Friedrich Vert-I-Pak Single Package Heat Pump

Product Profile

Product Overview

The Friedrich Vert-I-Pak is a Single Package Heat Pump designed for efficient room air conditioning. It is recognized as a leading solution by experts in the field.

Model Identification Guide

The Vert-I-Pak series follows a specific model numbering convention:

A typical model number is VHA09K34RTQ, indicating specific features like capacity, voltage, and options.

Options: RT = Standard Remote Operation

Electric Heater Size (A Series): 25 = 2.5 kW, 34 = 3.4 kW, 50 = 5.0 kW, 75 = 7.5 kW* (Available on 18 & 24 K/R models), 10 = 10.0 kW** (Available on 24 K/R models).

General Specifications

MODELVHA09KVHA09RVHA12KVHA12RVHA18KVHA18RVHA24KVHA24R
COOLING DATA
TOTAL COOLING CAP. (Btu/hr) @95°F9,0008,80011,00011,00017,60017,40021,80021,600
SENSIBLE COOLING CAP. (Btu/hr)6,6506,6508,1008,10012,50012,50015,40015,000
SEER211.911.911.911.911.911.911.911.9
EER210.610.610.610.610.610.610.610.6
VOLTAGE208/230265208/230265208/230265208/230265
HEATING DATA
HEAT PUMP CAP. (Btu/hr) @ 47°F8,2008,20010,40010,40016,00016,00018,50018,500
HEAT PUMP CAP. (Btu/hr) @ 17°F4,5004,5005,6005,6009,0009,00012,00012,000
COP3.13.13.13.13.13.13.13.1
HSPF26.36.36.36.36.36.36.36.3
HEATER SIZE (kW)2.5/3.4/5.02.5/3.4/5.02.5/3.4/5.02.5/3.4/5.02.5/3.4/5.0/7.52.5/3.4/5.0/7.52.5/3.4/5.0/7.5/10.02.5/3.4/5.0/7.5/10.0
PHYSICAL
DIMENSIONS (W X D X H)23"x23"x32"23"x23"x32"23"x23"x32"23"x23"x32"23"x23"x47"23"x23"x47"23"x23"x52"23"x23"x52"
REFRIGERANTR410a
VENTILATION AIRCFM UPTO 60

NOTE: Due to continuing research in new energy-saving technology, specifications are subject to change without notice.

Electrical Data

Vert-I-Pak FamilyModel NumberTotal Refrigeration AmpsTotal Electric Heat AmpsElectric Heat WattsElectric Heat AmpsCompressor RLA/LRABlower Motor FLA/HPCondenser Motor FLA/HPMOP/ MOCP
MCAMOCP
VHA09K (230/208)25RTQ6.811.5/10.42450/200010.7/9.64.2/210.8 - 1/81.8 - 1/414.415
34RTQ6.815.4/14.03350/274014.6/13.219.320
50RTQ6.822.5/20.55000/409021.7/19.728.230
VHA09R25RTQ6.81024509.24.7/230.8 - 1/81.8 - 1/412.515
34RTQ6.813.4335012.616.820
50RTQ6.819.7500018.924.725
VHA12K (230/208)25RTQ7.311.5/10.42450/200010.7/9.64.7/230.8 - 1/51.5 - 1/414.415
34RTQ7.315.4/14.03350/274014.6/13.219.320
50RTQ7.322.5/20.55000/409021.7/19.728.230
VHA12R25RTQ7.31024509.24.7/230.8 - 1/51.5 - 1/412.515
34RTQ7.313.4335012.616.820
50RTQ7.319.7500018.924.725
VHA18K (230/208)25RTQ9.111.5/10.42450/200010.7/9.66.8/300.8 - 1/51.5 - 1/414.415
34RTQ9.115.4/14.03350/274014.6/13.219.320
50RTQ9.122.5/20.55000/409021.7/19.728.230
75RTQ9.133.4/30.37500/613532.6/29.541.845
VHA18R25RTQ9.11024509.26.8/300.8 - 1/51.5 - 1/412.515
34RTQ9.113.4335012.616.820
50RTQ9.119.7500018.925.330
75RTQ9.129.1750028.336.440
VHA24K (230/208)25RTQ10.711.5/10.42450/200010.7/9.68.2/440.8 - 1/51.7 - 1/41620
34RTQ10.715.4/14.03350/274014.6/13.219.525
50RTQ10.722.5/20.55000/409021.7/19.729.630
75RTQ10.733.4/30.37500/613532.6/29.541.845
10RTQ10.744.3/40.110000/818043.5/39.355.460
VHA24R25RTQ10.71024509.28.2/440.8 - 1/51.7 - 1/415.320
34RTQ10.713.4335012.618.320
50RTQ10.719.7500018.927.130
75RTQ10.729.1750028.336.440
10RTQ10.738.51000037.748.250

Airflow Data

INDOOR CFM & EXTERNAL STATIC PRESSURE

MODELVHA09VHA12VHA18VHA24
LowHighLowHighLowHighLowHigh
ESP (")SCFM
0.0"360420360460620705675765
0.05"340400340450580675635735
0.10"325385325430550640600700
0.15"310370310415510610560670
0.20"295355295400480585525635
0.25"270*325270*380450565490615
0.30"260300*260350*400*550440*600
0.35"--------365500400540
0.40"--------320450*350490*

*Maximum Allowable Static. Units rated at 0.3" ESP.

BLOWER CONTROL

All Vert-I-Paks, by default, are configured for low-speed blower operation. The speed setting can be changed to high speed by updating the speed tap settings on the fan control relay. Any non-Friedrich thermostat or low-voltage device powered by the Vert-I-Pak requires review and approval.

NOTE: Fan speed cannot be changed at the thermostat. Regardless of wiring GH and/or GL, the unit will continue to operate at the speed setting at the fan control relay.

The blower control system involves wiring connections to an indoor motor controller, speed relay, and power source (L1, L2, GND). Low speed is the factory default, selected from the indoor motor controller. High speed is a field wiring option.

CONDENSER CFM & EXTERNAL STATIC PRESSURE

Vert-I-Pak units are designed for installation through an exterior wall using a plenum (VPAWP1-8, VPAWP1-14) and an external louver. If default plenum and louver combinations are not used, selections and design must be evaluated to ensure total pressure drop does not exceed maximum allowable limits.

ModelCFMDesign ESP ("WC)Maximum ESP ("WC)
VHA096500.030.12
VHA126500.030.12
VHA189500.030.12
VHA249800.030.12

Installation Overview

TYPICAL INSTALLATION FOR VERT-I-PAK

The typical installation involves several components:

Specific plenum dimensions are provided: VPAWP1-8 telescopes from 5 1/2" to 8" deep, and VPAWP1-14 telescopes from 8" to 14" deep. Both are 24 1/8" W x 30 3/8" H.

A VPDP2 drain pan is required for 18K and 24K models only.

INSTALL DIMENSIONS

The overall wall cutout dimensions are 24 5/8" W x 30 7/8" H.

NOTE: The distance between the rough opening and the finished floor/platform must be 1 inch.

CLOSET ORIENTATIONS AND DIMENSIONS

The unit can be installed in various closet orientations:

Front Installation-Top View

This view shows the unit from the front, indicating clearances to the outside grill and wall. Key dimensions include a minimum 3" clearance on sides and a 26 1/8" minimum required inside closet dimension. The access door cutout is 27", with a minimum required inside closet dimension of 29 1/8".

Left Installation-Top View

This view shows the unit from the left. It indicates a minimum 4 1/2" clearance on the left side, a minimum 3" clearance on the right, and a minimum 8" clearance required behind the unit. The access door cutout is 27". Minimum required inside closet dimensions are 31 1/8" (width) and 30 5/8" (depth).

Right Installation-Top View

This view shows the unit from the right. It indicates a minimum 3" clearance on the left side, a minimum 4 1/2" clearance on the right, and a minimum 8" clearance required behind the unit. The access door cutout is 27". Minimum required inside closet dimensions are 31 1/8" (width) and 30 5/8" (depth).

TYPICAL CLOSET FOR VERT-I-PAK

A typical closet installation includes:

A VPDP2 drain pan is required beneath the unit for all 18K and 24K models and must be installed prior to chassis installation.

The Access Panel with Return Air Grille (VPRG4/VPRG4R) has dimensions of 29" W x 58" H. The filter size is 25" x 20" (field supplied).

The same indoor (closet) wall cutout is used for all models, measuring 27" W x 55-3/4" H.

The access panel door has a hinge on the left side.

ACCESSORIES DIMENSIONS

Louver

Architectural Louver (VPAL2/-42/VPSC2/-42): An extruded aluminum grille that attaches to the outdoor section of the wall plenum. Dimensions are 25 9/16" W x 31 1/16" H.

Wall Plenum

The two-part sleeve (A and B) telescopes to fit different wall thicknesses. Dimensions are 24 1/8" W x 30 3/8" H. The required cutout dimensions are 24 5/8" W x 30 7/8" H.

Application and Installation

Installation Guidelines

Application and Accessories (All models)

Application and Accessories (18K & 24K Models)

Required and Optional Accessories

Required Accessories

Architectural Louver

VPAL2 and VPAL2-42: Extruded aluminum grille (30° or 42° blade angle) attaches to the outdoor section of the wall plenum. Dimensions: 25 9/16" W x 31 1/16" H.

VPSC2 and VPSC2-42: VPAL2 and VPAL2-42 in custom colors.

Wall Plenum

VPAWP1-8, VPAWP1-14: Two-part sleeve that telescopes in and out, fitting inside the exterior wall penetration. VPAWP1-8 telescopes from 5 1/2" to 8". VPAWP1-14 telescopes from 8" to 14". Dimensions: 24 1/8" W x 30 3/8" H. Cutout Dimensions: 24 5/8" W x 30 7/8" H.

Drain Pan

VPDP2: Required for all 18K and 24K models. Can be installed prior to chassis for easy installation/removal.

Optional Accessories

Return Air Grille/Access Panel

VPRG4/VPRG4R: Hinged panel allows access to the unit and return air filter. A field-supplied filter (25" x 20") should be mounted on the inside grille. Panel can be mounted with return air openings high or low for optimum sound attenuation. Dimensions: 29" W x 58" H. Cutout Dimensions: 27" W x 55 3/4" H.

First Company Sleeve Adapter

VPASA1: Single piece, welded adapter for retrofit into existing First Company SPXR-series single package vertical unit wall sleeve and louver. Easy connection to small chassis Vert-I-Pak only.

Single Stage Thermostats

Energy Management Thermostats

HVAC Engineering Specifications

Single Packaged Heat Pumps

General Construction

Units are factory assembled, piped, wired, and fully charged with R-410A. They are certified per AHRI Standard 210/240, ETL listed, and factory run-tested. Friedrich or equivalent manufactures the units.

Basic unit dimensions: not exceeding 23 1/8" W x 23 1/8" D. Overall height varies by model (up to 32 1/4" for 12,000 Btu, 47 1/4" for 18,000 Btu, 51 1/4" for 24,000 Btu).

The unit is designed to insert into a factory-supplied wall plenum (2 3/8" depth) to minimize room intrusion. Wall plenums accommodate wall thicknesses from 4 1/2" to 14" and are adjustable.

Ambient air is drawn through the upper portion of an architectural louver (25 9/16" W x 31 1/16" H) and heated air is exhausted through the lower portion. The unit secures to the louver via a two-part, weather-resistant wall plenum. Installations can be left, right, or straight-in without field modifications.

Construction: 18-gauge galvanized zinc-coated steel with 1/2" foil-backed insulation for sound and thermal efficiency.

Wall plenum: 20-gauge galvanized zinc-coated steel, pretreated and powder-coated. Black color for minimal exterior visibility. Shipped with a protective weatherboard.

Architectural louver: Extruded anodized aluminum with horizontal louvers.

The unit includes vibration isolators and a non-rigid plenum-to-chassis connection. It features a plastic fan, fan shroud, drain pan, and aluminum outdoor coil endplates for corrosion protection.

Units ship with return air filter brackets and a 14" x 20" or 18" x 20" filter.

Refrigeration System

Hermetically sealed system with a rotary compressor mounted on vibration isolators. Coils are copper tubes with aluminum plate fins. Capillaries are used as expansion devices. A fan slinger ring enhances efficiency and condensate disposal. Primary condensate removal uses 3/4" FTP fittings; a secondary overflow expels water outside if the primary drain line clogs.

Air Handling Section

Separate motors for indoor and outdoor air sections. Airflow is directed vertically through a rectangular opening (same size for 9K/12K and 18K/24K units).

Chassis includes a damper for up to 60 CFM of fresh air, filtered by a fine mesh screen. Damper controlled by a front-mounted slide lever.

Controls

Factory-equipped terminal strip for standard 24-volt single-stage heat/cool thermostat. Includes a transformer wired for Friedrich or approved devices. Low voltage inputs: C (common), R (24V power), Y (cooling), G (fan), W (heat), B (reversing valve). Unit is hard-wired with a quick-disconnect for control box service.

Corrosion Protection

Features corrosion-resistant materials and finish. Outdoor coil has Diamonblue advanced corrosion protection with hydrophilic-coated fins for extended coil life, especially in seacoast applications.

Accessory Access Panel

Optional factory-supplied panel provides access to the unit and return air. It includes a filter holder for a field-supplied 25" x 20" x 1" filter and a hinge bracket for mounting the door (return air openings high or low for optimal sound attenuation).

Limited Warranty

This certificate provides specific rights that may vary by state and province.

For servicing, contact the nearest authorized Friedrich Air Conditioning Co. service center, distributor, dealer, or contractor. Have the model and serial number readily available when requesting service.

Friedrich Vert-I-Pak Heat Pumps Limited Warranty

Warranties apply only to units installed within the continental United States, Alaska, Hawaii, Puerto Rico, Mexico, and Canada, and only if installed and operated according to printed instructions and local codes.

Defective parts must be made available to Friedrich in exchange for replacement parts. Proof of installation date is required; otherwise, the shipment date plus sixty days is used. Replacement parts can be new or re-manufactured and are warranted only for the unused portion of the unit's warranty.

Exclusions (User is responsible for costs):

  1. Service calls for: unit operation instruction, replacing house fuses, correcting house wiring, cleaning/replacing air filters, removing the unit from its installed location when inaccessible for service, or correcting improper installations.
  2. Parts or labor provided by anyone other than an authorized service center.
  3. Damage caused by: accident, abuse, negligence, misuse, riot, fire, flood, acts of God; corrosive atmosphere (chlorine, fluorine, damaging chemicals); unauthorized alteration or repair affecting stability/performance; failure to provide proper maintenance/service; incorrect power source; faulty installation or application; operation during construction.

Friedrich is not liable for incidental, consequential, or special damages or expenses. No representation or warranty of fitness for a particular use is made beyond what is stated. No one is authorized to change this certificate or create other obligations.

Implied warranties last for one year after the original purchase date. Some states/provinces may not allow limitations on implied warranty duration.

Performance of Friedrich's Warranty obligation may be met by: 1. Repair of the unit, 2. Refund of prorated value, or 3. Replacement unit of equal value, at Friedrich's sole discretion.

The English version of this warranty governs.

Vert-I-Pak is a registered Trademark owned by Friedrich Air Conditioning, LLC, A Rheem Company.

Models: VHA Q Series, VHA Q Series Single Package Heat Pump, Single Package Heat Pump, Package Heat Pump, Heat Pump, Pump

File Info : application/pdf, 13 Pages, 1.60MB

PDF preview unavailable. Download the PDF instead.

VHA Q Series PP Adobe PDF Library 17.0 Adobe InDesign 19.0 (Windows)

Related Documents

PreviewFriedrich Vert-I-Pak Single Package Heat Pump: Specifications, Installation & Performance
Comprehensive product profile for Friedrich Vert-I-Pak Single Package Heat Pumps. Find detailed specifications, electrical data, airflow, performance charts, installation guides, and accessory information for efficient HVAC solutions.
PreviewFriedrich VERT-I-PAK Product Profile: Vertical Air Conditioners and Heat Pumps
Explore the Friedrich VERT-I-PAK series of single package vertical air conditioners and heat pumps. This profile details features, specifications, and accessories for both A and B series models, designed for efficient heating and cooling in various applications.
PreviewFriedrich VPRG4/VPRG4R Return Air Grille/Access Panel Installation Instructions
Detailed installation guide for Friedrich VPRG4 and VPRG4R Return Air Grille and Access Panel, covering left and right hinged installations for Vert-I-Pak and VRP07 systems. Includes parts lists, preparation steps, and step-by-step instructions with diagram descriptions.
PreviewFriedrich VRP Variable Refrigerant Packaged Heat Pump Product Profile
Discover the Friedrich VRP, an innovative and intelligent Variable Refrigerant Packaged Heat Pump system. It provides superior cooling, efficient heating, advanced humidity control, and optional fresh air integration, ensuring optimal comfort and energy savings with its Precision Inverter technology.
PreviewFriedrich Endeavor™ F-Series Plus iM Heat Pumps: Specifications and Performance Data
Detailed specifications, features, performance data, and model information for the Friedrich Endeavor™ F-Series Plus iM Heat Pumps (FRP15AZ series). Includes efficiency ratings, capacities, dimensions, and warranty details.
PreviewFriedrich ZoneAire Premier Series PTAC Specifications and Accessories
Detailed specifications, performance data, electrical data, airflow data, and physical data for Friedrich ZoneAire Premier Series PTAC units, including electric heat and heat pump models. Lists available accessories and receptacle/fuse types.
PreviewFriedrich FreshAire PTAC Installation and Operation Manual
This Installation and Operation Manual provides detailed guidance for Friedrich FreshAire PTAC and Heat Pump units. It covers product features, installation steps, operational procedures, maintenance schedules, troubleshooting tips, and accessory information for the PV-SERIES.
PreviewFriedrich Breeze Select 2025 R-454B Heat Pump Quick Start Guide
A quick start guide for Friedrich Breeze Select 2025 R-454B Universal Heat Pump models, covering installation, operation, and troubleshooting.