Instruction Manual for POTTER models including: PAD100-SLCE Addressable Loop Expander, PAD100-SLCE, Addressable Loop Expander, Loop Expander, Expander
Potter Installation Manual PAD100-SLCE Addressable Loop Expander - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications
File Info : application/pdf, 2 Pages, 909.43KB
DocumentDocumentInstallation Manual: PAD100-SLCE Addressable Loop Expander NOTICE TO THE INSTALLER This manual provides an overview and the installation instructions for the PAD100-SLCE module. This module is only compatible with addressable fire systems that utilize the PAD Addressable Protocol. All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further information, refer to the control panel installation instructions. The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation. 1. Description The Signaling Line Circuit Expander allows up to thirty one additional loops. Each loop adds 127 addressable sensors or modules in any combination. The PAD100-SLCE may be configured for Class A or Class B wiring without the need for additional modules. The PAD100-SLCE communicates with the control panel via the 4-wire RS-485 communication bus. The loop adder is mounted in either the control panel cabinet, the intelligent power supply, AE-2, AE-8 or the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting 2. Setting the Address Each P-Link device has a five (5) position dip switch which is used to program the device address ranging from one (1) to thirtyone (31). The table below may be used to set dip switches when addressing any P-Link module: Figure 1. Dip Switch Settings Table (Addresses 131) 1 2 4 8 16 1 2 4 8 16 1 17 2 18 3 19 4 20 5 21 6 22 7 23 8 24 9 25 10 26 11 27 12 28 13 29 14 30 15 31 16 1 2 4 8 16 1 2 4 8 16 Note: Each "gray" box indicates that the dip switch is "On," and each "white" box indicates "Off." The examples shown below illustrate a P-Link's dip switch settings: the 1st example shows a P-Link module not addressed where all dip switch settings are in the default "Off" position, the 2nd illustrates an addressed P-Link module via the dip switch settings. Figure 2. Examples of P-Link Module Showing Default Dip Switch Setting (Unaddressed) & Addressed 1 2 4 8 16 All dip switches are On shown in the "Off" Off position. 1 2 4 8 16 On Off Example shows this P-Link module address = 10. Dip switches #2 & 8 are in the "On" position. Potter Electric Signal Company, LLC · St. Louis, MO · Phone: (800) 325-3936 Document 5406314-A 02/16 firealarmresources.com · www.pottersignal.com PAGE 1 OF 2 INSTALLATION MANUAL: PAD100-SLCE ADDRESSABLE LOOP EXPANDER Before connecting a device to the RS-485 connection, take the following precautions to prevent potential damage to the RS-485 connection or device. · Power to the RS-485 is removed. · Field wiring on module is correctly installed. · Field wiring has no open or short circuits. 3. Technical Specifications Standby Current Alarm Current SLC Voltage Max. SLC Resistance P-Link Voltage Operating Temperature Range Operating Humidity Range Max. no of PAD100-SLCE Dimensions 50mA 50mA 24 VDC 50 Ohms 24 VDC 32 to 120 F (0 to 49 C) 10% to 93% (non-condensing) 31 4" L x 6" W x 1 5/8" D 4. Installation The PAD100-SLCE is connected to the listed control panels using a four wire RS-485 connection. This connection is power limited and supervised. The PAD100-SLCE can be installed in the AE-2, AE-8, AE-14 expansion enclosure or inside the large listed fire alarm control panel enclosure using the supplied bracket. The wiring diagrams shown below illustrate how to wire a PAD100-SLCE as Class B and Class A. Figure 3. Examples of Wiring a PAD100-SLCE P-Link Class B & Class A Wiring To the next device Panel P-LINK Connection -+ A B Expansion Device - + AB Class A Expander Connection P-LINK -+ A B Panel P-LINK Connection -+ A B - + AB Expansion Device - + AB - + AB Expansion Device Notes: · RS-485 wiring style supports the Class A and Class B. · RS-485 wiring is power limited and supervised. · All wiring is between #12 (max.) and #22 (min.). · Wire Preparation Strip all wires 1/4 inch from their edges as shown here: Stripping too much insulation may cause a ground fault. Stripping too little may cause a poor connection and subsequently an open circuit. 1/4 inch Expansion Device These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection with installation, operation and maintenance. Specifications subject to change without prior notification. For Technical Assistance contact Potter Electric Signal Company at 866-956-1211. Actual performance is based on proper application of the product by a qualified professional. Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser's purpose, the matter should be referred to a distributor in your region. Potter Electric Signal Company, LLC · St. Louis, MO · Phone: (800) 325-3936 Document 5406314-A 02/16 firealarmresources.com · www.pottersignal.com PAGE 2 OF 2