User Manual for Sunco models including: EM_2HFL, EM_2HFL 2 Head LED Emergency Light, 2 Head LED Emergency Light, LED Emergency Light, Emergency Light, Light

View

Installation Guides, Manuals, and Specs | Sunco – Sunco Lighting

CEC Title 20 and Title 24 Efficiency Regulations – Sunco Lighting


File Info : application/pdf, 8 Pages, 292.22KB

EM 2HFL ManualMasterCopy 780bea6f-5f9f-4fcf-b4dd-4f149049eb25 ?v=1738184936
Lighting made better.
User Manual
2 Head LED Emergency Light
SKU: EM_2HFL
support@sunco.com (844) 334-9938

What's in the Box?
LED Emergency Light

A
x2 Mounting Screws

Le(tlittheerraellbye) light!

B x3 Wire Nuts
1

C
x2 Wall Anchors

Before Your Start
Safety Information

To reduce the risk of fire, electric shock, or physical injury:

· Turn off circuit breaker before installing this fixture.

· Not compatible with dimmers. · Not compatible with timing devices.

· Suitable for use in damp

· All electrical connections must be

environments at temperatures

in accordance with local and National

ranging from 32°F to 104°F. Not for use where directly exposed to
water.

Electric Code (N.E.C.) standards. · Please review installation manual
carefully before proceeding. Consult

· Not compatible with photo controls. a qualified electrician if you are

· Not compatible with occupancy

unfamiliar with proper electrical

sensors. · Not compatible with 3rd party
sensors.

wiring connections.
WARNING: Cancer & Reproductive Harmwww.P65Warnings.ca.gov

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: 1.) This device may not cause harmful interference.

2.) This device must accept any interference that may cause undesired operation. Please review all instructions carefully prior to installation.

2

Installation Guide
STEP 1

STEP 2

a. Turn off circuit breaker.
b. Using a flathead screwdriver, pry open triangle slots near the test button to remove backplate.
c. Set housing aside.

a. Thread fixture wires through backplate and connect to building wires.
120V: -Black to Black (Live) -White to White (Neutral)
277V: -Red to Black (Live) -White to White (Neutral)
b. Connect battery to PCB board by plugging connector into socket.
3

Installation Guide (Cont.)
STEP 3

STEP 4

(A)

a. Drill into desired mounting pattern indicators from the backplate.
b. Install mounting screws (A) into drilled mounting hole indicators to install fixture into wall.
c. For wall-mounting with conduit, attach backplate to wall. Thread fixture wires through conduit, then connect conduit.

a. Attach housing into place starting with the backplate's bottom side, then the top side (test button side).
b. Attach housing. Ensure that backplate is properly connected and sealed.
c. Turn on power. Press the test button to test light.
Battery may need 24 hours to charge before light fixture can be used for emergency purposes.
4

Product Details
Specifications

Voltage Wattage Charging Time
Finish Type LED Heads
Power Source Dimmable

120V/277V 2.4W 24h Matte 2 Battery
No

CCT Lumens Material Fire Resistant Frequency
Weight Warranty

6000K 230LM
ABS + PMMA
Yes 60Hz 1.35lbs 1 Year

5

Wiring Diagram
NOTE: Unused input lead must be properly
insulated with wire nut or other approved method.
6

Lighting made better.

support@sunco.com (844) 334-9938

REV1.0



References