MANUAL ON LOAD If No Sensor is Used, Tie the SPODM White Wire to Red Wire Note: up to 2 with neutral-less Note: up to 9 with neutral PNK * 0-10V Dimming Common from fixture may be pink or as otherwise indicated per section 410.69 of the 2020 NEC LOAD 3 PNK LOAD 2 PNK LOAD 1 PNK LOAD 2 PNK LOAD 1 * 0-10V Dimming Common from fixture may be pink

AUTO. ON. LOAD. MANUAL. ON. LOAD. If No Sensor is Used, Tie the SPODM White Wire to Red Wire. Note: up to 2 with neutral-less. Note: up to 9 with neutral.

PDF preview unavailable. Download the PDF instead.

2019 06:44:18&DOC Type=Other Information
Quick Recommendation Guide

Typical Applications

Private Offices
Up to 15'x15'

Without Obstructions With Obstructions Up to 20'x20' 0-10V Dimming
Conference Rooms
Up to 15'x15' Up to 20'x20'

WSXA** / WSXA D** WSXA PDT** / WSXA PDT D** CM PDT 9* WSXA PDT D** or SPODMRA D**
WSXA PDT** / WSXA PDT D**
CM PDT 9*

Up to 30'x30'
Classrooms
Up to 30'x30' Greater than 30'x30'
Open Office Areas

WV PDT 16*
WV PDT 16* Mult. WV PDT 16* or CM PDT*

8'-10' Mounting Height

Multiple CM PDT 9*

Restrooms
Private

WSXA ** / WSXA D**

Private with Fan Up to 4 Stalls 4 to 7 Stalls

WSXA 2P: FAN**
WSXA PDT** / WSXA PDT D**
CM PDT 9*

More than 7 Stalls

Multiple CM PDT 9*

Corridors
9' Mounting Height

CM 10*

12' Mounting Height
Gymnasiums
25' Mounting Height
Warehouses
360°, 15' - 45' Mounting Height

CM 10* LSXR 6 LSXR 6

Aisle Control

LSXR 50

(Typical Energy Savings: 30% - 50%)
Sensor must have visibility to desktop activity Small rooms without direct line of sight (also required if occupant has back to sensor) Place within visual sight of main entry door LED dimming control with or without motion sensor
(Typical Energy Savings: 30% - 50%)
Sensor will detect both motion and sound
Place within visual sight of main entry door Place sensor in corner along entrance wall
(Typical Energy Savings: 40% - 60%)
Place sensor in corner along entrance wall Place sensors in opposite corners
(Typical Energy Savings: 20% -40%)
Place sensors on 25' - 30' centers and cover all entrances
(Typical Energy Savings: 50% - 80%)
For rooms without obstructions No obstructions, relay 1 controls lights, relay 2 is for fan
For rooms with obstructions Place within visual sight of the main entry door Contact your Acuity Sales Representative for assistance
(Typical Energy Savings: 20% - 60%)
Place sensors 50' on center Place sensors 60' on center
(Typical Energy Savings: 20% - 50%)
Place sensors on 40' centers and cover all entrances
(Typical Energy Savings: 20% - 50%)
1 sensor per fixture Coverage spans multiple fixtures

* Requires power pack(s).  Results typical; actual savings may differ. **WSD series may be substituted in place of the WSX; see datasheet for product details.
Signifies switches that are JOT enabled for single room lighting controls.

Wall Switch Sensor WSXA
Wall Switch with Dimming WSXA D
Switch Interface SPODMRA D
Ceiling Mount Sensor CM
Wide View Sensor WV
Fixture Mount Sensor LSXR

www.acuitybrands.com/sensorswitch

Wiring Diagrams

LINE VOLTAGE SENSOR
(i.e., CMR 9)

LOW VOLTAGE
Single Sensor (i.e., CM 9)

R - RELAY OPTION

PP20

BLK - 120 V ORN - 277 V

D, ADC - DIMMING OPTIONS PNK

D, P, ADC - PHOTOCELL / DIMMING OPTIONS

PP20

BLK - 120 V ORN - 277 V

Multiple Sensors (i.e., wv 16 & CM 9)

WIRING TO GROUND (NO NEUTRAL)
Wall Switch Sensor Single Relay
Dual Relay

WIRING TO NEUTRAL
Wall Switch Sensor Single Relay

Dual Relay

Wire Color Key for Wiring to Ground or Wiring to Neutral
120/277 VAC Wiring

¡ Black* ¡ Black*

Line 1 Input Load 1 Output

Black Wires can be reversed

¡ Blue* ¡ Blue*

Line 2 Input Load 2 Output

Blue Wires can be reversed

Notes: 1. Unit will draw power from either line connection.
2. When switching 277 VAC or 347 VAC on both relays, the line inputs must be of the same phase.

BI-LEVEL (AUTO-ON/MANUAL ON) SOLUTION WITH CEILING SENSOR: 2-GANG
Class 1 Connections
PP20
AUTO ON LOAD

SP20

MANUAL ON LOAD

If No Sensor is Used, Tie the SPODM White Wire to Red Wire

LINE VOLTAGE - SINGLE RELAY (I.E., LSXR XX)

Notes

1. Black wires can be reversed

2. Wire is red for HVOLT version (required for 347 VAC)

3. Disconnect and cap

black output wire going

to driver/ballast if

PNK

switching fixture is not

required.

FIXTURE BALLAST
or LED DRIVER

SINGLE RELAY, MULTI-WAY CONFIGURATION, 120-277 VAC

LOAD 3 PNK

LOAD 2 PNK

Note: up to 9 with neutral

LOAD 1 PNK
* 0-10V Dimming Common from fixture may be pink or as otherwise indicated per section 410.69 of the 2020 NEC

SINGLE RELAY, MULTI-WAY CONFIGURATION, 120-277 VAC

LOAD 2 PNK

LOAD 1 PNK
* 0-10V Dimming Common from fixture may be pink or as otherwise indicated per section 410.69 of the 2020 NEC

Note: up to 2 with neutral-less

LINE VOLTAGE - DUAL RELAY (I.E., LSXR XX 2P)

Notes 1. Black wires can
be reversed.
2. Blue wires can be reversed.
3. Wire is red 347 VAC version.
4. Red wires can be reversed.

Load 1 FIXTURE BALLAST
or LED DRIVER
Load 2 FIXTURE BALLAST
or LED DRIVER