In manual mode, only one temperature level is maintained for the entire day. Icon in the frame indicates which mode is currently active. A different temperature ...

Manual mode – temperature setpoints

Manual mode – temperature setpoints. 3 temperature levels are available. In manual mode, only one temperature level is maintained for the entire day.

HTRS230(30) QG V1 ENG - Salus

Introduction. The HTRS230V(30) from SALUS Controls is a digital, wired and surface- mounted (or on a flush-box) non programmable room thermostat,.

PDF preview unavailable. Download the PDF instead.

HTRS230(30) QG V1 ENG
VI 2020 [ENG]
AC 230V

Wired digital thermostat - non-programmable Model: HTRS230(30)

Package content

User manual

Ver. 1 Date of issue: 24 VI 2020 Power supply: 230V

IMPORTER: QL CONTROLS Sp. z o.o. Sp. k. ul. Rolna 4, 43-262 Kobielice

PRODUCER: Salus Limited 6/F, Building 20E, Phase 3, Hong Kong Science Park, 20 Science Park East Avenue, Shatin, New Territories, Hong Kong

Front housing of the thermostat
Digital non-programmable thermostat Model: HTRS230(30)

Back housing of the thermostat

User manual
User manual

Mounting screws

Proper thermostat location

www.salus-controls.eu
SALUS Controls is a member of the Computime Group.
In accordance with the product development policy, SALUS Controls plc reserves the right to change specifications, design, and materials used in production, presented in this manual, without prior notice.
Introduction
The HTRS230V(30) from SALUS Controls is a digital, wired and surfacemounted (or on a flush-box) non programmable room thermostat, dedicated for surface heating / cooling control, characterized by high thermal inertia. It is connected to the wiring centre. The thermostat does not have the function of creating schedules - it lowers the set temperature via wiring centre after receiving the NSB signal from the weekly thermostat. Thanks to the built-in algorithms, it offers much better temperature control accuracy than traditional mechanical thermostats. The thermostat is characterized by silent operation. The controller is characterised by silent operation.
Product compliance
The product complies with the following EU directives: 2014/30/EU, 2014/35/EU, 2011/65/EU. Full information is available at www.saluslegal.com
Note!
This document is a quick guide to the installation and operation of the product and indicates its main features and functions. Detailed informations are in the full manual, which is available at www.saluscontrols.eu and which must be used for proper installation and operation of the product. Safety informations: Use in accordance with national and EU regulations. Use the device as intended and keep it dry. Product for indoor use only. Please read the entire manual before starting the installation and using the product. Installation: Installation must be carried out by a qualified person, with appropriate electrical authorisations, in accordance with national and EU standards and regulations. The manufacturer shall not be liable for failure to comply with the manual. NOTE: There may be additional protection requirements for the entire installation. The installer shall be responsible for compliance with such requirements.

The ideal position to thermostat mounting is about 1,5m under floor level far from heating or cooling sources. In addition, the thermostat should not be installed behind curtains or other obstacles or in places with high humidity, as this will prevent accurate measurements of room temperature. The thermostat must not be exposed to sunlight. Do not place the thermostat on an outer wall.

Connection description
Note:The thermostat is compatibile with the following Salus wiring centre models:KL06 230V, KL08NSB 230V, KL04NSB 230V or directly to the actuator.

NSB input

CO ThHeTrRmS 2o3s0tat

ATc3tu0aNtoCr

N /

L

L

N

ThHeTrmRSo2s3t0at CO L
N

SL
WKirLin08gNceSBntre L
N

Symbols explanation
Terminal Description
L, N Power supply (230V AC)
NSB Night temperature reduction (230V output)
SL 230 V AC output signal 230V AC
CO Switching jumper between heating and cooling (input 230V AC) Note: The following designations are used interchangeably for products: = SL = NSB

Montage

1

2

Make sure that the thermostat is not connected to the 230V AC. Then open the front housing using a screwdriver as shown above.
3

Connect the thermostat properly. Please refer to the "Connection description" section. Mount the thermostat using the designed screw holes.
4

Slide the thermostat on the back cover. The thermostat is configured for operation. Use buttons to set the temperature setpoint.
Button functions
Increase /or decrease setpoint temperature setpoint or value
Mode selection
Short press to confirm selection Press and hold ­ enter / exit the menu

LCD icon description

4

5

6

7

3

2

8

1

9

10

1. Heating mode 2. Cooling mode 3. Active work mode 4. Comfort temperature mode 5. Economic temperature mode

6. AUTO mode 7. Frost protection mode 8. Temperature unit 9. Current / set temperature 10. Manual mode / temp. override

Manual mode ­ temperature setpoints
3 temperature levels are available. In manual mode, only one temperature level is maintained for the entire day. Icon in the frame indicates which mode is currently active. A different temperature can be set for each level.
- Comfort temperature mode
- Economic temperature mode
- Frost protection mode Usually used during the period of longer absence, or during the holidays (only available in HEATING mode).

Press any button to highlight the screen, then follow the steps below:

1

2

Select the temperature mode using or buttons.

Temperature setpoint

Press any button to highlight the screen, then follow the steps below:

1

2

Current temperature.
3

Temperature setpoint in the selected work mode.
4

Set the temperature using
or buttons.

Confirm selection by button.

AUTO mode ­ NSB function
The NSB (Night Setback) function enables automatic reduction of the temperature setpoint on the HTRS230(30) SLAVE thermostat, via the HTRP230(50) programmable MASTER thermostat connected to the wiring centre (or other external clock). The temperature change takes place between the comfort temperature mode and economic temperature mode.
To activate AUTO mode, select the icon. Together with the icon, the thermostat shows the active temperature mode on the display: or .

Press any button to highlight the screen, then follow the steps below:

1

2

Select AUTO mode using or buttons.
Note:For the proper NSB function work, an appropriate cable connection is required.The connection description is on the previous page.

Calibration of displayed temperature ­ "offset" function
The thermostat allows to correct the displayed temperature by ±3.0°C. Follow the steps below:

Press any button to highlight the screen, then follow the steps below:

1

2

Press and hold button to enter the menu.

Confirm "offset" setting by button.

3

4

Set the temperature calibration value using
or buttons.

Temperature calibration can be made in the range from -3.0°C to +3.0°C. Confirm the selected
value by button.

Note:Calibration of the temperature can also be set in the installer parameters (parameter d02).

Heating / Cooling mode

Manual change:

Modes are indicated by

symbols.

Press and hold button to enter the menu, then use button to select

the Heating / Cooling mode change setting. Confirm changes using

button. Now use or buttons to set the heating or cooling mode.

Confirm by button.

Automatic change (via CO terminal): The heating/cooling mode can be changed automatically via the CO terminal in the thermostat. If 230 V AC power supply is connected to the CO terminal ­ then thermostat automatically switches to cooling mode. If you want to use this function, then you have to change the value of the d18 parameter to "1".

Cooling blocking: When D19 thermostat parameter is set to "1", then cooling is blocked for a single room. When the cooling function is blocked, no message is displayed.

Installer mode

Press any button to highlight the screen, then follow the steps below:

1

2

3 sec.

3 sec.

Press and hold and buttons simultaneously for
3 seconds.

Select the 47 code using or buttons.

3

4

Confirm by button.

You are now in the installer menu.
Select the parameter you wish to change by or buttons and enter using button. Use and to set the value of the parameter, and then
confirm it with .

Installer parameters

Function

Parameter Description Values

Default Values

According 0 to the PWM
algorithm

d01 Heating Control

Hysteresis:

1 0.5 °C

0

(± 0.25 °C)

Hysteresis: 2 1.0 °C
(± 0.5 °C)

Displayed d02 temperature
correction

If the thermostat indicates from an incorrect -3.0°C temperature, 0.0°C to +3.0°C then it can be corrected ±3.0°C

d05 Cooling Control

Hysteresis: 1 0.5 °C
(± 0.25 °C) 2
Hysteresis: 2 1.0 °C
(± 0.5 °C)

0 Disabled

d07 Valve Protection

1

1 Enabled

d08

Frost protection setpoint

The frost

protection

5.0 ­ 17.0°C

temperature is maintained for example during

5.0°C

active holiday

mode.

d12

Heating setpoint limits

5.0 ­ 35.0°C

Maximum temperature which can be set for heating

35.0°C

Minimum

d13 Cooling setpoint limits

5.0 ­ 40.0°C

temperature which can be set for cooling

5.0°C

d18

Heat/Cool Mode Selection

0

Manual by buttons use

0

1

Automatic by the CO terminal

d19

Cooling Blocking function

0

Cooling allowed

1

Cooling disabled

0

Numbers 1

Actuators loading

to 5 are the

d20

selection for different temperature

0 ­ 5

numbers of actuators con-

0

compensation

nected to the

thermostat.

Factory reset
If you made a mistake, want to change the thermostat parameters or return to factory settings, follow the steps below.
Note:This action will permanently delete all current settings.

Press any button to highlight the screen, then follow the steps below:

1

2

3 sec.

3 sec.

Press and hold and buttons simultaneously for
3 seconds.

Select the 49 code using or buttons.

3

4

Confirm by button.

Press button to reset the thermostat.

5

