and options

Diagram description: Shows remote control display for entering mode for setting option and option setting mode.

1 Enter the mode for setting the options:

  1. Remove the batteries from the remote control, and then insert them again.
  2. While holding down the ⬆️ (High Temp) and ⬇️ (Low Temp) buttons simultaneously, insert the batteries into the remote control.
  3. Make sure that you are entered to the mode for setting the options:

Diagram description: Shows remote display "On 00 Auto".

2 Set the option values.

❗ CAUTION: The total number of available options are 24: SEG1 to SEG24. Because SEG1, SEG7, SEG13, and SEG19 are the page options used by the previous remote control models, the modes to set values for these options are skipped automatically.

Set a 2-digit value for each option pair in the following order: SEG2 and SEG3 → SEG4 and SEG5 → SEG6 and SEG8 → SEG9 and SEG10 → SEG11 and SEG12 → SEG14 and SEG15 → SEG16 and SEG17 → SEG18 and SEG20 → SEG21 and SEG22 → SEG23 and SEG24

Option Code Table
SEG1SEG2SEG3SEG4SEG5SEG6
0XXXXX
SEG7SEG8SEG9SEG10SEG11SEG12
1XXXXX
SEG13SEG14SEG15SEG16SEG17SEG18
2XXXXX
SEG19SEG20SEG21SEG22SEG23SEG24
3XXXXX

On (SEG1 to SEG12)

Diagram description: Shows remote display "On 00 Auto".

Off (SEG13 to SEG24)

Diagram description: Shows remote display "Off 00 Auto".

Take the steps presented in the following table:

  1. Setting SEG2, SEG3 option: Press Low Fan button ⬇️ to enter SEG2 value. Press High Fan button ⬆️ to enter SEG3 value. Each time you press the button, 01–E–F will be selected in rotation.
  2. Setting Cool mode: Press Mode button to be changed to Cool mode in the ON status.
  3. Setting SEG4, SEG5 option: Press Low Fan button ⬇️ to enter SEG4 value. Press High Fan button ⬆️ to enter SEG5 value. Each time you press the button, 01–E–F will be selected in rotation.
Status
SEG2SEG3
On0080
AutoCool
SEG4SEG5
On8080
CoolCool

Step 14 Setting the indoor unit addresses and the installation options

Set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice when setting indoor unit address and installation option.

Please use the proper wireless remote controller which can set 24 digit option code.

Please refer to the wired remote controller installation manual for setting with the wired remote controller.

Common steps for setting the addresses and options

Diagram description: Shows remote control display for entering mode for setting option and option setting mode.

1 Enter the mode for setting the options:

  1. Remove the batteries from the remote control, and then insert them again.
  2. While holding down the ⬆️ (High Temp) and ⬇️ (Low Temp) buttons simultaneously, insert the batteries into the remote control.
  3. Make sure that you are entered to the mode for setting the options:

Diagram description: Shows remote display "On 00 Auto".

2 Set the option values.

❗ CAUTION: The total number of available options are 24: SEG1 to SEG24. Because SEG1, SEG7, SEG13, and SEG19 are the page options used by the previous remote control models, the modes to set values for these options are skipped automatically.

Set a 2-digit value for each option pair in the following order: SEG2 and SEG3 → SEG4 and SEG5 → SEG6 and SEG8 → SEG9 and SEG10 → SEG11 and SEG12 → SEG14 and SEG15 → SEG16 and SEG17 → SEG18 and SEG20 → SEG21 and SEG22 → SEG23 and SEG24

Option Code Table
SEG1SEG2SEG3SEG4SEG5SEG6
0XXXXX
SEG7SEG8SEG9SEG10SEG11SEG12
1XXXXX
SEG13SEG14SEG15SEG16SEG17SEG18
2XXXXX
SEG19SEG20SEG21SEG22SEG23SEG24
3XXXXX

On (SEG1 to SEG12)

Diagram description: Shows remote display "On 00 Auto".

Off (SEG13 to SEG24)

Diagram description: Shows remote display "Off 00 Auto".

Take the steps presented in the following table:

  1. Setting SEG2, SEG3 option: Press Low Fan button ⬇️ to enter SEG2 value. Press High Fan button ⬆️ to enter SEG3 value. Each time you press the button, 01–E–F will be selected in rotation.
  2. Setting Cool mode: Press Mode button to be changed to Cool mode in the ON status.
  3. Setting SEG4, SEG5 option: Press Low Fan button ⬇️ to enter SEG4 value. Press High Fan button ⬆️ to enter SEG5 value. Each time you press the button, 01–E–F will be selected in rotation.
Status
SEG2SEG3
On0080
AutoCool
SEG4SEG5
On8080
CoolCool

4 Setting Dry mode: Press Mode button to be changed to DRY mode in the ON status.

Status
SEG6SEG8
On0080
DryDry

5 Setting SEG6, SEG8 option: Press Low Fan button ⬇️ to enter SEG6 value. Press High Fan button ⬆️ to enter SEG8 value. Each time you press the button, 01–E–F will be selected in rotation.

6 Setting Fan mode: Press Mode button to be changed to FAN mode in the ON status.

SEG9SEG10
On8080
FanFan

7 Setting SEG9, SEG10 option: Press Low Fan button ⬇️ to enter SEG9 value. Press High Fan button ⬆️ to enter SEG10 value. Each time you press the button, 01–E–F will be selected in rotation.

8 Setting Heat mode: Press Mode button to be changed to HEAT mode in the ON status.

SEG11SEG12
On8080
HeatHeat

9 Setting SEG11, SEG12 option: Press Low Fan button ⬇️ to enter SEG11 value. Press High Fan button ⬆️ to enter SEG12 value. Each time you press the button, 01–E–F will be selected in rotation.

10 Setting Auto mode: Press Mode button to be changed to AUTO mode in the OFF status.

SEG14SEG15
Off8080
AutoAuto

11 Setting SEG14, SEG15 option: Press Low Fan button ⬇️ to enter SEG14 value. Press High Fan button ⬆️ to enter SEG15 value. Each time you press the button, 01–E–F will be selected in rotation.

Option setting
SEG16SEG17
Off0080
CoolCool

12 Setting Cool mode: Press Mode button to be changed to Cool mode in the OFF status.

13 Setting SEG16, SEG17 option: Press Low Fan button ⬇️ to enter SEG16 value. Press High Fan button ⬆️ to enter SEG17 value. Each time you press the button, 01–E–F will be selected in rotation.

Option setting
SEG18SEG20
Off0080
DryDry

14 Setting Dry mode: Press Mode button to be changed to Dry mode in the OFF status.

15 Setting SEG18, SEG20 option: Press Low Fan button ⬇️ to enter SEG18 value. Press High Fan button ⬆️ to enter SEG20 value. Each time you press the button, 01–E–F will be selected in rotation.

Option setting
SEG21SEG22
Off8080
FanFan

16 Setting Fan mode: Press Mode button to be changed to Fan mode in the OFF status.

17 Setting SEG21, SEG22 option: Press Low Fan button ⬇️ to enter SEG21 value. Press High Fan button ⬆️ to enter SEG22 value. Each time you press the button, 01–E–F will be selected in rotation.

Option setting
SEG23SEG24
Off0080
HeatHeat

18 Setting Heat mode: Press Mode button to be changed to HEAT mode in the OFF status.

19 Setting SEG23, SEG24 option: Press Low Fan button ⬇️ to enter SEG23 value. Press High Fan button ⬆️ to enter SEG24 value. Each time you press the button, 01–E–F will be selected in rotation.

Check whether the option values that you have set are correct by pressing the Mode button repeatedly.

[SEG2, SEG3]

Diagram description: Shows remote display "On 00 Auto".

[SEG4, SEG5]

Diagram description: Shows remote display "On 80 Cool".

[SEG6, SEG8]

Diagram description: Shows remote display "On 00 Dry".

[SEG9, SEG10]

Diagram description: Shows remote display "On 80 Fan".

[SEG11, SEG12]

Diagram description: Shows remote display "On 00 Heat".

[SEG14, SEG15]

Diagram description: Shows remote display "Off 80 Auto".

[SEG16, SEG17]

Diagram description: Shows remote display "Off 00 Cool".

[SEG18, SEG20]

Diagram description: Shows remote display "Off 80 Dry".

[SEG21, SEG22]

Diagram description: Shows remote display "Off 00 Fan".

[SEG23, SEG24]

Diagram description: Shows remote display "Off 80 Heat".

4 Save the option values into the indoor unit: Press the ◀️ button with the direction of remote control for set. For correcting option values, input the option values twice.

5 Check whether the air conditioner operates in accordance with the option values you have set:

  1. Reset the indoor unit by pressing the Reset button on the indoor or outdoor unit.
  2. Remove the batteries from the remote control, insert them again, and then press the ◀️ button on the remote control.

Emergency Temperature Output (ETO) function

❗ CAUTION: In order to deploy the ETO function, the MIM-B14, an external contact interface module, must be installed in each indoor unit.

Setting up the ETO

Diagram description: Shows the connection between Main indoor unit, Sub indoor unit, and External contact interface module (MIM-B14), with communication lines (F1 and F2) and error output ports.

ETO operation specifications

1 Main indoor unit
2 Sub indoor unit
Main indoor unit
Enable of ETOEnable of external contactError port output
XXN/A
X0Output due to an error
0XOutput by ETO entrance conditions (temperature / time / error occurrence)
00Output by ETO entrance conditions (temperature / time / error occurrence)
*Ready to control the main contact input
Sub indoor unit
Enable of entrance controlEnable of external contactOperation when outputting Main
XXN/A
X0On with the previous operation conditions
00On with the entrance control enabled

Setting the indoor unit addresses

Option No. for an indoor unit address: 0AXXXX-1XXXXX-2XXXXX-3XXXXX

Before installing an indoor unit, be sure to set an address for the indoor unit by taking the following steps:

  1. Make sure that the power is supplied to the indoor unit. If the indoor unit is not plugged in, it must include a power supply.

Diagram description: Shows an Indoor Unit with connection points.

2 Set an address for each indoor unit using the remote control, according to your air conditioning system plan, by referring to the following table and by following the steps in Common steps for setting the addresses and options on page 17.

OptionSEG1SEG2SEG3SEG4SEG5SEG6
FunctionPageModeSetting main addressIndoor unit number
Indication DetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetails
Indication and details0A0No main addressReserved0 to 1Tens digit0 to 9Units digit
OptionSEG7SEG8SEG9SEG10SEG11SEG12
FunctionPageSetting RMC addressGroup channel (x16)Group address
Indication DetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetails
Indication and detailsReservedReserved0No RMC address1RMC address setting modeRMC10 to 2RMC20 to F

❗ CAUTION: The main address must be set to a value in the range 0 to 15. If you set other values, communication error will occur.

Setting an indoor unit installation option (suitable for the condition of each installation location)

Option No.: 02XXXX-1XXXXX-2XXXXX-3XXXXX

1 Make sure that the power is supplied to the indoor unit. If the indoor unit is not plugged in, it must include a power supply.

2 The panel(display) should be connected to an indoor unit to receive option.

3 Set the installation option according to the installation condition of an air conditioner.

4 Set the indoor unit option by wireless remote controller.

OptionSEG1SEG2SEG3SEG4SEG5SEG6
ExplanationPAGEMODEUse of external temperature sensorUse of central control
Indication DetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetails
Indication and Details02RESERVED0Disuse1UseRESERVED
OptionSEG7SEG8SEG9SEG10SEG11SEG12
ExplanationPAGERESERVEDRESERVEDRESERVEDRESERVEDRESERVED
Indication and Details1
OptionSEG13SEG14SEG15SEG16SEG17SEG18
ExplanationPAGEUse of external controlSetting the output of external controlBuzzer controlNumber of hours using filter
Indication DetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetails
Indication and Details20Disuse1On/OffThermo0DisuseUse of buzzer1000 Hour
2OffSub. Existing Controlon1Non use of buzzer22000 Hour
3Window6
4DisuseMain, Existing Control
5On/OffSub, Reverse ControlOperation on
6Off
7Window
8Disuse
9On/OffMain, Reverse Control
AOff
BWindow
CDisuse
DOn/Off
EOff
FWindow

❗ CAUTION: SEG18 is applied in case of strong wind.

OptionSEG19SEG20SEG21SEG22SEG23SEG24
ExplanationPAGEIndividual control of a remote controllerHeating setting compensation
Indication DetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetails
Indication and Details0 or 1Indoor 10DefaultRESERVEDRESERVEDRESERVED
2Indoor 212°C
3Indoor 325°C
4Indoor 4

If you input a number other than 0~4 on the individual control of the indoor unit(SEG 20), the indoor is set as "Indoor 1".

Example) If you want to set as "Exterior temperature sensor: USE, External control: USE, Number of hours using filer: 2000hr",

SEG1SEG2SEG3SEG4SEG5SEG6
0210
SEG7SEG8SEG9SEG10SEG11SEG12
10
SEG13SEG14SEG15SEG16SEG17SEG18
2006
SEG19SEG20SEG21SEG22SEG23SEG24
300

assign option codes except SEG 1, 7,13,19 which are page options.

* Level control: The centralized controller can limit the functions and inputs of connected products with this function enabled. Example: Operation mode limit (Cooling only/Heating only/No limitation), Heating temperature upper limit, Cooling temperature lower limit) To enable 'Level control' when applying the DPM with the centralized controller, appoint the Main (Set 'Use of external control [SEG14] option to 4 or higher).

Example: When installing DPM (1 Outdoor unit with 4 indoor units)

Condition
SEG14 SettingResult
External controlLevel controlIndoor 1Indoor 2Indoor 3Indoor 4
DefaultNot set (0)Sub (All)
DisuseUse4Not set (0)Not set (0)Not set (0)Main (Indoor 1), Sub (Indoor 2,3,4)
Use (Indoor 3)DisuseNot set (0)Not set (0)1~3Not set (0)Sub (All)
Use (Indoor 4)UseNot set (0)Not set (0)Not set (0)5~7Main (Indoor 4), Sub (Indoor 1,2,3)

Changing a particular option

You can change each digit of set option.

OptionSEG1SEG2SEG3SEG4SEG5SEG6
ExplanationPAGEMODEThe option mode you want to changeThe tens' digit of an option SEG you will changeThe unit digit of an option SEG you will changeThe changed value
Indication DetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetailsIndicationDetails
Indication and Details0DOption mode0~FTens' digit of SEG0~9Unit digit of SEG0~9The changed value0~F

? NOTE: When changing a digit of an indoor unit address setting option, set the SEG3 as 'A'.

When changing a digit of indoor unit installation option, set the SEG3 as '2'.

Ex) When setting the 'buzzer control' into disuse status.

OptionSEG1SEG2SEG3SEG4SEG5SEG6
ExplanationPAGEMODEThe option mode you want to changeThe tens' digit of an option SEG you will changeThe unit digit of an option SEG you will changeThe changed value
Indication0D2171

Troubleshooting

LED Display on the indoor unit

AC052/071RNCDKG

Abnormal conditionsIndicatorsRemarks
BlueGreenOrangeRed
Power resetXXXXDisplayed on appropriate indoor unit which is operating
Error of temperature sensor in indoor unit (OPEN/SHORT)XXXXDisplayed on appropriate indoor unit which is operating
Error of the indoor unit pipe sensorXXXXDisplayed on appropriate indoor unit which is operating
Error of the outdoor unit pipe sensorXXXXDisplayed on outdoor unit
Communication error (Transmitter, wired remote control)XXXXError of indoor unit: Displayed on the indoor unit regardless of operation
Communication error between indoor unitsXXXXError of outdoor unit: Displayed on the indoor unit which is operating
Error of peripherals option set-upXXXXDisplayed on the indoor unit which is operating
EEPROM errorXXXX
EEPROM option errorXXXX
High pressure blockage error (Refrigerant completely Leakage error)XXXX
Error of outdoor Unit/Self-Diagnosis (Check error code in outdoor unit or solution display or thermal fuse on Indoor's POWER T/B(open))XXXX

: On, : Blinking, X: Off

AC100/120/140RNCDKG

Abnormal conditionsIndicatorsRemarks
BlueGreenOrangeRed
Power resetXXX0.5[S]=On, 0.5[S]=Off
Operation onXXX
Operation offXXXX
ReservationXXX
Filter signXXX
DefrostingXXX1[S]=On, 9[S]=Off
Smart install ErrorXXX
Communication error between indoor units and outdoor unitXXXX
EEPROM error /EEPROM option errorXXXX
Error of temperature sensor in indoor unit (open/short)XXXX
Error of outdoor Unit/Self-DiagnosisXXXX
Error of the indoor unit pipe sensorXXXX
Indoor fan errorXXXX
Thermal fuse open errorXXXX
Indoor unit float S/W 2nd detectionXXXX

: On, : Blinking, X: Off

Wired remote control

If an error occurs, ❓ is displayed on the wired remote control.

If you would like to see an error code, press the Test button.

DisplayExplanation
E108Error due to repeated communication address
E121Error on room temperature sensor of indoor unit (Short or Open)
E122Error on EVA IN sensor of indoor unit (Short or Open)
E123Error on EVA OUT sensor of indoor unit (Short or Open)
E153Error on float switch (2nd detection)
E154Indoor fan error
E198Error on thermal fuse of indoor unit (Open)
E201Communication error between indoor unit and outdoor unit (Pre tracking failure or when actual number of indoor units are different from the indoor unit quantity setting on the outdoor unit) Error due to communication traking failure after initial power is supplied.
E202Communication error between indoor unit and outdoor unit (When there is no response from indoor units after tracking is completed)
E203Communication error between outdoor unit inv main micom (For PF #4~#6 controller, error will be determined from the time when compressor is turned on)
E221Error on outdoor temperature sensor (Short or Open)
E231Error on outdoor COND OUT sensor (Short or Open)
E251Error on discharge temperature sensor of compressor 1 (Short or Open)
E320Error on OLP sensor (Short or Open)
E403Compressor down due to freeze protection control
E404System stop due to overload protection control
E416System stop due to discharge temperature
E422Blockage detected on high pressure pipe
E425Reverse phase or open phase
E440Heating operation restricted at outdoor temperature over Theat_high value (default: 30 °C)
E441Cooling operation restricted at outdoor temperature below Tcool_low value (default: 0 °C)
E458Fan speed error
DisplayExplanation
E461Error due to operation failure of inverter compressor
E462System stop due to full current control
E463Over current trip / PFC over current error
E464IPM Over Current(O.C)
E465Comp. Over load error
E466DC-Link voltage under/over error
E467Error due to abnormal rotation of the compressor or unconnected wire of compressor
E468Error on current sensor (Short or Open)
E469Error on DC-Link voltage sensor (Short or Open)
E470Outdoor unit EEPROM Read/Write error (Option)
E471Outdoor unit EEPROM Read/Write error (H/W)
E472AC Line Zero Cross Signal out
E473Comp Lock error
E474Error on IPM Heat Sink sensor of inverter 1 (Short or Open)
E475Error on inverter fan 2
E484PFC Overload (Over current) Error
E485Error on input current sensor of inverter 1 (Short or Open)
E500IPM over heat error on inverter 1
E508Smart install is not installed
E554Gas leak detected
E556Error due to mismatching capacity of indoor and outdoor unit
E557DPM remote controller option error
E590Inverter EEPROM CheckSum error
E660Inverter Boot Code error

This appliance is filled with R-32.

SAMSUNG

PDF preview unavailable. Download the PDF instead.

v1

Related Documents

PreviewSamsung Air Conditioner AC***DXADKG Installation Manual
Comprehensive installation manual for Samsung air conditioner model AC***DXADKG, covering safety, installation procedures, extra operations, maintenance, and troubleshooting. Includes details on R-32 refrigerant handling and electrical connections.
PreviewSamsung Air Conditioner User Manual AC***BNNPKG
User manual for the Samsung Air Conditioner model AC***BNNPKG, providing detailed information on safety, operation, cleaning, maintenance, troubleshooting, and technical specifications.
PreviewSamsung Air Conditioner User Manual - Safety, Operation, and Maintenance
Comprehensive user manual for Samsung Air Conditioners (models AC***RN*DKG, AC***BN*DKG), covering safety precautions, operating features, cleaning instructions, troubleshooting, technical specifications, and refrigerant information.
PreviewSamsung Air Conditioner User Manual: Operation, Maintenance, and Troubleshooting
Comprehensive user manual for Samsung air conditioners, covering operation features, cleaning and maintenance, troubleshooting common issues, and connecting to the SmartThings app. Includes safety information and product specifications.
PreviewSamsung Air Conditioner Installation Manual: AC***RNADKG / AC***RNTDKG
Detailed installation manual for Samsung air conditioners, models AC***RNADKG and AC***RNTDKG. Covers safety precautions, preparation, indoor unit installation, setting options, and troubleshooting.
PreviewSamsung Air Conditioner Installation Manual - Procedures and Safety Guidelines
Comprehensive installation manual for Samsung air conditioners, detailing safety information, step-by-step installation procedures for various models (e.g., AC***RN*DKG, AC...RN4DKG series), and troubleshooting tips. Includes diagrams and specifications.
PreviewSamsung Air Conditioner Installation Terms and Conditions
Detailed terms and conditions for the installation of Samsung air conditioning units, covering requirements, inclusions, exclusions, and costs. Ensures safe and proper installation procedures.
PreviewSamsung Air Conditioner User Manual - Model AC***BN6PKG
Comprehensive user manual for the Samsung Air Conditioner, model AC***BN6PKG. Includes safety information, installation, operation, maintenance, troubleshooting, and technical specifications.