2011 headend catalog > Critical Facilities Powering and Construction
Total Power Solutions by ALPHA Technologies
The Alpha Group - Total Power Solutions
> Alpha Power
Alpha pioneered the concept of reliable uninterruptible power for communications networks, and in the process has set a 35-year precedent for visionary, market-driven power solutions. Today, with millions of power systems installed around the world, we continue to focus on providing the most reliable, innovative and energy efficient powering solutions.
> Global Reach
With millions of powering system installed and sales, manufacturing and service facilities located around the world, we are able to help you in a language you'll understand. This global reach gives us the expertise to provide your specific power solution.
> Our Goal: Reducing Your Total Cost of Ownership
> Reliability
We are engineering the next generation of power technologies committed to reliability, cost savings and best-in-class performance.
> Sustainability
Running a more efficient powering network can reduce the resources consumed, and your operational expenses.
> Intelligence
Instead of giving you data, intelligent products give you answers. We are working to provide the answers to optimize system performance.
> Efficiency
Through proper load matching and power supply sizing, tailored powering systems can perform at up to 94 percent efficiency.
Table of Contents
Table of Contents
> DC Power Systems
3-27
> AlphaTVSSTM
65
CordexTM Power Systems........................................4
Cordex Controller Features....................................5 Cordex Comparison Chart.....................................6 Cordex CXCR/CXCP..............................................7 Cordex CXCM4......................................................8 Cordex CXCM2......................................................8 Cordex CXCM........................................................9 Cordex CXCI...........................................................9
> Total Power Solutions
67-73
System Solutions..................................................68
Installation and Construction Services.................69
Repairs and Refurbishments................................ 70
Customer Service................................................. 71
Alpha Building Systems........................................72
Cordex 400 and 650W......................................... 10 Cordex 400W/650W............................................ 11 Cordex HPTM 1.2kW............................................... 12 Cordex 1.8kW....................................................... 14 Cordex HP 2kW.................................................... 15 Cordex 3.6kW...................................................... 16 Cordex HP 4kW.................................................... 17 CXPS 48-1.2-225.................................................. 18 CXPS 48-1.8-i and CXPS 48-1.8-M2.................... 19
> Fiber Power
75-81
FlexPointTM 12Vdc, RFoG....................................... 76
FlexPoint AX 12Vdc, PON.....................................77
FlexNetTM 48Vdc 50W............................................78
FlexNet 48Vdc 150W............................................78
FlexNet 48Vdc 300W...........................................79
PMR and GMR Series..........................................80
Radium MiniBay................................................... 81
CXPS 48-1T..........................................................20
> Alpha Enclosures
83-97
CXPS 48-2T.......................................................... 21
Tempest Te25 / Te25xh........................................84
Cordex System.....................................................22
Tempest Te15.......................................................85
CXPS 2448-i....................................................... 24
Distribution Centers..............................................25
Tempest Te17.......................................................86
DC Accessories....................................................26
Tempest Te21.......................................................87
Tempest Te30.......................................................88
1
> Batteries and Accessories
29-37
Batteries
Telecommunications..........................................30
Telecommunications and Business Services..... 31
Business Services..............................................32
UPS......................................................................34
Battery Monitoring................................................35
Network Monitoring..............................................35
AlphaGuardTM........................................................36
Tempest Te45.......................................................89 Tempest Te45 Battery..........................................90 Tempest Te40 Battery..........................................91 Tempest Te41 Power............................................92 Tempest Te44.......................................................93 Flexible Backhaul Enclosure 2322.......................94 Flexible Backhaul Enclosure 2319........................95 Flexible Backhaul Enclosure 1417V......................96 Wireless Transport Enclosure...............................97
Battery Testing Equipment...................................37
> AlphaGenTM Generators
99-101
> DC to AC Inverters
39-47
AMPS80HP..........................................................40
AlphaGenTM 3.5kW to 2MW Systems................100 AlphaGen Telecom............................................. 101
AMPS24HP.......................................................... 41
Arcon Inverter Series............................................42
TEBEVERT Inverter Series...................................43
Invertronic Inverter System...................................44
Media Inverter System..........................................45
DSP Inverter Series..............................................46
MS Power Inverter Series..................................... 47
> Single and Three Phase UPS
49-63
AMPS80HP..........................................................50
AMPS24HP.......................................................... 51
EX UPS.................................................................52
EX RT UPS...........................................................54
1600 XP Series.....................................................56
TrinitiTM 4200 Series...............................................57
Galaxy 3500.........................................................58
Galaxy 4000.........................................................59
Galaxy 5000.........................................................60
Galaxy PW Series.................................................61
G9000 Series.......................................................62
Symmetra PX........................................................63
2
Table of Contents
DC Power Systems
The Alpha Group has more than 30 years of experience providing a wide variety of fully integrated power system solutions. With options for standardized systems and custom DC system integration, The Alpha Group has the flexibility to provide DC power solutions perfect for a wide range of power needs and various site installation requirements. Integrated shelf systems are available for all small power rectifier models providing a complete power solution in a single rack mount package. These systems incorporate a CordexTM controller, rectifiers and DC distribution options in a compact shelf design. Optional accessories such as LVDs, shunts and temperature compensation are available. For medium to large system applications, The Alpha Group can provide both standard and custom DC system solutions designed to maximize space and cost savings. Systems can be integrated with a wide array of options including various rack solutions, custom DC distribution configurations, multiple voltage output designs and front access. Coupling advanced Cordex power technology with an enormous selection of system components, The Alpha Group can easily provide optimal system solutions up to 8,000 Amps.
3
DC Power Systems
CordexTM Power Systems
Matrix
DC Power Systems
AMPS
(not to scale)
10,000
CXCM4 CXCR CXCP
9000A
8000
6750A 6000
CXCR
8000A
6000A
48V
4500A 4000
2250A 2000
1000
4000A 2000A
CXCM4 CXCR CXCP
2250A
1500A
1000A
CXCM4 CXCP
2000A
1350A
900A
4
800
600 500A
400
200
175
450A
500A
450A
CXCI CXCM2 CXCR
420A
210A
CXCI CXCM2 CXCR
375A
187A
CXCM1
225A
24V
CXCM4 CXCP
2000A 1560A 780A
DC Power Systems
150
CXCI
CXCI
130A 140A
125
CXCM CXCR
130A
120A
100
100A
83A 75A
75
CXCI
70A
65A
65A
50
42A
37A
25A
25
20A
13A
13A
14A
0
48-4kW HP Multi bay
48-3.6kW Multi bay
48-4kW HP Single bay
48-3.6kW Single bay
48-2kW HP 48-1.8kW 48-1.2kW HP 48-1kW
48-650W 48-650W 24-3.1kW
Single shelf Single shelf Single shelf Single shelf Single shelf Single shelf Single bay
w/expansion w/ expansion w/ expansion
w/ expansion
24-400W Single shelf w/ expansion
CordexTM Controller Features
DC Controllers
> The CordexTM CXC is Alpha's latest generation of advanced digital controllers for power system monitoring and control. CordexTM supervisory controllers come in a wide array of modular designs for compact integration into Alpha power systems. Stand-alone rack mount versions are also available for DC systems, legacy controller upgrades and site monitoring solutions.
A graphic LCD display with state-of-the-art touch-screen interface allows simple and convenient set up, control and monitoring of CordexTM rectifiers. Innovative IP technology allows complete configuration and monitoring from any location via the Internet using a standard web browser. CordexTM CXC controllers come standard with several advanced battery management features to allow for significant savings of capital and operational expenses. Additional features include user definable alarms with custom algorithms, digital and analog input monitoring, data logging, integrated SNMP and highly reliable CAN bus communications. Software upgrades are easily downloaded and provided free of charge.
> Main
> Battery Management
· Web based GUI Interface: Web browser support for local or
· Temperature Compensated Float Voltage: Increases voltage in
remote control and monitoring.
temperatures below 25°C / 77°F and decreases charge voltage
· Single point set up and control. · Auto voltage adjustment and load sharing. · Analog digital inputs. · Configurable Form C relay outputs.
above 25°C / 77°F. Maximizes life and capacity of battery and prevents thermal runway.
· Battery Equalize: Manual, automatic and periodic equalize
5
charge modes. Optional Battery Current Terminate function to
prevent over charging of battery.
· Various preset alarms and ability to configure up to 20 customized alarms.
· Battery Boost Mode: Offline high-voltage equalize charge with interlock safety feature.
· User programmable logic statements.
· Legacy Power System Upgrade: Controls legacy Pathfinder based systems and can be used as a site monitor for any 3rd party DC power system.
· Dynamic Charge Current Control: Limits battery recharge current to a fixed value. Helps prevent thermal runway.
· Battery Test: Sets rectifier voltage low and performs safe discharge of batteries through the connected system loads.
· CAN Communications: Common platform for Alpha power electronics and peripherals. Rugged and field proven protocol.
· Battery Capacity Prediction: Calculates current battery capacity after a discharge.
· Fail Safe System Operation: In the event of CXC failure, rectifiers continue to run with default settings, fail alarm is generated and LVDs (if equipped) remain energized.
· Power Save Function: Improves operational efficiency by running the minimum number of rectifier modules required per system load.
· System Start Delay: Allows delay for other AC powered equipment to start before rectifiers.
· Ramp Test Control: Disables fail alarm on no-load conditions.
· SNMP Support: Network management service support for managing multiple systems in a single network.
· Battery Runtime Prediction: Based on current battery capacity and system load.
· Battery Logging: Retain up to 40 records of battery statistics and events.
> Maintenance
· Data Logger: Record any system input(s), and set sample rate of record on deviation. Store up to 500 events via manual or auto start/stop.
· Typical data log applications: Detailed battery discharge info, AC voltage watch dog and outdoor cabinet thermal performance.
· Email notifications via TCP/IP.
· Cordex Peripheral Support: Optional add-ons for individual cell and temperature monitoring and controller I/O expansion.
· Easy Remote Software Upgrades: Fail-safe protected upgrades for controllers, rectifiers and peripherals.
· Multi language support including Chinese characters.
CordexTM Comparison Chart
> Cordex Controllers come standard with several advanced battery management features to allow for significant savings of capital and operational expenses. Some additional features include user definable alarms with custom algorithms, digital and analog input monitoring, data logging, integrated SNMP and CAN bus communications. The Cordex CXC is designed for effortless operation of the Cordex rectifier family, making time consuming and complicated set up and monitoring of DC power systems a thing of the past.
DC Controllers
CXCR/CXCP
CXCM4
CXCM2
CXCM1
CXCM
CXCI
Specifications
Screen:
Full Graphic LCD 160 x 160 pixels
Full Graphic LCD 160 x 160 pixels
Full Graphic LCD 160 x 160 pixels
Basic Current / Volts Display Only
Full Graphic LCD 160 x 160 pixels
Basic Current / Volts Display Only
Inputs
6
Analog:
2V, 2T, 4C, 2BIV
2V, 2T, 4C, 2BIV
1V, 2T, 2C, 4BIV
1V, 1C, 2T
2V, 2T,1C, 1BIV
1V, 1C, 2T
Digital:
8
4
6
2
3
2
Alarm Relay Outputs:
8 Form C
Dimensions
Height x Width x Depth (in/mm):
5.1 x 16.9 x 3.9 / 131 x 431 x 100
Rectifier shelf option availability
4kW HP (48Vdc)
Yes
8 Form C
7 x 3.4 x 10.1 / 177 x 87 x 257
Yes
6 Form C
4 Form C
8 Form C
3.4 x 5 x 9.7 / 86.4 x 128 x 247
1.6 x 334 x 10.1 / 41.4 x 84.4 x 256.8
6.9 x 2.9 x 10 / 177 x 74 x 255
4 Form C
3.5 x 1 x 11 / 88 x 26 x 280
3.6kW (48Vdc)
Yes
Yes
2kW HP (48Vdc)
Yes
Yes
Yes
1.8kW (48Vdc)
Yes
Yes
Yes
1.2kW HP (48Vdc)
Yes
1kW (48Vdc)
Yes
Yes
650W (48Vdc)
Yes
400W (24Vdc)
Yes
CordexTM CXCR/CXCP
System Controller
> LCD touch-screen user interface > Internet ready, integrated SNMP > High reliability CAN bus communication > User definable alarms > Flexible battery management features > Smart peripheral monitoring features > 19" and 23" Universal rack or panel mount configurations
CXCR Rack mount Controller
Cordex CXCR/CXCP
Features
Environment
Electrical
Extended Temperature:
-40 to 65°C / -40 to 149°F
LCD touchscreen display (160 x 160 pixels),
Humidity:
0 to 95% non-condensing
Display:
"OK / Major / Minor" 3-Color, LED display, Web based GUI via ethernet
Standards
Communication Ports:
RJ45 ethernet port (front accessible rear port) RS232 craft port (front)
Safety:
CSA C22.2 No 60950-1-03 CE marked
RS232 modem port (optional)
EMC:
ETSI 300 386
Controller I/O
7
CFR47 (FCC) Part 15 Class B
Voltage Inputs:
2
Temperature Inputs:
2
Emissions:
ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia)
Current Inputs:
4
Bi Voltage Inputs:
2
EN 61000-4-2 EN 61000-4-3
Digital Inputs:
8
Relay Outputs:
8
Immunity:
EN 61000-4-4 EN 61000-4-5 EN 61000-4-6
Mechanical
Dimensions H x W x D (excludes mounting brackets) (in/mm):
5.1 x 16.9 x 3.9 / 131 x 431 x 100
Mounting:
CXCR with 19" or 23" rack mounting CXCP panel mount
Weight (lb/kg):
13.8 / 6.2
DC Controllers
CordexTM CXCM4
System Controller
> User definable alarms and data logging > Flexible battery management features > Smart peripheral monitoring features > 4RU modular CXC for 3.1/3.6kW rectifiers
CXCM4
Cordex CXCM4
Features
Environment
Electrical
Extended Temperature:
-40 to 65°C / -40 to 149°F
Display: Communication Ports:
LCD touchscreen display (160x160 pixels), "OK / Major / Minor" 3-Color, LED display, Web based GUI via ethernet
RJ45 ethernet port, RS232 craft port (front)
Humidity: Standards
Safety:
0 to 95% non-condensing
UL/CSA C22.2 No 60950-1-03 CE marked
Controller I/O
ECM:
ETSI 300 386
Voltage Inputs:
1 + 1 Internal
Temperature Inputs:
2
Current Inputs:
4
Bi Voltage Inputs:
2
Digital Inputs:
4
Relay Outputs:
8
8
Mechanical
Dimensions H x W x D (in/mm): 7 x 3.4 x 10.1 / 177 x 87 x 257
Emissions: Immunity:
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia)
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6
Weight (lb/kg):
3.9 / 1.8
Mounting:
Modular controller for 3.1kW and 3.6kW shelves
DC Controllers
Cordex CXCM2
System Controller
> LCD touch-screen user interface > Internet ready, integrated SNMP > High reliability CAN bus communication > 2RU modular CXC for 1.8kW rectifiers
Cordex CXCM2
Features
Electrical
Input Voltage: Current:
17 to 65Vdc <100mA @ 48Vdc or <200mA @ 24Vdc
Display:
LCD touchscreen display (160x160 pixels), "OK / Major / Minor" 3-Color, LED display, Web based GUI via ethernet
Communication Ports: Controller I/O Voltage Inputs: Temperature Inputs: Current Inputs: Digital Inputs: Relay Outputs: Mechanical Dimensions H x W x D (in/mm): Mounting:
RJ45 ethernet port (front)
1 + 1 Internal 2 2 6 6
3.4 x 5 x 9.7 / 96.4 x 128 x 247 Modular controller for 1.8kW shelves
CXCM2
Environment Extended Temperature: Humidity: Standards Safety: ECM:
Emissions:
Immunity:
-40 to 65°C / -40 to 149°F 0 to 95% non-condensing
CSA C22.2 No 60950-1-03 CE marked
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia)
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6
CordexTM CXCM
System Controller
> LCD touch-screen user interface
> Internet ready, integrated SNMP
> High reliability CAN bus communication
> User definable alarms and data logging
> 4RU modular CXC for 1kW rectifier
CXCM
Cordex CXCM
Features
Environment
Electrical Display:
Communication Ports:
Controller I/O Voltage Inputs: Temperature Inputs: Current Inputs:
LCD touchscreen display (160 x 160) pixels, "OK / Major / Minor" 3-color, LED display, Web based GUI via ethernet RJ45 ethernet port (front accessible rear port) RS232 craft port (front) RS232 modem port (optional)
1 + 1 Internal 2 1
Extended Temperature: Humidity: Standards Safety: EMC:
Emissions:
-40 to 65°C / -40 to 149°F 0 to 95% non-condensing
CSA C22.2 No 60950-1-03 CE marked ETSI 300 386 CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia)
Bi Voltage Inputs:
1
EN 61000-4-2
Digital Inputs:
3 (2 +1 internal on some models)
EN 61000-4-3
Relay Outputs:
8
Mechanical
Immunity:
EN 61000-4-4
EN 61000-4-5 EN 61000-4-6
9
Dimensions H x W x D (in/mm): 6.9 x 2.9 x 10 / 177 x 74 x 255
Weight (lb/kg):
3.9 / 1.8
Mounting:
Modular controller for 1kW rectifier shelves
DC Controllers
Cordex CXCI
System Controller
> Control and monitor via Internet Explorer browser > Flexible battery management features > Smart peripheral monitoring features > Integrated option on 1.8kW, 650W and 400W shelves
Cordex CXCI
Features Electrical Input Voltage: Current:
Display:
Communication Ports:
System I/O Voltage Inputs: Temperature Inputs: Current Inputs: Digital Inputs: Alarm Relays:
17 to 65Vdc <100mA @ 48Vdc or <200mA @ 24Vdc 4 segment LCD for V/I display, "OK / Major / Minor" 3-color, LED display, Web based GUI via ethernet RJ45 ethernet port (front), RS232 modem port (front)
1 + 1 internal 2 1 (0 + 1 internal on some models) 2 4 (3 + 1 internal on some models)
CXCI
Mechanical Dimensions H x W x D (in/mm): 3.5 x 1 x 11 / 88 x 26 x 280
Mounting:
Integrated on Cordex 2RU series 19" and 23" shelves
Environment Temperature: Humidity: Standards
-40 to 65°C / -40 to 149°F 0 to 95% non-condensing
Safety:
CSA C22.2 No 60950-1-03 CE marked
CordexTM 400 and 650W
Modular Switched Mode Rectifier
> Available in 13.5A @ 48Vdc and 14A @ 24Vdc > High power density > Power limiting and wide range AC input > 91% efficiency and power factor correction > Hot swappable, 2RU ultra compact design
Cordex 400W Rectifier Module
Electrical
Input Voltage: Power Output: Input Frequency: Power Factor: THD: Efficiency: Output Voltage: Output Current:
90 to 320Vac 400W (max) 45 to 70Hz >99% <5% >90% 20 to 29Vdc 14A (current limited)
10
Load Regulation:
Static <±0.5%, Dynamic <±2% for 50 to 100% load step, 2ms recovery time
Line Regulation:
Static <±0.1%, Dynamic <±1% for any change within rated limits
Mechanical
Dimensions H x W x D (in/mm): 3.4 x 2.8 x 9.5 / 88.4 x 71.6 x 242
Weight (lb/kg):
3 / 1.4
DC Rectifiers
Cordex 650W Rectifier Module
Electrical
Input Voltage (120Vac Model)
Operating: Extended: Power Output:
90 to 140Vac (output power 650W) 90 to 70Vac (derated output power) 650W at nominal 120Vac
Input Voltage (Universal 100 to 240Vac Model)
Operating: Extended: Operating:
176 to 320Vac (output power 650W) 176 to 90Vac (derated output power) 100 to 140Vac (output power 500W)
Power Output:
650W at nominal 208 to 240Vac and 500W at nominal 120Vac
Specifications Input Frequency: Power Factor: THD: Efficiency: Output Voltage: Output Current:
Load Regulation:
45 to 70Hz >99% <5% >91% (1% loss for 120Vac model) 42 to 58Vdc 12A @ 54Vdc (13.5A max)
Static <±0.5%, Dynamic <±2% for 50 to 100% load step, 2ms recovery time
Line Regulation:
Static <±0.1%. Dynamic <±1% for any change within rated limits
Mechanical
Dimensions H x W x D (in/mm): 3.4 x 2.8 x 9.5 / 88.4 x 71.6 x 242
Weight (lb/kg):
3 / 1.4
CXRC 24-400W
Noise Wide Band Noise: Psophometric Noise: Features Indicators: Cooling:
Adjustments (via CXCI Controller):
Protection:
Environment Operation Temperature: Storage Temperature: Humidity: Elevation: Heat Dissipation: Standards Safety: EMC:
Emissions:
Immunity:
<30mVrms, <150mVpk to pk
<1mV
AC mains OK--green LED Module alarm--red LED
Natural convection
Float and equalize voltage Battery test voltage High and low voltage alarms High voltage shutdown Current limit Start delay time Slope %
Current limit/short circuit Input/output fuses Output high voltage shutdown Output power limiting Thermal foldback/shutdown Input transient AC low line foldback/shutdown AC high voltage shutdown
-40 to 50°C / -40 to 122°F (power derated up to 70°C / 158°F)
-40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 3000m / -1640 to 9840ft <94BTU per hour
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia) EN 61000-3-2 EN 61000-3-3
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3
CordexTM 400W/650W
Rectifier Shelf Systems
> Integrated DC distribution with optional LVD > Integrated 24 and 48Vdc shelf
power systems up to 2.6kW > Bulk 24 and 48Vdc power
systems up to 3.2kW > 19" and 23" rack mounting solutions > Designed for CSA, UL, CE, FCC
and C-tick standards
Cordex 48V-2.6kW Shelf System Cordex 24V-1.6kW Shelf System
Cordex 24-400W Rectifier Shelves
Rectifiers
Controllers
Distribution
Cordex 48-650W Rectifier Shelves
Rectifiers
Controllers
Distribution
19/23" 2RU
4 x CXRC
Universal Mount 24-400W
1 x CXCI
(4) AM bullet type breakers
19/23" 2RU
4 x CXRC
Universal Mount 48-650W
1 x CXCI
(4) AM bullet type breakers
19/23" 2RU
5 x CXRC
Universal Mount 24-400W
1 x CXCI
Bulk power for external distribution panel
19/23" 2RU
5 x CXRC
Universal Mount 48-650W
1 x CXCI
Bulk power for external distribution panel
19" and 23" Shelf Systems
23" 2RU Front Access
4 x CXRC 48-650W
1 x CXCI
(4) AM bullet (10) GMT fuse
11
DC Rectifiers
650W Cordex 2.6kW shelf power system with CXCI controller and bullet breaker distribution
650W Cordex 3.2kW bulk power system with CXCI controller. Optional LVD shunt with battery breaker
650W Cordex 2.6kW front access shelf power system with CXCI controller and bullet/ fuse distribution
650W Cordex 1.9kW front access shelf power system with CXCI controller and plug-in/fuse distribution
400W Cordex 1.6kW shelf power system with CXCI controller and bullet breaker distribution
400W Cordex 2kW bulk power system with CXCI controller
19" 2RU Front Access
3 x CXRC 48-650W
1 x CXCI
(4) AM plug-in (10) GMT fuse
19" Shelf Systems
Mechanical
Dimensions H x W x D (in/mm): 3.5 x 17.1 x 11.9 / 89 x 435 x 302
Weight (lb/kg):
15.5 / 6.9
Note: Shelf P/Ns do not include modules or distribution breakers Weights do not include modules Dimensions do not include mounting bracket
23" Front Access Shelf Systems
Mechanical
Dimensions H x W x D (in/mm): 3.5 x 21.4 x 12 / 88.9 x 543.6 x 304.8
Weight (lb/kg):
37 / 16.8 (fully equipped with four rectifiers)
Note: Shelf P/Ns do not include modules or distribution breakers Weights do not include modules Dimensions do not include mounting bracket
Communication Ports CAN: Ethernet: Environment Operating Temperature: Storage Temperature: Humidity: Elevation: Cooling:
Interface to control rectifiers. Smart peripherals 10/100 Base-T for TCIP/SNMP features
-40 to 50°C / -40 to 122°F -40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 3000m / -1640 to 9840ft Natural or forced convection, vertical airflow
Cordex HPTM 1.2kW
Modular Switched Mode Rectifier
> 93% efficiency for increased Op-Ex savings and reduced carbon footprint
> High temperature operation for installation in harsh outdoor environments
> 1RU x 2RU footprint for flexible and multiple mounting options > High power density (21.8W/in3) yields more space
for revenue generating equipment > Wide AC input range for a variety of global installation requirements
Cordex HP 1.2kW
DC Rectifiers
Efficiency % (normal operating conditions)
Cordex HP 1.2kW
Electrical
Features
Nominal Input Voltage:
176 to 276Vac
Input Voltage Extended (Low): 90 to 175Vac (derated output power)
Input Voltage Extended (High): 277 to 300Vac (derated power factor)
Input Current Nominal:
7.5A max
Input Current 90 to 132Vac: 6A max
Input Frequency:
45 to 70Hz
Power Factor:
>99%
12
THD:
Efficiency:
<5% @ nominal input voltage
>93% 50 to 100% load (nominal AC input) >90% 40 to 100% load (120Vac input)
Output Voltage:
42 to 58Vdc
Output Power (Nominal AC Input):
1200W
Output Power 110 to 132Vac:
600W (derated linearly to 491W @ 90Vac)
Output Current (Nominal AC Input):
22.2A @ 54V (25A max @ 48V)
Indicators: Cooling: Adjustments (Via CXC Controller):
Protection:
Standards
AC mains OK -- green LED DC output OK -- green LED Module alarm -- red LED
Fan cooled
Float and equalize voltage Battery test voltage High and low voltage alarms High voltage shutdown Current limit Start delay time Slope %
Current limit/short circuit Input/output fuses Output high voltage shutdown Output power limiting Thermal foldback/shutdown Input transient AC low line foldback/shutdown AC high voltage shutdown
Output Current 110 to 132Vac:
Load Regulation:
Line Regulation:
Noise Web Band: Psophometric: Mechanical Dimensions H x W x D (in/mm): Weight (lb/kg):
12.5A max (derated linearly to 10.2A @ 90Vac) Static <±0.5%, Dynamic <±1% for 40 to 90 to
40% lead step, 2ms recovery time Static <±0.1%, Dynamic <±1% for any change
within rated limits
<30mVrms, <150mV pk to pk <2mV
1.63 x 3.34 x 10.11 / 41.4 x 84.8 x 256.8 2.7 / 1.2
Safety: EMC:
Emissions:
Immunity:
CSA C22.2 No 60950-1-03 CE marked
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia) EN 61000-3-2 EN 61000-3-3
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3
Environment
Operation Temperature:
Storage Temperature: Humidity: Elevation: Heat Dissipation:
-40 to 65°C / -40 to 149°F (power derated up to 80°C / 176°F)
-40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 3000m / -1640 to 9840ft <308BTU per hour
NEBS / Telcordia:
GR-1089-CORE GR-63-CORE
Cordex HP 1.2kW Efficiency
94
93
93.53%
92
91
20
30
40
50
60
70
80
90
100
% Rectifier Load
Cordex HPTM 1.2kW
Modular Rectifier Shelf Systems
> Multiple 48V configurations up to 125A for various 48Vdc applications
> High Efficiency design for increased Op-Ex savings > High temperature rated fan-cooled design
for harsh outdoor installations > Wide range AC input and IEC line
cords for multiple AC services > Front access options for space restricted enclosures
CXRF-HP 48-1.2kW
Cordex 48-1.2kW Rectifier Shelves
2RU Front Access Shelf System
Rectifiers
Controllers
Distribution
Mechanical
19/23" 2RU Universal Mount (Front Access)
4 x CXRF HP 48-1.2kW
1 x CXCM1
(4) AM plug-in (10) GMT fuse
Dimensions H x W x D (in/mm): Shelf Weight (lb/kg): Rectifier Weight (lb/kg):
3.5 x 17.3 x 12 / 88 x 439.5 x 305 10.03 / 4.55 2.72 / 1.23
19/23" 1RU Universal Mount (Bulk Power w/ CXC)
4 x CXRF HP 48-1.2kW
1 x CXCM1
Bulk power for external distribution
Note: Rectifier front handle adds additional 0.49 / 12.5 depth
1RU Rear Access Shelf System
Mechanical
Dimensions H x W x D (in/mm): 1.7 x 17.3 x 12 / 44 x 439.5 x 305
13
19/23" 1RU Universal Mount (Bulk Power)
5 x CXRF HP 48-1.2kW
19" and 23" Shelf Systems
N/A (External)
Bulk power for external distribution
Shelf Weight (lb/kg):
6.6 / 3
Rectifier Weight (lb/kg):
2.72 / 1.23
Note: Rectifier front handle adds additional 0.49 / 12.5 depth. Shelf P/Ns do not include modules or distribution breakers. Dimensions do not include mounting bracket
Communication Ports
19/23" 2RU universal mount (Front Access)
CAN: Ethernet: Environment
Interface to control rectifiers, Smart peripherals 10/100 Base-T for TCIP/SNMP features
DC Rectifiers
Operating Temperature (Standard):
-40 to 65°C / -40 to 149°F
19/23" 1RU universal mount (Bulk Power w/ CXC)
19/23" 1RU universal mount (Bulk Power)
Operating Temperature (Extended):
Storage Temperature: Humidity: Elevation: Cooling: Components 877-690-19: 877-671-19: 747-622-20-000: 567-837-19: 036-201-20-000:
-40 to 80°C / -40 to 176°F (derated output power) -40 to 80°C / -40 to 176°F 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft Fan cooled (front to rear)
5-15P (120V) line cord, 2.m Universal lmc cord, ying leads, 3.5m Blank plate Kydex rear cover (1RU only) CXCM1 I/O terminal black kit (1RU only)
CordexTM 1.8kW
Modular Switched Mode Rectifier and Shelf
> Available in 37.5A @ 48Vdc > High power density, fan cooled > Universal, wide range AC input > 91% efficiency and power factor correction > Hot swappable, 2RU ultra compact design
Cordex 48-1.8kW
Cordex 1.8kW
Electrical
Environment
Nominal Input Voltage:
208 to 277Vac
Operating Temperature:
-40 to 65°C / -40 to 149°F
Operating Input Voltage:
176 to 312Vac
Storage Temperature:
-40 to 85°C / -40 to 185°F
Extended Input Voltage:
176 to 90Vac (derated power)
Humidity:
0 to 95% non-condensing
Input Frequency:
45 to 66Hz
Elevation:
-500 to 2800m / -1640 to 9186ft
Power Output:
Power Factor:
14
THD:
Efficiency:
Output Voltage:
Output Current:
Load Regulation: Line Regulation:
1800W continuous @ nominal l/P 1150W (115 to135Vac) (derated linearly to 900W @ 90Vac)
>0.99 (50 to 100% load) <5% >91% 42 to 60Vdc
37.5A @ 48Vdc (nominal l/P) 24A @ 48Vdc (115 to 135Vac) (derated linearly to 18.75W @ 90Vac)
<±0.5% (static) <±0.1% (static)
Heat Dissipation: Standards Safety: EMC:
Emissions:
<608BTU per hour
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia) EN 61000-3-2 EN 61000-3-3
DC Rectifiers
Transient Response: Noise Voice Band:
Wide Band:
±2% for 50 to 100% load step, 2ms recovery time
<32dBrnC <30mVrms (10kHz to 10MHz), <150mVpk to pk (10kHz to 100MHz)
Immunity:
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3
Psophometric: Acoustic:
<1mV <60dBA @ 1m / 3ft
19" and 23" Shelf Systems
Mechanical
Mechanical
Dimensions H x W x D (in/mm): 3.3 x 3.9 x 9.3 / 84 x 100 x 235
Dimensions H x W x D (in/mm): 3.5 x 17.2 x 12.2 / 89 x 438 x 310
Weight (lb/kg):
6.2 / 2.8
Weight (lb/kg):
19 / 8.5
Features Indicators: Controls:
AC mains OK--green LED Module OK--green LED Module fail--red LED
CAN interface to CXC
Mounting:
19" flush or center mount, 23" center mount only
23" Shelf Systems
Mechanical
Dimensions H x W x D (in/mm): 3.5 x 21.3 x 12.2 / 89 x 541 x 310
Weight (lb/kg):
22 / 10
Adjustments (via CXC Controller):
Float voltage, Equalize voltage, High voltage alarm, Low voltage alarm, High voltage shutdown, Current limit, Slope, Start delay timers
Mounting: Connections
23" flush or center mount
Protection:
Current limit/short circuit, Start delay, Input/ output fuses, Output high voltage shutdown, Power limiting, Thermal foldback/shutdown, Input transient, AC low line foldback/shutdown, AC high voltage shutdown
Input: Output: Chassis Ground: CAN Communication:
Terminal blocks, mini-fit connectors (23" only) Bus adapters with " studs on 1" center holes ¼" studs on " centers RJ12 offset
Typical 7.2kW 23" Shelf with CXCM2
Cordex HPTM 2kW
Modular Switched Mode Rectifier
> 94% efficiency for increased Op-Ex savings and reduced carbon footprint
> High temperature operation for installation in harsh outdoor environments
> Backwards compatible solution with Cordex 1.8kW rectifier shelves and power solutions
> Wide AC input operating range that satisfy a variety of global installation requirements
Cordex HP 2kW
Cordex HP 2kW
Electrical Nominal Input Voltage: Input Operating Voltage: Input Extended Voltage: Input Frequency:
Power:
Power Factor: THD: Efficiency: Output Voltage:
Output Current:
Load Regulation: Line Regulation:
Transient Response:
Noise
Web Band:
Voice Band: Psophometric: Acoustic: Mechanical Dimensions H x W x D (in/mm): Weight (lb/kg): Environment Standard Temperature:
Extended Temperature:
Storage Temperature: Humidity: Elevation: Heat Dissipation:
208 to 277Vac 187 to 320Vac 187 to 90Vac (derated power) 45 to 70Hz 2000W continuous/module (~1250W Output at 120Vac Input) >0.99 (50 to 100% load) <5% 94% 42 to 60Vdc 37A @ 54Vdc (41.6A max. 48V) (~26A @ 48Vdc at 120Vac Input) <±0.5% (static) <±0.1% (static) ±2% for 40 to 90% load step, 10ms recovery time
<30mV RMS (10kHz to 10MHz) <150mV pk to pk (10kHz to 100MHz) <38dBrnC <2mV <55dBa @ 1m / 3ft
3.3 x 3.94 x 9.25 / 84 x 100 x 235
6.6 / 3
-40 to 55°C / -40 to 131°F -40 to 75°C / -40 to 167°F (derated power) ~1800W @ 65°C / 149°F -40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft <437BTU per hour
Features
Indicators:
Controls: Adjustments (Via CXC Controller):
AC mains OK -- green LED DC output OK -- green LED Module alarm -- red LED
CAN interface to CXC controller
Float and equalize voltage, High and low voltage alarms, High voltage shutdown, Current limit, Start delay time, Slope %
Protection:
Current limit/short circuit, Start delay, Input/
output fuses, Output high voltage shutdown,
15
Power limiting, Thermal foldback/shutdown,
Input transient, AC low line foldback/shutdown,
AC high voltage shutdown
Standards
DC Rectifiers
Safety: EMC:
Emissions:
CSA C22.2 No 60950-1-03, UL 60950-1 1st Edition, CE marked
ETSI 300 386
CFR47 (FCC) Part 15 Class B, ICES-03 Class B EN55022 (CISPR 22) Class B, C-Tick (Australia) EN 61000-3-2, EN 61000-3-3
Immunity:
EN 61000-4-2, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11, ANSI/IEEE C62.41 Cat B3
19" / 23" Shelf
Mechanical
Dimensions H x W x D (in/mm): 3.4 x 17.4 x 12 / 86.3 x 442 x 304.8
Weight (lb/kg):
14.7 / 6.7
Mounting (4 Modules):
Fits 19" rack flush/center mount Fits 23" rack center mount only
23" Shelf
Mechanical
Dimensions H x W x D (in/mm): Weight (lb/kg): Mounting (5 Modules):
3.4 x 20.8 x 12 / 86.3 x 530 x 304.8 18.1 / 8.2 Fits 23" racks only flush/center mount
Connections Input: Output:
Chassis Ground:
CAN Communications:
Molex mini-fit type Bus adapters with " studs on 1" centers
Compression lug 6 to 16mm2 (10 to 6AWG)
RJ 12 offset
Typical 10kW 23" Shelf with CXCI
Typical 8kW 23"Shelf with CXCM2
CordexTM 3.6kW
Modular Switched Mode Rectifier
> Available in 130A @ 24Vdc or 75A @ 48Vdc > High power density, over 21kW per 23" shelf > Power limiting and wide range AC input > High efficiency and power factor correction > Hot swappable, 4RU ultra compact design
Cordex 48-3.6kW
Cordex 3.6kW
Electrical
Environment
Nominal Input Voltage:
208 to 277Vac
Operating Temperature:
-40 to 65°C / -40 to 149°F
Operating Input Voltage: Extended Input Voltage: Input Frequency: Power Output: Power Factor:
176 to 312Vac 176 to 90Vac (derated power) 45 to 66Hz 3600W continuous/module >0.99 (50 to 100% load)
Storage Temperature: Humidity: Elevation: Heat dissipation:
-40 to 85°C / -40 to 185°F 0 to 95% non-condensing -500 to 4000m / -1640 to 13120ft <1176BTU per hour
THD:
<5%
Standards
16
Efficiency:
Output Voltage:
Float Voltage:
>92% 42 to 60Vdc 48 to 58Vdc
Safety:
Output Current: Load Regulation:
66A @ 54Vdc (75A max 48V) <±0.5% (static)
EMC:
Line Regulation:
<±0.1% (static)
Transient Response: Noise
±2% for 50 to 100% load step, 2ms recovery time
Emissions:
Voice Band:
<32dBrnC
CSA C22.2 No 60950-1-03 UL 60950-1 1st Edition CE marked IEC/EN 60950-1
ETSI 300 386
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B C-Tick (Australia) EN 61000-3-2 EN 61000-3-3
DC Rectifiers
Wide Band:
<30mVrms (10kHz to 10MHz), <150mVpk to pk (10kHz to 100MHz)
Psophometric: Acoustic:
<1mV <60dBA @ 1m / 3ft
Mechanical
Dimensions H x W x D (in/mm): 6.3 x 3.4 x 11.8 / 160 x 87 x 300
Weight (lb/kg):
10 / 4.6
Features
Immunity: NEBS:
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3
GR-1089 CORE GR-69 CORE
Indicators:
AC mains OK--green LED Module OK--green LED Module fail--red LED
Controls:
CAN interface to CXC
Adjustments (via CXC Controller):
Float voltage, Equalize voltage, High/Low voltage alarm, High voltage shutdown, Current limit, Slope, Start delay
Protection:
Current limit/short circuit, Start delay, Input/ output fuses, Output high voltage shutdown, Power limiting, Thermal foldback/shutdown, Input transient, AC low line foldback/shutdown
Cordex HPTM 4kW
Modular Switched Mode Rectifier
> Near 95% efficiency for increased OPEX savings and reduced carbon footprint > High temperature tolerance for installation in harsh outdoor environments > Backwards compatibility with Cordex 3.6kW rectifier shelves
and power solutions provide cost effective upgrade path > Wide AC input operating range that satisfies a
variety of global installation requirements
Cordex HP 4kW
Electrical Nominal Input Voltage: Operating Input Voltage: Extended Input Voltage: Input Frequency: Power Output: Power Factor: THD: Efficiency: Output Voltage: Flood Voltage: Output Current: Load Regulation: Line Regulation: Transient Response: Noise Voice Band:
208 to 277Vac 187 to 320Vac 187 to 95Vac (derated power) 45 to 66Hz 4000W continuous/module >0.99 (50 to 100% load) >7% 94.9% peak @ 240Vac 44 to 60Vdc 48 to 58Vdc 74A @ 54Vdc (85A max 48V) <±0.5% (static) <±0.1% (static) ±3% for 40 to 90% load step
<38dBrnC
Wide Band:
<20mVrms (10kHz to 10MHz), <100mVpk to pk (10kHz to 100MHz)
Psophometric:
<2mV
Acoustic:
<60dBA @ 1m / 3ft (at 30°C / 86°F)
Mechanical
Dimensions H x W x D (in/mm): 6.3 x 3.4 x 11.8 / 160 x 87 x 300
Weight (lb/kg):
11 / 5
Features
Indicators:
AC mains OK--green LED DC Output OK--green LED Module fail--red LED
Controls:
CAN interface to CXC Controller
Adjustments (via CXC Controller):
Float voltage Equalize voltage High/Low voltage alarm High voltage shutdown Current limit Slope Start delay timers
Protection:
Current limit/short circuit Start delay Input/output fuses Output high voltage shutdown Power limiting Thermal foldback/shutdown Input transient AC low line foldback/shutdown AC high voltage shutdown
CordexHP 4kW
Environment
Standard Operating Temperature:
-40 to 55°C / -40 to 131°F
Extended Operating Temperature:
-40 to 75°C / -40 to 167°F (derated power) ~ 3600W @ 65°C / 149°F
Storage Temperature:
-40 to 85°C / -40 to 185°F
Humidity:
0 to 95% non-condensing
Elevation:
-500 to 4000m / -1640 to 13120ft
Heat dissipation:
<1190BTU per hour
17
Standards
Safety:
CSA C22.2 No 60950-1-03 UL 60950-1 CE marked IEC/EN 60950-1
EMC:
ETSI 300 386
Emissions:
CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B EN 61000-3-2 EN 61000-3-3
DC Rectifiers
Immunity:
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ANSI/IEEE C62.41 Cat B3
19" and 23" Shelf (5 Modules)
Mechanical
Dimensions H x W x D (in/mm): 6.9 x 17.4 x 15.3 / 177 x 442 x 389
Weight (lb/kg):
19 / 8.5
Mounting:
19" flush or center mount, 23" center mount only
23" Shelf (6 Modules)
Mechanical
Dimensions H x W x D (in/mm): 6.9 x 20.8 x 15.3 / 177 x 530 x 389
Weight (lb/kg):
21 / 9.5
Mounting:
23" flush or center mount
Connections Input: Output: Chassis Ground: CAN Communication:
Box type terminal block, 6 to 16mm2 (10 to 6AWG) Bus adapters with " studs on 1" centers Compression lug, 6 to 16mm2 (10 to 6AWG) RJ12 offset
CXPS 48-1.2-225
Standard 48Vdc Power System
> Integrated 48V, 225A system package with front access distribution
> High efficiency design for increased Op-Ex savings > High temperature rated fan-cooled design
for harsh outdoor installations > Wide range AC input and IEC line cords for multiple AC service > Flexible ordering options including configurations
with racks and battery trays
CXPS 48-1.2-225
CXPS 48-1.2-225
Electrical
Mechanical
Input Operating Voltage: Extended Voltage (High): Extended Voltage (Low):
Current:
208/220/240Vac (Continuous operation 90 to 300Vac) 277 to 300Vac (derated power factor) 90 to 176Vac (derated output power)
7.5A max per module (176 to 300Vac) 6A max per module (90 to 176Vac)
Dimensions H x W x D (in/mm):
System Weight (lb/kg): Rectifier Weight (lb/kg): Mounting:
8.7 x 17.2 x 14.8 / 222 x 438 x 376 (-000 configuration - excludes mounting brackets, rear cover, and module handle)
47/21.3 6.2/2.8 each 19/23" universal mount (center or flush)
Frequency:
18
Efficiency:
Power Factor:
45 to 66Hz >93% (50 to 100% load @ nominal voltage) >.99
Output
Current
System: Rectifier:
225A max @ nominal I/P 112.5A @ 115Vac I/P
25A @ 48Vdc (nominal I/P) 12.5A @ 48Vdc (115Vac) (Subject to derating below 110Vac)
Connections Load Breaker: Battery Breaker: Return Bar:
Alarm:
CXCM1 Input: Access: Environment
14x sets, ¼"-20 studs on " centers 4x sets, ¼"-20 studs on " centers 18x sets, ¼" holes on " centers
Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
25-pin D-Sub cable Front access after installation
DC Rectifiers
Power
System: Rectifier:
Features
10800W max @ nominal I/P 5400W @ 115Vac I/P
1200W max @ nominal I/P 600W @ 115Vac (Subject to derating below 110Vac)
Operating Temperature: Humidity: Elevation:
-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output
0 to 95% non-condensing
-500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with temperature derated to -40°C / 104°F output
Configurations 053-691-20-000: 053-619-20-040: 053-691-20-031:
Rectifier:
Distribution:
Base system with 19/23" universal mounting
System mounted in 23", 44RU Z4 rack with 2x battery trays for 2x 48V strings
System mounted in 19", 44RU Z4 rack with 3x battery trays for 3x 48V strings
Up to 9x HP 48V-1.2kW rectifier positions
14x load breaker positions (mid-trip, plug-in style) 4x battery breaker positions (series-trip, plug-in) Low voltage disconnect Shunt
Components 877-690-19: 877-671-19: 747-622-20-000: 470-347-10: 747-503-20: 747-504-20:
5-15P (120V) line cord, 2.5m Universal lmc cord, flying leads, 3.5m Blank plate 100A battery breaker 150A battery breaker 250A battery breaker
Controller:
CXCM1 Modular Controller
CXPS 48-1.8-i and CXPS 48-1.8-M2
Standard 48Vdc Power System
> Integrated 48V, 150-262A system package with front access distribution
> High temperature rated fan cooled design for harsh outdoor installations
> Wide range AC input for multiple worldwide AC services > Modular controller with touch screen display for full
local control over system (CXPS 48-1.8-M2 only) > Flexible ordering options including configurations with
racks and battery trays
CXPS 48-1.8-M2
CXPS 48-1.8-i and CXPS 48-1.8-M2
Electrical
CXPS 48-1.8-i
CXPS 48-1.8-M2
Mechanical
CXPS 48-1.8-i
CXPS 48-1.8-M2
Input Nominal Input Voltage: Input Current:
176 to 312 Vac, 90 to 176Vac (derated O/P power) 14.6A @ 240Vac, 12.2A @ 120Vac (per module)
Dimensions H x W x D (in/mm):
8.7 x 17.2 x 12.2 / 222 x 438 x 310 (-000 configuration - excludes mounting brackets, rear cover, and module handle)
Input Frequency:
45 to 66Hz
45 to 66Hz
System Weight (lb/kg): 42 / 19
62 / 28
Efficiency:
>91% (50 to 100% load @ norminal voltage)
Rectifier Weight (lb/kg): 6.2 / 2.8 each
6.2 / 2.8 each
Input Power Factor:
>.99
>.99
Mounting:
19/23" universal mount (center or flush)
Output
Connections
Load Breaker:
14x sets, ¼"-20 studs on " centers
System:
150A max @ nominal I/P 262.5A max @ nominal I/P 96A max @ 120Vac I/P 96A max @ 120Vac I/P
Battery Breaker:
4x sets, ¼"-20 studs on " centers
19
Current
Rectifier:
37.5A @ 48Vdc (nominal I/P) 24A @48Vdc (115 to 135Vac) (derated linearly to 18.75A @ 90Vac)
Return Bar: Rectifier Input:
18x sets, ¼" holes on " centers
HOT: 2x sets, " holes on 1" centers RTN: 2x sets, " holes on 1" centers
System:
7200W max @ nominal I/P 12600W max @ nominal I/P
4600W @ 120Vac I/P
8050W @ 120Vac I/P
Alarm: CSCI Input:
Screw terminal 1.31mm2 to 0.128mm2
25-pin D-Sub cable
-
DC Rectifiers
Power
Rectifier:
Features Configurations
1800W max @ nominal I/P 1150W (115 to 135Vac)
(derated linearly to 900W @ 90Vac)
CXCM2 Input:
-
Access:
Environment
Operating Temperature:
3x DB-style cable connections Front access after installation
-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output
Base System with 19/23" Universal Mounting:
053-990-20-000
053-991-20-000
System Mounted in 23", 44RU Z4 Rack with 2x Battery Trays for 2x 48V Strings:
053-990-20-040
053-991-20-040
System Mounted in 19", 44RU Z4 rack with 3x Battery Trays for 3x 48V Strings:
Rectifier:
053-990-20-031
053-991-20-031
Up to 4x 48V-1.8kW rectifier positions
Humidity:
Elevation:
Components 058-156-20: 058-157-20: 470-347-10: 747-503-20: 747-504-20:
0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with derated output
23" battery tray expansion kit (for use with -040 configuration) 19" battery tray expansion kit (for use with -031 configuration) 100A battery breaker 150A battery breaker 250A battery breaker
Distribution:
14x load breaker positions (mid-trip, plug-in style) 4x battery breaker positions (series-trip, plug-in) Low voltage disconnect Shunt
Controller:
CXCI integrated controller CXCM2 integrated controller
CXPS 48-1.8-i
CXPS 48-1T
48V 375 to 825A Power Systems
> 48Vdc systems using high density 3.6kW rectifiers > Front access DC connections > CXCM4 advanced modular controller > Flexible integrated rack options > Integrated system shunt and LVD
CXPS 48V 375A
CXPS 48-1T
Configurations
CXPS 48-1T (with LVD)
053-392-20-000:
Base system with 23" mounting
053-392-20-010:
System mounted in 22RU (½ height) battery mount rack
053-392-20-020:
System mounted in 44RU Zone 4 seismic rack
053-392-20-030:
System mounted in 44RU Zone 4 rack with 3x battery trays for 3x 48V strings
Rectifier:
Up to 5x 48V to 3.6kW rectifier positions
Distribution:
20
Controller:
18x AM plug-in breaker positions, 10x GMT type fuse positions, Shunt, Low voltage disconnect
CXCM4 modular controller
CXPS 48-1T_b (no LVD)
053-692-20-000:
Base system with 23" mounting
053-692-20-010:
System mounted in 44RU Zone 4 seismic rack
053-692-20-020:
System mounted in 44RU Zone 4 rack with 3x battery trays for 3x 48V strings
DC Rectifiers
Rectifier:
Up to 5x 48V to 3.6kW rectifier positions
Distribution:
24x AM plug-in breaker positions, 10x GMT type fuse positions, Shunt, Low voltage disconnect
Controller:
CXCM4 modular controller
Electrical
Input Voltage:
176 to 320Vac
Current:
16.8A @ 240Vac nominal (per rectifier module)
Frequency:
45 to 66Hz
Power Factor:
>0.99
Output Voltage:
42 to 60Vdc
Current:
System: 375A (expandable to 600A with additional CXRF shelf), Rectifier: 75A @ 48Vdc
Power:
System: 18kW (expandable to 28.8kW with additional CXRF shelf), Rectifier: 3600W max
Environment
Temperature: Humidity: Elevation:
-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output
0 to 95% non-condensing
-500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with derated output
Mechanical Dimensions H x W x D (in/mm): Weight (lb/kg): Mounting: Connections Load Breaker:
GMT Fuses:
Battery Terminations: Rectifier Input: Alarm Connections:
Access: Related Components 010-567-20: 058-716-20
19.25 x 23 x 18.8 / 488 x 584 x 477 (-000 configuration - excludes mounting brackets) 110 / 49.8 (no rectifiers or breakers included) 23" center mount
Hot: ¼" -20 studs on " centers Return: ¼" holes on " centers Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) " holes on 1" centers 4x sets per polarity " holes on 1" centers Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) Cable: top or bottom User: front access after installation
Cordex 48V-3.6kW rectifier Cordex rectifier CXRF 48-3.6kW expansion shelf kit
CXPS 48-1T Internal Distribution
CXPS 48-2T
48V 375 to 825A Power Systems
> 48Vdc systems using high density 3.6kW rectifiers > Front access DC connections > CXCM4 advanced modular controller > Flexible integrated rack options > Integrated system shunt and LVD
CXPS 48V 825A
CXPS 48-2T
Configurations CXPS 48-2T (with LVD) 053-393-20-000: 053-393-20-010: 053-393-20-020: 053-393-20-030: Rectifier: Distribution: Controller: CXPS 48-2T_b (no LVD) 053-693-20-000: 053-693-20-020: 053-693-20-030: Rectifier: Distribution: Controller: Electrical Input Voltage: Current: Frequency: Power Factor: Output Voltage:
Current:
Power:
Environment
Temperature:
Humidity:
Elevation:
Base system with 23" mounting System mounted in 22RU (½ height) battery mount rack System mounted in 44RU Zone 4 seismic rack System mounted in 44RU Zone 4 rack with 3x battery trays for 3x 48V strings Up to 11x 48V-3.6kW rectifier positions 38x AM plug-in breaker positions, 10x GMT type fuse positions, Shunt, Low voltage disconnect CXCM4 modular controller
Base system with 23" mounting System mounted in 44RU Zone 4 seismic rack System mounted in 44RU Zone 4 rack with 3x battery trays for 3x 48V strings Up to 11x 48V-3.6kW rectifier positions 48x AM plug-in breaker positions, 10x GMT type fuse positions, Shunt CXCM4 modular controller
176 to 320Vac 16.8A @ 240Vac nominal (per rectifier module) 45 to 66Hz >0.99 42 to 60Vdc System: 825A (expandable to 1200A with additional CXRF shelf), Rectifier: 75A @ 48Vdc
System: 39.6kW (expandable to 57.6kW with additional CXRF shelf), Rectifier: 3600W max
-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft -500 to 4000m / -1640 to 13124ft with derated output
Mechanical
Dimensions H x W x D (in/mm):
29.7 x 23 x 18.8 / 755 x 584 x 477 (-000 configuration - excludes mounting brackets)
Weight (lb/kg): Mounting:
155 / 70.3 (no rectifiers or breakers included) 23" center mount
Connections
Load Breaker:
Hot: ¼" -20 studs on " centers Return: ¼" holes on " centers
GMT Fuses:
Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
Battery Terminations:
" holes on 1" centers 4x sets per polarity
21
Rectifier Input: Alarm Connections:
" holes on 1" centers
Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
Access:
Cable: top or bottom User: front access after installation
Related Components
010-567-20: 058-716-20
Cordex 48V-3.6kW rectifier Cordex rectifier CXRF 48-3.6kW expansion shelf kit
DC Power Systems
CXPS 48-2T Internal Distribution
CordexTM System
48V 2000A Power Systems
> Up to 2000A system > Cordex modular rectifiers > User-configurable, modular distribution tiers > Intelligent system control and communication
Cordex System
Electrical
AC Input:
Rectifier Voltage:
22
Output Voltage:
Output Current:
Power:
Max. Bus Capacity:
DC Power Systems
Mechanical
Dimensions H x W x D (in/mm):
Weight (lb/kg):
Environment Temperature: Humidity: Elevation:
Single Phase, 208 to 277Vac Dual 3 Phase, 208 to 240Vac (w/o neutral) Dual 3 Phase, 360 to 480Vac (with neutral) 208 to 277Vac 45 to 70Hz 42 to 58Vdc (Cordex rectifiers) 66A @ 54Vdc per 3.6kW rectifier 21.6kW per rectifier shelf 2000A system bus 600A max. per distribution tier
84 x 28.1 x 19 / 2133 x 714 x 483
Approx. 902 / 410 with 4 tier distribution center and 5 fully loaded Cordex shelves
0 to 50°C / 32 to 122°F 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft
Cordex 48V 2000A
Related Components Rectifiers:
Choose up to six Cordex 48V rectifiers per shelf
Choose up to six field-expandable shelves per system
Low Voltage Disconnect:
Distribution: AM-type/TPS Bullet Style: GJ Breaker: Cordex Controller: Battery Options:
LVD optional 48Vdc/600A (one per distribution tier)
Choose distribution center for 1 tier, 2 tier or 4 tier Terminations (breaker options for tiers 1 through 4) 2 x ¼-20 studs on " centers per pole
2 x -16 studs on 1" centers per pole; i.e., 2-pole breaker will have two sets
The system's monitoring and control center
2V Battery cell monitor (1 string) 12V Battery cell monitor (4 strings) Battery tray with breaker (12V blocks)
Tier 1 Can Be Equipped With:
24-position AM-type bullet style breakers* 20-position bullet style breakers* with LVD
Tiers 2 to 4 Can Be Equipped With:
24-position AM-type bullet style breakers* 20-position bullet style breakers* with LVD 3-position GJ (with or without LVD)
* Bullets style TPS fuse holder and GMT fuse blocks available
3 positions GJ breaker tier rated at 600Amps
3 positions GJ breaker tier with LVD rated at 600Amps
24 position bullet breaker tier rated at 600Amps
20 position bullet breaker tier with LVD rated at 600Amps
CordexTM System
48V 8000A Power Systems
> 8000A Capacity > Designed for MSCs, COs and
Cable Headend facilities > Cordex 3.6kW modular rectifiers > Circuit breaker and TPL fuse options > Internal bay-to-bay copper busswork > Expandable power and distribution bays > Optional overhead buss duct system
Cordex 48V 4000A
Cordex System
Electrical
Environment
AC Input: Rectifier Voltage: Max. Bus Capacity:
Single Phase, 208 to 277Vac Dual 3 Phase, 208 to 240Vac (w/o neutral) Dual 3 Phase, 360 to 480Vac (with neutral)
208 to 277Vac
10000A system 2000A per bay
Temperature:
0 to 50°C / 32 to 122°F
Humidity:
0 to 95% non-condensing
Elevation:
-500 to 2800m / -1640 to 9186ft
System Level Alarms/
Alarms/control parameters are user-programmable
Controls:
through built-in digital supervisory unit
23
DC Power Systems
Distribution Fuses
TPL: GJ/GJ1P: Output Termination TPL Fuse:
GJ Breaker:
2 position, 61 to 800A breakers 1 pole up to 225A 2 pole 250 to 400A 3 pole 450 to 700A
2 hole ½" dia. on 1¾" centers or 2 hole " dia. on 1" centers
1 pole and 2 pole are " to 16, 3 pole are 2 hole, ½" dia. on 1¾" centers or " dia. on 1" centers
Indicators:
LCD with touch screen System OK -- green LED System minor alarm -- yellow LED System major alarm -- red LED
Alarm Connections: Load Disconnect:
0.34 to 2.5mm2 (14 to 22AWG) 48Vdc/1200A x N mounted on load side (optional)
Smart Peripheral Modules
Shunt Mulitplexer: Battery Cell Monitor: Battery Cell Monitor:
16 shunts per module 1 string, 2V cells per module 4 strings, 12V blocks per module
Ground Bar:
Overhead buss ground, 15 sets of 2 hole ½" dia. on 1¾" centers (basic system)
Mechanical
Enclosure:
1.095mm (14 gauge) steel
Mounting:
Standard 23" relay rack (flush rack mount) in box bay
Dimensions H x W x D (in/mm): 84 x 28 x 28 / 2133.6 x 711.2 x 711.2
Weight (lb/kg):
Approx. 600 / 272 per bay (no rectifiers)
CXPS 2448-i
24 to 48V DC-DC Converter System
> Integrated 8kW capacity 24-48Vdc converter system with front access distribution
> Support for small to medium 48Vdc loads from legacy 24V power system
> Integrated Cordex CSCi for advanced local and remote monitoring and control
> Internal low voltage shutdown for cost effective integration into existing systems
> Universal 19/23" mounting for flexible installation options into existing racks
CXPS 24-48-i Power System
CXPS 24-48-i
Electrical Input
Voltage:
+21 to +30Vdc 90 to 176Vac (derated O/P power)
Current System:
24
Current Converter:
Efficiency:
Feed A: <188A @ +24V input (216A max) Feed B: <188A @ +24V input (216A max)
<94A @ +24V input (108A max) >88% (50 to 100% load @ nominal voltage)
Output
DC Converters
Current System: Current Converter Module: Power System: Power Rectifier:
148A max @ 54Vdc 37A max @ 54Vdc 8000W max @ 54Vdc output 2000W max @ 54Vdc output
Features
Configurations
053-997-20-000: Converter:
Base system with 19/23" universal mounting Up to 4x CXDF 24-48/2kW converter positions
Distribution:
18x load breaker positions (mid-trip, plug-in style), shunt
Controller:
CXCi integrated controller
Mechanical
Dimensions H x W x D (in/mm):
System Weight (lb/kg): Rectifier Weight (lb/kg): Mounting: Connections
Load Breaker: Return Bar:
Alarm:
CXCi Input: Access: Environment
Operating Temperature:
Humidity: Elevation:
8.75 x 17.24 x 12.2 / 222 x 438 x 310 (-000 configuration - excludes mounting brackets, rear cover, and module handle) 42 / 19 6.2 / 2.8 each 19/23" universal mount (center or flush)
18x sets, ¼"-20 studs on " centers 18x sets, ¼" holes on " centers Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) 25-pin D-Sub cable Front access after installation
-40 to 65°C / -40 to 149°F -40 to 75°C / -40 to 167°F derated output 0 to 95% non-condensing -500 to 2800m / -1640 to 9186ft
Distribution Centers
> Various modular distribution configurations > Complete front access > Integrated CordexTM system controller > Integrated shunt and LVD options > AM plug-in breaker, GJ breaker and GMT fuse options
DCP03 Distribution Center
Vista Distribution Panel
Part Number
Breakers
Single Tier:
020-645-20
AM plug-in
Two Tier:
020-646-20
AM plug-in
Four Tier:
020-635-20
AM plug-in
Modular Distribution Tier Options
Single Voltage:
24 Position AM plug-in 20 Position AM plug-in w/ 600A LVD 3 Position GJ 3 Position GJ w/ 600A LVD
Position 20-24 40-48 80-96
Capacity 600A 1200A 2000A
Mounting
RU
23"
7
23"
9
23"
17
12x Primary and 10x secondary (AM plug-in)
Dual Voltage:
16x Primary and 6x secondary (AM plug-in) 8x Primary (w/ LVD) and 10x secondary (AM plug-in)
25
12x Primary (w/ LVD) and 6x secondary (AM plug-in)
Note: Consult factory for NEBS L3 certified system solutions using Vista UDC's
DC Distribution Centers
Distribution Panel Overview
Vista Two Tier UDC
Part Number
020-107-20
020-588-20
020-589-20
Stand Alone Breaker / Fuse Panels
020-671-20 020-675-20 020-534-20
Fuse Position 0 16* 20* 24* 18* 0
Fuse Type TPS* TPS* TPS* TPS* -
Breaker Position 16/22 16 20 24 18 3
Breaker Type
AM bolt-in AM bolt-in AM bolt-in AM bolt-in AM bolt-in
GJ bolt-in
Capacity 550A
Mounting
Front Access
19/23"
No
400A
19/23"
Yes
400A
23"
Yes
600A
23"
No
600A -
19/23"
No
19/23"
No
RU Additional Options
3
Gnd bar
5
Gnd bar, LVD
5
Gnd bar, LVD
3
-
3
-
3
-
020-578-20
0
-
4
GJ bolt-in -
23
No
4
-
020-103-20
32
GMT
0
-
60A
19/23"
No
1
Gnd bar
020-005-20
20
GMT
0
-
90A
19/23"
No
1
Gnd bar
020-597-20
2
TPL
0
-
1200A
23"
No
4
Shunt
020-702-20
18*
TPS*
18
AM plug-in
300A
19/23"
Yes
Controller I/O,
3
LVD, Shunt,
Batt breakers
020-645-20
20-24"
TPS*
20-24
AM plug-in**
800A
23"
Yes
7
Controller, LVD, Shunt
Universal
10
GMT
-
Distribution
Centers:
020-646-20
40-48"
TPS*
40-48
AM plug-in**
1000A
23"
Yes
9
Controller, LVD, Shunt
10
GMT
-
020-635-20
80-96"
TPS*
80-96
AM plug-in**
2000A
23"
Yes
17
Controller, LVD, Shunt
10
GMT
-
Notes: * TPS Fuses with AM plug-in breaker cartridges may be used as an alternative to breakers ** Compatible with multiple pole AM plug-in breakers (110 to 250A)
DC Accessories
> Rack mount power sources including integrated distribution fuses save space and provide flexibility
> Distribution systems from 50A GMT fuse panels to 800A circuit breaker distribution centers
> 19"/23" universal rack mount
GMT Fuse Panels
GMT 50 Series
Circuit Breaker Panel
KTK Fuse Panel
HDDC: High Density
19"/23" rack mount, 1RU high
Flush mount and center positions
Standard capacity: 50A per input
19"/23" rack mount, 1RU high
Bright, color coded LED indicators for A/B input power status, A/B fuse failure alarms
High power density
Form-C alarm contacts for A/B input power fail, A/B fuse fail (4 relays)
26
Single input and dual input:
High ampacity: 120A per A/B input Bright, color coded LED indicators for A/B input power status, A/B fuse
· 10 GMT output
failure alarms
· 10A/10B output · 20 GMT output
Form-C alarm contacts for A/B input power fail, A/B fuse fail (4 relays) Dual input: 4A/4B and KTK 30A fuse outputs
GMT 100/High Capacity Series
HDDC: High Density
DC Accessories
19"/23" rack mount, 1RU high Flush mount and center positions Bright, color coded LED indicators for A/B input power status, A/B fuse failure alarms Single input, A/B insolated input and A/B/C redundant configuration available Included LED indicators, form-C alarm contacts
100 Series High power density and ampacity:
· 100A per input: (single input, A/B input)
· 70A: (A/B/C- source) Form-C alarm
· 16 GMT outputs · 16A/16B GMT outputs
C-output diode routed, 32 fused redundant outputs
High Capacity Series 24 GMT fuse sockets 150A input bus rating Configurations include:
· Single input, 24 fuses · A/B input, 12A/12B fuses,
A/B/C version, 24 fuses
TPA Fuse Panel
19"/23" rack mount, 3RU high Single input A/B isolated input A/B input C-output redundant diode routed High breaker count to support VOD server redundant power supply circuit
requirements and combined high current load High power density and ampacity:
· 300A per input: (single input, A/B input) · 200A combined load: (A/B/C-source) Accepts up to 22 plug-in bullet terminal circuit breakers Alphanumeric LCD display for voltage, load current per bus, breaker status Form-C alarm contacts for Major and Minor alarms
1RU, 19"/23" rack mount Single input, A/B isolated input and A/B/C redundant configurations available 12 TPA fuse sockets 200A input bus rating Includes LED indicators, form-C alarm contacts
DC Accessories
> Compact, high power density DC distribution fuse panels and circuit breaker panels
> High current, high fuse/breaker count in a small RU footprint
> Battery disconnect for circuit breaker protection of the entire facility DC plant
DCX Series
HDX Compact
Matrix Breaker Panel
DCX Series
EEE Disconnect One Series
1RU, 19"/23" rack mount
27
Single input, A/B insolated input and A/B/C redundant configurations available
400, 600, 800, 1000, 1200, 1800 and 2400A models Direct Battery Terminal mounting options for most battery configurations. Bus
adapter and hardware kits provided for individual battery cell size configurations. LED indicators for On Line/Off Line status, EPO trip and general fault alarm status Form-C relay contact output for remote monitoring of status
200A input bus rating Uses new "slimline" 1RU circuit breakers (Breaker choices available from
5A to 100A) Includes LED indicators, form-C alarm contacts Configurations include:
Integrated EPO function for remote trip
· Single input, 20 breakers
Over-current and non over-current models
· A/B input, 10A/10B breakers, A/B/C version, 16 breakers
Super HDX
HDX Compact
DC Accessories
2RU, 19"/23" rack mount Single input, A/B insolated input configurations available 400A input bus rating Uses AM series bullet terminal circuit breakers (Breaker choices available
from 5A to 100A) 16 circuit breaker position No GMT fuses (unlike standard HDX) Targeted at Cisco 7609 installations
19"/23" rack mount, 2RU high Single input A/B isolated input High power density and ampacity:
· 300A per input: (single input, A/B input) · 300A combined load: (A/B/C-source) · Accepts up to 12 plug-in bullet terminal circuit breakers · 8 GMT fuses Standard unit includes front panel with A and B input LED indicators and breaker/fuse trip indicator LED Form-C alarm contacts for Major and Minor alarms
28
DC Accessories
Batteries and Accessories
Alpha's Headend battery line includes three distinct types of models: 20-year batteries, 10-year telecom front and top terminal, and flame retardant UPS batteries. These batteries provide improved performance, longer runtimes and extended service life. The front terminal models allow for easier access to the batteries during installation and routine maintenance. Alpha's Headend batteries are ideal for broadband, cellular, electric utility, PCS, customer premise, long distance and distributed power.
> Telecommunications
In critical standby power applications, maximum battery life is essential. Alpha offers a wide range of large format 2V Cell batteries, front and top terminal batteries ideal for providing extended runtime for telecom and wireless applications. Alpha's Telecom batteries include features such as 10-20 year design life, small footprint, customizable configuration, strong corrosion-resistant grid design, and easy installation and maintenance.
> AlphaCellTM HPL-FT
Alpha expands its Alphacell battery family to include the HPL-FT Series of front terminal batteries for Broadband Cable and Telecommunications applications. The AlphaCell HPL-FT series are valve regulated lead acid batteries designed for long life. Benefits of these new batteries include central gassing system, snap-in front covers, integral flame arrestor, construction from recyclable materials and low self-discharge rates.
> PowerAgent
29
The PowerAgent BMS is a remote monitoring system that alerts managers to degradations in the
power-producing capacity of batteries indoor/outdoor uninterruptible power supply applications.
Based on an advanced patent pending technology called "admittance" testing, the BMS employs DSP
(Digital Signal Processing) and standards-based interface protocols to facilitate seamless integration of
battery monitoring into an enterprise-wide network management fabric.
Batteries
> AlphaGuardTM
AlphaGuard monitors and protects your batteries by spreading the charge voltage equally across all the batteries in the string, ensuring that every battery, whether old or new, is properly charged. With an ideal voltage across each battery, life and runtime are optimized. Individual batteries in a string can be replaced as they fail, allowing batteries to be left in service longer.
> Battery Testing Equipment
A fast, reliable and affordable testing process is now available with the development of conductance based battery measurement technology. By coupling conductance testing with a simple utility load test, the system operator is armed with the quality of data necessary to know the status of their installed standby batteries and budget their replacement with confidence.
Telecommunications
Large Format 2V Cell Batteries
> 20-year design life batteries with VRLA technology > Space saving design for the greatest amount of power in a small footprint > Customizable to your system's configuration needs
MsEndur
C&D MS Endur 345 to 2180Ah
Part Number
# Cells/ Module
# Plates/ Cell
Nom Ah Cap (8hr)
System # of Cells
System Voltage
Model Volts
Dimensions H x W x D (in/mm)
Weight (lb/kg)
Cell Layout W x H
RAA64024CE01: 3
7
345
24
48
6
21.4 x 44.7 x 23.1 / 544 x 1135 x 587
1970 / 849 6 x 4
RBB46024CE01: 3
9
480
24
48
6
18.7 x 64.5 x 23.1 / 475 x 1638 x 587
2470 / 1120 4 x 6
RBB64024CE01: 3
9
480
24
48
6
26.1 x 44.7 x 23.1 / 663 x 1135 x 587
2410 / 1093 6 x 4
RCC46024CE01: 3
11
599
24
48
6
21.4 x 64.5 x 23.1 / 544 x 1638 x 587
2920 / 1324 4 x 6
RDF38024CE01: 3
15
839
24
48
6
30.4 x 44.7 x 23.1 / 772 x 1135 x 587
2850 / 1293 3 x 8
RDF46024CE01: 3
15
839
24
48
6
21.4 x 84.4 x 23.1 / 544 x 2144 x 587
3860 / 1751 4 x 6
REH38024CE01: 3
19
1079
24
48
6
27.9 x 64.5 x 23.1 / 703 x 1638 x 587
3790 / 1719 3 x 8
REH46024CE01: 3
19
1079
24
48
6
26.1 x 84.4 x 23.1 / 663 x 2144 x 587
4740 / 2150 4 x 6
RFK38024CE01: 3
23
1319
24
48
6
33.5 x 64.5 x 23.1 / 851 x 1638 x 587
4670 / 2118 3 x 8
RFK46024CE01: 3
23
1319
24
48
6
30.4 x 84.5 x 23.1 / 772 x 2146 x 587
5620 / 2549 4 x 6
30
RHP38024CE01: 3
27
1559
24
48
6
39.5 x 64.5 x 23.1 / 1001 x 1638 x 587
5550 / 2517 3 x 8
RHP46024CE01: 3
27
1559
24
48
6
34.4 x 84.4 x 23.1 / 874 x 2144 x 587
6550 / 2971 4 x 6
RJS38024CE01: 3
35
2038
24
48
6
45.5 x 64.5 x 23.1 / 1156 x 1638 x 587
6540 / 2966 3 x 8
RJS46024CE01: 3
35
2038
24
48
6
43.6 x 84.4 x 23.1 / 1107 x 2144 x 587
8320 / 3774 4 x 6
Batteries
East Penn Unigy II 760 to 2000Ah
Part Number
# Cells/ # Plates/ Module Cell
24AVR95-17:
3
17
24AVR95-19:
3
19
24AVR95-21:
3
21
24AVR95-23:
3
23
24AVR95-25:
3
25
24AVR95-27:
3
27
24AVR95-29:
3
29
24AVR95-31:
3
31
24AVR95-33:
3
33
24AVR125-33: 2
33
Nom Ah Cap (8hr) 760 855 950 1045 1140 1235 1330 1425 1520 2000
System # of Cells 24 24 24 24 24 24 24 24 24 24
System Voltage 48 48 48 48 48 48 48 48 48 48
Model Volts 6 6 6 6 6 6 6 6 6 6
Dimensions H x W x D (in/mm)
21.9 x 68.3 x 27.1 / 556 x 1735 x 688 24.2 x 68.3 x 27.1 / 615 x 1735 x 688 26.4 x 68.3 x 27.1 / 671 x 1735 x 688 28.7 x 68.3 x 27.1 / 729 x 1735 x 688 30.1 x 68.3 x 27.1 / 765 x 1735 x 688 33.2 x 68.3 x 27.1 / 843 x 1735 x 688 35.4 x 38.3 x 27.1 / 899 x 1735 x 688 37.7 x 68.3 x 27.1 / 958 x 1735 x 688 39.9 x 68.3 x 27.1 / 1013 x 1735 x 688 53.2 x 71.4 x 28.6 / 1351 x 1814 x 726
Weight (lb/kg) 3260 / 1479 3612 / 1638 3956 / 1794 4308 / 1954 4652 / 2110 4972 / 2255 5348 / 2426 5668 / 2571 6020 / 2737 8616 / 3908
Cell Layout W x H 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 (2 x 6) x 2
GNB Absolyte GP
Part Number
# Cells/ Module
100G13:
100G15:
3
100G17:
3
100G19:
3
100G21:
3
100G23:
3
100G25:
3
100G27:
3
100G29:
3
100G31:
3
100G33:
3
# Plates/ Cell
15 17 19 21 23 25 27 29 31 33
Nom Ah Cap (8hr) 600 696 800 896 1000 1096 1200 1296 1400 1496 1600
System # of Cells 24 24 24 24 24 24 24 24 24 24 24
System Voltage 48 48 48 48 48 48 48 48 48 48 48
Model Volts 6 6 6 6 6 6 6 6 6 6 6
Dimensions H x W x D (in/mm)
22.2 x 68.7 x 26.4 / 564 x 1745 x 671 24.5 x 68.7 x 26.4 / 622 x 1745 x 671 26.8 x 68.7 x 26.4 / 681 x 1745 x 671 29 x 68.7 x 26.4 / 737 x 1745 x 671 31.3 x 68.7 x 26.4 / 795 x 1745 x 671 33.5 x 68.7 x 26.4 / 851 x 1745 x 671 35.8 x 68.7 x 26.4 / 909 x 1745 x 671 38 x 68.7 x 26.4 / 965 x 1745 x 671 40.3 x 68.7 x 26.4 / 1024 x 1745 x 671 42.5 x 68.7 x 26.4 / 1080 x 1745 x 671
Weight (lb/kg)
Cell Layout W x H
2992 / 1357 3391 / 1539 3760 / 1706 4120 / 1869 4488 / 2036 4864 / 2206 5224 / 2370 5632 / 2555 6000 / 2722 6360 / 2885
3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8 3 x 8
Telecommunications
Front Terminal Batteries
> 10-year design life batteries > Valve regulated lead-acid batteries > Front access terminal design > Strong corrosion resistant grid design > Multicell design for ease of installation and maintenance > Can be used in any position: Upright, side or
end mounting recommended
Front Terminal Batteries
C&D True Front Access Series
Part Number
Model Volts
TEL 12-160FW:
12
TEL 12-160F:
12
TEL 12-180F:
12
Capacity @ 8hr Rate @ 1.75V/C 159.7 157.3 181.2
Dimensions H x W x D (in/mm) 10.10 x 16.37 x 6.88 / 256.54 x 415.90 x 174.70 11.14 x 20.16 x 4.86 / 282.96 x 512.17 x 123.39 12.60 x 20.16 x 4.86 / 320.04 x 512.17 x 123.39
Weight (lb/kg) 121 / 54.9 115 / 52.2 131 / 59.4
Terminal Type Threaded insert Threaded insert Threaded insert
East Penn ET Series Part Number 12AVR100-3ET: 12AVR150-ET:
Model Volts 12 12
Capacity @ 8hr Rate @ 1.75V/C 96 150
Dimensions H x W x D (in/mm) 20.1 x 4.3 x 9.4 / 510.5 x 109.2 x 2238.7 22 x 4.9 x 11.75 / 558.8 x 124.5 x 298.5
Weight (lb/kg) 75 / 34 115 / 52
Terminal Type Threaded insert Threaded insert
GNB Marathon Front Terminal
Part Number
Model Volts Capacity @ 8hr Rate @ 1.75V/C Dimensions H x W x D (in/mm)
Weight (lb/kg)
Terminal Type
M12V90FT:
12
90
10.6 x 4.1 x 15.6 / 270 x 105 x 395
68 / 31
Threaded insert
M12V105FT:
12
104
9.4 x 4.3 x 20.1 / 238 x 110 x 511
79 / 35.8
Threaded insert
M12V125FT:
12
125
M12V155FT:
12
155
11.1 x 4.9 x 22 / 283 x 124 x 559 11.1 x 4.9 x 22 / 283 x 124 x 559
105 / 47.6
Threaded insert
31
119 / 53.8
Threaded insert
M12V180FT:
12
180
12.5 x 4.9 x 22 / 317.5 x 124.6 x 558.8
133 / 60.3
Threaded insert
AlphaCellTM SMU-F Part Number SMU12-155FR: SMU12-170FR:
Model Volts 12 12
Capacity @ 8hr Rate @ 1.75V/C 150 172
Dimensions H x W x D (in/mm) 21.9 x 4.9 x 11.1 / 558 x 125 x 283 21.9 x 4.9 x 12.2 / 558 x 124 x 310
Weight (lb/kg) TopAccessStudHoleSize
119 / 54
8mm
129.8 / 59
8mm
Front Access Stud Size 6mm 6mm
Batteries
Telecommunications and Business Services
> 10 to 12-year design life batteries > Top terminal access design > Valve regulated lead acid technology > Heavy duty copper alloy terminals for ease
of assembly and reduced maintenance
C&D Tel Series Part Number Tel12-30: Tel12-45: Tel12-70: Tel12-80: Tel12-90: Tel12-105: Tel12-125:
East Penn Unigy I Series Part Number 12AVR-30: 12AVR-40: 12AVR-75: 12AVR-100: 12AVR-130:
GNB Marathon Series Part Number M6V190: M12V30T: M12V40: M12V45F: M12V70: M12V90:
Model Volts 12 12 12 12 12 12 12
Model Volts 12 12 12 12 12
Model Volts 6 12 12 12 12 12
Capacity @ 8hr Rate @ 1.75V/C 30 46 69 79 88 102 127
Capacity @ 8hr Rate @ 1.75V/C 3.4 4.4 8.82 11.76 15.6
Capacity @ 8hr Rate @ 1.75V/C 190 28 40 46 72 90
Dimensions H x W x D (in/mm) 7.8 x 5.2 x 6.8 / 197.4 x 131.9 x 172.7 8.9 x 5.4 x 8.1 / 228.3 x 138.9 x 205.6 10.3 x 6.8 x 8 / 260.5 x 173.4 x 203.6 12 x 6.8 x 8.1 / 305.8 x 173.4 x 205.3 13.5 x 6.8 x 8.5 / 343.1 x 171.7 x 216.2 20.1 x 4.3 x 9.4 / 511 x 110 x 238 13.6 x 6.8 x 10.9 / 344.7 x 171.7 x 277.7
Dimensions H x W x D (in/mm) 6.97 x 5 x 6.55 / 177.04 x 127 x 166.37 6.97 x 5 x 8.16 / 177.04 x 127 x 207.26 8.24 x 6.56 x 10.20 / 209.3 x 166.6 x 259.1 8.70 x 6.75 x 12.93 / 221 x 171.5 x 328.4 11.21 x 12.75 x 6.77 / 285 x 342 x 172
Dimensions H x W x D (in/mm) 9.25 x 6.85 x 12.04 / 235 x 174 x 306 7.32 x 5.11 x 6.73 / 186 x 130 x 171 7.44 x 6.57 x 7.79 / 189 x 167 x 198 10 x 4.76 x 8.66 / 254 x 121 x 200 9.25 x 6.85 x 10.23 / 235 x 174 x 260 9.25 x 6.85 x 12.04 / 235 x 174 x 306
Weight (lb/kg) 27 / 12 40 / 18 55 / 25 68 / 31 72 / 33 80 / 36 100 / 45
Weight (lb/kg) 21 / 9.5 26 / 11.8 55 / 25 72 / 32.7 98 / 44.5
Weight (lb/kg) 74 / 33.6 24 / 10.9 39 / 17.7 39 / 17.7 61 / 27.7 72 / 32.7
Top Terminal Batteries
Terminal Type Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert
Terminal Type Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert
Terminal Type Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert
Business Services
AlphaCellTM HPL-FT Batteries
> Front terminal design with protective covers > Specifically designed for mission-critical applications > High cyclic life capability > Flame retardant case and cover (to UL94VO) > 3-step terminal seal design ensures leak-free operation > Integral handles (115HPL-FT, 220HPL-FT) for ease of handling > Ideally suited for use in Alpha NPS and FT enclosures > Approved as non-hazardous cargo for ground/sea/air transportation
AlphaCellTM HPL-FT Batteries
Models:
70HPL-FT
Standard Warranty1:
3 years
Service Life:
Long
VRLA Battery Type:
High performance lead alloy
Heat Resistant:
High
Hydrogen Emission:
Low
Terminals:
14mm insert M8 x 1.25 thread
Terminal Torque:
8Nm
Case Material:
VO
Typical Runtime (minutes)2: 70
32
Cells Per Unit:
6
Voltage Per Unit:
12.8
Conductance Value:
1050
Max. Discharge Current (A): 1000
Short Circuit Current (A):
1400
10 Second Volts @ 100A:
11.3
Ohms Impedance 1 kHz:
6.5mOhms
Capacity @ 20hrs (to 1.75VPC) @ 25°C / 77°F:
42Ah
115HPL-FT 3 years Long High performance lead alloy High Low 14mm insert M8 x 1.25 thread 8Nm VO 115 6 12.8 1200 1000 2000 11.5 4.1mOhms
62Ah
220HPL-FT 3 years Long High performance lead alloy High Low 14mm insert M8 x 1.25 thread 8Nm VO 220 6 12.8 1600 1000 3500 11.7 2.5mOhms
107Ah
Batteries
Dimensions H x W3 x D3 (in/mm):
8.2 x 3.8 x 9.8 / 209 x 97 x 249
Weight (lb/kg):
27.9 / 15.3
Operating Temperature Range
Discharge:
-40 to 60°C / -40 to 140°F
Charge (with temp compensation):
-40 to 60°C / -40 to 140°F
10.3 x 4.2 x 11.3 / 263 x 108 x 287 46.2 / 22.2
-40 to 60°C / -40 to 140°F -40 to 60°C / -40 to 140°F
11.3 x 4.2 x 15.6 / 287 x 108 x 396 78.5 / 36
-40 to 60°C / -40 to 140°F -40 to 60°C / -40 to 140°F
Float Charging Voltage @ 25°C / 77°F (Vdc):
AC Ripple Charger:
13.5 to 13.6
13.5 to 13.6
13.5 to 13.6
0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4%V pk to pk
Notes: 1 Warranty varies by country and region. Warranty valid only when used with Alpha approved Power Supplies, Chargers and Enclosures. Consult your sales person for details 2 Runtimes at 25A to 1.75VPC @ 25°C. No deep discharge cycling required to obtain maximum runtime ratings 3 Dimensions at battery base
Business Services
FTTx Batteries
> Specifically engineered for long-life float service, standby applications
> One-year typical and three-year warranty option for the 7.2Ah battery
> Qualified with Alpha's FlexPointTM and FlexNetTM battery backup power supplies
> UL recognized component per UL 1989 for standby batteries
17Ah, 12Ah and 7.2Ah FTTx Batteries
Models: Specifications Warranty: Service Life: Battery Type: Dimensions H x W x D (in/mm): Weight (lb/kg):
AX-STDBAT-7
1 year Standard 7.2Ah AGM 3.94 x 2.56 x 5.94 / 100 x 65 x 151 5.28 / 2.4
AX-LONGBAT-7
3 year Long 7.2Ah AGM 3.94 x 2.56 x 5.94 / 100 x 65 x 151 6.17 / 2.8
AX-STDBAT-12
1 year Standard 12Ah AGM 3.94 x 2.56 x 5.94 / 100 x 65 x 151 5.94 / 2.69
AX-STDBAT-17
1 year Standard 12Ah AGM 6.57 x 3 x 7.13 / 167 x 76.2 x 181 12.13 / 5.5
7.2Ah Battery @ 25°C / 77°F
Constant Wattage Performance for 7.2Ah Battery (final voltage 1.75Vpc)
33
Discharge Time:
90min 2hrs
3hrs
4hrs
5hrs
6hrs
7hrs
8hrs
9hrs
10hrs
12hrs
20hrs
Discharge Wattage:
35.3
28
20
16
13.2
11.5
10.1
9.1
8.1
7.4
6.3
4.1
12Ah Battery @ 25°C / 77°F
Constant Wattage Performance for 12Ah Battery (final voltage 1.75Vpc)
Discharge Time:
90min 2hrs
3hrs
4hrs
5hrs
6hrs
7hrs
8hrs
9hrs
10hrs
12hrs
20hrs
Discharge Wattage:
--
--
33.4
26.7
22
19.2
16.9
15.2
13.5
12.4
10.5
6.8
Batteries
Recharge
17Ah Battery @ 25°C / 77°F
Constant Wattage Performance for 17Ah Battery (final voltage 1.75Vpc)
Discharge Time:
90min 2hrs
3hrs
4hrs
5hrs
6hrs
7hrs
8hrs
9hrs
10hrs
12hrs
20hrs
Discharge Wattage:
--
--
--
--
30.9
26.4
22.9
20.4
18.4
16.8
14.2
9.8
Percent Rated Current/Power Available
110% 100%
90% 80% 70% 60% 50% 40% 30% 20% 10%
0% -46°C -50°F
VRLA Battery Efficiency vs. Temperature and Discharge Rate
20hr 8hr 5hr
-46°C -36°C -29°C -23°C -18°C -12°C -7°C
-1°C
4°C
10°C
15°C
21°C
27°C
-40°F -30°F -20°F -10°F
-0°F 10°F
20°F
30°F
40°F 50°F
60°F
70°F
80°F
Battery Storage Guidelines
Under 25°C / 77°F storage conditions, batteries self-discharge at a rate of approximately 5% per month. The self-discharge rate of VRLA batteries increases with temperature. Recommended recharge times are shown at 180 days (6 months) at 25°C / 77°F, or 75 days (2.5 months) at elevated temperatures of 35 to 40°C / 95 to 104°F.
100 80
60
50°C 40
20
32°C 38°C
90°F 100°F
0
2
40°C
Recharge
35°C
30°C
10°C 35°C
4
6
8
10
12
UPS
Uninterruptible Power Supply Batteries
> 10-year design life > High rate flame retardant AGM UPS batteries
for all standby applications > Absorbed valve-regulated, lead-acid battery technology
designed for UPS standby power systems > Alpha Technical Services offers removal,
replacement and recycling of UPS Batteries > Most UPS brands serviced
East Penn Unigy High Rate Series
Part Number
Model Volts
U1HR1500:
12
45HR2000:
12
24HR3000:
12
27HR3500:
12
31HR4000:
12
31HR5000:
12
Watts per Cell @ 15min Rate @ 1.67Vpc
119 168 253 314 377 475
Dimensions H x W x D (in/mm)
6.93 x 5.18 x 7.71 / 176 x 132 x 196 8.26 x 5.31 x 8.84 / 210 x 135 x 225 8.24 x 6.80 x 10.20 / 209 x 173 x 259 8.24 x 6.80 x 12.01 / 209 x 173 x 305 8.70 x 6.75 x 12.93 / 221 x 171 x 328 11.20 x 6.77 x 13.46 / 284 x 172 x 342
34
CED AGM UPS - Flame Retardant High Rate Series
Part Number
Model Volts
Watts per Cell @ 15min Rate @ 1.67Vpc
Dimensions H x W x D (in/mm)
UPS12-100MR:
12
91
6.5 x 5.2 x 6.9 / 166.2 x 131.3 x 174.3
UPS11-150MR:
12
148
7.8 x 5.2 x 6.8 / 197.1 x 131.9 x 172.7
UPS12-210MR:
12
206
9 x 5.5 x 8.1 / 228.6 x 139.2 x 205.1
UPS12-300MR:
12
300
10.3 x 6.8 x 8 / 260.9 x 173.4 x 203.5
Batteries
UPS12-350MR:
12
350
12 x 6.8 x 8.1 / 305.8 x 173.4 x 204.8
UPS12-400MR:
12
400
13.4 x 6.8 x 8.5 / 340.9 x 172.7 x 216.4
UPS12-490MR:
12
488
13.6 x 6.8 x 10.9 / 344.7 x 172.7 x 277.7
UPS12-540MR:
12
537
12.6 x 6.9 x 8.9 / 320.8 x 177 x 227.2
UPS6-620MR:
6
620
12.6 x 6.9 x 9.9 / 321 x 177 x 253
GNB Sprinter UPS
Part Number
S6V740: S12V120: S12V170: S12V285: S12V300: S12V370: S12V500:
Model Volts
6 12 12 12 12 12 12
Watts per Cell @ 15min Rate @ 1.67Vpc
746 117 167 285 306 373 505
Dimensions H x W x D (in/mm)
9.25 x 6.85 x 12.04 / 235 x 174 x 306 6.53 x 6.57 x 6.81 / 166 x 167 x 173 7.44 x 6.57 x 7.79 / 189 x 167 x 198 9.25 x 6.85 x 10.23 / 235 x 174 x 260 9.25 x 6.85 x 9.25 / 235 x 174 x 306 9.25 x 6.85 x 12.04 / 235 x 174 x 306 11.33 x 6.77 x 13.54 / 288 x 172 x 344
UPS batteries
Weight (lb/kg)
27 / 12 40 / 18.1 56 / 25.4 66 / 30 74 / 33.6 98 / 44.5
Terminal Type
Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert
Weight (lb/kg) 21 / 10 27 / 12 40 / 18 57 / 26 67 / 30 74 / 34 10 / 45 100 / 45 72 / 33
Terminal Type Flag terminal Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert
Weight (lb/kg)
74 / 33.6 27 / 12.2 36 / 16.3 61 / 27.7 63 / 28.6 74 / 33.6 107 / 48.5
Terminal Type
Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert Threaded insert
Battery Monitoring
PowerAgent
> Ethernet, TCP/IP or SNMP > Flexible, scalable, easily installed > Programmable alarm thresholds for each battery > Built-in email notification > Sensors powered from monitored battery
Specifications
Site Controller
Number of Monitored Strings: Number of Batteries: Network Interface: Network Protocols: Local Diagnostic Interface:
Power:
Dimensions H x W x D (in/mm): Mounting:
6 max 240 max Ethernet 10/100 BaseT TCP/IP, UDP, HTTP, SNMP, Telnet, DHCP, SMTP Proprietary 9600 baud, RJ-45, ASCII 15 to 60Vdc, 2W nom, (110/220Vac power pack available) 6 x 9 x 1.6 / 152.4 x 228.6 x 40.64 Rack or wall
PowerAgent Site Controller and Sensor Module
Sensor Modules (Model PAS-PA-BSx-y-z)
Measurements:
String volts, battery volts, temperature, dynamic resistance/admittance
Controller Interface:
2 ea, RJ-45
Mounting:
Mounts on battery negative terminal; wire/lug connection to positive terminal
Indicators:
Red/green LED
Power:
Powered from monitored battery; 10ma avg standby current
Isolation:
Optically isolated from controller
Dimensions H x W x D (in/mm): 1.5 x 3 x 0.75 / 38.1 x 76.2 x 19.05
35
Batteries
Network Monitoring
ContactAgent
> Remote site monitoring and control for generators > Provides network access for non-network
equipment via web and SNMP > Email Alarm Capability > Contact closure or analog inputs and latched
relay contact outputs > Optional temperature and humidity measurements
ContactAgent
Specifications
Master Unit
Number of Inputs:
8 Digital (contact closure)
Electrical Input:
1ma max closed-switch current
Number of Outputs:
2 Form-C contact sets; state not preserved on power failure
Electrical Output:
60V max; 5A
Slave Unit Interface:
RS-485/RJ-45 connector
Operating Power
5Vdc from supplied wall-mount power supply
Network Interface:
10/100 Ethernet
Protocols:
TCP/IP, SMTP, HTTP, SMTP, DHCP, TFTP
Dimensions H x W x D (in/mm): 1.5 x 8 x 4.3 / 38.1 x 203.2 x 109.2 ( rack mountable)
* SNMP MIB documentation available upon request
RIM Module Number of Inputs: Analog Measurements: Temperature Sensor:
Humidity Sensor:
Max Number of Units: AC Line Measurement: ROM Module Number of Outputs: Electrical Output: Temperature Sensor:
Humidity Sensor:
Max Number of Units:
6 Digital/analog (user/definable) ±12Vdc, 0 to 8Vrms Standard, ±2°C/35.6°F from -40 to 80°C / -40 to 176°F Optional ±3% accuracy from 20 to 80% RH, ±5% accuracy from 0 to 19% RH and 81 to 100% RH 4 RIM modules per Master Unit Optional 90 to 140Vac, RMS, sine, 50/60Hz
4 Form-C contacts, state-preserved on power failure 60V max, 2A Standard, ±2°C/35.6°F from -40 to 80°C / -40 to 176°F Optional ±3% accuracy from 20 to 80% RH, ±5% accuracy from 0 to 19% RH and 81 to 100% RH RS-485 on RJ-45 connector, power supplied via daisy chain
AlphaGuardTM
Battery Charge Management System
> Maximizes battery life > Spreads charge voltage equally across batteries > Compensates for battery differences as they age > Replace single batteries, not the entire string > Single battery connections for charge
management and status monitoring > Safe unattended operation designed to CSA
C22.2 No. 107.1 and UL 1778 Standards > Optional Potted AlphaGuard for underground
battery vault applications
AlphaGuard CMT-3
AlphaGuard
Models:
AG-CMT-3:
AlphaGuard Charge Management SC, 36V --including 36Vdc battery string interface cable
AG-CMT-4:
AlphaGuard Charge Management SC, 48V --including 48Vdc battery string interface cable
Configuration
36
Quantity:
Service Location:
One (1) AlphaGuard is required per battery string With the battery string
Mechanical
Housing Material:
High impact plastic
Dimensions H x W x D (in/mm): 1.4 x 4.8 x 4.3 / 36 x 122 x 108
Weight (lb/kg):
0.8 / .36
Batteries
Electrical
Batteries:
Individual 12Vdc nominal batteries configured into 36 or 48Vdc strings
Circuit Protection:
Fast blow fuse, reverse polarity protected
Quiescent Current Draw:
1mA max. (Current consumed by AlphaGuard after low voltage total shutdown)
Charge Management:
Most effective during float period of charge
Max. Current:
2A @ 25°C / 77°F
Quality of Final Balance:
±100mV max. between any two (2) batteries
Charging Efficiency:
80 to 90%
Charge Balance:
±100mV typical
Low Voltage Cutoff:
34.5Vdc/46Vdc ±5%
Communication to XM2:
AG-DSM cable supplies battery readings to a DSM status monitoring card
Voltage Sense Regulation: ±100mV
Environment
Operating Temperature:
-40 to 55°C / -40 to 131°F
Humidity
5 to 95% non-condensing
Warranty
Warranty:
5 years
The AlphaGuard employs a patented Charge Management Technology (CMT) to shuttle excess charge current to batteries requiring a greater charge, and is contained in a small plastic enclosure that installs directly on top of one of the batteries in the string or in the optional battery integration tray. A short service cable connects the AlphaGuard to each of the batteries in the string. Both 36Vdc (3 battery) and 48Vdc (4 battery) versions are available. One AlphaGuard is required per string. An AlphaGuard configured with the optional voltage sense cabling and interface module (DSM, ESM, EDSM or External DOCSIS®) allows the AlphaGuard to interface with a statusmonitoring module. Two AlphaGuard modules can be connected to single interface module. Refer to individual interface module documentation for additional information.
Potted AlphaGuard CMT-3
AG-DSM-S9-Cable
AG-DSM-D9-Cable
AG-DSM-D35-Cable
AG-DSM-S35-Cable
Battery Cable 36V 6ft
Battery Cable 48V 6ft
Battery Testing Equipment
AlphaCellTM Battery Testing Equipment
> Complete battery life trending through conductance tests
> Non-intrusive conductance measurements do not reduce string life
> Quick, accurate measurements and data recording reduce on-site time
> Simple pinpoint testing requires only access to two battery posts or straps
> Enables early detection of questionable batteries in the network
Celltron Ultra CTU-6000
Battery Testing Equipment
Kit Contents
Model:
Celltron Ultra
Celltron AdvancedTM
Celltron Ultra Kit CTA-6000AT
Celltron Advanced Kit CTA-4000AT
Model Number: Applications: Voltage:
CTU-6000 (w/ temp. sensor)
CTA-4000 (kit) CTA-2000 (analyzer only)
Tests individual lead acid cells or monoblocs (up to 16V) in any common configuration, approximately 10-6000Ah
Tests individual lead acid cells or monoblocs (up to 16V) in any common configurations
1.5 to 20Vdc
1 to 20Vdc
Contains: Digital multimeter Infrared strip printer Lighted probes Clamps and probes
Contains:
Protective boot
Rechargeable battery pack
Infrared PC data receiver and software
Infrared printer
Infrared temperature sensor
Protective carrying case
37
Both clamp and probe cables
Spare fuses, printer paper, probe tips
Conductance:
100 to 19990 Siemens 100 to 9999 Siemens
Test Data Storage:
500 string locations of 480 test results stored internally
16 string locations of 480 test results stored internally
Batteries
Accuracy:
+2% across test range +2% across test range
Voltmeter Resolution: 5mVdc
5mVdc
Environmental:
0 to 40°C / 32 to 104°F, 95% non-condensing
Conductance Technology/Industry Approvals and Recommendations:
IEEE Standards 1188 and 484 EPRI Guide for testing stationary batteries International Telecommunications Energy Conference Bellcore T1Y1 Presentation for American National Standards Institute International Lead Zinc Research Organization Battery Council International
Applications
Cable TV/Broadband Power Networks · Outside Plant Batteries · Headend DC/AC Batteries · Premise Backup Supplies (FTTx) 6/12V, 5 to 600Ah Stationary Batteries Security system batteries Emergency lighting batteries
Optional Equipment:
Handheld Printer Infrared Module for PC
Features and Benefits
Simple - One-step testing, no instrument inputs or adjustments required. Quick - Battery voltage and conductance displayed in less than 10 seconds.
Test an entire 48V string in less than 1 minute. Safe - Utilizes patented conductance technology, a passive method that
minimizes technician risk. Accurate - Field test proven to ±2% accuracy across test range. Conductance
method recognized by IEEE standard for the testing of lead-acid batteries with proven correlation to battery capacity. Economical - Efficient and accurate battery tester priced to fit into every technician's tool kit.
DC to AC Inverters
Alpha Technologies offers a full line of modular inverter systems providing a new level of scalability, maintainability, compactness, reliability and performance. Alpha's scalable DC to AC inverter is recognized as the industry standard for critical AC power by many of the world's leading communications companies.
> AMPS80HP
Alpha's new high performance AC or hybrid AC/DC system offers telecom grade reliability, 94% efficiency and high power density. The AMPS80 features hot swappable 2.5kVA/ 2.0kW inverter modules and optional 1.8kW rectifier. The AMPS80 meets your current and future power needs by allowing you to purchase only the power modules you need for current needs while having ultimate flexibility to scale up or down, depending on future power needs. Front access and user-friendly connections make the system easy to install, service and upgrade.
> AMPS24HP
The AMPS24 features hot swappable 1.5kVA/1.2kW inverter modules and 1.8kW rectifier modules that are the building blocks of a highly reliable power system utilizing 48Vdc batteries. The AMPS24 meets your current and future needs by allowing them to purchase only the power modules for current needs while having ultimate flexibility to scaleup or down, depending on future power needs.
> Arcon Inverter Series
The Arcon Inverter System provides pure sine wave output ideal for telecom applications. Its high
frequency conversion and topology allow for high efficiency in a compact and user-friendly design.
With hot swappable modules and a patented technology, the Arcon Inverter System is very flexible and
39
customizable.
> TEBEVERT Inverter Series
DC to AC Inverters
The TEBEVERT DSP inverter system featuring Digital Signal Processing technology can be used in a wide array of telecom and industrial applications. The introduction of enhanced DSP controls and higher semi-conductor switching frequencies improves power density and operating efficiency while dramatically reducing physical size and weight.
> Invertronic Inverter System
The Invertronic Inverter System is a modular three phase inverter system with a high power density ideal for telecom and headend applications. The efficient load balancing between phases allows for minimal costs associated with distribution transformers, protective devices and cabling. The system's unique topology consisting of each inverter module having its own Static Bypass Switch, secures data bus communications.
> Media Inverter System
The Media Inverter System is a parallelable, rack-mounted twin sine inverter (TSI) system providing a pure AC sine wave output at 120 to 240Vac, 60 or 50Hz, with a THD <3% for any kind of load. Utilizing 48Vdc input, this high density system ranges from 1500 to 6000VA and is mountable on either a 19" open relay rack or conventional box bays. Unlike traditional inverters, the TSI increases your network's overall efficiency without compromise to the quality and stability of the output wave form.
> DSP Inverter Series
The DSP inverter system is designed to address the critical AC powering requirements of telecom applications, Voice over Internet Protocol (VoIP) and mission critical servers. The system can be scaled in 1kVA or 2.5kVA increments up to 27.5kVA in an N+1 redundant configuration. These units have been NEBS Level 3 Certified by a nationally recognized testing lab.
> MS Power Inverter Series
MS Inverters feature an integrated utility bypass and can be cascaded for redundancy. Designed for long mean time between failure, these inverters provide the dependable AC power your networks demand. These intelligent, dependable inverters provide economical AC power for all of your network needs.
AMPS80HP
Modular AC UPS System
> High performance AC or hybrid AC/DC backup power system offering 99.999% availability
> 94% Efficiency, 15 year Design Life and MTBF (Mean Time Between Failures) greater than 200,000 hours
> Intelligent system controller with integrated SNMP for local and remote management of AC and DC power modules, batteries, and other peripherals
> Hot swappable 2.5kVA/2.0kW inverter modules and optional 1.8kW rectifier modules
> Small footprint system offers up to 75kVA/60kW in a single 19" box bay rack
AMPS80
AMPS80HP
Specifications
Max. DC Input Current
Model Input and Output Phase:
AMPS80- AMPS80- AMPS80- AMPS80-
3-75
3-30
2-40
1-20
120/208V 3-ph
120/240 or 120 single 120/208V2-ph ph
@ 48Vdc:
1375A
550A
734A
@ 40Vdc:
1700A
680A
900A
Voltage Ripple:
<2mV / <38dbrnc
Unified System Controller with Integrated SNMP
366A 450A
40
Output Capacity:
7500 to 7500 to 5000 to 2500 to 75000VA 30000VA 40000VA 20000VA
Control and Monitoring:
Configure, control and monitor inverter and rectifier modules via Internet Explorer 7 onwards
DC to AC Inverters
Output Power (Resistive Load):
6000 to 6000 to 4000 to 2000 to 60000W 24000W 32000W 16000W
Maximum Output Current:
208Arms per phase
83Arms per phase
168Arms per phase
168Arms
Max./Min. No. of 2500VA/2000W Inverter Modules:
Technology:
Static Switch:
30/3
12/3
16/2
8/1
Twin Sine Inverter (TSI) technology; each inverter module has DC input and AC input
Not required; each module has its own static switch
Efficiency:
94% AC to AC; 90% DC to AC (from 50 to 100% full resistive load)
Waveform:
Pure sine wave
Output Power Factor:
0.8 (can run capacitive and inductive loads)
Transfer Time:
Zero transfer time
Warranty:
2 year standard (1 and 3 year optional extensions)
Inverter Module AC Output
Power Rating:
2500VA/2000W
Voltage Range (AC):
90 to 140V 90 to 140V 90 to 140V 90 to 140V
Voltage Accuracy:
±2%
±2%
±2%
±2%
Frequency:
60Hz (same as input frequency)
Inverter Frequency Accuracy: 0.03%
0.03%
0.03%
0.03%
Input Power Factor:
>99%
>99%
>99%
>99%
THD (Resistive Load):
<1.5%
<1.5%
<1.5%
<1.5%
Transient Load Recovery Time: 0.4ms
0.4ms
0.4ms
0.4ms
Soft Start Time:
20s
20s
20s
20s
Max. Crest Factor @ No. Power: 3.5
3.5
3.5
3.5
Short Circuit Overload Capacity: Short Term Overload Capacity:
10 x ln for 20msec (AC to AC mode) 150% for 5 seconds
Permanent Overload Capacity: 110%
110%
110%
110%
Synchronization Range:
57 to 63Hz 57 to 63Hz 57 to 63Hz 57 to 63Hz
Display:
Communication Ports: Mechanical Dimensions H x W x D (in/mm): System Weight Without Modules (lb/kg): Module Dimensions H x W x D (in/mm): Module Weight (lb/kg): Clearance (in/mm)
Front: Rear: Sides: Top: Environment Operating Temperature: Storage Temperature: Humidity: Elevation: Standards
Safety:
EMC:
Features:
LCD Touch-screen Display (160 x 160 pixels), OK/Major/Minor 3-Color LED display, Web based GUI via Ethernet RJ45 Ethernet Port, R232 Port (Front)
84 x 23.6 x 26.8 / 213 x 600 x 680
595 / 270
3.5 x 4 x 17.1 / 88.9 x 102 x 435
11 / 5
33 / 838.2 12 / 304.8 No clearance required 12 / 304.8
-20 to 40°C / -4 to 104°F (full load) -40 to 70°C / -40 to 158°F Up to 95% non-condensing Up to 2000m / 6562ft above sea level
UL1778 (2nd Ed); CSA C22.2 No. 107.3-05 UPS General Safety FCC CFR47 Part 15 Class A; ICES-003 Unified system controller with integrated SNMP communications, Top AC and DC feed access; bottom DC feed access (All user connections are front access), AC input and output breaker/ disconnect switch, Industrial grade surge suppression (rated to 40kA)
Inverter Module DC Output
Nominal Voltage:
48Vdc
Voltage Range (max.):
48Vdc
48Vdc
48Vdc
40 to 60Vdc (User Adjustable)
Options:
Up to 8 x 1.8kW rectifier modules, Integrated maintenance bypass switch, Inverter DC input breakers, Service-entrance grade surge suppression: 140kA rating (per phase), Lockable rack front-door, Batteries (various sizes and technologies)
AMPS24HP
Modular AC and Hybrid Power System
> High performance AC and hybrid AC/DC backup power system offering
99.999% reliability for mission critical indoor applications
> 93% Efficiency, 15 year Design Life and MTBF (Mean Time
Between Failures) greater than 200,000 hours results in
class leading TCO (Total Cost of Ownership)
> Intelligent system controller with integrated SNMP for local
and remote management
> Hot swappable 1.5kVA/1.2kW inverter modules and 1.8kW
rectifier modules (optional for inverter only systems) offer complete
flexibility, scalability and low MTTR (Mean Time To Repair)
AMPS24
> Up to 24kVA/19.2kW small footprint system maybe installed in a 19" or 23"
open-relay rack or box bay rack/cabinet with flexible mounting options
AMPS24HP Hybrid Systems
Specifications*
Models:
AMPS24-3-13.5-H3
AMPS24-2-18-H4
AMPS24-2-9-H2
AMPS24-1-9-H2
AMPS24-1-4.5-H1
Input and Output Phase:
120/208V 3-ph
120/240 or 120/208V 2-ph
120V single ph
Nominal Output Power (max): 4500 to 13500VA
3000 to 18000VA
3000 to 9000VA
1500 to 9000VA
1500 to 4500VA
Output Power (Resistive Load): 3600 to 10800W
2400 to 14400W
2400 to 7200W
1200 to 7200W
1200 to 3600W
Max. Output Current:
37.5Arms per phase
75Arms per phase
37.5Arms per phase
75Arms per phase
37.5Arms per phase
41
Max. No. of 1500VA/1200W Inverter Modules Per System:
9
12
6
6
3
Min. No. of 1500VA/1200W Inverter Modules Per System:
3
2
2
1
1
Max. No. of 1800W Rectifier Modules Per System:
3
4
2
2
1
DC to AC Inverters
AMPS24HP Inverter Systems
Specifications*
Models:
AMPS24-3-18-3i
Input and Output Phase: Nominal Output Power (max): Output Power (Resistive Load): Max. Output Current: Max. No. of 1500VA/1200W Inverter Modules Per System: Min. No. of 1500VA/1200W Inverter Modules Per System: Technology: Static Switch: Efficiency: Waveform: Output Power Factor: Transfer Time: Warranty:
120/208V 3-ph 4500 to 18000VA 3600 to 14400W 50Arms per phase 12
3
Inverter Module AC Output
Power Rating:
Nominal Voltage:
Voltage Accuracy:
Frequency:
Inverter Frequency Accuracy:
THS (Resistive Load):
Transient Load Recovery Time:
Soft Start Time: Max. Crest Factor at Nominal Power: Short Circuit Overload Capacity: * Specifications subject to change.
AMPS24-2-24-4i
AMPS24-2-12-2i
120/240 or 120/208V 2-ph
3000 to 24000VA
3000 to 12000VA
2400 to 19200W
2400 to 9600W
100Arms per phase
50Arms per phase
16
8
AMPS24-1-12-2i
AMPS24-1-6-1i
120V single ph
1500 to 12000VA
1500 to 6000VA
3600 to 9600W
2400 to 4800W
100Arms per phase
50Arms per phase
8
4
2
2
1
1
Twin Sine Inverter (TSI) technology; each inverter module has DC and AC input Not required; each module has its own static switch
93% AC-to-AC; 90% DC-to-AC (from 50 to 100% full resistive load) Pure sine wave
0.8 (Can run capacitive and inductive loads) Zero transfer time
2 Years (1 and 3 year optional extensions)
1500VA/2000W 120Vac ±2
60Hz (same as input frequency) 0.03% <1.5% 0.4ms 20s 3.5
10 x In for 20msec (AC to AC mode)
Arcon Inverter Series
> High efficiency > Full Digital Signal Processing control > Outstanding response time > Input / Output Radio Frequency Interference compliant to FCC > Complete supervision possibility > Parallel operation in True Redundant System > Large DC input voltage range > Patented technology
Arcon Inverter
Acron Inverter Series
Specifications
Environment
Input
Storage Temperature:
-40 to 80°C / -40 to 176°F
Operating Voltage Range: Max. Input Current: Output
40 to 80Vdc 89%
Permissible Ambient Temperature:
Standards
-20 to 50°C / -4 to 122°F
42
Nominal Output Voltage:
120V, adjustable 108-125Vac
Output Voltage Tolerance: +3% of adjustable nominal voltage
Output Voltage Frequency: 50 or 60Hz, selectable
Total Harmonic Distortion: Less than 3% (on linear load at nominal power)
Total Transient Recovery Time: Less than 0.3 msec (typical)
Turn-on Delay:
Less than 3 sec
Nominal Value of Output Current: 29.1A
Crest Factor at Nominal Power: 2
Output Power
Safety: Protections:
Dielectric Strength:
Cooling: Mechanical Dimensions H x W x D (mm): Weight (lb/kg):
EN60950 / UL1950 Internal electronic + Relays + Fuses 4300Vdc input/output, 4300Vdc output/earth, 2000Vdc input/earth Forced
2RU x 436 x 440 33.1 / 15 (approximately)
DC to AC Inverters
Nominal Value: Overload: Permanent Overload:
3000W/3500VA 6000VA (±15%, 5 sec. max, self-protected) 110%
Power Factor Influence:
Full power output (3500VA) with Pf from 0 to 0.86 Limited to 3000W with Pf from 0.86 to 1
Electro-Magnetic Compatibility
Standards Applied For Immunity:
EN 61000-4-2 / 4-3 / 4-4 / 4-5 / 4-6
Standards Applied For Emission:
ETS300-132-2 CISPR 22 Class B
Efficiency:
More than 89% (Nominal power in Watts)
TEBEVERT Inverter Series
5 to 25kVA Inverter System
> NEBs level 3 certified to assure compatibility with the telecommunications environment
> Hot swappable 5kVA inverter modules > Hot swappable static switch module > Integrated maintenance bypass switch > Automatic master-slave operation > Up to five inverter modules can be paralleled
as load increases
TEBEVERT DSP
TEBERVERT Inverter Series
60Hz Models
60Hz Models
Output Capacity:
5 to 25kVA
120, 208, 220, 240, 480Vac
Max. Number of Modules: 5
Output Capacity:
5 to 25kVA
Input
Cooling:
Temperature controlled fans
Nominal Bypass AC Input:
Number of Bypass AC Phases:
Bypass AC Input Wiring:
120Vac 1 L, N, PE
208, 220, 240, 480Vac 2
Maintenance Bypass Switch:
Standard make-before-break mechanically interlocked switch provided on all models equipped with the static bypass module
43
L1, L2, PE
Remote Alarming:
(1) Form-C Summary Alarm, Optional Relay Card (8 Alarms), Optional SNMP
Nominal DC Input:
DC Input Range: Reflected DC Ripple (48Vdc) (120Vdc): Output
-48Vdc or 120Vdc (requires different inverter modules)
-15%
+20%
<2mV reverse
<2mV reverse
smoothing, <5% RMS smoothing, <5% RMS
LED Indicators (Inverter Modules):
LED Indicators (Static Bypass Module):
Metering:
Output present, fault, overload, AC synchronized, parallel operation
Power flow diagram, normal, fault, AC present, DC present, overload, load on bypass, load on inverter
(4) segment LCD display switchable between output voltage and current
Nominal AC Output Voltage: 120Vac Optional AC Output Voltage: 120/240Vac
120Vac 120/240Vac
Cabinet Dimensions H x W x D (in/mm):
84 x 23.6 x 23.6 / 2134 x 600 x 600
DC to AC Inverters
Output Voltage Regulation:
Output Power Factor: Output Voltage Waveform: Output Crest Factor: Output Voltage Distortion: Output Overcurrent Protection: Overload Rating (Inverters): Overload Rating (Static Bypass):
±5% for all combinations of line, load and temperature
0.7 lagging to 0.8 leading
PWM Sine wave
PWM Sine wave
2.8:1
2.8:1
<3% @ 100% rated linear load
Electronic current limiting
200% for approx. 75 cycles (1.25 seconds)
500% for 100ms
500% for 100ms
System Operating Efficiency:
>85% on-line mode >97% off-line mode
Frequency Stability: Module Capacity: Static Switch Transfer Time:
±0.1% free running, ±3% when AC present
5kVA/4kW
5kVA/4kW
<2ms
<2ms
Standards
Radio Interference: Safety Listing: Product Certification:
Environment
Seismic Rating: Elevation: Operating Temperature: Operating Humidity: Module Data Power Rating: Nominal Input Current (-48Vdc): Max. Input Current (-48Vdc): Output Current (120Vac):
Certified to Telecordia GR-1089 UL60950, UL, cUL Pending NEBS Level 3
NEBS Level 3, Seismic Zone 4 Optional 1800m / 6000ft, 4000m / 1300ft at 30°C/86°F -5 to 50°C / 23 to 122°F 0 to 95% non-condensing 5kVA 5000VA / 4000W 98A 115.4A 41.6A
Invertronic Inverter System
Modular 3 Phase Inverter System
> Hot swappable 10kVA modules each with built-in SBS for scalability
> Employs 4th Generation DSP Technology for dynamic step load response
> Integrated Manual Bypass Switch in primary cabinet 1 > Front door mounted Graphical Display of
Operating Mode and System Parameters > Remote Monitoring via Network (HTML, SNMP)
Invertronic Inverter System
Invertronic Inverter System
Electrical
System
Input
Static Bypass Switch (SBS): 3 Phase SCR bridge built into each module
Input Voltage:
Nominal: 48Vdc, Operating range 42 to 60Vdc
Input Current:
Max. 228A at 42Vdc at full load, Nominal: 138A at 54Vdc at 80% load
44
Inrush Current:
Soft-start circuit limits inrush to <25% of full load current
Output Inverter Module Rating:
10kVA/8kW at 0.8 power factor inductive
SBS Priority: Transfer Time: SBS Overload Capability: SBS Transfer Criteria:
Remote Alarming:
Inverter Priority Only; Offline mode not possible
SBS is make-before-break; 2ms typical, 6mm max.
120% for 10min; 1000% for 8ms
Overload, modules over temperature, short circuit on output, low DC voltage, manual initiation, output AC volts out of range
Mains Failure, Battery Failure, Loss of Redundancy, Common Failure Output
DC to AC Inverters
Max. System Capacity: Max. Modules Per Cabinet: Max. Cabinets: AC Output Voltage: AC Output Amps:
120kVA/96kW at 0.8 power factor inductive 6 2 120/208Vac 3 phase, 4 wire, Y connected 27.8A per phase at full load
Metering: Indicators: Mechanical
Module Dimensions H x W x D (in/mm):
Phase voltages, currents, kW, kVA 13 Programmable LEDs on front door display panel
8.75 x 19.9 x 17.7 / 222 x 505 x 450
AC Output Frequency:
60Hz ±.01% on internal crystal; tolerance is programmable when synced to mains
Max. Allowable Phase Imbalance:
100%, up to full load per phase current rating
Load Power Factor Range:
0.7 lagging (inductive) to 0.8 leading (capacitive) with standard UPS de-rating
Output Regulation:
Static: ±1%; Dynamic: ±5% max with 100% step load change, settling time: <10msec
Efficiency: Crest Factor Accommodated: Distortion: Overload Capability:
>86% 3.0 / 1 <2% THD into a linear load; pure sine wave output 120% for 10min; 200% for 200min
Module Weight (lb/kg):
99 / 45
Cabinet Dimensions H x W x D (in/mm):
84 x 24 x 31.5 / 2134 x 600 x 800
Cabinet Weight (lb/kg): Heat Output: Operating Temperature Range: Operating Humidity Range: Elevation:
528 / 240 <30000BTUs/hour/fully loaded cabinet at full power 0 to 40°C / 32 to 104°F 0 to 95% non-condensing Fully rated to 1000m / 3280ft
Standards
Safety:
EN 60950, UL 1778, UL 1950
Design:
NEBS Level 3 compliant (certification in progress), Zone 4 cabinets
Emissions: Immunity:
EN 62040-2 classification C3, FCC Class A EN 61000-4-4, EN 61000-4-5
Electrostatic Discharge Immunity:
EN 61000-4-2, (level: 4kV contact, 8kV air discharge)
Media Inverter System
TSI Media 48/120 Inverter Platform
> Scalable up to 3kVA > Enhanced Power Conversion Feature > Supports redundancy > Hot swappable > Input DC Breakers > Output AC Breakers > Optional NEMA Outlets
Media Inverter System
Media Inverter System
Electrical
Mechanical
AC Output Power Nominal Output Power**:
n x 1500VA
Dimension H x W x D (in/mm):
3.5 x 19 or 23 x 12.5 / 88.9 x 482.6 or 584.2 x 317.5
Output Power**:
n x 1200W (resistive load)
Weight (lb/kg):
14.4 + n x 5.3 / 7.9 + n x 2.4
Short Time Overload Capacity: 150% 15Sec
Material (Casing):
Coated steel
Permanent Overload Capacity: 110% @ 40°C / 104°F
General
45
Load Power Factor:
Full power rating from 0 inductive to 0 capacitive, internal temperature management and cut off
EMC (Immunity):
IEC 1000-4
AC Input
EMC (Emission):
FCC Part 15
Nominal Voltage (DC):
48Vdc
Safety:
UL 1778 (Ed.4) Listed
Voltage Range (DC):
40 to 58Vdc
Cooling:
Forced
Nominal Current (@ 40Vdc)**: n x 34A
MTBF:
>200,000hrs
DC to AC Inverters
Max. Input Current**:
n x 42A for 5sec
Efficiency (Max) Online:
90%
Voltage Ripple:
<1mV resistive load @ 54Vdc input voltage boundaries user selectable
Enhanced Power Conversion (EPC):
93%
DC Input
Nominal Voltage:
120 or 240Vac (Single or dual phase)
Voltage Range:
83 to 140Vac (each phase)
Conformity Range:
Adjustable
Power Factor:
>99%
Frequency Range:
50 to 60Hz (selectable)
Synchronization Range:
47 to 53Hz / 57 to 63Hz
Transfer Performance
Total Transient Voltage Duration: 0s (transient free)
AC Output
Nominal Voltage:
120 or 240Vac (Single or dual phase)
Adjustable Voltage Range: 90 to 130Vac
Voltage Accuracy:
2%
Frequency:
50 to 60Hz
Frequency Accuracy:
0.03%
Total Harmonic Distortion: <3% (resistive load)
Load Impact Recovery Time: 0.4ms
Turn On Delay:
30s
Nominal Current**:
n x 12.5A (protected against reverse current)
Crest Factor @ Nominal Power: 2.2 with short circuit management and protection
Dielectric Strength DC/AC (@ 0.6mA):
4,300Vdc
RoHS-6:
Compliant
Connection I/O:
Terminal block or NEMA receptacle or Twist Locks or combo AC output receptacles
Protected against reversed polarity Self adaptive to wide operating conditions
Environment Elevation:
<1500m / 4921ft
Ambient Temperature**:
n x 1500VA, -20 to 40°C / -4 to 104°F, Pmax @ 100% Load, de-rating up to 65°C / 149°F
Storage Temperature:
-40 to 70°C / -40 to 158°F
Humidity:
95% non-condensing
Signaling and Supervision
Display:
Synoptic LED
Alarms Output:
Dry contacts on shelf (optional)
Supervision:
Use optional devices, Comprehensive table of troubleshooting codes
* Operation within lower voltage networks leads to derating of power performances ** "n" stands for Number of Modules in parallel
Short Circuit Clear Up Capacity:
10 x In for 20sec Available while Mains is available at AC input port;
with magnitude control and management
DSP Inverter Series
1 to 15kVA Inverter System
> Nebs level 3 certified to assure compatibility with the telecommunications environment
> Fourth generation DSP architecture utilizing SMD for high reliability
> Hot swappable EUE static switch and inverter modules > 6 or 15kVA EUE static switch available
DSP inverter
DSP Inverter Series
Inverter Module Rating: 1kVA
2.5kVA
Nominal System Output Capacity with One Rack Shelf:
1 to 5kVA (6kVA w/o EUE)
2.5 to 12.5kVA (15kVA w/o EUE)
Nominal Bypass AC Input: 120Vac
120Vac
Number of Bypass AC Phases: 1
1
Bypass AC Input Wiring:
L, N, PE
L, N, PE
Bypass Voltage Tolerance: ±10% (Adjustable ±5% to ±15%)
±10% (Adjustable ±5% to ±15%)
Maximum System Capacity with Two Rack
Shelves, without EUE:
12kVA
46
Nominal DC Input:
-48Vdc
30kVA -48Vdc
DC Input Range:
40.8 to 60Vdc
40.8 to 60Vdc
Power Rating:
1000VA / 800W
2500VA / 2000W
Nominal Input Current (-48Vdc): 19A
47A
DC to AC Inverters
Maximum Input Current:
22.5A
55A
Output
Output Current (120Vac):
8.33A
20.83A
Nominal Output Voltage:
120Vac
120Vac
Output Voltage Regulation:
±5% for all combinations of line, load and temperature
Output Power Factor:
0.7 lagging to 0.8 leading
0.7 lagging to 0.8 leading
Output Voltage Waveform: DSP Sine wave
DSP Sine wave
Output Crest Factor:
2.8:1
2.8:1
Output Voltage Distortion: Output Overcurrent Protection: Overload Rating (Inverters): Overload Rating (Static Bypass): Optional Maintenance Bypass Switch: Inverter Module Rating:
<3% @ 100% rated linear load Electronic current limiting
500% for 100mS
<3% @ 100% rated linear load Electronic current limiting 110% continuous, 120% for ~1 minute, 200% for ~4 seconds 500% for 100mS
Internally mounted, Make-before-break mechanically interlocked switch provided on all models equipped with the EUE static bypass module
1kVA
2.5kVA
Remote Alarming:
(1) Form-C Inverter fault, (1) Form-C Static Switch fault
LED Indicators (Inverter Modules):
On, Output present, DC Input OK, Inverter Fault, Parallel Operation, Overload, Bar graph for output power
Display/Metering (EUE, Static Bypass Module):
Graphic Display (Menu Driven, password protected), Power flow diagram, LED's (Normal, fault)
Mechanical
Rack Shelf Dimensions (in/mm): 12.25 x 23 x 19.8 / 311 x 584 x 503
12.25 x 23 x 25.25 / 311 x 584 x 590
Weight (lb/kg):
11 / 5
17.6 / 8
Environment
Elevation:
<3000m / 10000ft without derating
<3000m / 10000ft without derating
Operating Temperature:
0 to 55°C / 32 to 131°F
0 to 55°C / 32 to 131°F
Operating Humidity: Standards
0 to 95% non-condensing
0 to 95% non-condensing
Radio Interference:
Certified to Telecorodia GR-1089
Certified to Telecorodia GR-1089
Safety Listing:
UL60950
UL60950
Product Certification:
NEBS Level 3, Seismic Zone 4
NEBS Level 3, Seismic Zone 4
MS Power Inverter Series
1 and 2kVA Inverter System
> Standard 19"/23", 2RU rack mount > 1kVA/800W and 2kVA/1600W > Pure sine wave output > Utility bypass function > UL/cUL approved > RS-232 communication > Internal "over temperature" protection > Input reverse polarity protection > Output overload protection
MS Power Inverter
MS Power Inverter Series
Models
Majorsine1000-24-2U
Majorsine1000-48-2U
Majorsine2000-48-2U
Input
Voltage: Rated Current: Protection: Efficiency:
20 to 30Vdc 50A Fuse and DC Breaker
40 to 60Vdc
40 to 60Vdc
25A
50A
Fuse and DC Breaker
Fuse and DC Breaker
>85% (full linear load), 24Vdc I/P, 120Vac O/P
Output (Backup)
Capacity:
1kVA / 800W
1kVA / 800W
2kVA / 1600W
Voltage:
110, 115, 120, 125Vac
110, 115, 120, 125Vac
110, 115, 120, 125Vac
47
Voltage Regulation:
±2%
±2%
±2%
Frequency:
50/60Hz ±0.2Hz
50/60Hz ±0.2Hz
50/60Hz ±0.2Hz
Waveform:
Pure sine wave
Pure sine wave
Pure sine wave
THD (Linear Load):
3% 120V/100%
3% 120V/100%
3% 120V/100%
THD (SPS Load):
5% 120V/100%
5% 120V/100%
5% 120V/100%
Crest Factor:
31
31
31
Receptacles:
(4) NEMA 5-20R outlets
(4) NEMA 5-15R outlets
(4) NEMA 5-20R outlets
DC to AC Inverters
Utility Power (Bypass)
Voltage (Nominal): Frequency: Protection: Communication: LED Display:
120Vac 60 ±5Hz AC Circuit Breaker RS232 / Dry-contact Inverter ON, Overload, DC Abnormal
120Vac 60 ±5Hz AC Circuit Breaker RS232 / Dry-contact Inverter ON, Overload, DC Abnormal
120Vac 60 ±5Hz AC Circuit Breaker RS232 / Dry-contact Inverter ON, Overload, DC Abnormal
LCD Display:
Inverter ON, Output voltage and frequency, Input voltage, Load percentage, DC voltage, System model, Internal environment temp., Utility status, Short circuit, Over temp.
Protection
Short: Overload: Temperature:
For 1 second; Switch to bypass, then shutdown
105 to 125% for 3 minutes; 126 to 150% for 3 seconds; >150% for 1 second; Switch to bypass
55° ±5°C (Inside the case) 131° ±41°F
55° ±5°C (Inside the case) 131° ±41°F
55° ±5°C (Inside the case) 131° ±41°F
Environment
Operating Temperature: Storage Temperature: Humidity: Acoustic Noise: Safety: EMI / RFI:
0 to 50°C / 32 to 122°F -20 to 70°C / -4 to 158°F 0 to 90°C / 32 to 194°F non-condensing 46dBA @ 1 M UL / cUL FCC Class A
0 to 50°C / 32 to 122°F -20 to 70°C / -4 to 158°F 0 to 90°C / 32 to 194°F non-condensing 46dBA @ 1 M UL / cUL FCC Class A
0 to 50°C / 32 to 122°F -20 to 70°C / -4 to 158°F 0 to 90°C / 32 to 194°F non-condensing 46dBA @ 1 M UL / cUL FCC Class A
Mechanical
Dimensions H x W x D (in/mm):
Weight (lb/kg):
15.4 / 7
3.5 x 17.3 x 11.8 / 88 x 440 x 300, 2RU 15.4 / 7
17.6 / 8
Single and Three Phase UPS
> AMPS80HP
Alpha's new high performance AC or hybrid AC/DC system offers telecom grade reliability, 94% efficiency and high power density. The AMPS80 features hot swappable 2.5kVA/ 2.0kW inverter modules and optional 1.8kW rectifier. The AMPS80 meets your current and future power needs by allowing you to purchase and install individual modules for the ultimate flexibility to scale up or down. Front access and user-friendly connections make the system easy to install, service and upgrade.
> AMPS24HP
The AMPS24 features hot swappable 1.5kVA/1.2kW inverter modules and 1.8kW rectifier modules that are the building blocks of a highly reliable power system utilizing 48Vdc batteries. The AMPS24 meets your current and future needs by allowing them to purchase only the power modules for current needs while having ultimate flexibility to scaleup or down, depending on future power needs.
> EX UPS
The EX UPS offers high-performance power protection. With the ability to be rack mounted or a standalone tower, this UPS is ideal for mid-range servers, networks, IT equipment, and medical and storage devices. With a low cost of ownership and a broad range of features, the EX UPS is one of the best in its class.
> EX RT UPS
The EX RT UPS is a UPS designed for sensitive high-density server environments and harsh industrial applications. Specifically engineered to meet demanding customer applications in IT systems,
measuring instruments, PLCs and industrial PC markets, the EX RT is fully compatible with genset
redundancy requirements in most instances. The manual bypass, hot swappable I/O box and intuitive
49
LCD control panel are just a few of the many differentiating features that make the EX RT the ideal
product for the 5-11kVA power range.
Single and Three Phase UPS
> 1600XP Series
The 1600XP series offers a tower design solution with a LCD touchscreen display that provides unmatched access for UPS monitoring and control. As a double conversion on-line UPS, it is able to supply uninterrupted, clean single-phase power to your critical systems while keeping batteries charged continuously.
> TrinitiTM 4200 Series
The Alpha Triniti Series three phase UPS incorporates dual conversion technology designed to provide power conditioning for sensitive headend electronics, regardless of the quality of the utility or generator input power. Its unique active front end design provides power factor correction. In addition to providing utility cost savings, this feature provides compatibility with most existing headend generators, including those with mechanical governors running at near capacity.
> Galaxy
The Galaxy Series is the world's first data-center grade UPS designed specifically for mid-range enterprise level applications. The AlphaSource Galaxy delivers the optimum level of reliability, availability and scalability demanded by the new generation of critical enterprise applications.
> G9000
Using IGBT technology in the rectifier/converter, DC/DC chopper and inverter sections, the G9000 Series' double-conversion topology provides an AC/DC/AC efficiency of 97% at loads from 50 to 100%. Even at 20% loading, the efficiency remains greater than 95%. This industry-leading performance makes the G9000 the perfect solution for N+1 parallel systems where loads are typically 30 to 40%.
> Symmetra PX
The Symmetra PX 100kW is a world-class, high-efficiency power protection system designed to cost-effectively provide redundancy and high levels of availability in a two-rack footprint. The hot scalable Symmetra PX 100 provides up to 100kW of modular power protection for 208V deployments, as well as hot swappable long-life batteries and power distribution.
AMPS80HP
Modular AC UPS System
> High performance AC or hybrid AC/DC backup power system offering 99.999% availability
> 94% Efficiency, 15 year Design Life and MTBF (Mean Time Between Failures) greater than 200,000 hours
> Intelligent system controller with integrated SNMP for local and remote management of AC and DC power modules, batteries, and other peripherals
> Hot swappable 2.5kVA/2.0kW inverter modules and optional 1.8kW rectifier modules
> Small footprint system offers up to 75kVA/60kW in a single 19" box bay rack
AMPS80
AMPS80HP
Model
AMPS80- AMPS80- AMPS80- AMPS80-
3-75
3-30
2-40
1-20
Max. DC Input Current @ 48Vdc:
1375A
550A
734A
366A
Input and Output Phase:
120/208V 3-ph
120/240 or 120 single 120/208V2-ph ph
@ 40Vdc: Voltage Ripple:
1700A
680A
900A
<2mV / <38dbrnc
450A
Single and Three Phase UPS
Output Capacity:
50
Output Power
7500 to 75000VA
6000 to
7500 to 30000VA
6000 to
5000 to 40000VA
4000 to
2500 to 20000VA
2000 to
Unified System Controller with Integrated SNMP
Control and Monitoring:
Configure, control and monitor inverter and rectifier modules via Internet Explorer 7 onwards
(Resistive Load):
60000W 24000W 32000W 16000W
LCD Touch-screen Display (160 x 160 pixels),
Maximum Output Current:
208Arms per phase
83Arms per phase
168Arms per phase
168Arms
Display:
OK/Major/Minor 3-Color LED display, Web based GUI via Ethernet
Max./Min. No. of 2500VA/2000W Inverter Modules:
30/3
12/3
16/2
8/1
Communication Ports: Mechanical
RJ45 Ethernet Port, R232 Port (Front)
Technology:
Twin Sine Inverter (TSI) technology; each inverter module has DC input and AC input
Dimensions H x W x D (in/mm):
84 x 23.6 x 26.8 / 213 x 600 x 680
Static Switch: Efficiency: Waveform:
Not required; each module has its own static switch
94% AC to AC; 90% DC to AC (from 50 to 100% full resistive load)
Pure sine wave
System Weight Without Modules (lb/kg):
Module Dimensions H x W x D (in/mm):
595 / 270 3.5 x 4 x 17.1 / 88.9 x 102 x 435
Output Power Factor:
0.8 (can run capacitive and inductive loads)
Module Weight (lb/kg):
11 / 5
Transfer Time:
Zero transfer time
Clearance (in/mm)
Warranty:
2 year standard (1 and 3 year optional extensions)
Front:
33 / 838.2
Inverter Module AC Output
Power Rating:
Voltage Range (AC):
90 to 140V
Voltage Accuracy:
±2%
2500VA/2000W
90 to 140V 90 to 140V
±2%
±2%
90 to 140V ±2%
Rear: Sides: Top: Environment
12 / 304.8 No clearance required 12 / 304.8
Frequency:
60Hz (same as input frequency)
Operating Temperature:
-20 to 40°C / -4 to 104°F (full load)
Inverter Frequency Accuracy: 0.03%
0.03%
0.03%
0.03%
Storage Temperature:
-40 to 70°C / -40 to 158°F
Input Power Factor:
>99%
>99%
>99%
>99%
Humidity:
Up to 95% non-condensing
THD (Resistive Load):
<1.5%
<1.5%
<1.5%
<1.5%
Elevation:
Up to 2000m / 6562ft above sea level
Transient Load Recovery Time: 0.4ms
0.4ms
0.4ms
0.4ms
Standards
Soft Start Time:
20s
20s
20s
20s
Max. Crest Factor @ No. Power: 3.5
3.5
3.5
3.5
Short Circuit Overload Capacity: Short Term Overload Capacity:
10 x ln for 20msec (AC to AC mode) 150% for 5 seconds
Permanent Overload Capacity: 110%
110%
110%
110%
Synchronization Range:
57 to 63Hz 57 to 63Hz 57 to 63Hz 57 to 63Hz
Inverter Module DC Output
Safety: EMC:
Features:
UL1778 (2nd Ed); CSA C22.2 No. 107.3-05 UPS General Safety
FCC CFR47 Part 15 Class A; ICES-003
Unified system controller with integrated SNMP communications, Top AC and DC feed access; bottom DC feed access (All user connections are front access), AC input and output breaker/ disconnect switch, Industrial grade surge suppression (rated to 40kA)
Nominal Voltage: Voltage Range (max.):
48Vdc
48Vdc
48Vdc
48Vdc
40 to 60Vdc (User Adjustable)
Options:
Up to 8 x 1.8kW rectifier modules, Integrated maintenance bypass switch, Inverter DC input breakers, Service-entrance grade surge suppression: 140kA rating (per phase), Lockable rack front-door, Batteries (various sizes and technologies)
AMPS24HP
Modular AC and Hybrid Power System
> High performance AC and hybrid AC/DC backup power system offering
99.999% reliability for mission critical indoor applications
> 93% Efficiency, 15 year Design Life and MTBF (Mean Time
Between Failures) greater than 200,000 hours results in
class leading TCO (Total Cost of Ownership)
> Intelligent system controller with integrated SNMP for local
and remote management
> Hot swappable 1.5kVA/1.2kW inverter modules and 1.8kW
rectifier modules (optional for inverter only systems) offer complete
flexibility, scalability and low MTTR (Mean Time To Repair)
AMPS24
> Up to 24kVA/19.2kW small footprint system maybe installed in a 19" or 23"
open-relay rack or box bay rack/cabinet with flexible mounting options
AMPS24HP Hybrid Systems
Specifications*
Models:
AMPS24-3-13.5-H3
AMPS24-2-18-H4
AMPS24-2-9-H2
AMPS24-1-9-H2
AMPS24-1-4.5-H1
Input and Output Phase:
120/208V 3-ph
120/240 or 120/208V 2-ph
120V single ph
Nominal Output Power (max): 4500 to 13500VA
3000 to 18000VA
3000 to 9000VA
1500 to 9000VA
1500 to 4500VA
Output Power (Resistive Load): 3600 to 10800W
2400 to 14400W
2400 to 7200W
1200 to 7200W
1200 to 3600W
Max. Output Current:
37.5Arms per phase
75Arms per phase
37.5Arms per phase
75Arms per phase
37.5Arms per phase
51
Max. No. of 1500VA/1200W Inverter Modules Per System:
9
12
6
6
3
Min. No. of 1500VA/1200W Inverter Modules Per System:
3
2
2
1
1
Max. No. of 1800W Rectifier Modules Per System:
3
4
2
2
1
Single and Three Phase UPS
AMPS24HP Inverter Systems
Specifications*
Models:
AMPS24-3-18-3i
Input and Output Phase: Nominal Output Power (max): Output Power (Resistive Load): Max. Output Current: Max. No. of 1500VA/1200W Inverter Modules Per System: Min. No. of 1500VA/1200W Inverter Modules Per System: Technology: Static Switch: Efficiency: Waveform: Output Power Factor: Transfer Time: Warranty:
120/208V 3-ph 4500 to 18000VA 3600 to 14400W 50Arms per phase 12
3
Inverter Module AC Output
Power Rating:
Nominal Voltage:
Voltage Accuracy:
Frequency:
Inverter Frequency Accuracy:
THS (Resistive Load):
Transient Load Recovery Time:
Soft Start Time: Max. Crest Factor at Nominal Power: Short Circuit Overload Capacity: * Specifications subject to change.
AMPS24-2-24-4i
AMPS24-2-12-2i
120/240 or 120/208V 2-ph
3000 to 24000VA
3000 to 12000VA
2400 to 19200W
2400 to 9600W
100Arms per phase
50Arms per phase
16
8
AMPS24-1-12-2i
AMPS24-1-6-1i
120V single ph
1500 to 12000VA
1500 to 6000VA
3600 to 9600W
2400 to 4800W
100Arms per phase
50Arms per phase
8
4
2
2
1
1
Twin Sine Inverter (TSI) technology; each inverter module has DC and AC input Not required; each module has its own static switch
93% AC-to-AC; 90% DC-to-AC (from 50 to 100% full resistive load) Pure sine wave
0.8 (Can run capacitive and inductive loads) Zero transfer time
2 Years (1 and 3 year optional extensions)
1500VA/2000W 120Vac ±2
60Hz (same as input frequency) 0.03% <1.5% 0.4ms 20s 3.5
10 x In for 20msec (AC to AC mode)
EX UPS
> Double conversion UPS technology for 100% compatibility with any application, environment or genset and high output to protect equipment with PFC power supplies
> Wide input voltage window to conserve battery time for blackouts only
> Automatic bypass for high availability
EX UPS Mini Tower
EX UPS
Models
Specifications
Input Voltage:
Frequency Range:
Rating:
Input Connection:
Topology:
Output Voltage:
52
Output Frequency:
Output Receptacle:
Additional Outputs with HotSwap MBP:
PULSL700T
40 to 70Hz 700VA / 630W 5-15P
(4) 5-15R (4) NEMA 5-15R
PULSL1000T
PULSL1500T
PULSL1000R-XL2U PULSL1500R-XL2U
100/120/140/1601 to 248V
40 to 70Hz
40 to 70Hz
40 to 70Hz
1000VA / 900W
1500VA / 1350W
1000VA / 900W
5-15P
5-15P
5-15P
Online double conversion with automatic bypass and power factor correction
120V (adjustable to 100/110/127V)
50/60Hz, auto-select or frequency converter mode2
(4) 5-15R
(4) 5-15R
(6) 5-15R
(4) NEMA 5-15R
(4) NEMA 5-15R
(4) NEMA 5-15R
40 to 70Hz 1500VA / 1350W 5-15P
(6) 5-15R (4) NEMA 5-15R
Additional Outputs with FlexPDU:
NEMA L5-20R
NEMA L5-20R
NEMA L5-20R
NEMA L5-20R
NEMA L5-20R
Single Phase UPS
Mechanical
Configuration:
Mini Tower
Mini Tower
Mini Tower
Rack
Rack
Dimensions H x W x D (in/mm):
9.5 x 6 x 17.3 / 241.3 x 152.4 x 439.4
9.5 x 6 x 19.3 / 241.3 x 152.4 x 490.2
3.5 x 17.3 x 19 / 88.9 x 439.4 x 482.6
Weight (lb/kg):
25.7 / 11.7
33 / 15
39.6 / 18
39.6 / 18
45 / 20.4
Communication and Management
Indicators: Display: Communication Ports: Communication Card Slots:
(3) LEDs with adjustable multilingual display Display of measurements, access to control and setup menus (1) USB port, (1) RS232 serial port and relay contacts3, (1) mini terminal block for remote on/off and emergency stop (1) Slot for NMC Mini-Slot 206 card, NMC ModBus/JBux or MC Contacts/Serial
Environment
Operating Temperature: Noise Level:
0 to 40°C / 32 to 104°F 45dBA
0 to 40°C / 32 to 104°F 45dBA
0 to 40°C / 32 to 104°F 45dBA
0 to 40°C / 32 to 104°F 45dBA
0 to 40°C / 32 to 104°F 45dBA
Standards
Performance/Safety/EMC: Approvals:
IEC 62 040-3 (VFI-SS-113), IEC 62 040-1-1, IEC 60 950-1 (RD), FCC Subpart B, Class A UL, cUL, CE CB report
Warranty
2 year factory warranty
Notes: 1 Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA); for active output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively 2 Derated by 15% when used as a frequency converter 3 USB and RS232 serial ports cannot be used simultaneously
EX UPS
> Extended runtime capabilities with multiple, hot swappable battery modules (optional)
> Remote reboot of locked equipment, sequential start-up through individually switchable outlets
EX UPS Rack/Tower 2RU
EX UPS
Models
PULSML2200-XL2U PULSML2200-XL3U PULSML3000-XL2U PULSML3000-XL3U PULSML3000-XL3UXL
Specifications
Input Voltage:
501 - 100 to 142V
501 - 100 to 142V
501 - 100 to 142V
501 - 100 to 142V
501 - 100 to 142V
Frequency Range:
40 to 70Hz
40 to 70Hz
40 to 70Hz
40 to 70Hz
40 to 70Hz
Rating:
2100/1650
2100/1650
3000/2550
3000/2550
3000/2550
Input Connection:
5-20P
5-20P
L5-30P
L5-30P
L5-30P
Topology:
Online with automatic bypass and power factor correction
Output Voltage:
120V (adjustable to 100/110/127V)
Output Frequency:
50/60Hz, auto-select or frequency converter mode2
53
Output Receptacle:
(6) NEMA 5-20R + (1) NEMA L5-20R
(6) NEMA 5-20R + (1) NEMA L5-20R
(6) NEMA 5-20R + (1) NEMA L5-30R
(6) NEMA 5-20R + (1) NEMA L5-30R
(6) NEMA 5-20R + (1) NEMA L5-30R
Additional Outputs with HotSwap MBP:
(5) NEMA 5-15R or (5) NEMA 5-20R
Single Phase UPS
Additional Outputs with FlexPDU:
(10) NEMA 5-15R or (10) NEMA 5-20R or (8) NEMA L5-20R
Mechanical Configuration:
Rack/Tower 2RU
Rack/Tower 3RU
Rack/Tower 2RU
Rack/Tower 3RU
Rack/Tower 3RU XL
Dimensions H x W x D (in/mm):
3.4 (2RU) x 17.3 x 25.2 / 5.1 (3RU) x 17.3 x 19.3 / 3.4 (2RU) x 17.3 x 25.2 / 5.1 (3RU) x 17.3 x 19.3 / 5.1 (3RU) x 17.3 x 19.3 /
86.4 x 439.4 x 640.1
129.5 x 439.4 x 490.2
86.4 x 439.4 x 640.1
129.5 x 439.4 x 490.2
129.5 x 439.4 x 490.2
Weight (lb/kg):
68.2 / 30.9
68.2 / 30.9
68.2 / 30.9
66 / 29.9
66 / 29.9
Communication and Management
Indicators:
(3) LEDs with adjustable multilingual display
Display:
Display of measurements, access to control and setup menus
Communication Ports:
(1) USB port, (1) RS232 serial port and relay contacts3, (1) mini terminal block for remote on/off and emergency stop
Communication Card Slots:
(1) Slot for NMC Mini-Slot 2006 card, NMC ModBus/JBus or MC Contacts/Serial
Environment
Operating Temperature:
0 to 40°C / 32 to 104°F 0 to 40°C / 32 to 104°F 0 to 40°C / 32 to 104°F 0 to 40°C / 32 to 104°F 0 to 40°C / 32 to 104°F
Noise Level:
45dBA
45dBA
45dBA
45dBA
45dBA
Standards
Performance/Safety/EMC:
IEC/EN 62-040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 -50-1 (RD), IEC/EN 62 040-2 C1, FCC Subpart B, Class A
Approvals:
CE, TüV, CB Report, UL and CUL (CSA)
Notes: 1 Lower limits for reduced load 2 Derated by 15% when used as a frequency converter 3 USB and RS232 serial ports cannot be used simultaneously
EX RT UPS
> Internal static bypass > Input/output (I/0) box with manual bypass > Large input voltage range without using battery power > 40 to 70Hz input frequency range > Standalone solution with modular design for industrial needs > Communications slot compatible with multiple
communication card protocols
EX RT UPS
EX RT UPS
Models
EXRTG5000-XL6UMS
EXRTG7000-XL6UMS
EXRTG11000-XL6UMS
Configuration:
Rack/Tower
Rack/Tower
Rack/Tower
Specifications
Nominal Input Voltage: Input Voltage Range:
Input Frequency Range:
Rating:
Input Connection:
54
Topology:
Output Voltage:
Output Frequency:
120 to 280V @ 70% rated output
120 to 280V @ 70% rated output
120 to 280V @ 70% rated output
156 to 280V @ 100% rated output 40 to 70Hz, frequency converter as a standard 5000VA/4000W
156 to 280V @ 100% rated output 40 to 70Hz, frequency converter as a standard 7000VA/4900W
156 to 280V @ 100% rated output 40 to 70Hz, frequency converter as a standard 11000/8000W
Hardwired
Hardwired
Hardwired
Online with automatic bypass
Online with automatic bypass
Online with automatic bypass
200/2081/220/230/240/250; 120V output voltage available with transformer
50/60Hz auto -select
Output Receptacle: Overall Efficiency:
Hardwired 90 to 97% (Online mode - ECO mode)
Hardwired 90 to 97% (Online mode - ECO mode)
Hardwired 90 to 97% (Online mode - ECO mode)
Single Phase UPS
Harmonic Current Distortion: Crest Factor:
<5% 3:1
<5% 3:1
<5% 3:1
Overload Capacity:
Battery Test:
Operating Temperature:
Block Power Module Input/Output terminal Block: Maximum Wire Size (Solid or Standard Wire): Step-Down Transformer:
Output Configuration:
2 min if 120%<overload<110%, 1 min if 110%<overload<125%, 30 sec if 125%<overload<150%, 500 msec if overload>150%
Weekly without load interruption2
45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F
Weekly without load interruption2
45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F
Weekly without load interruption2
45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F
Hardwired
Hardwired
Hardwired
5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
120/208/240Vac output
5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
120/208/240Vac output
5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
120/208/240Vac output
Terminal block, plus (2) NEMA L6-30R (208V), (8) NEMA 5-20R; optional PDUs for additional NEMA or IEC receptacles
Mechanical
Configuration: Dimensions H x W x D (in/mm): Weight (lb/kg):
Rack/Tower 10.3 (6RU) x 17.5 x 26.3 / 261.6 x 444.5 x 668 192 / 87.1
Rack/Tower 10.3 (6RU) x 17.5 x 26.3 / 261.6 x 444.5 x 668 192 / 87.1
Rack/Tower 10.3 (6RU) x 17.5 x 26.3 / 261.6 x 444.5 x 668 211 / 95.7
Communication
Communication Ports Type: Communication Card Slots:
(6) Voltage-free dry contacts DB-9 rated at 2A 48Vdc, (1) RS 232, (1) RJ11 for RPO (Remote Power Off) (1) Slot for Mini-Slot communication card [Network Management Card (SNMP/Web), NMC ModBus/JBus, MC Contacts/Serial]
Standards
Performance and Safety: EMC:
IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards IEC 62040-2; EN 50091-2; FCC Class A
Warranty
2 years, parts and labor (US and Canada)
Notes: 1 Default voltage 2 Configurable to daily or monthly
EX RT UPS
> Versatile 6RU rack or tower design > Multilingual LCD > Integrated NEMA receptacles included
with transformer configuration > Optional rack mount PDU with NEMA
or IEC sockets to facilitate power distribution within the enclosure
EX RT UPS
EX RT UPS
Models
EXRTL5000-XL9UMS
EXRTL7000-XL9UMS
EXRTL11000-XL9UMS
Specifications
Nominal Input Voltage:
120 to 280V @ 70% rated output
120 to 280V @ 70% rated output
120 to 280V @ 70% rated output
Input Voltage Range:
156 to 280V @ 100% rated output
156 to 280V @ 100% rated output
156 to 280V @ 100% rated output
Input Frequency Range:
40 to 70Hz, frequency converter as a standard 40 to 70Hz, frequency converter as a standard 40 to 70Hz, frequency converter as a standard
Rating:
5000VA/4000W
7000VA/4900W
11000/8000W
Input Connection:
Hardwired
Hardwired
Hardwired
Topology:
Online with automatic bypass
Online with automatic bypass
Online with automatic bypass
Output Voltage: Output Frequency:
200/2081/220/230/240/250; 120V output voltage available with transformer
55
50/60Hz auto -select
Output Receptacle:
Hardwired + (2) NEMA L6-30R + (8) NEMA 5-20R
Overall Efficiency:
90 to 97% (Online mode - ECO mode)
90 to 97% (Online mode - ECO mode)
90 to 97% (Online mode - ECO mode)
Harmonic Current Distortion: <5%
<5%
<5%
Crest Factor:
3:1
3:1
3:1
Overload Capacity:
2 min if 120%<overload<110%, 1 min if 110%<overload<125%, 30 sec if 125%<overload<150%, 500 msec if overload>150%
Battery Test:
Weekly without load interruption2
Weekly without load interruption2
Weekly without load interruption2
Operating Temperature:
45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F 45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F 45°C / 113°F for 8 hr, 0 to 40°C / 32 to 104°F
Block Power Module Input/Output terminal Block:
Hardwired
Hardwired
Hardwired
Single Phase UPS
Maximum Wire Size (Solid or Standard Wire):
5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
5/7kVA: 10mm/6 AWG 11kVA: 13mm/4 AWG
Step-Down Transformer: Output Configuration:
120/208/240Vac output
120/208/240Vac output
120/208/240Vac output
Terminal block, plus (2) NEMA L6-30R (208V), (8) NEMA 5-20R; optional PDUs for additional NEMA or IEC receptacles
Mechanical
Configuration:
Rack/Tower
Rack/Tower
Rack/Tower
Dimensions H x W x D (in/mm):
15.5 (9RU) x 17.5 x 26.3 / 393.7 x 444.5 x 668
15.5 (9RU) x 17.5 x 26.3 / 393.7 x 444.5 x 668
15.5 (9RU) x 17.5 x 26.3 / 393.7 x 444.5 x 668
Weight (lb/kg):
365 / 165.6
365 / 165.6
384 / 174.2
Communication
Communication Ports Type: Communication Card Slots:
(6) Voltage-free dry contacts DB-9 rated at 2A 48Vdc, (1) RS 232, (1) RJ11 for RPO (Remote Power Off) (1) Slot for Mini-Slot communication card [Network Management Card (SNMP/Web), NMC ModBus/JBus, MC Contacts/Serial]
Standards
Performance and Safety: EMC: Warranty 2 years, parts and labor (US and Canada)
IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards IEC 62040-2; EN 50091-2; FCC Class A
Notes: 1 Default voltage 2 Configurable to daily or monthly
1600 XP Series
Single Phase UPS
> True on-line, double conversion UPS > Electronic power factor correction for 100% generator compatibility > User-friendly, programmable touch-screen display > Internal isolation transformer > Hot swappable battery packs and cooling fans > External battery connector > SNMP/Web-based monitoring
1600 XP Series
1600 XP Series
Power Rating
3.6kVA / 3.1kW 6kVA / 5.1kW 8kVA / 6.8kW 10kVA / 8.5kW 14kVA / 11.9kW 18kVA / 15.3kW 22kVA / 18.7kW
Specifications
Topology: Certifications: Input
True on-line, double conversion; IGBT power factor corrected input; internal isolation transformer UL 1778, CUL, CE, FCC Class A, IEEE 587, ANSI/C62.41, ISO 9001, ISO 14001, NEMA/PE1-1993, RoHs
Input Voltage:
Single-phase 208/240Vac (Three-wire input/L-L, G); 230Vac (Three-wire input/L, N, G), +10 to 30%
Input Frequency:
45 to 65Hz (Auto Sensing)
Input Power Factor:
>0.95 for all loads >0.95 for all loads >0.95 for all loads >0.95 for all loads >0.95 for all loads >0.95 for all loads >0.95 for all loads
Input Current THD:
>5% (Even for 100% non-linear loads)
AC Input Breaker Rating: 30A
50A
60A
63A
100A
100A
125A
Battery
56
Battery Type:
Valve-regulated lead acid; flame retardant (9Amp Hr)
Backup Time (Fully Charged):
7 minutes
7 minutes
7 minutes
5 minutes
7 minutes
5 minutes
3 minutes
0.85 Power factor; 25°C / 77°F; Approx. 30% more runtime for output power factor of 0.7 (Triple backup time at 1/2 load)
Recharge Time:
24 Hours (full), 12 Hours (90%)
DC Link:
144Vdc
216Vdc
288Vdc
288Vdc
288Vdc
288Vdc
288Vdc
Output
Single Phase UPS
Output Voltage: Output Voltage Regulation: Output Frequency: Output Voltage THD: Common Mode Noise: Rated-Load Power Factor: Rated Output Current @ 240V: Max. Peak Output Current: Overload Capacity: Environmental
Single-phase 240/208/120Vac (Four-wire output/L-L, N, G); 230Vac (Three-wire Output L, N, G)
±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical ±3%; ±1% typical
50/60Hz; ±0.5Hz/1.0Hz/1.5Hz (Factor or authorized service center selectable)
<3% for linear load; 1% typical
<0.5V RMS
<0.5V RMS
<0.5V RMS
<0.5V RMS
<0.5V RMS
<0.5V RMS
<0.5V RMS
0.85 (0.6 to 1.0) lag
15A
25A
33.3A
41.6A
58A
75A
91.6A
45A
75A
100A
125A
174A
225A
275A
Inverter mode: 150% for 10 seconds, 125% for 30 seconds; Bypass mode: 125% for 10 minutes, 1000% for one cycle
Efficiency (AC-DC-AC): Temperature Range: Heat Generation (BTU/hr): Elevation: Audible Noise:
>85% 1843 <60dBa @ 1 Meter
>85%
>85%
>85%
>85%
>85%
0 to 40°C / 32 to 104°F (Operating); -20 to 40°C / -4 to 104°F (Storage)
3071
4095
5118
7168
9213
2000m/6600ft max. without derating
<60dBa @ 1 Meter <60dBa @ 1 Meter <60dBa @ 1 Meter <60dBa @ 1 Meter <60dBa @ 1 Meter
>85% 11260 <60dBa @ 1 Meter
Mechanical
Enclosure: Dimensions H x W x D (in/mm): Weight (lb/kg):
22.1 x 10 x 33 / 561.34 x 254 x 838.2
280 / 127
Steel enclosure; Complies with NEMA 1 and UL Type-1 standard
27.5 x 10 x 33 / 698.5 x 254 x 838.2
28.4 x 13 x 34.9 / 721.36 x 330.2 x 886.46
39.1 x 17.5 x 36.1 / 993.14 x 445.5 x 916.94
346 / 157
476 / 214
784 / 355
835 / 379
Battery Pack Dimensions H x W x D (in/mm):
5 x 7.3 x 19 / 127 x 185.4 x 482.6 (Six batteries of REW 45-12FR per pack)
Battery Pack Quantity:
Two
Three
Four
Eight
Features
Options Warranty
Output isolation transformer, RS232 and dry contact interface, Crest factor of 3, Angled terminal blocks for easy installation, Casters for mobility SNMP and WEB-based monitoring, Matching battery cabinet, Internet/external maintenance bypass, Receptacle panel and line cord
3 years on electronics (UPS); 2 years on battery
TrinitiTM 4200 Series
Three Phase UPS
> 15, 25, 50 and 80kVA power ratings > 100% front access > Internal maintenance bypass (except on 80kVA) > "Active Front End" provides total power factor correction and utility cost savings > Internal batteries reduce footprint for easy installation (except on 80kVA)
Triniti 4200 Series
Model
Triniti 15
Output Power Rating:
15kVA/12kW
Input Voltage (-15 to 10%; -30% if derated):
Output Voltage (±2% regulation balanced load):
Input Circuit Breaker @ 208V:
Output Current Per Phase @ 208/120V:
Typical Heat Output (KBTU/Hr):
Audible Noise at 1 Meter From Front Panel:
208/120 4 wire + gnd
208/120 4 wire + gnd 60A 41.7A 5.73 <60dBA
Internal Battery Runtime
Full Load @ 0.7 Power Factor: 10min Half Load @ 0.7 Power Factor: 30min
Mechanical
Dimensions H x W x D (in/mm):
Weight (lb/kg):
59.8 x 36.3 x 20 / 508 x 922 x 1518.9
900 / 408.2
* 4 to 64min runtime options
Triniti 25 25kVA/20kW 208/480 3 wire + gnd
208/120 4 wire + gnd 90A 69.4A 7.6 <60dBA
5min 15min
59.8 x 36.3 x 20 / 508 x 922 x 1518.9 910 / 412.7
Power Rating
Input Power Factor Correction: Input Harmonic Currents: Input Frequency Range: Load Crest Factor: Overload Capacity Inverter: Overload Capacity Bypass: Neutral Conductor Size:
>0.95 PF (lagging) <3% THD (typical) 60Hz, ±5% 3 125% for 90sec, 150% for 30sec 125% for 10ms, 1000% for 1 cycle 1.73 x conductor
Load Inrush Current Protection:
Automatically transfers to bypass then retransfers to inverter
Typical Efficiency AC/AC: Output Frequency:
87% 60Hz, ±0.1%
Status and Control
AC Input Present:
Input and output frequency
Inverter Operating:
Operating status menu
UPS on Bypass:
Diagnostic status menu
UPS on Battery:
DB9 dry contact interface
Fault:
RS232 communications
Input and Output Voltage: Emergency power off switch
Output Current Indicator: Run/Stop key switch
Battery Voltage Indicator:
Terminal block (input/output power connector) Internal maintenance bypass (except on 80kVA)
Optional Features:
External maintenance bypass, SNMP
Warranty
3 year parts and labor, 2 years on batteries. See warranty statement for further details, conditions and limitations.
Triniti 50 50kVA/40kW 208/480 3 wire + gnd
208/120 4 wire + gnd 175A 138A 17.73 <65dBA
5min 15min
59.8 x 37.6 x 35.6 / 904.2 x 939.8 x 1518.9 2548 / 1155.8
Triniti 15kVA
Triniti 80 80kVA/64kW 208/480 3 wire + gnd
208/120 4 wire + gnd 300A 222A 24.27 <65dBA
57
External Battery Pack Options*
74 x 31 x 44 / 1117.6 x 787.4 x 1879.6 2450 / 111.3
Three Phase UPS
Triniti 80kVA
Galaxy 3500
Three Phase UPS
> Power ranges 10, 15, 20 and 30kVA
> Double conversion on-line technology
> Compact and robust design
> Best-in-class efficiency (94%)
> Parallel capability
> Network manageability
Galaxy 3500
Galaxy 3500 Wide Enclosure
Galaxy 3500 Narrow Enclosure
Rated Power
10kVA / 8kW
15kVA / 12kW
20kVA / 16kW
30kVA / 24kW
Normal AC Supply Input
Input Voltage (V): Frequency (Hz): Input Power Factor: THDI: Input Voltage Tolerance Utility Operation: Dual Mains Input: Input Voltage Tolerance Bypass: Backfeed Protection:
208V (Three phase + neutral) 40 to 70Hz >0.98 at load >50% <5% at Full load
Yes
Built-in backfeed contactor
208V (Three phase + neutral) 40 to 70Hz >0.98 at load >50% <5% at Full load
208V (Three phase + neutral) 40 to 70Hz >0.98 at load >50% <5% at Full load
166 to 240V (at Full load) 100 to 240V (at half load) 208V
Yes
Yes
±10% standard ±4, 6, 8, 10% (programmable)
Built-in backfeed contactor
Built-in backfeed contactor
208V (Three phase + neutral) 40 to 70Hz >0.98 at load >50% <5% at Full load
Yes
Built-in backfeed contactor
Three Phase UPS
58
Output
Nominal Output Voltage (V):
208V (Three phase + neutral)
208V (Three phase + neutral)
208V (Three phase + neutral)
208V (Three phase + neutral)
Efficiency (AC-AC):
at Full Load at 50% Load
93.5% 92.5%
93.0% 93.5%
94.1% 93.8%
93.3% 94.3%
DC-AC Nominal Battery Voltage: 93.8%
93.8%
93.8%
93.8%
Load Power Factor:
0.5 leading to 0.5 lagging
0.5 leading to 0.5 lagging
0.5 leading to 0.5 lagging
0.5 leading to 0.5 lagging
Output Frequency:
Overload Capacity Operation:
Utility Battery
V THD:
150% for 60 seconds
Mains synchronized in normal operation 60Hz ± 0.05% free-running
125% for 10 minutes, 150% for 60 seconds
150% for 60 seconds
150% for 60 seconds
<2% From 0 to 100% linear load, <5% full non-linear load
150% for 60 seconds
Output Voltage Tolerance:
±1% Static, ±5% at 100% load step
Communication and Management
Communication Interface:
Network management card with environmental monitor
Control Panel:
Power view multi-function LCD, status and control console
Mechanical
Dimensions H x W x D (in/mm):
Weight (lb/kg):
Narrow Tower Wide Tower Narrow Tower Wide Tower
58.70 x 14 x 33 / 1490.98 x 355.6 x 838.2
--
58.70 x 20.60 x 33 / 1490.98 x 508 x 838.2
671 / 304 with 1 Battery module 873 / 395 with 1 Battery module --
711 / 322 with 2 Battery modules 913 / 414 with 2 Battery modules 979 / 444 with 2 Battery modules
--
-- 1181 / 535 with 2 Battery modules
Color:
Metallic Gray (RAL 9023)
Protection
Surge:
IEC61000-4-5, EN50091-2 ANSI-IEEE C62-41
Thermal:
Yes
Short Circuit:
Yes
Regulatory
Standards:
UL 1778, EN50091-2, IEC 62040-2 FCC15A, CE
Environmental
Temperature Range: Humidity:
Operating: 0 to 40°C / 32 to 104°F, Storage: -15 to 40°C / 5 to 104°F 0 to 95% non-condensing
Elevation:
Operating: 0 to 1000m /0 to 3280ft, Storage: 0 to 15,000m / 0 to 49,212ft
Max. Audible Noise: Protection Class:
<43.3dBA at <70% load (at 1m from unit)
<46.2dBA at <70% load (at 1m from unit) IP51/NEMA 12
Galaxy 4000
Three Phase UPS
> Power ranges 40, 50, 65 and 75kVA > True online double conversion technology > Low UPS to generator sizing > Power surge stabilization system > Power factor corrected input SNMP and
network based power management options
Galaxy 4000
Galaxy 4000
Power Rating
40kVA / 32kW
50kVA / 40kW
65kVA / 52kW
75kVA / 60kW
Input
Voltage:
208V
208V
208V
208V
Input Frequency:
60Hz (±5%)
60Hz (±5%)
60Hz (±5%)
60Hz (±5%)
Power Factor:
>0.98
>0.98
>0.98
>0.98
Current Distortion (THD):
<3% @ Full load
<3% @ Full load
<3% @ Full load
<3% @ Full load
Current (A @ 208V):
102
127
166
191
Output
Voltage:
208V
208V
208V
208V
Frequency:
60Hz (±1 to 4% selectable)
60Hz (±1 to 4% selectable)
60Hz (±1 to 4% selectable)
60Hz (±1 to 4% selectable)
Transient Response:
±5% for 0 to 100% to 0%
±5% for 0 to 100% to 0%
±5% for 0 to 100% to 0%
±5% for 0 to 100% to 0%
59
Voltage Distortion THD:
<1% L-L and L-N
<1% L-L and L-N
<1% L-L and L-N
<1% L-L and L-N
Inverter Overload 130%:
1min
1min
1min
1min
Inverter Overload 145%:
30 sec
30 sec
30 sec
30 sec
Bypass Overload:
10x nominal current - 1 cycle
10x nominal current - 1 cycle
10x nominal current - 1 cycle
10x nominal current - 1 cycle
Output Current (A @ 208V): 111
139
180
208
Three Phase UPS
Heat Rejection (max BTUs): 14900
18700
24200
28000
Runtimes @ 100% Load
1 x 285W/Cell:
12
9
6
-
1 x 370W/Cell:
20
14
9
8
1 x 500W/Cell:
28
22
15
11
2 x 370W/Cell:
47
36
25
22
2 x 500W/Cell:
67
52
38
31
3 x 500W/Cell:
98
85
60
53
4 x 500W/Cell:
136
115
85
72
Mechanical
Standard Cabinet Dimensions (in/mm):
33.5 x 35.6 x 72.1 / 1831.3 x 904.2 x 850.9
33.5 x 35.6 x 72.1 / 1831.3 x 904.2 x 850.9
33.5 x 35.6 x 72.1 / 1831.3 x 904.2 x 850.9
33.5 x 35.6 x 72.1 / 1831.3 x 904.2 x 850.9
Weight (lb/kg):
1235 / 560
1235 / 560
1235 / 560
1235 / 560
Battery Cabinet Dimensions (in/mm):
26.5 x 35.5 x 72.1 / 673 x 901 x 1831
26.5 x 35.5 x 72.1 / 673 x 901 x 1831
26.5 x 35.5 x 72.1 / 673 x 901 x 1831
26.5 x 35.5 x 72.1 / 673 x 901 x 1831
Weight (lb/kg):
2045 / 928
2045 / 928
2045 / 928
2045 / 928
Battery Cabinet Dimensions (in/mm):
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
33.5 x 35.6 x 72.1 / 850 x 901 x 1831
Weight (lb/kg): Standards Standards:
2745 / 1245
2745 / 1245
2745 / 1245
2745 / 1245
ISO 9001, UL 1778, cUL, FCC Part 15, subpart J, Class A, NEMA PE 1, NEMA 250, NFPA 70, IEC 10000 (801) level 4, OSHA
Standard Features:
True double conversion online topology, Input power factor correction (IGBT rectifier), Dual input, Input distortion management, Digital power quality management system (PWM/IGBT inverter), Step load voltage stabilization, Intelligent battery management system, Fault tolerant architecture, Casters with stabilizing feet, Network based software for multi-server control, Dry contact I/O card, SNMP manageable, Graphic display with multilingual user interface, Bottom or top entry, Four communications ports
Galaxy 5000
Three Phase UPS
> IGBT technology supplies clean, stable power to sensitive loads > Connect up to 6 units in parallel: add redundancy
or grow with your power requirements > Allows connection to two separate input
sources for increased availability > Built in static and maintenance bypass for seamless transfer
to utility for maintenance or in the event of heavy overload
Galaxy 5000
Gaxaly 5000
Power Rating
40kVA / 36kW
50kVA / 45kW
60kVA / 54kW
80kVA / 72kW
100kVA / 90kW
130kVA / 117kW
Input
Voltage (V): Frequency: Power Factor: Current Distortion (THDI): Bypass Overload:
60Hz ±5% <0.99 <5%
480V Core, 3 Wire + G (220V, 208V, 600V w/ Aux Transformer 4 Wire + G)
60Hz ±5%
60Hz ±5%
60Hz ±5%
60Hz ±5%
<0.99
<0.99
<0.99
<0.99
<5%
<5%
<5%
<5%
10x nominal current for 1 cycle
60Hz ±5% <0.99 <5%
Output
60
Output Voltage:
Frequency:
60Hz
Voltage Regulation:
Voltage Transient Response:
Voltage Recovery Time:
Voltage Distortion:
Inverter Overload:
Heat Rejection (BTU) @ 480V: 9248
60Hz 11560
480V Core, 3 Wire + G (220V, 208V, 600V w/ Aux Transformer 4 Wire + G)
60Hz
60Hz
60Hz
±-1% balanced load, ±-2.5% unbalanced load
±-5% for 100% step load, ±1% for loss or return of AC input
Within 1% of nominal within 1 cycle
<1% L-L and L-N for non-linear loads (<2% max)
150% for 1min, 125% for 10min
13872
18496
19607
60Hz 25489
Three Phase UPS
Overall Efficiency
Double Conversion Mode: Up to 94%
Up to 94%
Up to 94%
Up to 94%
Up to 94%
Up to 94%
Environment
Temperature Range: Elevation:
Operating UPS: 0 to 40°C / 32 to 104°F, Operating battery: 25°C / 77°F, Storage: -20 to 45°C / -4 to 113°F
1000m / 3281ft
1000m / 3281ft
1000m / 3281ft
1000m / 3281ft
1000m / 3281ft
1000m / 3281ft
Mechanical
Dimensions H x W x D (in/mm):
Weight (lb/kg):
882 / 400.06
882 / 400.06
75 x 28 x 33.42 / 1905 x 711.2 x 848.86
882 / 400.06
882 / 400.06
1146 / 519.81
1146 / 519.81
Matching Maintenance Bypass Dimensions H x W x D (in/mm):
75 x 28 x 33.42 / 1905 x 711.2 x 848.86
Transformer Cabinet Dimensions H x W x D (in/mm):
75 x 28 x 33.42 / 1905 x 711.2 x 848.86
Distribution Cabinet Dimensions H x W x D (in/mm):
75 x 42 x 33.42 / 1905 x 1066.8 x 848.86
Top Entry Cabinet Dimensions H x W x D (in/mm):
75 x 14 x 33.42 / 1905 x 355.6 x 484.86
Battery Cabinet Dimensions H x W x D (in/mm):
75 x 26 x 33.42 / 1905 x 660.4 x 848.86
Battery Cabinet Dimensions H x W x D (in/mm):
75 x 32 x 33.42 / 1905 x 812.8 x 848.86
Battery Cabinet Dimensions H x W x D (in/mm):
75 x 48 x 33.42 / 1905 x 1219.2 x 848.86
Parallel System Bypass Cabinet Dimensions H x W x D (in/mm):
(480V Only): 75 x 28 or 42 x 33.42 / 1905 x 711.2 or 1066.8 x 848.86
Galaxy PW Series
Three Phase UPS
> Parallel modules for capacity or redundancy > 0.9 output power factor > Modular design for easy upgrading or expansion > Field upgradable power output** > Generator friendly for low UPS to generator sizing ratios > Advanced battery management system
with automatic self testing
** on 100-200kVA modules only
Galaxy PW
Galaxy PW Series
Power Rating
150kVA / 135kW
180kVA / 162kW
200kVA / 180kW
225kVA / 202.5kW
Input Input Voltage (V): Frequency (Hz):
208, 480V Three phases, 3W + G 60Hz (±10%)
Nominal Input Current at 208V:
685A
600A
692A
692A
Input THDI:
<7.5% at 100% load
Output
Voltage: Power Factor:
208, 480V Three phases, 3W + G
61
>0.9
THDV (Linear Loads):
<1.5% Ph/Ph, <2% Ph/n
THDV (Non-linear Loads):
<2% Ph/Ph, <3% Ph/n
Voltage Transient Reponse:
±2% at 100% Step load
Three Phase UPS
Nominal Output Current at 208V:
418A
501A
556A
625A
Inverter Overload Capacity (A):
150% for 1 minute, 125% for 10 minutes
Bypass Bypass Instant Overload: Overall Efficiency System Efficiency: Full Load Heat Rejection: Environmental Operating Temperature: Storage Temperature: Humidity: Audible Nosie: Mechanical
57,301BTU
22 Times nominal current (1 cycle)
93% at 100% Load 68,762BTU
72,477BTU
UPS: 0 to 40°C / 32 to 104°F -20 to 45°C / -4 to 113°F 0 to 95% non-condensing 68dBA
93.5% at 100% Load 73,383BTU
Module Dimensions H x W x D (in/mm):
UPS Module Weight (lb/kg):
75 x 48 x 33 / 190 x 1219.2 x 838.2 3050/1383
G9000 Series
Three Phase UPS
> Next generation IGBT Technology > True on-line, double-conversion UPS > Parallel up to eight units > High efficiency for lower operational cost > Smallest footprint and highest power density in industry
G9000 Series
G9000 Series
Models
T90S3S08KS6XSN
T90S3S10S6XSN
T90S3S16S6XSN
T90S3S22KS6XSN
T90S3S30KS6XSN*
T90S3S50KS6XSN*
T90S3S75KS6XSN*
Specifications
Capacity:
80kVA/72kW
100kVA/90kW
160kVA/144kW 225kVA/202.5kW 300kVA/300kW 500kVA/500kW 750kVA/750kW
Topology:
True on-line, Double-conversion, Advanced multi-level IGBT technology
Input
Voltage:
480V, Three-phase, Three-wire + Ground/bypass input, 480V, Three-phase, Three-wire + ground
Voltage Range:
480V, -20% to 15% (384 to 552V without utilizing battery)
Power Factor:
>0.99
>0.99
>0.99
>0.99
>0.99
>0.99
>0.99
62
Current THD:
Frequency:
60Hz (±10%)
60Hz (±10%)
<3% @ 100% Load (no input filter required)
60Hz (±10%)
60Hz (±10%)
60Hz (±10%)
60Hz (±10%)
60Hz (±10%)
Output
Voltage:
480V, Three-phase, Three-wire + ground
Frequency:
60Hz, ±0.01% (in free-running mode)
Three Phase UPS
Voltage Regulation:
±1.0% (0.5% Typical)
Power Factor:
0.9 Lagging
0.9 Lagging
0.9 Lagging
0.9 Lagging
1.0 (Unity)
1.0 (Unity)
1.0 (Unity)
Power Factor Range:
0.9 Lagging to 0.95 Leading
Voltage THD:
<2% for linear load, <5% for non-linear load
Overload (Inverter):
125% for 2 minutes; 150% for 60 seconds
125% for 10 minutes; 150% for 60 seconds
Overload (Bypass):
1000% for one cycle
500% for one cycle
Parallel Capability:
4 units max
4 units max
4 units max
4 units max
8 units max
8 units max
8 units max
Battery
DC Link:
480Vdc
480Vdc
480Vdc
480Vdc
480Vdc
480Vdc
480Vdc
Environment
Temperature Range:
0 to 40°C / 32 to 104°F
Humidity:
5 to 95% non-condensing
Heat Rejection:
10771 BTUs/Hr 13463 BTUs/Hr 17821 BTUs/Hr 25060 BTUs/Hr 30709 BTUs/Hr 51182 BTUs/Hr 79200 BTUs/Hr
Efficiency (Full Load):
95.8%
95.8%
96.5%
96.5%
97%
97%
97%
Efficiency (20% Load):
92.5%
92.5%
94.7%
94.9%
95.8%
95.8%
95.8%
Elevation:
2250m/7380ft max without derating
Audible Noise:
70dBA @ 1m
70dBA @ 1m
70dBA @ 1m
70dBA @ 1m
73dBA @ 1m
73dBA @ 1m
73dBA @ 1m
Mechanical
Dimensions H x W x D (in/mm):
Weight (lb/kg): Features
80.6 x 27.6 x 32.8 / 2049 x 700 x 832
855 / 388
855 / 388
80.6 x 35.4 x 32.8 / 2047 x 900 x 832
1160 / 526
1230 / 558
80.7 x 86.7 x 33 / 2050 x 2200 x 838
2200 / 1000
3300 / 1500
80.7 x 102.3 x 33 / 2050 x 2600 x 838
4255 / 1930
Digital Signal Processor (DSP) Control, Fully digital IGBT converter and inverter, High efficiency over wide load range, transformer-less design, N+1 and N+N (Up to eight in parallel) capability, Dual-input feed, Electronic battery isolation, RS232 and dry contact interface, small footprint, lightweight design
Standards UL 1778, CUL, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), FCC Class A, Article 47, Part 15.B
Warranty 3 year onsite (Optional 2 year extended warranty)
* Preliminary specifications only; subject to change without notice
Symmetra PX
Three Phase UPS
> Scalable from 10 to 100kW > Modular components simplify future
expansion as your load grows > N+1 redundant up to 90kW > Hot swappable power, battery and breaker modules > Space saving high density design
Symmetra PX
Power Rating
100kW
Mains Input (Normal Operation)
Grid System:
3 Phases + neutral + ground
Voltage Range (full load): 177 to 239V
Frequency Range:
40 to 70Hz
PF:
>0.99% @ >25% Load
I thd (full load):
<5%
Nominal Input Current:
302A @ 208A
Maximum Input Current:
332A (Nominal Vin, 10% charging batteries)
Input Current Limit:
360A
Max. Input Short-Circuit Level: 30kA
Protection:
Backfeed contactor
Bypass Input (Bypass Operation)
Grid System:
3 Phases + neutral + ground
Nominal Input (V):
208V
Voltage Range:
±10%
Frequency (nominal):
50/60Hz
Frequency (range):
±0.1Hz, ±3Hz, ±10Hz (user selectable)
Nominal Input Current:
278A @ 278V
Max. Overload Input Current: 347A
Output
Power Rating:
100kW
Grid System:
3 Phases + neutral + ground
Nominal Output (V):
208V L-L
Nominal Output Current:
278A @ 208V
Max. Battery Operation Time: Unlimited
Frequency Regulation:
50/60Hz Bypass synchronized, 50/60Hz ±0.1% free running
Sync. Slew Rate:
Programmable to 0.25, 0.5, 1, 2, 4, 6Hz/sec
Overload:
150% for 30 seconds (Normal and battery operation)
V thd:
<2% @ 100% Resistive load, <6.5% @ 100% SMPS load
Load PF:
From 0.5 leading to 0.5 lagging without any derating
Mechanical
Dimensions H x W x D (in/mm)
79.1 x 23.6 x 42.1 / 2011 x 600 x 1070
Net Weight (lb/kg): Shipping Weight (lb/kg): UPS Maximum Capacity 10kW Power Modules: Battery Modules: Power Distribution Modules: Regulatory Standards:
716 / 324 789 / 357
10 9 24
UL1778 second edition, FCC Part 15, CE
Symmetra PX
63
Three Phase UPS
64
Surge Protection
AlphaTVSSTM
Transient Voltage Surge Suppression
> Safe operation no explosions, no smoke, no fumes and no flames
> Isolates the load from damaging transients and other abnormal line conditions
> Lifetime of 20+ years > NEMA 4X rated enclosure > UL recognized surge suppression
component (UL 1449 3rd edition)
The StrikesorbTM surge suppression module incorporates state-of-the-art developments in metal oxide
technology to provide superior protection throughout its long service life. It has been designed to
withstand repeated surges, providing cost-effective and maintenance-free operation in harsh
environments. Strikesorb is the only UL (1449 3nd edition) recognized surge protection module rated for
safe operation without the use of additional internal fuses. This technology, combined with the capability
to be connected directly on the power lines (feed-through connection) make Strikesorb the most reliable
surge protection device available.
65
Models
ATVSS-2-120 ATVSS-3-120/240 ATVSS-4-120/208 ATVSS-2-240 ATVSS-4-220/380
Surge Suppression
Electrical
Nominal Operation Voltage: 120V
Maximum Continuous Operating Voltage:
150V
Vref (Peak) @ 5mA AC (Peak): 263V
Operating Frequency Range: 25 to 500Hz
Leakage Current at Vn:
0.30mA
Surge Protection Levels
Surge Voltage Rating:
500V
Response Time:
<1ns
Maximum Surge Current: 140kA
Maximum Lightning Current: 7.5kA
Let through Voltage
For Surge Current 10kA (8/20): 435V
Enclosure
IP65-NEMA4
120V/240V 150V 263V 25 to 500Hz 0.30mA
500V <1ns 140kA 7.5kA
435V IP65-NEMA4
120V/208V 150V 263V 25 to 500Hz 0.30mA
500V <1ns 140kA 7.5kA
435V IP65-NEMA4
240V 300V 526V 25 to 500Hz 0.35mA
800V <1ns 140kA 7.5kA
895V IP65-NEMA4
220V/380V 480V 833V 25 to 500Hz 0.45mA
1500V <1ns 140kA 7.5kA
1355V IP65-NEMA4
Dimensions H x W x D (in/mm):
8 x 6 x 6 /
12 x 10 x 6 /
12 x 10 x 6 /
8 x 6 x 6 /
12 x 10 x 6 /
203 x 152 x 152 305 x 254 x 152 305 x 254 x 152 203 x 152 x 152 305 x 254 x 152
Operating Temperature:
-40 to 85°C / -40 to 185°F
Strikesorb Module
Large Thermal Capacity Electrodes: Absorb heat generated during surges and decelerate MOV ageing
Strong Aluminum Housing: Prevents explosions
1500+ Pounds of Pressure: Results in very low dynamic resistance
No Fuel to Burn: Prevents fire and smoke emission
Single, Distribution-Grade Varistor: Contributes to reliability, long lifetime, avoiding parallel connected MOVs
Coaxial symmetry and uniform surge current distribution
66
Alpha Technologies Services
Total Power Solutions
> Complete System Solutions
Systems engineered to work together are more efficient and more reliable. Alpha provides you complete systems to serve every point of your cable broadband network, as well as options for integrating renewable energy or Hybrid Power Systems into your operations. From power supplies and batteries to solar modules and turn-key buildings, our powering systems are fully integrated for maximum reliability and carefully engineered to minimize your total cost of ownership.
> Installation and Construction Services
With a national network of contractors, project managers and Alpha technicians, we can provide turnkey solutions for outside plant, headend, telecommunications, industrial and renewable energy applications. We work to combine your small-, medium- and large-scale projects with the necessary installation resources. Our complete installation and facility construction services include structure engineering, right-of-way and easement procurement, site preparation, equipment installation, utility hook-up coordination, system turn-up and system testing.
> Repairs, Refurbishments and Factory Upgrades
Featuring an on-site CableUPS® inverter module exchange, our goal is to maintain network uptime
providing you access to quick and stress-free system repairs and refurbishment options for all of your
network equipment. Our repair and development laboratories are designed for product repair,
refurbishment and improvement of all Alpha and third-party equipment including cable power supplies,
RF line gear, Headend, UPS fiber and test equipment.
67
Total Power Solutions
> On-Site Service
With Alpha Technologies Services repair depots established across North America, we provide convenient pick-up and drop-off services. In addition to our scheduled driving routes, we offer preventive maintenance programs and emergency response capabilities where trained Alpha field technicians can be dispatched 24 hours a day in specially equipped and stocked service vehicles.
> Technical Support and Customer Service
Because your networks are operating 24 hours a day, we offer you around-the-clock telephone technical support and web-based tools to generate RMAs and track open repairs, history and billing.
> Our ISO 14001:2004 Environmental Management System
Alpha strives to continually improve our Environmental Management System by benchmarking opportunities for improving our performance and demonstrating conformity to system requirements.
We are committed to be industry and community leaders for sustainable business processes by meeting legal/other requirements, communicating with internal/external customers and protecting our environment through the implementation of sustainable business processes and preventing pollution from occurring through our product design and daily practices.
System Solutions
> Fully integrated powering systems to protect your network > Next generation power solutions for emerging topologies > Power conditioning and back-up from Headend to home > Complete line of system accessories to maximize
reliability, efficiency and system runtime
We specialize in engineering complete network power systems committed to reliability, OpEx savings and environmental sustainability.
We understand that systems engineered to work together are
more efficient and more reliable. As a result, we provide you
complete systems serving every point of your cable broadband
network, as well as options for integrating renewable energy or
hybrid power systems into your operations. From power supplies
and batteries to solar modules and turn-key buildings, our
powering systems are fully integrated for maximum reliability and
68
carefully engineered to minimize your total cost of ownership.
We are proud to have served the telecommunications industry for more than 35 years, and we invite you to learn how we can strengthen your entire network with Alpha Power.
Our RFoG and GPON Fiber Power Systems provide the same reliability as our HFC systems with added features including outdoor access to batteries and multiple configuration options.
Total Power Solutions
High performance outside plant systems include multiple power supply, enclosure and battery options, as well as a full line of system accessories for climate-specific applications to provide extended runtimes and protect your powering investments.
Heavy-duty reinforced concrete equipment structures can be outfitted to your custom need, including back-up power, power conditioning, climate control, security and
communications, as well as on-site calibration and preventive maintenance programs.
Installation and Construction Services
> Complete design, engineering, permitting, construction and commissioning > Headends, equipment shelters and other critical facilities > Turnkey installation, turn-up and test services > Grid-Tied and Off-Grid Renewable Energy Systems
69
Alpha project managers will complete all site surveys, geological testing, engineering drawings and building permit applications. Our nationwide network of contractors and project managers then coordinate the entire implementation on-site, from concept to commissioning.
Total Power Solutions
Grid-Tied Solar Power can help minimize operating expenses and reduce your carbon footprint. (153kW Grid-Tied system in Phoenix, AZ)
Off-Grid Solar and Hybrid Power Systems can provide the necessary redundancy for critical loads and help extend network signal to remote areas. (11kW Off-Grid Hybrid Power System in Southwest Colorado)
Repairs and Refurbishments
Full Service Repair for All Broadband Equipment > 40 Years experience in RF Line gear, Headend, Fiber and Test Equipment Repair > All RF Repairs are certified using a fully loaded Digital QAM Spectrum Power Supply Refurbishments and Factory Upgrades > On-site Power Supply Inverter Module Exchange offers zero turn around time > Refurbishment features include:
· Replacement of all Capacitors · 2 or 3 year warranty of Complete Power Supply · Implementation of engineering changes to improve reliability > Options to upgrade to Embedded DOCSIS status monitoring
70
Total Power Solutions
Automated test equipment is used to efficiently verify all functions of refurbished power supplies.
Refurbished equipment is put through a rigorous burn-in cycle to identify marginal components.
Customer-requested and factory-recommended improvements are implemented at time of service.
Extensive experience repairing and refurbishing all telecommunications network equipment including Cable Power Supplies, RF Line gear, Headend, Fiber and Test Equipment.
Customer Service
On-site Personal Service > Free pick up and delivery on National Route Service > Reduced freight costs for best cost service Web Based Online Management Tools > Create RMA requests > Track open repairs, repair history and billing history
Track all aspects of your repairs online or call one of our customer service representatives.
Routine maintenance programs ensure system reliability. Burnaby, BC
Bellingham, WA
71
24/7 phone support available when you need it.
Mississauga, ON
Total Power Solutions
Phoenix, AZ
Pennsauken, NJ
Dallas, TX
Suwanee, GA
Aiken, SC
Alpha Technologies Service Depot Locations across North America offer convenient pick-up and drop off services.
Alpha Building Systems
Powering Solutions from Concept to Activation
Solid Building Construction > Single and multi-story building designs > Heavy duty reinforced concrete equipment structures meet most stringent wind and seismic requirements
· Vandal resistant, high security and maintenance-free · Durable washed and sealed aggregate exterior · Other finishing options available > Lighter-weight, composite-panel equipment structures are ideal for rooftop applications or temporary installations · Versatile shelters for difficult site pavements · Can be installed and equipped in hours · Durable stucco-embossed white enamel
72
Total Power Solutions
Alpha project managers will complete all site surveys, geological testing, engineering drawings and building permit application.
Heavy-duty reinforced concrete equipment structures are vandal-resistant, high security and virtually maintenance-free.
Lighter-weight composite-panel equipment structures are also available.
Site completion including landscaping, fencing and security.
Alpha Building Systems
Powering Solutions from Concept to Activation
Turnkey Solution For Any Communications Powering Application > Site survey and geological testing > Engineering drawings > Building permits > On-site construction > Careful shipping and off-loading > Site completion including landscaping, fencing and security Interior Finishing to Meet Every Requirement > Custom wall framing completed at the factory > Commercial grade tile flooring > White laminated 7/16" panelling > Fire rated to necessary specifications > Electrical system capabilities up to 1200Amps > Environmental controls
73
Pre-wired and equipment ready.
Electrical system capabilities up to 1200Amps.
Total Power Solutions
Custom wall framing allows units to be pre-wired and equipment-ready upon arrival.
Commercial grade tile flooring and durable white laminated 7/16" wall panelling.
12V FlexPoint AX Series Indoor/Outdoor Hybrid Solution
Operator Accessible Battery
12V FlexPoint AX Series Full Outdoor Solution
Operator Accessible
Home Converter
74
Indoor
10.5 to 14Vdc
5-24 Watts
BBPS
Typical Output ONT
Power & Remote Alarms
11.6 to 16Vdc Three Conductor Low Voltage DC
Ground Rod
Utility Meter and Meter Base
AC to DC Power Converter
Fiber Voice, Video and Data Enters Through Wall
10.5 to 14Vdc
5-24 Watts
BBPS
Typical Output ONT
11.6 to 16Vdc
Three Conductor Low Voltage DC
Power & Remote Alarms
Fiber
Voice, Video and Data Enters Through Wall
Ground Rod
48V FlexNet MPS Series Indoor Solution
Operator Accessible Battery
48V FlexNet FMPS Series Indoor Solution
Operator Accessible Battery
Total Power Solutions
Indoor
42 to 56Vdc
50 Watts
MPS
Typical Output ONT
Power & Remote Alarms
90 to 132Vac
Ground Rod
Fiber
Voice, Video and Data
FMPS
Indoor
90 to 320Vac
42 to 58Vdc 150 Watts ONT Typical Output
Power & Remote Alarms
ONT
Ground Rod
Fiber Voice, Video and Data
Fiber Voice, Video and Data
Fiber Power
lpha Technologies offers a complete portfolio of fiber-to-the-home powering options with the FlexPointTM line of 12Vdc single-family unit solutions (SFU) and the FlexNetTM line of 48Vdc multiple dwelling unit (MDU) and small office home office (SOHO) power supplies. All of Alpha's powering solutions are engineered to perform reliably in the most demanding environmental conditions while optimizing battery life and performance.
12Vdc Solutions
> FlexPoint 1207-F For RFoG Applications
The indoor FlexPoint 1207, 7 Watt, 12Vdc standby power supply is an environmentally-hardened standby power supply intended to be placed indoor or outdoor in sheltered locations. Its compact size allows placement in the most densely populated structured medial enclosures. The FP1207 includes a unique emergency battery reserve function that provides greater lifeline service availability by preserving 25% of the usable battery capacity for user initiated emergency telephone calls. User interfaces include visual status indicators, audible alarms, silence alarm button and an auxiliary 12Vdc power input port allowing additional battery capacity to be added for longer standby runtimes.
> Integrated Fiber Enclosure (IFE)
The FlexPoint IFE-A30-1 Integrated Fiber Enclosure from Alpha Technologies provides a reliable, compact and cost-effective means to simplify RFoG deployment. The enclosure contains a fiber management system, an 8-way coaxial splitter and a FlexPoint power supply with provisions for installing RFoG devices. The door-mounted FlexPoint power supply provides 20 hours of battery backup runtime. The enclosure is lockable, making this system a secure and convenient solution for Micro Node management.
> FlexPoint AX Series For EPON/GPON and RFoG
75
The indoor/outdoor FlexPoint AX Series, 30 Watt, 12Vdc fiber-to-the-premises optical network terminal
(ONT) power supply system, provides network operators a highly reliable, scalable set of solutions
for full or partial outdoor RFoG and PON installations. This system provides service technicians 24/7
access to the power system. FlexPoint AX home converters and power ring converters provide
12Vdc support for indoor and outdoor applications not requiring standby power. As services expand
to include voice or critical data support, 7.2 or 17Ah battery backup power supplies (BBPS) can be
easily added.
Fiber Power Systems
48Vdc Solutions
> FlexNet MPS48-7 Series
Alpha extends its family of FlexNet element powering solutions to include the MPS48-7F and MPS48-7T multipurpose power supplies. The MPS48-7F supports fiber-to-the-home applications including MDU, MTU and SBU ONT products. The MPS48-7T supports critical network communication loads. These units are indoor or outdoor, wall or pole mounted microprocessor controlled UPS system providing 50 Watts of 48Vdc. The input is powered from 120, 240 or higher AC voltages with an optional step-down transformer. A 48Vdc string of standard 7.2Ah maintenance free sealed lead acid batteries provide standby power.
> FlexNet FMPS
The FTTx Multipurpose Power Supply (FMPS) is an indoor/outdoor system providing 150W of 48Vdc power to MDU and SOHO optical network terminals. The FlexNet FMPS is an environmentally hardened wall mount enclosure system with dual ONT connections supported with one or two 48Vdc strings of 7.2Ah batteries. The system includes one or two parallel outputs and alarm connections, supporting distances of up to 100ft between the FMPS and ONT, allowing the FMPS to be located close to existing power outlets.
> FlexNet FiberUPS®
The FlexNet FiberUPS is a 300 Watts, 48Vdc battery backup power module supporting a variety of indoor and outdoor applications. With pole, wall or ground mount enclosure options, the FlexNet FiberUPS will keep field distributed electronics up and running during power disturbances and outages.
> PMR and GMR Series
The PMR and GMR series is comprised of two sizes of pole mount and two sizes of ground mount factory configured and regulatory certified rainproof enclosure systems. PMR and GMR are highly configurable systems including 19" adjustable or pullout swing racks, AC service entrance and distribution, surge suppression, fiber management, power bypass cabling, FiberUPS DC power supply, DC distribution and 50Ah AlphaCellTM batteries.
FlexPointTM 12Vdc
RFoG Battery Back Up Power Supplies
> Supports expanding services > Indoor and outdoor applications > 24-Hour operational access to outdoor solutions > Safe, low-voltage distribution
1207-F 7W RFoG System with Primary and Standby Power
Specifications
Input: Output Voltage: Output Power: Number of Batteries:
85 to 264Vac (45-66Hz) 10.5 to 14.4Vdc 7 Watts One 7.2Ah battery
Battery Backup Runtime:
Approx. ~ 20hrs w/ 3.5W load, Approx. ~ 12hrs w/ 7W load
Status Indicators: Dimensions H x W x D (in/mm):
Visual and audible 7.75 x 8.75 x 3 / 177 x 224 x 76.2
Unit
Weight (lb/kg):
76
Battery
1.3 / 0.59 5.7 / 2.6
Backup Power for Business Service RFoG Deployment
Specifications
Battery Backup Runtime:
Approx. ~ 20hrs w/ 3.5W load, Approx. ~ 12hrs w/ 7W load
Coaxial Management: Fiber Management: Features: Dimensions H x W x D (in/mm): Weight (lb/kg):
8-Way Coax Splitter Fiber wrap spool 12-fiber splice tray Lockable, secure indoor enclosure 12 x 12 x 8 / 304.8 x 304.8 x 203.2 8 / 3.6
Fiber Power Systems
AX 30W RFoG System with Primary and Standby Power
Specifications
Input: Output Voltage: Output Power: Mounting: BBPS-F Dimensions H x W x D (in/mm): Weight (lb/kg):
85 to 132Vac 10.5 to 14.4 Vdc 30 Watts Partial outdoor 7.75 x 8.75 x 3 / 177 x 224 x 76.2 3 / 1.4
Home Converter Dimensions H x W x D (in/mm):
8.5 x 3 x 2 / 21.5 x 7.6 x 5
Home Converter Weight (lb/kg):
1 /.45
Application
AX RFoG Indoor Powering - UPS
Operational Temperature Indoor Range: -40 to 113°F (-40 to 45°C Operational Temperature Outdoor Range: -40 to 113°F (-40 to 45°C)
RFoG Device
AX HC/BBPS-F
FPR1207-F7.2 -- Indoor 12V 7W Power System
Integrated Fiber Enclosure (IFE) -- For RFoG Deployment
AX HC/BBPS-F -- Outdoor 12V 30W Power System
Home Converter
BBPS-F
FlexPointTM AX 12Vdc
PON Battery Back Up Power Supplies
> Full or partial outdoor configurations > Outdoor rated BBPS including
battery for 24/7 availability > Utility meter base provides most reliable
source of AC power at home
FlexPoint AX Series
AX 30W EPON/GPON System with and without Standby Power
Specifications
AX PC/BBPS -- Outdoor 12V 30W System
Input:
170 to 264Vac
Output Voltage:
10.5 to 14.4Vdc
Output Power:
30 Watts
Mounting:
Outdoor
BBPS Dimensions H x W x D (in/mm): 7.75 x 8.75 x 3 / 177 x 224 x 76.2
Weight (lb/kg):
3 / 1.4
Power-Ring Dimensions H x Dia (in/mm): 4.75 x 7 / 120 x 178
Power-Ring Weight (lb/kg);
1.5 / 0.68
Power-Ring
Power Converter Dimensions H x W x D (in/mm):
Power Converter Weight (lb/kg):
8 x 2 x 2 / 209 x 51 x 51 0.7 / 0.32
Home Converter
BBPS
77
Applications
AX PON Outdoor Powering Non-UPS Operational Temperature Outdoor Range: -40 to 45°C / -40 to 113°F
AX PON Outdoor Powering UPS Operational Temperature Outdoor Range: -40 to 45°C / -40 to 113°F
Fiber Power Systems
AX 30W EPON/GPON System with and without Standby Power
Specifications
Input:
85 to 132Vac
Output Voltage:
10.5 to 14.4Vac
Output Power:
30 Watts
Mounting:
Partial outdoor
BBPS Dimensions H x W x D (in/mm): 7.75 x 8.75 x 3 / 177 x 224 x 76.2
Weight (lb/kg):
3 / 1.4
HomeConverterDimensionsHxWxD(in/mm): 8.5 x 3 x 2 / 21.5 x 7.6 x 5
Home Converter Weight (lb/kg):
1 /.45
Applications
AX PON Indoor Powering Non-UPS
Operational Temperature Range: -40 to 45°C / -40 to 113°F
AX HC/BBPS -- Indoor / Outdoor 12V 30W Power System
Home Converter
BBPS
AX PON Indoor Powering UPS
Operational Temperature Indoor Range: -40 to 45°C / -40 to 113°F Operational Temperature Outdoor Range: -40 to 45°C / -40 to 113°F
FlexNetTM 48Vdc 50W
Battery Back Up Power Supplies
> Rugged outdoor or indoor 48Vdc 50W wall or pole mount UPS > Aesthetically pleasing, minimizes presence in public locations > Optional compensated battery charging for optimum battery life > Local and remote status monitoring and reporting
FlexNet FMPS48-7 Series
Specifications
Input: Output Voltage: Output Power: Output Interface Module-F: Output Interface Module-T:
Unit Dimensions H x W x D (in/mm):
Weight (lb/kg):
System Dimensions
H x W x D (in/mm):
78
Weight (lb/kg):
Number of Batteries:
Runtime:
90 to 132 or 180 to 264Vac 42 to 56Vdx 50 Watts continuous Packet Cable Alarms Dry Contact Alarms
4.18 x 8.75 x 2.12 / 106.17 x 222.25 x 53.84
1.5 / 0.68
17.5 x 12.75 x 5.25 / 445 x 324 x 133
11 / 4.9, 34.6 / 15.7 w/ batteries
Four 7.2Ah Valve Regulated Lead Acid (VRLA)
18 Hours @ 20W load; 8 Hours @ 40W load
FlexNet MPS48-7 Series
FN50-48-7F -- With Output Interface Module-F
FN50-48-7T -- With Output Interface Module-T
Fiber Power Systems
FlexNetTM 48Vdc 150W
Battery Back Up Power Supplies
> FTTP outdoor UPS for Multiple Dwelling, Multiple Tenant and Small Business Unit applications
> Battery management performs periodic battery capacity testing and status reporting to the ONT and customer
> Battery heater option provides extended runtime for applications in cold weather conditions
> Status indicators and audible alarm provide local reporting
FlexNet FMPS
Specifications Input: Output Voltage: Output Power: FMPS Dimensions H x W x D (in/mm): Weight (lb/kg):
Number of Batteries:
90 to 320Vac 42 to 58Vdc 150 Watts continuous
23.75 x 14 x 5.5 / 603.25 x 355.6 x 139.7
25 / 11.3
Four or eight 7.2Ah Valve Regulated Lead Acid (VRLA)
FlexNet FMPS
FlexNetTM 48Vdc 300W
Battery Back Up Power Supplies
> 300W 48Vdc UPS for outdoor or indoor applications > Power modules can be used in a variety of Alpha enclosures > Temperature compensated battery
charging for extended battery life > Flexible cabinet mounting > Visual and electrical indicators for on-site and remote reporting
FlexNet ELPM-300
FlexNet ELPM-300
Specifications Input: Frequency: Output Voltage: Output Power: Dimensions H x W x D (in/mm): Weight (lb/kg): Number of Batteries: Approx. Backup Time:
85 to 170 or 132 to 264Vac selectable 50 or 60Hz 42 to 54Vdc 300 Watts 6 x 10.1 x 3.25 / 152 x 256.5 x 82.6 10 / 4.5 Four 12Vdc 50Ah (85GXL) 8 Hours @ 275W load
LPE and ELPM-300 -- 300W for MDUs, Dark Spots and Business Parks
LPE and FlexNet ELPM-300
Specifications
79
Enclosure Dimensions H x W x D (in/mm): 26 x 16.5 x 12 / 661 x 420 x 305
Enclosure Weight (lb/kg):
25 / 11.3
Material:
Exterior Powdercoated aluminum
Number of Batteries:
Four 12Vdc 17Ah
Door and Lid Seal: Approx. Backup Time:
Poron gasketing 4 Hours at 250W load
Fiber Power Systems
PMR and GMR Series
Specifications
PMR-S1 Dimensions H x W x D (in/mm): 32.2 x 26 x 19.25 / 818 x 660 x 489
Weight (lb/kg):
40 / 18
GMR-S1 Dimensions H x W x D (in/mm): 31 x 27.5 x 20 / 787 x 699 x 508
Weight (lb/kg):
49 / 22
PMR-S2 Dimensions H x W x D (in/mm): 37 x 30 x 19.25 / 940 x 762 x 489
Weight (lb/kg):
47 / 21
GMR-S2 Dimensions H x W x D (in/mm): 38 x 31 x 20 / 965 x 787 x 508
Weight (lb/kg):
63 / 29
Number of Batteries:
Four 12Vdc 50Ah (85GXL)
Approx. Backup Time:
8 Hours at 275W load
Enclosure Mounting and Door - PMR Series:
Galvanized steel brackets for wood, and concrete pole mount and wall mount
PMR and GMR Series -- 300W for field deployment of TTx Optical Line Terminal (ONT)
Enclosure Mounting and Door - GMR Series: Fiber Strain Relief Tie Bar Optional:
Splice Tray:
Fiber Management Panel:
Precast polymer concrete pad or PS-6/PS-6XL pedestal systems
19" mounting provides ability to strain relief fiber cable plugged into the front of communications equipment
Splice Tray Kit (12 count), includes Splice tray with Elastomer Splice Block, Felt Tape, Tie Wraps, Cover and Recording Label
Provides fiber slack storage and secures a splice tray using a Velcro strap. Tie wrap slots on sides permit securing fiber cables to panel
PMR and GMR Series
Pole and Ground Mount Enclosures
> Supports field deployment of FTTx Optical Line Terminals (OLT)
> FlexNetTM 300W UPS provides over 10hrs of runtime
> Thermostatically controlled 48 or
120Vdc fan and heater options
GMR
> Adjustable 19" EIA equipment racks
> All aluminum construction, durable powdercoat finish, stainless steel hardware
PMR
PMR and GMR Series
Mechanical
Fiber Management Options
Models: Mounting: Dimensions
PMR-S1 Pole 32.2 x 26 x 19.25
GMR-S1 Ground 31 x 27.5 x 20 /
PMR-S2 Pole
GMR-S2 Ground
37 x 30 x 19.25 / 38 x 31 x 20 /
Fiber Strain Relief Tie Bar (Optional):
19" mounting provides ability to strain relief fiber cable plugged into the front of communications equipment
HxWxD(in/mm): /818x660x489 787 x 699 x 508 940x762x489 965 x 787 x 508
Weight (lb/kg): 40/18
49/22
47/21
63/29
Splice Tray (Optional):
Splice Tray Kit (12 count), includes Splice tray with Elastomer Splice Block, Felt Tape, Tie Wraps, Cover and Recording Label
Material:
Powdercoated aluminum
80
Vent Screen
Mesh fabric with .005 x .005 / .12 x .12
(in/mm):
opening size to minimize snow, water and dust ingress
Fiber Management Panel (Optional):
Provides fiber slack storage and secures a splice tray using a Velcro strap. Tie wrap slots on sides permit securing fiber cables to panel
Door and Lid Seal:
Poron gasketing
Power Supply and Batteries
Color: Tamper Switch:
Gray or white (Custom colors available) Optional
Model:
FlexNet 300 -- 300W 48Vdc output with 48V battery bus with 19" reversible mounting bracket options
Fiber Power Enclosures
Grounding Internal Ground Bar: Safety Ground: Lid: Door(s)
PMR Series: GMR Series: Enclosure Mounting
PMR Series:
Five usable lugs Adjacent to AC outlets (Optional stainless steel ground stud) Removable (PMR Series includes lanyard)
Hinged removable with stainless steel spring latch and door open prop rod Removable lift-off front and rear door
Galvanized steel brackets for wood, and concrete pole-mount and wall mount
Batteries:
48Vdc string of 85 GXL (50Ah) positioned on ends (negative terminal side down) with battery retaining bar option
Battery Cable Kit: Battery Heater:
Fused Optional
AC Service:
External 70A rainproof SUSE rated breaker box with internal 120Vac 20A receptacles
Regulatory:
CSA
Notes: 1. Additional rack space capacity if batteries are not installed 2. Runtime of 10hrs based on 212W load and new batteries discharged to 1.75VPC
at 25°C/77°F
GMR Series:
Precast polymer concrete pad or PS-6/PS-6XL pedestal systems
Thermal Management Cooling: Heating: Internal Mounting Rails
120Vac and 48Vdc fan options 120Vac and 48Vdc heater options
Rack Mounting: Grounding: Adjustment:
EIA 19" mounting rails using Tinnerman mounting clips
Rails grounded to chassis
1" increments over 6" when batteries are not installed
Enclosure Environment Rating
Equipment Mounting Area:
Designed to IP X5 per IEC 529 Dust ingress controlled by screen opening IP X5 applies to the equipment mounting area The service entrance is rated 3R
Shown with FTTX actives installed, 19" swing rack, 50Ah AlphaCell batteries, AC and DC distribution, Fiber management and 300W power supply
Radium MiniBay
Environmentally Controlled Enclosures
> Scalable, environmentally controlled enclosure system > Fully integrated system and agency certified > Ideal for remote optical transition applications > High capacity 24 or 48Vdc 3000BTU
(879W) DC powered air conditioner > Natural gas or propane DC generator system
supports critical communications > Reduces operational and recurring costs
Radium MiniBay
The Radium MiniBay is a modular, highly configurable Telecom
Fans and Filters
grade enclosure system including fully scalable power to
The most basic thermal management system supporting the MiniBay utilizes
4,000W and 1240Ah of battery capacity with ample rack space
conformal-coated, variable speed and alarm monitored fans with electrostatic air filters providing up to 500W thermal dissipation. This configuration has a NEMA
for communications electronics. The MiniBay system benefits
3R rating
from more than 30 years of Alpha's Outside Plant (OSP)
· Variable speed controlled DC fans continue to operate during a utility outage · Conformal-coated fans
powering experience. The MiniBay integrates Alpha's
· Electrostatic and washable air filters · Field replaceable fans
comprehensive line of power solutions for today's complex Hub and environmentally controlled enclosure requirements including Alpha's AC UPS, CordexTM rectifiers, and the
Heat Exchanger
An airtight rear door and a heat exchanger equipped hinged front door providing
81
over 500W thermal dissipation. With a 500W load, the internal ambient
AlphaGenTM series of telephony grade DC generators. Features
temperature will not exceed 9.4 to 2.7°C / 15 to 27°F above external ambient. With a 250W load, the internal ambient temperature will not exceed 7°C / 12.6°F
for the Radium MiniBay include: front and rear accessible 19"
above external ambient. This configuration as a NEMA 4x rating
Fiber Power Enclosures
or 23" equipment racks providing up to 46 rack mount spaces,
· Heat exchanger heat pipe technology provides efficient thermal transfer · Minimizes internal temperature rise above external ambient
durable powdercoated aluminum construction, battery storage
· Variable speed controlled DC fans continue to operate during a utility outage · Field replaceable fans
modules isolated from the equipment section each supporting up to four 155Ah batteries for a 19A load for 8hrs. Typical CSA-NRTL marked configurations include integrated AC
DC Air Conditioner
For applications requiring the most reliable below cooling and dehumidifying system for supporting seamless performance through extended utility outages.
service entrance, surge protection, AC distribution, DC
Cooling capacity 878W dissipated at 43°C / 109.4°F outdoor ambient allowing a Maximum* internal ambient of 40°C / 104°F
distribution, standby generator interface, heat exchanger, fan/filter or air conditioner thermal management, rectifiers
· Variable speed brushless motor 24/48Vdc compressor system assures optimum efficiency over the full range of thermal loading and ambient temperatures
· 3000BTU @ 43°C / 110°F rating
or AC UPS equipment.
· Redundant conformal-coated fans have >50000hrs of life and low voltage disconnect circuitry
Standards Environmental Rating: Seismic Rating: Design Standards:
NEMA 3R when configured with door mounted fans and filter system. NEMA 4X when configured with heat exchanger or air conditioning system
Consult factory. A seismic rating is based on a set system configuration with defined mounting locations and equipment types
Following NEC and Telcordia Technologies (Bellcore) GR-487, GR-63 and GR-1089 guidelines
AC Air Conditioner
Ideal for applications requiring cooling and dehumidifying with little or no standby runtime performance. Cooling capacity 146W dissipated at 43°C / 109.4°F outdoor ambient allowing a Maximum internal ambient of 40°C / 104°F · 5000BTUBTU @ 43°C / 110°F rating · Washable electrostatic filters · 240Vac * Reducing the internal dissipated heat load reduces internal ambient
Compliance:
Third party approval from National Recognized Testing Laboratory (NRTL)
Material:
High strength corrosion resistant aluminum
Finish:
Almond color powdercoat finish
Weight and Dimensions
Weight (lb/kg): Dimensions H x W x D (in/mm):
Equipment Enclosure: 195 / 88.5
44 x 30 x 32 / 1117.6 x 762 x 812.8
Battery Storage Module: 130 / 59
14 x 30 x 32 / 355.6 x 762 x 812.8
Riser Module:
102 / 46.3
14 x 30 x 32 / 355.6 x 762 x 812.8
Side Chamber SC1:
100 / 45.4
72 x 32 x 12 / 1828.8 x 812.8 x 304.8
Side Chamber SC2:
89 / 40.4
72 x 32 x 12 / 1828.8 x 812.8 x 304.8
48Vdc air conditioner
Battery drawer
Rack space for customer supplied equipment RSM 48/10 Rectifiers with distribution
MiniBay with Fiber Management
82
Fiber Power Enclosures
Alpha Enclosures
Tempest brings convenience, strength and versatility to outdoor power system enclosures. The fully integrated modular design combines AC, DC and backup battery power into one space. All are designed to serve ASDL, TI and fiber optic transmission system (FOTS) facility applications.
> Tempest Te25 Series
The Te25 is designed to meet the requirements for service providers with remote outdoor or secure indoor applications. Welded aluminum construction provides structural integrity that will withstand seismic events and harsh weather conditions.
> Tempest Te25xh Series
Tempest brings convenience and versatility to outdoor power system enclosures. In addition to ADSL, TI, and fiber optic transmission system (FOTS) facility applications, the Te25xh is designed to meet the requirements for service providers with many other remote outdoor or secure indoor applications.
Welded aluminum construction provides structural integrity that will withstand seismic events and harsh weather conditions. The Te25xh is designed for remote applications and can be pole or pedestal mounted. It is also available in a secure indoor rack or wall mount configuration.
> Tempest Te15
The Tempest Te15's compact footprint is an ideal, economical solution for microwave, fiber and E911 applications. The optional integrated solar shield, heater, and air conditioner protect the batteries and equipment from severe environmental conditions. Fully secure pad-lockable doors and intrusion alarms keep equipment safe and secure.
> Tempest Te17
Tempest brings convenience and versatility to outdoor power system enclosures. In addition to
ADSL, TI and fiber optic transmission system (FOTS) facility applications, the Te17 is designed to
meet the requirements of WiMax service providers.
83
> Tempest Te21
The Tempest Te21's compact footprint is an ideal, economical solution for microwave, fiber and E911 applications. Lower compartment air conditioning protects the batteries and customer equipment from severe environmental conditions. Upper compartment fan cooling provides adequate cooling for 65°C/149°F temperature hardened power systems.
DC Power Enclosures
> Tempest Te30
The mid-size Te30 enclosure lineup provides up to 27RU of equipment in a 23" rack. A variety of HVAC options maintain a clean internal temperature controlled environment for reliable equipment operation in all kinds of outdoor environmental conditions. The Te30 is designed for installation flexibility. A number of cable entry locations are provided along with a cable management plinth option. Cable entry panels provide access by conduit, multiple cable entry assemblies and water tight fittings. In addition, the Te30 provides options for various AC service entrance and distribution panels adding installation and application flexibility. The Te30 provides an excellent solution for general purpose mid-size enclosure applications.
> Tempest Te4(x)
Alpha introduces its newest enclosure line, the GR-487 compliant Te4(x). The Te40 to Te43 provides an 84-inch tall enclosure that is configurable to a range of different requirements. The Te4(x) line-up is third-party agency certified to meet GR-487 requirements. Compliance includes 30-day salt fog, Zone-4 seismic and 70mph wind driven requirements, as well as several other criteria.
> Flexible Backhaul Enclosure
Alpha's Flexible Backhaul Enclosure is engineered to house optical fiber equipment to support high speed cellular data backhaul. Built with eleven rack mount spaces, the Alpha FBE is able to house fiber and powering gear including an Ethernet switch, power inverters, rectifiers, fiber splice tray, GMT and additional controls. An optional configuration enabling the addition of Batteries, DC rectifiers and Service Utility Entrance is available. With Telecom-grade, quarter-turn locks and key-operated Demark access, the FBE offers easy maintenance access and complete security.
> Wireless Transport Enclosure
The Wireless Transfer Enclosure is ideal for Wireless Backhaul Business Services applications. It offers a self-contained total power solution for a wide range of applications including wireless outdoor base stations, wireless IP access and bulk power. With a compact 24" x 24" footprint, the WTE features a standard 19" rack mount system with has 17RU (front/rear) of rack space, and an internal Breaker Distribution Panel with GFCI and Surge Protection.
Tempest Te25 / Te25xh
Outdoor System Enclosure
> Designed for outdoor or secure indoor applications
> Easily transportable > Durable aluminum construction > Pedestal, wall, pole or rack mount > Compact footprint
Tempest Te25 / Te25xh
Specifications
Material:
High strength corrosion resistant aluminum
Finish:
Powdercoat
Equipment Space:
20RU (Te25xh), 11RU (Te25)
Cable Entrance:
Knockouts located at bottom and back of enclosure
Equipment Rails:
19"
Electrical
Input Voltage Range N/A: 120/240Vac
Voltage:
-48Vdc
Current:
40A (n+1)
Mechanical
84
Te25 Cabinet Dimensions H x W x D (in/mm):
20.3 x 21.4 x 20.4 / 516 x 544 x 518
Te25 Weight (lb/kg):
65 / 29
DC Power Enclosures
Te25xh Cabinet Dimensions H x W x D (in/mm):
36 x 21.4 x 20.4 / 914 x 544 x 518
Te25xh Weight (lb/kg):
90 / 41
Hinge Type: Handle: Door Latch:
3 Position lift off hinge (Te25xh) 2 Position lift off hinge (Te25)
Padlockable (Te25xh)
3 Point Latch (Te25xh) Padlockable 1/4 turn latch
Equipment Shelves: Battery Trays (Qty): Environment Operating Temperature: Storage Temperature: Cooling: Door Installed Louvers: Audible Noise:
Optional (Te25xh) 1
-40 to 46°C / -40 to 115°F -40 to 85°C / -40 to 185°F Thermostat control filtered and fan cooled Equipped with washable/replacement filter <45dBa
Tempest Te25
Installation
Access:
Rear louver can be removed for equipment installation
Maintenance
Front access after installation filter access on front door
System Specification (As Shown)
· 48Vdc Cordex rectifier shelf c/w DC distribution · 4 x 92Ahr batteries · External 8 position AC distribution with 30A generator connector and
manual transfer switch · 8 position GMT fuse panel (Te25xh) · Fan filtered ambient cooled (Te25xh) · Alarm terminal block · Ground bar
System Options: Standards CSA/UL: Telcordia: NEMA Rating:
Consult factory for custom system solutions
C22.2 No 60950-01-03 Designed to meet zone 4 requirements (Te25) Type 3R (CSA C22.2 No 94-M91)
Tempest Te25 (with batteries)
Tempest Te25xh
Tempest Te25xh (open)
Tempest Te15
Modular Enclosure
> Modular design for single or multiple cabinet configurations
> Welded aluminum construction > 39RU of rack space > Heating and cooling options > Compact footprint
Tempest Te15
Electrical
Input Voltage:
Number of Breakers: Transfer Switch/Generator Connector: TVSS: Mechanical
120/240Vac 200A 1 120Vac 100A 1 18 maximum
Optional
Optional
Top Compartment Dimensions H x W x D (in/mm):
8 x 32 x 32 / 203 x 813 x 813
Main Compartment Dimensions H x W x D (in/mm):
69 x 32 x 32 / 1753 x 813 x 813
Bottom Compartment Dimensions H x W x D (in/mm):
8 x 32 x 32 / 203 x 813 x 813
Solar Shield Dimensions H x W x D (in/mm): DC Connections:
Chassis Ground:
Security: Rack Space: Alarm Connection: Description:
3 x 32 x 32 / 76 x 813 x 813
Multiple connection Multiple connection Buss bar located in cabinet Lockable front door 23" rails, 39RU
Terminal block High/Low Temperature Intrusion
Tempest Te15 Side mounted AC distribution
Standards
CSA:
C22.2 No 60950-01-03 Std. No 60950-01 NEMA Type 3R (CSA C22.2 No 94-M91)
Seismic:
Designed to meet Zone 4 requirements
Related Components
85
Heating and Cooling:
600W
Air Conditioning:
Up to 8000BTU
Fan Cooling:
Optional
Heat Exchanger:
Optional
DC Power Enclosures
Tempest Te15 (open)
Tempest Te17
Outdoor Enclosure
> Designed for outdoor network applications > Easily transportable > Durable welded aluminum construction > Variety of configurations possible
with 23RU of space > Compact footprint
Tempest Te17 (shown with 5000BTU air conditioner, bottom compartment, and solar shield)
Tempest Te17
Specifications
Enclosure Options
Material:
High strength corrosion resistant aluminum
Mounting:
Pad or platform mount
Finish: Equipment Space:
Powdercoat 23RU
HVAC Options:
Heat exchanger 33W/°C, 3500 BTU air conditioner or fan filtered ambient cooling
86
Cable Entrance:
Knockouts located in riser and bottom of enclosure
System Specifications (As Shown)
Equipment Rails:
23"
Electrical
· 24Vdc Cordex rectifier shelf c/w DC distribution · Internal 8 position AC panel
Input Voltage Range N/A: Voltage:
120/240Vac 24Vdc
· Air conditioner and heater · EVS (Emergency ventilation system) · Customer specific equipment layout
Current: Mechanical
64A (n+1)
· Alarm terminal block · Ground bar
Dimensions H x W x D (in/mm):
58 x 30 x 28 / 1473 x 762 x 711
System Options: Standards
Consult factory for custom system solutions
Weight (lb/kg): Hinge Type: Door Latch:
450 / 204 Piano style hinge 2x padlockable 1/4 turn socket pin-head key
CSA/UL: Telcordia: NEMA Rating:
C22.2 No. 60950 Designed to meet zone 4 requirements Type 3R (CSA C22.2 No 94-M91)
DC Power Enclosures
Battery Trays (Qty):
Configuration dependent - 8RU per front terminal battery shelf
Environment Operating Temperature: Storage Temperature: Cooling: Heating:
-40 to 46°C / -40 to 115°F -40 to 85°C / -40 to 185°F 3500 BTU air condition 550W heater option
EVS:
DC fan powered EVS (Emergency Ventilation System) option
Installation
Access:
Removable enclosure rear panel and removable lower compartment panels
Maintenance Front access after installation
Tempest Te17 (shown configured to customer specification)
Tempest Te21
Modular Enclosure
> Modular design for single or multiple cabinet configurations
> Welded aluminum construction > Dual compartment system > Compact footprint > Up to 39.6kW at 48V > Multiple point cable access
Tempest Te21
Tempest Te21
Electrical
Standards
Input Voltage:
120/240Vac, connected direct to site AC distribution panel
CSA:
C22.2 No 60950-01-03 Std. No 60950-01
Mechanical
NEMA Type 3R (CSA C22.2 No 94-M91)
Dimensions H x W x D (in/mm): 84 x 30 x 30 / 2137 x 762 x 762
Weight (lb/kg):
863 / 392 (no batteries)
Seismic:
Designed to meet Zone 4 requirements
87
Related Components
Chassis Ground:
Multiple connection Buss bar located in cabinet
Heater: Air Conditioning:
600W Up to 58000BTU
Security:
Lockable front door
Fan Cooling:
Optional
DC Distribution:
2 x 1200A 20 position bullet breaker 4 x 600A load shedding capability
Batteries: Customer Equipment: Alarm
2 shelves 4 battery/shelf 8RU available
Connection: Description:
Terminal block High/low temperature intrusion
DC Power Enclosures
Tempest Te21 (open)
Tempest Te30
Multi-functional Enclosure
> Modular enclosure design for mid size applications > Provides multiple enclosure line-ups including
power, battery and radio equipment installations > Air conditioning, fan cooling and
vented options available > NEMA 3R rating (IP55) > Multiple cable access points
Tempest Te30
Electrical
Input Voltage:
120/240Vac 100A 1
Generator Switch/ Generator Connector:
Optional
TVSS:
Optional
88
AC Panels/Breakers:
Configurable - contact factory
Mechanical
Part Number:
029-016-20
Dimensions H x W x D (in/mm):
58.4 x 30 x 30 / 1483 x 762 x 762 including 10/254 plinth
DC Power Enclosures
Weight (lb/kg): Mounting: Enclosure: Internal Rack:
500 / 227 (no batteries, no rectifiers) Pad or platform Aluminum shell 5052-H32 23", 26RU
Environment
Operating Temperature: Storage Temperature: Humidity: Elevation: Weather Tightness: Audible Noise:
-40 to 46°C / -40 to 115°F -40 to 85°C / -40 to 185°F 0 to 95% non-condensing 3600m / 12000ft, see operating temperature NEMA Type 3R 44dBA @ 7m / 23ft (air conditioned system)
Tempest Te30
Alarm Connection: Description: Chassis Ground: Security: Standards
Enclosure Rating:
Product Safety: Seismic: Related Components
Cooling Options:
Heating:
Terminal block High/Low Temperature Intrusion Multiple connection Pad lockable doors
CSA/UL type 3R IP55 equivalent CSA/UL 60950 Designed to meet Zone 4 requirements
5000BTU/hr air conditioner on front door DC fan cooling (and/or backup) Vented Up to 550W, 100-120Vac 50/60Hz
Tempest Te45
72" Single Compartment Power Enclosure
> Designed for single or multiple enclosure applications
> Durable welded aluminum construction > Variety of configurations possible
with 39RU of space > Compact footprint > GR-487 compliant
Tempest Te45
Tempest Te45 Backhaul Enclosure
Specifications
System Specifications (As Shown)
Dimensions H x W x D (in/mm): 72 x 30 x 30 / 1829 x 762 x 762
· 48Vdc Cordex 1.8kW rectifiers
Weight (lb/kg):
600 / 273
· AC panel c/w generator panel and ATS (Automatic Transfer Switch)
Equipment Space: Access:
23" 39RU Removable rear panels and front hinged door
· Air conditioner w/heater · EVS (Emergency Ventilation System) · Alarm terminal block
Door Latch / Hinge Type: 3 Point latch / 4 Position lift off hinges
· Ground bar
Handle:
Padlockable
89
System Options:
Consult factory for custom system solutions
Battery Trays (Qty):
Configuration dependent - 8RU per front terminal battery shelf
CSA/UL:
C22.2 No. 60950
NEMA Rating:
Type 3R (CSAC22.2 No 94-M91)
DC Power Enclosures
Tempest Te45 Battery
72" Front Terminal Battery Enclosure
> 8 Strings at 24Vdc, 4 strings at 48Vdc > Designed for single or multiple
enclosure applications > Durable welded aluminum construction > Compact footprint
Tempest Te45 Battery
Specifications
Material:
High strength corrosion resistant aluminum
Finish:
Powdercoat
Equipment Space:
39RU
Cable Entrance:
Knockouts on sides and bottom
90
Equipment Rails:
23"
Electrical
Input Voltage Range N/A: 120/240Vac
Mechanical
DC Power Enclosures
Dimensions H x W x D (in/mm):
72 x 30 x 30 / 1829 x 762 x 762
Weight (lb/kg): Hinge Type: Handle: Door Latch: Battery Trays (Qty): Environment Operating Temperature: Storage Temperature: Cooling: Heating:
600 / 273 4 Position lift off hinges Padlockable 3 Point latch 4 Front terminal battery shelves
-40 to 46°C / -40 to 115°F -40 to 85°C / -40 to 185°F 4000 BTU air conditioner 500W
EVS:
DC Fan powered EVS (Emergency Ventilation System) option
Audible Noise:
<65dBa
Tempest Te45 Battery
Installation
Access:
Removable rear panels and front hinged door provide full enclosure access
Maintenance
Front access after installation Enclosure Options
Mounting:
Pad or platform mount
System Specifications (As Shown)
· 4 Battery shelves for GNB 155Ahr front terminal batteries · Air conditioner w/ heater · EVS (Emergency Ventilation System) · Alarm terminal block · Ground bar
System Options: Standards CSA/UL:
Telcordia:
NEMA Rating:
Consult factory for custom system solutions
C22.2 No. 60952 GR-487 compliance- contact factory for specific compliances Type 3R (CSAC22.2. No 94-M91)
Tempest Te40 Battery
84" Front Terminal Battery Enclosure
> 10 Strings at 24Vdc, 5 strings at 48Vdc > 120Amp buss > Designed for single or multiple
enclosure applications > Durable welded aluminum construction > Compact footprint
Tempest Te40 Backhaul Enclosure
Tempest Te40 Battery
Specifications
System Specifications (As Shown)
Dimensions H x W x D (in/mm):
Weight (lb/kg): Equipment Space:
84 x 30 x 30 / 2134 x 762 x 762
1300 / 590 23" 44RU
· 5 Battery shelves for GNB 155Ahr front terminal batteries · Air conditioner w/heater · Alarm terminal block · Ground bar
Access:
Removable rear panels and front hinged door
System Options:
Consult factory for custom system solutions
91
Door Latch / Hinge Type:
3 Point latch / 5 Position lift off hinges
Agency Standards:
C22.2 No. 60954
NEMA Rating:
Type 3R (CSAC22.2 No 94-M91)
DC Power Enclosures
Tempest Te41 Power
84" Dual Compartment Power Enclosure
> Designed for single or multiple enclosure applications > Dual compartment system > Durable welded aluminum construction > Variety of configurations possible with 23RU of space > Compact footprint > Up to 39.6kW at 48Vdc or 34.1kW at 24Vdc > Multiple point cable access
Tempest Te41 Backhual Enclosure
Specifications
Dimensions H x W x D (in/mm):
84 x 30 x 30 / 2134 x 762 x 762
Weight (lb/kg):
1300 / 590
Equipment Space:
23" 19RU (upper), 26RU (Lower)
Access:
Removable rear panels and front hinged door
92
Door Latch / Hinge Type:
2 point latch upper and lower compartments / 5 position lift off hinges
Agency Standards: NEMA Rating:
C22.2 No. 60953 Type 3R (CSAC22.2 No 94-M91)
Tempest Te41 Power
System Specifications (As Shown)
· 48Vdc Cordex 3.6kW rectifiers (3.1kW Cordex system optional) · Qty 48 DC breaker positions · Qty 4 LVD disconnects for staged shutdown during power outage · AC panel c/w generator panel and ATS (Automated Transfer Switch) · Air conditioner w/ heater · Fan/filter ambient cooled upper compartment · Customer specific equipment layout · Alarm terminal block · Ground bar
System Options:
Consult factory for custom system solutions
DC Power Enclosures
Tempest Te44
Large Format Battery Enclosure
> Designed for Absolyte GNB 100 C-31 battery stacks
> Durable welded aluminum construction > Build on-site modularity
Tempest Te44
Tempest Te44
Specifications
Installation
Material:
High strength corrosion resistant aluminum
Access:
Modular design - built on site
Finish:
Powdercoat
Maintenance
Cable Entrance: Electrical Input Voltage Range N/A: Voltage: Mechanical
Bottom and sides
120Vac for air conditioner -48 or 24Vdc configurations
Front access after installation
Enclosure Options
Mounting Option:
Pad or platform mount
93
Other Options:
Single or dual stack configurations
System Specifications
Dimensions H x W x D (in/mm):
41.5 x 52 x 36 / 1054 x 1321 x 914 76 x 52 x 36 / 1928 x 1321 x 914
· Designed for GNB 100G31 Absolyte battery packs · Single or dual stack configuration
Weight (lb/kg):
550 / 250 900 / 408
· High temp and hydrogen detection controlled EVS · Alarm terminal block
Door Latch:
4 x padlockable 1/4 turn socket pin-head key
· Ground bar
Environment
System Options:
Consult factory for custom system solutions
Operating Temperature:
-40 to 46°C / -40 to 115°F
Standards
Storage Temperature:
-40 to 85°C / -40 to 185°F
CSA/UL:
C22.2 No. 60953
DC Power Enclosures
Cooling: Heating:
EVS:
2000 BTU air conditioner 500W
EVS (Emergency Ventilation System) with hydrogen control
Telcordia: NEMA Rating:
GR-487 compliance- contact factory for specific compliances
3R
Flexible Backhaul Enclosure 2322
> Provides 15RU for 19" horizontal mounted equipment or 10RU for vertical mounted equipment
> Front and side door access with removable lid > Durable welded aluminum construction > Wall, H-Frame, pole or ground mount options > Multiple thermal management options
FBE2322-ENC
FBE2322-ENC
Specifications
Outer Dimensions H x W x D (in/mm):
29.6 x 27 x 24 / 751.84 x 685.8 x 609.6
Equipment Space:
Front to back adjustable 19" 15RU horizontal or 23" 10RU vertical
Access:
Front hinged door, left and right lift off doors, removable lid
Door Latch / Hinge Type:
1/4 Turn padlockable / reversible 2 position lift off hinge
CSA/UL:
NEMA Rating:
94
60950-22 ITE electrical enclosure Type 3R
Enclosure Options
CordexHP 1.2kW 48Vdc Modular Switched Mode Rectifier
Multiple 48V configurations up to 125 Amps for various 48Vdc applications
High Efficiency design for increased OpEx savings
High Temperature rated fan-cooled design for harsh outdoor installations
DC Power Enclosures
Cordex 4R/8D ADIO CXC Smart Peripheral
Provides additional I/O expansion to existing CXC site controller
Seamless expansion of four relay outputs and eight digital inputs
Ideal for alternate device monitoring and control such as HVAC and generators
System Options Mounting:
Thermal:
Emergency Ventilation System: DC Power: AC Services Entrances: Generator: Alarm:
Wall, H-Frame, Ground or Precast Mounting Pad
Air conditioner with heater, heat exchanger, variable speed-controlled fan cooled
Variable speed controlled fan cooled activated with high temp or HVAC fail alarm
48Vdc Cordex HP 1.2kW rectifiers 70Amp 2 position or 100Amp 8 position External L14-30P generator plug Alarm terminal block
Fuses Panels Stand-Alone DC Distribution
19" and 23" rack mount models 12, 24 or 48V configurations Designed for flexible and custom DC distribution
AlphaCellTM HPL-FT Batteries
AGM runtimes up to 160 minutes in outdoor applications
Absorbent Glass Mat (AGM) technology for efficient gas recombination
HPL-FT features front terminal design with protective covers
Specifically designed for mission-critical applications
Cooling Options
Fan Cooled
Heat Exchanger
Air Conditioner
Flexible Backhaul Enclosure 2319
> Modular enclosure system, allows for easy battery expansion
> Demark access door > Front access for fan and filter maintenance > 24 or 48V configurations
FBE2319-ENC
Specifications
Models:
Outer Dimensions H x W x D (in/mm): Weight (lb/kg): Equipment Space: Access:
Door Latch / Hinge Type:
CSA/UL: NEMA Rating: System Options Mounting: Thermal: DC Power: AC Services Entrances: Generator: Alarm:
FBE2319-ENC
FBE2319-ENC with Battery Enclosure
27 x 23 x 22.3 / 686 x 584 x 565
41 x 23 x 22.3 / 1041 x 584 x 565
57 / 26 Front to back adjustable 19" 11RU Front hinged door with demark access door
1/4 Turn padlockable / reversible 2 position lift off hinge
60950-22 ITE electrical enclosure Type 3R
Wall, H-Frame, Ground or Precast Mouting Pad Heat exchanger, variable speed controlled fan cooled 48Vdc Cordex HP 1.2kW rectifiers 70Amp 2 position or 100Amp 8 position External L14-30P generator plug Alarm terminal block
FBE2319-ENC with Demark access door and fan cool option
95
FBE2319-ENC with Heat Exchanger Door, Battery Expansion and Ground Mount Option
DC Power Enclosures
Flexible Backhaul Enclosure 1417V
> Provides 7RU for 19" vertically mounted equipment in smallest foot print possible
> Front and side access to installed equipment > Wall or H-frame mount options > Aluminum welded construction with durable powdercoated exterior > Variable speed controlled fan cooled
FBE1417V-ENC
FBE1417V-ENC
Specifications
Outer Dimensions H x W x D (in/mm):
24.6 x 18 x 19.5 / 625 x 452 x 495
Weight (lb/kg):
35 / 15.9
Equipment Space:
Vertical 19" 7RU
Access:
Front hinged door, left and right lift off doors
96
Door Latch / Hinge Type:
1/4 Turn padlockable / reversible 2 position lift off hinge
CSA/UL: NEMA Rating: System Options
60950-22 ITE electrical enclosure Type 3R
Mounting: Thermal: 1RU Option Panel:
Wall or H-Frame Variable speed controlled fan cooled Alarm terminal block, fiber management
FBE1417V-ENC
DC Power Enclosures
Wireless Transport Enclosure
> Equipment mounting area is 17RU > Equipment rails are front-to-back adjustable, suitable
for mounting 19 inch rack mount equipment > Integrates Heat Exchanger and
Thermoelectric Cooling System > Equipment area is cooled by an Air-to-Air heat
exchanger with variable speed blower control > Internal L14-30P Generator inlet plug with
generator cord access through door
Wireless Transport Enclosure
Wireless Transport Enclosure
Specifications
System Specifications (As Shown)
Outer Dimensions H x W x D (in/mm):
70 x 24 x 29 / 1778 x 610 x 737
· Dual compartments - Upper compartment - heat exchanger
Weight (lb/kg):
330 / 150
- Lower compartment - thermoelectric cooling · Two battery trays (Consult factory for battery specifications)
Equipment Space:
Adjustable 19" 17RU plus 2 battery trays
· Front to back adjustable 19" equipment mounting rails
Access:
Front hinged door and rear lift off door
· Internal AC panel
· Generator plug and transfer switch
97
Door Latch / Hinge Type:
1/ 4 turn padlockable / reversable 4 position lift off hinge
· Alarm terminal block · Ground bar
CSA/UL: NEMA Rating:
60950-22 ITE electrical enclosure Type 3R
System Options:
Optional per-formed mounting pad Consult factory for custom system solutions
DC Power Enclosures
98
DC Power Enclosures
AlphaGenTM Generators
Adding a generator to any type of power system provides additional peace of mind. A generator serves as assurance that even in severe conditions, you will be able to keep your system up and functioning. All AlphaGen systems are engineered to have significantly reduced noise levels, high power density and status monitoring.
> AlphaGen 8kW to 2MW Systems
Critical power applications are part of every industry; protecting them starts with reliable generators, available in diesel, gas and LP configurations. Our EPA-compliant diesel models deliver dependable power to a wide range of output requirements. From small-load hub and small business to large Headend or facility backup, every generator is engineered to provide maximum power, performance, flexibility and fuel efficiency.
> AlphaGen Curbside Generator
The AlphaGen curbside generator system is specifically designed for Cable Broadband communications networks. Every AlphaGen system incorporates industry leading power technology, including natural gas or propane powered engine generators, exclusive audible noise baffling, remote status monitoring features and durable weather resistant enclosures.
99
Generators
AlphaGenTM 3.5kW to 2MW Systems
Generator Systems
> Design, install and maintain industrial generators > Custom generator solutions to meet your power supply needs > Generator solutions to most CRT and Facility Requirements > Power range from 3.5kW to 2MW or more > Propane (LP), Natural Gas (NG) or Diesel > Single phase or Three phase Systems > Fixed or portable solutions > Options include Automatic Transfer Switch
100
AlphaGen System
Generators
Alpha has the capability to design, install and maintain industrial generators to meet your power supply needs. Contact an Alpha representative for more details.
AlphaGenTM Telecom
Generator Systems
> Cost effective extended runtime solution for outdoor powering applications
> Quiet operation, small size and low profile allow for easier installation in populated areas
> Eliminates large quantities of batteries otherwise required for extended runtime
> Telecom grade 48Vdc output
AlphaGen Telecom
Model DC Output Voltage: DC Output Load Regulation: Output Current:
3.5kW
39V ±0.5V @ no load 36V configuration 52V ±0.5V @ no load 48V configuration 0.5V 39V @ 90A max / 52V @ 67A max
5kW
39V ±0.5V @ no load 36V configuration 52V ±0.5V @ no load 48V configuration 0.5V 39V @ 128A max / 52V @ 96A max
Engine:
398cc, Air cooled, Single OHV 10.5hp (using natural gas fuel)
RPM (Variable Speed):
2800 to 3600RPM
Acoustical Noise
dBA 10' @ 100% Rated Load: 68.7
dBA 20' @ 100% Rated Load: 63
dBA 10' @ 70% Rated Load: 68.3
dBA 20' @ 70% Rated Load: 62.6
2800 to 3600RPM
68.5 62.5 66.9 60.9
Models:
CE-3x2
CE-9x2
CE-3x2
CE-9x2
7.5kW 52V ±0.5V @ no load 48V configuration 104V ±0.5V @ no load 96V configuration 0.5V 52V @ 144A max / 104V @ 72A max 642cc, Air cooled, Twin OHV 15hp (using natural gas fuel) 2800 to 3600RPM
70.3 64.3 66.4 60.4
PN-6x
Dimensions H x W x D (in/mm):
44 x 26 x 24 /
52 x 52 x 24 /
44 x 26 x 24 /
52 x 52 x 24 /
39 (57 with optional pedestal) x 39.25 x 24
1117.6 x 660.4 x 609.6 1320.8 x 1320.8 x 609.6 1117.6 x 660.4 x 609.6 1320.8 x 1320.8 x 609.6 / 99 (144) x 100 x 61
Weight (lb/kg):
383 / 174
413 / 187
383 / 174
413 / 187
338 / 174 (370 / 168 with optional pedestal)
APU Fuel Consumption
Natural Gas 1000BTU/ft.3:
60ft3/hr
80ft3/hr
156ft3/hr
Propane Gas 2520BTU/ft.3:
0.82 gal/hr to 30ft3/hr to 3.46lb/hr
1.10gal/hr to 40ft3/hr to 4.62lb/hr
1.48gal/hr to 54ft3/hr to 6.24lb/hr
Exterior Surface Temperature:
Meets requirements of UL/CSA
Gas Inlet Pressure:
0.5 to 2 PSI Inlet Pressure (Contact Alpha Engineering for additional supply resources)
Ign Charger Voltage:
13.5Vdc
13.5Vdc
13.5Vdc
13.5Vdc
13.5Vdc
Ign Charger Current:
6A max
6A max
6A max
6A max
6A max
Remote Interface Length*:
75ft max Distance depends upon proper installation, derating and wire gauge
50ft max Distance depends upon proper installation, derating and wire gauge
25ft max Distance depends upon proper installation, derating and wire gauge
Agency Compliance:
UL2200, NFPA 37/54/58 and 70, CSA C22.2 FCC Class A
* Please contact Alpha Technologies for remote interface length distance
All Models Fuel System, Controls and Monitoring: Sensors: Safety Shutdowns: Optional Feature:
Configuration Options:
The controls and fuel system meet applicable sections of NFPA 37, 54 and 58 for automatic unattended operation of remotely located generators. Full System Control and Status Monitoring included. Gas Hazard, Pad Shear, Water Intrusion and Tamper
Low oil pressure, Water intrusion, Over speed, Over temp, Pad Shear, Over crank, Low fuel pressure shutdown (propane only), Gas hazard (propane or natural gas) Cold Start Kit: Provides additional starting capability at temperatures below -18°C / 0°F
CE-3X3.5 or 5kW
CE-9x2 3.5 or 5kW
CE-3/9G Propane Storage for Generator (For 3.5 and 5kW)
PN-6x 7.5kW (PN-6x is not compatible with CE-3/9G)
Alpha Technologies Inc. 3767 Alpha Way Bellingham WA 98226 United States Tel: +1 360 647 2360 Fax: +1 360 671 4936
VISIT US AT WWW.ALPHA.COM
Alpha Technologies Ltd. 7700 Riverfront Gate Burnaby BC V5J 5M4 Canada Tel: +1 604 436 5900 Fax: +1 604 432 1233
Alpha Industrial Power Inc. 1075 Satellite Blvd NW Suite 400 Suwanee GA 30024 United States Tel: +1 678 475 3995 Fax: +1 678 584 9259
Alpha Energy 1628 W Williams Drive Phoenix AZ 85027 United States Tel: +1 602 997 1007 Fax: +1 623 249 7833
Alpha Technologies GmbH Hansastrasse 8 D 91126 Schwabach Germany Tel: +49 9122 79889 0 Fax: +49 9122 79889 21
Alpha Technologies Europe Ltd. Twyford House Thorley Bishop's Stortford, Hertfordshire CM22 7PA United Kingdom Tel: +44 1279 501110 Fax: +44 1279 659870
AlphaTec Ltd. 339 Saint Andrews Street Suite 101 Andrea Chambers 3307 Limassol Cyprus Tel: +357 25 375675 Fax: +357 25 359595
AlphaTEK ooo Khokhlovskiy Pereulok 16 Stroenie 1 Office 403 109028 Moscow Russia Tel: +7 495 916 1854 Fax: +7 495 916 1349
Alpha Technologies Suite 1903, 19/F., Tower 1 33 Canton Road, Tsim Sha Tsui China Hong Kong City, Kowloon Hong Kong Tel: +852 2736 8663 Fax: +852 2199 7988
Altair Advanced Industries, Inc. 3765 Alpha Way Bellingham WA 98226 United States Tel: +1 360 671 7703 Fax: +1 360 733 8690
Alpha Technologies Inc.
Due to continuing product development, Alpha reserves the right to change specifications without notice. Copyright © 2011 Alpha Technologies Inc. All Rights Reserved. Alpha is a registered trademark of Alpha Technologies. 049-071-11-A001 (02/2011)
Adobe InDesign CS5 (7.0) Adobe PDF Library 9.9