GPD506andC21BypassTM4506.10

StartUp Instructions

Yaskawa ElectricAmerica, Inc

HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:....................4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT B

PDF preview unavailable. Download the PDF instead.

Yaskawa Manuals 527
GPD 506/P5 Start-up Procedure and Checklist
Preparation for GPD506/P5 Drive Start-Up .......................................................................2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option: ....................4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass Option: .........8
Before proceeding, familiarize yourself with TM (or I/O) 4506. you will find:
· "Simplified" Start-Up on page i · Contents on page x · Terminal Functions on page 1-8 · Connection diagrams on page 1-10 and 1-15 · "Initial" Start-Up on page 2-1 · Digital Operator description on page 4-1 · Quick Start Displays on page 4-2 · Programmable Features on page 5-1 (TM 4506 only) · Complete Listing of Parameter on page A1-1 · An Index at the back
Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 1 of 10

Preparation for GPD506/P5 Drive Start-Up
For HVAC Applications

In order to provide you with the most reliable drive available, and to avoid any extra costs related to loss or reduction of warranty coverage, an authorized Yaskawa Electric service representative should complete this start-up procedure. Please complete the following checklist and maintain it in a secured location as technical service personnel may request information from this checklist. Inability to provide this information may result in delays and extra costs to the end user.

Date: Start-up Person: Customer (Company): Sales Order #: Printed Name: Phone #:

Location: Serial #: Company: Signature:

Owners Representative: Printed Name: Company:

Phone #: Signature:

Check Step

1. The GPD 506/P5 is thoroughly tested at the factory. The start-up person should verify that the drive is free of shipping and installation damage. Shipping damage is not covered by the Yaskawa warranty; claims must be filed directly with the shipping company as soon as possible.

2. Review the Technical Manual, TM 4506, Installation/Operation Manual, I/O 4506 and any option instructions and schematics shipped with the drive.

3. Verify that the model numbers and voltage ratings are as specified in the purchase order by matching the nameplate data for each unit to the purchase order.

4. Verify that the drive has been installed in accordance with TM (or I/O) 4506, Section 1. "RECEIVING AND INSTALLATION". CAUTION: Failure to comply with TM (or I/O) 4506 Section 1, starting on page 1-1, may void the product warranty.

5. Inspect the security of the supply line power, ground connections and all control circuit connections as identified in these documents:
! Drive alone: refer to the Technical Manual TM (or I/O) 4506, Section 1. ! Drive/Bypass package: refer to the bypass schematic and TM (or I/O) 4506,
Section 1. ! Additional options: refer to any option instructions and schematics included with
shipment.

Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 2 of 10

IMPORTANT: Double check all the power wires and motor wires (L1, L2, L3 and T1, T2, T3) to make sure that they are securely tightened down to their respective lugs, loose wire connections may cause problems at any time. IMPORTANT: Confirm that the incoming line power supply is connected to the drive INPUT TERMINALS L1, L2, & L3, and NOT to the output motor terminals T1, T2 & T3.
6. Review the installer's "as wired" schematic. Determine where the motor "safety circuit" is connected. Verify that the customer's emergency contacts are properly terminated in the drive's safety shutdown circuit: · If normally closed, these contacts may be wired in series with the RUN command contacts, which are between terminal S1 and SC of the drive. No special programming is required. - See TM (or I/O) 4506, page 1-15.
· Alternately, these contacts could be wired to terminal S3 as External Fault Inputs, and may be either normally closed or normally open contacts. - See TM 4506, page 5-29 for programming instructions.
Verify that all other field installed wires are correctly terminated (including the shields).
7. Record the motor nameplate information: Voltage __________ Service Factor ___________ Full Load Amps (FLA) ___________
8. Verify that the input voltage matches the drive's rating.
9. Verify that the motor is wired for the application voltage.
10. IMPORTANT: Verify that the motor rated full load amps (FLA) does not exceed the rated output current of the drive controlling it. When multiple motors are simultaneously operated by the drive, the sum of all motor rated FLA values must be less than or equal to that of the drive controlling them.
11. Record any other connections to the drive, by terminal number to determine if special programming of any of the follow is required. ! Multi-function Inputs - see TM 4506, paragraph 5.19 starting on page 5-28 ! Multi-Function Outputs - see TM 4506, paragraph 5.20, starting on page 5-41
12. Verify that the building automation system logic is ready to perform adequately for start, stop and speed command functions.
THIS CONCLUDES THE PREPARATION PROCESS FOR DRIVE START-UP. KEEP YOUR TECHNICAL MANUAL, INSTALLATION/OPERATION MANUAL , OPTION SCHEMATICS, AND ANY OTHER INSTRUCTIONS SENT WITH THE DRIVE EASILY ACCESSIBLE TO ASSIST YOU THROUGH THE REMAINDER OF THE START-UP PROCESS.
Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 3 of 10

HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:
(For start-up of GPD 506/P5 without Bypass please go to page 8) [Please review "Preparation for Drive Start-up on page 1]
Check Step
1. Verify that the electrical supply power lines are connected to the input circuit breaker and that the motor leads are connected to the output terminals of the overload relay. Ensure that all connections are tight, factory connections sometimes come loose during shipment.
2. Record all other connections to the bypass cabinet or the VFD and confirm that the building management system logic is ready to perform adequately for start, stop and speed command functions.
3. Before applying power, make sure that the following conditions are met: ! The DRIVE/OFF/BYPASS switch is in the OFF position. ! The HAND/STOP/AUTO switch is in the STOP position. ! The NORMAL/TEST switch is in the NORMAL position. [Note: If the TEST position is selected while the DRIVE/OFF/BYPASS switch is in the DRIVE position; the fault code "EF3" will be displayed on the digital operator. TEST mode is only available when in the OFF or BYPASS positions.] ! The VAV terminal unit dampers, in fan applications, are open to prevent duct flexing or damage in a full speed or across the line starting situation. ! The electro-mechanical motor overload, labeled "S12", is adjusted to equal the full load amps (FLA) from the motor nameplate.
4. Apply power to the drive and bypass package, make sure that all three phases are present and that the input voltage is correct for the system being set up. Then move the DRIVE/OFF/BYPASS switch to the DRIVE position. [Note: If the FAULT light is on at this time, press the reset button on the motor overload relay, labeled "S12" and check the "safety device" circuit between terminals TB1-1 and TB1-2.]
5. The DRIVE, STOP and REMOTE SEQ and REF LEDs on the drive should be on.
Quick start displays are directly available by pressing the DSPL key. When scrolling through these displays, the DRIVE LED is on when the drive can accept a run command (drive mode) and off when it can not accept a run command. - See TM (or I/O) 4506, page 4-2
6. Press the DSPL key until "Parameter nXXX" is displayed -or- simultaneously press the DSPL and ENTER keys. This enters the "Programming mode" of the GPD 506/P5 ­ from here, any of the 116 parameters can be accessed and changed using the DSPL, #,$, and ENTER keys. - See TM 4506, page 5-1 for a list of programmable features. Using the DSPL, #, and ENTER keys as needed, verify that the parameters are correct for the drive and installation conditions. See the "Special Parameter Settings as printed on page 2 of the bypass schematic and consider any parameters specific to this application.
Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 4 of 10

IMPORTANT
· The, "Special Parameter Settings" Table on page 2 of the bypass schematic documents several parameters that have been factory set to meet the needs of the bypass control circuit (for example: the LOCAL/REMOTE key has been disabled). These parameters should not be changed. If an "initialization" is performed, via parameter n001, to re-set the drive to "factory settings", then the parameters in Table 4 must be re-established in order for the bypass to work properly.
· The Special Parameters Table is also used to document parameters that have been factory set, for convenience, to typical values for fan and pump applications. These parameters may be changed to meet the needs of the specific application and include: n006 Reverse prohibit, n018 Acceleration time, n019 Deceleration time and n055 Momentary power loss ride-through. For example: In fan applications employing duct high pressure safety limit switches, it may be necessary to further adjust the deceleration time to avoid high pressure limit trips due to damper closure as the system is shut down. An alternate solution in this situation is to set parameter n004 to "Coast to Stop". - See TM 4506, page 5-55]
7. Using the DSPL, #, and ENTER keys, display "Motor Rated FLA". Set this parameter to the Full Load Amps (FLA) rating on the nameplate of the motor. This will provide motor overload protection. - See TM 4506, page 5-57
8. Set n009 to "Enter Not Used" to avoid the need to press the ENTER key when adjusting the speed command from the digital operator.
9. Verify n072 is set to "Enabled" to enable the Stall Prevention During Deceleration function. - See TM 4506, page 5-53
10. Set n073 to "100%" to optimize Stall Prevention During Acceleration for most HVAC applications. - See TM 4506, page 5-53
11. Press the display key again to return to DRIVE operation. The Remote SEQ and REF LED's should be on at this time as well as the STOP and DRIVE LEDs.
12 To start the Drive, move the HAND/STOP/AUTO switch to HAND. The RUN LED will turn on and the Drive will ramp up to "6 HZ" -or- ramp to the speed potentiometer setting if a speed pot. is included in the bypass unit. Verify that motor rotation is correct. [Note: In bypass packages the drive is programmed at the factory for 5 seconds of DC injection braking at start (to stop a rotating motor when switching from BYPASS to DRIVE), expect to see this delay each time the drive is started. - See TM 4506, page 5-8]
If the direction of motor rotation is wrong, turn the DRIVE/OFF/BYPASS switch to OFF; and turn Power Off! Wait for the Red CHARGE LED (near the drive power terminals) to go out. When it does, swap the wires on the motor terminals T1 & T2 or on the output terminals of the motor overload relay, labeled "S12". Tighten the terminal lugs, reapply the power, turn to DRIVE; and re-check the rotation direction.
Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 5 of 10

13. With correct motor rotation, press the DSPL key until "Frequency Ref" is displayed. Using the #,$, ENTER, RUN, and STOP keys, manually run the drive throughout its entire operating range, while observing operation. If excessive vibration of the driven load is noted at specific input frequencies, the Critical Frequency Rejection function may be used to eliminate this vibration, by programming n062 through n064. - See TM 4506, page 5-7.
14. Determine whether the remote speed reference is a 0-10 VDC or a 4-20 mA signal. Connect the positive side of a 0-10 VDC signal to terminal TB1-22 of the bypass terminal strip. Connect the positive side of a 4-20 mA signal to terminal TB1-20. Connect the COMMON of the remote speed reference to terminal TB1-21. - See the connection diagram on page 1 of the bypass schematic. [Note: Connect only one input. The factory default is 0 to 10 VDC, to change to 4-20 mA adjust parameter n043 to "FV=AUX FI=MSTR" as shown on page 5-15 of TM 4506] Turn the HAND/STOP/AUTO switch to AUTO, then request a run command and speed reference from the building automation system to confirm remote operation.
15. Check the signal for proper polarity. Observe if the remote speed command can achieve the minimum and maximum speeds desired. If not, perform the following: - See TM 4506, pages 5-13 and 5-14 for further information.
For 0-10 VDC input (Terminal FV) 1. With no input, adjust Bias (n049 setting) until an output of "0.0 Hz" is obtained.
2. With full scale input, adjust Gain (n048 setting) until an output of "60.0 Hz" (or other desired maximum frequency) is obtained.
For 4-20 mA input (Terminal FI) 1. With 4 mA input, adjust Bias (n051 setting ) until an output of "0.0 Hz" is obtained.
2. With 20 mA input, adjust Gain (n050 setting ) until an output of "60.0 Hz" (or other desired maximum frequency) is obtained.
16. Turn the DRIVE/OFF/BYPASS switch to OFF. If the drive is in the RUN mode, it will ramp to a stop before input power shuts off. Once power to the drive is off, select the TEST position of the NORMAL/TEST switch. Only input power is supplied in this mode of operation, the motor is not connected to the drive output. The remote "SEQ" & "REF" LED's should now be off. RUN, STOP, and Frequency Reference may now be selected using the Digital Keypad. When the TEST function is verified, press the STOP button on the drive and return the switch to NORMAL.
17. Verify that the electro-mechanical motor overload relay, labeled "S12", is adjusted to equal the full load amps (FLA) value from the motor nameplate.
Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 6 of 10

18. In preparation for testing the bypass, observe the trip setting of the circuit breaker, labeled CB1. The trip point is factory set at the lowest possible setting and must be adjusted for each application. This breaker will trip due to inrush current and load inertia unless it is re-set! For fan applications adjust the trip setting to ten times motor FLA. For pump applications adjust the trip setting to six times motor FLA. If circuit breaker tripping is experienced at these settings during motor starting on bypass, increase the setting gradually until the motor can be started without circuit breaker tripping.
19. Be prepared to monitor rotation of the motor in bypass operation. "Bump" the BYPASS/OFF/DRIVE switch to the BYPASS position and quickly back to OFF. Check the motor rotation. Do not allow the motor to operate in BYPASS until rotation is correct!
20. If the rotation direction in bypass is correct, skip the rest of this step. If not check for the following and perform the described corrections: ! Turn off the incoming power feed to the drive. Since the correct rotation in Drive mode was previously established, do not change any output wires at motor. ! Instead, verify that power to the circuit breaker is off. Now Swap L1 & L2 on the input side of the circuit breaker/disconnect switch, labeled "CB1". This will affect rotation in the bypass operation only. Once connections are complete and tight, reapply incoming power and repeat the previous step to re-check the rotation direction.
21. Run the motor in bypass by placing the BYPASS/OFF/DRIVE switch in BYPASS. Record all the phase voltages and currents at this time.
22. Select the STOP position of the HAND/STOP/AUTO switch and place the BYPASS/OFF/DRIVE switch in DRIVE. Turn to the HAND position and scroll the frequency reference to "60 HZ" operation. Monitor the voltages and currents in each of the output phases at full speed to make sure that the voltages are balanced and that the currents are within the motor nameplate rating during accel, stable speed, and decel.
23. If this application requires the drive to operate in PID mode, see TM 4506, pages 5-45 through 5-49.
24. With the BYPASS/OFF/DRIVE switch set to OFF, set the building automation system to give the drive a run command and a speed request. Put the BYPASS/OFF/DRIVE switch into BYPASS and let the load speed up and stabilize. Turn the BYPASS/OFF/DRIVE switch to OFF momentarily, then move the switch to DRIVE. Observe if the DC braking is enough to stop the fan in the time period set in parameter n070 (5 sec factory setting). If not, set this parameter out to its maximum setting, which is 10.0 seconds. If this is not enough, slowly increase the braking current setting (parameter n068) but do not go above 90% to protect the drive output devices. - See TM 4506, page 5-8
THIS COMPLETES THE START-UP PROCEDURE FOR THE GPD506 WITH BYPASS.
Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 7 of 10

HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass Option:
(For start-up of GPD 506/P5 with Bypass please go to page 4) [Please review "Preparation for Drive Start-up" on page 1]
Check Step
1. Energize the drive, confirm that all three phases are present and that the input voltage is correct for the system being set up. The DRIVE, STOP and REMOTE SEQ and REF LEDs should be on.
Quick start displays are directly available by pressing the DSPL key. When scrolling through these displays, the DRIVE LED is on when the drive can accept a run command (drive mode) and off when it can not accept a run command. - See TM (or I/O) 4506, page 4-2
2. Press the LOCAL/REMOTE key to turn off the REMOTE SEQ and REF LEDs. This puts the drive in the local control mode, allowing RUN, STOP and speed commands by the digital operator. "Frequency Ref" should be displayed on the Digital Operator (if not, press the DSPL key until the display reads "Frequency Ref").
3. Press the # key until the display reads "6.0 Hz". Press the ENTER key. Press the DSPL key until "Output Freq" is displayed. Press the RUN key. The display should ramp up to "6.0 Hz".
4. Press the DSPL key until "Forward/Reverse" is displayed. The display should read "For" (Forward direction) and the FWD LED should be on (If not, press the # key until the display reads "For", and then press the ENTER key). Check the direction of the motor shaft rotation to be sure that the proper direction of motor rotation is established.
If the direction of motor rotation is wrong, press the STOP key. Remove power from the drive. Wait for the Red CHARGE LED (near the power terminals) to go out. When it does, swap the wires on motor terminals T1 & T2. Tighten the terminal lugs, and power up the drive. Press the LOCAL/REMOTE key to put the drive in the Local control mode, then press the RUN key and verify that the direction of the motor shaft rotation is now correct.
5. Press the DSPL key until "Output Freq" is displayed. Press the STOP key. The display should ramp down to "0.0 Hz" and the FWD LED should go off.
6. Using the DSPL, #, and ENTER keys as needed, display "Accel Time 1". Set this parameter to "60.0 Sec". This will establish a typical 60 second accel ramp for fan applications. For pump applications, this value may be left at the default 10 seconds.
7. Using the DSPL, #, and ENTER keys, display "Decel Time 1". Set this parameter to "60.0 Sec". This will establish a typical 60 second decel ramp for fan applications. For pump applications, this value may be left at the default 10 seconds. [Note: In fan applications employing duct high pressure safety limit switches, it may be necessary to further adjust this deceleration time to avoid high pressure limit trips due to damper closure as the system is shut down. An alternate solution in this situation is to set parameter n004 to "Coast to Stop". - See TM 4506, page 5-55
Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 8 of 10

8. Press the DSPL key until "V/f Selection" is displayed. "60 Hz Preset" should be displayed on the second line (If not, press the # key until the display reads "60 Hz Preset", and then press the ENTER key). This will establish an optimum volts/hertz pattern for HVAC applications. - See TM 4506, page 5-60
9. Using the DSPL, #, and ENTER keys, display "Motor Rated FLA". Set this parameter to the Full Load Amps (FLA) rating on the nameplate of the motor. This will provide motor overload protection. - See TM 4506, page 5-57
10. Press the DSPL key until "Parameter nXXX" is displayed -or- simultaneously press the DSPL and ENTER keys. This enters the "programming mode" of the GPD 506/P5 ­ from here, any of the 116 parameters can be accessed and changed using the DSPL, #,$, and ENTER keys. - See TM 4506, page 5-1 for a list of programmable features.
11. Set n001 to "3". This allows all the GPD506 parameters (n001-n116) to be both Read & Set. - See TM 4506, page 5-50
12. Set n006 to "REV Prohibited" to disable Reverse operation.
13. Set n009 to "Enter Not Used" to avoid the need to press the ENTER key when adjusting the speed command from the digital operator.
14. Set n055 to "2 Seconds Max" to enable the Power Loss Ride Through function. - See TM 4506, page 5-26
15. Set n060 to "10" to enable the maximum number of Automatic Restart Attempts, see
TM 4506, page 5-5. WARNING: Selecting the auto-restart feature can cause the motor to start unexpectedly. - See TM 4506, page 5-5
16. Press the DSPL key until "Frequency Ref" is displayed. Using the #,$, ENTER, RUN, and STOP keys, manually run the drive throughout its entire operating range, while observing operation. If excessive vibration of the driven load is noted at specific input frequencies, the Critical Frequency Rejection function may be used to eliminate this vibration, by programming n062 through n064. - See TM 4506, page 5-7.
17. Verify that n072 is set to "Enabled" to enable the Stall Prevention During Deceleration function. - See TM 4506, page 5-53
18. Set n073 to "100%" to optimize Stall Prevention During Acceleration for most HVAC applications. - See TM 4506, page 5-53
19. Press the display key again to return to DRIVE operation. If you are using a remote speed command, press the LOCAL/REMOTE key until the REMOTE SEQ and REF LEDs are on. This puts the drive in the Remote Control mode.
Yaskawa Electric America, Inc www.drives.com Instruction Manual TM4506.10 Date 09/16/02 Page 9 of 10

20. Determine whether the remote speed reference is a 0-10 VDC or a 4-20 mA signal. Connect the positive side of a 0-10 VDC signal to terminal FV. Connect the positive side of a 4-20 mA signal to terminal FI. Connect the COMMON of the remote speed reference to terminal FC. - See the connection diagram on page 1-15 in TM (or IO) 4506.
[Note: Connect only one input. The factory default is 0 to 10 VDC, to change to 4-20 mA adjust parameter n043 to "FV=AUX FI=MSTR" as shown on page 5-15 of TM 4506]
21. Check the signal for proper polarity. Observe if the remote speed command can achieve the minimum and maximum speeds desired. If not, perform the following: See TM 4506, pages 5-13 and 5-14 for further information. For 0-10 VDC input (Terminal FV)
1. With no input, adjust Bias (n049 setting) until an output of "0.0 Hz" is obtained. 2. With full scale input, adjust Gain (n048 setting) until an output of "60.0 Hz" (or other
desired maximum frequency) is obtained. For 4-20 mA input (Terminal FI) 3. With 4 mA input, adjust Bias (n051 setting ) until an output of "0.0 Hz" is obtained. 4. With 20 mA input, adjust Gain (n050 setting ) until an output of "60.0 Hz" (or other desired maximum frequency) is obtained. 22. If your application requires the PID function for closed-loop Setpoint Control operation, see TM 4506, pages 5-45 through 5-49.
THIS COMPLETES THE START-UP PROCEDURE FOR THE GPD506 WITHOUT BYPASS.