PDF preview unavailable. Download the PDF instead.

2011 headend catalog
> Critical Facilities Powering and Construction
Total Power Solutions by ALPHA Technologies

The Alpha Group - Total Power Solutions
> Alpha Power
Alpha pioneered the concept of reliable uninterruptible power for communications networks, and in the process has set a 35-year precedent for visionary, market-driven power solutions. Today, with millions of power systems installed around the world, we continue to focus on providing the most reliable, innovative and energy efficient powering solutions.
> Global Reach
With millions of powering system installed and sales, manufacturing and service facilities located around the world, we are able to help you in a language you'll understand. This global reach gives us the expertise to provide your specific power solution.

> Our Goal: Reducing Your Total Cost of Ownership
> Reliability
We are engineering the next generation of power technologies committed to reliability, cost savings and best-in-class performance.
> Sustainability
Running a more efficient powering network can reduce the resources consumed, and your operational expenses.

> Intelligence
Instead of giving you data, intelligent products give you answers. We are working to provide the answers to optimize system performance.
> Efficiency
Through proper load matching and power supply sizing, tailored powering systems can perform at up to 94 percent efficiency.

Table of Contents

Table of Contents

> DC Power Systems

3-27

> AlphaTVSSTM

65

CordexTM Power Systems........................................4

Cordex Controller Features....................................5 Cordex Comparison Chart.....................................6 Cordex CXCR/CXCP..............................................7 Cordex CXCM4......................................................8 Cordex CXCM2......................................................8 Cordex CXCM........................................................9 Cordex CXCI...........................................................9

> Total Power Solutions

67-73

System Solutions..................................................68

Installation and Construction Services.................69

Repairs and Refurbishments................................ 70

Customer Service................................................. 71

Alpha Building Systems........................................72

Cordex 400 and 650W......................................... 10 Cordex 400W/650W............................................ 11 Cordex HPTM 1.2kW............................................... 12 Cordex 1.8kW....................................................... 14 Cordex HP 2kW.................................................... 15 Cordex 3.6kW...................................................... 16 Cordex HP 4kW.................................................... 17 CXPS 48-1.2-225.................................................. 18 CXPS 48-1.8-i and CXPS 48-1.8-M2.................... 19

> Fiber Power

75-81

FlexPointTM 12Vdc, RFoG....................................... 76

FlexPoint AX 12Vdc, PON.....................................77

FlexNetTM 48Vdc 50W............................................78

FlexNet 48Vdc 150W............................................78

FlexNet 48Vdc 300W...........................................79

PMR and GMR Series..........................................80

Radium MiniBay................................................... 81

CXPS 48-1T..........................................................20

> Alpha Enclosures

83-97

CXPS 48-2T.......................................................... 21

Tempest Te25 / Te25xh........................................84

Cordex System.....................................................22

Tempest Te15.......................................................85

CXPS 24­48-i....................................................... 24

Distribution Centers..............................................25

Tempest Te17.......................................................86

DC Accessories....................................................26

Tempest Te21.......................................................87

Tempest Te30.......................................................88

1

> Batteries and Accessories

29-37

Batteries

Telecommunications..........................................30

Telecommunications and Business Services..... 31

Business Services..............................................32

UPS......................................................................34

Battery Monitoring................................................35

Network Monitoring..............................................35

AlphaGuardTM........................................................36

Tempest Te45.......................................................89 Tempest Te45 Battery..........................................90 Tempest Te40 Battery..........................................91 Tempest Te41 Power............................................92 Tempest Te44.......................................................93 Flexible Backhaul Enclosure 2322.......................94 Flexible Backhaul Enclosure 2319........................95 Flexible Backhaul Enclosure 1417V......................96 Wireless Transport Enclosure...............................97

Battery Testing Equipment...................................37

> AlphaGenTM Generators

99-101

> DC to AC Inverters

39-47

AMPS80HP..........................................................40

AlphaGenTM 3.5kW to 2MW Systems................100 AlphaGen Telecom............................................. 101

AMPS24HP.......................................................... 41

Arcon Inverter Series............................................42

TEBEVERT Inverter Series...................................43

Invertronic Inverter System...................................44

Media Inverter System..........................................45

DSP Inverter Series..............................................46

MS Power Inverter Series..................................... 47

> Single and Three Phase UPS

49-63

AMPS80HP..........................................................50

AMPS24HP.......................................................... 51

EX UPS.................................................................52

EX RT UPS...........................................................54

1600 XP Series.....................................................56

TrinitiTM 4200 Series...............................................57

Galaxy 3500.........................................................58

Galaxy 4000.........................................................59

Galaxy 5000.........................................................60

Galaxy PW Series.................................................61

G9000 Series.......................................................62

Symmetra PX........................................................63

2

Table of Contents

DC Power Systems
The Alpha Group has more than 30 years of experience providing a wide variety of fully integrated power system solutions. With options for standardized systems and custom DC system integration, The Alpha Group has the flexibility to provide DC power solutions perfect for a wide range of power needs and various site installation requirements. Integrated shelf systems are available for all small power rectifier models providing a complete power solution in a single rack mount package. These systems incorporate a CordexTM controller, rectifiers and DC distribution options in a compact shelf design. Optional accessories such as LVDs, shunts and temperature compensation are available. For medium to large system applications, The Alpha Group can provide both standard and custom DC system solutions designed to maximize space and cost savings. Systems can be integrated with a wide array of options including various rack solutions, custom DC distribution configurations, multiple voltage output designs and front access. Coupling advanced Cordex power technology with an enormous selection of system components, The Alpha Group can easily provide optimal system solutions up to 8,000 Amps.
3

DC Power Systems

CordexTM Power Systems
Matrix

DC Power Systems

AMPS
(not to scale)
10,000

CXCM4 CXCR CXCP

9000A

8000

6750A 6000

CXCR
8000A
6000A

48V

4500A 4000
2250A 2000
1000

4000A 2000A

CXCM4 CXCR CXCP
2250A
1500A
1000A

CXCM4 CXCP
2000A
1350A

900A

4

800

600 500A
400
200
175

450A

500A

450A

CXCI CXCM2 CXCR
420A
210A

CXCI CXCM2 CXCR
375A
187A

CXCM1
225A

24V
CXCM4 CXCP
2000A 1560A 780A

DC Power Systems

150

CXCI

CXCI

130A 140A

125

CXCM CXCR

130A

120A

100

100A

83A 75A
75

CXCI

70A

65A

65A

50

42A

37A

25A

25

20A

13A

13A

14A

0
48-4kW HP Multi bay

48-3.6kW Multi bay

48-4kW HP Single bay

48-3.6kW Single bay

48-2kW HP 48-1.8kW 48-1.2kW HP 48-1kW

48-650W 48-650W 24-3.1kW

Single shelf Single shelf Single shelf Single shelf Single shelf Single shelf Single bay

w/expansion w/ expansion w/ expansion

w/ expansion

24-400W Single shelf w/ expansion

CordexTM Controller Features

DC Controllers

> The CordexTM CXC is Alpha's latest generation of advanced digital controllers for power system monitoring and control. CordexTM supervisory controllers come in a wide array of modular designs for compact integration into Alpha power systems. Stand-alone rack mount versions are also available for DC systems, legacy controller upgrades and site monitoring solutions.
A graphic LCD display with state-of-the-art touch-screen interface allows simple and convenient set up, control and monitoring of CordexTM rectifiers. Innovative IP technology allows complete configuration and monitoring from any location via the Internet using a standard web browser. CordexTM CXC controllers come standard with several advanced battery management features to allow for significant savings of capital and operational expenses. Additional features include user definable alarms with custom algorithms, digital and analog input monitoring, data logging, integrated SNMP and highly reliable CAN bus communications. Software upgrades are easily downloaded and provided free of charge.

> Main

> Battery Management

· Web based GUI Interface: Web browser support for local or

· Temperature Compensated Float Voltage: Increases voltage in

remote control and monitoring.

temperatures below 25°C / 77°F and decreases charge voltage

· Single point set up and control. · Auto voltage adjustment and load sharing. · Analog digital inputs. · Configurable Form C relay outputs.

above 25°C / 77°F. Maximizes life and capacity of battery and prevents thermal runway.

· Battery Equalize: Manual, automatic and periodic equalize

5

charge modes. Optional Battery Current Terminate function to

prevent over charging of battery.

· Various preset alarms and ability to configure up to 20 customized alarms.

· Battery Boost Mode: Offline high-voltage equalize charge with interlock safety feature.

· User programmable logic statements.
· Legacy Power System Upgrade: Controls legacy Pathfinder based systems and can be used as a site monitor for any 3rd party DC power system.

· Dynamic Charge Current Control: Limits battery recharge current to a fixed value. Helps prevent thermal runway.
· Battery Test: Sets rectifier voltage low and performs safe discharge of batteries through the connected system loads.

· CAN Communications: Common platform for Alpha power electronics and peripherals. Rugged and field proven protocol.

· Battery Capacity Prediction: Calculates current battery capacity after a discharge.

· Fail Safe System Operation: In the event of CXC failure, rectifiers continue to run with default settings, fail alarm is generated and LVDs (if equipped) remain energized.
· Power Save Function: Improves operational efficiency by running the minimum number of rectifier modules required per system load.
· System Start Delay: Allows delay for other AC powered equipment to start before rectifiers.
· Ramp Test Control: Disables fail alarm on no-load conditions.
· SNMP Support: Network management service support for managing multiple systems in a single network.

· Battery Runtime Prediction: Based on current battery capacity and system load.
· Battery Logging: Retain up to 40 records of battery statistics and events.
> Maintenance
· Data Logger: Record any system input(s), and set sample rate of record on deviation. Store up to 500 events via manual or auto start/stop.
· Typical data log applications: Detailed battery discharge info, AC voltage watch dog and outdoor cabinet thermal performance.

· Email notifications via TCP/IP.
· Cordex Peripheral Support: Optional add-ons for individual cell and temperature monitoring and controller I/O expansion.

· Easy Remote Software Upgrades: Fail-safe protected upgrades for controllers, rectifiers and peripherals.

· Multi language support including Chinese characters.

CordexTM Comparison Chart
> Cordex Controllers come standard with several advanced battery management features to allow for significant savings of capital and operational expenses. Some additional features include user definable alarms with custom algorithms, digital and analog input monitoring, data logging, integrated SNMP and CAN bus communications. The Cordex CXC is designed for effortless operation of the Cordex rectifier family, making time consuming and complicated set up and monitoring of DC power systems a thing of the past.

DC Controllers

CXCR/CXCP

CXCM4

CXCM2

CXCM1

CXCM

CXCI

Specifications

Screen:

Full Graphic LCD 160 x 160 pixels

Full Graphic LCD 160 x 160 pixels

Full Graphic LCD 160 x 160 pixels

Basic Current / Volts Display Only

Full Graphic LCD 160 x 160 pixels

Basic Current / Volts Display Only

Inputs
6
Analog:

2V, 2T, 4C, 2BIV

2V, 2T, 4C, 2BIV

1V, 2T, 2C, 4BIV

1V, 1C, 2T

2V, 2T,1C, 1BIV

1V, 1C, 2T

Digital:

8

4

6

2

3

2

Alarm Relay Outputs:

8 Form C

Dimensions

Height x Width x Depth (in/mm):

5.1 x 16.9 x 3.9 / 131 x 431 x 100

Rectifier shelf option availability

4kW HP (48Vdc)

Yes

8 Form C
7 x 3.4 x 10.1 / 177 x 87 x 257
Yes

6 Form C

4 Form C

8 Form C

3.4 x 5 x 9.7 / 86.4 x 128 x 247

1.6 x 334 x 10.1 / 41.4 x 84.4 x 256.8

6.9 x 2.9 x 10 / 177 x 74 x 255

4 Form C
3.5 x 1 x 11 / 88 x 26 x 280

3.6kW (48Vdc)

Yes

Yes

2kW HP (48Vdc)

Yes

Yes

Yes

1.8kW (48Vdc)

Yes

Yes

Yes

1.2kW HP (48Vdc)

Yes

1kW (48Vdc)

Yes

Yes

650W (48Vdc)

Yes

400W (24Vdc)

Yes

CordexTM CXCR/CXCP
System Controller
> LCD touch-screen user interface > Internet ready, integrated SNMP > High reliability CAN bus communication > User definable alarms > Flexible battery management features > Smart peripheral monitoring features > 19" and 23" Universal rack or panel mount configurations

CXCR Rack mount Controller

Cordex CXCR/CXCP

Features

Environment

Electrical

Extended Temperature:

-40 to 65°C / -40 to 149°F

LCD touchscreen display (160 x 160 pixels),

Humidity:

0 to 95% non-condensing

Display:

"OK / Major / Minor" 3-Color, LED display, Web based GUI via ethernet

Standards

Communication Ports:

RJ45 ethernet port (front accessible rear port) RS232 craft port (front)

Safety:

CSA C22.2 No 60950-1-03 CE marked

RS232 modem port (optional)

EMC:

ETSI 300 386

Controller I/O

7
CFR47 (FCC) Part 15 Class B

Voltage Inputs:

2

Temperature Inputs:

2

Emissions:

ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia)

Current Inputs:

4

Bi Voltage Inputs:

2

EN 61000-4-2 EN 61000-4-3

Digital Inputs:

8

Relay Outputs:

8

Immunity:

EN 61000-4-4 EN 61000-4-5 EN 61000-4-6

Mechanical

Dimensions H x W x D (excludes mounting brackets) (in/mm):

5.1 x 16.9 x 3.9 / 131 x 431 x 100

Mounting:

CXCR with 19" or 23" rack mounting CXCP panel mount

Weight (lb/kg):

13.8 / 6.2

DC Controllers

CordexTM CXCM4
System Controller

> User definable alarms and data logging > Flexible battery management features > Smart peripheral monitoring features > 4RU modular CXC for 3.1/3.6kW rectifiers
CXCM4

Cordex CXCM4

Features

Environment

Electrical

Extended Temperature:

-40 to 65°C / -40 to 149°F

Display: Communication Ports:

LCD touchscreen display (160x160 pixels), "OK / Major / Minor" 3-Color, LED display, Web based GUI via ethernet
RJ45 ethernet port, RS232 craft port (front)

Humidity: Standards
Safety:

0 to 95% non-condensing
UL/CSA C22.2 No 60950-1-03 CE marked

Controller I/O

ECM:

ETSI 300 386

Voltage Inputs:

1 + 1 Internal

Temperature Inputs:

2

Current Inputs:

4

Bi Voltage Inputs:

2

Digital Inputs:

4

Relay Outputs:

8

8

Mechanical

Dimensions H x W x D (in/mm): 7 x 3.4 x 10.1 / 177 x 87 x 257

Emissions: Immunity:

CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia)
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6

Weight (lb/kg):

3.9 / 1.8

Mounting:

Modular controller for 3.1kW and 3.6kW shelves

DC Controllers

Cordex CXCM2
System Controller

> LCD touch-screen user interface > Internet ready, integrated SNMP > High reliability CAN bus communication > 2RU modular CXC for 1.8kW rectifiers

Cordex CXCM2

Features

Electrical

Input Voltage: Current:

17 to 65Vdc <100mA @ 48Vdc or <200mA @ 24Vdc

Display:

LCD touchscreen display (160x160 pixels), "OK / Major / Minor" 3-Color, LED display, Web based GUI via ethernet

Communication Ports: Controller I/O Voltage Inputs: Temperature Inputs: Current Inputs: Digital Inputs: Relay Outputs: Mechanical Dimensions H x W x D (in/mm): Mounting:

RJ45 ethernet port (front)
1 + 1 Internal 2 2 6 6
3.4 x 5 x 9.7 / 96.4 x 128 x 247 Modular controller for 1.8kW shelves

CXCM2

Environment Extended Temperature: Humidity: Standards Safety: ECM:
Emissions:
Immunity:

-40 to 65°C / -40 to 149°F 0 to 95% non-condensing
CSA C22.2 No 60950-1-03 CE marked
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia)
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6

CordexTM CXCM
System Controller

> LCD touch-screen user interface

> Internet ready, integrated SNMP

> High reliability CAN bus communication

> User definable alarms and data logging

> 4RU modular CXC for 1kW rectifier

CXCM

Cordex CXCM

Features

Environment

Electrical Display:
Communication Ports:
Controller I/O Voltage Inputs: Temperature Inputs: Current Inputs:

LCD touchscreen display (160 x 160) pixels, "OK / Major / Minor" 3-color, LED display, Web based GUI via ethernet RJ45 ethernet port (front accessible rear port) RS232 craft port (front) RS232 modem port (optional)
1 + 1 Internal 2 1

Extended Temperature: Humidity: Standards Safety: EMC:
Emissions:

-40 to 65°C / -40 to 149°F 0 to 95% non-condensing
CSA C22.2 No 60950-1-03 CE marked ETSI 300 386 CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia)

Bi Voltage Inputs:

1

EN 61000-4-2

Digital Inputs:

3 (2 +1 internal on some models)

EN 61000-4-3

Relay Outputs:

8

Mechanical

Immunity:

EN 61000-4-4

EN 61000-4-5 EN 61000-4-6

9

Dimensions H x W x D (in/mm): 6.9 x 2.9 x 10 / 177 x 74 x 255

Weight (lb/kg):

3.9 / 1.8

Mounting:

Modular controller for 1kW rectifier shelves

DC Controllers

Cordex CXCI
System Controller

> Control and monitor via Internet Explorer browser > Flexible battery management features > Smart peripheral monitoring features > Integrated option on 1.8kW, 650W and 400W shelves

Cordex CXCI
Features Electrical Input Voltage: Current:
Display:
Communication Ports:
System I/O Voltage Inputs: Temperature Inputs: Current Inputs: Digital Inputs: Alarm Relays:

17 to 65Vdc <100mA @ 48Vdc or <200mA @ 24Vdc 4 segment LCD for V/I display, "OK / Major / Minor" 3-color, LED display, Web based GUI via ethernet RJ45 ethernet port (front), RS232 modem port (front)
1 + 1 internal 2 1 (0 + 1 internal on some models) 2 4 (3 + 1 internal on some models)

CXCI

Mechanical Dimensions H x W x D (in/mm): 3.5 x 1 x 11 / 88 x 26 x 280

Mounting:

Integrated on Cordex 2RU series 19" and 23" shelves

Environment Temperature: Humidity: Standards

-40 to 65°C / -40 to 149°F 0 to 95% non-condensing

Safety:

CSA C22.2 No 60950-1-03 CE marked

CordexTM 400 and 650W
Modular Switched Mode Rectifier
> Available in 13.5A @ 48Vdc and 14A @ 24Vdc > High power density > Power limiting and wide range AC input > 91% efficiency and power factor correction > Hot swappable, 2RU ultra compact design

Cordex 400W Rectifier Module

Electrical

Input Voltage: Power Output: Input Frequency: Power Factor: THD: Efficiency: Output Voltage: Output Current:

90 to 320Vac 400W (max) 45 to 70Hz >99% <5% >90% 20 to 29Vdc 14A (current limited)

10

Load Regulation:

Static <±0.5%, Dynamic <±2% for 50 to 100% load step, 2ms recovery time

Line Regulation:

Static <±0.1%, Dynamic <±1% for any change within rated limits

Mechanical

Dimensions H x W x D (in/mm): 3.4 x 2.8 x 9.5 / 88.4 x 71.6 x 242

Weight (lb/kg):

3 / 1.4

DC Rectifiers

Cordex 650W Rectifier Module

Electrical

Input Voltage (120Vac Model)

Operating: Extended: Power Output:

90 to 140Vac (output power 650W) 90 to 70Vac (derated output power) 650W at nominal 120Vac

Input Voltage (Universal 100 to 240Vac Model)

Operating: Extended: Operating:

176 to 320Vac (output power 650W) 176 to 90Vac (derated output power) 100 to 140Vac (output power 500W)

Power Output:

650W at nominal 208 to 240Vac and 500W at nominal 120Vac

Specifications Input Frequency: Power Factor: THD: Efficiency: Output Voltage: Output Current:
Load Regulation:

45 to 70Hz >99% <5% >91% (1% loss for 120Vac model) 42 to 58Vdc 12A @ 54Vdc (13.5A max)
Static <±0.5%, Dynamic <±2% for 50 to 100% load step, 2ms recovery time

Line Regulation:

Static <±0.1%. Dynamic <±1% for any change within rated limits

Mechanical

Dimensions H x W x D (in/mm): 3.4 x 2.8 x 9.5 / 88.4 x 71.6 x 242

Weight (lb/kg):

3 / 1.4

CXRC 24-400W

Noise Wide Band Noise: Psophometric Noise: Features Indicators: Cooling:
Adjustments (via CXCI Controller):
Protection:
Environment Operation Temperature: Storage Temperature: Humidity: Elevation: Heat Dissipation: Standards Safety: EMC:
Emissions:
Immunity:

<30mVrms, <150mVpk to pk
<1mV
AC mains OK--green LED Module alarm--red LED
Natural convection
Float and equalize voltage Battery test voltage High and low voltage alarms High voltage shutdown Current limit Start delay time Slope %
Current limit/short circuit Input/output fuses Output high voltage shutdown Output power limiting Thermal foldback/shutdown Input transient AC low line foldback/shutdown AC high voltage shutdown
-40 to 50°C / -40 to 122°F (power derated up to 70°C / 158°F)
-40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 3000m / -1640 to 9840ft <94BTU per hour
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia) EN 61000-3-2 EN 61000-3-3
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3

CordexTM 400W/650W
Rectifier Shelf Systems
> Integrated DC distribution with optional LVD > Integrated 24 and 48Vdc shelf
power systems up to 2.6kW > Bulk 24 and 48Vdc power
systems up to 3.2kW > 19" and 23" rack mounting solutions > Designed for CSA, UL, CE, FCC
and C-tick standards

Cordex 48V-2.6kW Shelf System Cordex 24V-1.6kW Shelf System

Cordex 24-400W Rectifier Shelves

Rectifiers

Controllers

Distribution

Cordex 48-650W Rectifier Shelves

Rectifiers

Controllers

Distribution

19/23" 2RU

4 x CXRC

Universal Mount 24-400W

1 x CXCI

(4) AM bullet type breakers

19/23" 2RU

4 x CXRC

Universal Mount 48-650W

1 x CXCI

(4) AM bullet type breakers

19/23" 2RU

5 x CXRC

Universal Mount 24-400W

1 x CXCI

Bulk power for external distribution panel

19/23" 2RU

5 x CXRC

Universal Mount 48-650W

1 x CXCI

Bulk power for external distribution panel

19" and 23" Shelf Systems

23" 2RU Front Access

4 x CXRC 48-650W

1 x CXCI

(4) AM bullet (10) GMT fuse

11

DC Rectifiers

650W Cordex 2.6kW shelf power system with CXCI controller and bullet breaker distribution
650W Cordex 3.2kW bulk power system with CXCI controller. Optional LVD shunt with battery breaker
650W Cordex 2.6kW front access shelf power system with CXCI controller and bullet/ fuse distribution
650W Cordex 1.9kW front access shelf power system with CXCI controller and plug-in/fuse distribution
400W Cordex 1.6kW shelf power system with CXCI controller and bullet breaker distribution
400W Cordex 2kW bulk power system with CXCI controller

19" 2RU Front Access

3 x CXRC 48-650W

1 x CXCI

(4) AM plug-in (10) GMT fuse

19" Shelf Systems

Mechanical

Dimensions H x W x D (in/mm): 3.5 x 17.1 x 11.9 / 89 x 435 x 302

Weight (lb/kg):

15.5 / 6.9

Note: Shelf P/Ns do not include modules or distribution breakers Weights do not include modules Dimensions do not include mounting bracket

23" Front Access Shelf Systems

Mechanical

Dimensions H x W x D (in/mm): 3.5 x 21.4 x 12 / 88.9 x 543.6 x 304.8

Weight (lb/kg):

37 / 16.8 (fully equipped with four rectifiers)

Note: Shelf P/Ns do not include modules or distribution breakers Weights do not include modules Dimensions do not include mounting bracket

Communication Ports CAN: Ethernet: Environment Operating Temperature: Storage Temperature: Humidity: Elevation: Cooling:

Interface to control rectifiers. Smart peripherals 10/100 Base-T for TCIP/SNMP features
-40 to 50°C / -40 to 122°F -40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 3000m / -1640 to 9840ft Natural or forced convection, vertical airflow

Cordex HPTM 1.2kW
Modular Switched Mode Rectifier
> 93% efficiency for increased Op-Ex savings and reduced carbon footprint
> High temperature operation for installation in harsh outdoor environments
> 1RU x 2RU footprint for flexible and multiple mounting options > High power density (21.8W/in3) yields more space
for revenue generating equipment > Wide AC input range for a variety of global installation requirements

Cordex HP 1.2kW

DC Rectifiers
Efficiency % (normal operating conditions)

Cordex HP 1.2kW

Electrical

Features

Nominal Input Voltage:

176 to 276Vac

Input Voltage Extended (Low): 90 to 175Vac (derated output power)

Input Voltage Extended (High): 277 to 300Vac (derated power factor)

Input Current Nominal:

7.5A max

Input Current 90 to 132Vac: 6A max

Input Frequency:

45 to 70Hz

Power Factor:

>99%

12

THD:

Efficiency:

<5% @ nominal input voltage
>93% 50 to 100% load (nominal AC input) >90% 40 to 100% load (120Vac input)

Output Voltage:

42 to 58Vdc

Output Power (Nominal AC Input):

1200W

Output Power 110 to 132Vac:

600W (derated linearly to 491W @ 90Vac)

Output Current (Nominal AC Input):

22.2A @ 54V (25A max @ 48V)

Indicators: Cooling: Adjustments (Via CXC Controller):
Protection:
Standards

AC mains OK -- green LED DC output OK -- green LED Module alarm -- red LED
Fan cooled
Float and equalize voltage Battery test voltage High and low voltage alarms High voltage shutdown Current limit Start delay time Slope %
Current limit/short circuit Input/output fuses Output high voltage shutdown Output power limiting Thermal foldback/shutdown Input transient AC low line foldback/shutdown AC high voltage shutdown

Output Current 110 to 132Vac:
Load Regulation:
Line Regulation:
Noise Web Band: Psophometric: Mechanical Dimensions H x W x D (in/mm): Weight (lb/kg):

12.5A max (derated linearly to 10.2A @ 90Vac) Static <±0.5%, Dynamic <±1% for 40 to 90 to
40% lead step, 2ms recovery time Static <±0.1%, Dynamic <±1% for any change
within rated limits
<30mVrms, <150mV pk to pk <2mV
1.63 x 3.34 x 10.11 / 41.4 x 84.8 x 256.8 2.7 / 1.2

Safety: EMC:
Emissions:
Immunity:

CSA C22.2 No 60950-1-03 CE marked
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia) EN 61000-3-2 EN 61000-3-3
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3

Environment
Operation Temperature:
Storage Temperature: Humidity: Elevation: Heat Dissipation:

-40 to 65°C / -40 to 149°F (power derated up to 80°C / 176°F)
-40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 3000m / -1640 to 9840ft <308BTU per hour

NEBS / Telcordia:

GR-1089-CORE GR-63-CORE

Cordex HP 1.2kW Efficiency
94

93

93.53%

92

91

20

30

40

50

60

70

80

90

100

% Rectifier Load

Cordex HPTM 1.2kW
Modular Rectifier Shelf Systems
> Multiple 48V configurations up to 125A for various 48Vdc applications
> High Efficiency design for increased Op-Ex savings > High temperature rated fan-cooled design
for harsh outdoor installations > Wide range AC input and IEC line
cords for multiple AC services > Front access options for space restricted enclosures

CXRF-HP 48-1.2kW

Cordex 48-1.2kW Rectifier Shelves

2RU Front Access Shelf System

Rectifiers

Controllers

Distribution

Mechanical

19/23" 2RU Universal Mount (Front Access)

4 x CXRF HP 48-1.2kW

1 x CXCM1

(4) AM plug-in (10) GMT fuse

Dimensions H x W x D (in/mm): Shelf Weight (lb/kg): Rectifier Weight (lb/kg):

3.5 x 17.3 x 12 / 88 x 439.5 x 305 10.03 / 4.55 2.72 / 1.23

19/23" 1RU Universal Mount (Bulk Power w/ CXC)

4 x CXRF HP 48-1.2kW

1 x CXCM1

Bulk power for external distribution

Note: Rectifier front handle adds additional 0.49 / 12.5 depth
1RU Rear Access Shelf System
Mechanical

Dimensions H x W x D (in/mm): 1.7 x 17.3 x 12 / 44 x 439.5 x 305

13

19/23" 1RU Universal Mount (Bulk Power)

5 x CXRF HP 48-1.2kW

19" and 23" Shelf Systems

N/A (External)

Bulk power for external distribution

Shelf Weight (lb/kg):

6.6 / 3

Rectifier Weight (lb/kg):

2.72 / 1.23

Note: Rectifier front handle adds additional 0.49 / 12.5 depth. Shelf P/Ns do not include modules or distribution breakers. Dimensions do not include mounting bracket

Communication Ports

19/23" 2RU universal mount (Front Access)

CAN: Ethernet: Environment

Interface to control rectifiers, Smart peripherals 10/100 Base-T for TCIP/SNMP features

DC Rectifiers

Operating Temperature (Standard):

-40 to 65°C / -40 to 149°F

19/23" 1RU universal mount (Bulk Power w/ CXC)
19/23" 1RU universal mount (Bulk Power)

Operating Temperature (Extended):
Storage Temperature: Humidity: Elevation: Cooling: Components 877-690-19: 877-671-19: 747-622-20-000: 567-837-19: 036-201-20-000:

-40 to 80°C / -40 to 176°F (derated output power) -40 to 80°C / -40 to 176°F 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft Fan cooled (front to rear)
5-15P (120V) line cord, 2.m Universal lmc cord, ying leads, 3.5m Blank plate Kydex rear cover (1RU only) CXCM1 I/O terminal black kit (1RU only)

CordexTM 1.8kW
Modular Switched Mode Rectifier and Shelf
> Available in 37.5A @ 48Vdc > High power density, fan cooled > Universal, wide range AC input > 91% efficiency and power factor correction > Hot swappable, 2RU ultra compact design

Cordex 48-1.8kW

Cordex 1.8kW

Electrical

Environment

Nominal Input Voltage:

208 to 277Vac

Operating Temperature:

-40 to 65°C / -40 to 149°F

Operating Input Voltage:

176 to 312Vac

Storage Temperature:

-40 to 85°C / -40 to 185°F

Extended Input Voltage:

176 to 90Vac (derated power)

Humidity:

0 to 95% non-condensing

Input Frequency:

45 to 66Hz

Elevation:

-500 to 2800m / -1640 to 9186ft

Power Output:

Power Factor:

14

THD:

Efficiency:

Output Voltage:

Output Current:

Load Regulation: Line Regulation:

1800W continuous @ nominal l/P 1150W (115 to135Vac) (derated linearly to 900W @ 90Vac)
>0.99 (50 to 100% load) <5% >91% 42 to 60Vdc
37.5A @ 48Vdc (nominal l/P) 24A @ 48Vdc (115 to 135Vac) (derated linearly to 18.75W @ 90Vac)
<±0.5% (static) <±0.1% (static)

Heat Dissipation: Standards Safety: EMC:
Emissions:

<608BTU per hour
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia) EN 61000-3-2 EN 61000-3-3

DC Rectifiers

Transient Response: Noise Voice Band:
Wide Band:

±2% for 50 to 100% load step, 2ms recovery time
<32dBrnC <30mVrms (10kHz to 10MHz), <150mVpk to pk (10kHz to 100MHz)

Immunity:

EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3

Psophometric: Acoustic:

<1mV <60dBA @ 1m / 3ft

19" and 23" Shelf Systems

Mechanical

Mechanical

Dimensions H x W x D (in/mm): 3.3 x 3.9 x 9.3 / 84 x 100 x 235

Dimensions H x W x D (in/mm): 3.5 x 17.2 x 12.2 / 89 x 438 x 310

Weight (lb/kg):

6.2 / 2.8

Weight (lb/kg):

19 / 8.5

Features Indicators: Controls:

AC mains OK--green LED Module OK--green LED Module fail--red LED
CAN interface to CXC

Mounting:

19" flush or center mount, 23" center mount only

23" Shelf Systems

Mechanical

Dimensions H x W x D (in/mm): 3.5 x 21.3 x 12.2 / 89 x 541 x 310

Weight (lb/kg):

22 / 10

Adjustments (via CXC Controller):

Float voltage, Equalize voltage, High voltage alarm, Low voltage alarm, High voltage shutdown, Current limit, Slope, Start delay timers

Mounting: Connections

23" flush or center mount

Protection:

Current limit/short circuit, Start delay, Input/ output fuses, Output high voltage shutdown, Power limiting, Thermal foldback/shutdown, Input transient, AC low line foldback/shutdown, AC high voltage shutdown

Input: Output: Chassis Ground: CAN Communication:

Terminal blocks, mini-fit connectors (23" only) Bus adapters with " studs on 1" center holes ¼" studs on " centers RJ12 offset

Typical 7.2kW 23" Shelf with CXCM2

Cordex HPTM 2kW
Modular Switched Mode Rectifier

> 94% efficiency for increased Op-Ex savings and reduced carbon footprint
> High temperature operation for installation in harsh outdoor environments
> Backwards compatible solution with Cordex 1.8kW rectifier shelves and power solutions
> Wide AC input operating range that satisfy a variety of global installation requirements

Cordex HP 2kW

Cordex HP 2kW
Electrical Nominal Input Voltage: Input Operating Voltage: Input Extended Voltage: Input Frequency:
Power:
Power Factor: THD: Efficiency: Output Voltage:
Output Current:
Load Regulation: Line Regulation:
Transient Response:
Noise
Web Band:
Voice Band: Psophometric: Acoustic: Mechanical Dimensions H x W x D (in/mm): Weight (lb/kg): Environment Standard Temperature:
Extended Temperature:
Storage Temperature: Humidity: Elevation: Heat Dissipation:

208 to 277Vac 187 to 320Vac 187 to 90Vac (derated power) 45 to 70Hz 2000W continuous/module (~1250W Output at 120Vac Input) >0.99 (50 to 100% load) <5% 94% 42 to 60Vdc 37A @ 54Vdc (41.6A max. 48V) (~26A @ 48Vdc at 120Vac Input) <±0.5% (static) <±0.1% (static) ±2% for 40 to 90% load step, 10ms recovery time
<30mV RMS (10kHz to 10MHz) <150mV pk to pk (10kHz to 100MHz) <38dBrnC <2mV <55dBa @ 1m / 3ft
3.3 x 3.94 x 9.25 / 84 x 100 x 235
6.6 / 3
-40 to 55°C / -40 to 131°F -40 to 75°C / -40 to 167°F (derated power) ~1800W @ 65°C / 149°F -40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft <437BTU per hour

Features

Indicators:
Controls: Adjustments (Via CXC Controller):

AC mains OK -- green LED DC output OK -- green LED Module alarm -- red LED
CAN interface to CXC controller
Float and equalize voltage, High and low voltage alarms, High voltage shutdown, Current limit, Start delay time, Slope %

Protection:

Current limit/short circuit, Start delay, Input/

output fuses, Output high voltage shutdown,

15

Power limiting, Thermal foldback/shutdown,

Input transient, AC low line foldback/shutdown,

AC high voltage shutdown

Standards

DC Rectifiers

Safety: EMC:
Emissions:

CSA C22.2 No 60950-1-03, UL 60950-1 1st Edition, CE marked
ETSI 300 386
CFR47 (FCC) Part 15 Class B, ICES-03 Class B EN55022 (CISPR 22) Class B, C-Tick (Australia) EN 61000-3-2, EN 61000-3-3

Immunity:

EN 61000-4-2, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11, ANSI/IEEE C62.41 Cat B3

19" / 23" Shelf

Mechanical

Dimensions H x W x D (in/mm): 3.4 x 17.4 x 12 / 86.3 x 442 x 304.8

Weight (lb/kg):

14.7 / 6.7

Mounting (4 Modules):

Fits 19" rack flush/center mount Fits 23" rack center mount only

23" Shelf

Mechanical

Dimensions H x W x D (in/mm): Weight (lb/kg): Mounting (5 Modules):

3.4 x 20.8 x 12 / 86.3 x 530 x 304.8 18.1 / 8.2 Fits 23" racks only flush/center mount

Connections Input: Output:
Chassis Ground:
CAN Communications:

Molex mini-fit type Bus adapters with " studs on 1" centers
Compression lug 6 to 16mm2 (10 to 6AWG)
RJ 12 offset

Typical 10kW 23" Shelf with CXCI

Typical 8kW 23"Shelf with CXCM2

CordexTM 3.6kW
Modular Switched Mode Rectifier
> Available in 130A @ 24Vdc or 75A @ 48Vdc > High power density, over 21kW per 23" shelf > Power limiting and wide range AC input > High efficiency and power factor correction > Hot swappable, 4RU ultra compact design

Cordex 48-3.6kW

Cordex 3.6kW

Electrical

Environment

Nominal Input Voltage:

208 to 277Vac

Operating Temperature:

-40 to 65°C / -40 to 149°F

Operating Input Voltage: Extended Input Voltage: Input Frequency: Power Output: Power Factor:

176 to 312Vac 176 to 90Vac (derated power) 45 to 66Hz 3600W continuous/module >0.99 (50 to 100% load)

Storage Temperature: Humidity: Elevation: Heat dissipation:

-40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 4000m / -1640 to 13120ft <1176BTU per hour

THD:

<5%

Standards

16

Efficiency:

Output Voltage:

Float Voltage:

>92% 42 to 60Vdc 48 to 58Vdc

Safety:

Output Current: Load Regulation:

66A @ 54Vdc (75A max 48V) <±0.5% (static)

EMC:

Line Regulation:

<±0.1% (static)

Transient Response: Noise

±2% for 50 to 100% load step, 2ms recovery time

Emissions:

Voice Band:

<32dBrnC

CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia) EN 61000-3-2 EN 61000-3-3

DC Rectifiers

Wide Band:

<30mVrms (10kHz to 10MHz), <150mVpk to pk (10kHz to 100MHz)

Psophometric: Acoustic:

<1mV <60dBA @ 1m / 3ft

Mechanical

Dimensions H x W x D (in/mm): 6.3 x 3.4 x 11.8 / 160 x 87 x 300

Weight (lb/kg):

10 / 4.6

Features

Immunity: NEBS:

EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3
GR-1089 CORE GR-69 CORE

Indicators:

AC mains OK--green LED Module OK--green LED Module fail--red LED

Controls:

CAN interface to CXC

Adjustments (via CXC Controller):

Float voltage, Equalize voltage, High/Low voltage alarm, High voltage shutdown, Current limit, Slope, Start delay

Protection:

Current limit/short circuit, Start delay, Input/ output fuses, Output high voltage shutdown, Power limiting, Thermal foldback/shutdown, Input transient, AC low line foldback/shutdown

Cordex HPTM 4kW
Modular Switched Mode Rectifier
> Near 95% efficiency for increased OPEX savings and reduced carbon footprint > High temperature tolerance for installation in harsh outdoor environments > Backwards compatibility with Cordex 3.6kW rectifier shelves
and power solutions provide cost effective upgrade path > Wide AC input operating range that satisfies a
variety of global installation requirements

Cordex HP 4kW
Electrical Nominal Input Voltage: Operating Input Voltage: Extended Input Voltage: Input Frequency: Power Output: Power Factor: THD: Efficiency: Output Voltage: Flood Voltage: Output Current: Load Regulation: Line Regulation: Transient Response: Noise Voice Band:

208 to 277Vac 187 to 320Vac 187 to 95Vac (derated power) 45 to 66Hz 4000W continuous/module >0.99 (50 to 100% load) >7% 94.9% peak @ 240Vac 44 to 60Vdc 48 to 58Vdc 74A @ 54Vdc (85A max 48V) <±0.5% (static) <±0.1% (static) ±3% for 40 to 90% load step
<38dBrnC

Wide Band:

<20mVrms (10kHz to 10MHz), <100mVpk to pk (10kHz to 100MHz)

Psophometric:

<2mV

Acoustic:

<60dBA @ 1m / 3ft (at 30°C / 86°F)

Mechanical

Dimensions H x W x D (in/mm): 6.3 x 3.4 x 11.8 / 160 x 87 x 300

Weight (lb/kg):

11 / 5

Features

Indicators:

AC mains OK--green LED DC Output OK--green LED Module fail--red LED

Controls:

CAN interface to CXC Controller

Adjustments (via CXC Controller):

Float voltage Equalize voltage High/Low voltage alarm High voltage shutdown Current limit Slope Start delay timers

Protection:

Current limit/short circuit Start delay Input/output fuses Output high voltage shutdown Power limiting Thermal foldback/shutdown Input transient AC low line foldback/shutdown AC high voltage shutdown

CordexHP 4kW

Environment

Standard Operating Temperature:

-40 to 55°C / -40 to 131°F

Extended Operating Temperature:

-40 to 75°C / -40 to 167°F (derated power) ~ 3600W @ 65°C / 149°F

Storage Temperature:

-40 to 85°C / -40 to 185°F

Humidity:

0 to 95% non-condensing

Elevation:

-500 to 4000m / -1640 to 13120ft

Heat dissipation:

<1190BTU per hour

17

Standards

Safety:

CSA C22.2 No 60950-1-03 UL 60950-1 CE marked IEC/EN 60950-1

EMC:

ETSI 300 386

Emissions:

CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B EN 61000-3-2 EN 61000-3-3

DC Rectifiers

Immunity:

EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3

19" and 23" Shelf (5 Modules)

Mechanical

Dimensions H x W x D (in/mm): 6.9 x 17.4 x 15.3 / 177 x 442 x 389

Weight (lb/kg):

19 / 8.5

Mounting:

19" flush or center mount, 23" center mount only

23" Shelf (6 Modules)

Mechanical

Dimensions H x W x D (in/mm): 6.9 x 20.8 x 15.3 / 177 x 530 x 389

Weight (lb/kg):

21 / 9.5

Mounting:

23" flush or center mount

Connections Input: Output: Chassis Ground: CAN Communication:

Box type terminal block, 6 to 16mm2 (10 to 6AWG) Bus adapters with " studs on 1" centers Compression lug, 6 to 16mm2 (10 to 6AWG) RJ12 offset

CXPS 48-1.2-225
Standard 48Vdc Power System
> Integrated 48V, 225A system package with front access distribution
> High efficiency design for increased Op-Ex savings > High temperature rated fan-cooled design
for harsh outdoor installations > Wide range AC input and IEC line cords for multiple AC service > Flexible ordering options including configurations
with racks and battery trays

CXPS 48-1.2-225

CXPS 48-1.2-225

Electrical

Mechanical

Input Operating Voltage: Extended Voltage (High): Extended Voltage (Low):
Current:

208/220/240Vac (Continuous operation 90 to 300Vac) 277 to 300Vac (derated power factor) 90 to 176Vac (derated output power)
7.5A max per module (176 to 300Vac) 6A max per module (90 to 176Vac)

Dimensions H x W x D (in/mm):
System Weight (lb/kg): Rectifier Weight (lb/kg): Mounting:

8.7 x 17.2 x 14.8 / 222 x 438 x 376 (-000 configuration - excludes mounting brackets, rear cover, and module handle)
47/21.3 6.2/2.8 each 19/23" universal mount (center or flush)

Frequency:

18

Efficiency:

Power Factor:

45 to 66Hz >93% (50 to 100% load @ nominal voltage) >.99

Output

Current

System: Rectifier:

225A max @ nominal I/P 112.5A @ 115Vac I/P
25A @ 48Vdc (nominal I/P) 12.5A @ 48Vdc (115Vac) (Subject to derating below 110Vac)

Connections Load Breaker: Battery Breaker: Return Bar:
Alarm:
CXCM1 Input: Access: Environment

14x sets, ¼"-20 studs on " centers 4x sets, ¼"-20 studs on " centers 18x sets, ¼" holes on " centers
Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
25-pin D-Sub cable Front access after installation

DC Rectifiers

Power

System: Rectifier:

Features

10800W max @ nominal I/P 5400W @ 115Vac I/P
1200W max @ nominal I/P 600W @ 115Vac (Subject to derating below 110Vac)

Operating Temperature: Humidity: Elevation:

-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output
0 to 95% non-condensing
-500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with temperature derated to -40°C / 104°F output

Configurations 053-691-20-000: 053-619-20-040: 053-691-20-031:
Rectifier:
Distribution:

Base system with 19/23" universal mounting
System mounted in 23", 44RU Z4 rack with 2x battery trays for 2x 48V strings
System mounted in 19", 44RU Z4 rack with 3x battery trays for 3x 48V strings
Up to 9x HP 48V-1.2kW rectifier positions
14x load breaker positions (mid-trip, plug-in style) 4x battery breaker positions (series-trip, plug-in) Low voltage disconnect Shunt

Components 877-690-19: 877-671-19: 747-622-20-000: 470-347-10: 747-503-20: 747-504-20:

5-15P (120V) line cord, 2.5m Universal lmc cord, flying leads, 3.5m Blank plate 100A battery breaker 150A battery breaker 250A battery breaker

Controller:

CXCM1 Modular Controller

CXPS 48-1.8-i and CXPS 48-1.8-M2
Standard 48Vdc Power System

> Integrated 48V, 150-262A system package with front access distribution
> High temperature rated fan cooled design for harsh outdoor installations
> Wide range AC input for multiple worldwide AC services > Modular controller with touch screen display for full
local control over system (CXPS 48-1.8-M2 only) > Flexible ordering options including configurations with
racks and battery trays

CXPS 48-1.8-M2

CXPS 48-1.8-i and CXPS 48-1.8-M2

Electrical

CXPS 48-1.8-i

CXPS 48-1.8-M2

Mechanical

CXPS 48-1.8-i

CXPS 48-1.8-M2

Input Nominal Input Voltage: Input Current:

176 to 312 Vac, 90 to 176Vac (derated O/P power) 14.6A @ 240Vac, 12.2A @ 120Vac (per module)

Dimensions H x W x D (in/mm):

8.7 x 17.2 x 12.2 / 222 x 438 x 310 (-000 configuration - excludes mounting brackets, rear cover, and module handle)

Input Frequency:

45 to 66Hz

45 to 66Hz

System Weight (lb/kg): 42 / 19

62 / 28

Efficiency:

>91% (50 to 100% load @ norminal voltage)

Rectifier Weight (lb/kg): 6.2 / 2.8 each

6.2 / 2.8 each

Input Power Factor:

>.99

>.99

Mounting:

19/23" universal mount (center or flush)

Output

Connections

Load Breaker:

14x sets, ¼"-20 studs on " centers

System:

150A max @ nominal I/P 262.5A max @ nominal I/P 96A max @ 120Vac I/P 96A max @ 120Vac I/P

Battery Breaker:

4x sets, ¼"-20 studs on " centers

19

Current

Rectifier:

37.5A @ 48Vdc (nominal I/P) 24A @48Vdc (115 to 135Vac) (derated linearly to 18.75A @ 90Vac)

Return Bar: Rectifier Input:

18x sets, ¼" holes on " centers
HOT: 2x sets, " holes on 1" centers RTN: 2x sets, " holes on 1" centers

System:

7200W max @ nominal I/P 12600W max @ nominal I/P

4600W @ 120Vac I/P

8050W @ 120Vac I/P

Alarm: CSCI Input:

Screw terminal 1.31mm2 to 0.128mm2

25-pin D-Sub cable

-

DC Rectifiers

Power

Rectifier:

Features Configurations

1800W max @ nominal I/P 1150W (115 to 135Vac)
(derated linearly to 900W @ 90Vac)

CXCM2 Input:

-

Access:

Environment

Operating Temperature:

3x DB-style cable connections Front access after installation
-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output

Base System with 19/23" Universal Mounting:

053-990-20-000

053-991-20-000

System Mounted in 23", 44RU Z4 Rack with 2x Battery Trays for 2x 48V Strings:

053-990-20-040

053-991-20-040

System Mounted in 19", 44RU Z4 rack with 3x Battery Trays for 3x 48V Strings:
Rectifier:

053-990-20-031

053-991-20-031

Up to 4x 48V-1.8kW rectifier positions

Humidity:
Elevation:
Components 058-156-20: 058-157-20: 470-347-10: 747-503-20: 747-504-20:

0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with derated output
23" battery tray expansion kit (for use with -040 configuration) 19" battery tray expansion kit (for use with -031 configuration) 100A battery breaker 150A battery breaker 250A battery breaker

Distribution:

14x load breaker positions (mid-trip, plug-in style) 4x battery breaker positions (series-trip, plug-in) Low voltage disconnect Shunt

Controller:

CXCI integrated controller CXCM2 integrated controller

CXPS 48-1.8-i

CXPS 48-1T
48V 375 to 825A Power Systems
> 48Vdc systems using high density 3.6kW rectifiers > Front access DC connections > CXCM4 advanced modular controller > Flexible integrated rack options > Integrated system shunt and LVD

CXPS 48V 375A

CXPS 48-1T

Configurations

CXPS 48-1T (with LVD)

053-392-20-000:

Base system with 23" mounting

053-392-20-010:

System mounted in 22RU (½ height) battery mount rack

053-392-20-020:

System mounted in 44RU Zone 4 seismic rack

053-392-20-030:

System mounted in 44RU Zone 4 rack with 3x battery trays for 3x 48V strings

Rectifier:

Up to 5x 48V to 3.6kW rectifier positions

Distribution:

20

Controller:

18x AM plug-in breaker positions, 10x GMT type fuse positions, Shunt, Low voltage disconnect
CXCM4 modular controller

CXPS 48-1T_b (no LVD)

053-692-20-000:

Base system with 23" mounting

053-692-20-010:

System mounted in 44RU Zone 4 seismic rack

053-692-20-020:

System mounted in 44RU Zone 4 rack with 3x battery trays for 3x 48V strings

DC Rectifiers

Rectifier:

Up to 5x 48V to 3.6kW rectifier positions

Distribution:

24x AM plug-in breaker positions, 10x GMT type fuse positions, Shunt, Low voltage disconnect

Controller:

CXCM4 modular controller

Electrical

Input Voltage:

176 to 320Vac

Current:

16.8A @ 240Vac nominal (per rectifier module)

Frequency:

45 to 66Hz

Power Factor:

>0.99

Output Voltage:

42 to 60Vdc

Current:

System: 375A (expandable to 600A with additional CXRF shelf), Rectifier: 75A @ 48Vdc

Power:

System: 18kW (expandable to 28.8kW with additional CXRF shelf), Rectifier: 3600W max

Environment

Temperature: Humidity: Elevation:

-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output
0 to 95% non-condensing
-500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with derated output

Mechanical Dimensions H x W x D (in/mm): Weight (lb/kg): Mounting: Connections Load Breaker:
GMT Fuses:
Battery Terminations: Rectifier Input: Alarm Connections:
Access: Related Components 010-567-20: 058-716-20

19.25 x 23 x 18.8 / 488 x 584 x 477 (-000 configuration - excludes mounting brackets) 110 / 49.8 (no rectifiers or breakers included) 23" center mount
Hot: ¼" -20 studs on " centers Return: ¼" holes on " centers Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) " holes on 1" centers 4x sets per polarity " holes on 1" centers Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) Cable: top or bottom User: front access after installation
Cordex 48V-3.6kW rectifier Cordex rectifier CXRF 48-3.6kW expansion shelf kit

CXPS 48-1T Internal Distribution

CXPS 48-2T
48V 375 to 825A Power Systems
> 48Vdc systems using high density 3.6kW rectifiers > Front access DC connections > CXCM4 advanced modular controller > Flexible integrated rack options > Integrated system shunt and LVD

CXPS 48V 825A

CXPS 48-2T
Configurations CXPS 48-2T (with LVD) 053-393-20-000: 053-393-20-010: 053-393-20-020: 053-393-20-030: Rectifier: Distribution: Controller: CXPS 48-2T_b (no LVD) 053-693-20-000: 053-693-20-020: 053-693-20-030: Rectifier: Distribution: Controller: Electrical Input Voltage: Current: Frequency: Power Factor: Output Voltage:
Current:
Power:
Environment
Temperature:
Humidity:
Elevation:

Base system with 23" mounting System mounted in 22RU (½ height) battery mount rack System mounted in 44RU Zone 4 seismic rack System mounted in 44RU Zone 4 rack with 3x battery trays for 3x 48V strings Up to 11x 48V-3.6kW rectifier positions 38x AM plug-in breaker positions, 10x GMT type fuse positions, Shunt, Low voltage disconnect CXCM4 modular controller
Base system with 23" mounting System mounted in 44RU Zone 4 seismic rack System mounted in 44RU Zone 4 rack with 3x battery trays for 3x 48V strings Up to 11x 48V-3.6kW rectifier positions 48x AM plug-in breaker positions, 10x GMT type fuse positions, Shunt CXCM4 modular controller
176 to 320Vac 16.8A @ 240Vac nominal (per rectifier module) 45 to 66Hz >0.99 42 to 60Vdc System: 825A (expandable to 1200A with additional CXRF shelf), Rectifier: 75A @ 48Vdc
System: 39.6kW (expandable to 57.6kW with additional CXRF shelf), Rectifier: 3600W max
-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with derated output

Mechanical

Dimensions H x W x D (in/mm):

29.7 x 23 x 18.8 / 755 x 584 x 477 (-000 configuration - excludes mounting brackets)

Weight (lb/kg): Mounting:

155 / 70.3 (no rectifiers or breakers included) 23" center mount

Connections

Load Breaker:

Hot: ¼" -20 studs on " centers Return: ¼" holes on " centers

GMT Fuses:

Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)

Battery Terminations:

" holes on 1" centers 4x sets per polarity

21

Rectifier Input: Alarm Connections:

" holes on 1" centers
Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)

Access:

Cable: top or bottom User: front access after installation

Related Components

010-567-20: 058-716-20

Cordex 48V-3.6kW rectifier Cordex rectifier CXRF 48-3.6kW expansion shelf kit

DC Power Systems

CXPS 48-2T Internal Distribution

CordexTM System
48V 2000A Power Systems
> Up to 2000A system > Cordex modular rectifiers > User-configurable, modular distribution tiers > Intelligent system control and communication

Cordex System
Electrical
AC Input:

Rectifier Voltage:

22

Output Voltage:

Output Current:

Power:

Max. Bus Capacity:

DC Power Systems

Mechanical
Dimensions H x W x D (in/mm):

Weight (lb/kg):

Environment Temperature: Humidity: Elevation:

Single Phase, 208 to 277Vac Dual 3 Phase, 208 to 240Vac (w/o neutral) Dual 3 Phase, 360 to 480Vac (with neutral) 208 to 277Vac 45 to 70Hz 42 to 58Vdc (Cordex rectifiers) 66A @ 54Vdc per 3.6kW rectifier 21.6kW per rectifier shelf 2000A system bus 600A max. per distribution tier
84 x 28.1 x 19 / 2133 x 714 x 483
Approx. 902 / 410 with 4 tier distribution center and 5 fully loaded Cordex shelves
0 to 50°C / 32 to 122°F 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft

Cordex 48V 2000A

Related Components Rectifiers:

Choose up to six Cordex 48V rectifiers per shelf
Choose up to six field-expandable shelves per system

Low Voltage Disconnect:
Distribution: AM-type/TPS Bullet Style: GJ Breaker: Cordex Controller: Battery Options:

LVD optional 48Vdc/600A (one per distribution tier)
Choose distribution center for 1 tier, 2 tier or 4 tier Terminations (breaker options for tiers 1 through 4) 2 x ¼-20 studs on " centers per pole
2 x -16 studs on 1" centers per pole; i.e., 2-pole breaker will have two sets
The system's monitoring and control center
2V Battery cell monitor (1 string) 12V Battery cell monitor (4 strings) Battery tray with breaker (12V blocks)

Tier 1 Can Be Equipped With:

24-position AM-type bullet style breakers* 20-position bullet style breakers* with LVD

Tiers 2 to 4 Can Be Equipped With:

24-position AM-type bullet style breakers* 20-position bullet style breakers* with LVD 3-position GJ (with or without LVD)

* Bullets style TPS fuse holder and GMT fuse blocks available

3 positions GJ breaker tier rated at 600Amps

3 positions GJ breaker tier with LVD rated at 600Amps

24 position bullet breaker tier rated at 600Amps

20 position bullet breaker tier with LVD rated at 600Amps

CordexTM System
48V 8000A Power Systems
> 8000A Capacity > Designed for MSCs, COs and
Cable Headend facilities > Cordex 3.6kW modular rectifiers > Circuit breaker and TPL fuse options > Internal bay-to-bay copper busswork > Expandable power and distribution bays > Optional overhead buss duct system

Cordex 48V 4000A

Cordex System

Electrical

Environment

AC Input: Rectifier Voltage: Max. Bus Capacity:

Single Phase, 208 to 277Vac Dual 3 Phase, 208 to 240Vac (w/o neutral) Dual 3 Phase, 360 to 480Vac (with neutral)
208 to 277Vac
10000A system 2000A per bay

Temperature:

0 to 50°C / 32 to 122°F

Humidity:

0 to 95% non-condensing

Elevation:

-500 to 2800m / -1640 to 9186ft

System Level Alarms/

Alarms/control parameters are user-programmable

Controls:

through built-in digital supervisory unit

23

DC Power Systems

Distribution Fuses
TPL: GJ/GJ1P: Output Termination TPL Fuse:
GJ Breaker:

2 position, 61 to 800A breakers 1 pole up to 225A 2 pole 250 to 400A 3 pole 450 to 700A
2 hole ½" dia. on 1¾" centers or 2 hole " dia. on 1" centers
1 pole and 2 pole are " to 16, 3 pole are 2 hole, ½" dia. on 1¾" centers or " dia. on 1" centers

Indicators:

LCD with touch screen System OK -- green LED System minor alarm -- yellow LED System major alarm -- red LED

Alarm Connections: Load Disconnect:

0.34 to 2.5mm2 (14 to 22AWG) 48Vdc/1200A x N mounted on load side (optional)

Smart Peripheral Modules

Shunt Mulitplexer: Battery Cell Monitor: Battery Cell Monitor:

16 shunts per module 1 string, 2V cells per module 4 strings, 12V blocks per module

Ground Bar:

Overhead buss ground, 15 sets of 2 hole ½" dia. on 1¾" centers (basic system)

Mechanical

Enclosure:

1.095mm (14 gauge) steel

Mounting:

Standard 23" relay rack (flush rack mount) in box bay

Dimensions H x W x D (in/mm): 84 x 28 x 28 / 2133.6 x 711.2 x 711.2

Weight (lb/kg):

Approx. 600 / 272 per bay (no rectifiers)

CXPS 24­48-i
24 to 48V DC-DC Converter System

> Integrated 8kW capacity 24-48Vdc converter system with front access distribution
> Support for small to medium 48Vdc loads from legacy 24V power system
> Integrated Cordex CSCi for advanced local and remote monitoring and control
> Internal low voltage shutdown for cost effective integration into existing systems
> Universal 19/23" mounting for flexible installation options into existing racks

CXPS 24-48-i Power System

CXPS 24-48-i
Electrical Input
Voltage:

+21 to +30Vdc 90 to 176Vac (derated O/P power)

Current System:
24
Current Converter:
Efficiency:

Feed A: <188A @ +24V input (216A max) Feed B: <188A @ +24V input (216A max)
<94A @ +24V input (108A max) >88% (50 to 100% load @ nominal voltage)

Output

DC Converters

Current System: Current Converter Module: Power System: Power Rectifier:

148A max @ 54Vdc 37A max @ 54Vdc 8000W max @ 54Vdc output 2000W max @ 54Vdc output

Features

Configurations

053-997-20-000: Converter:

Base system with 19/23" universal mounting Up to 4x CXDF 24-48/2kW converter positions

Distribution:

18x load breaker positions (mid-trip, plug-in style), shunt

Controller:

CXCi integrated controller

Mechanical
Dimensions H x W x D (in/mm):
System Weight (lb/kg): Rectifier Weight (lb/kg): Mounting: Connections
Load Breaker: Return Bar:
Alarm:
CXCi Input: Access: Environment
Operating Temperature:
Humidity: Elevation:

8.75 x 17.24 x 12.2 / 222 x 438 x 310 (-000 configuration - excludes mounting brackets, rear cover, and module handle) 42 / 19 6.2 / 2.8 each 19/23" universal mount (center or flush)
18x sets, ¼"-20 studs on " centers 18x sets, ¼" holes on " centers Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) 25-pin D-Sub cable Front access after installation
-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft

Distribution Centers
> Various modular distribution configurations > Complete front access > Integrated CordexTM system controller > Integrated shunt and LVD options > AM plug-in breaker, GJ breaker and GMT fuse options

DCP03 Distribution Center

Vista Distribution Panel

Part Number

Breakers

Single Tier:

020-645-20

AM plug-in

Two Tier:

020-646-20

AM plug-in

Four Tier:

020-635-20

AM plug-in

Modular Distribution Tier Options

Single Voltage:

24 Position AM plug-in 20 Position AM plug-in w/ 600A LVD 3 Position GJ 3 Position GJ w/ 600A LVD

Position 20-24 40-48 80-96

Capacity 600A 1200A 2000A

Mounting

RU

23"

7

23"

9

23"

17

12x Primary and 10x secondary (AM plug-in)

Dual Voltage:

16x Primary and 6x secondary (AM plug-in) 8x Primary (w/ LVD) and 10x secondary (AM plug-in)

25

12x Primary (w/ LVD) and 6x secondary (AM plug-in)

Note: Consult factory for NEBS L3 certified system solutions using Vista UDC's

DC Distribution Centers

Distribution Panel Overview

Vista Two Tier UDC

Part Number

020-107-20

020-588-20

020-589-20

Stand Alone Breaker / Fuse Panels

020-671-20 020-675-20 020-534-20

Fuse Position 0 16* 20* 24* 18* 0

Fuse Type TPS* TPS* TPS* TPS* -

Breaker Position 16/22 16 20 24 18 3

Breaker Type
AM bolt-in AM bolt-in AM bolt-in AM bolt-in AM bolt-in
GJ bolt-in

Capacity 550A

Mounting

Front Access

19/23"

No

400A

19/23"

Yes

400A

23"

Yes

600A

23"

No

600A -

19/23"

No

19/23"

No

RU Additional Options

3

Gnd bar

5

Gnd bar, LVD

5

Gnd bar, LVD

3

-

3

-

3

-

020-578-20

0

-

4

GJ bolt-in -

23

No

4

-

020-103-20

32

GMT

0

-

60A

19/23"

No

1

Gnd bar

020-005-20

20

GMT

0

-

90A

19/23"

No

1

Gnd bar

020-597-20

2

TPL

0

-

1200A

23"

No

4

Shunt

020-702-20

18*

TPS*

18

AM plug-in

300A

19/23"

Yes

Controller I/O,

3

LVD, Shunt,

Batt breakers

020-645-20

20-24"

TPS*

20-24

AM plug-in**

800A

23"

Yes

7

Controller, LVD, Shunt

Universal

10

GMT

-

Distribution

Centers:

020-646-20

40-48"

TPS*

40-48

AM plug-in**

1000A

23"

Yes

9

Controller, LVD, Shunt

10

GMT

-

020-635-20

80-96"

TPS*

80-96

AM plug-in**

2000A

23"

Yes

17

Controller, LVD, Shunt

10

GMT

-

Notes: * TPS Fuses with AM plug-in breaker cartridges may be used as an alternative to breakers ** Compatible with multiple pole AM plug-in breakers (110 to 250A)

DC Accessories
> Rack mount power sources including integrated distribution fuses save space and provide flexibility
> Distribution systems from 50A GMT fuse panels to 800A circuit breaker distribution centers
> 19"/23" universal rack mount

GMT Fuse Panels

GMT 50 Series

Circuit Breaker Panel
KTK Fuse Panel

HDDC: High Density

19"/23" rack mount, 1RU high

Flush mount and center positions

Standard capacity: 50A per input

19"/23" rack mount, 1RU high

Bright, color coded LED indicators for A/B input power status, A/B fuse failure alarms

High power density

Form-C alarm contacts for A/B input power fail, A/B fuse fail (4 relays)

26

Single input and dual input:

High ampacity: 120A per A/B input Bright, color coded LED indicators for A/B input power status, A/B fuse

· 10 GMT output

failure alarms

· 10A/10B output · 20 GMT output

Form-C alarm contacts for A/B input power fail, A/B fuse fail (4 relays) Dual input: 4A/4B and KTK 30A fuse outputs

GMT 100/High Capacity Series

HDDC: High Density

DC Accessories

19"/23" rack mount, 1RU high Flush mount and center positions Bright, color coded LED indicators for A/B input power status, A/B fuse failure alarms Single input, A/B insolated input and A/B/C redundant configuration available Included LED indicators, form-C alarm contacts

100 Series High power density and ampacity:
· 100A per input: (single input, A/B input)
· 70A: (A/B/C- source) Form-C alarm
· 16 GMT outputs · 16A/16B GMT outputs
C-output diode routed, 32 fused redundant outputs

High Capacity Series 24 GMT fuse sockets 150A input bus rating Configurations include:
· Single input, 24 fuses · A/B input, 12A/12B fuses,
A/B/C version, 24 fuses

TPA Fuse Panel

19"/23" rack mount, 3RU high Single input A/B isolated input A/B input C-output redundant diode routed High breaker count to support VOD server redundant power supply circuit
requirements and combined high current load High power density and ampacity:
· 300A per input: (single input, A/B input) · 200A combined load: (A/B/C-source) Accepts up to 22 plug-in bullet terminal circuit breakers Alphanumeric LCD display for voltage, load current per bus, breaker status Form-C alarm contacts for Major and Minor alarms

1RU, 19"/23" rack mount Single input, A/B isolated input and A/B/C redundant configurations available 12 TPA fuse sockets 200A input bus rating Includes LED indicators, form-C alarm contacts

DC Accessories
> Compact, high power density DC distribution fuse panels and circuit breaker panels
> High current, high fuse/breaker count in a small RU footprint
> Battery disconnect for circuit breaker protection of the entire facility DC plant
DCX Series

HDX Compact
Matrix Breaker Panel

DCX Series

EEE Disconnect One Series

1RU, 19"/23" rack mount

27

Single input, A/B insolated input and A/B/C redundant configurations available

400, 600, 800, 1000, 1200, 1800 and 2400A models Direct Battery Terminal mounting options for most battery configurations. Bus
adapter and hardware kits provided for individual battery cell size configurations. LED indicators for On Line/Off Line status, EPO trip and general fault alarm status Form-C relay contact output for remote monitoring of status

200A input bus rating Uses new "slimline" 1RU circuit breakers (Breaker choices available from
5A to 100A) Includes LED indicators, form-C alarm contacts Configurations include:

Integrated EPO function for remote trip

· Single input, 20 breakers

Over-current and non over-current models

· A/B input, 10A/10B breakers, A/B/C version, 16 breakers

Super HDX

HDX Compact

DC Accessories

2RU, 19"/23" rack mount Single input, A/B insolated input configurations available 400A input bus rating Uses AM series bullet terminal circuit breakers (Breaker choices available
from 5A to 100A) 16 circuit breaker position No GMT fuses (unlike standard HDX) Targeted at Cisco 7609 installations

19"/23" rack mount, 2RU high Single input A/B isolated input High power density and ampacity:
· 300A per input: (single input, A/B input) · 300A combined load: (A/B/C-source) · Accepts up to 12 plug-in bullet terminal circuit breakers · 8 GMT fuses Standard unit includes front panel with A and B input LED indicators and breaker/fuse trip indicator LED Form-C alarm contacts for Major and Minor alarms

28

DC Accessories

Batteries and Accessories

Alpha's Headend battery line includes three distinct types of models: 20-year batteries, 10-year telecom front and top terminal, and flame retardant UPS batteries. These batteries provide improved performance, longer runtimes and extended service life. The front terminal models allow for easier access to the batteries during installation and routine maintenance. Alpha's Headend batteries are ideal for broadband, cellular, electric utility, PCS, customer premise, long distance and distributed power.

> Telecommunications
In critical standby power applications, maximum battery life is essential. Alpha offers a wide range of large format 2V Cell batteries, front and top terminal batteries ideal for providing extended runtime for telecom and wireless applications. Alpha's Telecom batteries include features such as 10-20 year design life, small footprint, customizable configuration, strong corrosion-resistant grid design, and easy installation and maintenance.

> AlphaCellTM HPL-FT
Alpha expands its Alphacell battery family to include the HPL-FT Series of front terminal batteries for Broadband Cable and Telecommunications applications. The AlphaCell HPL-FT series are valve regulated lead acid batteries designed for long life. Benefits of these new batteries include central gassing system, snap-in front covers, integral flame arrestor, construction from recyclable materials and low self-discharge rates.

> PowerAgent

29

The PowerAgent BMS is a remote monitoring system that alerts managers to degradations in the

power-producing capacity of batteries indoor/outdoor uninterruptible power supply applications.

Based on an advanced patent pending technology called "admittance" testing, the BMS employs DSP

(Digital Signal Processing) and standards-based interface protocols to facilitate seamless integration of

battery monitoring into an enterprise-wide network management fabric.

Batteries

> AlphaGuardTM
AlphaGuard monitors and protects your batteries by spreading the charge voltage equally across all the batteries in the string, ensuring that every battery, whether old or new, is properly charged. With an ideal voltage across each battery, life and runtime are optimized. Individual batteries in a string can be replaced as they fail, allowing batteries to be left in service longer.

> Battery Testing Equipment
A fast, reliable and affordable testing process is now available with the development of conductance based battery measurement technology. By coupling conductance testing with a simple utility load test, the system operator is armed with the quality of data necessary to know the status of their installed standby batteries and budget their replacement with confidence.

Telecommunications
Large Format 2V Cell Batteries
> 20-year design life batteries with VRLA technology > Space saving design for the greatest amount of power in a small footprint > Customizable to your system's configuration needs

MsEndur

C&D MS Endur 345 to 2180Ah

Part Number

# Cells/ Module

# Plates/ Cell

Nom Ah Cap (8hr)

System # of Cells

System Voltage

Model Volts

Dimensions H x W x D (in/mm)

Weight (lb/kg)

Cell Layout W x H

RAA64024CE01: 3

7

345

24

48

6

21.4 x 44.7 x 23.1 / 544 x 1135 x 587

1970 / 849 6 x 4

RBB46024CE01: 3

9

480

24

48

6

18.7 x 64.5 x 23.1 / 475 x 1638 x 587

2470 / 1120 4 x 6

RBB64024CE01: 3

9

480

24

48

6

26.1 x 44.7 x 23.1 / 663 x 1135 x 587

2410 / 1093 6 x 4

RCC46024CE01: 3

11

599

24

48

6

21.4 x 64.5 x 23.1 / 544 x 1638 x 587

2920 / 1324 4 x 6

RDF38024CE01: 3

15

839

24

48

6

30.4 x 44.7 x 23.1 / 772 x 1135 x 587

2850 / 1293 3 x 8

RDF46024CE01: 3

15

839

24

48

6

21.4 x 84.4 x 23.1 / 544 x 2144 x 587

3860 / 1751 4 x 6

REH38024CE01: 3

19

1079

24

48

6

27.9 x 64.5 x 23.1 / 703 x 1638 x 587

3790 / 1719 3 x 8

REH46024CE01: 3

19

1079

24

48

6

26.1 x 84.4 x 23.1 / 663 x 2144 x 587

4740 / 2150 4 x 6

RFK38024CE01: 3

23

1319

24

48

6

33.5 x 64.5 x 23.1 / 851 x 1638 x 587

4670 / 2118 3 x 8

RFK46024CE01: 3

23

1319

24

48

6

30.4 x 84.5 x 23.1 / 772 x 2146 x 587

5620 / 2549 4 x 6

30

RHP38024CE01: 3

27

1559

24

48

6

39.5 x 64.5 x 23.1 / 1001 x 1638 x 587

5550 / 2517 3 x 8

RHP46024CE01: 3

27

1559

24

48

6

34.4 x 84.4 x 23.1 / 874 x 2144 x 587

6550 / 2971 4 x 6

RJS38024CE01: 3

35

2038

24

48

6

45.5 x 64.5 x 23.1 / 1156 x 1638 x 587

6540 / 2966 3 x 8

RJS46024CE01: 3

35

2038

24

48

6

43.6 x 84.4 x 23.1 / 1107 x 2144 x 587

8320 / 3774 4 x 6

Batteries

East Penn Unigy II 760 to 2000Ah

Part Number

# Cells/ # Plates/ Module Cell

24AVR95-17:

3

17

24AVR95-19:

3

19

24AVR95-21:

3

21

24AVR95-23:

3

23

24AVR95-25:

3

25

24AVR95-27:

3

27

24AVR95-29:

3

29

24AVR95-31:

3

31

24AVR95-33:

3

33

24AVR125-33: 2

33

Nom Ah Cap (8hr) 760 855 950 1045 1140 1235 1330 1425 1520 2000

System # of Cells 24 24 24 24 24 24 24 24 24 24

System Voltage 48 48 48 48 48 48 48 48 48 48

Model Volts 6 6 6 6 6 6 6 6 6 6

Dimensions H x W x D (in/mm)
21.9 x 68.3 x 27.1 / 556 x 1735 x 688 24.2 x 68.3 x 27.1 / 615 x 1735 x 688 26.4 x 68.3 x 27.1 / 671 x 1735 x 688 28.7 x 68.3 x 27.1 / 729 x 1735 x 688 30.1 x 68.3 x 27.1 / 765 x 1735 x 688 33.2 x 68.3 x 27.1 / 843 x 1735 x 688 35.4 x 38.3 x 27.1 / 899 x 1735 x 688 37.7 x 68.3 x 27.1 / 958 x 1735 x 688 39.9 x 68.3 x 27.1 / 1013 x 1735 x 688 53.2 x 71.4 x 28.6 / 1351 x 1814 x 726

Weight (lb/kg) 3260 / 1479 3612 / 1638 3956 / 1794 4308 / 1954 4652 / 2110 4972 / 2255 5348 / 2426 5668 / 2571 6020 / 2737 8616 / 3908

Cell Layout W x H 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 (2 x 6) x 2

GNB Absolyte GP

Part Number

# Cells/ Module

100G13:

100G15:

3

100G17:

3

100G19:

3

100G21:

3

100G23:

3

100G25:

3

100G27:

3

100G29:

3

100G31:

3

100G33:

3

# Plates/ Cell
15 17 19 21 23 25 27 29 31 33

Nom Ah Cap (8hr) 600 696 800 896 1000 1096 1200 1296 1400 1496 1600

System # of Cells 24 24 24 24 24 24 24 24 24 24 24

System Voltage 48 48 48 48 48 48 48 48 48 48 48

Model Volts 6 6 6 6 6 6 6 6 6 6 6

Dimensions H x W x D (in/mm)
22.2 x 68.7 x 26.4 / 564 x 1745 x 671 24.5 x 68.7 x 26.4 / 622 x 1745 x 671 26.8 x 68.7 x 26.4 / 681 x 1745 x 671 29 x 68.7 x 26.4 / 737 x 1745 x 671 31.3 x 68.7 x 26.4 / 795 x 1745 x 671 33.5 x 68.7 x 26.4 / 851 x 1745 x 671 35.8 x 68.7 x 26.4 / 909 x 1745 x 671 38 x 68.7 x 26.4 / 965 x 1745 x 671 40.3 x 68.7 x 26.4 / 1024 x 1745 x 671 42.5 x 68.7 x 26.4 / 1080 x 1745 x 671

Weight (lb/kg)

Cell Layout W x H

2992 / 1357 3391 / 1539 3760 / 1706 4120 / 1869 4488 / 2036 4864 / 2206 5224 / 2370 5632 / 2555 6000 / 2722 6360 / 2885

3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8

Telecommunications
Front Terminal Batteries

> 10-year design life batteries > Valve regulated lead-acid batteries > Front access terminal design > Strong corrosion resistant grid design > Multicell design for ease of installation and maintenance > Can be used in any position: Upright, side or
end mounting recommended

Front Terminal Batteries

C&D True Front Access Series

Part Number

Model Volts

TEL 12-160FW:

12

TEL 12-160F:

12

TEL 12-180F:

12

Capacity @ 8hr Rate @ 1.75V/C 159.7 157.3 181.2

Dimensions H x W x D (in/mm) 10.10 x 16.37 x 6.88 / 256.54 x 415.90 x 174.70 11.14 x 20.16 x 4.86 / 282.96 x 512.17 x 123.39 12.60 x 20.16 x 4.86 / 320.04 x 512.17 x 123.39

Weight (lb/kg) 121 / 54.9 115 / 52.2 131 / 59.4

Terminal Type Threaded insert Threaded insert Threaded insert

East Penn ET Series Part Number 12AVR100-3ET: 12AVR150-ET:

Model Volts 12 12

Capacity @ 8hr Rate @ 1.75V/C 96 150

Dimensions H x W x D (in/mm) 20.1 x 4.3 x 9.4 / 510.5 x 109.2 x 2238.7 22 x 4.9 x 11.75 / 558.8 x 124.5 x 298.5

Weight (lb/kg) 75 / 34 115 / 52

Terminal Type Threaded insert Threaded insert

GNB Marathon Front Terminal

Part Number

Model Volts Capacity @ 8hr Rate @ 1.75V/C Dimensions H x W x D (in/mm)

Weight (lb/kg)

Terminal Type

M12V90FT:

12

90

10.6 x 4.1 x 15.6 / 270 x 105 x 395

68 / 31

Threaded insert

M12V105FT:

12

104

9.4 x 4.3 x 20.1 / 238 x 110 x 511

79 / 35.8

Threaded insert

M12V125FT:

12

125

M12V155FT:

12

155

11.1 x 4.9 x 22 / 283 x 124 x 559 11.1 x 4.9 x 22 / 283 x 124 x 559

105 / 47.6

Threaded insert

31

119 / 53.8

Threaded insert

M12V180FT:

12

180

12.5 x 4.9 x 22 / 317.5 x 124.6 x 558.8

133 / 60.3

Threaded insert

AlphaCellTM SMU-F Part Number SMU12-155FR: SMU12-170FR:

Model Volts 12 12

Capacity @ 8hr Rate @ 1.75V/C 150 172

Dimensions H x W x D (in/mm) 21.9 x 4.9 x 11.1 / 558 x 125 x 283 21.9 x 4.9 x 12.2 / 558 x 124 x 310

Weight (lb/kg) TopAccessStudHoleSize

119 / 54

8mm

129.8 / 59

8mm

Front Access Stud Size 6mm 6mm

Batteries

Telecommunications and Business Services

> 10 to 12-year design life batteries > Top terminal access design > Valve regulated lead acid technology > Heavy duty copper alloy terminals for ease
of assembly and reduced maintenance

C&D Tel Series Part Number Tel12-30: Tel12-45: Tel12-70: Tel12-80: Tel12-90: Tel12-105: Tel12-125:
East Penn Unigy I Series Part Number 12AVR-30: 12AVR-40: 12AVR-75: 12AVR-100: 12AVR-130:
GNB Marathon Series Part Number M6V190: M12V30T: M12V40: M12V45F: M12V70: M12V90:

Model Volts 12 12 12 12 12 12 12
Model Volts 12 12 12 12 12
Model Volts 6 12 12 12 12 12

Capacity @ 8hr Rate @ 1.75V/C 30 46 69 79 88 102 127
Capacity @ 8hr Rate @ 1.75V/C 3.4 4.4 8.82 11.76 15.6
Capacity @ 8hr Rate @ 1.75V/C 190 28 40 46 72 90

Dimensions H x W x D (in/mm) 7.8 x 5.2 x 6.8 / 197.4 x 131.9 x 172.7 8.9 x 5.4 x 8.1 / 228.3 x 138.9 x 205.6 10.3 x 6.8 x 8 / 260.5 x 173.4 x 203.6 12 x 6.8 x 8.1 / 305.8 x 173.4 x 205.3 13.5 x 6.8 x 8.5 / 343.1 x 171.7 x 216.2 20.1 x 4.3 x 9.4 / 511 x 110 x 238 13.6 x 6.8 x 10.9 / 344.7 x 171.7 x 277.7
Dimensions H x W x D (in/mm) 6.97 x 5 x 6.55 / 177.04 x 127 x 166.37 6.97 x 5 x 8.16 / 177.04 x 127 x 207.26 8.24 x 6.56 x 10.20 / 209.3 x 166.6 x 259.1 8.70 x 6.75 x 12.93 / 221 x 171.5 x 328.4 11.21 x 12.75 x 6.77 / 285 x 342 x 172
Dimensions H x W x D (in/mm) 9.25 x 6.85 x 12.04 / 235 x 174 x 306 7.32 x 5.11 x 6.73 / 186 x 130 x 171 7.44 x 6.57 x 7.79 / 189 x 167 x 198 10 x 4.76 x 8.66 / 254 x 121 x 200 9.25 x 6.85 x 10.23 / 235 x 174 x 260 9.25 x 6.85 x 12.04 / 235 x 174 x 306

Weight (lb/kg) 27 / 12 40 / 18 55 / 25 68 / 31 72 / 33 80 / 36 100 / 45
Weight (lb/kg) 21 / 9.5 26 / 11.8 55 / 25 72 / 32.7 98 / 44.5
Weight (lb/kg) 74 / 33.6 24 / 10.9 39 / 17.7 39 / 17.7 61 / 27.7 72 / 32.7

Top Terminal Batteries
Terminal Type Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert
Terminal Type Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert
Terminal Type Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert

Business Services
AlphaCellTM HPL-FT Batteries
> Front terminal design with protective covers > Specifically designed for mission-critical applications > High cyclic life capability > Flame retardant case and cover (to UL94VO) > 3-step terminal seal design ensures leak-free operation > Integral handles (115HPL-FT, 220HPL-FT) for ease of handling > Ideally suited for use in Alpha NPS and FT enclosures > Approved as non-hazardous cargo for ground/sea/air transportation

AlphaCellTM HPL-FT Batteries

Models:

70HPL-FT

Standard Warranty1:

3 years

Service Life:

Long

VRLA Battery Type:

High performance lead alloy

Heat Resistant:

High

Hydrogen Emission:

Low

Terminals:

14mm insert M8 x 1.25 thread

Terminal Torque:

8Nm

Case Material:

VO

Typical Runtime (minutes)2: 70

32

Cells Per Unit:

6

Voltage Per Unit:

12.8

Conductance Value:

1050

Max. Discharge Current (A): 1000

Short Circuit Current (A):

1400

10 Second Volts @ 100A:

11.3

Ohms Impedance 1 kHz:

6.5mOhms

Capacity @ 20hrs (to 1.75VPC) @ 25°C / 77°F:

42Ah

115HPL-FT 3 years Long High performance lead alloy High Low 14mm insert M8 x 1.25 thread 8Nm VO 115 6 12.8 1200 1000 2000 11.5 4.1mOhms
62Ah

220HPL-FT 3 years Long High performance lead alloy High Low 14mm insert M8 x 1.25 thread 8Nm VO 220 6 12.8 1600 1000 3500 11.7 2.5mOhms
107Ah

Batteries

Dimensions H x W3 x D3 (in/mm):

8.2 x 3.8 x 9.8 / 209 x 97 x 249

Weight (lb/kg):

27.9 / 15.3

Operating Temperature Range

Discharge:

-40 to 60°C / -40 to 140°F

Charge (with temp compensation):

-40 to 60°C / -40 to 140°F

10.3 x 4.2 x 11.3 / 263 x 108 x 287 46.2 / 22.2
-40 to 60°C / -40 to 140°F -40 to 60°C / -40 to 140°F

11.3 x 4.2 x 15.6 / 287 x 108 x 396 78.5 / 36
-40 to 60°C / -40 to 140°F -40 to 60°C / -40 to 140°F

Float Charging Voltage @ 25°C / 77°F (Vdc):
AC Ripple Charger:

13.5 to 13.6

13.5 to 13.6

13.5 to 13.6

0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4%V pk to pk

Notes: 1 Warranty varies by country and region. Warranty valid only when used with Alpha approved Power Supplies, Chargers and Enclosures. Consult your sales person for details 2 Runtimes at 25A to 1.75VPC @ 25°C. No deep discharge cycling required to obtain maximum runtime ratings 3 Dimensions at battery base

Business Services
FTTx Batteries
> Specifically engineered for long-life float service, standby applications
> One-year typical and three-year warranty option for the 7.2Ah battery
> Qualified with Alpha's FlexPointTM and FlexNetTM battery backup power supplies
> UL recognized component per UL 1989 for standby batteries

17Ah, 12Ah and 7.2Ah FTTx Batteries

Models: Specifications Warranty: Service Life: Battery Type: Dimensions H x W x D (in/mm): Weight (lb/kg):

AX-STDBAT-7
1 year Standard 7.2Ah AGM 3.94 x 2.56 x 5.94 / 100 x 65 x 151 5.28 / 2.4

AX-LONGBAT-7
3 year Long 7.2Ah AGM 3.94 x 2.56 x 5.94 / 100 x 65 x 151 6.17 / 2.8

AX-STDBAT-12
1 year Standard 12Ah AGM 3.94 x 2.56 x 5.94 / 100 x 65 x 151 5.94 / 2.69

AX-STDBAT-17
1 year Standard 12Ah AGM 6.57 x 3 x 7.13 / 167 x 76.2 x 181 12.13 / 5.5

7.2Ah Battery @ 25°C / 77°F

Constant Wattage Performance for 7.2Ah Battery (final voltage 1.75Vpc)

33

Discharge Time:

90min 2hrs

3hrs

4hrs

5hrs

6hrs

7hrs

8hrs

9hrs

10hrs

12hrs

20hrs

Discharge Wattage:

35.3

28

20

16

13.2

11.5

10.1

9.1

8.1

7.4

6.3

4.1

12Ah Battery @ 25°C / 77°F

Constant Wattage Performance for 12Ah Battery (final voltage 1.75Vpc)

Discharge Time:

90min 2hrs

3hrs

4hrs

5hrs

6hrs

7hrs

8hrs

9hrs

10hrs

12hrs

20hrs

Discharge Wattage:

--

--

33.4

26.7

22

19.2

16.9

15.2

13.5

12.4

10.5

6.8

Batteries
Recharge

17Ah Battery @ 25°C / 77°F

Constant Wattage Performance for 17Ah Battery (final voltage 1.75Vpc)

Discharge Time:

90min 2hrs

3hrs

4hrs

5hrs

6hrs

7hrs

8hrs

9hrs

10hrs

12hrs

20hrs

Discharge Wattage:

--

--

--

--

30.9

26.4

22.9

20.4

18.4

16.8

14.2

9.8

Percent Rated Current/Power Available

110% 100%
90% 80% 70% 60% 50% 40% 30% 20% 10%
0% -46°C -50°F

VRLA Battery Efficiency vs. Temperature and Discharge Rate

20hr 8hr 5hr

-46°C -36°C -29°C -23°C -18°C -12°C -7°C

-1°C

4°C

10°C

15°C

21°C

27°C

-40°F -30°F -20°F -10°F

-0°F 10°F

20°F

30°F

40°F 50°F

60°F

70°F

80°F

Battery Storage Guidelines
Under 25°C / 77°F storage conditions, batteries self-discharge at a rate of approximately 5% per month. The self-discharge rate of VRLA batteries increases with temperature. Recommended recharge times are shown at 180 days (6 months) at 25°C / 77°F, or 75 days (2.5 months) at elevated temperatures of 35 to 40°C / 95 to 104°F.

100 80

60
50°C 40

20

32°C 38°C

90°F 100°F

0

2

40°C

Recharge

35°C

30°C

10°C 35°C

4

6

8

10

12

UPS
Uninterruptible Power Supply Batteries
> 10-year design life > High rate flame retardant AGM UPS batteries
for all standby applications > Absorbed valve-regulated, lead-acid battery technology
designed for UPS standby power systems > Alpha Technical Services offers removal,
replacement and recycling of UPS Batteries > Most UPS brands serviced

East Penn Unigy High Rate Series

Part Number

Model Volts

U1HR1500:

12

45HR2000:

12

24HR3000:

12

27HR3500:

12

31HR4000:

12

31HR5000:

12

Watts per Cell @ 15min Rate @ 1.67Vpc
119 168 253 314 377 475

Dimensions H x W x D (in/mm)
6.93 x 5.18 x 7.71 / 176 x 132 x 196 8.26 x 5.31 x 8.84 / 210 x 135 x 225 8.24 x 6.80 x 10.20 / 209 x 173 x 259 8.24 x 6.80 x 12.01 / 209 x 173 x 305 8.70 x 6.75 x 12.93 / 221 x 171 x 328 11.20 x 6.77 x 13.46 / 284 x 172 x 342

34

CED AGM UPS - Flame Retardant High Rate Series

Part Number

Model Volts

Watts per Cell @ 15min Rate @ 1.67Vpc

Dimensions H x W x D (in/mm)

UPS12-100MR:

12

91

6.5 x 5.2 x 6.9 / 166.2 x 131.3 x 174.3

UPS11-150MR:

12

148

7.8 x 5.2 x 6.8 / 197.1 x 131.9 x 172.7

UPS12-210MR:

12

206

9 x 5.5 x 8.1 / 228.6 x 139.2 x 205.1

UPS12-300MR:

12

300

10.3 x 6.8 x 8 / 260.9 x 173.4 x 203.5

Batteries

UPS12-350MR:

12

350

12 x 6.8 x 8.1 / 305.8 x 173.4 x 204.8

UPS12-400MR:

12

400

13.4 x 6.8 x 8.5 / 340.9 x 172.7 x 216.4

UPS12-490MR:

12

488

13.6 x 6.8 x 10.9 / 344.7 x 172.7 x 277.7

UPS12-540MR:

12

537

12.6 x 6.9 x 8.9 / 320.8 x 177 x 227.2

UPS6-620MR:

6

620

12.6 x 6.9 x 9.9 / 321 x 177 x 253

GNB Sprinter UPS
Part Number
S6V740: S12V120: S12V170: S12V285: S12V300: S12V370: S12V500:

Model Volts
6 12 12 12 12 12 12

Watts per Cell @ 15min Rate @ 1.67Vpc
746 117 167 285 306 373 505

Dimensions H x W x D (in/mm)
9.25 x 6.85 x 12.04 / 235 x 174 x 306 6.53 x 6.57 x 6.81 / 166 x 167 x 173 7.44 x 6.57 x 7.79 / 189 x 167 x 198 9.25 x 6.85 x 10.23 / 235 x 174 x 260 9.25 x 6.85 x 9.25 / 235 x 174 x 306 9.25 x 6.85 x 12.04 / 235 x 174 x 306 11.33 x 6.77 x 13.54 / 288 x 172 x 344

UPS batteries

Weight (lb/kg)
27 / 12 40 / 18.1 56 / 25.4 66 / 30 74 / 33.6 98 / 44.5

Terminal Type
Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert

Weight (lb/kg) 21 / 10 27 / 12 40 / 18 57 / 26 67 / 30 74 / 34 10 / 45 100 / 45 72 / 33

Terminal Type Flag terminal Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert

Weight (lb/kg)
74 / 33.6 27 / 12.2 36 / 16.3 61 / 27.7 63 / 28.6 74 / 33.6 107 / 48.5

Terminal Type
Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert

Battery Monitoring
PowerAgent
> Ethernet, TCP/IP or SNMP > Flexible, scalable, easily installed > Programmable alarm thresholds for each battery > Built-in email notification > Sensors powered from monitored battery

Specifications

Site Controller

Number of Monitored Strings: Number of Batteries: Network Interface: Network Protocols: Local Diagnostic Interface:
Power:
Dimensions H x W x D (in/mm): Mounting:

6 max 240 max Ethernet 10/100 BaseT TCP/IP, UDP, HTTP, SNMP, Telnet, DHCP, SMTP Proprietary 9600 baud, RJ-45, ASCII 15 to 60Vdc, 2W nom, (110/220Vac power pack available) 6 x 9 x 1.6 / 152.4 x 228.6 x 40.64 Rack or wall

PowerAgent Site Controller and Sensor Module

Sensor Modules (Model PAS-PA-BSx-y-z)

Measurements:

String volts, battery volts, temperature, dynamic resistance/admittance

Controller Interface:

2 ea, RJ-45

Mounting:

Mounts on battery negative terminal; wire/lug connection to positive terminal

Indicators:

Red/green LED

Power:

Powered from monitored battery; 10ma avg standby current

Isolation:

Optically isolated from controller

Dimensions H x W x D (in/mm): 1.5 x 3 x 0.75 / 38.1 x 76.2 x 19.05
35

Batteries

Network Monitoring
ContactAgent

> Remote site monitoring and control for generators > Provides network access for non-network
equipment via web and SNMP > Email Alarm Capability > Contact closure or analog inputs and latched
relay contact outputs > Optional temperature and humidity measurements

ContactAgent

Specifications

Master Unit

Number of Inputs:

8 Digital (contact closure)

Electrical Input:

1ma max closed-switch current

Number of Outputs:

2 Form-C contact sets; state not preserved on power failure

Electrical Output:

60V max; 5A

Slave Unit Interface:

RS-485/RJ-45 connector

Operating Power

5Vdc from supplied wall-mount power supply

Network Interface:

10/100 Ethernet

Protocols:

TCP/IP, SMTP, HTTP, SMTP, DHCP, TFTP

Dimensions H x W x D (in/mm): 1.5 x 8 x 4.3 / 38.1 x 203.2 x 109.2 ( rack mountable)

* SNMP MIB documentation available upon request

RIM Module Number of Inputs: Analog Measurements: Temperature Sensor:
Humidity Sensor:
Max Number of Units: AC Line Measurement: ROM Module Number of Outputs: Electrical Output: Temperature Sensor:
Humidity Sensor:
Max Number of Units:

6 Digital/analog (user/definable) ±12Vdc, 0 to 8Vrms Standard, ±2°C/35.6°F from -40 to 80°C / -40 to 176°F Optional ±3% accuracy from 20 to 80% RH, ±5% accuracy from 0 to 19% RH and 81 to 100% RH 4 RIM modules per Master Unit Optional 90 to 140Vac, RMS, sine, 50/60Hz
4 Form-C contacts, state-preserved on power failure 60V max, 2A Standard, ±2°C/35.6°F from -40 to 80°C / -40 to 176°F Optional ±3% accuracy from 20 to 80% RH, ±5% accuracy from 0 to 19% RH and 81 to 100% RH RS-485 on RJ-45 connector, power supplied via daisy chain

AlphaGuardTM
Battery Charge Management System
> Maximizes battery life > Spreads charge voltage equally across batteries > Compensates for battery differences as they age > Replace single batteries, not the entire string > Single battery connections for charge
management and status monitoring > Safe unattended operation designed to CSA
C22.2 No. 107.1 and UL 1778 Standards > Optional Potted AlphaGuard for underground
battery vault applications

AlphaGuard CMT-3

AlphaGuard

Models:

AG-CMT-3:

AlphaGuard Charge Management SC, 36V --including 36Vdc battery string interface cable

AG-CMT-4:

AlphaGuard Charge Management SC, 48V --including 48Vdc battery string interface cable

Configuration

36

Quantity:

Service Location:

One (1) AlphaGuard is required per battery string With the battery string

Mechanical

Housing Material:

High impact plastic

Dimensions H x W x D (in/mm): 1.4 x 4.8 x 4.3 / 36 x 122 x 108

Weight (lb/kg):

0.8 / .36

Batteries

Electrical

Batteries:

Individual 12Vdc nominal batteries configured into 36 or 48Vdc strings

Circuit Protection:

Fast blow fuse, reverse polarity protected

Quiescent Current Draw:

1mA max. (Current consumed by AlphaGuard after low voltage total shutdown)

Charge Management:

Most effective during float period of charge

Max. Current:

2A @ 25°C / 77°F

Quality of Final Balance:

±100mV max. between any two (2) batteries

Charging Efficiency:

80 to 90%

Charge Balance:

±100mV typical

Low Voltage Cutoff:

34.5Vdc/46Vdc ±5%

Communication to XM2:

AG-DSM cable supplies battery readings to a DSM status monitoring card

Voltage Sense Regulation: ±100mV

Environment

Operating Temperature:

-40 to 55°C / -40 to 131°F

Humidity

5 to 95% non-condensing

Warranty

Warranty:

5 years

The AlphaGuard employs a patented Charge Management Technology (CMT) to shuttle excess charge current to batteries requiring a greater charge, and is contained in a small plastic enclosure that installs directly on top of one of the batteries in the string or in the optional battery integration tray. A short service cable connects the AlphaGuard to each of the batteries in the string. Both 36Vdc (3 battery) and 48Vdc (4 battery) versions are available. One AlphaGuard is required per string. An AlphaGuard configured with the optional voltage sense cabling and interface module (DSM, ESM, EDSM or External DOCSIS®) allows the AlphaGuard to interface with a statusmonitoring module. Two AlphaGuard modules can be connected to single interface module. Refer to individual interface module documentation for additional information.
Potted AlphaGuard CMT-3

AG-DSM-S9-Cable

AG-DSM-D9-Cable

AG-DSM-D35-Cable

AG-DSM-S35-Cable

Battery Cable 36V 6ft

Battery Cable 48V 6ft

Battery Testing Equipment
AlphaCellTM Battery Testing Equipment

> Complete battery life trending through conductance tests
> Non-intrusive conductance measurements do not reduce string life
> Quick, accurate measurements and data recording reduce on-site time
> Simple pinpoint testing requires only access to two battery posts or straps
> Enables early detection of questionable batteries in the network

Celltron Ultra CTU-6000

Battery Testing Equipment

Kit Contents

Model:

Celltron Ultra

Celltron AdvancedTM

Celltron Ultra Kit CTA-6000AT

Celltron Advanced Kit CTA-4000AT

Model Number: Applications: Voltage:

CTU-6000 (w/ temp. sensor)

CTA-4000 (kit) CTA-2000 (analyzer only)

Tests individual lead acid cells or monoblocs (up to 16V) in any common configuration, approximately 10-6000Ah

Tests individual lead acid cells or monoblocs (up to 16V) in any common configurations

1.5 to 20Vdc

1 to 20Vdc

Contains: Digital multimeter Infrared strip printer Lighted probes Clamps and probes

Contains:

Protective boot

Rechargeable battery pack

Infrared PC data receiver and software

Infrared printer

Infrared temperature sensor

Protective carrying case

37

Both clamp and probe cables

Spare fuses, printer paper, probe tips

Conductance:

100 to 19990 Siemens 100 to 9999 Siemens

Test Data Storage:

500 string locations of 480 test results stored internally

16 string locations of 480 test results stored internally

Batteries

Accuracy:

+2% across test range +2% across test range

Voltmeter Resolution: 5mVdc

5mVdc

Environmental:

0 to 40°C / 32 to 104°F, 95% non-condensing

Conductance Technology/Industry Approvals and Recommendations:

IEEE Standards 1188 and 484 EPRI Guide for testing stationary batteries International Telecommunications Energy Conference Bellcore T1Y1 Presentation for American National Standards Institute International Lead Zinc Research Organization Battery Council International
Applications
Cable TV/Broadband Power Networks · Outside Plant Batteries · Headend DC/AC Batteries · Premise Backup Supplies (FTTx) 6/12V, 5 to 600Ah Stationary Batteries Security system batteries Emergency lighting batteries

Optional Equipment:
Handheld Printer Infrared Module for PC

Features and Benefits

Simple - One-step testing, no instrument inputs or adjustments required. Quick - Battery voltage and conductance displayed in less than 10 seconds.
Test an entire 48V string in less than 1 minute. Safe - Utilizes patented conductance technology, a passive method that
minimizes technician risk. Accurate - Field test proven to ±2% accuracy across test range. Conductance
method recognized by IEEE standard for the testing of lead-acid batteries with proven correlation to battery capacity. Economical - Efficient and accurate battery tester priced to fit into every technician's tool kit.

DC to AC Inverters

Alpha Technologies offers a full line of modular inverter systems providing a new level of scalability, maintainability, compactness, reliability and performance. Alpha's scalable DC to AC inverter is recognized as the industry standard for critical AC power by many of the world's leading communications companies.

> AMPS80HP
Alpha's new high performance AC or hybrid AC/DC system offers telecom grade reliability, 94% efficiency and high power density. The AMPS80 features hot swappable 2.5kVA/ 2.0kW inverter modules and optional 1.8kW rectifier. The AMPS80 meets your current and future power needs by allowing you to purchase only the power modules you need for current needs while having ultimate flexibility to scale up or down, depending on future power needs. Front access and user-friendly connections make the system easy to install, service and upgrade.

> AMPS24HP

The AMPS24 features hot swappable 1.5kVA/1.2kW inverter modules and 1.8kW rectifier modules that are the building blocks of a highly reliable power system utilizing 48Vdc batteries. The AMPS24 meets your current and future needs by allowing them to purchase only the power modules for current needs while having ultimate flexibility to scaleup or down, depending on future power needs.

> Arcon Inverter Series

The Arcon Inverter System provides pure sine wave output ideal for telecom applications. Its high

frequency conversion and topology allow for high efficiency in a compact and user-friendly design.

With hot swappable modules and a patented technology, the Arcon Inverter System is very flexible and

39

customizable.

> TEBEVERT Inverter Series

DC to AC Inverters

The TEBEVERT DSP inverter system featuring Digital Signal Processing technology can be used in a wide array of telecom and industrial applications. The introduction of enhanced DSP controls and higher semi-conductor switching frequencies improves power density and operating efficiency while dramatically reducing physical size and weight.

> Invertronic Inverter System

The Invertronic Inverter System is a modular three phase inverter system with a high power density ideal for telecom and headend applications. The efficient load balancing between phases allows for minimal costs associated with distribution transformers, protective devices and cabling. The system's unique topology consisting of each inverter module having its own Static Bypass Switch, secures data bus communications.

> Media Inverter System

The Media Inverter System is a parallelable, rack-mounted twin sine inverter (TSI) system providing a pure AC sine wave output at 120 to 240Vac, 60 or 50Hz, with a THD <3% for any kind of load. Utilizing 48Vdc input, this high density system ranges from 1500 to 6000VA and is mountable on either a 19" open relay rack or conventional box bays. Unlike traditional inverters, the TSI increases your network's overall efficiency without compromise to the quality and stability of the output wave form.

> DSP Inverter Series

The DSP inverter system is designed to address the critical AC powering requirements of telecom applications, Voice over Internet Protocol (VoIP) and mission critical servers. The system can be scaled in 1kVA or 2.5kVA increments up to 27.5kVA in an N+1 redundant configuration. These units have been NEBS Level 3 Certified by a nationally recognized testing lab.

> MS Power Inverter Series

MS Inverters feature an integrated utility bypass and can be cascaded for redundancy. Designed for long mean time between failure, these inverters provide the dependable AC power your networks demand. These intelligent, dependable inverters provide economical AC power for all of your network needs.

AMPS80HP
Modular AC UPS System

> High performance AC or hybrid AC/DC backup power system offering 99.999% availability
> 94% Efficiency, 15 year Design Life and MTBF (Mean Time Between Failures) greater than 200,000 hours
> Intelligent system controller with integrated SNMP for local and remote management of AC and DC power modules, batteries, and other peripherals
> Hot swappable 2.5kVA/2.0kW inverter modules and optional 1.8kW rectifier modules
> Small footprint system offers up to 75kVA/60kW in a single 19" box bay rack

AMPS80

AMPS80HP

Specifications

Max. DC Input Current

Model Input and Output Phase:

AMPS80- AMPS80- AMPS80- AMPS80-

3-75

3-30

2-40

1-20

120/208V 3-ph

120/240 or 120 single 120/208V2-ph ph

@ 48Vdc:

1375A

550A

734A

@ 40Vdc:

1700A

680A

900A

Voltage Ripple:

<2mV / <38dbrnc

Unified System Controller with Integrated SNMP

366A 450A

40

Output Capacity:

7500 to 7500 to 5000 to 2500 to 75000VA 30000VA 40000VA 20000VA

Control and Monitoring:

Configure, control and monitor inverter and rectifier modules via Internet Explorer 7 onwards

DC to AC Inverters

Output Power (Resistive Load):

6000 to 6000 to 4000 to 2000 to 60000W 24000W 32000W 16000W

Maximum Output Current:

208Arms per phase

83Arms per phase

168Arms per phase

168Arms

Max./Min. No. of 2500VA/2000W Inverter Modules:
Technology:
Static Switch:

30/3

12/3

16/2

8/1

Twin Sine Inverter (TSI) technology; each inverter module has DC input and AC input
Not required; each module has its own static switch

Efficiency:

94% AC to AC; 90% DC to AC (from 50 to 100% full resistive load)

Waveform:

Pure sine wave

Output Power Factor:

0.8 (can run capacitive and inductive loads)

Transfer Time:

Zero transfer time

Warranty:

2 year standard (1 and 3 year optional extensions)

Inverter Module AC Output

Power Rating:

2500VA/2000W

Voltage Range (AC):

90 to 140V 90 to 140V 90 to 140V 90 to 140V

Voltage Accuracy:

±2%

±2%

±2%

±2%

Frequency:

60Hz (same as input frequency)

Inverter Frequency Accuracy: 0.03%

0.03%

0.03%

0.03%

Input Power Factor:

>99%

>99%

>99%

>99%

THD (Resistive Load):

<1.5%

<1.5%

<1.5%

<1.5%

Transient Load Recovery Time: 0.4ms

0.4ms

0.4ms

0.4ms

Soft Start Time:

20s

20s

20s

20s

Max. Crest Factor @ No. Power: 3.5

3.5

3.5

3.5

Short Circuit Overload Capacity: Short Term Overload Capacity:

10 x ln for 20msec (AC to AC mode) 150% for 5 seconds

Permanent Overload Capacity: 110%

110%

110%

110%

Synchronization Range:

57 to 63Hz 57 to 63Hz 57 to 63Hz 57 to 63Hz

Display:
Communication Ports: Mechanical Dimensions H x W x D (in/mm): System Weight Without Modules (lb/kg): Module Dimensions H x W x D (in/mm): Module Weight (lb/kg): Clearance (in/mm)
Front: Rear: Sides: Top: Environment Operating Temperature: Storage Temperature: Humidity: Elevation: Standards
Safety:
EMC:
Features:

LCD Touch-screen Display (160 x 160 pixels), OK/Major/Minor 3-Color LED display, Web based GUI via Ethernet RJ45 Ethernet Port, R232 Port (Front)
84 x 23.6 x 26.8 / 213 x 600 x 680
595 / 270
3.5 x 4 x 17.1 / 88.9 x 102 x 435
11 / 5
33 / 838.2 12 / 304.8 No clearance required 12 / 304.8
-20 to 40°C / -4 to 104°F (full load) -40 to 70°C / -40 to 158°F Up to 95% non-condensing Up to 2000m / 6562ft above sea level
UL1778 (2nd Ed); CSA C22.2 No. 107.3-05 UPS General Safety FCC CFR47 Part 15 Class A; ICES-003 Unified system controller with integrated SNMP communications, Top AC and DC feed access; bottom DC feed access (All user connections are front access), AC input and output breaker/ disconnect switch, Industrial grade surge suppression (rated to 40kA)

Inverter Module DC Output

Nominal Voltage:

48Vdc

Voltage Range (max.):

48Vdc

48Vdc

48Vdc

40 to 60Vdc (User Adjustable)

Options:

Up to 8 x 1.8kW rectifier modules, Integrated maintenance bypass switch, Inverter DC input breakers, Service-entrance grade surge suppression: 140kA rating (per phase), Lockable rack front-door, Batteries (various sizes and technologies)

AMPS24HP
Modular AC and Hybrid Power System

> High performance AC and hybrid AC/DC backup power system offering

99.999% reliability for mission critical indoor applications

> 93% Efficiency, 15 year Design Life and MTBF (Mean Time

Between Failures) greater than 200,000 hours results in

class leading TCO (Total Cost of Ownership)

> Intelligent system controller with integrated SNMP for local

and remote management

> Hot swappable 1.5kVA/1.2kW inverter modules and 1.8kW

rectifier modules (optional for inverter only systems) offer complete

flexibility, scalability and low MTTR (Mean Time To Repair)

AMPS24

> Up to 24kVA/19.2kW small footprint system maybe installed in a 19" or 23"

open-relay rack or box bay rack/cabinet with flexible mounting options

AMPS24HP Hybrid Systems

Specifications*

Models:

AMPS24-3-13.5-H3

AMPS24-2-18-H4

AMPS24-2-9-H2

AMPS24-1-9-H2

AMPS24-1-4.5-H1

Input and Output Phase:

120/208V 3-ph

120/240 or 120/208V 2-ph

120V single ph

Nominal Output Power (max): 4500 to 13500VA

3000 to 18000VA

3000 to 9000VA

1500 to 9000VA

1500 to 4500VA

Output Power (Resistive Load): 3600 to 10800W

2400 to 14400W

2400 to 7200W

1200 to 7200W

1200 to 3600W

Max. Output Current:

37.5Arms per phase

75Arms per phase

37.5Arms per phase

75Arms per phase

37.5Arms per phase

41

Max. No. of 1500VA/1200W Inverter Modules Per System:

9

12

6

6

3

Min. No. of 1500VA/1200W Inverter Modules Per System:

3

2

2

1

1

Max. No. of 1800W Rectifier Modules Per System:

3

4

2

2

1

DC to AC Inverters

AMPS24HP Inverter Systems

Specifications*

Models:

AMPS24-3-18-3i

Input and Output Phase: Nominal Output Power (max): Output Power (Resistive Load): Max. Output Current: Max. No. of 1500VA/1200W Inverter Modules Per System: Min. No. of 1500VA/1200W Inverter Modules Per System: Technology: Static Switch: Efficiency: Waveform: Output Power Factor: Transfer Time: Warranty:

120/208V 3-ph 4500 to 18000VA 3600 to 14400W 50Arms per phase 12
3

Inverter Module AC Output

Power Rating:
Nominal Voltage:
Voltage Accuracy:
Frequency:
Inverter Frequency Accuracy:
THS (Resistive Load):
Transient Load Recovery Time:
Soft Start Time: Max. Crest Factor at Nominal Power: Short Circuit Overload Capacity: * Specifications subject to change.

AMPS24-2-24-4i

AMPS24-2-12-2i

120/240 or 120/208V 2-ph

3000 to 24000VA

3000 to 12000VA

2400 to 19200W

2400 to 9600W

100Arms per phase

50Arms per phase

16

8

AMPS24-1-12-2i

AMPS24-1-6-1i

120V single ph

1500 to 12000VA

1500 to 6000VA

3600 to 9600W

2400 to 4800W

100Arms per phase

50Arms per phase

8

4

2

2

1

1

Twin Sine Inverter (TSI) technology; each inverter module has DC and AC input Not required; each module has its own static switch
93% AC-to-AC; 90% DC-to-AC (from 50 to 100% full resistive load) Pure sine wave
0.8 (Can run capacitive and inductive loads) Zero transfer time
2 Years (1 and 3 year optional extensions)

1500VA/2000W 120Vac ±2
60Hz (same as input frequency) 0.03% <1.5% 0.4ms 20s 3.5
10 x In for 20msec (AC to AC mode)

Arcon Inverter Series
> High efficiency > Full Digital Signal Processing control > Outstanding response time > Input / Output Radio Frequency Interference compliant to FCC > Complete supervision possibility > Parallel operation in True Redundant System > Large DC input voltage range > Patented technology

Arcon Inverter

Acron Inverter Series

Specifications

Environment

Input

Storage Temperature:

-40 to 80°C / -40 to 176°F

Operating Voltage Range: Max. Input Current: Output

40 to 80Vdc 89%

Permissible Ambient Temperature:
Standards

-20 to 50°C / -4 to 122°F

42

Nominal Output Voltage:

120V, adjustable 108-125Vac

Output Voltage Tolerance: +3% of adjustable nominal voltage

Output Voltage Frequency: 50 or 60Hz, selectable

Total Harmonic Distortion: Less than 3% (on linear load at nominal power)

Total Transient Recovery Time: Less than 0.3 msec (typical)

Turn-on Delay:

Less than 3 sec

Nominal Value of Output Current: 29.1A

Crest Factor at Nominal Power: 2

Output Power

Safety: Protections:
Dielectric Strength:
Cooling: Mechanical Dimensions H x W x D (mm): Weight (lb/kg):

EN60950 / UL1950 Internal electronic + Relays + Fuses 4300Vdc input/output, 4300Vdc output/earth, 2000Vdc input/earth Forced
2RU x 436 x 440 33.1 / 15 (approximately)

DC to AC Inverters

Nominal Value: Overload: Permanent Overload:

3000W/3500VA 6000VA (±15%, 5 sec. max, self-protected) 110%

Power Factor Influence:

Full power output (3500VA) with Pf from 0 to 0.86 Limited to 3000W with Pf from 0.86 to 1

Electro-Magnetic Compatibility

Standards Applied For Immunity:

EN 61000-4-2 / 4-3 / 4-4 / 4-5 / 4-6

Standards Applied For Emission:

ETS300-132-2 CISPR 22 Class B

Efficiency:

More than 89% (Nominal power in Watts)

TEBEVERT Inverter Series
5 to 25kVA Inverter System
> NEBs level 3 certified to assure compatibility with the telecommunications environment
> Hot swappable 5kVA inverter modules > Hot swappable static switch module > Integrated maintenance bypass switch > Automatic master-slave operation > Up to five inverter modules can be paralleled
as load increases

TEBEVERT DSP

TEBERVERT Inverter Series

60Hz Models

60Hz Models

Output Capacity:

5 to 25kVA

120, 208, 220, 240, 480Vac

Max. Number of Modules: 5

Output Capacity:

5 to 25kVA

Input

Cooling:

Temperature controlled fans

Nominal Bypass AC Input:
Number of Bypass AC Phases:
Bypass AC Input Wiring:

120Vac 1 L, N, PE

208, 220, 240, 480Vac 2

Maintenance Bypass Switch:

Standard make-before-break mechanically interlocked switch provided on all models equipped with the static bypass module

43

L1, L2, PE

Remote Alarming:

(1) Form-C Summary Alarm, Optional Relay Card (8 Alarms), Optional SNMP

Nominal DC Input:
DC Input Range: Reflected DC Ripple (48Vdc) (120Vdc): Output

-48Vdc or 120Vdc (requires different inverter modules)

-15%

+20%

<2mV reverse

<2mV reverse

smoothing, <5% RMS smoothing, <5% RMS

LED Indicators (Inverter Modules):
LED Indicators (Static Bypass Module):
Metering:

Output present, fault, overload, AC synchronized, parallel operation
Power flow diagram, normal, fault, AC present, DC present, overload, load on bypass, load on inverter
(4) segment LCD display switchable between output voltage and current

Nominal AC Output Voltage: 120Vac Optional AC Output Voltage: 120/240Vac

120Vac 120/240Vac

Cabinet Dimensions H x W x D (in/mm):

84 x 23.6 x 23.6 / 2134 x 600 x 600

DC to AC Inverters

Output Voltage Regulation:
Output Power Factor: Output Voltage Waveform: Output Crest Factor: Output Voltage Distortion: Output Overcurrent Protection: Overload Rating (Inverters): Overload Rating (Static Bypass):

±5% for all combinations of line, load and temperature

0.7 lagging to 0.8 leading

PWM Sine wave

PWM Sine wave

2.8:1

2.8:1

<3% @ 100% rated linear load

Electronic current limiting

200% for approx. 75 cycles (1.25 seconds)

500% for 100ms

500% for 100ms

System Operating Efficiency:

>85% on-line mode >97% off-line mode

Frequency Stability: Module Capacity: Static Switch Transfer Time:

±0.1% free running, ±3% when AC present

5kVA/4kW

5kVA/4kW

<2ms

<2ms

Standards
Radio Interference: Safety Listing: Product Certification:
Environment
Seismic Rating: Elevation: Operating Temperature: Operating Humidity: Module Data Power Rating: Nominal Input Current (-48Vdc): Max. Input Current (-48Vdc): Output Current (120Vac):

Certified to Telecordia GR-1089 UL60950, UL, cUL Pending NEBS Level 3
NEBS Level 3, Seismic Zone 4 Optional 1800m / 6000ft, 4000m / 1300ft at 30°C/86°F -5 to 50°C / 23 to 122°F 0 to 95% non-condensing 5kVA 5000VA / 4000W 98A 115.4A 41.6A

Invertronic Inverter System
Modular 3 Phase Inverter System
> Hot swappable 10kVA modules each with built-in SBS for scalability
> Employs 4th Generation DSP Technology for dynamic step load response
> Integrated Manual Bypass Switch in primary cabinet 1 > Front door mounted Graphical Display of
Operating Mode and System Parameters > Remote Monitoring via Network (HTML, SNMP)

Invertronic Inverter System

Invertronic Inverter System

Electrical

System

Input

Static Bypass Switch (SBS): 3 Phase SCR bridge built into each module

Input Voltage:

Nominal: 48Vdc, Operating range 42 to 60Vdc

Input Current:

Max. 228A at 42Vdc at full load, Nominal: 138A at 54Vdc at 80% load

44

Inrush Current:

Soft-start circuit limits inrush to <25% of full load current

Output Inverter Module Rating:

10kVA/8kW at 0.8 power factor inductive

SBS Priority: Transfer Time: SBS Overload Capability: SBS Transfer Criteria:
Remote Alarming:

Inverter Priority Only; Offline mode not possible
SBS is make-before-break; 2ms typical, 6mm max.
120% for 10min; 1000% for 8ms
Overload, modules over temperature, short circuit on output, low DC voltage, manual initiation, output AC volts out of range
Mains Failure, Battery Failure, Loss of Redundancy, Common Failure Output

DC to AC Inverters

Max. System Capacity: Max. Modules Per Cabinet: Max. Cabinets: AC Output Voltage: AC Output Amps:

120kVA/96kW at 0.8 power factor inductive 6 2 120/208Vac 3 phase, 4 wire, Y connected 27.8A per phase at full load

Metering: Indicators: Mechanical
Module Dimensions H x W x D (in/mm):

Phase voltages, currents, kW, kVA 13 Programmable LEDs on front door display panel
8.75 x 19.9 x 17.7 / 222 x 505 x 450

AC Output Frequency:

60Hz ±.01% on internal crystal; tolerance is programmable when synced to mains

Max. Allowable Phase Imbalance:

100%, up to full load per phase current rating

Load Power Factor Range:

0.7 lagging (inductive) to 0.8 leading (capacitive) with standard UPS de-rating

Output Regulation:

Static: ±1%; Dynamic: ±5% max with 100% step load change, settling time: <10msec

Efficiency: Crest Factor Accommodated: Distortion: Overload Capability:

>86% 3.0 / 1 <2% THD into a linear load; pure sine wave output 120% for 10min; 200% for 200min

Module Weight (lb/kg):

99 / 45

Cabinet Dimensions H x W x D (in/mm):

84 x 24 x 31.5 / 2134 x 600 x 800

Cabinet Weight (lb/kg): Heat Output: Operating Temperature Range: Operating Humidity Range: Elevation:

528 / 240 <30000BTUs/hour/fully loaded cabinet at full power 0 to 40°C / 32 to 104°F 0 to 95% non-condensing Fully rated to 1000m / 3280ft

Standards

Safety:

EN 60950, UL 1778, UL 1950

Design:

NEBS Level 3 compliant (certification in progress), Zone 4 cabinets

Emissions: Immunity:

EN 62040-2 classification C3, FCC Class A EN 61000-4-4, EN 61000-4-5

Electrostatic Discharge Immunity:

EN 61000-4-2, (level: 4kV contact, 8kV air discharge)

Media Inverter System
TSI Media 48/120 Inverter Platform
> Scalable up to 3kVA > Enhanced Power Conversion Feature > Supports redundancy > Hot swappable > Input DC Breakers > Output AC Breakers > Optional NEMA Outlets

Media Inverter System

Media Inverter System

Electrical

Mechanical

AC Output Power Nominal Output Power**:

n x 1500VA

Dimension H x W x D (in/mm):

3.5 x 19 or 23 x 12.5 / 88.9 x 482.6 or 584.2 x 317.5

Output Power**:

n x 1200W (resistive load)

Weight (lb/kg):

14.4 + n x 5.3 / 7.9 + n x 2.4

Short Time Overload Capacity: 150% 15Sec

Material (Casing):

Coated steel

Permanent Overload Capacity: 110% @ 40°C / 104°F

General

45

Load Power Factor:

Full power rating from 0 inductive to 0 capacitive, internal temperature management and cut off

EMC (Immunity):

IEC 1000-4

AC Input

EMC (Emission):

FCC Part 15

Nominal Voltage (DC):

48Vdc

Safety:

UL 1778 (Ed.4) Listed

Voltage Range (DC):

40 to 58Vdc

Cooling:

Forced

Nominal Current (@ 40Vdc)**: n x 34A

MTBF:

>200,000hrs

DC to AC Inverters

Max. Input Current**:

n x 42A for 5sec

Efficiency (Max) Online:

90%

Voltage Ripple:

<1mV resistive load @ 54Vdc input voltage boundaries user selectable

Enhanced Power Conversion (EPC):

93%

DC Input

Nominal Voltage:

120 or 240Vac (Single or dual phase)

Voltage Range:

83 to 140Vac (each phase)

Conformity Range:

Adjustable

Power Factor:

>99%

Frequency Range:

50 to 60Hz (selectable)

Synchronization Range:

47 to 53Hz / 57 to 63Hz

Transfer Performance

Total Transient Voltage Duration: 0s (transient free)

AC Output

Nominal Voltage:

120 or 240Vac (Single or dual phase)

Adjustable Voltage Range: 90 to 130Vac

Voltage Accuracy:

2%

Frequency:

50 to 60Hz

Frequency Accuracy:

0.03%

Total Harmonic Distortion: <3% (resistive load)

Load Impact Recovery Time: 0.4ms

Turn On Delay:

30s

Nominal Current**:

n x 12.5A (protected against reverse current)

Crest Factor @ Nominal Power: 2.2 with short circuit management and protection

Dielectric Strength DC/AC (@ 0.6mA):

4,300Vdc

RoHS-6:

Compliant

Connection I/O:

Terminal block or NEMA receptacle or Twist Locks or combo AC output receptacles
Protected against reversed polarity Self adaptive to wide operating conditions

Environment Elevation:

<1500m / 4921ft

Ambient Temperature**:

n x 1500VA, -20 to 40°C / -4 to 104°F, Pmax @ 100% Load, de-rating up to 65°C / 149°F

Storage Temperature:

-40 to 70°C / -40 to 158°F

Humidity:

95% non-condensing

Signaling and Supervision

Display:

Synoptic LED

Alarms Output:

Dry contacts on shelf (optional)

Supervision:

Use optional devices, Comprehensive table of troubleshooting codes

* Operation within lower voltage networks leads to derating of power performances ** "n" stands for Number of Modules in parallel

Short Circuit Clear Up Capacity:

10 x In for 20sec Available while Mains is available at AC input port;
with magnitude control and management

DSP Inverter Series
1 to 15kVA Inverter System
> Nebs level 3 certified to assure compatibility with the telecommunications environment
> Fourth generation DSP architecture utilizing SMD for high reliability
> Hot swappable EUE static switch and inverter modules > 6 or 15kVA EUE static switch available

DSP inverter

DSP Inverter Series

Inverter Module Rating: 1kVA

2.5kVA

Nominal System Output Capacity with One Rack Shelf:

1 to 5kVA (6kVA w/o EUE)

2.5 to 12.5kVA (15kVA w/o EUE)

Nominal Bypass AC Input: 120Vac

120Vac

Number of Bypass AC Phases: 1

1

Bypass AC Input Wiring:

L, N, PE

L, N, PE

Bypass Voltage Tolerance: ±10% (Adjustable ±5% to ±15%)

±10% (Adjustable ±5% to ±15%)

Maximum System Capacity with Two Rack

Shelves, without EUE:

12kVA

46

Nominal DC Input:

-48Vdc

30kVA -48Vdc

DC Input Range:

40.8 to 60Vdc

40.8 to 60Vdc

Power Rating:

1000VA / 800W

2500VA / 2000W

Nominal Input Current (-48Vdc): 19A

47A

DC to AC Inverters

Maximum Input Current:

22.5A

55A

Output

Output Current (120Vac):

8.33A

20.83A

Nominal Output Voltage:

120Vac

120Vac

Output Voltage Regulation:

±5% for all combinations of line, load and temperature

Output Power Factor:

0.7 lagging to 0.8 leading

0.7 lagging to 0.8 leading

Output Voltage Waveform: DSP Sine wave

DSP Sine wave

Output Crest Factor:

2.8:1

2.8:1

Output Voltage Distortion: Output Overcurrent Protection: Overload Rating (Inverters): Overload Rating (Static Bypass): Optional Maintenance Bypass Switch: Inverter Module Rating:

<3% @ 100% rated linear load Electronic current limiting
500% for 100mS

<3% @ 100% rated linear load Electronic current limiting 110% continuous, 120% for ~1 minute, 200% for ~4 seconds 500% for 100mS

Internally mounted, Make-before-break mechanically interlocked switch provided on all models equipped with the EUE static bypass module

1kVA

2.5kVA

Remote Alarming:

(1) Form-C Inverter fault, (1) Form-C Static Switch fault

LED Indicators (Inverter Modules):

On, Output present, DC Input OK, Inverter Fault, Parallel Operation, Overload, Bar graph for output power

Display/Metering (EUE, Static Bypass Module):

Graphic Display (Menu Driven, password protected), Power flow diagram, LED's (Normal, fault)

Mechanical

Rack Shelf Dimensions (in/mm): 12.25 x 23 x 19.8 / 311 x 584 x 503

12.25 x 23 x 25.25 / 311 x 584 x 590

Weight (lb/kg):

11 / 5

17.6 / 8

Environment

Elevation:

<3000m / 10000ft without derating

<3000m / 10000ft without derating

Operating Temperature:

0 to 55°C / 32 to 131°F

0 to 55°C / 32 to 131°F

Operating Humidity: Standards

0 to 95% non-condensing

0 to 95% non-condensing

Radio Interference:

Certified to Telecorodia GR-1089

Certified to Telecorodia GR-1089

Safety Listing:

UL60950

UL60950

Product Certification:

NEBS Level 3, Seismic Zone 4

NEBS Level 3, Seismic Zone 4

MS Power Inverter Series
1 and 2kVA Inverter System

> Standard 19"/23", 2RU rack mount > 1kVA/800W and 2kVA/1600W > Pure sine wave output > Utility bypass function > UL/cUL approved > RS-232 communication > Internal "over temperature" protection > Input reverse polarity protection > Output overload protection

MS Power Inverter

MS Power Inverter Series

Models

Majorsine1000-24-2U

Majorsine1000-48-2U

Majorsine2000-48-2U

Input

Voltage: Rated Current: Protection: Efficiency:

20 to 30Vdc 50A Fuse and DC Breaker

40 to 60Vdc

40 to 60Vdc

25A

50A

Fuse and DC Breaker

Fuse and DC Breaker

>85% (full linear load), 24Vdc I/P, 120Vac O/P

Output (Backup)

Capacity:

1kVA / 800W

1kVA / 800W

2kVA / 1600W

Voltage:

110, 115, 120, 125Vac

110, 115, 120, 125Vac

110, 115, 120, 125Vac

47

Voltage Regulation:

±2%

±2%

±2%

Frequency:

50/60Hz ±0.2Hz

50/60Hz ±0.2Hz

50/60Hz ±0.2Hz

Waveform:

Pure sine wave

Pure sine wave

Pure sine wave

THD (Linear Load):

3% 120V/100%

3% 120V/100%

3% 120V/100%

THD (SPS Load):

5% 120V/100%

5% 120V/100%

5% 120V/100%

Crest Factor:

31

31

31

Receptacles:

(4) NEMA 5-20R outlets

(4) NEMA 5-15R outlets

(4) NEMA 5-20R outlets

DC to AC Inverters

Utility Power (Bypass)

Voltage (Nominal): Frequency: Protection: Communication: LED Display:

120Vac 60 ±5Hz AC Circuit Breaker RS232 / Dry-contact Inverter ON, Overload, DC Abnormal

120Vac 60 ±5Hz AC Circuit Breaker RS232 / Dry-contact Inverter ON, Overload, DC Abnormal

120Vac 60 ±5Hz AC Circuit Breaker RS232 / Dry-contact Inverter ON, Overload, DC Abnormal

LCD Display:

Inverter ON, Output voltage and frequency, Input voltage, Load percentage, DC voltage, System model, Internal environment temp., Utility status, Short circuit, Over temp.

Protection

Short: Overload: Temperature:

For 1 second; Switch to bypass, then shutdown

105 to 125% for 3 minutes; 126 to 150% for 3 seconds; >150% for 1 second; Switch to bypass

55° ±5°C (Inside the case) 131° ±41°F

55° ±5°C (Inside the case) 131° ±41°F

55° ±5°C (Inside the case) 131° ±41°F

Environment

Operating Temperature: Storage Temperature: Humidity: Acoustic Noise: Safety: EMI / RFI:

0 to 50°C / 32 to 122°F -20 to 70°C / -4 to 158°F 0 to 90°C / 32 to 194°F non-condensing 46dBA @ 1 M UL / cUL FCC Class A

0 to 50°C / 32 to 122°F -20 to 70°C / -4 to 158°F 0 to 90°C / 32 to 194°F non-condensing 46dBA @ 1 M UL / cUL FCC Class A

0 to 50°C / 32 to 122°F -20 to 70°C / -4 to 158°F 0 to 90°C / 32 to 194°F non-condensing 46dBA @ 1 M UL / cUL FCC Class A

Mechanical

Dimensions H x W x D (in/mm):

Weight (lb/kg):

15.4 / 7

3.5 x 17.3 x 11.8 / 88 x 440 x 300, 2RU 15.4 / 7

17.6 / 8

Single and Three Phase UPS

> AMPS80HP
Alpha's new high performance AC or hybrid AC/DC system offers telecom grade reliability, 94% efficiency and high power density. The AMPS80 features hot swappable 2.5kVA/ 2.0kW inverter modules and optional 1.8kW rectifier. The AMPS80 meets your current and future power needs by allowing you to purchase and install individual modules for the ultimate flexibility to scale up or down. Front access and user-friendly connections make the system easy to install, service and upgrade.

> AMPS24HP
The AMPS24 features hot swappable 1.5kVA/1.2kW inverter modules and 1.8kW rectifier modules that are the building blocks of a highly reliable power system utilizing 48Vdc batteries. The AMPS24 meets your current and future needs by allowing them to purchase only the power modules for current needs while having ultimate flexibility to scaleup or down, depending on future power needs.

> EX UPS
The EX UPS offers high-performance power protection. With the ability to be rack mounted or a standalone tower, this UPS is ideal for mid-range servers, networks, IT equipment, and medical and storage devices. With a low cost of ownership and a broad range of features, the EX UPS is one of the best in its class.

> EX RT UPS

The EX RT UPS is a UPS designed for sensitive high-density server environments and harsh industrial applications. Specifically engineered to meet demanding customer applications in IT systems,

measuring instruments, PLCs and industrial PC markets, the EX RT is fully compatible with genset

redundancy requirements in most instances. The manual bypass, hot swappable I/O box and intuitive

49

LCD control panel are just a few of the many differentiating features that make the EX RT the ideal

product for the 5-11kVA power range.

Single and Three Phase UPS

> 1600XP Series
The 1600XP series offers a tower design solution with a LCD touchscreen display that provides unmatched access for UPS monitoring and control. As a double conversion on-line UPS, it is able to supply uninterrupted, clean single-phase power to your critical systems while keeping batteries charged continuously.

> TrinitiTM 4200 Series
The Alpha Triniti Series three phase UPS incorporates dual conversion technology designed to provide power conditioning for sensitive headend electronics, regardless of the quality of the utility or generator input power. Its unique active front end design provides power factor correction. In addition to providing utility cost savings, this feature provides compatibility with most existing headend generators, including those with mechanical governors running at near capacity.

> Galaxy
The Galaxy Series is the world's first data-center grade UPS designed specifically for mid-range enterprise level applications. The AlphaSource Galaxy delivers the optimum level of reliability, availability and scalability demanded by the new generation of critical enterprise applications.

> G9000
Using IGBT technology in the rectifier/converter, DC/DC chopper and inverter sections, the G9000 Series' double-conversion topology provides an AC/DC/AC efficiency of 97% at loads from 50 to 100%. Even at 20% loading, the efficiency remains greater than 95%. This industry-leading performance makes the G9000 the perfect solution for N+1 parallel systems where loads are typically 30 to 40%.

> Symmetra PX
The Symmetra PX 100kW is a world-class, high-efficiency power protection system designed to cost-effectively provide redundancy and high levels of availability in a two-rack footprint. The hot scalable Symmetra PX 100 provides up to 100kW of modular power protection for 208V deployments, as well as hot swappable long-life batteries and power distribution.

AMPS80HP
Modular AC UPS System

> High performance AC or hybrid AC/DC backup power system offering 99.999% availability
> 94% Efficiency, 15 year Design Life and MTBF (Mean Time Between Failures) greater than 200,000 hours
> Intelligent system controller with integrated SNMP for local and remote management of AC and DC power modules, batteries, and other peripherals
> Hot swappable 2.5kVA/2.0kW inverter modules and optional 1.8kW rectifier modules
> Small footprint system offers up to 75kVA/60kW in a single 19" box bay rack

AMPS80

AMPS80HP

Model

AMPS80- AMPS80- AMPS80- AMPS80-

3-75

3-30

2-40

1-20

Max. DC Input Current @ 48Vdc:

1375A

550A

734A

366A

Input and Output Phase:

120/208V 3-ph

120/240 or 120 single 120/208V2-ph ph

@ 40Vdc: Voltage Ripple:

1700A

680A

900A

<2mV / <38dbrnc

450A

Single and Three Phase UPS

Output Capacity:
50
Output Power

7500 to 75000VA
6000 to

7500 to 30000VA
6000 to

5000 to 40000VA
4000 to

2500 to 20000VA
2000 to

Unified System Controller with Integrated SNMP

Control and Monitoring:

Configure, control and monitor inverter and rectifier modules via Internet Explorer 7 onwards

(Resistive Load):

60000W 24000W 32000W 16000W

LCD Touch-screen Display (160 x 160 pixels),

Maximum Output Current:

208Arms per phase

83Arms per phase

168Arms per phase

168Arms

Display:

OK/Major/Minor 3-Color LED display, Web based GUI via Ethernet

Max./Min. No. of 2500VA/2000W Inverter Modules:

30/3

12/3

16/2

8/1

Communication Ports: Mechanical

RJ45 Ethernet Port, R232 Port (Front)

Technology:

Twin Sine Inverter (TSI) technology; each inverter module has DC input and AC input

Dimensions H x W x D (in/mm):

84 x 23.6 x 26.8 / 213 x 600 x 680

Static Switch: Efficiency: Waveform:

Not required; each module has its own static switch
94% AC to AC; 90% DC to AC (from 50 to 100% full resistive load)
Pure sine wave

System Weight Without Modules (lb/kg):
Module Dimensions H x W x D (in/mm):

595 / 270 3.5 x 4 x 17.1 / 88.9 x 102 x 435

Output Power Factor:

0.8 (can run capacitive and inductive loads)

Module Weight (lb/kg):

11 / 5

Transfer Time:

Zero transfer time

Clearance (in/mm)

Warranty:

2 year standard (1 and 3 year optional extensions)

Front:

33 / 838.2

Inverter Module AC Output

Power Rating:

Voltage Range (AC):

90 to 140V

Voltage Accuracy:

±2%

2500VA/2000W

90 to 140V 90 to 140V

±2%

±2%

90 to 140V ±2%

Rear: Sides: Top: Environment

12 / 304.8 No clearance required 12 / 304.8

Frequency:

60Hz (same as input frequency)

Operating Temperature:

-20 to 40°C / -4 to 104°F (full load)

Inverter Frequency Accuracy: 0.03%

0.03%

0.03%

0.03%

Storage Temperature:

-40 to 70°C / -40 to 158°F

Input Power Factor:

>99%

>99%

>99%

>99%

Humidity:

Up to 95% non-condensing

THD (Resistive Load):

<1.5%

<1.5%

<1.5%

<1.5%

Elevation:

Up to 2000m / 6562ft above sea level

Transient Load Recovery Time: 0.4ms

0.4ms

0.4ms

0.4ms

Standards

Soft Start Time:

20s

20s

20s

20s

Max. Crest Factor @ No. Power: 3.5

3.5

3.5

3.5

Short Circuit Overload Capacity: Short Term Overload Capacity:

10 x ln for 20msec (AC to AC mode) 150% for 5 seconds

Permanent Overload Capacity: 110%

110%

110%

110%

Synchronization Range:

57 to 63Hz 57 to 63Hz 57 to 63Hz 57 to 63Hz

Inverter Module DC Output

Safety: EMC:
Features:

UL1778 (2nd Ed); CSA C22.2 No. 107.3-05 UPS General Safety
FCC CFR47 Part 15 Class A; ICES-003
Unified system controller with integrated SNMP communications, Top AC and DC feed access; bottom DC feed access (All user connections are front access), AC input and output breaker/ disconnect switch, Industrial grade surge suppression (rated to 40kA)

Nominal Voltage: Voltage Range (max.):

48Vdc

48Vdc

48Vdc

48Vdc

40 to 60Vdc (User Adjustable)

Options:

Up to 8 x 1.8kW rectifier modules, Integrated maintenance bypass switch, Inverter DC input breakers, Service-entrance grade surge suppression: 140kA rating (per phase), Lockable rack front-door, Batteries (various sizes and technologies)

AMPS24HP
Modular AC and Hybrid Power System

> High performance AC and hybrid AC/DC backup power system offering

99.999% reliability for mission critical indoor applications

> 93% Efficiency, 15 year Design Life and MTBF (Mean Time

Between Failures) greater than 200,000 hours results in

class leading TCO (Total Cost of Ownership)

> Intelligent system controller with integrated SNMP for local

and remote management

> Hot swappable 1.5kVA/1.2kW inverter modules and 1.8kW

rectifier modules (optional for inverter only systems) offer complete

flexibility, scalability and low MTTR (Mean Time To Repair)

AMPS24

> Up to 24kVA/19.2kW small footprint system maybe installed in a 19" or 23"

open-relay rack or box bay rack/cabinet with flexible mounting options

AMPS24HP Hybrid Systems

Specifications*

Models:

AMPS24-3-13.5-H3

AMPS24-2-18-H4

AMPS24-2-9-H2

AMPS24-1-9-H2

AMPS24-1-4.5-H1

Input and Output Phase:

120/208V 3-ph

120/240 or 120/208V 2-ph

120V single ph

Nominal Output Power (max): 4500 to 13500VA

3000 to 18000VA

3000 to 9000VA

1500 to 9000VA

1500 to 4500VA

Output Power (Resistive Load): 3600 to 10800W

2400 to 14400W

2400 to 7200W

1200 to 7200W

1200 to 3600W

Max. Output Current:

37.5Arms per phase

75Arms per phase

37.5Arms per phase

75Arms per phase

37.5Arms per phase

51

Max. No. of 1500VA/1200W Inverter Modules Per System:

9

12

6

6

3

Min. No. of 1500VA/1200W Inverter Modules Per System:

3

2

2

1

1

Max. No. of 1800W Rectifier Modules Per System:

3

4

2

2

1

Single and Three Phase UPS

AMPS24HP Inverter Systems

Specifications*

Models:

AMPS24-3-18-3i

Input and Output Phase: Nominal Output Power (max): Output Power (Resistive Load): Max. Output Current: Max. No. of 1500VA/1200W Inverter Modules Per System: Min. No. of 1500VA/1200W Inverter Modules Per System: Technology: Static Switch: Efficiency: Waveform: Output Power Factor: Transfer Time: Warranty:

120/208V 3-ph 4500 to 18000VA 3600 to 14400W 50Arms per phase 12
3

Inverter Module AC Output

Power Rating:
Nominal Voltage:
Voltage Accuracy:
Frequency:
Inverter Frequency Accuracy:
THS (Resistive Load):
Transient Load Recovery Time:
Soft Start Time: Max. Crest Factor at Nominal Power: Short Circuit Overload Capacity: * Specifications subject to change.

AMPS24-2-24-4i

AMPS24-2-12-2i

120/240 or 120/208V 2-ph

3000 to 24000VA

3000 to 12000VA

2400 to 19200W

2400 to 9600W

100Arms per phase

50Arms per phase

16

8

AMPS24-1-12-2i

AMPS24-1-6-1i

120V single ph

1500 to 12000VA

1500 to 6000VA

3600 to 9600W

2400 to 4800W

100Arms per phase

50Arms per phase

8

4

2

2

1

1

Twin Sine Inverter (TSI) technology; each inverter module has DC and AC input Not required; each module has its own static switch
93% AC-to-AC; 90% DC-to-AC (from 50 to 100% full resistive load) Pure sine wave
0.8 (Can run capacitive and inductive loads) Zero transfer time
2 Years (1 and 3 year optional extensions)

1500VA/2000W 120Vac ±2
60Hz (same as input frequency) 0.03% <1.5% 0.4ms 20s 3.5
10 x In for 20msec (AC to AC mode)

EX UPS
> Double conversion UPS technology for 100% compatibility with any application, environment or genset and high output to protect equipment with PFC power supplies
> Wide input voltage window to conserve battery time for blackouts only
> Automatic bypass for high availability

EX UPS Mini Tower

EX UPS

Models

Specifications

Input Voltage:

Frequency Range:

Rating:

Input Connection:

Topology:

Output Voltage:

52

Output Frequency:

Output Receptacle:

Additional Outputs with HotSwap MBP:

PULSL700T
40 to 70Hz 700VA / 630W 5-15P
(4) 5-15R (4) NEMA 5-15R

PULSL1000T

PULSL1500T

PULSL1000R-XL2U PULSL1500R-XL2U

100/120/140/1601 to 248V

40 to 70Hz

40 to 70Hz

40 to 70Hz

1000VA / 900W

1500VA / 1350W

1000VA / 900W

5-15P

5-15P

5-15P

Online double conversion with automatic bypass and power factor correction

120V (adjustable to 100/110/127V)

50/60Hz, auto-select or frequency converter mode2

(4) 5-15R

(4) 5-15R

(6) 5-15R

(4) NEMA 5-15R

(4) NEMA 5-15R

(4) NEMA 5-15R

40 to 70Hz 1500VA / 1350W 5-15P
(6) 5-15R (4) NEMA 5-15R

Additional Outputs with FlexPDU:

NEMA L5-20R

NEMA L5-20R

NEMA L5-20R

NEMA L5-20R

NEMA L5-20R

Single Phase UPS

Mechanical

Configuration:

Mini Tower

Mini Tower

Mini Tower

Rack

Rack

Dimensions H x W x D (in/mm):

9.5 x 6 x 17.3 / 241.3 x 152.4 x 439.4

9.5 x 6 x 19.3 / 241.3 x 152.4 x 490.2

3.5 x 17.3 x 19 / 88.9 x 439.4 x 482.6

Weight (lb/kg):

25.7 / 11.7

33 / 15

39.6 / 18

39.6 / 18

45 / 20.4

Communication and Management

Indicators: Display: Communication Ports: Communication Card Slots:

(3) LEDs with adjustable multilingual display Display of measurements, access to control and setup menus (1) USB port, (1) RS232 serial port and relay contacts3, (1) mini terminal block for remote on/off and emergency stop (1) Slot for NMC Mini-Slot 206 card, NMC ModBus/JBux or MC Contacts/Serial

Environment

Operating Temperature: Noise Level:

0 to 40°C / 32 to 104°F 45dBA

0 to 40°C / 32 to 104°F 45dBA

0 to 40°C / 32 to 104°F 45dBA

0 to 40°C / 32 to 104°F 45dBA

0 to 40°C / 32 to 104°F 45dBA

Standards

Performance/Safety/EMC: Approvals:

IEC 62 040-3 (VFI-SS-113), IEC 62 040-1-1, IEC 60 950-1 (RD), FCC Subpart B, Class A UL, cUL, CE CB report

Warranty

2 year factory warranty

Notes: 1 Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA); for active output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively 2 Derated by 15% when used as a frequency converter 3 USB and RS232 serial ports cannot be used simultaneously

EX UPS
> Extended runtime capabilities with multiple, hot swappable battery modules (optional)
> Remote reboot of locked equipment, sequential start-up through individually switchable outlets

EX UPS Rack/Tower 2RU

EX UPS

Models

PULSML2200-XL2U PULSML2200-XL3U PULSML3000-XL2U PULSML3000-XL3U PULSML3000-XL3UXL

Specifications

Input Voltage:

501 - 100 to 142V

501 - 100 to 142V

501 - 100 to 142V

501 - 100 to 142V

501 - 100 to 142V

Frequency Range:

40 to 70Hz

40 to 70Hz

40 to 70Hz

40 to 70Hz

40 to 70Hz

Rating:

2100/1650

2100/1650

3000/2550

3000/2550

3000/2550

Input Connection:

5-20P

5-20P

L5-30P

L5-30P

L5-30P

Topology:

Online with automatic bypass and power factor correction

Output Voltage:

120V (adjustable to 100/110/127V)

Output Frequency:

50/60Hz, auto-select or frequency converter mode2

53

Output Receptacle:

(6) NEMA 5-20R + (1) NEMA L5-20R

(6) NEMA 5-20R + (1) NEMA L5-20R

(6) NEMA 5-20R + (1) NEMA L5-30R

(6) NEMA 5-20R + (1) NEMA L5-30R

(6) NEMA 5-20R + (1) NEMA L5-30R

Additional Outputs with HotSwap MBP:

(5) NEMA 5-15R or (5) NEMA 5-20R

Single Phase UPS

Additional Outputs with FlexPDU:

(10) NEMA 5-15R or (10) NEMA 5-20R or (8) NEMA L5-20R

Mechanical Configuration:

Rack/Tower 2RU

Rack/Tower 3RU

Rack/Tower 2RU

Rack/Tower 3RU

Rack/Tower 3RU XL

Dimensions H x W x D (in/mm):

3.4 (2RU) x 17.3 x 25.2 / 5.1 (3RU) x 17.3 x 19.3 / 3.4 (2RU) x 17.3 x 25.2 / 5.1 (3RU) x 17.3 x 19.3 / 5.1 (3RU) x 17.3 x 19.3 /

86.4 x 439.4 x 640.1

129.5 x 439.4 x 490.2

86.4 x 439.4 x 640.1

129.5 x 439.4 x 490.2

129.5 x 439.4 x 490.2

Weight (lb/kg):

68.2 / 30.9

68.2 / 30.9

68.2 / 30.9

66 / 29.9

66 / 29.9

Communication and Management

Indicators:

(3) LEDs with adjustable multilingual display

Display:

Display of measurements, access to control and setup menus

Communication Ports:

(1) USB port, (1) RS232 serial port and relay contacts3, (1) mini terminal block for remote on/off and emergency stop

Communication Card Slots:

(1) Slot for NMC Mini-Slot 2006 card, NMC ModBus/JBus or MC Contacts/Serial

Environment

Operating Temperature:

0 to 40°C / 32 to 104°F 0 to 40°C / 32 to 104°F 0 to 40°C / 32 to 104°F 0 to 40°C / 32 to 104°F 0 to 40°C / 32 to 104°F

Noise Level:

45dBA

45dBA

45dBA

45dBA

45dBA

Standards

Performance/Safety/EMC:

IEC/EN 62-040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 -50-1 (RD), IEC/EN 62 040-2 C1, FCC Subpart B, Class A

Approvals:

CE, TüV, CB Report, UL and CUL (CSA)

Notes: 1 Lower limits for reduced load 2 Derated by 15% when used as a frequency converter 3 USB and RS232 serial ports cannot be used simultaneously

EX RT UPS
> Internal static bypass > Input/output (I/0) box with manual bypass > Large input voltage range without using battery power > 40 to 70Hz input frequency range > Standalone solution with modular design for industrial needs > Communications slot compatible with multiple
communication card protocols

EX RT UPS

EX RT UPS

Models

EXRTG5000-XL6UMS

EXRTG7000-XL6UMS

EXRTG11000-XL6UMS

Configuration:

Rack/Tower

Rack/Tower

Rack/Tower

Specifications

Nominal Input Voltage: Input Voltage Range:

Input Frequency Range:

Rating:

Input Connection:

54

Topology:

Output Voltage:

Output Frequency:

120 to 280V @ 70% rated output

120 to 280V @ 70% rated output

120 to 280V @ 70% rated output

156 to 280V @ 100% rated output 40 to 70Hz, frequency converter as a standard 5000VA/4000W

156 to 280V @ 100% rated output 40 to 70Hz, frequency converter as a standard 7000VA/4900W

156 to 280V @ 100% rated output 40 to 70Hz, frequency converter as a standard 11000/8000W

Hardwired

Hardwired

Hardwired

Online with automatic bypass

Online with automatic bypass

Online with automatic bypass

200/2081/220/230/240/250; 120V output voltage available with transformer

50/60Hz auto -select

Output Receptacle: Overall Efficiency:

Hardwired 90 to 97% (Online mode - ECO mode)

Hardwired 90 to 97% (Online mode - ECO mode)

Hardwired 90 to 97% (Online mode - ECO mode)

Single Phase UPS

Harmonic Current Distortion: Crest Factor:

<5% 3:1

<5% 3:1

<5% 3:1

Overload Capacity:
Battery Test:
Operating Temperature:
Block Power Module Input/Output terminal Block: Maximum Wire Size (Solid or Standard Wire): Step-Down Transformer:
Output Configuration:

2 min if 120%<overload<110%, 1 min if 110%<overload<125%, 30 sec if 125%<overload<150%, 500 msec if overload>150%

Weekly without load interruption2
45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F

Weekly without load interruption2
45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F

Weekly without load interruption2
45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F

Hardwired

Hardwired

Hardwired

5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
120/208/240Vac output

5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
120/208/240Vac output

5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
120/208/240Vac output

Terminal block, plus (2) NEMA L6-30R (208V), (8) NEMA 5-20R; optional PDUs for additional NEMA or IEC receptacles

Mechanical

Configuration: Dimensions H x W x D (in/mm): Weight (lb/kg):

Rack/Tower 10.3 (6RU) x 17.5 x 26.3 / 261.6 x 444.5 x 668 192 / 87.1

Rack/Tower 10.3 (6RU) x 17.5 x 26.3 / 261.6 x 444.5 x 668 192 / 87.1

Rack/Tower 10.3 (6RU) x 17.5 x 26.3 / 261.6 x 444.5 x 668 211 / 95.7

Communication

Communication Ports Type: Communication Card Slots:

(6) Voltage-free dry contacts DB-9 rated at 2A 48Vdc, (1) RS 232, (1) RJ11 for RPO (Remote Power Off) (1) Slot for Mini-Slot communication card [Network Management Card (SNMP/Web), NMC ModBus/JBus, MC Contacts/Serial]

Standards

Performance and Safety: EMC:

IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards IEC 62040-2; EN 50091-2; FCC Class A

Warranty

2 years, parts and labor (US and Canada)

Notes: 1 Default voltage 2 Configurable to daily or monthly

EX RT UPS

> Versatile 6RU rack or tower design > Multilingual LCD > Integrated NEMA receptacles included
with transformer configuration > Optional rack mount PDU with NEMA
or IEC sockets to facilitate power distribution within the enclosure

EX RT UPS

EX RT UPS

Models

EXRTL5000-XL9UMS

EXRTL7000-XL9UMS

EXRTL11000-XL9UMS

Specifications

Nominal Input Voltage:

120 to 280V @ 70% rated output

120 to 280V @ 70% rated output

120 to 280V @ 70% rated output

Input Voltage Range:

156 to 280V @ 100% rated output

156 to 280V @ 100% rated output

156 to 280V @ 100% rated output

Input Frequency Range:

40 to 70Hz, frequency converter as a standard 40 to 70Hz, frequency converter as a standard 40 to 70Hz, frequency converter as a standard

Rating:

5000VA/4000W

7000VA/4900W

11000/8000W

Input Connection:

Hardwired

Hardwired

Hardwired

Topology:

Online with automatic bypass

Online with automatic bypass

Online with automatic bypass

Output Voltage: Output Frequency:

200/2081/220/230/240/250; 120V output voltage available with transformer

55

50/60Hz auto -select

Output Receptacle:

Hardwired + (2) NEMA L6-30R + (8) NEMA 5-20R

Overall Efficiency:

90 to 97% (Online mode - ECO mode)

90 to 97% (Online mode - ECO mode)

90 to 97% (Online mode - ECO mode)

Harmonic Current Distortion: <5%

<5%

<5%

Crest Factor:

3:1

3:1

3:1

Overload Capacity:

2 min if 120%<overload<110%, 1 min if 110%<overload<125%, 30 sec if 125%<overload<150%, 500 msec if overload>150%

Battery Test:

Weekly without load interruption2

Weekly without load interruption2

Weekly without load interruption2

Operating Temperature:

45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F 45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F 45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F

Block Power Module Input/Output terminal Block:

Hardwired

Hardwired

Hardwired

Single Phase UPS

Maximum Wire Size (Solid or Standard Wire):

5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG

5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG

5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG

Step-Down Transformer: Output Configuration:

120/208/240Vac output

120/208/240Vac output

120/208/240Vac output

Terminal block, plus (2) NEMA L6-30R (208V), (8) NEMA 5-20R; optional PDUs for additional NEMA or IEC receptacles

Mechanical

Configuration:

Rack/Tower

Rack/Tower

Rack/Tower

Dimensions H x W x D (in/mm):

15.5 (9RU) x 17.5 x 26.3 / 393.7 x 444.5 x 668

15.5 (9RU) x 17.5 x 26.3 / 393.7 x 444.5 x 668

15.5 (9RU) x 17.5 x 26.3 / 393.7 x 444.5 x 668

Weight (lb/kg):

365 / 165.6

365 / 165.6

384 / 174.2

Communication

Communication Ports Type: Communication Card Slots:

(6) Voltage-free dry contacts DB-9 rated at 2A 48Vdc, (1) RS 232, (1) RJ11 for RPO (Remote Power Off) (1) Slot for Mini-Slot communication card [Network Management Card (SNMP/Web), NMC ModBus/JBus, MC Contacts/Serial]

Standards

Performance and Safety: EMC: Warranty 2 years, parts and labor (US and Canada)

IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards IEC 62040-2; EN 50091-2; FCC Class A

Notes: 1 Default voltage 2 Configurable to daily or monthly

1600 XP Series
Single Phase UPS

> True on-line, double conversion UPS > Electronic power factor correction for 100% generator compatibility > User-friendly, programmable touch-screen display > Internal isolation transformer > Hot swappable battery packs and cooling fans > External battery connector > SNMP/Web-based monitoring

1600 XP Series

1600 XP Series

Power Rating

3.6kVA / 3.1kW 6kVA / 5.1kW 8kVA / 6.8kW 10kVA / 8.5kW 14kVA / 11.9kW 18kVA / 15.3kW 22kVA / 18.7kW

Specifications

Topology: Certifications: Input

True on-line, double conversion; IGBT power factor corrected input; internal isolation transformer UL 1778, CUL, CE, FCC Class A, IEEE 587, ANSI/C62.41, ISO 9001, ISO 14001, NEMA/PE1-1993, RoHs

Input Voltage:

Single-phase 208/240Vac (Three-wire input/L-L, G); 230Vac (Three-wire input/L, N, G), +10 to 30%

Input Frequency:

45 to 65Hz (Auto Sensing)

Input Power Factor:

>0.95 for all loads >0.95 for all loads >0.95 for all loads >0.95 for all loads >0.95 for all loads >0.95 for all loads >0.95 for all loads

Input Current THD:

>5% (Even for 100% non-linear loads)

AC Input Breaker Rating: 30A

50A

60A

63A

100A

100A

125A

Battery

56

Battery Type:

Valve-regulated lead acid; flame retardant (9Amp Hr)

Backup Time (Fully Charged):

7 minutes

7 minutes

7 minutes

5 minutes

7 minutes

5 minutes

3 minutes

0.85 Power factor; 25°C / 77°F; Approx. 30% more runtime for output power factor of 0.7 (Triple backup time at 1/2 load)

Recharge Time:

24 Hours (full), 12 Hours (90%)

DC Link:

144Vdc

216Vdc

288Vdc

288Vdc

288Vdc

288Vdc

288Vdc

Output

Single Phase UPS

Output Voltage: Output Voltage Regulation: Output Frequency: Output Voltage THD: Common Mode Noise: Rated-Load Power Factor: Rated Output Current @ 240V: Max. Peak Output Current: Overload Capacity: Environmental

Single-phase 240/208/120Vac (Four-wire output/L-L, N, G); 230Vac (Three-wire Output L, N, G)

±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical

50/60Hz; ±0.5Hz/1.0Hz/1.5Hz (Factor or authorized service center selectable)

<3% for linear load; 1% typical

<0.5V RMS

<0.5V RMS

<0.5V RMS

<0.5V RMS

<0.5V RMS

<0.5V RMS

<0.5V RMS

0.85 (0.6 to 1.0) lag

15A

25A

33.3A

41.6A

58A

75A

91.6A

45A

75A

100A

125A

174A

225A

275A

Inverter mode: 150% for 10 seconds, 125% for 30 seconds; Bypass mode: 125% for 10 minutes, 1000% for one cycle

Efficiency (AC-DC-AC): Temperature Range: Heat Generation (BTU/hr): Elevation: Audible Noise:

>85% 1843 <60dBa @ 1 Meter

>85%

>85%

>85%

>85%

>85%

0 to 40°C / 32 to 104°F (Operating); -20 to 40°C / -4 to 104°F (Storage)

3071

4095

5118

7168

9213

2000m/6600ft max. without derating

<60dBa @ 1 Meter <60dBa @ 1 Meter <60dBa @ 1 Meter <60dBa @ 1 Meter <60dBa @ 1 Meter

>85% 11260 <60dBa @ 1 Meter

Mechanical

Enclosure: Dimensions H x W x D (in/mm): Weight (lb/kg):

22.1 x 10 x 33 / 561.34 x 254 x 838.2
280 / 127

Steel enclosure; Complies with NEMA 1 and UL Type-1 standard

27.5 x 10 x 33 / 698.5 x 254 x 838.2

28.4 x 13 x 34.9 / 721.36 x 330.2 x 886.46

39.1 x 17.5 x 36.1 / 993.14 x 445.5 x 916.94

346 / 157

476 / 214

784 / 355

835 / 379

Battery Pack Dimensions H x W x D (in/mm):

5 x 7.3 x 19 / 127 x 185.4 x 482.6 (Six batteries of REW 45-12FR per pack)

Battery Pack Quantity:

Two

Three

Four

Eight

Features

Options Warranty

Output isolation transformer, RS232 and dry contact interface, Crest factor of 3, Angled terminal blocks for easy installation, Casters for mobility SNMP and WEB-based monitoring, Matching battery cabinet, Internet/external maintenance bypass, Receptacle panel and line cord

3 years on electronics (UPS); 2 years on battery

TrinitiTM 4200 Series
Three Phase UPS

> 15, 25, 50 and 80kVA power ratings > 100% front access > Internal maintenance bypass (except on 80kVA) > "Active Front End" provides total power factor correction and utility cost savings > Internal batteries reduce footprint for easy installation (except on 80kVA)

Triniti 4200 Series

Model

Triniti 15

Output Power Rating:

15kVA/12kW

Input Voltage (-15 to 10%; -30% if derated):
Output Voltage (±2% regulation balanced load):
Input Circuit Breaker @ 208V:
Output Current Per Phase @ 208/120V:
Typical Heat Output (KBTU/Hr):
Audible Noise at 1 Meter From Front Panel:

208/120 4 wire + gnd
208/120 4 wire + gnd 60A 41.7A 5.73 <60dBA

Internal Battery Runtime

Full Load @ 0.7 Power Factor: 10min Half Load @ 0.7 Power Factor: 30min

Mechanical

Dimensions H x W x D (in/mm):
Weight (lb/kg):

59.8 x 36.3 x 20 / 508 x 922 x 1518.9
900 / 408.2

* 4 to 64min runtime options

Triniti 25 25kVA/20kW 208/480 3 wire + gnd
208/120 4 wire + gnd 90A 69.4A 7.6 <60dBA
5min 15min
59.8 x 36.3 x 20 / 508 x 922 x 1518.9 910 / 412.7

Power Rating

Input Power Factor Correction: Input Harmonic Currents: Input Frequency Range: Load Crest Factor: Overload Capacity Inverter: Overload Capacity Bypass: Neutral Conductor Size:

>0.95 PF (lagging) <3% THD (typical) 60Hz, ±5% 3 125% for 90sec, 150% for 30sec 125% for 10ms, 1000% for 1 cycle 1.73 x conductor

Load Inrush Current Protection:

Automatically transfers to bypass then retransfers to inverter

Typical Efficiency AC/AC: Output Frequency:

87% 60Hz, ±0.1%

Status and Control

AC Input Present:

Input and output frequency

Inverter Operating:

Operating status menu

UPS on Bypass:

Diagnostic status menu

UPS on Battery:

DB9 dry contact interface

Fault:

RS232 communications

Input and Output Voltage: Emergency power off switch

Output Current Indicator: Run/Stop key switch

Battery Voltage Indicator:

Terminal block (input/output power connector) Internal maintenance bypass (except on 80kVA)

Optional Features:

External maintenance bypass, SNMP

Warranty

3 year parts and labor, 2 years on batteries. See warranty statement for further details, conditions and limitations.

Triniti 50 50kVA/40kW 208/480 3 wire + gnd
208/120 4 wire + gnd 175A 138A 17.73 <65dBA
5min 15min
59.8 x 37.6 x 35.6 / 904.2 x 939.8 x 1518.9 2548 / 1155.8

Triniti 15kVA
Triniti 80 80kVA/64kW 208/480 3 wire + gnd
208/120 4 wire + gnd 300A 222A 24.27 <65dBA
57
External Battery Pack Options*
74 x 31 x 44 / 1117.6 x 787.4 x 1879.6 2450 / 111.3

Three Phase UPS

Triniti 80kVA

Galaxy 3500
Three Phase UPS

> Power ranges 10, 15, 20 and 30kVA

> Double conversion on-line technology

> Compact and robust design

> Best-in-class efficiency (94%)

> Parallel capability

> Network manageability

Galaxy 3500

Galaxy 3500 Wide Enclosure

Galaxy 3500 Narrow Enclosure

Rated Power

10kVA / 8kW

15kVA / 12kW

20kVA / 16kW

30kVA / 24kW

Normal AC Supply Input

Input Voltage (V): Frequency (Hz): Input Power Factor: THDI: Input Voltage Tolerance Utility Operation: Dual Mains Input: Input Voltage Tolerance Bypass: Backfeed Protection:

208V (Three phase + neutral) 40 to 70Hz >0.98 at load >50% <5% at Full load
Yes
Built-in backfeed contactor

208V (Three phase + neutral) 40 to 70Hz >0.98 at load >50% <5% at Full load

208V (Three phase + neutral) 40 to 70Hz >0.98 at load >50% <5% at Full load

166 to 240V (at Full load) 100 to 240V (at half load) 208V

Yes

Yes

±10% standard ±4, 6, 8, 10% (programmable)

Built-in backfeed contactor

Built-in backfeed contactor

208V (Three phase + neutral) 40 to 70Hz >0.98 at load >50% <5% at Full load
Yes
Built-in backfeed contactor

Three Phase UPS

58

Output

Nominal Output Voltage (V):

208V (Three phase + neutral)

208V (Three phase + neutral)

208V (Three phase + neutral)

208V (Three phase + neutral)

Efficiency (AC-AC):

at Full Load at 50% Load

93.5% 92.5%

93.0% 93.5%

94.1% 93.8%

93.3% 94.3%

DC-AC Nominal Battery Voltage: 93.8%

93.8%

93.8%

93.8%

Load Power Factor:

0.5 leading to 0.5 lagging

0.5 leading to 0.5 lagging

0.5 leading to 0.5 lagging

0.5 leading to 0.5 lagging

Output Frequency:

Overload Capacity Operation:

Utility Battery

V THD:

150% for 60 seconds

Mains synchronized in normal operation 60Hz ± 0.05% free-running

125% for 10 minutes, 150% for 60 seconds

150% for 60 seconds

150% for 60 seconds

<2% From 0 to 100% linear load, <5% full non-linear load

150% for 60 seconds

Output Voltage Tolerance:

±1% Static, ±5% at 100% load step

Communication and Management

Communication Interface:

Network management card with environmental monitor

Control Panel:

Power view multi-function LCD, status and control console

Mechanical
Dimensions H x W x D (in/mm):
Weight (lb/kg):

Narrow Tower Wide Tower Narrow Tower Wide Tower

58.70 x 14 x 33 / 1490.98 x 355.6 x 838.2

--

58.70 x 20.60 x 33 / 1490.98 x 508 x 838.2

671 / 304 with 1 Battery module 873 / 395 with 1 Battery module --

711 / 322 with 2 Battery modules 913 / 414 with 2 Battery modules 979 / 444 with 2 Battery modules

--
-- 1181 / 535 with 2 Battery modules

Color:

Metallic Gray (RAL 9023)

Protection

Surge:

IEC61000-4-5, EN50091-2 ANSI-IEEE C62-41

Thermal:

Yes

Short Circuit:

Yes

Regulatory

Standards:

UL 1778, EN50091-2, IEC 62040-2 FCC15A, CE

Environmental

Temperature Range: Humidity:

Operating: 0 to 40°C / 32 to 104°F, Storage: -15 to 40°C / 5 to 104°F 0 to 95% non-condensing

Elevation:

Operating: 0 to 1000m /0 to 3280ft, Storage: 0 to 15,000m / 0 to 49,212ft

Max. Audible Noise: Protection Class:

<43.3dBA at <70% load (at 1m from unit)

<46.2dBA at <70% load (at 1m from unit) IP51/NEMA 12

Galaxy 4000
Three Phase UPS

> Power ranges 40, 50, 65 and 75kVA > True online double conversion technology > Low UPS to generator sizing > Power surge stabilization system > Power factor corrected input SNMP and
network based power management options

Galaxy 4000

Galaxy 4000

Power Rating

40kVA / 32kW

50kVA / 40kW

65kVA / 52kW

75kVA / 60kW

Input

Voltage:

208V

208V

208V

208V

Input Frequency:

60Hz (±5%)

60Hz (±5%)

60Hz (±5%)

60Hz (±5%)

Power Factor:

>0.98

>0.98

>0.98

>0.98

Current Distortion (THD):

<3% @ Full load

<3% @ Full load

<3% @ Full load

<3% @ Full load

Current (A @ 208V):

102

127

166

191

Output

Voltage:

208V

208V

208V

208V

Frequency:

60Hz (±1 to 4% selectable)

60Hz (±1 to 4% selectable)

60Hz (±1 to 4% selectable)

60Hz (±1 to 4% selectable)

Transient Response:

±5% for 0 to 100% to 0%

±5% for 0 to 100% to 0%

±5% for 0 to 100% to 0%

±5% for 0 to 100% to 0%

59

Voltage Distortion THD:

<1% L-L and L-N

<1% L-L and L-N

<1% L-L and L-N

<1% L-L and L-N

Inverter Overload 130%:

1min

1min

1min

1min

Inverter Overload 145%:

30 sec

30 sec

30 sec

30 sec

Bypass Overload:

10x nominal current - 1 cycle

10x nominal current - 1 cycle

10x nominal current - 1 cycle

10x nominal current - 1 cycle

Output Current (A @ 208V): 111

139

180

208

Three Phase UPS

Heat Rejection (max BTUs): 14900

18700

24200

28000

Runtimes @ 100% Load

1 x 285W/Cell:

12

9

6

-

1 x 370W/Cell:

20

14

9

8

1 x 500W/Cell:

28

22

15

11

2 x 370W/Cell:

47

36

25

22

2 x 500W/Cell:

67

52

38

31

3 x 500W/Cell:

98

85

60

53

4 x 500W/Cell:

136

115

85

72

Mechanical

Standard Cabinet Dimensions (in/mm):

33.5 x 35.6 x 72.1 / 1831.3 x 904.2 x 850.9

33.5 x 35.6 x 72.1 / 1831.3 x 904.2 x 850.9

33.5 x 35.6 x 72.1 / 1831.3 x 904.2 x 850.9

33.5 x 35.6 x 72.1 / 1831.3 x 904.2 x 850.9

Weight (lb/kg):

1235 / 560

1235 / 560

1235 / 560

1235 / 560

Battery Cabinet Dimensions (in/mm):

26.5 x 35.5 x 72.1 / 673 x 901 x 1831

26.5 x 35.5 x 72.1 / 673 x 901 x 1831

26.5 x 35.5 x 72.1 / 673 x 901 x 1831

26.5 x 35.5 x 72.1 / 673 x 901 x 1831

Weight (lb/kg):

2045 / 928

2045 / 928

2045 / 928

2045 / 928

Battery Cabinet Dimensions (in/mm):

33.5 x 35.6 x 72.1 / 850 x 901 x 1831

33.5 x 35.6 x 72.1 / 850 x 901 x 1831

33.5 x 35.6 x 72.1 / 850 x 901 x 1831

33.5 x 35.6 x 72.1 / 850 x 901 x 1831

Weight (lb/kg): Standards Standards:

2745 / 1245

2745 / 1245

2745 / 1245

2745 / 1245

ISO 9001, UL 1778, cUL, FCC Part 15, subpart J, Class A, NEMA PE 1, NEMA 250, NFPA 70, IEC 10000 (801) level 4, OSHA

Standard Features:

True double conversion online topology, Input power factor correction (IGBT rectifier), Dual input, Input distortion management, Digital power quality management system (PWM/IGBT inverter), Step load voltage stabilization, Intelligent battery management system, Fault tolerant architecture, Casters with stabilizing feet, Network based software for multi-server control, Dry contact I/O card, SNMP manageable, Graphic display with multilingual user interface, Bottom or top entry, Four communications ports

Galaxy 5000
Three Phase UPS
> IGBT technology supplies clean, stable power to sensitive loads > Connect up to 6 units in parallel: add redundancy
or grow with your power requirements > Allows connection to two separate input
sources for increased availability > Built in static and maintenance bypass for seamless transfer
to utility for maintenance or in the event of heavy overload

Galaxy 5000

Gaxaly 5000

Power Rating

40kVA / 36kW

50kVA / 45kW

60kVA / 54kW

80kVA / 72kW

100kVA / 90kW

130kVA / 117kW

Input

Voltage (V): Frequency: Power Factor: Current Distortion (THDI): Bypass Overload:

60Hz ±5% <0.99 <5%

480V Core, 3 Wire + G (220V, 208V, 600V w/ Aux Transformer 4 Wire + G)

60Hz ±5%

60Hz ±5%

60Hz ±5%

60Hz ±5%

<0.99

<0.99

<0.99

<0.99

<5%

<5%

<5%

<5%

10x nominal current for 1 cycle

60Hz ±5% <0.99 <5%

Output

60

Output Voltage:

Frequency:

60Hz

Voltage Regulation:

Voltage Transient Response:

Voltage Recovery Time:

Voltage Distortion:

Inverter Overload:

Heat Rejection (BTU) @ 480V: 9248

60Hz 11560

480V Core, 3 Wire + G (220V, 208V, 600V w/ Aux Transformer 4 Wire + G)

60Hz

60Hz

60Hz

±-1% balanced load, ±-2.5% unbalanced load

±-5% for 100% step load, ±1% for loss or return of AC input

Within 1% of nominal within 1 cycle

<1% L-L and L-N for non-linear loads (<2% max)

150% for 1min, 125% for 10min

13872

18496

19607

60Hz 25489

Three Phase UPS

Overall Efficiency

Double Conversion Mode: Up to 94%

Up to 94%

Up to 94%

Up to 94%

Up to 94%

Up to 94%

Environment

Temperature Range: Elevation:

Operating UPS: 0 to 40°C / 32 to 104°F, Operating battery: 25°C / 77°F, Storage: -20 to 45°C / -4 to 113°F

1000m / 3281ft

1000m / 3281ft

1000m / 3281ft

1000m / 3281ft

1000m / 3281ft

1000m / 3281ft

Mechanical

Dimensions H x W x D (in/mm):

Weight (lb/kg):

882 / 400.06

882 / 400.06

75 x 28 x 33.42 / 1905 x 711.2 x 848.86

882 / 400.06

882 / 400.06

1146 / 519.81

1146 / 519.81

Matching Maintenance Bypass Dimensions H x W x D (in/mm):

75 x 28 x 33.42 / 1905 x 711.2 x 848.86

Transformer Cabinet Dimensions H x W x D (in/mm):

75 x 28 x 33.42 / 1905 x 711.2 x 848.86

Distribution Cabinet Dimensions H x W x D (in/mm):

75 x 42 x 33.42 / 1905 x 1066.8 x 848.86

Top Entry Cabinet Dimensions H x W x D (in/mm):

75 x 14 x 33.42 / 1905 x 355.6 x 484.86

Battery Cabinet Dimensions H x W x D (in/mm):

75 x 26 x 33.42 / 1905 x 660.4 x 848.86

Battery Cabinet Dimensions H x W x D (in/mm):

75 x 32 x 33.42 / 1905 x 812.8 x 848.86

Battery Cabinet Dimensions H x W x D (in/mm):

75 x 48 x 33.42 / 1905 x 1219.2 x 848.86

Parallel System Bypass Cabinet Dimensions H x W x D (in/mm):

(480V Only): 75 x 28 or 42 x 33.42 / 1905 x 711.2 or 1066.8 x 848.86

Galaxy PW Series
Three Phase UPS

> Parallel modules for capacity or redundancy > 0.9 output power factor > Modular design for easy upgrading or expansion > Field upgradable power output** > Generator friendly for low UPS to generator sizing ratios > Advanced battery management system
with automatic self testing
** on 100-200kVA modules only

Galaxy PW

Galaxy PW Series
Power Rating

150kVA / 135kW

180kVA / 162kW

200kVA / 180kW

225kVA / 202.5kW

Input Input Voltage (V): Frequency (Hz):

208, 480V Three phases, 3W + G 60Hz (±10%)

Nominal Input Current at 208V:

685A

600A

692A

692A

Input THDI:

<7.5% at 100% load

Output

Voltage: Power Factor:

208, 480V Three phases, 3W + G

61

>0.9

THDV (Linear Loads):

<1.5% Ph/Ph, <2% Ph/n

THDV (Non-linear Loads):

<2% Ph/Ph, <3% Ph/n

Voltage Transient Reponse:

±2% at 100% Step load

Three Phase UPS

Nominal Output Current at 208V:

418A

501A

556A

625A

Inverter Overload Capacity (A):

150% for 1 minute, 125% for 10 minutes

Bypass Bypass Instant Overload: Overall Efficiency System Efficiency: Full Load Heat Rejection: Environmental Operating Temperature: Storage Temperature: Humidity: Audible Nosie: Mechanical

57,301BTU

22 Times nominal current (1 cycle)

93% at 100% Load 68,762BTU

72,477BTU

UPS: 0 to 40°C / 32 to 104°F -20 to 45°C / -4 to 113°F 0 to 95% non-condensing 68dBA

93.5% at 100% Load 73,383BTU

Module Dimensions H x W x D (in/mm):
UPS Module Weight (lb/kg):

75 x 48 x 33 / 190 x 1219.2 x 838.2 3050/1383

G9000 Series
Three Phase UPS
> Next generation IGBT Technology > True on-line, double-conversion UPS > Parallel up to eight units > High efficiency for lower operational cost > Smallest footprint and highest power density in industry

G9000 Series

G9000 Series
Models

T90S3S08KS6XSN

T90S3S10S6XSN

T90S3S16S6XSN

T90S3S22KS6XSN

T90S3S30KS6XSN*

T90S3S50KS6XSN*

T90S3S75KS6XSN*

Specifications

Capacity:

80kVA/72kW

100kVA/90kW

160kVA/144kW 225kVA/202.5kW 300kVA/300kW 500kVA/500kW 750kVA/750kW

Topology:

True on-line, Double-conversion, Advanced multi-level IGBT technology

Input

Voltage:

480V, Three-phase, Three-wire + Ground/bypass input, 480V, Three-phase, Three-wire + ground

Voltage Range:

480V, -20% to 15% (384 to 552V without utilizing battery)

Power Factor:

>0.99

>0.99

>0.99

>0.99

>0.99

>0.99

>0.99

62

Current THD:

Frequency:

60Hz (±10%)

60Hz (±10%)

<3% @ 100% Load (no input filter required)

60Hz (±10%)

60Hz (±10%)

60Hz (±10%)

60Hz (±10%)

60Hz (±10%)

Output

Voltage:

480V, Three-phase, Three-wire + ground

Frequency:

60Hz, ±0.01% (in free-running mode)

Three Phase UPS

Voltage Regulation:

±1.0% (0.5% Typical)

Power Factor:

0.9 Lagging

0.9 Lagging

0.9 Lagging

0.9 Lagging

1.0 (Unity)

1.0 (Unity)

1.0 (Unity)

Power Factor Range:

0.9 Lagging to 0.95 Leading

Voltage THD:

<2% for linear load, <5% for non-linear load

Overload (Inverter):

125% for 2 minutes; 150% for 60 seconds

125% for 10 minutes; 150% for 60 seconds

Overload (Bypass):

1000% for one cycle

500% for one cycle

Parallel Capability:

4 units max

4 units max

4 units max

4 units max

8 units max

8 units max

8 units max

Battery

DC Link:

480Vdc

480Vdc

480Vdc

480Vdc

480Vdc

480Vdc

480Vdc

Environment

Temperature Range:

0 to 40°C / 32 to 104°F

Humidity:

5 to 95% non-condensing

Heat Rejection:

10771 BTUs/Hr 13463 BTUs/Hr 17821 BTUs/Hr 25060 BTUs/Hr 30709 BTUs/Hr 51182 BTUs/Hr 79200 BTUs/Hr

Efficiency (Full Load):

95.8%

95.8%

96.5%

96.5%

97%

97%

97%

Efficiency (20% Load):

92.5%

92.5%

94.7%

94.9%

95.8%

95.8%

95.8%

Elevation:

2250m/7380ft max without derating

Audible Noise:

70dBA @ 1m

70dBA @ 1m

70dBA @ 1m

70dBA @ 1m

73dBA @ 1m

73dBA @ 1m

73dBA @ 1m

Mechanical

Dimensions H x W x D (in/mm):
Weight (lb/kg): Features

80.6 x 27.6 x 32.8 / 2049 x 700 x 832

855 / 388

855 / 388

80.6 x 35.4 x 32.8 / 2047 x 900 x 832

1160 / 526

1230 / 558

80.7 x 86.7 x 33 / 2050 x 2200 x 838

2200 / 1000

3300 / 1500

80.7 x 102.3 x 33 / 2050 x 2600 x 838
4255 / 1930

Digital Signal Processor (DSP) Control, Fully digital IGBT converter and inverter, High efficiency over wide load range, transformer-less design, N+1 and N+N (Up to eight in parallel) capability, Dual-input feed, Electronic battery isolation, RS232 and dry contact interface, small footprint, lightweight design

Standards UL 1778, CUL, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), FCC Class A, Article 47, Part 15.B
Warranty 3 year onsite (Optional 2 year extended warranty)
* Preliminary specifications only; subject to change without notice

Symmetra PX
Three Phase UPS
> Scalable from 10 to 100kW > Modular components simplify future
expansion as your load grows > N+1 redundant up to 90kW > Hot swappable power, battery and breaker modules > Space saving high density design

Symmetra PX

Power Rating

100kW

Mains Input (Normal Operation)

Grid System:

3 Phases + neutral + ground

Voltage Range (full load): 177 to 239V

Frequency Range:

40 to 70Hz

PF:

>0.99% @ >25% Load

I thd (full load):

<5%

Nominal Input Current:

302A @ 208A

Maximum Input Current:

332A (Nominal Vin, 10% charging batteries)

Input Current Limit:

360A

Max. Input Short-Circuit Level: 30kA

Protection:

Backfeed contactor

Bypass Input (Bypass Operation)

Grid System:

3 Phases + neutral + ground

Nominal Input (V):

208V

Voltage Range:

±10%

Frequency (nominal):

50/60Hz

Frequency (range):

±0.1Hz, ±3Hz, ±10Hz (user selectable)

Nominal Input Current:

278A @ 278V

Max. Overload Input Current: 347A

Output

Power Rating:

100kW

Grid System:

3 Phases + neutral + ground

Nominal Output (V):

208V L-L

Nominal Output Current:

278A @ 208V

Max. Battery Operation Time: Unlimited

Frequency Regulation:

50/60Hz Bypass synchronized, 50/60Hz ±0.1% free running

Sync. Slew Rate:

Programmable to 0.25, 0.5, 1, 2, 4, 6Hz/sec

Overload:

150% for 30 seconds (Normal and battery operation)

V thd:

<2% @ 100% Resistive load, <6.5% @ 100% SMPS load

Load PF:

From 0.5 leading to 0.5 lagging without any derating

Mechanical

Dimensions H x W x D (in/mm)

79.1 x 23.6 x 42.1 / 2011 x 600 x 1070

Net Weight (lb/kg): Shipping Weight (lb/kg): UPS Maximum Capacity 10kW Power Modules: Battery Modules: Power Distribution Modules: Regulatory Standards:

716 / 324 789 / 357
10 9 24
UL1778 second edition, FCC Part 15, CE

Symmetra PX
63

Three Phase UPS

64

Surge Protection

AlphaTVSSTM
Transient Voltage Surge Suppression

> Safe operation ­ no explosions, no smoke, no fumes and no flames
> Isolates the load from damaging transients and other abnormal line conditions
> Lifetime of 20+ years > NEMA 4X rated enclosure > UL recognized surge suppression
component (UL 1449 3rd edition)

The StrikesorbTM surge suppression module incorporates state-of-the-art developments in metal oxide

technology to provide superior protection throughout its long service life. It has been designed to

withstand repeated surges, providing cost-effective and maintenance-free operation in harsh

environments. Strikesorb is the only UL (1449 ­ 3nd edition) recognized surge protection module rated for

safe operation without the use of additional internal fuses. This technology, combined with the capability

to be connected directly on the power lines (feed-through connection) make Strikesorb the most reliable

surge protection device available.

65

Models

ATVSS-2-120 ATVSS-3-120/240 ATVSS-4-120/208 ATVSS-2-240 ATVSS-4-220/380

Surge Suppression

Electrical

Nominal Operation Voltage: 120V

Maximum Continuous Operating Voltage:

150V

Vref (Peak) @ 5mA AC (Peak): 263V

Operating Frequency Range: 25 to 500Hz

Leakage Current at Vn:

0.30mA

Surge Protection Levels

Surge Voltage Rating:

500V

Response Time:

<1ns

Maximum Surge Current: 140kA

Maximum Lightning Current: 7.5kA

Let through Voltage

For Surge Current 10kA (8/20): 435V

Enclosure

IP65-NEMA4

120V/240V 150V 263V 25 to 500Hz 0.30mA
500V <1ns 140kA 7.5kA
435V IP65-NEMA4

120V/208V 150V 263V 25 to 500Hz 0.30mA
500V <1ns 140kA 7.5kA
435V IP65-NEMA4

240V 300V 526V 25 to 500Hz 0.35mA
800V <1ns 140kA 7.5kA
895V IP65-NEMA4

220V/380V 480V 833V 25 to 500Hz 0.45mA
1500V <1ns 140kA 7.5kA
1355V IP65-NEMA4

Dimensions H x W x D (in/mm):

8 x 6 x 6 /

12 x 10 x 6 /

12 x 10 x 6 /

8 x 6 x 6 /

12 x 10 x 6 /

203 x 152 x 152 305 x 254 x 152 305 x 254 x 152 203 x 152 x 152 305 x 254 x 152

Operating Temperature:

-40 to 85°C / -40 to 185°F

Strikesorb Module

Large Thermal Capacity Electrodes: Absorb heat generated during surges and decelerate MOV ageing
Strong Aluminum Housing: Prevents explosions
1500+ Pounds of Pressure: Results in very low dynamic resistance
No Fuel to Burn: Prevents fire and smoke emission
Single, Distribution-Grade Varistor: Contributes to reliability, long lifetime, avoiding parallel connected MOVs
Coaxial symmetry and uniform surge current distribution

66

Alpha Technologies Services

Total Power Solutions

> Complete System Solutions
Systems engineered to work together are more efficient and more reliable. Alpha provides you complete systems to serve every point of your cable broadband network, as well as options for integrating renewable energy or Hybrid Power Systems into your operations. From power supplies and batteries to solar modules and turn-key buildings, our powering systems are fully integrated for maximum reliability and carefully engineered to minimize your total cost of ownership.

> Installation and Construction Services
With a national network of contractors, project managers and Alpha technicians, we can provide turnkey solutions for outside plant, headend, telecommunications, industrial and renewable energy applications. We work to combine your small-, medium- and large-scale projects with the necessary installation resources. Our complete installation and facility construction services include structure engineering, right-of-way and easement procurement, site preparation, equipment installation, utility hook-up coordination, system turn-up and system testing.

> Repairs, Refurbishments and Factory Upgrades

Featuring an on-site CableUPS® inverter module exchange, our goal is to maintain network uptime

providing you access to quick and stress-free system repairs and refurbishment options for all of your

network equipment. Our repair and development laboratories are designed for product repair,

refurbishment and improvement of all Alpha and third-party equipment including cable power supplies,

RF line gear, Headend, UPS fiber and test equipment.

67

Total Power Solutions

> On-Site Service
With Alpha Technologies Services repair depots established across North America, we provide convenient pick-up and drop-off services. In addition to our scheduled driving routes, we offer preventive maintenance programs and emergency response capabilities where trained Alpha field technicians can be dispatched 24 hours a day in specially equipped and stocked service vehicles.

> Technical Support and Customer Service
Because your networks are operating 24 hours a day, we offer you around-the-clock telephone technical support and web-based tools to generate RMAs and track open repairs, history and billing.

> Our ISO 14001:2004 Environmental Management System
Alpha strives to continually improve our Environmental Management System by benchmarking opportunities for improving our performance and demonstrating conformity to system requirements.

We are committed to be industry and community leaders for sustainable business processes by meeting legal/other requirements, communicating with internal/external customers and protecting our environment through the implementation of sustainable business processes and preventing pollution from occurring through our product design and daily practices.

System Solutions
> Fully integrated powering systems to protect your network > Next generation power solutions for emerging topologies > Power conditioning and back-up from Headend to home > Complete line of system accessories to maximize
reliability, efficiency and system runtime

We specialize in engineering complete network power systems committed to reliability, OpEx savings and environmental sustainability.

We understand that systems engineered to work together are

more efficient and more reliable. As a result, we provide you

complete systems serving every point of your cable broadband

network, as well as options for integrating renewable energy or

hybrid power systems into your operations. From power supplies

and batteries to solar modules and turn-key buildings, our

powering systems are fully integrated for maximum reliability and

68

carefully engineered to minimize your total cost of ownership.

We are proud to have served the telecommunications industry for more than 35 years, and we invite you to learn how we can strengthen your entire network with Alpha Power.

Our RFoG and GPON Fiber Power Systems provide the same reliability as our HFC systems with added features including outdoor access to batteries and multiple configuration options.

Total Power Solutions

High performance outside plant systems include multiple power supply, enclosure and battery options, as well as a full line of system accessories for climate-specific applications to provide extended runtimes and protect your powering investments.

Heavy-duty reinforced concrete equipment structures can be outfitted to your custom need, including back-up power, power conditioning, climate control, security and
communications, as well as on-site calibration and preventive maintenance programs.

Installation and Construction Services
> Complete design, engineering, permitting, construction and commissioning > Headends, equipment shelters and other critical facilities > Turnkey installation, turn-up and test services > Grid-Tied and Off-Grid Renewable Energy Systems
69
Alpha project managers will complete all site surveys, geological testing, engineering drawings and building permit applications. Our nationwide network of contractors and project managers then coordinate the entire implementation on-site, from concept to commissioning.

Total Power Solutions

Grid-Tied Solar Power can help minimize operating expenses and reduce your carbon footprint. (153kW Grid-Tied system in Phoenix, AZ)

Off-Grid Solar and Hybrid Power Systems can provide the necessary redundancy for critical loads and help extend network signal to remote areas. (11kW Off-Grid Hybrid Power System in Southwest Colorado)

Repairs and Refurbishments
Full Service Repair for All Broadband Equipment > 40 Years experience in RF Line gear, Headend, Fiber and Test Equipment Repair > All RF Repairs are certified using a fully loaded Digital QAM Spectrum Power Supply Refurbishments and Factory Upgrades > On-site Power Supply Inverter Module Exchange offers zero turn around time > Refurbishment features include:
· Replacement of all Capacitors · 2 or 3 year warranty of Complete Power Supply · Implementation of engineering changes to improve reliability > Options to upgrade to Embedded DOCSIS status monitoring
70

Total Power Solutions

Automated test equipment is used to efficiently verify all functions of refurbished power supplies.

Refurbished equipment is put through a rigorous burn-in cycle to identify marginal components.

Customer-requested and factory-recommended improvements are implemented at time of service.

Extensive experience repairing and refurbishing all telecommunications network equipment including Cable Power Supplies, RF Line gear, Headend, Fiber and Test Equipment.

Customer Service
On-site Personal Service > Free pick up and delivery on National Route Service > Reduced freight costs for best cost service Web Based Online Management Tools > Create RMA requests > Track open repairs, repair history and billing history

Track all aspects of your repairs online or call one of our customer service representatives.

Routine maintenance programs ensure system reliability. Burnaby, BC
Bellingham, WA

71
24/7 phone support available when you need it.
Mississauga, ON

Total Power Solutions

Phoenix, AZ

Pennsauken, NJ

Dallas, TX

Suwanee, GA

Aiken, SC

Alpha Technologies Service Depot Locations across North America offer convenient pick-up and drop off services.

Alpha Building Systems
Powering Solutions from Concept to Activation
Solid Building Construction > Single and multi-story building designs > Heavy duty reinforced concrete equipment structures meet most stringent wind and seismic requirements
· Vandal resistant, high security and maintenance-free · Durable washed and sealed aggregate exterior · Other finishing options available > Lighter-weight, composite-panel equipment structures are ideal for rooftop applications or temporary installations · Versatile shelters for difficult site pavements · Can be installed and equipped in hours · Durable stucco-embossed white enamel
72

Total Power Solutions

Alpha project managers will complete all site surveys, geological testing, engineering drawings and building permit application.

Heavy-duty reinforced concrete equipment structures are vandal-resistant, high security and virtually maintenance-free.

Lighter-weight composite-panel equipment structures are also available.

Site completion including landscaping, fencing and security.

Alpha Building Systems
Powering Solutions from Concept to Activation
Turnkey Solution For Any Communications Powering Application > Site survey and geological testing > Engineering drawings > Building permits > On-site construction > Careful shipping and off-loading > Site completion including landscaping, fencing and security Interior Finishing to Meet Every Requirement > Custom wall framing completed at the factory > Commercial grade tile flooring > White laminated 7/16" panelling > Fire rated to necessary specifications > Electrical system capabilities up to 1200Amps > Environmental controls
73

Pre-wired and equipment ready.

Electrical system capabilities up to 1200Amps.

Total Power Solutions

Custom wall framing allows units to be pre-wired and equipment-ready upon arrival.

Commercial grade tile flooring and durable white laminated 7/16" wall panelling.

12V FlexPoint AX Series Indoor/Outdoor Hybrid Solution
Operator Accessible Battery

12V FlexPoint AX Series Full Outdoor Solution
Operator Accessible

Home Converter
74

Indoor

10.5 to 14Vdc

5-24 Watts

BBPS

Typical Output ONT

Power & Remote Alarms

11.6 to 16Vdc Three Conductor Low Voltage DC

Ground Rod

Utility Meter and Meter Base
AC to DC Power Converter
Fiber Voice, Video and Data Enters Through Wall

10.5 to 14Vdc

5-24 Watts

BBPS

Typical Output ONT

11.6 to 16Vdc
Three Conductor Low Voltage DC

Power & Remote Alarms

Fiber
Voice, Video and Data Enters Through Wall

Ground Rod

48V FlexNet MPS Series Indoor Solution
Operator Accessible Battery

48V FlexNet FMPS Series Indoor Solution
Operator Accessible Battery

Total Power Solutions

Indoor

42 to 56Vdc

50 Watts

MPS

Typical Output ONT

Power & Remote Alarms

90 to 132Vac

Ground Rod

Fiber
Voice, Video and Data

FMPS
Indoor
90 to 320Vac

42 to 58Vdc 150 Watts ONT Typical Output
Power & Remote Alarms
ONT

Ground Rod

Fiber Voice, Video and Data
Fiber Voice, Video and Data

Fiber Power

lpha Technologies offers a complete portfolio of fiber-to-the-home powering options with the FlexPointTM line of 12Vdc single-family unit solutions (SFU) and the FlexNetTM line of 48Vdc multiple dwelling unit (MDU) and small office home office (SOHO) power supplies. All of Alpha's powering solutions are engineered to perform reliably in the most demanding environmental conditions while optimizing battery life and performance.

12Vdc Solutions

> FlexPoint 1207-F For RFoG Applications
The indoor FlexPoint 1207, 7 Watt, 12Vdc standby power supply is an environmentally-hardened standby power supply intended to be placed indoor or outdoor in sheltered locations. Its compact size allows placement in the most densely populated structured medial enclosures. The FP1207 includes a unique emergency battery reserve function that provides greater lifeline service availability by preserving 25% of the usable battery capacity for user initiated emergency telephone calls. User interfaces include visual status indicators, audible alarms, silence alarm button and an auxiliary 12Vdc power input port allowing additional battery capacity to be added for longer standby runtimes.

> Integrated Fiber Enclosure (IFE)
The FlexPoint IFE-A30-1 Integrated Fiber Enclosure from Alpha Technologies provides a reliable, compact and cost-effective means to simplify RFoG deployment. The enclosure contains a fiber management system, an 8-way coaxial splitter and a FlexPoint power supply with provisions for installing RFoG devices. The door-mounted FlexPoint power supply provides 20 hours of battery backup runtime. The enclosure is lockable, making this system a secure and convenient solution for Micro Node management.

> FlexPoint AX Series For EPON/GPON and RFoG

75

The indoor/outdoor FlexPoint AX Series, 30 Watt, 12Vdc fiber-to-the-premises optical network terminal

(ONT) power supply system, provides network operators a highly reliable, scalable set of solutions

for full or partial outdoor RFoG and PON installations. This system provides service technicians 24/7

access to the power system. FlexPoint AX home converters and power ring converters provide

12Vdc support for indoor and outdoor applications not requiring standby power. As services expand

to include voice or critical data support, 7.2 or 17Ah battery backup power supplies (BBPS) can be

easily added.

Fiber Power Systems

48Vdc Solutions
> FlexNet MPS48-7 Series
Alpha extends its family of FlexNet element powering solutions to include the MPS48-7F and MPS48-7T multipurpose power supplies. The MPS48-7F supports fiber-to-the-home applications including MDU, MTU and SBU ONT products. The MPS48-7T supports critical network communication loads. These units are indoor or outdoor, wall or pole mounted microprocessor controlled UPS system providing 50 Watts of 48Vdc. The input is powered from 120, 240 or higher AC voltages with an optional step-down transformer. A 48Vdc string of standard 7.2Ah maintenance free sealed lead acid batteries provide standby power.
> FlexNet FMPS
The FTTx Multipurpose Power Supply (FMPS) is an indoor/outdoor system providing 150W of 48Vdc power to MDU and SOHO optical network terminals. The FlexNet FMPS is an environmentally hardened wall mount enclosure system with dual ONT connections supported with one or two 48Vdc strings of 7.2Ah batteries. The system includes one or two parallel outputs and alarm connections, supporting distances of up to 100ft between the FMPS and ONT, allowing the FMPS to be located close to existing power outlets.
> FlexNet FiberUPS®
The FlexNet FiberUPS is a 300 Watts, 48Vdc battery backup power module supporting a variety of indoor and outdoor applications. With pole, wall or ground mount enclosure options, the FlexNet FiberUPS will keep field distributed electronics up and running during power disturbances and outages.
> PMR and GMR Series
The PMR and GMR series is comprised of two sizes of pole mount and two sizes of ground mount factory configured and regulatory certified rainproof enclosure systems. PMR and GMR are highly configurable systems including 19" adjustable or pullout swing racks, AC service entrance and distribution, surge suppression, fiber management, power bypass cabling, FiberUPS DC power supply, DC distribution and 50Ah AlphaCellTM batteries.

FlexPointTM 12Vdc
RFoG Battery Back Up Power Supplies
> Supports expanding services > Indoor and outdoor applications > 24-Hour operational access to outdoor solutions > Safe, low-voltage distribution

1207-F 7W RFoG System with Primary and Standby Power

Specifications

Input: Output Voltage: Output Power: Number of Batteries:

85 to 264Vac (45-66Hz) 10.5 to 14.4Vdc 7 Watts One 7.2Ah battery

Battery Backup Runtime:

Approx. ~ 20hrs w/ 3.5W load, Approx. ~ 12hrs w/ 7W load

Status Indicators: Dimensions H x W x D (in/mm):

Visual and audible 7.75 x 8.75 x 3 / 177 x 224 x 76.2

Unit

Weight (lb/kg):

76

Battery

1.3 / 0.59 5.7 / 2.6

Backup Power for Business Service RFoG Deployment

Specifications

Battery Backup Runtime:

Approx. ~ 20hrs w/ 3.5W load, Approx. ~ 12hrs w/ 7W load

Coaxial Management: Fiber Management: Features: Dimensions H x W x D (in/mm): Weight (lb/kg):

8-Way Coax Splitter Fiber wrap spool 12-fiber splice tray Lockable, secure indoor enclosure 12 x 12 x 8 / 304.8 x 304.8 x 203.2 8 / 3.6

Fiber Power Systems

AX 30W RFoG System with Primary and Standby Power

Specifications

Input: Output Voltage: Output Power: Mounting: BBPS-F Dimensions H x W x D (in/mm): Weight (lb/kg):

85 to 132Vac 10.5 to 14.4 Vdc 30 Watts Partial outdoor 7.75 x 8.75 x 3 / 177 x 224 x 76.2 3 / 1.4

Home Converter Dimensions H x W x D (in/mm):

8.5 x 3 x 2 / 21.5 x 7.6 x 5

Home Converter Weight (lb/kg):

1 /.45

Application
AX RFoG Indoor Powering - UPS
Operational Temperature Indoor Range: -40 to 113°F (-40 to 45°C Operational Temperature Outdoor Range: -40 to 113°F (-40 to 45°C)

RFoG Device

AX HC/BBPS-F
FPR1207-F7.2 -- Indoor 12V 7W Power System

Integrated Fiber Enclosure (IFE) -- For RFoG Deployment

AX HC/BBPS-F -- Outdoor 12V 30W Power System

Home Converter

BBPS-F

FlexPointTM AX 12Vdc
PON Battery Back Up Power Supplies

> Full or partial outdoor configurations > Outdoor rated BBPS including
battery for 24/7 availability > Utility meter base provides most reliable
source of AC power at home

FlexPoint AX Series

AX 30W EPON/GPON System with and without Standby Power

Specifications

AX PC/BBPS -- Outdoor 12V 30W System

Input:

170 to 264Vac

Output Voltage:

10.5 to 14.4Vdc

Output Power:

30 Watts

Mounting:

Outdoor

BBPS Dimensions H x W x D (in/mm): 7.75 x 8.75 x 3 / 177 x 224 x 76.2

Weight (lb/kg):

3 / 1.4

Power-Ring Dimensions H x Dia (in/mm): 4.75 x 7 / 120 x 178

Power-Ring Weight (lb/kg);

1.5 / 0.68

Power-Ring

Power Converter Dimensions H x W x D (in/mm):
Power Converter Weight (lb/kg):

8 x 2 x 2 / 209 x 51 x 51 0.7 / 0.32

Home Converter

BBPS
77

Applications
AX PON Outdoor Powering ­ Non-UPS Operational Temperature Outdoor Range: -40 to 45°C / -40 to 113°F

AX PON Outdoor Powering ­ UPS Operational Temperature Outdoor Range: -40 to 45°C / -40 to 113°F

Fiber Power Systems

AX 30W EPON/GPON System with and without Standby Power

Specifications

Input:

85 to 132Vac

Output Voltage:

10.5 to 14.4Vac

Output Power:

30 Watts

Mounting:

Partial outdoor

BBPS Dimensions H x W x D (in/mm): 7.75 x 8.75 x 3 / 177 x 224 x 76.2

Weight (lb/kg):

3 / 1.4

HomeConverterDimensionsHxWxD(in/mm): 8.5 x 3 x 2 / 21.5 x 7.6 x 5

Home Converter Weight (lb/kg):

1 /.45

Applications
AX PON Indoor Powering ­ Non-UPS
Operational Temperature Range: -40 to 45°C / -40 to 113°F

AX HC/BBPS -- Indoor / Outdoor 12V 30W Power System

Home Converter

BBPS

AX PON Indoor Powering ­ UPS
Operational Temperature Indoor Range: -40 to 45°C / -40 to 113°F Operational Temperature Outdoor Range: -40 to 45°C / -40 to 113°F

FlexNetTM 48Vdc 50W
Battery Back Up Power Supplies
> Rugged outdoor or indoor 48Vdc 50W wall or pole mount UPS > Aesthetically pleasing, minimizes presence in public locations > Optional compensated battery charging for optimum battery life > Local and remote status monitoring and reporting

FlexNet FMPS48-7 Series

Specifications

Input: Output Voltage: Output Power: Output Interface Module-F: Output Interface Module-T:

Unit Dimensions H x W x D (in/mm):

Weight (lb/kg):

System Dimensions

H x W x D (in/mm):

78

Weight (lb/kg):

Number of Batteries:

Runtime:

90 to 132 or 180 to 264Vac 42 to 56Vdx 50 Watts continuous Packet Cable Alarms Dry Contact Alarms
4.18 x 8.75 x 2.12 / 106.17 x 222.25 x 53.84
1.5 / 0.68
17.5 x 12.75 x 5.25 / 445 x 324 x 133
11 / 4.9, 34.6 / 15.7 w/ batteries
Four 7.2Ah Valve Regulated Lead Acid (VRLA)
18 Hours @ 20W load; 8 Hours @ 40W load

FlexNet MPS48-7 Series
FN50-48-7F -- With Output Interface Module-F
FN50-48-7T -- With Output Interface Module-T

Fiber Power Systems

FlexNetTM 48Vdc 150W
Battery Back Up Power Supplies
> FTTP outdoor UPS for Multiple Dwelling, Multiple Tenant and Small Business Unit applications
> Battery management performs periodic battery capacity testing and status reporting to the ONT and customer
> Battery heater option provides extended runtime for applications in cold weather conditions
> Status indicators and audible alarm provide local reporting

FlexNet FMPS
Specifications Input: Output Voltage: Output Power: FMPS Dimensions H x W x D (in/mm): Weight (lb/kg):
Number of Batteries:

90 to 320Vac 42 to 58Vdc 150 Watts continuous
23.75 x 14 x 5.5 / 603.25 x 355.6 x 139.7
25 / 11.3
Four or eight 7.2Ah Valve Regulated Lead Acid (VRLA)

FlexNet FMPS

FlexNetTM 48Vdc 300W
Battery Back Up Power Supplies

> 300W 48Vdc UPS for outdoor or indoor applications > Power modules can be used in a variety of Alpha enclosures > Temperature compensated battery
charging for extended battery life > Flexible cabinet mounting > Visual and electrical indicators for on-site and remote reporting

FlexNet ELPM-300

FlexNet ELPM-300
Specifications Input: Frequency: Output Voltage: Output Power: Dimensions H x W x D (in/mm): Weight (lb/kg): Number of Batteries: Approx. Backup Time:

85 to 170 or 132 to 264Vac selectable 50 or 60Hz 42 to 54Vdc 300 Watts 6 x 10.1 x 3.25 / 152 x 256.5 x 82.6 10 / 4.5 Four 12Vdc 50Ah (85GXL) 8 Hours @ 275W load

LPE and ELPM-300 -- 300W for MDUs, Dark Spots and Business Parks

LPE and FlexNet ELPM-300

Specifications

79

Enclosure Dimensions H x W x D (in/mm): 26 x 16.5 x 12 / 661 x 420 x 305

Enclosure Weight (lb/kg):

25 / 11.3

Material:

Exterior Powdercoated aluminum

Number of Batteries:

Four 12Vdc 17Ah

Door and Lid Seal: Approx. Backup Time:

Poron gasketing 4 Hours at 250W load

Fiber Power Systems

PMR and GMR Series

Specifications

PMR-S1 Dimensions H x W x D (in/mm): 32.2 x 26 x 19.25 / 818 x 660 x 489

Weight (lb/kg):

40 / 18

GMR-S1 Dimensions H x W x D (in/mm): 31 x 27.5 x 20 / 787 x 699 x 508

Weight (lb/kg):

49 / 22

PMR-S2 Dimensions H x W x D (in/mm): 37 x 30 x 19.25 / 940 x 762 x 489

Weight (lb/kg):

47 / 21

GMR-S2 Dimensions H x W x D (in/mm): 38 x 31 x 20 / 965 x 787 x 508

Weight (lb/kg):

63 / 29

Number of Batteries:

Four 12Vdc 50Ah (85GXL)

Approx. Backup Time:

8 Hours at 275W load

Enclosure Mounting and Door - PMR Series:

Galvanized steel brackets for wood, and concrete pole mount and wall mount

PMR and GMR Series -- 300W for field deployment of TTx Optical Line Terminal (ONT)

Enclosure Mounting and Door - GMR Series: Fiber Strain Relief Tie Bar Optional:
Splice Tray:
Fiber Management Panel:

Precast polymer concrete pad or PS-6/PS-6XL pedestal systems
19" mounting provides ability to strain relief fiber cable plugged into the front of communications equipment
Splice Tray Kit (12 count), includes Splice tray with Elastomer Splice Block, Felt Tape, Tie Wraps, Cover and Recording Label
Provides fiber slack storage and secures a splice tray using a Velcro strap. Tie wrap slots on sides permit securing fiber cables to panel

PMR and GMR Series
Pole and Ground Mount Enclosures

> Supports field deployment of FTTx Optical Line Terminals (OLT)

> FlexNetTM 300W UPS provides over 10hrs of runtime

> Thermostatically controlled 48 or

120Vdc fan and heater options

GMR

> Adjustable 19" EIA equipment racks

> All aluminum construction, durable powdercoat finish, stainless steel hardware

PMR
PMR and GMR Series

Mechanical

Fiber Management Options

Models: Mounting: Dimensions

PMR-S1 Pole 32.2 x 26 x 19.25

GMR-S1 Ground 31 x 27.5 x 20 /

PMR-S2 Pole

GMR-S2 Ground

37 x 30 x 19.25 / 38 x 31 x 20 /

Fiber Strain Relief Tie Bar (Optional):

19" mounting provides ability to strain relief fiber cable plugged into the front of communications equipment

HxWxD(in/mm): /818x660x489 787 x 699 x 508 940x762x489 965 x 787 x 508

Weight (lb/kg): 40/18

49/22

47/21

63/29

Splice Tray (Optional):

Splice Tray Kit (12 count), includes Splice tray with Elastomer Splice Block, Felt Tape, Tie Wraps, Cover and Recording Label

Material:

Powdercoated aluminum

80
Vent Screen

Mesh fabric with .005 x .005 / .12 x .12

(in/mm):

opening size to minimize snow, water and dust ingress

Fiber Management Panel (Optional):

Provides fiber slack storage and secures a splice tray using a Velcro strap. Tie wrap slots on sides permit securing fiber cables to panel

Door and Lid Seal:

Poron gasketing

Power Supply and Batteries

Color: Tamper Switch:

Gray or white (Custom colors available) Optional

Model:

FlexNet 300 -- 300W 48Vdc output with 48V battery bus with 19" reversible mounting bracket options

Fiber Power Enclosures

Grounding Internal Ground Bar: Safety Ground: Lid: Door(s)
PMR Series: GMR Series: Enclosure Mounting
PMR Series:

Five usable lugs Adjacent to AC outlets (Optional stainless steel ground stud) Removable (PMR Series includes lanyard)
Hinged removable with stainless steel spring latch and door open prop rod Removable lift-off front and rear door
Galvanized steel brackets for wood, and concrete pole-mount and wall mount

Batteries:

48Vdc string of 85 GXL (50Ah) positioned on ends (negative terminal side down) with battery retaining bar option

Battery Cable Kit: Battery Heater:

Fused Optional

AC Service:

External 70A rainproof SUSE rated breaker box with internal 120Vac 20A receptacles

Regulatory:

CSA

Notes: 1. Additional rack space capacity if batteries are not installed 2. Runtime of 10hrs based on 212W load and new batteries discharged to 1.75VPC
at 25°C/77°F

GMR Series:

Precast polymer concrete pad or PS-6/PS-6XL pedestal systems

Thermal Management Cooling: Heating: Internal Mounting Rails

120Vac and 48Vdc fan options 120Vac and 48Vdc heater options

Rack Mounting: Grounding: Adjustment:

EIA 19" mounting rails using Tinnerman mounting clips
Rails grounded to chassis
1" increments over 6" when batteries are not installed

Enclosure Environment Rating

Equipment Mounting Area:

Designed to IP X5 per IEC 529 Dust ingress controlled by screen opening IP X5 applies to the equipment mounting area The service entrance is rated 3R

Shown with FTTX actives installed, 19" swing rack, 50Ah AlphaCell batteries, AC and DC distribution, Fiber management and 300W power supply

Radium MiniBay
Environmentally Controlled Enclosures

> Scalable, environmentally controlled enclosure system > Fully integrated system and agency certified > Ideal for remote optical transition applications > High capacity 24 or 48Vdc 3000BTU
(879W) DC powered air conditioner > Natural gas or propane DC generator system
supports critical communications > Reduces operational and recurring costs

Radium MiniBay

The Radium MiniBay is a modular, highly configurable Telecom

Fans and Filters

grade enclosure system including fully scalable power to

The most basic thermal management system supporting the MiniBay utilizes

4,000W and 1240Ah of battery capacity with ample rack space

conformal-coated, variable speed and alarm monitored fans with electrostatic air filters providing up to 500W thermal dissipation. This configuration has a NEMA

for communications electronics. The MiniBay system benefits

3R rating

from more than 30 years of Alpha's Outside Plant (OSP)

· Variable speed controlled DC fans continue to operate during a utility outage · Conformal-coated fans

powering experience. The MiniBay integrates Alpha's

· Electrostatic and washable air filters · Field replaceable fans

comprehensive line of power solutions for today's complex Hub and environmentally controlled enclosure requirements including Alpha's AC UPS, CordexTM rectifiers, and the

Heat Exchanger

An airtight rear door and a heat exchanger equipped hinged front door providing

81

over 500W thermal dissipation. With a 500W load, the internal ambient

AlphaGenTM series of telephony grade DC generators. Features

temperature will not exceed 9.4 to 2.7°C / 15 to 27°F above external ambient. With a 250W load, the internal ambient temperature will not exceed 7°C / 12.6°F

for the Radium MiniBay include: front and rear accessible 19"

above external ambient. This configuration as a NEMA 4x rating

Fiber Power Enclosures

or 23" equipment racks providing up to 46 rack mount spaces,

· Heat exchanger heat pipe technology provides efficient thermal transfer · Minimizes internal temperature rise above external ambient

durable powdercoated aluminum construction, battery storage

· Variable speed controlled DC fans continue to operate during a utility outage · Field replaceable fans

modules isolated from the equipment section each supporting up to four 155Ah batteries for a 19A load for 8hrs. Typical CSA-NRTL marked configurations include integrated AC

DC Air Conditioner
For applications requiring the most reliable below cooling and dehumidifying system for supporting seamless performance through extended utility outages.

service entrance, surge protection, AC distribution, DC

Cooling capacity 878W dissipated at 43°C / 109.4°F outdoor ambient allowing a Maximum* internal ambient of 40°C / 104°F

distribution, standby generator interface, heat exchanger, fan/filter or air conditioner thermal management, rectifiers

· Variable speed brushless motor 24/48Vdc compressor system assures optimum efficiency over the full range of thermal loading and ambient temperatures
· 3000BTU @ 43°C / 110°F rating

or AC UPS equipment.

· Redundant conformal-coated fans have >50000hrs of life and low voltage disconnect circuitry

Standards Environmental Rating: Seismic Rating: Design Standards:

NEMA 3R when configured with door mounted fans and filter system. NEMA 4X when configured with heat exchanger or air conditioning system
Consult factory. A seismic rating is based on a set system configuration with defined mounting locations and equipment types
Following NEC and Telcordia Technologies (Bellcore) GR-487, GR-63 and GR-1089 guidelines

AC Air Conditioner
Ideal for applications requiring cooling and dehumidifying with little or no standby runtime performance. Cooling capacity 146W dissipated at 43°C / 109.4°F outdoor ambient allowing a Maximum internal ambient of 40°C / 104°F · 5000BTUBTU @ 43°C / 110°F rating · Washable electrostatic filters · 240Vac * Reducing the internal dissipated heat load reduces internal ambient

Compliance:

Third party approval from National Recognized Testing Laboratory (NRTL)

Material:

High strength corrosion resistant aluminum

Finish:

Almond color powdercoat finish

Weight and Dimensions

Weight (lb/kg): Dimensions H x W x D (in/mm):

Equipment Enclosure: 195 / 88.5

44 x 30 x 32 / 1117.6 x 762 x 812.8

Battery Storage Module: 130 / 59

14 x 30 x 32 / 355.6 x 762 x 812.8

Riser Module:

102 / 46.3

14 x 30 x 32 / 355.6 x 762 x 812.8

Side Chamber SC1:

100 / 45.4

72 x 32 x 12 / 1828.8 x 812.8 x 304.8

Side Chamber SC2:

89 / 40.4

72 x 32 x 12 / 1828.8 x 812.8 x 304.8

48Vdc air conditioner
Battery drawer

Rack space for customer supplied equipment RSM 48/10 Rectifiers with distribution
MiniBay with Fiber Management

82

Fiber Power Enclosures

Alpha Enclosures

Tempest brings convenience, strength and versatility to outdoor power system enclosures. The fully integrated modular design combines AC, DC and backup battery power into one space. All are designed to serve ASDL, TI and fiber optic transmission system (FOTS) facility applications.

> Tempest Te25 Series
The Te25 is designed to meet the requirements for service providers with remote outdoor or secure indoor applications. Welded aluminum construction provides structural integrity that will withstand seismic events and harsh weather conditions.

> Tempest Te25xh Series
Tempest brings convenience and versatility to outdoor power system enclosures. In addition to ADSL, TI, and fiber optic transmission system (FOTS) facility applications, the Te25xh is designed to meet the requirements for service providers with many other remote outdoor or secure indoor applications.

Welded aluminum construction provides structural integrity that will withstand seismic events and harsh weather conditions. The Te25xh is designed for remote applications and can be pole or pedestal mounted. It is also available in a secure indoor rack or wall mount configuration.

> Tempest Te15
The Tempest Te15's compact footprint is an ideal, economical solution for microwave, fiber and E911 applications. The optional integrated solar shield, heater, and air conditioner protect the batteries and equipment from severe environmental conditions. Fully secure pad-lockable doors and intrusion alarms keep equipment safe and secure.

> Tempest Te17

Tempest brings convenience and versatility to outdoor power system enclosures. In addition to

ADSL, TI and fiber optic transmission system (FOTS) facility applications, the Te17 is designed to

meet the requirements of WiMax service providers.

83

> Tempest Te21

The Tempest Te21's compact footprint is an ideal, economical solution for microwave, fiber and E911 applications. Lower compartment air conditioning protects the batteries and customer equipment from severe environmental conditions. Upper compartment fan cooling provides adequate cooling for 65°C/149°F temperature hardened power systems.

DC Power Enclosures

> Tempest Te30
The mid-size Te30 enclosure lineup provides up to 27RU of equipment in a 23" rack. A variety of HVAC options maintain a clean internal temperature controlled environment for reliable equipment operation in all kinds of outdoor environmental conditions. The Te30 is designed for installation flexibility. A number of cable entry locations are provided along with a cable management plinth option. Cable entry panels provide access by conduit, multiple cable entry assemblies and water tight fittings. In addition, the Te30 provides options for various AC service entrance and distribution panels adding installation and application flexibility. The Te30 provides an excellent solution for general purpose mid-size enclosure applications.

> Tempest Te4(x)
Alpha introduces its newest enclosure line, the GR-487 compliant Te4(x). The Te40 to Te43 provides an 84-inch tall enclosure that is configurable to a range of different requirements. The Te4(x) line-up is third-party agency certified to meet GR-487 requirements. Compliance includes 30-day salt fog, Zone-4 seismic and 70mph wind driven requirements, as well as several other criteria.

> Flexible Backhaul Enclosure
Alpha's Flexible Backhaul Enclosure is engineered to house optical fiber equipment to support high speed cellular data backhaul. Built with eleven rack mount spaces, the Alpha FBE is able to house fiber and powering gear including an Ethernet switch, power inverters, rectifiers, fiber splice tray, GMT and additional controls. An optional configuration enabling the addition of Batteries, DC rectifiers and Service Utility Entrance is available. With Telecom-grade, quarter-turn locks and key-operated Demark access, the FBE offers easy maintenance access and complete security.

> Wireless Transport Enclosure
The Wireless Transfer Enclosure is ideal for Wireless Backhaul Business Services applications. It offers a self-contained total power solution for a wide range of applications including wireless outdoor base stations, wireless IP access and bulk power. With a compact 24" x 24" footprint, the WTE features a standard 19" rack mount system with has 17RU (front/rear) of rack space, and an internal Breaker Distribution Panel with GFCI and Surge Protection.

Tempest Te25 / Te25xh
Outdoor System Enclosure

> Designed for outdoor or secure indoor applications
> Easily transportable > Durable aluminum construction > Pedestal, wall, pole or rack mount > Compact footprint

Tempest Te25 / Te25xh

Specifications

Material:

High strength corrosion resistant aluminum

Finish:

Powdercoat

Equipment Space:

20RU (Te25xh), 11RU (Te25)

Cable Entrance:

Knockouts located at bottom and back of enclosure

Equipment Rails:

19"

Electrical

Input Voltage Range N/A: 120/240Vac

Voltage:

-48Vdc

Current:

40A (n+1)

Mechanical
84

Te25 Cabinet Dimensions H x W x D (in/mm):

20.3 x 21.4 x 20.4 / 516 x 544 x 518

Te25 Weight (lb/kg):

65 / 29

DC Power Enclosures

Te25xh Cabinet Dimensions H x W x D (in/mm):

36 x 21.4 x 20.4 / 914 x 544 x 518

Te25xh Weight (lb/kg):

90 / 41

Hinge Type: Handle: Door Latch:

3 Position lift off hinge (Te25xh) 2 Position lift off hinge (Te25)
Padlockable (Te25xh)
3 Point Latch (Te25xh) Padlockable 1/4 turn latch

Equipment Shelves: Battery Trays (Qty): Environment Operating Temperature: Storage Temperature: Cooling: Door Installed Louvers: Audible Noise:

Optional (Te25xh) 1
-40 to 46°C / -40 to 115°F -40 to 85°C / -40 to 185°F Thermostat control filtered and fan cooled Equipped with washable/replacement filter <45dBa

Tempest Te25

Installation

Access:

Rear louver can be removed for equipment installation

Maintenance

Front access after installation filter access on front door

System Specification (As Shown)

· 48Vdc Cordex rectifier shelf c/w DC distribution · 4 x 92Ahr batteries · External 8 position AC distribution with 30A generator connector and
manual transfer switch · 8 position GMT fuse panel (Te25xh) · Fan filtered ambient cooled (Te25xh) · Alarm terminal block · Ground bar

System Options: Standards CSA/UL: Telcordia: NEMA Rating:

Consult factory for custom system solutions
C22.2 No 60950-01-03 Designed to meet zone 4 requirements (Te25) Type 3R (CSA C22.2 No 94-M91)

Tempest Te25 (with batteries)

Tempest Te25xh

Tempest Te25xh (open)

Tempest Te15
Modular Enclosure
> Modular design for single or multiple cabinet configurations
> Welded aluminum construction > 39RU of rack space > Heating and cooling options > Compact footprint

Tempest Te15
Electrical

Input Voltage:
Number of Breakers: Transfer Switch/Generator Connector: TVSS: Mechanical

120/240Vac 200A 1 120Vac 100A 1 18 maximum
Optional
Optional

Top Compartment Dimensions H x W x D (in/mm):

8 x 32 x 32 / 203 x 813 x 813

Main Compartment Dimensions H x W x D (in/mm):

69 x 32 x 32 / 1753 x 813 x 813

Bottom Compartment Dimensions H x W x D (in/mm):

8 x 32 x 32 / 203 x 813 x 813

Solar Shield Dimensions H x W x D (in/mm): DC Connections:
Chassis Ground:
Security: Rack Space: Alarm Connection: Description:

3 x 32 x 32 / 76 x 813 x 813
Multiple connection Multiple connection Buss bar located in cabinet Lockable front door 23" rails, 39RU
Terminal block High/Low Temperature Intrusion

Tempest Te15 Side mounted AC distribution

Standards

CSA:

C22.2 No 60950-01-03 Std. No 60950-01 NEMA Type 3R (CSA C22.2 No 94-M91)

Seismic:

Designed to meet Zone 4 requirements

Related Components
85

Heating and Cooling:

600W

Air Conditioning:

Up to 8000BTU

Fan Cooling:

Optional

Heat Exchanger:

Optional

DC Power Enclosures

Tempest Te15 (open)

Tempest Te17
Outdoor Enclosure
> Designed for outdoor network applications > Easily transportable > Durable welded aluminum construction > Variety of configurations possible
with 23RU of space > Compact footprint

Tempest Te17 (shown with 5000BTU air conditioner, bottom compartment, and solar shield)

Tempest Te17

Specifications

Enclosure Options

Material:

High strength corrosion resistant aluminum

Mounting:

Pad or platform mount

Finish: Equipment Space:

Powdercoat 23RU

HVAC Options:

Heat exchanger 33W/°C, 3500 BTU air conditioner or fan filtered ambient cooling

86

Cable Entrance:

Knockouts located in riser and bottom of enclosure

System Specifications (As Shown)

Equipment Rails:

23"

Electrical

· 24Vdc Cordex rectifier shelf c/w DC distribution · Internal 8 position AC panel

Input Voltage Range N/A: Voltage:

120/240Vac 24Vdc

· Air conditioner and heater · EVS (Emergency ventilation system) · Customer specific equipment layout

Current: Mechanical

64A (n+1)

· Alarm terminal block · Ground bar

Dimensions H x W x D (in/mm):

58 x 30 x 28 / 1473 x 762 x 711

System Options: Standards

Consult factory for custom system solutions

Weight (lb/kg): Hinge Type: Door Latch:

450 / 204 Piano style hinge 2x padlockable 1/4 turn socket pin-head key

CSA/UL: Telcordia: NEMA Rating:

C22.2 No. 60950 Designed to meet zone 4 requirements Type 3R (CSA C22.2 No 94-M91)

DC Power Enclosures

Battery Trays (Qty):

Configuration dependent - 8RU per front terminal battery shelf

Environment Operating Temperature: Storage Temperature: Cooling: Heating:

-40 to 46°C / -40 to 115°F -40 to 85°C / -40 to 185°F 3500 BTU air condition 550W heater option

EVS:

DC fan powered EVS (Emergency Ventilation System) option

Installation

Access:

Removable enclosure rear panel and removable lower compartment panels

Maintenance Front access after installation

Tempest Te17 (shown configured to customer specification)

Tempest Te21
Modular Enclosure
> Modular design for single or multiple cabinet configurations
> Welded aluminum construction > Dual compartment system > Compact footprint > Up to 39.6kW at 48V > Multiple point cable access

Tempest Te21

Tempest Te21

Electrical

Standards

Input Voltage:

120/240Vac, connected direct to site AC distribution panel

CSA:

C22.2 No 60950-01-03 Std. No 60950-01

Mechanical

NEMA Type 3R (CSA C22.2 No 94-M91)

Dimensions H x W x D (in/mm): 84 x 30 x 30 / 2137 x 762 x 762

Weight (lb/kg):

863 / 392 (no batteries)

Seismic:

Designed to meet Zone 4 requirements
87

Related Components

Chassis Ground:

Multiple connection Buss bar located in cabinet

Heater: Air Conditioning:

600W Up to 58000BTU

Security:

Lockable front door

Fan Cooling:

Optional

DC Distribution:

2 x 1200A 20 position bullet breaker 4 x 600A load shedding capability

Batteries: Customer Equipment: Alarm

2 shelves 4 battery/shelf 8RU available

Connection: Description:

Terminal block High/low temperature intrusion

DC Power Enclosures

Tempest Te21 (open)

Tempest Te30
Multi-functional Enclosure
> Modular enclosure design for mid size applications > Provides multiple enclosure line-ups including
power, battery and radio equipment installations > Air conditioning, fan cooling and
vented options available > NEMA 3R rating (IP55) > Multiple cable access points

Tempest Te30

Electrical

Input Voltage:

120/240Vac 100A 1

Generator Switch/ Generator Connector:

Optional

TVSS:

Optional

88

AC Panels/Breakers:

Configurable - contact factory

Mechanical

Part Number:

029-016-20

Dimensions H x W x D (in/mm):

58.4 x 30 x 30 / 1483 x 762 x 762 including 10/254 plinth

DC Power Enclosures

Weight (lb/kg): Mounting: Enclosure: Internal Rack:

500 / 227 (no batteries, no rectifiers) Pad or platform Aluminum shell 5052-H32 23", 26RU

Environment

Operating Temperature: Storage Temperature: Humidity: Elevation: Weather Tightness: Audible Noise:

-40 to 46°C / -40 to 115°F -40 to 85°C / -40 to 185°F 0 to 95% non-condensing 3600m / 12000ft, see operating temperature NEMA Type 3R 44dBA @ 7m / 23ft (air conditioned system)

Tempest Te30

Alarm Connection: Description: Chassis Ground: Security: Standards
Enclosure Rating:
Product Safety: Seismic: Related Components
Cooling Options:
Heating:

Terminal block High/Low Temperature Intrusion Multiple connection Pad lockable doors
CSA/UL type 3R IP55 equivalent CSA/UL 60950 Designed to meet Zone 4 requirements
5000BTU/hr air conditioner on front door DC fan cooling (and/or backup) Vented Up to 550W, 100-120Vac 50/60Hz

Tempest Te45
72" Single Compartment Power Enclosure
> Designed for single or multiple enclosure applications
> Durable welded aluminum construction > Variety of configurations possible
with 39RU of space > Compact footprint > GR-487 compliant

Tempest Te45

Tempest Te45 Backhaul Enclosure

Specifications

System Specifications (As Shown)

Dimensions H x W x D (in/mm): 72 x 30 x 30 / 1829 x 762 x 762

· 48Vdc Cordex 1.8kW rectifiers

Weight (lb/kg):

600 / 273

· AC panel c/w generator panel and ATS (Automatic Transfer Switch)

Equipment Space: Access:

23" 39RU Removable rear panels and front hinged door

· Air conditioner w/heater · EVS (Emergency Ventilation System) · Alarm terminal block

Door Latch / Hinge Type: 3 Point latch / 4 Position lift off hinges

· Ground bar

Handle:

Padlockable

89

System Options:

Consult factory for custom system solutions

Battery Trays (Qty):

Configuration dependent - 8RU per front terminal battery shelf

CSA/UL:

C22.2 No. 60950

NEMA Rating:

Type 3R (CSAC22.2 No 94-M91)

DC Power Enclosures

Tempest Te45 Battery
72" Front Terminal Battery Enclosure
> 8 Strings at 24Vdc, 4 strings at 48Vdc > Designed for single or multiple
enclosure applications > Durable welded aluminum construction > Compact footprint

Tempest Te45 Battery

Specifications

Material:

High strength corrosion resistant aluminum

Finish:

Powdercoat

Equipment Space:

39RU

Cable Entrance:

Knockouts on sides and bottom

90

Equipment Rails:

23"

Electrical

Input Voltage Range N/A: 120/240Vac

Mechanical

DC Power Enclosures

Dimensions H x W x D (in/mm):

72 x 30 x 30 / 1829 x 762 x 762

Weight (lb/kg): Hinge Type: Handle: Door Latch: Battery Trays (Qty): Environment Operating Temperature: Storage Temperature: Cooling: Heating:

600 / 273 4 Position lift off hinges Padlockable 3 Point latch 4 Front terminal battery shelves
-40 to 46°C / -40 to 115°F -40 to 85°C / -40 to 185°F 4000 BTU air conditioner 500W

EVS:

DC Fan powered EVS (Emergency Ventilation System) option

Audible Noise:

<65dBa

Tempest Te45 Battery

Installation

Access:

Removable rear panels and front hinged door provide full enclosure access

Maintenance

Front access after installation Enclosure Options

Mounting:

Pad or platform mount

System Specifications (As Shown)

· 4 Battery shelves for GNB 155Ahr front terminal batteries · Air conditioner w/ heater · EVS (Emergency Ventilation System) · Alarm terminal block · Ground bar

System Options: Standards CSA/UL:
Telcordia:
NEMA Rating:

Consult factory for custom system solutions
C22.2 No. 60952 GR-487 compliance- contact factory for specific compliances Type 3R (CSAC22.2. No 94-M91)

Tempest Te40 Battery
84" Front Terminal Battery Enclosure
> 10 Strings at 24Vdc, 5 strings at 48Vdc > 120Amp buss > Designed for single or multiple
enclosure applications > Durable welded aluminum construction > Compact footprint

Tempest Te40 Backhaul Enclosure

Tempest Te40 Battery

Specifications

System Specifications (As Shown)

Dimensions H x W x D (in/mm):
Weight (lb/kg): Equipment Space:

84 x 30 x 30 / 2134 x 762 x 762
1300 / 590 23" 44RU

· 5 Battery shelves for GNB 155Ahr front terminal batteries · Air conditioner w/heater · Alarm terminal block · Ground bar

Access:

Removable rear panels and front hinged door

System Options:

Consult factory for custom system solutions

91

Door Latch / Hinge Type:

3 Point latch / 5 Position lift off hinges

Agency Standards:

C22.2 No. 60954

NEMA Rating:

Type 3R (CSAC22.2 No 94-M91)

DC Power Enclosures

Tempest Te41 Power
84" Dual Compartment Power Enclosure
> Designed for single or multiple enclosure applications > Dual compartment system > Durable welded aluminum construction > Variety of configurations possible with 23RU of space > Compact footprint > Up to 39.6kW at 48Vdc or 34.1kW at 24Vdc > Multiple point cable access

Tempest Te41 Backhual Enclosure

Specifications

Dimensions H x W x D (in/mm):

84 x 30 x 30 / 2134 x 762 x 762

Weight (lb/kg):

1300 / 590

Equipment Space:

23" 19RU (upper), 26RU (Lower)

Access:

Removable rear panels and front hinged door

92

Door Latch / Hinge Type:

2 point latch upper and lower compartments / 5 position lift off hinges

Agency Standards: NEMA Rating:

C22.2 No. 60953 Type 3R (CSAC22.2 No 94-M91)

Tempest Te41 Power

System Specifications (As Shown)

· 48Vdc Cordex 3.6kW rectifiers (3.1kW Cordex system optional) · Qty 48 DC breaker positions · Qty 4 LVD disconnects for staged shutdown during power outage · AC panel c/w generator panel and ATS (Automated Transfer Switch) · Air conditioner w/ heater · Fan/filter ambient cooled upper compartment · Customer specific equipment layout · Alarm terminal block · Ground bar

System Options:

Consult factory for custom system solutions

DC Power Enclosures

Tempest Te44
Large Format Battery Enclosure
> Designed for Absolyte GNB 100 C-31 battery stacks
> Durable welded aluminum construction > Build on-site modularity

Tempest Te44

Tempest Te44

Specifications

Installation

Material:

High strength corrosion resistant aluminum

Access:

Modular design - built on site

Finish:

Powdercoat

Maintenance

Cable Entrance: Electrical Input Voltage Range N/A: Voltage: Mechanical

Bottom and sides
120Vac for air conditioner -48 or 24Vdc configurations

Front access after installation

Enclosure Options

Mounting Option:

Pad or platform mount

93

Other Options:

Single or dual stack configurations

System Specifications

Dimensions H x W x D (in/mm):

41.5 x 52 x 36 / 1054 x 1321 x 914 76 x 52 x 36 / 1928 x 1321 x 914

· Designed for GNB 100G31 Absolyte battery packs · Single or dual stack configuration

Weight (lb/kg):

550 / 250 900 / 408

· High temp and hydrogen detection controlled EVS · Alarm terminal block

Door Latch:

4 x padlockable 1/4 turn socket pin-head key

· Ground bar

Environment

System Options:

Consult factory for custom system solutions

Operating Temperature:

-40 to 46°C / -40 to 115°F

Standards

Storage Temperature:

-40 to 85°C / -40 to 185°F

CSA/UL:

C22.2 No. 60953

DC Power Enclosures

Cooling: Heating:
EVS:

2000 BTU air conditioner 500W
EVS (Emergency Ventilation System) with hydrogen control

Telcordia: NEMA Rating:

GR-487 compliance- contact factory for specific compliances
3R

Flexible Backhaul Enclosure 2322

> Provides 15RU for 19" horizontal mounted equipment or 10RU for vertical mounted equipment
> Front and side door access with removable lid > Durable welded aluminum construction > Wall, H-Frame, pole or ground mount options > Multiple thermal management options

FBE2322-ENC

FBE2322-ENC
Specifications
Outer Dimensions H x W x D (in/mm):

29.6 x 27 x 24 / 751.84 x 685.8 x 609.6

Equipment Space:

Front to back adjustable 19" 15RU horizontal or 23" 10RU vertical

Access:

Front hinged door, left and right lift off doors, removable lid

Door Latch / Hinge Type:

1/4 Turn padlockable / reversible 2 position lift off hinge

CSA/UL:
NEMA Rating:
94

60950-22 ITE electrical enclosure Type 3R

Enclosure Options
CordexHP 1.2kW 48Vdc Modular Switched Mode Rectifier

Multiple 48V configurations up to 125 Amps for various 48Vdc applications
High Efficiency design for increased OpEx savings
High Temperature rated fan-cooled design for harsh outdoor installations

DC Power Enclosures

Cordex 4R/8D ADIO CXC Smart Peripheral

Provides additional I/O expansion to existing CXC site controller
Seamless expansion of four relay outputs and eight digital inputs
Ideal for alternate device monitoring and control such as HVAC and generators

System Options Mounting:
Thermal:
Emergency Ventilation System: DC Power: AC Services Entrances: Generator: Alarm:

Wall, H-Frame, Ground or Precast Mounting Pad
Air conditioner with heater, heat exchanger, variable speed-controlled fan cooled
Variable speed controlled fan cooled activated with high temp or HVAC fail alarm
48Vdc Cordex HP 1.2kW rectifiers 70Amp 2 position or 100Amp 8 position External L14-30P generator plug Alarm terminal block

Fuses Panels Stand-Alone DC Distribution
19" and 23" rack mount models 12, 24 or 48V configurations Designed for flexible and custom DC distribution
AlphaCellTM HPL-FT Batteries
AGM runtimes up to 160 minutes in outdoor applications
Absorbent Glass Mat (AGM) technology for efficient gas recombination
HPL-FT features front terminal design with protective covers
Specifically designed for mission-critical applications

Cooling Options
Fan Cooled

Heat Exchanger

Air Conditioner

Flexible Backhaul Enclosure 2319

> Modular enclosure system, allows for easy battery expansion
> Demark access door > Front access for fan and filter maintenance > 24 or 48V configurations

FBE2319-ENC
Specifications
Models:
Outer Dimensions H x W x D (in/mm): Weight (lb/kg): Equipment Space: Access:
Door Latch / Hinge Type:
CSA/UL: NEMA Rating: System Options Mounting: Thermal: DC Power: AC Services Entrances: Generator: Alarm:

FBE2319-ENC

FBE2319-ENC with Battery Enclosure

27 x 23 x 22.3 / 686 x 584 x 565

41 x 23 x 22.3 / 1041 x 584 x 565

57 / 26 Front to back adjustable 19" 11RU Front hinged door with demark access door

1/4 Turn padlockable / reversible 2 position lift off hinge
60950-22 ITE electrical enclosure Type 3R

Wall, H-Frame, Ground or Precast Mouting Pad Heat exchanger, variable speed controlled fan cooled 48Vdc Cordex HP 1.2kW rectifiers 70Amp 2 position or 100Amp 8 position External L14-30P generator plug Alarm terminal block

FBE2319-ENC with Demark access door and fan cool option
95
FBE2319-ENC with Heat Exchanger Door, Battery Expansion and Ground Mount Option

DC Power Enclosures

Flexible Backhaul Enclosure 1417V
> Provides 7RU for 19" vertically mounted equipment in smallest foot print possible
> Front and side access to installed equipment > Wall or H-frame mount options > Aluminum welded construction with durable powdercoated exterior > Variable speed controlled fan cooled

FBE1417V-ENC

FBE1417V-ENC

Specifications

Outer Dimensions H x W x D (in/mm):

24.6 x 18 x 19.5 / 625 x 452 x 495

Weight (lb/kg):

35 / 15.9

Equipment Space:

Vertical 19" 7RU

Access:

Front hinged door, left and right lift off doors

96

Door Latch / Hinge Type:

1/4 Turn padlockable / reversible 2 position lift off hinge

CSA/UL: NEMA Rating: System Options

60950-22 ITE electrical enclosure Type 3R

Mounting: Thermal: 1RU Option Panel:

Wall or H-Frame Variable speed controlled fan cooled Alarm terminal block, fiber management

FBE1417V-ENC

DC Power Enclosures

Wireless Transport Enclosure

> Equipment mounting area is 17RU > Equipment rails are front-to-back adjustable, suitable
for mounting 19 inch rack mount equipment > Integrates Heat Exchanger and
Thermoelectric Cooling System > Equipment area is cooled by an Air-to-Air heat
exchanger with variable speed blower control > Internal L14-30P Generator inlet plug with
generator cord access through door

Wireless Transport Enclosure

Wireless Transport Enclosure

Specifications

System Specifications (As Shown)

Outer Dimensions H x W x D (in/mm):

70 x 24 x 29 / 1778 x 610 x 737

· Dual compartments - Upper compartment - heat exchanger

Weight (lb/kg):

330 / 150

- Lower compartment - thermoelectric cooling · Two battery trays (Consult factory for battery specifications)

Equipment Space:

Adjustable 19" 17RU plus 2 battery trays

· Front to back adjustable 19" equipment mounting rails

Access:

Front hinged door and rear lift off door

· Internal AC panel

· Generator plug and transfer switch

97

Door Latch / Hinge Type:

1/ 4 turn padlockable / reversable 4 position lift off hinge

· Alarm terminal block · Ground bar

CSA/UL: NEMA Rating:

60950-22 ITE electrical enclosure Type 3R

System Options:

Optional per-formed mounting pad Consult factory for custom system solutions

DC Power Enclosures

98

DC Power Enclosures

AlphaGenTM Generators
Adding a generator to any type of power system provides additional peace of mind. A generator serves as assurance that even in severe conditions, you will be able to keep your system up and functioning. All AlphaGen systems are engineered to have significantly reduced noise levels, high power density and status monitoring.
> AlphaGen 8kW to 2MW Systems
Critical power applications are part of every industry; protecting them starts with reliable generators, available in diesel, gas and LP configurations. Our EPA-compliant diesel models deliver dependable power to a wide range of output requirements. From small-load hub and small business to large Headend or facility backup, every generator is engineered to provide maximum power, performance, flexibility and fuel efficiency.
> AlphaGen Curbside Generator
The AlphaGen curbside generator system is specifically designed for Cable Broadband communications networks. Every AlphaGen system incorporates industry leading power technology, including natural gas or propane powered engine generators, exclusive audible noise baffling, remote status monitoring features and durable weather resistant enclosures.
99

Generators

AlphaGenTM 3.5kW to 2MW Systems
Generator Systems
> Design, install and maintain industrial generators > Custom generator solutions to meet your power supply needs > Generator solutions to most CRT and Facility Requirements > Power range from 3.5kW to 2MW or more > Propane (LP), Natural Gas (NG) or Diesel > Single phase or Three phase Systems > Fixed or portable solutions > Options include Automatic Transfer Switch
100

AlphaGen System

Generators

Alpha has the capability to design, install and maintain industrial generators to meet your power supply needs. Contact an Alpha representative for more details.

AlphaGenTM Telecom
Generator Systems

> Cost effective extended runtime solution for outdoor powering applications
> Quiet operation, small size and low profile allow for easier installation in populated areas
> Eliminates large quantities of batteries otherwise required for extended runtime
> Telecom grade 48Vdc output

AlphaGen Telecom

Model DC Output Voltage: DC Output Load Regulation: Output Current:

3.5kW
39V ±0.5V @ no load 36V configuration 52V ±0.5V @ no load 48V configuration 0.5V 39V @ 90A max / 52V @ 67A max

5kW
39V ±0.5V @ no load 36V configuration 52V ±0.5V @ no load 48V configuration 0.5V 39V @ 128A max / 52V @ 96A max

Engine:

398cc, Air cooled, Single OHV 10.5hp (using natural gas fuel)

RPM (Variable Speed):

2800 to 3600RPM

Acoustical Noise

dBA 10' @ 100% Rated Load: 68.7

dBA 20' @ 100% Rated Load: 63

dBA 10' @ 70% Rated Load: 68.3

dBA 20' @ 70% Rated Load: 62.6

2800 to 3600RPM
68.5 62.5 66.9 60.9

Models:

CE-3x2

CE-9x2

CE-3x2

CE-9x2

7.5kW 52V ±0.5V @ no load 48V configuration 104V ±0.5V @ no load 96V configuration 0.5V 52V @ 144A max / 104V @ 72A max 642cc, Air cooled, Twin OHV 15hp (using natural gas fuel) 2800 to 3600RPM
70.3 64.3 66.4 60.4
PN-6x

Dimensions H x W x D (in/mm):

44 x 26 x 24 /

52 x 52 x 24 /

44 x 26 x 24 /

52 x 52 x 24 /

39 (57 with optional pedestal) x 39.25 x 24

1117.6 x 660.4 x 609.6 1320.8 x 1320.8 x 609.6 1117.6 x 660.4 x 609.6 1320.8 x 1320.8 x 609.6 / 99 (144) x 100 x 61

Weight (lb/kg):

383 / 174

413 / 187

383 / 174

413 / 187

338 / 174 (370 / 168 with optional pedestal)

APU Fuel Consumption

Natural Gas 1000BTU/ft.3:

60ft3/hr

80ft3/hr

156ft3/hr

Propane Gas 2520BTU/ft.3:

0.82 gal/hr to 30ft3/hr to 3.46lb/hr

1.10gal/hr to 40ft3/hr to 4.62lb/hr

1.48gal/hr to 54ft3/hr to 6.24lb/hr

Exterior Surface Temperature:

Meets requirements of UL/CSA

Gas Inlet Pressure:

0.5 to 2 PSI Inlet Pressure (Contact Alpha Engineering for additional supply resources)

Ign Charger Voltage:

13.5Vdc

13.5Vdc

13.5Vdc

13.5Vdc

13.5Vdc

Ign Charger Current:

6A max

6A max

6A max

6A max

6A max

Remote Interface Length*:

75ft max Distance depends upon proper installation, derating and wire gauge

50ft max Distance depends upon proper installation, derating and wire gauge

25ft max Distance depends upon proper installation, derating and wire gauge

Agency Compliance:

UL2200, NFPA 37/54/58 and 70, CSA C22.2 FCC Class A

* Please contact Alpha Technologies for remote interface length distance

All Models Fuel System, Controls and Monitoring: Sensors: Safety Shutdowns: Optional Feature:
Configuration Options:

The controls and fuel system meet applicable sections of NFPA 37, 54 and 58 for automatic unattended operation of remotely located generators. Full System Control and Status Monitoring included. Gas Hazard, Pad Shear, Water Intrusion and Tamper
Low oil pressure, Water intrusion, Over speed, Over temp, Pad Shear, Over crank, Low fuel pressure shutdown (propane only), Gas hazard (propane or natural gas) Cold Start Kit: Provides additional starting capability at temperatures below -18°C / 0°F

CE-3X3.5 or 5kW

CE-9x2 3.5 or 5kW

CE-3/9G Propane Storage for Generator (For 3.5 and 5kW)

PN-6x 7.5kW (PN-6x is not compatible with CE-3/9G)

Alpha Technologies Inc. 3767 Alpha Way Bellingham WA 98226 United States Tel: +1 360 647 2360 Fax: +1 360 671 4936

VISIT US AT WWW.ALPHA.COM

Alpha Technologies Ltd. 7700 Riverfront Gate Burnaby BC V5J 5M4 Canada Tel: +1 604 436 5900 Fax: +1 604 432 1233

Alpha Industrial Power Inc. 1075 Satellite Blvd NW Suite 400 Suwanee GA 30024 United States Tel: +1 678 475 3995 Fax: +1 678 584 9259

Alpha Energy 1628 W Williams Drive Phoenix AZ 85027 United States Tel: +1 602 997 1007 Fax: +1 623 249 7833

Alpha Technologies GmbH Hansastrasse 8 D 91126 Schwabach Germany Tel: +49 9122 79889 0 Fax: +49 9122 79889 21

Alpha Technologies Europe Ltd. Twyford House Thorley Bishop's Stortford, Hertfordshire CM22 7PA United Kingdom Tel: +44 1279 501110 Fax: +44 1279 659870

AlphaTec Ltd. 339 Saint Andrews Street Suite 101 Andrea Chambers 3307 Limassol Cyprus Tel: +357 25 375675 Fax: +357 25 359595

AlphaTEK ooo Khokhlovskiy Pereulok 16 Stroenie 1 Office 403 109028 Moscow Russia Tel: +7 495 916 1854 Fax: +7 495 916 1349

Alpha Technologies Suite 1903, 19/F., Tower 1 33 Canton Road, Tsim Sha Tsui China Hong Kong City, Kowloon Hong Kong Tel: +852 2736 8663 Fax: +852 2199 7988

Altair Advanced Industries, Inc. 3765 Alpha Way Bellingham WA 98226 United States Tel: +1 360 671 7703 Fax: +1 360 733 8690

Alpha Technologies Inc.

Due to continuing product development, Alpha reserves the right to change specifications without notice. Copyright © 2011 Alpha Technologies Inc. All Rights Reserved. Alpha is a registered trademark of Alpha Technologies. 049-071-11-A001 (02/2011)


Adobe InDesign CS5 (7.0) Adobe PDF Library 9.9