315AAV066135 315AAV/315JAV Variable-Speed 4-Way Multipoise Induced Combustion Gas Furnace Sizes 045 thru 155 Series F
Product Data
PLUS 80V Energy Efficient Gas Furnace
A10255
The Plus 80V Variable--Speed 4--Way Multipoise Gas Furnace offers outstanding comfort and electrical efficiency in an 80% AFUE furnace. You get all of the benefits of Perfect Heatt and Perfect Humidityt: reduced drafts, reduced sound levels, longer, more gentle cycles, and less temperature differences between rooms. Also, it improves indoor air quality, plus provides outstanding electrical efficiency all year long: Homeowners can now economically run constant fan to help eliminate temperature differences throughout the house and to get better indoor air quality. This Perfect Humidity furnace also increases comfort in the summer by wringing out extra humidity. The 315AAV/JAV furnaces are approved for use with natural or propane gas, and the 315JAV is approved for use in Low NOx Air Management Districts. Bryant EvolutionR System When this Plus 80V gas furnace is matched with the Evolution Control and an air conditioner or heat pump, you will experience the ultimate in Perfect Heat and Perfect Humidity through unmatched control of temperature, humidity, indoor air quality, and zoning. The Bryant Evolution System also allows for worry-free operation through on-screen, text-based service reminders and equipment malfunction alerts. For even greater comfort and convenience, match the Plus 80V furnace with a two--speed Puron air conditioner or heat pump. This
will create a fully communicating system, requiring only 4 thermostat wires between system components, and troubleshooting can even be done from the outdoor unit without entering the home.
Optional remote access through telephone or Internet is also available when combined with a remote connectivity kit.
STANDARD FEATURES
S Evolutiont System--match with the Evolutiont Control for Evolutiont System benefits
S Perfect Heat, Perfect Humidityt operation Including Super-dehumidify mode for maximum humidity control Two-stage heating even with single--stage thermostat-patented Adaptive Control Technology Reduced operating sound through low--stage operation and sound elimination combustion system
S Variable-speed ECM blower motor Increased SEER ratings for A/C and H/P systems as compared to the Air Conditioning Heating and Refrigeration Institute's standard coil--only ratings when paired with selected Bryant evaporator coils. Matches CFM to cooling system over a wide range of static points
S SmartEvapt can lower the humidity level in the home by nearly 10 percent
S Certified to leak 2 percent or less of its nominal air
conditioning CFM delivered when pressurized to 1--In.
Water Gauge with all present air inlets, air outlets, and
condensate drain port(s) sealed.
S Four-position furnace: Upflow, Horizontal Right, Horizontal Left, Downflow Thirteen different vent options
S Compact design only 33-1/3 in. (847 mm) tall S Microprocessor based "smart" control center
Fan on Plust-- Continuous Fan speed adjustable from thermostat Adjustable heating air temperature rise Adapts heating stages to meet demand Up to 12 cooling airflow selections with a wide range of capability Dehumidify mode Enhanced diagnostics with LED and reflective sight glass, non--volatile fault code memory, and self test feature On--board fuse for transformer protection S Patented blocked vent safeguard to ensure proper furnace venting S Insulated blower compartment S HYBRID HEATr Dual Fuel System compatible
S All models are chimney friendly when used with accessory vent kit
S Perfect Lightt Igniter S Residential installations eligible for consumer financing
through the Comfort Credit Program
315AAV/JAV FRONT OF CASING FRONT OF CASING
DIMENSIONS
5.1 [130.5]
2 1/16 [51.6]
1.7 [43.5]
C
Ø7/8 [22.2] ACCESSORY (2)
5 15/16 [150.7]
5 1/2 [140.3]
8 7/16 [213.5]
9 7/8 [250.7]
AIR FLOW
Ø7/8 [22.2] ACCESSORY
27 3/4 [704.7]
33 1/4 [843.9]
Ø1/2 [12.7] THERMOSTAT WIRE ENTRY
1 15/16 [49.2]
2 5/16 3 7/16 [59] [86.8] 5 7/8 [148.5]
TOP OF CASING Ø7/8 [22.2] JUNCTION BOX LOCATION
Ø1 3/4 [44.5] GAS ENTRY
AIR FLOW A B
TOP OF CASING
6 13/16 [172.3] 5 7/8 [148.5] 5 5/8 [143.3] 5 7/16 [138.5] 1 15/16 [49.2]
4 13/16 [122.2]
9 9/16 [243.3]
27 3/4 [704.7]
29 9/16 [750.7]
Ø7/8 [22.2] J.BOX PROVISION Ø7/8 [22.2] ACCESSORY
8 5/8 [219]
AIR FLOW
19 [481.7] OUTLET
Ø1/2 [12.7] THERMOSTAT WIRE ENTRY
Ø1 3/4 [44.5] GAS ENTRY
7 13/16 [197.8]
9 11/16 [245.4]
11
7/16
[290.7]
Ø7/8 [22.2] ACCESSORY
21.6 [549.5] BOTTOM INLET
28.39 [721.2]
29 [736.9]
6.1 [155.7]
D
BOTTOM RETURN WIDTH
3/4 [19.1]
KNOCK OUTS FOR VENTING(5 PLACES)
Ø7/8 [22.2] ACCESSORY
22 1/16 [560]
SIDE INLET (BOTH SIDES)
14 7/8 [337.3] (BOTH SIDES)
1 1/4 1 [31.8] [25.4]
A10271 1. Two additional 7/8--in. (22 mm) dia. knockouts are located in the top plate. 2. Minimum return--air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. 3. Minimum return--air opening at furnace.
a. For 800 CFM--16--in. (406 mm) round or 14--1/2 x 12--in. (368 x 305 mm) rectangle. b. For 1200 CFM--20--in. (508 mm) round or 14--1/2 x 19--1/3 in. (368 x 491 mm)rectangle. c. For 1600 CFM--22--in. (559 mm) round or 14--1/2 x 22--1/16--in. (368 x 560 mm) rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the bottom, or the bottom of single side inlets. The use of both side inlets, a combination of one side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
FURNACE SIZE
036070
A CABINET
WIDTH IN. (mm)
14 ---3/16 (360)
B OUTLET WIDTH
IN. (mm)
12 ---9/16 (319)
C TOP & BOTTOM FLUE COLLAR IN. (mm)
9 ---5/16 (237)
D BOTTOM INLET WIDTH IN. (mm)
12 ---11/16 (322)
VENT CONNECTION
SIZE IN. (mm)
4 (102)
SHIPPING WT.
LB (KG)
115 (52)
ACCESSORY FILTER MEDIA CABINET SIZE
IN. (mm)
16 (406)
048090
17 ---1/2 (445)
15 ---7/8 (403)
11 ---9/16 (294)
16 ---1/8 (410)
4 (102)
130 (59)
16 (406)
060110
21 (533)
19 ---3/8 (492)
13 ---5/16 (338)
19 ---1/2 (495)
4 (102)
155 (70)
20 (508)
066135
24 ---1/2 (622)
22 ---7/8 (581)
15 ---1/16 (383)
23 (584)
4 (102)
166 (75)
24 (610)
066155
24 ---1/2 (622)
22 ---7/8 (581)
15 ---1/16 (383)
23 (584)
4 (102)
175 (79)
24 (610)
*135 and 155 size furnaces require a 5 or 6 ---in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete installation requirements.
2
CLEARANCE TO COMBUSTIBLES
D
315AAV/JAV
A10269
DES I GN
Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
C
ERTIFIE
Always Ask For
3
315AAV/JAV
SPECIFICATIONS
UNIT SIZE RATINGS AND PERFORMANCE
Input Btuh* Non --- weatherized ICS
315JAV Upflow; all 315AAV 315JAV Downflow/Horizontal
Output Capacity (Btuh) Non --- weatherized ICS
AFUE
315JAV Upflow; all 315AAV 315JAV Downflow/Horizontal
Certified Temperature Rise Range --- ° F (° C)
High Low High Low High Low High Low
High
Low
Certified External Static Pressure
Heat/Cool
Airflow CFM
Heating High/Low Cooling
ELECTRICAL
Unit Volts--- Hertz--- Phase
Operating Voltage Range
Min-Max
Maximum Unit Amps
Maximum Wire Length (Measure 1 Way in Ft (M)
Minimum Wire Size
Maximum Fuse or Ckt Bkr Size (Amps)**
Transformer (24v)
External Control
Heating
Power Available
Cooling
Air Conditioning Blower Relay
CONTROLS
Limit Control
Heating Blower Control
Burners (Monoport)
Gas Connection Size
GAS CONTROLS
Gas Valve (Redundant)
Mfr.
Min. inlet pressure (In. W.C.)
Max. inlet pressure (In. W.C.)
Ignition Device
Factory-installed orifice
BLOWER DATA
Direct-Drive Motor HP (ECM)
Motor Full Load Amps
RPM (Nominal)-Speeds
Blower Wheel Diameter x Width --- In. (mm)
036070
048090
060110
066135
66,000 43,500 63,000 43,500 54,000 35,000 51,000 35,000
80.0 30-60 (17--- 33) 30-60 (17--- 33) 0.12/0.50 1060/615 1225
88,000 58,000 84,000 58,000 71,000 47,000 68,000 47,000
80.0 40-70 (22--- 39) 30-60 (17--- 33) 0.15/0.50 1090/825 1400
110,000 72,500 105,000 72,500 89,000 59,000 85,000 59,000
80.0 40-70 (22--- 39) 25-55 (14--- 30) 0.20/0.50 1330/1110 2095
132,000 87,000 126,000 87,000 107,000 70,000 102,000 70,000
80.0 40-70 (22--- 39) 25-55 (14--- 30) 0.20/0.50 1725/1430 2100
9.0
9.6
30 (9.1)
29 (8.8)
14
15
115-60-1 104-127
15.1 29 (8.8)
40va 12va 35va Standard
14.9 30 (9.1)
12 20
SPST
Solid-State Time Operation
3
4
5
6
1/2-in. NPT
White-Rodgers 4.5 (Natural Gas) 13.6 (Natural Gas)
Hot Surface Size 43
1/2 7.7 300-1300 10 x 6 (254 x 152)
1/2 7.7 300-1300 10 x 8 (254 x 203)
1 12.8 300-1300 11 x 10 (279 x 254)
1 12.8 300-1300 11 x 11 (279 x 279)
066155 154,000 101,500 147,000 101,500 125,000 82,000 119,000 82,000
80.0 45-75 (25--- 42) 30-60 (17--- 33) 0.20/0.50 1775/1440 2095
15.0 29 (8.8)
7
1 12.8 300-1300 11 x 11 (279 x 279)
* Gas input ratings are certified for elevations to 2000 ft. (610 M) In USA for elevations above 2000 ft (610 M), reduce ratings 4 percent for each 1000 ft (305 M) above sea level. Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 ---2009 Table F.4 or furnace installation instructions.
Capacity in accordance with U.S. Government DOE test procedures.
Airflow shown is for bottom only return-air supply for the as-shipped speed tap. For air delivery above 1800 CFM, see Air Delivery table for other options. A filter is required for each return-air supply. An airflow reduction of up to 7 percent may occur when using the factory-specified 4-5/16 in. (110 mm) wide, high efficiency media filter.
** Time ---delay type is recommended.
ICS Isolated Combustion System
4
315AAV/JAV
AIR DELIVERY - CFM (With Filter)*
Unit Size 036070
Operating Mode
CFM Airflow Setting
External Static
Pressure Range* (In. W.C.)
Low Heat
735 (615)
0--- 0.50
High Heat
1180 (1060)
0--- 1.0
1--- 1/2--- Ton Cooling
525
0--- 0.50
2--- Ton A/C Cooling
700
0--- 0.50
2--- 1/2--- Ton A/C Cooling
875
0--- 1.0
3--- Ton A/C Cooling
1050
0--- 1.0
3--- 1/2--- Ton A/C Cooling
1225
0--- 1.0
Maximum
1400
0--- 1.0
048090
Low Heat
985 (825)
0--- 1.0
High Heat
1210 (1090)
0--- 1.0
1--- 1/2--- Ton A/C Cooling
525
0--- 0.50
2--- Ton A/C Cooling
700
0--- 0.50
2--- 1/2--- Ton A/C Cooling
875
0--- 1.0
3--- Ton A/C Cooling
1050
0--- 1.0
3--- 1/2--- Ton A/C Cooling
1225
0--- 1.0
4--- Ton A/C Cooling
1400
0--- 1.0
Maximum
1600
0--- 1.0
060110***
Low Heat
1320 (1110)
0--- 1.0
High Heat
1475 (1330)
0--- 1.0
2--- Ton A/C Cooling
700
0--- 0.50
2--- 1/2--- Ton A/C Cooling
875
0--- 0.50
3--- Ton A/C Cooling
1050
0--- 0.50
3--- 1/2--- Ton A/C Cooling
1225
0--- 1.0
4--- Ton A/C Cooling
1400
0--- 1.0
5--- Ton A/C Cooling
1750
0--- 1.0
6--- Ton A/C Cooling
2100
0--- 1.0
Maximum
2200
0--- 1.0
066135
Low Heat
1700 (1430)
0--- 1.0
High Heat
1915 (1725)
0--- 1.0
2--- Ton A/C Cooling
700
0--- 0.50
2--- 1/2--- Ton A/C Cooling
875
0--- 0.50
3--- Ton A/C Cooling
1050
0--- 0.50
3--- 1/2--- Ton A/C Cooling
1225
0--- 1.0
4--- Ton A/C Cooling
1400
0--- 1.0
5--- Ton A/C Cooling
1750
0--- 1.0
6--- Ton A/C Cooling
2100
0--- 1.0
Maximum
2200
0--- 1.0
066155
Low Heat
1715 (1440)
0--- 1.0
High Heat
1970 (1775)
0--- 1.0
2--- Ton A/C Cooling
700
0--- 0.50
2--- 1/2--- Ton A/C Cooling
875
0--- 0.50
3--- Ton A/C Cooling
1050
0--- 0.50
3--- 1/2--- Ton A/C Cooling
1225
0--- 1.0
4--- Ton A/C Cooling
1400
0--- 1.0
5--- Ton A/C Cooling
1750
0--- 1.0
6--- Ton A/C Cooling
2100
0--- 1.0
Maximum
2200
0--- 1.0
External Static Pressure (ESP) (In. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
AIRFLOW (CFM) 735 735 735 735 725
1160 1165 1175 1180 1180 1180 1180 1180 1180 1175
515 690 875 1050 1220 1395
500 680 875 1050 1225 1400
500 675 875 1050 1225 1400
490 680 870 1050 1225 1400
485 675 865 1050 1225 1395
855 1050 1220 1385
850 1045 1205 1370
835 1035 1190 1340
825 1020 1185 1300
820 1000 1170 1245
950 970 985 985 985 985 985 985 985 980
1190 1205 1210 1210 1210 1210 1210 1210 1210 1200
525 680 815 1005 1190 1350 1595
520 680 845 1005 1200 1370 1600
525 680 845 1015 1200 1390 1600
495 675 855 1035 1205 1390 1600
475 670 850 1040 1205 1400 1595
850 1040 1215 1390 1555
845 1035 1205 1380 1505
835 1030 1200 1380 1465
820 1025 1185 1360 1430
805 1010 1170 1340 1390
1275 1295 1315 1320 1320 1320 1320 1320 1320 1315
1460 1465 1475 1475 1475 1475 1475 1475 1465 1465
700 875 1050 1225 1400 1750 2100 2200
700 875 1050 1225 1400 1750 2100 2190
700 875 1050 1225 1400 1750 2100 2190
700 875 1050 1225 1400 1750 2100 2180
700 875 1050 1225 1400 1750 2090 2155
1225 1400 1750 2075 2145
1225 1400 1750 2055 2125
1225 1400 1750 2040 2100
1225 1400 1740 2005 2080
1225 1400 1725 1970 2020
1700 1700 1700 1700 1700 1695 1700 1695 1685 1670
1900 1905 1915 1915 1915 1915 1915 1915 1915 1915
700 870 1010 1155 1395 1740 2075 2180
700 870 1030 1180 1400 1750 2085 2195
700 865 1050 1200 1400 1750 2090 2200
700 865 1050 1210 1400 1750 2100 2200
665 865 1050 1220 1400 1735 2100 2200
1225 1400 1740 2100 2200
1225 1400 1735 2090 2185
1225 1390 1730 2080 2165
1225 1375 1715 2055 2140
1225 1355 1700 2025 2095
1715 1715 1715 1715 1715 1705 1710 1705 1705 1695
1955 1965 1965 1970 1970 1970 1970 1970 1970 1960
700 865 1015 1160 1385 1745 2055 2175
700 875 1020 1185 1400 1750 2070 2190
700 875 1035 1215 1400 1750 2080 2200
700 865 1045 1225 1400 1750 2085 2200
680 865 1050 1225 1400 1745 2095 2200
1225 1400 1740 2100 2200
1225 1395 1745 2100 2200
1225 1395 1745 2100 2200
1225 1380 1740 2090 2180
1225 1360 1735 2065 2160
*Actual external static pressure (ESP) can be determined by using the fan laws (CFM 2 proportional to ESP); such as, a system with 1180 CFM at 0.5 ESP would operate at cooling airflow of 1050 CFM at 0.4 ESP and low--- heating airflow of 735 CFM at 0.19 ESP. {Comfort airflow values are shown in parenthesis. Comfort airflow is selected when the low--- heat rise adjustment switch (SW1--- 3) is OFF and the comfort/efficiency switch (SW1--- 4) is ON. }Ductwork must be sized for high--- heating CFM within the operational range of ESP. {{Operation within the blank areas of the chart is not recommended because high--- heat operation will be above 1.0 ESP. ***All airflows on 110 size furnace are 5% less on side return only installations.
5
315AAV/JAV
ACCESSORIES
DESCRIPTION Media Filter Cabinet
Cartridge Media Filter
EZ Flex Media Filter with End Caps
Replacement EZ Flex Filter Media
External Bottom Return Filter Rack
External Side Return Filter Rack Unframed Filter, 3/4-in. (19 mm) Flue Extension Combustible Floor Base Downflow Vent Guard Vent Extension Kit Chimney Adapter Kit Chimney Adapter Kit Natural-to-Propane Conversion Kit * Propane-to-Natural Conversion Kit Label Kit ECM Motor Simulator Advanced Product Monitor High Altitude Kit
Gas Orifice
UV Lights Heat/Energy Recovery Ventilator Humidifier Electronic or Mechanical Air Cleaner
PART NO. FILCABXL0016 FILCABXL0020 FILCABXL0024 FILBBCAR0016 FILBBCAR0020 FILBBCAR0024 EXPXXUNV0016 EXPXXUNV0020 EXPXXUNV0024 EXPXXFIL0016 EXPXXFIL0020 EXPXXFIL0024 KGBFR0401B14 KGBFR0501B17 KGBFR0601B21 KGBFR0701B24 KGAFR0801SRE KGAWF1306UFR KGAWF1406UFR KGAWF1506UFR KGAFE0112UPH KGASB0201ALL KGBVG0101DFG KGAVE0101DNH KGACA02014FC KGACA02015FC KGANP4601ALL KGAPN3901ALL KGALB0101KIT KGASD0301FMS KGAFP0301APM KGAHA5801PSW LH32DB207 LH32DB202 LH32DB200 LH32DB205 LH32DB208 LH32DB078 LH32DB076 LH32DB203 LH32DB201 LH32DB206 LH32DB209 LH32DB210
036070 X
X
X
X
X
X X
X X X X X X X X X X X
048090 X
X
X
X
X
X X
X X X X X X X X X X X
060110 X
X
X
X
X X X X X X X X X X X X X X
066135
X
X
X
X
X X
X X X X X X X X X X X X
See Installation Instructions for model, altitude, and heat value usages.
Model UVL Models HRV or ERV
Model HUM Model EACA or EZXCAB
* Factory authorized, field installed. Fuel conversion kits are CSA (Formerly AGA/CGA) recognized. Suitable for Side Return Filter Rack. X = Accessory S = Standard
066155
X
X
X
X
X X
X X X X X X X X X X X X
6
315AAV/JAV
CONTROLS - THERMOSTAT AND ZONING
DESCRIPTION NON-PROGRAMMABLE For use with 1-speed Air Conditioner --- deg. F/C, Auto Changeover For use with 1-speed Heat Pump --- deg. F/C, Auto Changeover For use with 2-speed Air Conditioner --- deg. F/C, Auto Changeover For use with multi-use / stage configurations --- deg. F/C, Auto Changeover/Temperature and Humidity Control PROGRAMMABLE THERMOSTAT SELECTION For use with 1-speed Air Conditioner --- deg. F/C, Auto Changeover, 7-Day Programmable For use with 1-speed Heat Pump --- deg. F/C, Auto Changeover, 7-Day Programmable For use with 2-speed Air Conditioner --- deg. F/C, Auto Changeover, 7-Day Programmable For use with 1-speed Air Conditioner --- deg. F/C, 5--- 2 Day Programmable For use with multi-stage applications --- deg. F/C, Auto Changeover, 7-Day Programmable For multi-use / stage configurations --- deg. F/C, Auto Changeover, 7-Day Programmable/Temperature and Humidity Control ZONING CONTROL SELECTION Zone Perfect 3-Zone kit Zone Perfect Plus 2-Zone kit/Temperature and Humidity Control Zone Perfect Plus 4-Zone kit/Temperature and Humidity Control Zone Perfect Plus 8-Zone kit/Temperature and Humidity Control EVOLUTIONt** CONTROLS Evolutiont Control Deluxe 7-Day Programmable (Wall-mounted system control.) Evolutiont Control Deluxe Zoning 7-Day Programmable (Wall-mounted control for a multi-zone system.) Evolutiont 4-Zone Damper Control Module (Wall-mounted control for a four-zone system.) Evolutiont Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.) Evolutiont Remote Room Sensor (Monitors temperature in an individual zone.)
Evolutiont System Access Module (Hardware for wireless access and control via phone or internet.)
Evolutiont Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators or older two-speed outdoor models to system.)
Decorative Back Plate for Evolutiont Control (Decorative wall plate.)
PART NO.
T6--- NAC, T2--- NAC T6--- NHP, T2--- NHP* T6--- NRH* T6--- PRH
T6--- PAC T6--- PHP* T6--- PRH* T6--- PAC T2--- PHP T6--- PRH
ZONEBB3ZAC01, ZONEBB3ZHP01 ZONEBB2KIT01-B ZONEBB4KIT01-B ZONEBB8KIT01-B
SYSTXBBUID01 SYSTXBBUIZ01 SYSTXBB4ZC02 SYSTXBBSMS01
SYSTXBBRRS01 SYSTXBBSAM01 SYSTBBNIM01
SYSTXXXBPU01
* Model HP and 2S thermostat must be field converted to air conditioner operation. Thermidistat Control can be configured for multiple use and staging. It must be configured for each specific application. Dual Fuel thermostat is used with furnace and heat pump application. ** When applied with Bryant's Perfect Humidityt series 355AAV, 315AAV/JAV and FE Indoor Models Must be installed in Dual-Fuel Evolution system applications.
MODEL NUMBER NOMENCLATURE
315
A
A
V
066
135
A
E
JA
Bryant Type Code Gas Furnace, 4--- Way Multipoise, 80% Fixed--- Capacity
Model Code A = Standard J = Low NOx
Electrical Supply A = 110 to 125 Volts
Variations
Cooling Capacity 024 --- 800 CFM 036 --- 1200 CFM 042 --- 1400 CFM 048 --- 1600 CFM 060 --- 2000 CFM 066 --- 2200 CFM
Series A B C D E F
Brand Name A --- Common Unit
Heating Size (Btuh) 045 --- 45,000 070 --- 70,000 090 --- 90,000 110 --- 110,000 135 --- 135,000 155 --- 155,000
Variations
7
315AAV/JAV
SEE NOTES: 1,2,4,7,8,9 UPFLOW
A02058
SEE NOTES: 1,2,3,4,7,8,9 UPFLOW
A02059
SEE NOTES: 1,2,4,5,7,8,9 DOWNFLOW
A02061
SEE NOTES:1,2,3,4,5,7,8,9 DOWNFLOW
A02060
SEE NOTES: 1,2,3,4,5,7,8,9 DOWNFLOW
A02063
SEE NOTES: 1,2,4,5,6,7,8,9 DOWNFLOW
A02062
Venting Notes 1. For common vent, vent connector sizing and vent material: United States, latest edition of the National Fuel Gas
Code (NFGC), ANSI Z223.1/NFPA 54. 2. Immediately increase to 5-in. (127 mm) vent connector outside furnace casing when 5-in. (127 mm) vent connector
required, refer to Note 1. 3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace,
except when Downflow Vent Guard is used in downflow position.
4. Type B vent where required, refer to Note 1. 5. 4--- in. (102 mm) single wall vent must be used inside furnace casing and the Downflow Vent Guard Kit. 6. Accessory Downflow Vent Guard Kit required in downflow installations with bottom vent configuration. 7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kits for sizing
and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, space approximately 180° apart.
9. Secure all other single wall vent connector joints with (3) corrosion-resistant screws spaced approximately 120° apart. Secure Type B vent connectors per vent connector manufacturer's recommendations.
8
315AAV/JAV
SEE NOTES: 1,2,4,5,7,8,9 HORIZONTAL RIGHT
A02068
SEE NOTES: 1,2,4,5,7,8,9 HORIZONTAL RIGHT
A02070
SEE NOTES: 1,2,4,7,8,9 HORIZONTAL RIGHT
A02069
SEE NOTES: 1,2,4,7,8,9 HORIZONTAL LEFT
A02064
SEE NOTES: 1,2,4,5,7,8,9 HORIZONTAL LEFT A02065
SEE NOTES: 1,2,4,5,7,8,9 HORIZONTAL LEFT
A02066
SEE NOTES: 1,2,4,5,7,8,9 HORIZONTAL LEFT
A02067
9
315AAV/JAV
GUIDE SPECIFICATIONS
Gas Furnace
315AAV/JAV
General
SYSTEM DESCRIPTION
Furnish a _________________ fixed capacity gas-fired furnace for use with natural gas or propane (factory authorized conversion kit required for propane). QUALITY ASSURANCE
Unit will be designed, tested and constructed to the current ANSI Z 21.47/CSA 2.3 design standard for gas-fired central furnaces.
Unit will be 3rd party certified by CSA to the current ANSI Z 21.47/CSA 2.3 design standard for gas-fired central furnaces.
Unit will carry the CSA Blue StarR label. Unit efficiency testing will be performed per the current DOE test procedure as listed in the Federal Register. Unit will be certified for capacity and efficiency and listed in the latest AHRI Consumer's Directory of Certified Efficiency Ratings. Unit shall carry the current Federal Trade Commission Energy Guide efficiency label. DELIVERY, STORAGE AND HANDLING
Unit shall be shipped as single package only and is stored and handled per unit manufacturer's recommendations. WARRANTY (for inclusion by specifying engineer)
U.S. only. Warranty certificate available upon request. Products
EQUIPMENT
Components shall include: slow-opening gas valve to reduce ignition noise, regulate gas flow, with electric switch gas shut-off; flame proving sensor, hot surface igniter, pressure switch assembly, flame rollout switch, blower and inducer assembly, 40va transformer; low- voltage (heating) (heating/cooling) thermostat.
Blower Wheel and Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and dynamically balanced. Variable- speed ECM blower motor shall be permanently lubricated with sealed bearings, of _______hp, and shall be multiple-speed direct drive. Blower motor shall be soft mounted to the blower scroll to reduce vibration transmission.
Filters
Furnace may have reusable-type filters. Filter shall be _______ in. (mm) (x) _______in. (mm).
Casing
Casing shall be of .030- in. (.76 mm) thickness minimum, pre- painted galvanized steel.
Inducer Motor
Inducer motor shall be soft mounted to reduce vibration transmission.
Draft Safeguard Switch
Draft Safeguard Switch (blocked vent safeguard) shall be factory installed to reduce the possibility of vent gas infiltration due to a blocked or restricted vent pipe.
Heat Exchangers
Heat exchangers shall be a 4-Pass 20 gage aluminized steel of fold-and-crimp sectional design when applied operating under negative pressure.
Controls
Control shall include a micro-processor based integrated electronic control board with at least 11 service troubleshooting codes displayed via enhanced flashing LED diagnostic light on the control, a self-test feature that checks all major functions of the furnace within one minute, and a replaceable automotive-type circuit protection fuse. Multiple operational settings available including, separate blower speeds for low heat, high heat, low cooling, high cooling and continuous fan. Continuous fan speed may be adjusted from the thermostat. Cooling airflow will be selectable between 350 or 400 CFM per ton of air conditioning. Features will also include temporary reduced airflow in the cooling mode for improved dehumidification when an Evolutiont Control or ThermidistatR is selected as the thermostat. OPERATING CHARACTERISTICS
Heating Capacity shall be ________ Btuh input; ________ Btuh output capacity.
Fuel Gas Efficiency shall be 80% AFUE. Air delivery shall be ___________ CFM minimum at 0.50 In. W.C. external static pressure. Dimensions shall be: depth __________ in. (mm); width _________ in. (mm); height_________in. (mm) (casing only). Height shall be_________in. (mm) with A/C coil and _____________in. (mm) overall with plenum. ELECTRICAL REQUIREMENTS
Electrical supply shall be 115 volts, 60 Hz, single- phase (nominal). Minimum wire size shall be_________AWG; maximum fuse size or circuit breaker shall be __________Amps. SPECIAL FEATURES
Refer to section of the product data sheet identifying accessories and descriptions for specific features and available enhancements.