PDSFE4A-12 FINAL

bac0760

PDSFE4A-12()

FAN COIL 2 TO 3-1/2 TON PURON VARIABLE SPEED ALUM EVOLUTION | Behler-Young

PDSFE4A-12
FE4A, FE5A EVOLUTIONr SERIES
COMMUNICATING VARIABLE-SPEED FAN COIL PURONr REFRIGERANT
SIZES 002 THRU 006
Product Data
PREMIUM ENVIRONMENTALLY RESPONSIBLE FAN COIL
The latest in technology makes the FE4A and FE5A fan coil models the most advanced air handlers available. With attention to quiet, efficient, and comfortable operation, Bryant has developed a new benchmark for homeowner comfort and ease of installation. The FE4A and FE5A utilize the Evolutionr Control as a required accessory to enable state of the art smart-diagnostics capability. This enables faster troubleshooting, providing ease of service and repair. The FE4A and FE5A also provide a 4-wire hook up with matching outdoor unit and the Evolutionr Control. This makes installation simpler and a lot quicker than with conventional fan coils. The FE4A and FE5A have advanced technology that allows the fan coil to self-configure with a matching outdoor unit and the Evolutionr Control, cutting down on installation time. The FE4A and FE5A feature Puronr refrigerant, the chlorine-free alternate that is the future for the residential heating and cooling industry. The FE4A and FE5A using PuronR refrigerant maximize performance for environmentally balanced systems. In addition to environmental safety, these systems are 30 to 40% more efficient than standard heating and cooling systems, thereby combining excellence in efficiency and environmental responsibility.
The FE4A and FE5A provide these benefits due to Bryant's command of Electronically Commutating Motor (ECM) technology. These motors are extremely efficient at all speeds, and enable the FE4A and FE5A to operate at the correct speed to deliver airflow precisely, ensuring proper performance across a wide range of duct static pressures. This adaptive efficiency also makes installation quality easier to achieve for today's demanding homeowner.
Bryant's command of ECM technology may be most evident in the comfort advantages that an ECM can deliver. For true comfort, the homeowner can achieve command of both temperature and humidity in cooling and heating modes.
Another feature which sets the FE4A and FE5A apart is the factory-installed TXV, which enhances efficiency and provides compressor-protecting operation at all recommended conditions. Grooved tubing, louvered aluminum fins, and the large face areas of the FE4A and FE5A refrigerant coils also provide superior efficiency, for high SEER and HSPF performance.
Bryant leads the way in condensate control, a hallmark of these multipoise fan coils. All of these featured components are protected within a rugged, pre-painted metal cabinet lined with super-thick, high-density insulation. For neat, high quality installations, the unit exterior features sweat refrigerant connections for simple leak free performance, and multiple electrical entry for both high and low voltage service.
Assembled at the factory compliant with low leak requirements of less than 2% cabinet leakage rate at 0.5 inches W.C. and 1.4% cabinet leakage rate at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard.

FEATURES
Smart Diagnostics
S Self configuring (ease of installation) S Easier troubleshooting, providing faster service and repair S Energy Tracking capability with the Evolutionr Connext Wall Control w/software version 13 or later
(Energy Tracking has the ability to monitor and estimate the energy consumption of your Evolutionr system.)
Environmentally Responsible Refrigerant Technology
S PuronR refrigerant the chlorine-free, non-ozone depleting refrigerant S Thermostatic Expansion Valve (TXV) designed to maximize performance with PuronR refrigerant
Energy Efficient Operation
S Electronically Commutated Motor (ECM) operates efficiently at all speeds S Maximizes efficiency of heating and cooling systems S Ultra-low power consumption during fan only operation
Comfort Control
S Warm, comfortable heating air temperatures S Unmatched humidity control
Airflow and Sound Technology
S Logarithmic spiral blower housings for high blower efficiency and quiet operation S Diffuser air discharge section for high airflow efficiency and quiet, smooth operation S High duct static capability S Design meets stringent regulations for cabinet air leakage of less than 2% when tested at 0.5 inches W.C., and cabinet air leakage less
than 1.4% at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard.
Condensate Control and Disposal Technology
S Minimal standing water - less microbial growth for improved IAQ and reduced condensate line clogging and related condensate leakage S Condensate fittings relocated away from turbulent airflow patterns at the blower entrance for improved condensate control performance S Overflow feature for slope coil units allows condensate to exit the unit without damage to product under clogged primary and secondary
line conditions S Tested for condensate disposal at conditions much more severe than those required by ARI S Primary and secondary drain connections to comply with HUD S All pans constructed of an injection molded glass-filled polycarbonate engineered resin material, with brass drain connections S High density, super thick cabinetry insulation with vapor barrier S Pre-painted galvanized sheet metal cabinet
Heat Transfer Technology
S Grooved tubing S Lanced sine wave aluminum fins S Discreet refined counterflow refrigerant circuitry S Bi-flow hard-shutoff TXV metering device
Quality Assisting, Ease of Installation and Service Features
S Easy 4 wire hook up: convenient and reduces installation time. S FE4A unit is multipoise S FE5A unit is upflow/downflow only (single drain pan). S Provision made for suspending from roof or ceiling joints S Modular cabinet on sizes 003 through 006 S Sweat connections for leak free service S Multiple electrical entry for application flexibility (high and low voltage) S Low voltage terminal strip, to safely hold connections within the cabinet S Cabinet construction features innovations designed to prevent cabinet sweating
Controls and Electrical Features
S Easy plug connection provided for quick installation of accessory heater packages S 40VA 208/230v transformer S Replaceable 3-amp blade-type auto fuse protects against transformer secondary short
Filter Features
S Factory supplied filter S Cleanable polyester filter media S Filter "springs" out for easy access - no tools required S Newly improved filter rack area - filter door insulation added for an improved air seal
2

MODEL NUMBER NOMENCLATURE

1 2 3 4 5 6 7 8 9 10 11 12 FE4 ANB0 0 2 0 0 0

Product F = Fan Coil
Type E = Evolutionr, VS, Puronr Refrigerant
Position 4 = Multi-poise 5 = Upflow / Downflow
Series A
Electrical N = 208/230v, 1ph-60 Hz

Coil Type T00 = Tin-plated 000 = Copper L00 = Aluminum
Capacity 002 = 18-36,000 003 = 24-42,000 004 = 24-42,000 005 = 30-48,000 006 = 36-60,000
Cabinet / Insulation B = Modular F = Single piece

Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the program For verification of certification for individual products, go to www.ahridirectory.org.

3

004 -

4

DIMENSIONS

UNIT SIZE
FE4A 002 FE4A 003 FE4A 003* FE4A 005 FE4A 005* FE4A 006* FE5A 004* * Modular Cabinet

A in 42-11/16 53-7/16 53-7/16 53-7/16 53-7/16 59-3/16 59-3/16

mm 1084 1357 1357 1357 1357 1503 1503

B

in

mm

17-5/8

448

21-1/8

537

21-1/8

537

21-1/8

537

21-1/8

537

24-11/16

627

24-11/16

627

C

in

mm

15-3/4

400

19-1/4

489

19-1/4

489

19-1/4

489

19-1/4

489

22-3/4

578

22-3/4

578

D

in .

mm

15-5/8

397

19-1/8

486

19-1/8

486

19-1/8

486

19-1/8

486

22-11/16

576

22-11/16

576

E

in

mm

10-3/4

273

19-3/16

487

19-3/16

487

19-1/2

495

19-1/2

495

25-1/4

641

25-1/4

641

H*

in

mm

--

--

--

--

28-5/16

719

--

--

28-5/16

719

34-1/16

865

34-1/16

865

5

DIMENSIONS

UNIT
FE4A FE4A FE4A FE4A FE4A FE4A FE5A * Modular Cabinet

SIZE
002 003 003* 005 005* 006* 004*

F

in

mm

18-9/16

472

26-15/16

684

26-15/16

684

27-1/4

692

27-1/4

692

32-15/16

837

32-15/16

837

G

in

mm

18-1/4

464

27-1/2

699

27-1/2

699

26-15/16

684

26-15/16

684

32-5/8

829

32-5/8

829

COIL CONFIGURATION

Slope

"A"

--

Yes

Yes

--

Yes

--

--

Yes

--

Yes

--

Yes

--

Yes

SHIPPING WEIGHT lb / kg 135 / 61 150 / 68 150 / 68 172 / 78 172 / 78 207 / 94 200 / 91

ORDERING NO.
FE4ANF002000 FE4ANF002T00 FE4ANF002L00 FE4ANF003000 FE4AN(B,F)003T00 FE4AN(B,F)003L00 FE4ANF005000 FE4AN(B,F)005T00 FE4AN(B,F)005L00 FE4ANB006000 FE4ANB006T00 FE4ANB006L00
FE5ANB004T00 FE5ANB004L00

PHYSICAL DATA

FIELD-INSTALLED HEAT (kW)
5, 8, 9, 10, 15, 20 5, 8, 9, 10, 15, 18, 20 5, 8, 9, 10, 15, 18, 20, 24, 30 8, 9, 10, 15, 18, 20, 24, 30 5, 8, 9, 10, 15, 18, 20

NOMINAL COOLING CA
PACITY (BTUH)

Height

DIMENSIONS Width

18,000 to
36,000

42-11/16-in10 17-5/8-in 448

84 mm

mm

24,000 to
42,000

53-7/16-in 21-1/8-in 537

1357 mm

mm

30,000 to
48,000

53-7/16-in 21-1/8-in 537

1357 mm

mm

36,000 to
60,000

59-3/16-in 24-11/16-in

1503 mm

627 mm

24,000 to
42,000

59-3/16-in 24-11/16-in

1503 mm

627 mm

Depth
22-1/16-in 560 mm
22-1/16-in 560 mm
22-1/16-in 560 mm
22-1/16-in 560 mm
22-1/16-in 560 mm

SHIPPING WEIGHT
lb / kg
135 lb 61 kg
150 lb 68 kg
172 lb 78 kg
207 lb 94 kg
200 lb 91 kg

MODEL

SIZE

002

COIL

Refrigerant Metering Device

TXV Size

2 Ton

Configuration

A

Rows--Fins/In.

Face Area (Sq Ft)

3.46

MATCHES OUTDOOR UNIT SIZES

Nominal Cooling Tons

1.5, 2, 2.5, 3

FAN

Air Discharge

CFM/Ton (Nominal Clg/Htg)

Motor HP (ECM)

1/2

Filter 21-1/2-in (546 mm) x

16-3/8-in (417 mm)

CABINET CONFIGURATION OPTIONS

1-piece

SPECIFICATIONS

FE4A

003

005

006

PuronR Refrigerant (R-410A) TXV

3 Ton

4 Ton

Slope

A

3 / 14.5

3.46

5.93

5 Ton A
7.42

2, 2.5, 3, 3.5

2.5, 3, 3.5, 4

3, 3.5, 4, 5

Upflow, Downflow, Horizontal

350+

1/2

1/2

19-7/8-in (505 mm)

19-7/8-in (505 mm)

3/4
23-5/16-in (592 mm)

1-piece / Modular 1-piece / Modular

Modular

FE5A 004
3 Ton A
7.42
2, 2.5, 3, 3.5
Upflow, Downflow
3/4 23-5/16-in
(592 mm)
Modular

6

PERFORMANCE DATA

AIRFLOW DELIVERY -- COOLING, HEATING, ELECTRIC HEATING MODES

The FE4 and FE5A fan coils will provide airflow at a rate that is requested by the Integrated System User Interface during air conditioning or heat pump heating (without electric heat) modes. The nominal airflow for both heating and cooling modes is 350 cfm/ton nominal size of the outdoor unit installed. The airflow actually requested by the User Interface is modified by its internal algorithms for zoning, comfort or efficiency concerns. Refer to the

documentation for the User Interface for more information on how the User Interface controls the fan coil. Safe operation of electric heaters requires airflow delivery at or above the minimum CFM for electric heater application listed in the chart below. The fan coil will adjust its airflow delivery to maintain safe airflow as operating mode and staging conditions require.

FE4A/FE5A FAN COIL AIRFLOW DELIVERY CHART (CFM) -- ELECTRIC HEATING MODELS

MODEL FE4A OUTDOOR UNIT CAPACITY BTUH 5

ELECTRIC HEATER kW RANGE

9

10

15

20

EMERGENCY

625

625

675

775

950

18,000

625

625

675

--

--

002

24,000

650

725

775

900

--

30,000

800

875

875

925

1125

36,000

975

975

975

1025 1125

EMERGENCY

675

700

775

850

1050

24,000

675

875

875

1100 1150

003

30,000

800

875

875

1100 1150

36,000

975

975

1025 1150 1250

42,000

1125

1125 1125 1150 1350

EMERGENCY

675

700

775

850

1050

30,000

800

875

875

1100 1150

005

36,000

975

975

1025 1150 1250

42,000

1125

1125 1125 1150 1250

48,000

1305

1305 1305 1305 1350

EMERGENCY

1050

1050 1050 1050 1125

36,000

1050

1050 1100 1350 1350

006

42,000

1125

1125 1150 1350 1350

48,000

1300

1300 1300 1350 1500

60,000

1625

1625 1625 1625 1750

MODEL FE5A OUTDOOR UNIT CAPACITY BTUH 5

ELECTRIC HEATER kW RANGE

9

10

15

20

EMERGENCY

675

775

775

900

1125

24,000

975

975

975

--

--

004

30,000

1050

1050 1100 1125

--

36,000

1050

1050 1100 1350 1350

42,000

1125

1125 1150 1350 1350

Note 1: Emergency - Air conditioner with electric heater application, or emergency heat. Note 2: These airflows are minimum airflows as UL listed. Note 3: Dashed entry indicates that the heater/fan coil/outdoor unit combination is not approved. Do not apply.

24
-- -- -- -- --
-- -- -- -- --
1400 -- -- --
1500
1750 -- --
1750 1750
24
-- -- -- -- --

30
-- -- -- -- --
-- -- -- -- --
1425 -- -- --
1600
1750 -- --
1750 1750
30
-- -- -- -- --

7

ACCEPTABLE DUCT CONDITIONS
0.7

0.6

0.5

SUPPLY STATIC PRESSURE (in wc)

0.4 ACCEPTABLE RANGE
0.3
0.2

TOO HIGH RETURN STATIC PRESSURE (DIFFICULT TO MAKE TRAP)

0.1

0

0

0.1

0.2

0.3

0.4

0.5

0.6

RETURN STATIC PRESSURE (in wc)

A07273

For satisfactory operation (specifically making dry secondary trap), subject fan coils must be installed with duct systems which fall within the "Acceptable Range" illustrated above.

MINIMUM RPM TABLE

MAXIMUM STATIC TABLE

MODEL

SYSTEM SIZES

CFM RANGE

MIN RPM

MODEL

AIRFLOW DELIVERY

AVAILABLE STATIC PRESSURE

FE4ANF002 FE4AN(B,F)003 FE4AN(B,F)005
FE4ANB006 FE5ANB004

018, 024, 030, 036 024, 030, 036, 042 030, 036, 042, 048 036, 042, 048, 060 024, 030, 036, 042

150 - 1200 300 200 - 1400 285 250 - 1600 275 500 - 2000 275 500 - 1400 275

FE4ANF002

525 CFM 700 CFM 875 CFM 1050 CFM 1200 CFM

1.00 in wc 1.00 in wc 1.00 in wc 0.80 in wc 0.60 in wc

700 CFM

1.00 in wc

875 CFM

1.00 in wc

FE4AN(B,F)003

1050 CFM 1225 CFM

1.00 in wc 1.00 in wc

1400 CFM

0.80 in wc

875 CFM

1.00 in wc

1050 CFM

1.00 in wc

FE4AN(B,F)005

1225 CFM 1400 CFM

1.00 in wc 1.00 in wc

1600 CFM

0.50 in wc

1050 CFM

1.00 in wc

1225 CFM

1.00 in wc

FE4ANB006

1400 CFM 1750 CFM

1.00 in wc 1.00 in wc

2000 CFM

0.60 in wc

700 CFM

1.00 in wc

875 CFM

1.00 in wc

FE5ANB004

1050 CFM 1225 CFM

1.00 in wc 1.00 in wc

1400 CFM

1.00 in wc

8

GROSS COOLING CAPACITIES (MBTUH)

INDOOR COIL

SATURATED TEMPERATURE LEAVING EVAPORATOR (_F / _C)

AIR

35 / 2

40 / 4

45 / 7

50 / 10

55 / 13

CFM EWB

TC

SHC BF

TC

SHC BF

TC

SHC BF

TC

SHC BF

TC

SHC BF

FE4ANF002

72/22 40.19 19.65 0.00 36.23 17.59 0.00 31.86 15.48 0.00 27.00 13.31 0.00 21.65 11.11 0.00

500 67/19 32.99 19.92 0.01 28.96 17.79 0.01 24.52 15.62 0.01 19.64 13.40 0.01 14.28 11.17 0.01

62/17 26.44 20.11 0.01 22.36 17.93 0.01 17.93 15.73 0.01 13.56 13.56 0.03 11.28 11.28 0.19

72/22 49.76 24.23 0.00 44.85 21.76 0.00 39.40 19.20 0.00 33.36 16.55 0.01 26.66 13.83 0.01

650 67/19 40.90 24.80 0.01 35.90 22.22 0.01 30.37 19.55 0.02 24.27 16.82 0.02 17.58 14.06 0.02

62/17 32.84 25.24 0.02 27.75 22.56 0.02 22.25 19.85 0.02 17.13 17.13 0.06 14.25 14.25 0.21

72/22 61.99 30.08 0.00 55.87 27.15 0.00 49.04 24.04 0.01 41.48 20.80 0.02 33.10 17.46 0.02

875 67/19 51.08 31.23 0.03 44.83 28.09 0.03 37.91 24.84 0.03 30.23 21.47 0.03 21.83 18.03 0.03

62/17 41.11 32.14 0.03 34.76 28.88 0.03 27.91 25.53 0.04 22.04 22.04 0.10 18.33 18.33 0.25

72/22 67.83 32.91 0.00 61.10 29.76 0.00 53.66 26.40 0.02 45.36 22.89 0.03 36.17 19.27 0.03

1000 67/19 55.96 34.39 0.04 49.12 31.01 0.04 41.53 27.48 0.04 33.11 23.83 0.04 23.88 20.06 0.04

62/17 45.09 35.62 0.04 38.13 32.08 0.04 30.69 28.43 0.05 24.54 24.54 0.12 20.40 20.40 0.27

72/22 77.77 37.84 0.00 70.13 34.30 0.03 61.59 30.55 0.05 52.04 26.60 0.05 41.42 22.50 0.05

1250 67/19 64.36 40.02 0.06 56.52 36.24 0.06 47.77 32.27 0.06 38.04 28.12 0.06 27.46 23.81 0.07

62/17 51.98 41.92 0.06 44.00 37.93 0.06 35.61 33.77 0.08 29.12 29.12 0.16 24.20 24.20 0.30

FE4ANF003

72/22 43.01 20.98 0.00 38.69 18.78 0.00 33.92 16.51 0.00 28.64 14.18 0.00 22.85 11.81 0.01

600 67/19 35.27 21.34 0.01 30.88 19.04 0.01 26.07 16.71 0.01 20.79 14.34 0.01 15.03 11.95 0.01

62/17 28.24 21.59 0.01 23.81 19.25 0.01 19.05 16.90 0.02 14.56 14.56 0.05 12.11 12.11 0.21

72/22 53.83 26.15 0.00 48.40 23.49 0.00 42.36 20.71 0.00 35.72 17.83 0.02 28.38 14.89 0.02

800 67/19 44.23 26.92 0.02 38.71 24.10 0.02 32.61 21.20 0.03 25.91 18.24 0.03 18.65 15.26 0.03

62/17 35.47 27.49 0.03 29.87 24.58 0.03 23.89 21.65 0.03 18.67 18.67 0.09 15.51 15.51 0.24

72/22 63.07 30.60 0.00 56.66 27.57 0.00 49.58 24.36 0.02 41.76 21.04 0.03 33.10 17.62 0.03

1000 67/19 51.91 31.82 0.04 45.41 28.58 0.04 38.24 25.24 0.04 30.31 21.78 0.04 21.76 18.29 0.05

62/17 41.71 32.80 0.04 35.12 29.43 0.04 28.13 26.00 0.05 22.41 22.41 0.12 18.60 18.60 0.27

72/22 71.01 34.48 0.00 63.77 31.12 0.02 55.79 27.57 0.04 46.95 23.88 0.05 37.18 20.08 0.05

1200 67/19 58.54 36.17 0.05 51.21 32.59 0.05 43.10 28.87 0.06 34.13 25.02 0.06 24.47 21.08 0.06

62/17 47.12 37.60 0.06 39.70 33.86 0.06 31.89 30.00 0.07 25.83 25.83 0.15 21.43 21.43 0.29

72/22 77.95 37.95 0.01 70.07 34.31 0.04 61.29 30.47 0.06 51.54 26.47 0.06 40.78 22.33 0.07

1400 67/19 64.44 40.15 0.07 56.37 36.28 0.07 47.43 32.24 0.07 37.54 28.04 0.07 26.89 23.69 0.08

62/17 51.95 42.08 0.07 43.78 37.99 0.08 35.30 33.73 0.09 28.95 28.95 0.19 24.01 24.01 0.32

FE5ANB004

72/22 40.42 19.84 0.00 36.59 17.80 0.00 32.35 15.70 0.00 27.64 13.54 0.00 22.39 11.33 0.00

600 67/19 33.22 20.00 0.00 29.31 17.90 0.00 24.99 15.74 0.00 20.19 13.53 0.00 14.87 11.27 0.00

62/17 26.67 20.11 0.00 22.69 17.95 0.00 18.31 15.75 0.00 13.60 13.54 0.00 11.29 11.29 0.17

72/22 52.07 25.46 0.00 47.19 22.92 0.00 41.75 20.28 0.00 35.66 17.53 0.00 28.84 14.70 0.00

800 67/19 42.88 25.89 0.00 37.88 23.24 0.00 32.31 20.49 0.00 26.10 17.66 0.00 19.18 14.75 0.00

62/17 34.51 26.21 0.00 29.39 23.46 0.00 23.73 20.64 0.00 17.81 17.81 0.01 14.85 14.85 0.18

72/22 62.54 30.48 0.00 56.75 27.53 0.00 50.25 24.45 0.00 42.94 21.21 0.00 34.73 17.84 0.00

1000 67/19 51.63 31.28 0.00 45.66 28.17 0.01 38.98 24.93 0.01 31.49 21.55 0.01 23.12 18.06 0.01

62/17 41.65 31.91 0.01 35.51 28.66 0.01 28.71 25.30 0.01 21.89 21.89 0.03 18.26 18.26 0.19

72/22 71.89 34.94 0.00 65.33 31.70 0.00 57.89 28.24 0.00 49.50 24.59 0.00 40.06 20.76 0.00

1200 67/19 59.49 36.20 0.01 52.68 32.73 0.01 45.02 29.06 0.01 36.39 25.22 0.01 26.71 21.21 0.01

62/17 48.10 37.22 0.01 41.07 33.55 0.01 33.27 29.72 0.01 25.77 25.77 0.05 21.51 21.51 0.20

72/22 80.24 38.94 0.00 73.00 35.45 0.00 64.73 31.69 0.00 55.41 27.69 0.01 44.86 23.46 0.01

1400 67/19 66.53 40.71 0.01 58.99 36.93 0.01 50.47 32.91 0.02 40.84 28.66 0.02 29.98 24.20 0.02

62/17 53.91 42.17 0.02 46.10 38.14 0.02 37.43 33.92 0.02 29.46 29.46 0.07 24.60 24.60 0.22

FE4ANF005

72/22 57.24 28.01 0.00 51.64 25.08 0.00 45.46 22.08 0.00 38.59 19.00 0.00 30.99 15.85 0.00

750 67/19 46.98 28.35 0.00 41.29 25.33 0.00 35.01 22.24 0.00 28.09 19.09 0.00 20.47 15.90 0.01

62/17 37.67 28.59 0.01 31.89 25.50 0.01 25.61 22.37 0.01 19.28 19.28 0.02 16.05 16.05 0.19

72/22 69.68 33.97 0.00 62.89 30.52 0.00 55.32 26.92 0.00 46.89 23.21 0.00 37.57 19.40 0.00

950 67/19 57.29 34.68 0.01 50.33 31.06 0.01 42.64 27.33 0.01 34.14 23.51 0.01 24.80 19.63 0.01

62/17 45.99 35.21 0.01 38.92 31.47 0.01 31.24 27.68 0.01 23.90 23.90 0.04 19.89 19.89 0.20

72/22 80.80 39.28 0.00 72.96 35.40 0.00 64.17 31.32 0.00 54.37 27.06 0.01 43.48 22.66 0.01

1150 67/19 66.56 40.46 0.02 58.50 36.34 0.02 49.54 32.05 0.02 39.60 27.64 0.02 28.70 23.15 0.02

62/17 53.51 41.36 0.02 45.29 37.07 0.02 36.38 32.70 0.02 28.26 28.26 0.07 23.51 23.51 0.22

72/22 97.47 47.29 0.00 88.05 42.83 0.00 77.49 38.05 0.01 65.68 33.04 0.02 52.41 27.78 0.02

1500 67/19 80.52 49.40 0.03 70.85 44.58 0.03 60.01 39.53 0.03 47.89 34.25 0.03 34.64 28.83 0.04

62/17 64.96 51.12 0.03 55.02 46.04 0.03 44.30 40.80 0.04 35.27 35.27 0.10 29.34 29.34 0.25

72/22 105.61 51.26 0.00 95.43 46.52 0.01 84.03 41.43 0.03 71.21 36.06 0.03 56.82 30.42 0.03

1700 67/19 87.38 53.92 0.04 76.93 48.80 0.04 65.20 43.40 0.04 52.01 37.70 0.04 37.60 31.83 0.05

62/17 70.60 56.17 0.04 59.87 50.74 0.04 48.32 45.08 0.05 38.96 38.96 0.13 32.40 32.40 0.27

FE4ANB006

72/22 76.01 37.07 0.00 68.82 33.39 0.00 60.76 29.56 0.00 51.72 25.55 0.00 41.64 21.42 0.00

1050 67/19 62.63 37.91 0.01 55.22 34.04 0.01 46.97 30.03 0.01 37.78 25.89 0.01 27.60 21.64 0.01

62/17 50.40 38.54 0.01 42.81 34.53 0.01 34.49 30.41 0.01 26.28 26.28 0.03 21.90 21.90 0.19

72/22 89.66 43.58 0.00 81.26 39.43 0.00 71.77 35.02 0.00 61.13 30.39 0.00 49.17 25.55 0.01

1300 67/19 74.04 45.04 0.01 65.36 40.60 0.01 55.62 35.94 0.01 44.72 31.09 0.01 32.62 26.09 0.01

62/17 59.73 46.18 0.01 50.78 41.52 0.02 40.97 36.70 0.02 31.77 31.77 0.06 26.48 26.48 0.21

72/22 110.09 53.41 0.00 99.92 48.64 0.00 88.41 43.46 0.01 75.38 37.95 0.02 60.66 32.13 0.02

1750 67/19 91.28 56.16 0.02 80.74 50.96 0.03 68.83 45.42 0.03 55.35 39.55 0.03 40.35 33.42 0.03

62/17 73.94 58.45 0.03 63.04 52.91 0.03 51.08 47.08 0.03 40.82 40.82 0.10 34.04 34.04 0.24

72/22 121.19 58.89 0.00 110.14 53.79 0.01 97.57 48.25 0.02 83.25 42.30 0.03 67.02 35.98 0.03

2050 67/19 100.75 62.56 0.04 89.24 56.99 0.04 76.15 51.01 0.04 61.30 44.63 0.04 44.72 37.88 0.04

62/17 81.81 65.71 0.04 69.88 59.72 0.04 56.88 53.37 0.05 46.27 46.27 0.12 38.60 38.60 0.26

72/22 126.10 61.36 0.00 114.71 56.14 0.02 101.67 50.45 0.03 86.78 44.32 0.03 69.87 37.76 0.04

2200 67/19 104.99 65.51 0.04 93.05 59.79 0.04 79.44 53.62 0.04 63.97 47.02 0.04 46.71 40.00 0.05

62/17 85.35 69.12 0.04 72.98 62.94 0.05 59.55 56.35 0.06 48.85 48.85 0.14 40.75 40.75 0.27

9

CFM - Cubic Ft per Minute

EWB - Entering Wet Bulb (_F / _C)

SHC - Gross Sensible Capacity 1000 Btuh BF - Bypass Factor

NOTES: 1. Contact manufacturer for cooling capacities at conditions other
than shown in table.

2. Formulas:
Leaving db = entering db -sensible heat cap.
1.09 x CFM
Leaving wb = wb corresponding to enthalpy of air leaving coil (hlwb) hlwb = hewb -total capacity (Btuh)
4.5 x CFM
where hewb = enthalpy of air entering coil. Direct interpolation is permissible. Do not extrapolate.

3. SHC is based on 80_F db temperature of air entering coil. Below 80_F db, subtract (Correction Factor x CFM) from SHC. Above 80_F db, add (Correction Factor x CFM) to SHC.

4. Bypass Factor = 0 indicates no psychometric solution. Use by pass factor of next lower EWB for approximation.

LWB - Leaving Wet Bulb (_F / _C) TC - Gross Cooling Capacity 1000 Btuh MBH - 1000 Btuh

SHC CORRECTION FACTOR

BYPASS FACTOR
0.10 0.20 0.30

ENTERING AIR DRY-BULB TEMPERATURE (_F)

79 78 77

76

75

Under 75

81 82 83 84 85

Over 85

Correction Factor

.098 1.96 2.94 3.92 4.91 Use formula

0.87 1.74 2.62 3.49 4.36

shown

0.76 1.53 2.29 3.05 3.82

below

Interpolation is permissible. Correction Factor = 1.09 x (1 - BF) x (db - 80)

ESTIMATED SOUND POWER LEVEL (dBA)

MODEL SIZE

CONDITIONS

OCTAVE BAND CENTER FREQUENCY

CFM

ESP

63

125

250

500

1000

2000

4000

400

0.25

61.0

57.0

55.0

50.0

48.0

46.0

42.0

600

0.25

62.7

58.7

56.7

51.7

49.7

47.7

43.7

800

0.25

64.0

60.0

58.0

53.0

51.0

49.0

45.0

FE4ANF002

1000

0.25

65.0

61.0

57.0

56.0

52.0

50.0

46.0

1200

0.25

65.8

61.8

57.8

56.8

52.8

50.8

46.8

1400

0.25

66.4

62.4

58.4

57.4

53.4

51.4

47.4

400

0.25

61.0

57.0

55.0

50.0

48.0

46.0

42.0

600

0.25

62.7

58.7

56.7

51.7

49.7

47.7

43.7

800

0.25

64.0

60.0

58.0

53.0

51.0

49.0

45.0

FE4ANF003

1000

0.25

65.0

61.0

59.0

54.0

52.0

50.0

46.0

1200

0.25

65.8

61.8

59.8

54.8

52.8

50.8

46.8

1400

0.25

66.4

62.4

58.4

57.4

53.4

51.4

47.4

1600

0.25

67.0

63.0

59.0

58.0

54.0

52.0

48.0

600

0.25

62.7

58.7

56.7

51.7

49.7

47.7

43.7

800

0.25

64.0

60.0

58.0

53.0

51.0

49.0

45.0

1000

0.25

65.0

61.0

59.0

54.0

52.0

50.0

46.0

FE5ANB004

1200

0.25

65.8

61.8

59.8

54.8

52.8

50.8

46.8

1400

0.25

66.4

62.4

60.4

55.4

53.4

51.4

47.4

1600

0.25

67.0

63.0

61.0

56.0

54.0

52.0

48.0

400

0.25

61.0

57.0

55.0

50.0

48.0

46.0

42.0

600

0.25

62.7

58.7

56.7

51.7

49.7

47.7

43.7

800

0.25

64.0

60.0

58.0

53.0

51.0

49.0

45.0

FE4ANF005

1000

0.25

65.0

61.0

59.0

54.0

52.0

50.0

46.0

1200

0.25

65.8

61.8

59.8

54.8

52.8

50.8

46.8

1400

0.25

66.4

62.4

58.4

57.4

53.4

51.4

47.4

1600

0.25

67.0

63.0

59.0

58.0

54.0

52.0

48.0

600

0.25

62.7

58.7

56.7

51.7

49.7

47.7

43.7

800

0.25

64.0

60.0

58.0

53.0

51.0

49.0

45.0

1000

0.25

65.0

61.0

59.0

54.0

52.0

50.0

46.0

1200

0.25

65.8

61.8

59.8

54.8

52.8

50.8

46.8

FE4ANB006

1400

0.25

66.4

62.4

60.4

55.4

53.4

51.4

47.4

1600

0.25

67.0

63.0

61.0

56.0

54.0

52.0

48.0

1800

0.25

67.5

63.5

59.5

58.5

54.5

52.5

48.5

2000

0.25

68.0

64.0

60.0

59.0

55.0

53.0

49.0

2150

0.25

68.3

64.3

60.3

59.3

55.3

53.3

49.3

*Est. sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook, chapter 52, p. 52.7.

AIRFLOW PERFORMANCE CORRECTION FACTORS

HEATER kW

ELEMENTS

STATIC PRESSURE CORRECTION (in wc)

Sizes 002­005

Size 006

0

0

+.02

+.03

5

1

+.01

+.02

8, 10

2

0

0

9, 15

3

­.02

­.03

20

4

­.04

­.06

18, 24, 30

6

­.06

­.10

The airflow performance table was developed using fan coils with 10kW electric heaters (2 elements) in the units. For fan coils with heaters made up of a different

number of elements, the external available static at a given CFM from the table may be corrected by adding or subtracting pressure. Use table for this correction.

10

FACTORY-INSTALLED FILTER STATIC PRESSURE DROP (in wc)

MODEL

CFM

FE4A

400

600

800

1000

1200

1400

1600

002

0.020

0.044

0.048

0.072

0.100

--

--

003

--

0.020

0.035

0.051

0.070

0.092

--

005

--

--

0.035

0.051

0.070

0.092

0.120

006

--

--

--

0.038

0.053

0.070

0.086

MODEL

CFM

FE5A

400

600

800

1000

1200

1400

1600

004

--

0.015

0.026

0.038

0.053

0.070

--

1800 -- -- --
0.105
1800 --

2000 -- -- --
0.133
2000 --

AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (in wc) AT INDICATED AIRFLOW (DRY TO WET COIL)

MODEL

CFM

FE4A

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

002

0.012

0.016

0.022

0.028

0.034

0.040

0.049

--

--

--

--

003

--

0.026

0.034

0.042

0.052

0.063

0.075

0.083

0.091

0.098

0.110

005

--

0.006

0.008

0.010

0.012

0.015

0.017

0.020

0.023

0.027

0.030

CFM

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

2100

006

0.013

0.016

0.018

0.020

0.023

0.027

0.030

0.034

0.039

0.044

0.048

MODEL

CFM

FE5A

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

004

0.004

0.005

0.007

0.009

0.011

0.013

0.016

0.018

0.020

0.023

--

NOTE: Subtract the above pressure drop corrections from unit airflow data when that component or condition is used. The remaining external static pressure will be available for the duct system.

UNITS WITHOUT ELECTRIC HEAT

UNIT SIZE

VOLTS-PHASE

FLA

MIN CKT AMPS

BRANCH CIRCUIT

Min Wire Size Awg*

Fuse/Ckt Bkr Amps

002

208/230-1

4.3

5.4

14

15

003

208/230-1

4.3

5.4

14

15

005

208/230-1

4.3

5.4

14

15

004, 006

208/230-1

6.8

8.5

14

15

* Use copper wire only to connect unit. If other than uncoated (non-plated) 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for

larger than 10 AWG) is used consult applicable tables of the National Electric Code (ANSI/NFPA 70).

NOTE: If branch circuit wire length exceeds 100-ft (30.5 m), consult NEC 210-19a to determine maximum wire length. Use 2% voltage drop.

FLA -- Full Load Amps

ACCESSORY ELECTRIC HEATERS

HEATER PART NO.

kW @ 240V

VOLTS/ PHASE

KFCEH0501N05

5

230/1

KFCEH0901N10

10

230/1

KFCEH3001F15

15

230/1

KFCEH3201F20

20

230/1

KFCEH2901N09

9

230/1*

KFCEH1601315

15

230/3

KFCEH3401F24

24

230/3

KFCEH3501F30

30

230/3

KFCEH2401C05

5

230/1

KFCEH2601C10

10

230/1

KFCEH3101C15

15

230/1

KFCEH3301C20

20

230/1

* Field convertible to 3 phase.

{ These heaters field convertible to single phase.

STAGES (kW OPERATING)
5 10 5, 15 5, 20 3, 9 5, 15 8, 16, 24 10, 20, 30 5 10 5, 15 5, 20

INTERNAL CIRCUIT PROTECTION

FAN COIL SIZE USED
WITH

HEATING CAP. @ 230V

INTELLIGENT HEAT CAPABLE (kW OPERATING)

None

All

15,700

--

None

All

31,400

--

Fuses**

All

47,100

5, 10, 15

Fuses**

All

62,800

5, 10, 15, 20

None

All

28,300

3, 6, 9

None

All

47,100

--

Fuses

005, 006

78,500

8, 16, 24

Fuses

005, 006

94,200

10, 20, 30

Ckt Bkr

All

15,700

--

Ckt Bkr

All

31,400

--

Ckt Bkr

All

47,100

5, 10, 15

Ckt Bkr

All

62,800

5, 10, 15, 20

** Single point wiring kit required for these heaters in Canada.

 Blower motor heat not included.

ELECTRIC HEATER INTERNAL PROTECTION

HEATER kW 5 8 9 10 15 15 18 20 24 30
* All circuit breakers are 2 pole.

PHASE 1 1 1/3 1 1 3 3 1 3/1 3/1

FUSES QTY / SIZE -- -- -- --
2/30, 2/60 -- -- 4/60 6/60 6/60

CKT BKR QTY / SIZE* 1/60 1/60 -- 1/60 2/60 -- -- 2/60 -- --

11

ACCESSORY ELECTRIC HEATER ELECTRICAL DATA

HEATER PART NO.

kW

P H A S E

INTERNAL CIRCUIT PROTEC
TION

240v

208v

KFCEH0501N05

5

3.8

1

None

KFCEH2401C05

5

3.8

1

Ckt Bkr

KFCEH0801N08

8

6.0

1

None

KFCEH2501C08

8

6.0

1

Ckt Bkr

KFCEH2901N09*

9

6.8

1

None

KFCEH2901N09*

9

6.8

3

None

KFCEH0901N10

10

7.5

1

None

KFCEH2601C10

10

7.5

1

Ckt Bkr

KFCEH3001F15* 1

15

11.3

1

Fuse

KFCEH3101C15*

15

11.3

1

Ckt Bkr

KFCEH1601315

15

11.3

3

None

KFCEH2001318

18

13.5

3

None

KFCEH3201F20* 1

20

15.0

1

Fuse

KFCEH3301C20*

20

15.0

1

Ckt Bkr

24

18.0

3

KFCEH3401F24*

24

18.0

1

Fuse Fuse

30

22.5

3

KFCEH3501F30*

30

22.5

1

Fuse Fuse

HEATER AMPS 208/230V

Single Circuit
18.1/20.0 18.1/20.0 28.9/32.0 28.9/32.0 32.8/36.0 18.8/20.8 36.2/40.0 36.2/40.0 54.2/59.9
-- 31.3/34.6 37.6/41.5 72.3/79.9
-- 50.1/55.4 86.7/95.5 62.6/69.2 109.0/120.0

Dual Circuit

L1,L2

L3,L4

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

--

36.2/40.0

18.1/20.0

36.2/40.0

18.1/20.0

--

--

--

--

36.2/40.0

36.2/40.0

36.2/40.0

36.2/40.0

--

--

--

--

--

--

--

--

Min Ampacity 208/230V**

Single Circuit

Dual Circuit

L1,L2

L3,L4

31.2/33.5

--

--

31.2/33.5

--

--

44.7/48.5

--

--

44.7/48.5

--

--

49.5/53.5

--

--

32.0/34.5

--

--

53.8/58.5

--

--

53.8/58.5

--

--

76.3/83.4

53.8/58.5

22.7/25.0

--

53.8/58.5

22.7/25.0

47.7/51.8

--

--

55.5/60.4

--

--

98.9/108.4

53.8/58.5

45.3/50.0

--

53.8/58.5

45.3/50.0

71.2/77.8

--

--

116.9/127.9

--

--

86.8/95.0

--

--

144.8/158.5

--

--

Min Wire Size (AWG) 208/230V

Single Circuit

Dual Circuit

L1,L2

L3,L4

8/8

--

--

8/8

--

--

8/8

--

--

8/8

--

--

8/6

--

--

8/8

--

--

6/6

--

--

6/6

--

--

4/4

6/6

10/10

--

6/6

10/10

8/6

--

--

6/6

--

--

3/2

6/6

8/8

--

6/6

8/8

4/4

--

--

1/1

--

--

3/3

--

--

0/00

--

--

BRANCH CIRCUIT

Min Gnd Wire Size 208/230V

Single Circuit

Dual Circuit

L1,L2

L3,L4

10/10

--

--

10/10

--

--

10/10

--

--

10/10

--

--

10/10

--

--

10/10

--

--

10/10

--

--

10/10

--

--

8/8

10/10

10/10

--

10/10

10/10

10/10

--

--

10/8

--

--

8/6

10/10

10/10

--

10/10

10/10

8/8

--

--

6/6

--

--

8/8

--

--

6/6

--

--

Max Fuse/Ckt Bkr Amps 208/230V

Single Circuit

Dual Circuit

L1,L2

L3,L4

35/35

--

--

35/35

--

--

45/50

--

--

45/50

--

--

50/60

--

--

35/35

--

--

60/60

--

--

60/60

--

--

80/90

60/60

25/25

--

60/60

25/25

50/60

--

--

60/70

--

--

100/110

60/60

50/50

--

60/60

50/50

80/80

--

--

125/150

--

--

90/100

--

--

150/175

--

--

Max Wire Length 208/230V (ft)

Single Circuit

Dual Circuit

L1,L2

L3,L4

85/88

--

--

85/88

--

--

59/60

--

--

59/60

--

--

54/87

--

--

83/85

--

--

78/80

--

--

78/80

--

--

88/89

78/80

75/76

--

78/80

75/76

56/90

--

--

76/77

--

--

85/109

78/80

59/59

--

78/80

59/59

94/95

--

--

115/116

--

--

97/98

--

--

117/150

--

--

FIELD MULTIPOINT WIRING OF 24-AND 30-kW SINGLE PHASE

12

HEATER PART NO.

P

kW

H

A

S

240V 208V E

HEATER AMPS 208/230V

L1,L2

L3,L4

L5,L6

MIN AMPACITY 208/230V**

L1,L2

L3,L4

L5,L6

MIN WIRE SIZE (AWG) 208/230V
L1,L2 L3,L4 L5,L6

MIN GND WIRE SIZE 208/230V

MAX FUSE/CKT BKR AMPS
208/230V
L1,L2 L3,L4 L5,L6

MAX WIRE LENGTH 208/230V (FT)
L1,L2 L3,L4 L5,L6

KFCEH3401F24 *

24

18.0

1 28.9/32.0 28.9/32.0 28.9/32.0 44.7/48.5 36.2/40.0 36.2/40.0

8/8

8/8

8/8

10/10

45/50 40/40 40/40 59/60 73/73

73/73

KFCEH3501F30 *

30

22.5

1 36.2/40.0 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 45.3/50.0

6/6

8/8

8/8

10/10

60/60 50/50 50/50 78/80 59/59

59/59

* Heaters are Intelligent Heat capable when used with the FE fan coil and Zone Perfect Plust or Evolution Controlt. { Field convertible to 1 phase, single or multiple supply circuit. } Field convertible to 3 phase. ** Includes blower motor amps of largest fan coil used with heater. {{ Copper wire must be used. If other than uncoated (non-plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of
the National Electric Code (ANSI/NFPA 70). }} Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%. NOTES: 1. Single circuit application of F15 and F20 heaters requires single-point wiring kit accessory.

ACCESSORIES

REQUIRED ACCESSORY

ITEM

Evolutionr Connext Control with Integrated Wi-Fi

or

1.

Evolutionr Connext Control Wi-Fi

with bundled router

or

Evolutionr Connext Control

ACCESSORY PART NO.*
SYSTXBBECC01
SYSTXBBECW01
SYSTXBBECN01

FAN COIL SIZE USED WITH All
All All

ADDITIONAL ACCESSORIES

ITEM

2.

Evolutionr Series 4 Zone Board

3.

Evolutionr Series Smart Sensor

4.

Evolutionr Remote Room Sensor

5.

Evolutionr Series Network Interface Module

6.

Disconnect Kit

7.

Downflow Base Kit

8.

Downflow Conversion Kit

9.

Single-Point Wiring Kit

10.

Filter Kit (12 Pack)

11.

Filter Media Cabinet

12.

Media Filter Cartridges

13.

Evolutionr Series Air Purifier

14.

PVC Condensate Trap Kit (50 pack)

15.

Air Cleaner 240-volt Conversion Kit

16.

Downflow/Horizontal Conversion Gasket Kit

17.

Horizontal Water Management Kit (25 pack)

18.

Standard Filter Rack Kit

19.

Hydronic Relay Interface Kit

20.

Door Gasket Kit **

ACCESSORY PART NO.*
SYSTXBB4ZC01 SYSTXBBSMS01-D
SYSTXBBRRS01 SYSTXBBNIM01 KFADK0201DSC KFACB0201CFB KFACB0301CFB KFACB0401CFB KFADC0201SLP KFADC0401ACL KFASP0101SPK KFAFK0212MED KFAFK0312LRG KFAFK0412XXL FNCCABBB0017 FNCCABBB0021 FNCCABBB0024 FILBBFNC0017 FILBBFNC0021 FILBBFNC0024 GAPABXBB1620 GAPABXBB2020 GAPABXBB2024 KFAET0150ETK KEAVC0201240 KFAHD0101SLP KFAHC0125AAA KFAFR0101FRM KFAFR0201FRM KFAFR0301FRM KFAFR0401FRM KFAIF0101HWC
344994-751

FAN COIL SIZE USED WITH
All All All All Cooling controls and heaters 3- through 10-kW 002 003, 005 004, 006 003 002, 004, 005, 006 Only with 15- and 20-kW Fused Heaters 002 003, 005 004, 006 002 003, 005 004, 006 002 003, 005 004, 006 002 003, 005 004, 006 All All All All NA 002 003, 005 004, 006 All All

* Factory authorized and listed, field installed. ** This kit is for replacement of factory installed gaskets if they are damaged or removed from the fan coil.

13

ACCESSORIES (CONT.)
Accessory Kits Description Suggested and Required Use 1. Evolutionr Connext Control with Integrated Wi-Fi
Deluxe programmable wall-mounted system control with integrated Wi-Fi. or Evolutionr Connext Control Wi-Fi with bundled router Deluxe programmable wall-mounted system control with integrated Wi-Fi. Sold bundled with Wi-Fi router or Evolutionr Connext Control Deluxe programmable wall-mounted system control without remote access.
2. Evolutionr 4 Zone Board 4-Zone Damper Control Module wall-mounted control. REQUIRED USE: For all four-zone systems. For systems with 5 to 8 zones, a second Damper Control Module is required.
3. Evolutionr Smart Sensor Wall control used to monitor temperature and/or fan control. SUGGESTED USE: For use in zone systems.
4. Evolutionr Remote Room Sensor Wired remote temperature sensor for zone control. SUGGESTED USE: For use in zone systems..
5. Evolutionr Series Network Interface Module Connects Heat Recovery and Energy Recovery Ventilators on non-zoning applications and non-communicating 2-speed units. REQUIRED USE: For non-zoned systems installed with HRV or ERV, Hybrid Heat with non-communicating heat pumps or non- communicating 2-speed units.
6. Disconnect Kit The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely. SUGGESTED USE: Units for 3- through 10-kW electric resistance heaters and cooling controls.
7. Downflow Base Kit This kit is designed to provide a 1-in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides a gap-free seal with the floor. REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
8. Downflow Conversion Kit Fan coils are shipped from the factory for upflow or horizontal-left applications. Downflow conversion kits provide proper condensate water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A-coils. REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
9. Single Point Wiring Kit The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run 2 heavy-gauge, high-voltage wires into the fan coil rather than 4 light-gauge, high-voltage wires. SUGGESTED USE: Fan coils with 15- and 20-kW fused heaters only.
10. Filter Kit (12 pack) The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevents them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and, in turn, the efficiency of the system. SUGGESTED USE: To replace filters in fan coils. REQUIRED USE: All units unless a filter grille is used.
11. Filter Media Cabinet This cabinet is mounted to the fan coil on the return air end and designed to slip over the outer fan coil casing. The cabinets are insulated using the same insulation as production fan coils. They are designed for the removal of particulates from indoor air using FILCCFNC00(14, 17, 21, 24) media filter cartridges. SUGGESTED USE: All fan coils.
12. Media Filter Cartridges These fan coil media filter cartridge kits are designed for the removal of particles from indoor air. The cartridge is installed in the return air duct next to the air handler or further upstream. SUGGESTED USE: All fan coils.
13. Evolutionr Series Air Purifier The Evolution Series Air Purifier wires directly to fan coil and requires no duct transitions with Bryant units. It comes with an airflow sensor. SUGGESTED USE: All fan coils.
14. Condensate Drain Trap Kit This kit consists of 50 PVC condensate traps. Each trap is pre-formed and ready for field installation. This deep trap helps the system make and hold proper condensate flow even during blower initiation. SUGGESTED USE: All fan coils.
15. Air Cleaner 240-volt Conversion Kit The AIRA electronic air cleaner comes ready for 115-v operation. REQUIRED USE: This kit is required when running 240-volt circuit to air cleaner.
14

ACCESSORIES (CONT.)
16. Downflow/Horizontal Conversion Gasket Kit This kit provides the proper gasketing of units when applied in either a downflow or horizontal application. REQUIRED USE: Fan coils in either downflow or horizontal applications.
17. Horizontal Water Management Kit This kit provides proper installation of fan coils under conditions of high static pressure and high relative humidity. SUGGESTED USE: All fan coils (except FE5 and FF1).
18. Standard Filter Rack Kit This kit mounts in fan coil filter rack area and modifies the existing filter rack to support standard 1-in. filter sizes. SUGGESTED USE: Fan coils using standard filter sizes.
19. Hydronic Relay Interface Kit This kit provides interface of the FE4 and FE5 fan coils with Hydronic Heat equipment. NOTE: Electric heat cannot be used with Hydronic Interface Relay Kit. SUGGESTED USE: All FE4 and FE5 fan coils installed with hydronic heat.
20. Door Gasket Kit This kit consists of specific adhesive-backed foam strips which are applied to the unit door and frame, limiting air leakage.
15

NOTES: ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------

E2019 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 07/19

U.S. Export Classification: EAR99.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

16

Catalog No. PDSFE4A-12