Auto-OFF timer. Turns off the unit after a certain period of operation. ... Humidity setting. Sets the humidity level in 1% increments for the humidifier.
Job Name: ____________________ Location: _____________________ Date: ________________________ Purchaser: ____________________ Engineer: _____________________ Submitted To: _________________ For: Reference Approval Submitted By: _________________ Unit Designation: _______________ Schedule No.: ________________ CITY MULTI PAR-U01MEDU-K Construction Model No.: ___________ Submittal Date: Smart ME Remote Controller ME remote controller is a remote controller designed to control Mitsubishi Electric's air conditioning units and also allows for the control of other manufacturer's products connected via Mitsubishi Electric's AHC (Advanced HVAC CONTROLLER). It can control up to sixteen indoor units and one AHC. ME remote controller features such basic functions as operations and monitoring of air conditioning units and schedule-control functions and is equipped with four built-in sensors (temperature, humidity, occupancy, brightness), which enable an integrated control of the system, including the humidifiers and ventilation units connected to the system via AHC, to help create a comfortable environment. When the built-in occupancy sensor detects vacancy in a specific zone, the controller uses its internal function to reduce energy-consumption. NOTES: SB_PAR-U01MEDU-K_202002 CITY MULTI NOTES: Functions 1. Operation/Displ Item Description ON/OFF Switches between ON and OFF. : Each group : Not available Setting Display Operation mode Switches between Cool/Drying/Fan/Auto/Setback/Heat. switching *Available operation mode varies depending on the model. Hold Switches between enable and disable the Hold function. If the Hold function is enable, the following functions will be prohited. Timer/Schedule (Weekly timer) /Auto return Temperature setting Changes the set temperature. * Set temperature range varies depending on the indoor unit model. Changes fan speed. Fan speed setting * Available fan speeds vary depending on the model. Air flow direction Changes airflow direction. setting * Available airflow directions vary depending on the model. Louver setting Ventilation equipment control Switches between louver ON/OFF. * Available Louver setting vary depending on the model. Interlocked setting and interlocked operation setting with City Multi Lossnay units can be performed. The Stop/Low/High settings of the ventilation equipment can be controlled. Backlight Touching the screen turns the backlight on. It will stay lit for the amount of time that was specified on the MENU screen. Clock display Date (year/month/day) and time (hour/minute) can be set. The set time as well as the day of the week will be displayed on the Home display. The clock can be displayed in 12-hour format (AM/PM before or after the time) and 24-hour format. Daylight saving Sets the daylight saving time period. Room temp./ humidity display Displays the room temperature and humidity on the Home display. Error information When an error occurs, an error code and the unit address appear. A contact number can be set to appear when an error occurs. (The above information needs to be entered in the Service menu.) Filter information A filter sign will appear when it is time to clean the filter. SB_PAR-U01MEDU-K_202002 CITY MULTI NOTES: 2. Schedule and timer setti : Each group : Not available Item Description Setting Display Schedule (Weekly timer) Weekly ON/OFF times, operation mode, and set temperatures can be set. · Time can be set in 5-minute increments. Up to 8 schedule patterns can be set per day of the week. * Not valid when the ON/OFF timer is set. Timer ON/OFF timer Turns ON and OFF daily at a set time. · Time can be set in 5-minute increments. · It is also possible to set the ON time only or the OFF time only. Auto-OFF timer Turns off the unit after a certain period of operation. · Operation time can be set to a value from 30 to 240 in 10-minute increments. 3. Energy-save control assist functi : Each group : Not available Item Energy-save control during vacancy Description Setting Display When vacancy is detected by the occupancy sensor, the energysave control assist function is activated. Five control types are available for selection: ON/OFF/Operation mode/Set temperature/Fan speed/Thermo-off. The brightness sensor can be used in conjunction with the occupancy sensor to detect the occupancy/vacancy status more accurately. 4. Restriction settin : Each group : Not available Item Allows/disallows local operation Description Setting Display The following operation can be prohibited by applying certain settings on the centralized controller: ON/OFF, operation mode setting, temperature setting, fan speed, air direction, and filter sign reset. * While an operation is prohibited, the operation icon lights up. Operation lock The following operation can be prohibited respectively: ON/OFF, operation mode setting, temperature setting, Hold setting, and airflow direction setting. Temperature range restriction Auto return The room temperature range for each operation mode can be restricted. The units operate at the preset temperature after a designated period. (Time can be set to a value from 10 to 120 in 10-minute increments.) * Not valid when the temperature setting range is restricted. Password User password (required for schedule setting etc.) and Service password (required for test run and function setting etc.) can be set. SB_PAR-U01MEDU-K_202002 CITY MULTI 5. AHC control functions Item Description : Each group : Not available Setting Display Status monitor Displays the status of general equipments connected to the AHC. Humidity setting Sets the humidity level in 1% increments for the humidifier connected to the AHC, if any. 6. Miscellaneous ite Item Description Service Contains Set up, Error history, and Test run. : Each group : Not available Setting Display NOTES: SB_PAR-U01MEDU-K_202002Acrobat Distiller 9.5.3 (Windows)