SWG SIDEWALL POWER VENTING KIT
Installation Specifications For The Following Furnaces
Certified As A Component Part of The Furnace Application.

This instruction sheet contains OEM specific information that supercedes the provided instruction manual where applicable. All field wiring shown in included wiring diagrams are correct regardless whether the CK-43 or CK-43F is used.

Contents

Kit P/N

Furnace Manufacturer

Page

46205411 Amana Refrigeration Inc.

2

46205405 American Standard Inc. & The Trane Co.

4

46205407 Armstrong Air Conditioning Inc.

6

46205410 Bard Manufacturing Co.

7

46205403 Carrier Corp.

8

46205408 Consolidated Industries Corp.

10

46205406 Dunkirk Radiator Corp.

11

Evcon Industries Inc.

13

46205401 International Comfort Products (Adjustable) 14

46205413 International Comfort Products (Fixed)

16

46205402 Lennox International Inc.

17

46205409 Rheem Air Conditioning

18

46205404 York International Corp.

19

Field Controls, L.L.C., 2630 Airport Road, Kinston, NC 28504 Technical Support (800) 742-8368

SWG-4AM AMANA SIDEWALL POWER VENTING KIT Field Controls P/N 46205411

Kit Includes: SWGII-4HD Sidewall Power Venter CK-43 Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Adjustable Post Purge

Recommended For Use On The Following Amana Model Furnaces:

GBI GCIC GUI GUID GCI GHI GUIA GCIA GMI GUIB GCIB GSI GUIC

NOT For Use On The Following Amana Model Furnaces:

GCIS GUIS GUIV

Furnace Configuration and Vent Pipe Restrictions
Type B-1 vent pipe shall be used to join the furnace to the venting system and for the entire length of the venting system. Exception: Up to 24" of single wall vent pipe may be used to connect the furnace to the barometric damper. The barometric damper tee may be single wall. Type B-1/double wall vent pipe MUST be used from the barometric damper tee to the power venter.

For Furnace Models GUIA, GUIB, GUIC, and GUID

BTU/Hr. Diameter of

Installer

Maximum

Flue Collar Provided Flue Equivalent Length

on Furnace Pipe Transition (ft.) for 4" Vent Pipe

Size Diameters

46,000

4"

None

100

69,000

4"

None

100

92,000

4"

None

100

115,000

4"

None

85

138,000

4"

None

65

Maximum Equivalent Length (ft.) for 5" Vent Pipe
100 100 100 95 80

For Furnace Models GCIA, GCIB, and GCIC

BTU/Hr. Diameter of

Installer

Maximum

Flue Collar Provided Flue Equivalent Length

on Furnace Pipe Transition (ft.) for 4" Vent Pipe

Size Diameters

46,000

3"

3" to 4"

100

69,000

3"

3" to 4"

100

92,000

3"

3" to 4"

100

115,000

3"

3" to 4"

85

138,000

3"

3" to 4"

65

Maximum Equivalent Length (ft.) for 5" Vent Pipe
100 100 100 95 80

Page 2

For Furnace Models GBI, GCI, GHI, GSI, and GUI

BTU/Hr. Diameter of

Installer

Maximum

Flue Collar Provided Flue Equivalent Length

on Furnace Pipe Transition (ft.) for 4" Vent Pipe

Size Diameters

45,000

3"

3" to 4"

100

70,000

3"

3" to 4"

100

90,000

3"

3" to 4"

100

115,000

4"

None

85

140,000

4"

None

65

Maximum Equivalent Length (ft.) for 5" Vent Pipe
100 100 100 95 80

For Furnace Models GMI

BTU/Hr. Diameter of

Installer

Flue Collar Provided Flue

on Furnace Pipe Transition

Size Diameters

40,000

3"

3" to 4"

60,000

4"

None

80,000

4"

None

100,000

4"

None

120,000

4"

None

140,000

4"

None

Maximum Equivalent Length (ft.) for 4" Vent Pipe
100 100 100 100 80 60

Maximum Equivalent Length (ft.) for 5" Vent Pipe
100 100 100 100 90 80

General Wiring

For complete installation information refer to the Field Controls SWG-4AM Power Venter Installation Manual for details (P/N 46333300.)
Page 3

SWG-4AT AMERICAN STANDARD AND TRANE SIDEWALL POWER VENTING KIT Field Controls P/N 46205405

Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge

For Use With The Following American Standard And Trane Furnaces:

AUD-C TUD-C AUD-R TUD-R

CUE-A TUE-A ADD-C TDD-C

ADD-R TDD-R CDE-A TDE-A

Furnace Configuration And Vent Pipe Restrictions:

Furnace Input BTU/Hr 40,000 60,000 80,000 100,000 120,000 140,000

Diameter Of Vent Pipe Collar On Furnace (In.)
4 4 4 4 4 4

Maximum Equivalent Vent Length (Ft.) 65 65 65 65 65 65

General Wiring

Refer to the Diagrams on the following page for guidance in wiring the Power Venter and Control Kit to the appliance.

For complete installation information refer to the Field Controls SWG-4AT Power Venter Installation Manual for details (P/N 46306700.)

Page 4

Page 5

SWG-4A ARMSTRONG SIDEWALL POWER VENTING KIT
Field Controls P/N 46205407
Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge

For use with Armstrong furnace models that begin with the following:

AMEG6G EG5G EG6G EG7G EG8G GCJ GHJ GUJ

Furnace Configuration and Vent Pipe Restrictions

Model Number
AMEG6G EG5G EG6G EG7G EG8G GCJ GHJ GUJ

Configuration
Upflow Lowboy Upflow Downflow Horizontal Downflow-Horizontal Upflow-Horizontal Upflow

Furnace Vent Collar Diameter
(in.) 4 4 4 4 4 4 4 4

Max. Equivalent Vent Length (ft.); 4" Diameter
Vent Pipe 60 60 60 60 41 60 60 60

General Wiring

For complete installation information refer to the Field Controls SWG-4A Power Venter Installation Manual for details (P/N 46333500.)
Page 6

SWG-4B BARD SIDEWALL POWER VENTING KIT Field Controls P/N 46205410

Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge
For Use With The Following Bard Standard Furnaces:

Upflow IH60D36 (A,B) IH85D48 (A,B,D) IH115D48 (A,B)
IH115D60A IH145D60A

Downflow IC60D36A IC85D42 (A,D) IC115D48A
-----------

Lowboy ------
IL85D42 (A,D) IL115D48A -----IL145D60A

Unit Selection Table:

Furnace Input

Diameter Of Vent Installer Provided Flue Maximum Equivalent

Btu/Hr

Pipe Collar On

Pipe Transition Size*

Vent Length (Ft.)

Furnace (In.)

4" Vent Pipe

58,000

3"

3"-4"

65

86,000

4" **

3"-4" ***

65

115,000

4"

None Required

65

145,000

4"

None Required

65

*

Transition should be attached to the furnace vent pipe collar if required.

** 86,000 Btu models with A or B suffix letter have 3" collars.

*** 86,000 Btu models with D suffix have 4" collars and do not require a 3" to 4" transition.

General Wiring

For complete installation information refer to the Field Controls SWG-4B Power Venter Installation Manual for details (P/N 46332100.)

Page 7

SWGII-4CC CARRIER SIDEWALL POWER VENTING KIT Field Controls P/N 46205403, Carrier P/N KGASW03012SP

Kit Includes: SWGII-4HD Sidewall Power Venter CK-43CC Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge

For Use With The Following Carrier Furnace Models:

58UXT 58WAV

58DXT 58ZAV

58UXV 58PAV

58UHV 58RAV

58TUA 58TMA GB1AAV GB3AAV

For Use With The Following BDP Furnace Models:

330JAV 331JAV 333JAV 333BAV 330AAV 331AAV 395CAV 376CAV 383KAV 373LAV 480BAV 481BAV GB1AAV GB3AAV

For All Single-Furnace Systems: Use one SWGII-4CC Kit for each furnace, and do not common-vent with other appliance(s). To common-vent these furnaces with other appliances, use SWGII-4HD Kit with instruction P/N 46139100 and a CK Series Control Kit for each appliance.

For All Two-Stage furnaces: When setting up a two-stage furnace, the furnace should be operating on HIGH-STAGE HEAT while adjusting the sidewall power venter airflow adjustment damper, draft control, and proving switch.

VENTING INSTALLATION OPTIONS

FURNACE MODELS

4-in. dia. Type B-1 vent up 3-in. dia. Type B-1 vent up to 40 ft. Draft Safeguard

to 40 ft. long, up to 4

long, up to 4 elbows, and 1 tee § Switch Assembly

elbows, and 1 tee §

Two-Stage models 58UXT 330JAV 58DXT 331JAV 58UXV 333JAV 58UHV 333BAV 58TUA 330AAV 58TMA 331AAV

PERMITTED WITH ALL GAS INPUT SIZES

PERMITTED WITH ALL GAS INPUT SIZES 

A 5"-to-4" reducer is required between furnace and vent for inputs greater
than 105,000 Btu/hr.

A reducer is required between furnace and vent for these inputs: up through 105,000 Btu/hr 4"-to-3" more than 105,000 Btu/hr 5"-to-3".

PERMITTED WITH OR
WITHOUT THE DRAFT
SAFEGUARD *

Single-Stage models 58WAV 395CAV 58ZAV 376CAV 58PAV 383KAV 58RAV 373LAV GB1AAV 480BAV GB3AAV 481BAV

PERMITTED WITH ALL PERMITTED WITH GAS INPUTS

GAS INPUT SIZES

OF 88,000 Btu/hr AND LESS 

A 5"-to-4" reducer is required between furnace and vent for inputs greater
than 115,000 Btu/hr.

A 4"-to-3" reducer is required between furnace and vent.

PERMITTED ONLY WITH THE DRAFT SAFEGUARD 

Page 8

* The furnace's Draft Safeguard switch assembly can remain in place as installed at the factory, or the Draft Safeguard switch assembly can be removed (relief box opening sealed with Block-off Plate and switch replaced with Splice Connector from Kit KGASW0101/02012SP).
 The Draft Safeguard switch assembly must remain installed and operational in the furnace. § See Equivalent Length Table II. Fewer elbows permit longer straight length & vice-versa.  3"-to-4" increaser is required between vent pipe and power venter. General Wiring:
For complete installation information refer to the Field Controls SWGII-4CC Power Venter Installation Manual for details (P/N 46295100.)
Page 9

SWG-4CD CONSOLIDATED SIDEWALL POWER VENTING KIT Field Controls P/N 46205408
Kit Includes: SWGII-4HD Sidewall Power Venter WMO-1 Thermal Safety Switch (Must be purchased separately if using other venting kit on Consolidated Furnaces.) CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge
For use with the following series of furnaces:

This furnace was built by CONSOLIDATED

INDUSTRIES under the names: QUATRO, TECH-4,

QUADPRO, QUADTECH, MULTIFLOW, BRENTWOOD,

and SUNBURST.

Model Numbers:

MAA040NR2R MBA040NH2R MCA040NR2R MDA040NH2R

MAA040NR3R MBA040NH3R MCA040NR3R MDA040NH3R

MAA060NR2R MBA060NH2R MCA060NR2R MDA060NH2R

MAA060NR3R MBA060NH3R MCA060NR3R MDA060NH3R

MAA060NR4R MBA060NH4R MCA060NR4R MAA080NR2R MBA080NH2R MCA080NR2R MAA080NR3R MBA080NH3R MCA080NR3R

MDA060NH4R MDA080NH2R MDA080NH3R

MAA080NR4R MBA080NH4R MCA080NR4R MDA080NH4R

MAA080NR5R MBA080NH5R MCA080NR5R MDA080NH5R

MAA100NR3R MBA100NH3R MCA100NR3R MDA100NH3R

MAA100NR4R MBA100NH4R MCA100NR4R MDA100NH4R

MAA100NR5R MBA100NH5R MCA100NR5R MDA100NH5R

MAA120NR4R MBA120NH4R MCA120NR4R MDA120NH4R

MAA120NR5R MBA120NH5R MCA120NR5R MDA120NH5R

MAA140NR4R MBA140NH4R MCA140NR4R MDA140NH4R MAA140NR5R MBA140NH5R MCA140NR5R MDA140NH5R

Note: Model numbers may have suffix "X".

This kit may also be used with furnaces manufactured by

Consolidated Industries and sold by a number of other companies

under their names.

General Information:

Page 10

This furnace was built by CONSOLIDATED INDUSTRIES under the name PREMIER.
Model Numbers:
HBA040NR3R HBA060NR4R HBA080NR4R HBA100NR5R HBA120NR5R
Note: Model numbers may have suffix "X". This kit may also be used with furnaces manufactured by Consolidated Industries and sold by a number of other companies under their names.

1. Maximum equivalent vent length is 63 feet for all furnaces listed! 2. The SWG-4CD power venter kit must be installed using type B-1 vent pipe only!
General Wiring

For complete installation information refer to the Field Controls SWG-4CD Power Venter Installation Manual for details (P/N 46333600.)

SWG-4D DUNKIRK SIDEWALL POWER VENTING KIT Field Controls P/N 46205406

Kit Includes: SWGII-4HD Sidewall Power Venter CK-43D Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Adjustable post purge

For use with the Dunkirk Radiator Boiler Models XEB 2-5 or Equivalent* *To determine equivalent models, call (716)366-5500 and ask for Technical Service Department
Unit Sizing and Equivalent Footage

Max. Horizontal Vent Run

Min. Horizontal Vent Run

50'+ Tee with a 3"x4" increaser for the barometric draft control + 3"x4" increaser with
power venter

2'+ 90° elbow + tee with a 3"x4" increaser for the barometric draft control + 3"x4" increaser with power venter

For additional elbows, reduce the maximum vent length as follows:

Page 11

3" x 90° elbow - reduce vent length by 3 feet for each elbow Standard 3" single walled galvanized venting or 3" Type B vent pipe should be used. Draft Control Installation: 1. Install a 3" vent pipe tee of the same material as the vent piping 12" to 24" away from the
outlet of the boiler's blower. Then place a 3"X4" reducer in the tee for mounting the barometric draft control as shown in the Figure below. 2. Seal the vent pipe tee and reducer using the sealing and joining procedures in the boiler installation instructions. Seal the barometric draft control into the tee using the same high temperature silicone as used on the vent piping. 3. The front face of the control MUST be plumb and the bearing surfaces MUST be level whether the control is on a horizontal, vertical, or sloping vent pipe. Use a spirit level and level accurately. If necessary, the control may be held in place by sheet metal screws.
Dunkirk instructions continued on next page.
Page 12

General Wiring
For complete installation information refer to the Field Controls SWG-4D,5D Power Venter Installation Manual for details (P/N 46298400.)
SWG-4E EVCON SIDEWALL POWER VENTING KIT Field Controls Standard Model SWGII-4HD and CK-43F
Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge
For Use On The Following Evcon Series of Furnace Models: 2800 AGU BGU
Page 13

General Wiring:
For complete installation information refer to the Standard Field Controls SWG/SWGII series Power Venter Installation Manual (P/N 46139100), and the CK-43F Control Kit Installation Manual (P/N 46285100) for details.
SWG-4IC INTER-CITY SIDEWALL POWER VENTING KIT Field Controls P/N 46205401
Kit Includes: SWGII-4HD Sidewall Power Venter CK-43 Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Adjustable Post purge
For Use With The Following Furnace Models: GDJ GDL GNI GNJ GNL CUGE CUG5 NCC5 NDC7 NDN5 NTC5 NTC7 NTN5 NUG5
Page 14

Unit Sizing:

BTU/HR Input

Diameter Of Vent Pipe To

Flue Pipe Transition Size

Power Venter

Diameter

50,000

3"

3" TO 4"

75,000

4"

None Required

100,000

4"

None Required

125,000

4"

None Required

Maximum Pipe Length - (3) 90° Elbows, 30 feet of vent pipe and reducer or increaser if required.

Minimum Pipe Length - (1) 90° Elbow, 5 feet of vent pipe and a reducer or increaser if required.

General Wiring

For complete installation information refer to the Field Controls SWG-4IC Power Venter Installation Manual for details (P/N 46201400.)
Page 15

SWG-4ICF INTER-CITY SIDEWALL POWER VENTING KIT Field Controls P/N 46205413

Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge

For Use With The Following Series Of Furnaces

GDJ NCC5

GDL NDC7

GNI NDN5

GNJ NTC5

GNL NTC7

CUGE NTN5

CUG5 NUG5

Unit Selection Table

BTU/HR Input 50,000 75,000
100,000 125,000

Diameter Of Vent Pipe To Power Venter 3" 4" 4" 4"

Flue Pipe Transition Size Diameter 3" TO 4"
None Required None Required None Required

General Wiring

For complete installation information refer to the Field Controls SWG-4ICF Power Venter Installation Manual for details (P/N 46319700.)
Page 16

SWG-4L LENNOX SIDEWALL POWER VENTING KIT
Field Controls P/N 46205402
Kit Includes: SWGII-4HD Sidewall Power Venter CK-43 Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Adjustable post purge

For Use On The Following Lennox Series Furnaces: G23 G24M 80MGF

Unit Selection And Maximum Vent Length Table

BTU/Hr Input Diameter Of

Vent Pipe Collar

On Furnace

45,000*

3"

50,000

3"

60,000*

3"

75,000*

4"

100,000*

4"

120,000*

4"

125,000

5"

140,000*

4"

150,000

5"

*G24M/80MGF Input Rates

Installer Provided Flue Pipe Transition
Size Diameters 3" to 4" 3" to 4" 3" to 4"
None Required None Required None Required
4" to 5" None Required
4" to 5"

Maximum Equivalent Length (Ft) For 4" Vent Pipe
60 60 60 60 60 60 60 48 35

Maximum Equivalent Length (Ft) For 5" Vent Pipe
60 60 60 60 60 60 60 60 60

General Wiring:

For complete installation information refer to the Field Controls SWG-4L Power Venter Installation Manual for details (P/N 46257600.)

Page 17

SWG-4R RHEEM SIDEWALL POWER VENTING KIT Field Controls P/N 46205409

Kit Includes: SWGII-4HD Sidewall Power Venter CK-43R Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge
For Use With The Following Rheem, Ruud, And Weatherking Model Series Furnaces:

(-)GDG* (-)GDJ* (-)GPJ* (-)GVJ* (-)GVA (-)GYA

(-)GVH* (-)GPH* (-)GLG (-)GLH* (-)GVG (-)GLJ* (-)GDC (-)GLC (-)GDE (-)GLE (-)GVC (-)GYC (-)GVB (-)GYB WGVAH WGVAG WGDAG WGLAG

*Indicated models are CGA certified with the SWG-4R as a vent system.

Indicated 45,000 and 67,500 BTU furnaces must not be auxiliary power vented unless the original vent pressure switch is replace with a 0.30 vent pressure switch, Rheem P/N 42-24064-01. Failure to replace the pressure switch as specified could lead to improper operation of the furnace resulting in property damage, personal injury, or death.

Application & Installation Notes:

1. READ THE POWER VENTER APPLICATION & INSTALLATION INSTRUCTIONS VERY CAREFULLY BEFORE ATTEMPTING TO INSTALL AND/OR OPERATE THE POWER VENTER.
2. Do not use this kit with HTPV or SVS vent pipe. Use only "B" type vent pipe. 3. Do not exceed 30 linear feet of type "B" vent pipe or maximum of three 90° elbows. 4. Carefully observe the minimum required % combustion efficiency and the maximum
measure flue gas temperature. 5. Each furnace must have a dedicated power venter. Common venting with more than one
appliance to a power venter is not permitted. 6. Note: Where a 3" to 4" and 4" to 6" vent pipe transitions are necessary, use only tapered
transitions. 7. The barometric draft control is supplied with the power venting kit. (It is required, but not
supplied with the Tjernlund kit.) Regardless of vent pipe diameter size, a 4" diameter gas furnace barometric draft control is required to be installed with in three (3) feet of the furnace cabinet. 8. Do not attempt to use this power venter on a furnace equipped with a draft hood or a vent damper. 9. Carefully observe ambient air temperature limitations.

Important:

Under no circumstances can any standing pilot furnace be horizontally vented. Under no circumstances can any additional appliances be common vented with the
furnace by the Field Controls SWG-4R. Under no circumstances can a furnace equipped with a natural draft diverter be
horizontally vented.

Page 18

Vent Specifications: 1. All vent pipe and elbows must be Type B, double wall vent. 2. The maximum vent length is 30 feet with a maximum of three 90° elbows. 3. The minimum vent length is 5 feet. 4. Use 3" vents for models with inputs through 75,000 BTU/Hr. 5. Use 4" vents for models with inputs over 75,000 BTU/Hr. 6. A 4" barometric damper is included in the power venter kit. When 3" vent pipe is used, a 3" to
4" single wall increaser is required for connecting the barometric damper and for connecting the power venter. A single wall increaser will also be required at the furnaces with 3" outlet collars when 4" vent pipe is used. General Wiring
For complete installation information refer to the Field Controls SWG-4R Power Venter Installation Manual for details (P/N 46331300.)
SWG-4Y YORK SIDEWALL POWER VENTING KIT Field Controls Part #46205404
Kit Includes: SWGII-4HD Sidewall Power Venter CK-43F Control Kit Includes: 4" MG-1 Barometric Draft Control Fan Proving Switch Fixed post purge
Approved For Use On The Following York International Model Furnaces: Page 19

P1UK P2MP P9MP P2DP P3UC P9UC P3CC P9CC PKMD PAKU PBKM XEM PBKD XED PCMU PKMU PCMD

Unit Sizing And Equivalent Footage
Refer to the following to choose the proper size vent pipe and fittings for connecting the SWG power venter to the appliance. The following table also lists the maximum equivalent length of vent pipe allowed, depending on the appliance input rating and the diameter of vent pipe used.

BTU/Hr Input
40,000 60,000 80,000 100,000 120,000 140,000

Diameter Of Vent Pipe Collar On Furnace

Installer Provided Flue Pipe Transition
Size Diameters

3"

3" TO 4"

3"

3" TO 4"

4"

None Required

4"

None Required

4"

None Required

4"

None Required

Maximum Equivalent Length (Feet) 4" Vent Pipe
100 100 100 100 80 65

General Wiring

For complete installation information refer to the Field Controls SWG-4Y Power Venter installation manual for details (P/N 46297600.)
P/N 46334200
Page 20

