CP4B

Battery Powered Programmable Thermostat

Installation and Operation Guide

Installation Instructions

Factory Default Settings

Contacts:Volt Free
Temperature indicator:°C
Switching differential:0.4°C
In built frost protection:5°C - Not adjustable
Clock:24 hours
Keypad lock:Off
Operating mode:5/2 day

Frost Protection

Frost protection is built into this thermostat. It is set at 5°C and is not adjustable. It will only be activated when the thermostat is in the OFF mode and the room temperature falls below 5°C.

Specifications

Power supply:2 x AA Alkaline Batteries
Battery replacement:Once a year
Temp. control range:5 ... 35°C
Ambient temperature:0 ... 45°C
Contact rating:8A 230Vac
Switch output:SPDT Volt Free
Dimensions:130 x 99 x 25mm
Temperature sensor:NTC 100K Ohm @ 25°C
Temperature indication:°C
Switching differential:0.4°C
Frost protection:Only operational in Off mode
Pollution degree:Pollution degree 2

Wiring Diagram

Internal Wiring Diagram for CP4B

Terminals: O, T (OpenTherm), 1 (ON), 2 (OFF), 3 (COM).

If mains voltage output is required, 230V must be connected to terminal COM.

Important: Do not connect Mains Voltage to OpenTherm® terminals.

How your programmable thermostat works

When the thermostat is in the AUTO mode, it will operate according to the times and temperatures that have been programmed. The user can select from 6 different programs per day, each with a time and a temperature.

There is no OFF time, only a higher and a lower temperature setpoint. If the user does not want the thermostat to operate, set the temperature for this time to be a low temperature. The thermostat will turn ON if the room temperature is lower than the setpoint for the current period.

Example: If P1 is set to be 21°C at 6am, and if P2 is set to be 10°C at 8am, the thermostat will look for the temperature to be 21°C between 6am and 8am.

Mounting & Installation

Caution! Installation and connection should only be carried out by a qualified person. Only qualified electricians or authorised service staff are permitted to open the thermostat. If the thermostat is used in a way not specified by the manufacturer, its safety may be impaired. Prior to setting the thermostat, it is necessary to complete all required settings described in the section.

This thermostat must be directly mounted on a wall.

Mounting & Installation (Continued)

  1. The mounting height should be 1.5 metres above the floor level.
  2. The thermostat should be wall mounted in the room where the heating is to be controlled. The place of installation should be chosen so that the thermostat can measure the room temperature as accurately as possible. Exposure to direct sunlight or other heating / cooling sources should be avoided when the thermostat is mounted.
  3. Lower the flap at the front of the thermostat. There is a battery compartment located below the buttons. Apply downward pressure to remove the cover.
  4. Remove the backplate from the thermostat by inserting a screwdriver into the slots in the battery compartment and pull apart.
  5. Fix the backplate to the wall and ensure electrical connections are terminated correctly.
  6. Attach the front housing to the backplate and insert the 2 x AA batteries and the thermostat will turn on. Close the battery compartment.

Installation Steps Diagram Description:

  • Diagram 1 shows thermostat dimensions, CE mark, IP20 rating, temperature range (°C/°F), and humidity range.
  • Diagram 2 illustrates installation prohibitions, such as avoiding placement near radiators or in direct sunlight.
  • Diagram 3 shows how to open the battery compartment flap.
  • Diagram 4 demonstrates removing the backplate using a screwdriver.
  • Diagram 5 illustrates fixing the backplate to the wall and making electrical connections.
  • Diagram 6 shows attaching the front housing and inserting batteries.

Operating Instructions

LCD Symbol Description

The LCD display shows various information:

  • Current program: Indicates the active program.
  • Day of the week: Displays the current day (MON, TUE, WED, etc.).
  • Temperature: Shows the current room temperature or setpoint.
  • Day / Month: Displays the current date.
  • Current Time: Shows the current time, used for boost function.
  • Battery low symbol: [!] Appears when batteries are low.
  • Heating on symbol: [flame] Indicates heating is active.
  • Keypad lock symbol: [lock] Appears when the keypad is locked.
  • Operating mode: Shows the current mode (e.g., AUTO, MAN, OFF).

Button Description

The thermostat has the following buttons:

  • Set point increase: [+]
  • Set point decrease: [-]
  • Reset button: [RESET]
  • OK confirm button: [OK]
  • Mode buttons: [AUTO] (Automatic), [MAN] (Manual), [OFF] (Off)
  • Programming buttons: [PROG] (Program mode), [TIME] (Set Date/Time), [HOL] (Holiday mode), [COPY] (Copy function), [BOOST] (Boost mode)

Resetting the thermostat

Press the [RESET] button on the side of the thermostat. 'rst no' will appear on the screen. Press the [+/-] buttons. 'rst yes' will appear on the screen. Press the [OK] button to reset the thermostat. The thermostat will now be reset to the default settings.

Keypad lock and unlock

To lock the keypad, press and hold the [+] and [-] buttons for 10 seconds. A [lock] symbol will appear on the screen. The keypad is now locked.

To unlock the keypad, press and hold the [+] and [-] buttons for 10 seconds. The [lock] symbol will disappear from the screen. The keypad is now unlocked.

Setting the date, time, programming mode and Daylight Savings Time

  1. Press the [TIME] button once; the year will begin flashing.
  2. Press the [+] or [-] buttons to adjust the year. Press [OK].
  3. Press the [+] or [-] buttons to adjust the month. Press [OK].
  4. Press the [+] or [-] buttons to adjust the day. Press [OK].
  5. Press the [+] or [-] buttons to adjust the hour. Press [OK].
  6. Press the [+] or [-] buttons to adjust the minute. Press [OK].
  7. Press the [+] or [-] buttons to adjust from 5/2d to 7d or 24h mode.
  8. Press the [+] or [-] buttons to turn DST (Day Light Saving time) On or Off.
  9. Press the [AUTO] button or wait 5 seconds, and the thermostat will return to normal operation.

Factory Program Setting

5/2 Day Mode

P1P2P3P4P5P6
Mon-Fri06:30
21°C
08:00
10°C
12:00
10°C
14:00
10°C
17:30
21°C
22:00
10°C
Sat-Sun08:00
21°C
10:00
10°C
12:00
10°C
14:00
10°C
17:30
21°C
23:00
10°C

7 Day Mode

P1P2P3P4P5P6
Mon-Fri06:30
21°C
08:00
10°C
12:00
10°C
14:00
10°C
17:30
21°C
22:00
10°C
Sat-Sun08:00
21°C
10:00
10°C
12:00
10°C
14:00
10°C
17:30
21°C
23:00
10°C

24 Hour Mode

P1P2P3P4P5P6
Everyday06:30
21°C
08:00
10°C
12:00
10°C
14:00
10°C
17:30
21°C
22:00
10°C

Programming Modes

The CP4B Room Thermostat has the following programming modes available:

  • 5/2 Day mode: Programming Monday to Friday as one block and Saturday and Sunday as a second block. Each block can have 6 different times and temperatures.
  • 7 Day mode: Programming all 7 days individually with six different times and temperatures per day.
  • 24 Hour mode: Programming all 7 days as one block with the same six times and temperatures.

Adjust the program setting in 5/2 Day mode

Press the [PROG] button once. Programming for Monday to Friday is now selected.

  • Press the [+] or [-] buttons to adjust the P1 time. Press [OK].
  • Press the [+] or [-] buttons to adjust the P1 temperature. Press [OK].
  • Repeat this process to adjust P2 to P6 times and temperatures. Press [OK].

Programming for Saturday to Sunday is now selected.

  • Press the [+] or [-] buttons to adjust the P1 time. Press [OK].
  • Press the [+] or [-] buttons to adjust the P1 temperature. Press [OK].
  • Repeat this process to adjust P2 to P6 times and temperatures.

Press the [AUTO] button to return to the automatic mode.

While in PROG Mode pressing the [PROG] button will jump from P1-P2 etc without changing the temperature. While in PROG Mode pressing the [TIME] button will jump to the next day or block of days.

Copy Function

Copy function may only be used if the thermostat is in the 7d mode. Set the times and temperatures for the day that you wish to copy from in the programming mode. When still on the day press the [COPY] button. The day of the week that you have selected will be shown with 'COPY' below it. The next day will begin to flash on the top of the screen. Press the [+] button to copy the times and temperatures to that day. Press the [-] button to skip that day. You can copy to multiple days using the [+] button. Press the [OK] button when copying has been completed.

Temporary Override

When in AUTO mode, press the [+] or [-] buttons to adjust the temperature setpoint. 'OvEr' will appear on the screen. Press [OK] or after 5 seconds the thermostat will operate to this temperature setpoint, until the next switching time.

To cancel temporary override, press the [OFF] button and then press the [AUTO] button to return to the automatic mode.

Permanent Override

Press the [MAN] button to enter the manual mode (Permanent Override), 'MAN' will appear on the screen. Press the [+] or [-] buttons to adjust the temperature setpoint. Press [OK] or after 5 seconds the thermostat will operate in this mode.

To cancel permanent override, press the [OFF] button to turn the thermostat off or press the [AUTO] button to return to the automatic mode.

Boost Function

Press the [BOOST] button, one two or three times. The time that the thermostat will boost to will flash on the screen. Press the [OK] button. The temperature will now flash. Adjust the boost temperature setpoint by pressing the [+] or [-] buttons. Press the [OK] button or wait for 5 seconds for the boost to activate. 'BOOST TO' will now be displayed on the screen with the time that the thermostat is activated to, displayed above the text. Press the [BOOST] button again to deactivate the boost.

If you do not press any button after pressing the boost button, the boost will activate to a default boost setting of 21°C.

Holiday Function

This will switch your heating system off between the start and end times you select.

Press the [HOL] button, 'HOLIDAY FROM' will appear on screen.

  • Press the [+] or [-] buttons to adjust the year. Press [OK].
  • Press the [+] or [-] buttons to adjust the month. Press [OK].
  • Press the [+] or [-] buttons to adjust the day. Press [OK].
  • Press the [+] or [-] buttons to adjust the hour. Press [OK].

'HOLIDAY TO' will appear on screen.

  • Press the [+] or [-] buttons to adjust the year. Press [OK].
  • Press the [+] or [-] buttons to adjust the month. Press [OK].
  • Press the [+] or [-] buttons to adjust the day. Press [OK].
  • Press the [+] or [-] buttons to adjust the hour. Press [OK].

The thermostat will now return to the mode it was in before the Holiday settings were entered. To cancel Holiday mode, press the [HOL] button.

Backlight mode selection

There are two settings for selection. The factory default setting is AUTO.

  • OFF: The backlight is permanently OFF.
  • AUTO: On pressing any button the backlight stays on for 5 seconds.

To adjust the backlight setting, lower the cover on the front of the unit. Press the [OK] button for 5 seconds. Press either the [+] or [-] buttons to select the OFF or AUTO mode. Press the [OK] button.

Battery low warning

When the batteries are almost empty, the [!] symbol will appear on the screen. The batteries must now be replaced or the unit will shut down.

Replacing the batteries

Lower the flap on the front of the thermostat. There is a battery compartment located below the buttons. Apply downward pressure to remove the cover. Insert the 2 x AA batteries and the thermostat will turn on. Close the battery compartment.

Installer menu

To access the installer menu, you must hold [PROG] and [OK] for 5 seconds. When in the installer menu, use the [+] , [-] , [AUTO] , [MAN] , [OFF] or [OK] buttons to navigate and select. Use [AUTO], [MAN], [OFF] or to go back a step.

  • P0 1: Mode (Normal / Optimum Start / TPI)
  • P0 2: Hi Lo (Limiting the Thermostat)
  • P0 3: Hysteresis (Differential)
  • P0 4: Calibration
  • P0 5: Frost Protection
  • P0 6: Exit

Installer menu - OpenTherm® Instructions

(Only for use with OT boilers)

  • P0 6: Setting DHW Temperature
  • P0 7: OpenTherm® Information
  • P0 8: DHOP
  • P0 9: Set OpenTherm® Parameters
  • Exit

PO 1 Operating Mode (Normal / Optimum Start / TPI)

Nor (Normal Mode)

When the thermostat is in Normal mode, the thermostat will try to reach the target temperature after the program changes. Example: Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:30am and the room temperature will start to increase then.

OS (Optimum Start Mode)

[BOILER PLUS] When the thermostat is in Optimum Start mode, the thermostat will try to reach the target temperature by the start time of the next switching time. This is done by setting the Ti (time interval) on the thermostat in this menu to 10, 15, 20, 25 or 30. This will allow the thermostat 10, 15, 20, 25 or 30 minutes to increase the room temperature by 1°C. Ti can be set when OS is selected in the installer menu. [settings] 20°C

To achieve the target temperature when the program starts, the thermostat will read:

  1. The Room Temperature (RT)
  2. The Setpoint Temperature (ST)
  3. The Target Temperature Difference (TTD) is the difference between the setpoint temperature and the room temperature.

The time (in minutes) that it will take to overcome (TTD) is called Optimum Start Time (OST) and its maximum value is 3 hours = 180 mins. This is subtracted from the start time. As the temperature increases the thermostat will recalculate the OST if the temperature is increasing too quickly.

Optimum Start Control Graphs

These graphs illustrate the relationship between Target Temperature Difference (TTD) and Optimum Start Time (OST) for different Ti values.

Example when Ti = 20: Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 05:30am to reach 21°C for 06:30am @ Ti=20.

Example when Ti = 10: Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:00am to reach 21°C for 06:30am @ Ti=10.

TPI (Time Proportional & Integral Mode)

When the thermostat is in TPI mode and the temperature is rising in the zone and falls into the Proportional Bandwidth section, TPI will start to affect the thermostats operation. The thermostat will turn on and off as it gains heat so that it doesn't overshoot the setpoint by too much. It will also turn on if the temperature is falling so it doesn't undershoot the setpoint which will leave the user with a more comfortable level of heat.

There are 2 settings that will affect the thermostats operation:

  1. CYC - No. of Heating Cycles per Hour: [settings] 6 Cycles. This value will decide how often the thermostat will cycle the heating on and off when trying to achieve the setpoint temperature. You can select 2/3/6 or 12.
  2. Pb - Proportional Bandwidth: [settings] 2°C. This value refers to the temperature below the setpoint at which the thermostat will start to operate in TPI Control. You can set this temperature from 1.5°C to 3.0°C in 0.1°C increments.

TPI Control Example: Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:30am and the room temperature will start to increase then but will switch itself off before it reaches temperature and allow the room temperature to increase naturally – this cycle may begin again if the thermostat isn't reaching temperature.

PO 2 Setting high & low limits

High 35°C and Low 5°C. This menu allows the installer to change the minimum and maximum temperature range that the thermostat can be set at.

PO 3 Hysteresis HOn and HOff

This menu allows the installer to change the switching differential of the thermostat when the temperature is rising and falling. HOn is the fall in temperature – Default – 0.4°C. This will allow a fall of 0.4°C from the setpoint before the thermostat turns on again. HOff is the rise in temperature – Default – 0.0°C. This will allow the temperature to rise 0°C above its setpoint.

PO 4 Calibrate the thermostat

This menu allows the installer to re-calibrate the thermostat. The current temperature will be displayed on the screen and can be adjusted by pressing the [+] or [-] buttons.

PO 5 Frost Protection

[settings] 5°C. This menu allows the installer to activate or de-activate frost protection. When frost protection is activated the thermostat will switch on the boiler when the temperature drops below 5°C.

PO 6 Exit

This menu allows the installer to return to the main interface. It is also possible to exit the installer menu by pressing [AUTO], [MAN] or [OFF] whilst in the installer menu.

PO 6 Setting DHW Temperature

This menu allows the installer to change the DHW temperature of the boiler. The temperature can be set in 0.5°C increments by pressing the [+] or [-] buttons. Press the [OK] button to select the desired temperature. This menu is only available when the thermostat is connected to OpenTherm® and DHOP is ON (P08 OT installer menu).

PO 7 OpenTherm® Information

This menu allows the installer to view information received from the OpenTherm® boiler. It may take a few seconds to load information relating to each parameter. The information that can be shown from the boiler is outlined in the table below.

Displayed on screenDescriptionRemark
tSEtTarget water temp
tFLOOutlet water temp
trEtReturn water temp
tdHDHW temperatureThis is only visible if DHOP is On (P08 OT Installer menu)
tFLUFlue gas temperatureDependent on boiler
tEStOutdoor temperatureDependent on boiler
nOdUModulation percentage
FLOrWater flowThis is only visible if DHOP is On (P08 OT Installer menu)
PrESWater pressureDependent on boiler

PO 8 DHOP

This menu allows the installer to activate or de-activate DHW target temperature control from the thermostat. This menu is only available when the thermostat is connected to OpenTherm®.

PO 9 Set OpenTherm® Parameters

This menu allows the installer to configure the OpenTherm® parameters. To access the menu please enter the password "08" with the [+] or [-] buttons. Press [OK] to confirm. The parameters that can be set are outlined in the table below.

ParameterDescriptionRangeDefault
HHCH t-1Maximum set point heating45 - 85°C85°C
LLCH t-2Minimum set point heating10 - HHCH°C45°C
CLI t-3This allows users to select different climatic curves for weather compensation. This only applies to boilers with an outside sensor connected.0.2 - 3.01.2
InFL t-4Influence of room sensor on modulation of the boiler. Recommended value is 10.0 - 2010
HHbO t-5Maximum allowable CH water setpoint. (°C)ID49 Max ≥ID57 ≥ID49 Min85°C
ExitPress OK button to turn back to main interface.

Climatic Curve

The Climatic Curve graph shows relationships between outdoor temperature and heating output for different settings.

Exit: This menu allows the installer to return to the main interface. It is also possible to exit the installer menu by pressing [AUTO], [MAN] or [OFF] whilst in the installer menu.

System architecture

Example A: 1 no. Thermostat controlling OT Boiler

Diagram shows a CP4B Thermostat connected to an OpenTherm® Boiler.

Contact Information

EPH Controls IE

technical@ephcontrols.com

www.ephcontrols.com/contact-us

+353 21 471 8440

Cork, T12 W665

EPH Controls UK

technical@ephcontrols.co.uk

www.ephcontrols.com/contact-us

+44 1933 322 072

Harrow, HA1 1BD

© 2024 EPH Controls Ltd.

Models: CP B, CP4B, CP4B Battery Powered Programmable Thermostat, CP4B, Battery Powered Programmable Thermostat, Powered Programmable Thermostat, Programmable Thermostat, Thermostat

File Info : application/pdf, 40 Pages, 1.14MB

CP4B Datasheet

References

Related Documents

Preview EPH CP4V2 Programmable RF Thermostat & Receiver: Installation and Operation Guide
Comprehensive guide for installing and operating the EPH Controls CP4V2 Programmable RF Thermostat and RF1B Wireless Receiver, covering setup, features, and system integration for efficient home heating control.
Preview CP4M Room Thermostat - Hardwired Open Therm® Operating Instructions
Detailed operating instructions for the EPH Controls CP4M Hardwired Open Therm® Room Thermostat, covering setup, programming, installer settings, and advanced features for efficient heating control.
Preview EPH Controls CP4D Programmable RF Thermostat & Receiver Installation and Operation Guide
Comprehensive guide for installing and operating the EPH Controls CP4D programmable RF thermostat and receiver system, detailing setup, features, and system integration.
Preview EPH Controls CP4V2 Programmable RF Thermostat & Receiver Installation and Operation Guide
Comprehensive guide for installing and operating the EPH Controls CP4V2 Programmable RF Thermostat and its associated RF1B Receiver. Covers setup, programming, features, and troubleshooting for efficient home heating control.
Preview EPH Controls CP4 Programmable RF Thermostat & Receiver - Simple & User Friendly
Discover the EPH Controls CP4, a user-friendly, programmable RF thermostat and receiver designed for simple and efficient heating and hot water control. Features include a large LCD, ergonomic buttons, multi-zone capability with OpenTherm, and a contemporary design. Enjoy cost-effective energy savings and easy installation with pre-paired components.
Preview EPH Controls CRTP2 Room Thermostat Operating Instructions
Comprehensive operating instructions for the EPH Controls CRTP2 Battery Operated Room Thermostat, covering installation, settings, programming, and advanced features like Optimum Start Mode.
Preview EPH Controls R47 V2 4 Zone Programmer: Installation and Operating Guide
Comprehensive guide for the EPH Controls R47 V2 4 Zone Programmer, covering installation, operation, programming, and advanced features. Learn how to set up and manage heating zones efficiently.
Preview COMBIPACK3 Wireless Non Programmable Thermostat Easy User Guide
An easy user guide for the EPH Controls COMBIPACK3 Wireless Non Programmable Thermostat (Model RFRA). This guide explains the thermostat's buttons, symbols, how to set the temperature, and its on/off function.