ENGLISH

QUICK GUIDE
Refer to the User's Guide for full instructions.

IXIO-DT1
MOTION AND PRESENCE SENSOR FOR
AUTOMATIC SLIDING DOORS
Software version 6.3 / Configuration 42.4463.03 (refer to Admin menu for product software vesion)

!

READ BEFORE BEGINNING INSTALLATION & SETUP

!

The sensor should be mounted securely to avoid extreme vibrations.

Do not cover the sensor.

Avoid moving objects and light sources in the detection field.

Avoid highly reflective objects in the infrared field.

The door control unit and the header cover profile must be correctly grounded.

Only trained and qualified personnel are recommended for installation and setup of the sensor.

Following installation, always test for proper operation (according to ANSI 156.10) before leaving the premises.

The warranty is invalid if unauthorized repairs are made or attempted by unauthorized personnel.

This device can be expected to comply with Part 15 of the FCC Rules, provided it is assembled in exact accordance with the instructions provided with this kit. Operation is subject to the following conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

1 MOUNTING & WIRING

Refer to Application Note 76.0035 if an IXIO Spacer is required for the given application.

SENSOR

DOOR CONTROL

RED BLACK BROWN BLUE WHITE (COM)

POWER SUPPLY POWER SUPPLY
SAFETY INPUT SAFETY INPUT OPENING INPUT

POWER 12 � 24 VAC/VDC 12 � 30 VDC 2.5 W (max)

max. 2 in

YELLOW (N.C) GREEN (N.O.) PURPLE PURPLE

OPENING INPUT OPENING INPUT
TEST OUTPUT* TEST OUTPUT*

TEST low: < 1 V high: > 10 V (30 V max.) response time: typ. < 5 ms

Sensor connectivity (power and relays) must utilize only the supplied harness.
Sensor power must be supplied from a Class 2 supply source limited to 15 W.
Sensor is intended to be monitored for proper operation by the door operator or system.
Harness shall be routed separated from any Mains or non-Class 2 voltage cable for correct operation or shall be rated for the Mains voltage, and suitable protection and routing means shall be used according to National and Local Codes to prevent damage
to the harness and/or IXIO sensor.

75.1219.02 IXIO-DT1 QG 20240722

Page 1 of 4

2 RADAR OPENING IMPULSE FIELD
ANGLE

WIDTH

TILT

ROTATE

3 INFRARED SAFETY FIELD

ANGLE

Activate the visible spots.
WIDTH

or WIDE

or NARROW

DOOR C1 C2
max. 3 in

CLOSER
AWAY Adjust the angle, if necessary.

Always verify the actual detection field width by walk-testing according to ANSI 156.10.

4 SETUP

STEP OUT OF THE INFRARED FIELD!

SETUP 1 (QUICK) reference picture
either hold the knob for 2 seconds, or use the remote control buttons as specified

+

2 s OR

SETUP 2 (ASSISTED) test of full door cycle + reference picture
either hold the knob for 4 seconds, or use the remote control buttons as specified

+

+

4 s OR

TEST THE PROPER OPERATION OF THE INSTALLATION BEFORE LEAVING THE PREMISES!

COLORS
(green) Motion detection

Page 2 of 4

(red) Presence detection

LED SIGNALS BEHAVIORS

LED flashes

LED flashes red-green

LED flashes quickly x LED flashes x times

LED is off 75.1219.02 IXIO-DT1 QG 20240722

OVERVIEW OF SETTINGS

RC BUTTONS

01 23456789
Back More

RAD: FIELDSIZE

small

>

>

>

>

>

>

>

>

large

RAD: SHAPE

LCD: "narrow" and "wide" setting options (default = wide)

Remote Control:

= wide,

= narrow

AIR: WIDTH

see note 1

AIR: OUTPUT
TEST More Back

DeEner/NO Energ/NC

NC

NO

Energ/NC DeEner/NO

NC

NO

off

on on+auto

see note 2 see note 3

BASIC

+ +

Back More

RAD: FIELDSIZE small

>

>

>

>

>

RAD: IMMUNITY

low

>

>

>

>

RAD: DIRECTION off

bi

uni

MTF

RAD: HOLDTIME auto

1 s

2 s

3 s

4 s

5 s

RAD: REENTRY

small

>

>

>

>

>

RAD: OUTPUT

DeEner/NO Energ/NC

NC

NO

Energ/NC DeEner/NO

NC

NO

AIR: IMMUNITY

normal enhanced

AIR: WIDTH

>

>

>

large

>

>

>

high

uni + reentry

see note 4

6 s

7 s

8 s

9 s see note 5

>

>

>

large

see note 2

mode B

see note 1

ADVANCED

AIR: NUMBER AIR: PRESENCE TIME AIR: FREQ

1

2

30 s 1 min 2 min 5 min 10 min 20 min 60 min infinte

A

B

AIR: OUTPUT TEST REDIRECTION

DeEner/NO Energ/NC

NC

NO

Energ/NC DeEner/NO

NC

NO

off

on on+auto

R1 MW R1MWorIR

R2 IR

R2 IR

see note 2 see note 3 see note 6

FACTORY RESET

full reset

partial reset

see note 7

Back More

factory value

motion (green)

presence (red)

ZIP CODE ID # CONFIG P/N

all parameter settings in zipped format (see application note on ZIP CODE � 76.0024) unique ID-number

Download the BEA DECODER app for a quick overview of settings

SOFT P/N

ERROR LOG

last 10 errors + day indication

AIR: SPOTVIEW view of spot(s) that trigger detection

AIR: C1 ENERG signal amplitude received on curtain

AIR: C2 ENERG signal amplitude received on curtain 2 POWERSUPPLY supply voltage at power connector OPERATINGTIME power duration since first startup

RESET LOG PASSWORD ADMIN

delete all saved errors LCD and remote control password (0000= no password) enter code to access admin mode

75.1219.02 IXIO-DT1 QG 20240722

Page 3 of 4

DIAGNOSTICS

OVERVIEW OF SETTINGS (cont.)

Note 1 Note 2
Note 3
Note 4 Note 5 Note 6
Note 7

Always use a screwdriver when making further AIR adjustments to the arrow position on the sensor.

RADAR

AIR

NO = normally open NC = normally closed DeEner = de-energized relay (active) Energ = energized relay (passive)

NO = normally open NC = normally closed

The sensor LED will briefly flash RED during monitoring communication with door control. This indicates that external monitoring is functional. Monitoring functionality must be active on the sensor and door control, and monitoring wires must be properly connected to the door control.

MTF = uni-directional with motion-tracking feature uni + reentry: BEA recommends only adjusting using the LCD

Auto mode evaluates traffic rate and adjusts hold time from 0.5 to 3 seconds

REDIRECTION setting (F1 on remote control):

R1-MW, R2-IR (f1=0): R1 = MW (i.e. motion detection) R2 = IR (i.e. presence detection)
partial: outputs are not reset

R1-MW or IR, R2-IR (F1=1): R1 = MW or IR (i.e. motion or presence detection) R2 = IR (i.e. presence detection)

TECHNICAL SPECIFICATIONS

Output
Test/Monitoring input: Supply voltage: Mounting height:

Relay 1

Relay 2

Electromechanical relay (potential and polarity free) Max. contact current: 1 A Max. contact voltage: 30 VAC Adjustable hold time: 0.5 � 9 s

Solid-state relay (potential and polarity free) Max. contact current: 100 mA Max. contact voltage: 42 VDC / 30 VAC

Sensitivity: Low: < 1 V High: > 10 V (max. 30 V)
Response time on test request: typical < 5 ms

12 � 24 VAC �10% 12 � 30 VDC �10% to be operated from SELV-compatible power supplies only

6'6" � 11'6" local regulations may impact acceptable mounting height (pedestrian applications only)

Specifications are subject to change without prior notice. All values measured in specific conditions.

�BEA | Original Instructions | PLEASE KEEP FOR FURTHER USE - DESIGNED FOR COLOR PRINTING

BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
BEA, Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or incorrect adjustments of the sensor/device; therefore, BEA, Inc. does not guarantee any use of the sensor/device outside of its intended purpose.
BEA, Inc. strongly recommends that installation and service technicians be AAADM-certified for pedestrian doors, IDA-certified for doors/ gates, and factory-trained for the type of door/gate system.
Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor/device system performance is compliant with local, national, and international regulations, codes, and standards.
Once installation or service work is complete, a safety inspection of the door/gate shall be performed per the door/gate manufacturer's recommendations and/or per AAADM/ANSI/DASMA guidelines (where applicable) for best industry practices. Safety inspections must be performed during each service call � examples of these safety inspections can be found on an AAADM safety information label (e.g. ANSI/DASMA 102, ANSI/DASMA 107, UL294, UL325, and International Building Code).
Verify that all appropriate industry signage, warning labels, and placards are in place.

Tech Support: 1-800-407-4545 | Customer Service: 1-800-523-2462 General Tech Questions: techservices-us@BEAsensors.com | www.BEAsensors.com

Page 4 of 4