SIEMENS Installation Instructions

Model PSX-12C

12 Amp Power Supply Extender (S24235-B120-A2)

Introduction

The SIEMENS Model PSX-12C is a high current power supply extender. The power supply extender works in conjunction with the PSC-12C power supply to provide an additional 12A of regulated 24VDC for internal or external system use.

Up to three PSX-12C modules may be connected to one PSC-12C power supply and one set of batteries. The PSX-12C has a microprocessor-controlled transfer circuit that allows it to switch the system power to stand-by batteries during loss or reduction of the AC power.

The PSX-12C incorporates a 18A circuit breaker on the battery input.

Figure 1 shows the SIEMENS PSX-12C 12 Amp Power Supply Extender.

The PSX-12C communicates directly to the PMI-S to report fault conditions and allows the PMI-S to query the status of the power supply extender.

The PSX-12C mounts at the back of the enclosure of the system and occupies one location on the Mounting Plate.

Features

Operation

The PSX-12C occupies one network address in the CAN network and has three functional components: the Controller, the Power Supply Extender and the Interface Board.

The Controller monitors the status of the Power Supply Extender (loss of network communication, 24VDC terminal overload and the status of the battery). This information is relayed to the User Interface, where applicable, and is communicated to the PMI-S for system reporting. The Controller also allows the PMI-S to query the state of the power supply extender and its current load and can send a diagnostics command to the PSX-12C.

The Power Supply Extender has an Off-line switch mode power converter and power factor correction circuit to improve conductive RF emission at low frequency. It is designed to take voltage inputs of 120VAC-240VAC at 50Hz/60Hz and has one resettable circuit breaker that can also be used as a battery power switch.

The Interface Board provides diagnostics LEDs, system connections and the terminal connections on the PSX-12C.

Terminal Blocks, Controls and Indicators

The PSX-12C has one reset switch, six LEDs, one address switch, one circuit breaker, two terminal blocks, two terminal connections and two 60 pin flat ribbon connections as shown in Figure 2. The ribbon cable connectors are used to connect the PSX-12C with a PSC-12C, additional PSX-12-Cs or a Card Cage (CC-2/CC-5).

A reset switch is located on the top of the front panel. Pushing the reset switch reinitializes the PSX-12C operation.

The LEDs located at the top left of the module and are defined as follows:

Figure 2 illustrates the terminal blocks, controls, and indicators of the PSX-12C.

The terminal blocks of the PSX-12C are defined as follows (refer to Figure 2):

TB3: 24VDC Power Limited Output Terminal

This terminal output is limited to 4A. When it is exceeded, it will shut down, light its associated diagnostics LED and send a fault condition to the PMI-S.

This output is normally connected to the modules and cards located on the door of the enclosure or to the remote CAN network modules. This output is power limited to NFPA 70 per 760. All wiring must be in accordance with Article 760 of NEC or local building codes. (See Figure 2.)

TB4: 24VDC Non-Power Limited Output Terminal

This terminal is non-power limited and can supply up to 12A. When the current draw is exceeded, it shuts down, lights its associated LED and sends a fault condition to the PMI-S.

This output is normally connected to the input terminals of the CC-5. All wiring must be in accordance with Article 760 of NEC or local building codes. (See Figure 2.)

The total cumulative sum of the 24VDC output (power limited + non-power limited) must not exceed 12A. Over current draw will initiate a PSX-12C shut down.

[WARNING] The main AC power line must be turned OFF prior to installation.

Pre-Installation

P9: Connects the back-up battery to the PSX-12C.

[CAUTION] Always apply AC power first followed by the battery.

P12: AC input connector (60-pin). Connects the PSX-12C to the system. It is a straight-through connection between the two connectors. It contains the communication signals and system signal bus that is necessary for the proper operation of the system.

These connectors are power limited. If the PSX-12C is located in a different row in the enclosure, an optional extended ribbon cable, SIEMENS Model FCL (C24200-K28-B6), must be used.

Installation Kit Components

The PSX-12C installation kit has the following components:

ItemPart Number
1 AC power - cableC24200-K10-B7
1 DC wire red / blueC24200-K10-B6
1 Ribbon cable 60 Pins, l = 165mmA5Q00004611
4 Flat head screwsA5Q00003958
1 Contact washerH70093-A50-S667

The following part is optional:

The following components must be set prior installing the module in the enclosure:

[CAUTION] Verify that the dedicated circuit breaker for the PSX-12-C is turned OFF at the mains.

Installation

[WARNING] Disconnect BATTERY and AC prior to working on equipment.

The PSX-12C mounts on the Mounting Plate (CAB-MP). The Mounting Plate may be located either "IN" or "OUT" of the enclosure to perform this installation procedure. If the Mounting Plate is located "IN” the enclosure you will have to gain access to it by opening the enclosure Inner and Outer doors. If the Mounting Plate is located outside of the enclosure, place it in front of you so that the word "TOP" is at the top and away from you.

The PSX-12C can occupy any position on the mounting plate, but it should be installed in the row and position that is located directly above the PTB to which it is connected. (Refer to Figures 3 and 5). When the PSX-12C is mounted correctly on the Mounting Plate it will be flush on the top, bottom, and right with the Mounting Plate and the mounting screw holes of the PSX-12C will align with the threaded posts.

Figure 3 shows the location of the PSX-12C on the Mounting Plate (MP-M), indicating positions for top and bottom threaded posts.

Installation Steps:

  1. Install four M5 screws in the threaded posts at the mounting position. Screw each of the M5 screws into the threaded posts 5-6 turns.
  2. Place the PSX-12C over the four screws on the Mounting Plate and slide it down or towards you to rest on the four screws.

Figure 4 illustrates the mounting of the PSX-12C onto the Mounting Plate. It shows the PSX-12C sliding down until flush on the top, right, and bottom.

When the PSX-12C is in the correct position it will be flush with the top, bottom and right side of the Mounting Plate.

  1. Tighten the four screws.

Wiring

The PSX-12C has removable terminal blocks and connectors at the top and bottom of the module. The terminal block at the top of the PSX-12C is power limited. The terminals and connectors at the bottom of the PSX-12C are non-power limited. (Refer to Figure 5.)

Use a separate or dedicated circuit breaker and run the earth ground from a suitable source to the PSX-12C. Check local requirements. Conduit is not an acceptable Earth Ground Conductor. Wire in accordance with local codes.

Figure 5 shows the PSX-12C wiring within CAB enclosures, indicating power-limited and non-power-limited wiring between components like CC-5, PSC-12C, and the PSX-12C, with connections to AC mains and battery.

Figure 6 details the wiring in the CAB-2 enclosure, showing connections between PSC-12C, PSX-12C, and other components, including AC input (230VAC 50...60Hz) and battery connections. It illustrates specific wire colors (gnye, bl, bk, br) and terminal designations (P9, P12, TB2, TB3, TB4).

Figure 7 details the wiring in the CAB-19 enclosure, similar to Figure 6 but with a different configuration of PSX-12C units and connections, including AC input (230VAC 50...60Hz) and battery connections.

Power Supply Load Calculations

To ensure that the PSX-12C power supply is not overloaded, use the form and follow the procedure listed below.

POWER SUPPLY LOAD CALCULATION FORM

Card / ModuleQuantityScrew Terminal 24V Current Per Card/ModuleTotal 24 VDC Current
AIC00
DAC-NET00
FCM-6S14mA + 1mA per active LED
FMT-S150mA
LCM-8S14mA + 1mA per active LED
LPB00
LVM-SS/HS25mA
LVM-D100mA
NIC-C00
OCM-1614mA + 10mA per active LED
PMI00
RNI75mA
RPM150mA
SCM-8S14mA + 1mA per active LED
SIM-1610mA per active relay + 1.2mA per supv. input
TZC-8B355mA
ZAC-40150mA + 53mA per Watt
ZAM-180280mA + 53mA per Watt
ZIC-4ACUsage dependant(Must not exceed 12 Amps)

Procedure:

  1. Enter the quantity of each card/module in the enclosure.
  2. Calculate both the 24VDC and 6.2VDC loads for each row.
  3. Total the Active 24VDC and Active 6.2VDC columns.
  4. Ensure that both totals are within the power supply output ratings.

Battery Power

Make sure that the battery circuit breaker is in the OFF position. Use either 14 or 12 AWG for (2.5mm² or 4mm²) battery connection. Battery backup is required. (15 amp hours is the minimum size and 100 amp hours is the maximum size of the battery for the PSX-12C).

Battery Connections

  1. Attach the red battery wire to the quick disconnect on the positive terminal and the blue battery wire to the quick disconnect on the negative terminal with the M5 screws and lock nuts supplied with the PSC-12C.
  2. Close the covers of the battery terminals.

Figure 8 illustrates the wiring of batteries, showing connections to terminals with M5 screws and lock nuts, and a 0.5m long wire assembly.

Wiring Batteries

Figure 9 shows diagrams for wiring batteries to multiple PSX-12C units, illustrating connections from batteries to the PSX-12C units via terminals like P9 and TB4.

Electrical Ratings

ParameterRating
Input Voltage120VAC / 220VAC / 240VAC +10%, -15%
Input Current3.3A Max. @ 120VAC
2.5A Max. @ 220VAC
2.0A Max. @ 240VAC
Screw Terminal 24V CurrentPower Limited: 4A Max.
Non-Power Limited: 12A Max.
24V Standby Current150mA

For CE applications in Cerberus E100 systems refer to Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).

Models: PSX-12C 12 Amp Power Supply Extender, PSX-12C, 12 Amp Power Supply Extender, Power Supply Extender, Supply Extender, Extender

File Info : application/pdf, 12 Pages, 973.84KB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676769600

References

Acrobat Distiller 6.0 (Windows)

Related Documents

PreviewSiemens VNT-PS Installation Instructions: Power Supply for VNT
Detailed installation instructions and wiring diagrams for the Siemens VNT-PS power supply, essential for the VNT (Virtual Network Tunnel) in FireFinder-XLS fire alarm systems. Learn proper mounting and connection procedures.
PreviewSiemens SITOP PSU300S 6EP1437-2BA20: 24V 40A Switch Mode Power Supply Operating Instructions
Comprehensive operating instructions and technical specifications for the Siemens SITOP PSU300S 6EP1437-2BA20, a 24V 40A 3-phase AC input switch mode power supply unit. Covers safety, mounting, connection, technical data, signaling, and accessories.
PreviewSiemens SITOP PSU200M Power Supply Unit - Operating Instructions
Comprehensive operating instructions and safety guidelines for the Siemens SITOP PSU200M power supply unit, covering installation, connection, operation, and technical specifications. Available in multiple languages.
PreviewSiemens SIMARIS design & SIMARIS project Technical Manual
Comprehensive technical manual for Siemens SIMARIS design and SIMARIS project software, covering network calculation, system planning, and electrical equipment specifications.
PreviewSiemens DAC-NET Digital Audio Card - NETWORK Installation Instructions
This document provides comprehensive installation instructions for the Siemens DAC-NET Digital Audio Card - NETWORK. It details the product's features, operation modes (Class B and Class X), controls, indicators, pre-installation setup, wiring diagrams, and the physical installation process. The DAC-NET serves as a CAN-BUS master for CAN modules, handling digital audio data via ASI-BUS and communicating with BACnet networks.
PreviewSIMARIS design and SIMARIS project Technical Manual
This technical manual provides essential and special information on network calculation and system planning using Siemens' SIMARIS Planning Tools, covering power supply systems, degrees of protection, functional endurance, circuit-breakers, busbar trunking systems, and more.
PreviewSiemens SN1224L1125 Indoor Load Center: Safety and Installation Guide
Essential safety warnings, installation guidelines, and technical specifications for the Siemens SN1224L1125 Indoor Load Center, a Plug-On Neutral Ready Type 1 electrical panel.
PreviewSiemens SITOP Stromversorgungen: Effizienz, Zuverlässigkeit und Integration
Entdecken Sie die umfassende Produktpalette der Siemens SITOP Stromversorgungen, die für höchste Effizienz, Zuverlässigkeit und nahtlose Integration in industrielle Automatisierungssysteme entwickelt wurden. Erfahren Sie mehr über die vielfältigen SITOP Lösungen für Ihre industriellen Anwendungen.