FAN COIL 2 TO 3-1/2 TON PURON VARIABLE SPEED ALUM EVOLUTION | Behler-Young
FE4A, FE5A EVOLUTIONr SERIES
COMMUNICATING VARIABLE-SPEED FAN COIL PURONr REFRIGERANT
SIZES 002 THRU 006
Product Data
PREMIUM ENVIRONMENTALLY RESPONSIBLE FAN COIL
The latest in technology makes the FE4A and FE5A fan coil models the most advanced air handlers available. With attention to quiet, efficient, and comfortable operation, Bryant has developed a new benchmark for homeowner comfort and ease of installation. The FE4A and FE5A utilize the Evolutionr Control as a required accessory to enable state of the art smart-diagnostics capability. This enables faster troubleshooting, providing ease of service and repair. The FE4A and FE5A also provide a 4-wire hook up with matching outdoor unit and the Evolutionr Control. This makes installation simpler and a lot quicker than with conventional fan coils. The FE4A and FE5A have advanced technology that allows the fan coil to self-configure with a matching outdoor unit and the Evolutionr Control, cutting down on installation time. The FE4A and FE5A feature Puronr refrigerant, the chlorine-free alternate that is the future for the residential heating and cooling industry. The FE4A and FE5A using PuronR refrigerant maximize performance for environmentally balanced systems. In addition to environmental safety, these systems are 30 to 40% more efficient than standard heating and cooling systems, thereby combining excellence in efficiency and environmental responsibility.
The FE4A and FE5A provide these benefits due to Bryant's command of Electronically Commutating Motor (ECM) technology. These motors are extremely efficient at all speeds, and enable the FE4A and FE5A to operate at the correct speed to deliver airflow precisely, ensuring proper performance across a wide range of duct static pressures. This adaptive efficiency also makes installation quality easier to achieve for today's demanding homeowner.
Bryant's command of ECM technology may be most evident in the comfort advantages that an ECM can deliver. For true comfort, the homeowner can achieve command of both temperature and humidity in cooling and heating modes.
Another feature which sets the FE4A and FE5A apart is the factory-installed TXV, which enhances efficiency and provides compressor-protecting operation at all recommended conditions. Grooved tubing, louvered aluminum fins, and the large face areas of the FE4A and FE5A refrigerant coils also provide superior efficiency, for high SEER and HSPF performance.
Bryant leads the way in condensate control, a hallmark of these multipoise fan coils. All of these featured components are protected within a rugged, pre-painted metal cabinet lined with super-thick, high-density insulation. For neat, high quality installations, the unit exterior features sweat refrigerant connections for simple leak free performance, and multiple electrical entry for both high and low voltage service.
Assembled at the factory compliant with low leak requirements of less than 2% cabinet leakage rate at 0.5 inches W.C. and 1.4% cabinet leakage rate at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard.
FEATURES
Smart Diagnostics
S Self configuring (ease of installation) S Easier troubleshooting, providing faster service and repair S Energy Tracking capability with the Evolutionr Connext Wall Control w/software version 13 or later
(Energy Tracking has the ability to monitor and estimate the energy consumption of your Evolutionr system.)
Environmentally Responsible Refrigerant Technology
S PuronR refrigerant the chlorine-free, non-ozone depleting refrigerant S Thermostatic Expansion Valve (TXV) designed to maximize performance with PuronR refrigerant
Energy Efficient Operation
S Electronically Commutated Motor (ECM) operates efficiently at all speeds S Maximizes efficiency of heating and cooling systems S Ultra-low power consumption during fan only operation
Comfort Control
S Warm, comfortable heating air temperatures S Unmatched humidity control
Airflow and Sound Technology
S Logarithmic spiral blower housings for high blower efficiency and quiet operation S Diffuser air discharge section for high airflow efficiency and quiet, smooth operation S High duct static capability S Design meets stringent regulations for cabinet air leakage of less than 2% when tested at 0.5 inches W.C., and cabinet air leakage less
than 1.4% at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard.
Condensate Control and Disposal Technology
S Minimal standing water - less microbial growth for improved IAQ and reduced condensate line clogging and related condensate leakage S Condensate fittings relocated away from turbulent airflow patterns at the blower entrance for improved condensate control performance S Overflow feature for slope coil units allows condensate to exit the unit without damage to product under clogged primary and secondary
line conditions S Tested for condensate disposal at conditions much more severe than those required by ARI S Primary and secondary drain connections to comply with HUD S All pans constructed of an injection molded glass-filled polycarbonate engineered resin material, with brass drain connections S High density, super thick cabinetry insulation with vapor barrier S Pre-painted galvanized sheet metal cabinet
Heat Transfer Technology
S Grooved tubing S Lanced sine wave aluminum fins S Discreet refined counterflow refrigerant circuitry S Bi-flow hard-shutoff TXV metering device
Quality Assisting, Ease of Installation and Service Features
S Easy 4 wire hook up: convenient and reduces installation time. S FE4A unit is multipoise S FE5A unit is upflow/downflow only (single drain pan). S Provision made for suspending from roof or ceiling joints S Modular cabinet on sizes 003 through 006 S Sweat connections for leak free service S Multiple electrical entry for application flexibility (high and low voltage) S Low voltage terminal strip, to safely hold connections within the cabinet S Cabinet construction features innovations designed to prevent cabinet sweating
Controls and Electrical Features
S Easy plug connection provided for quick installation of accessory heater packages S 40VA 208/230v transformer S Replaceable 3-amp blade-type auto fuse protects against transformer secondary short
Filter Features
S Factory supplied filter S Cleanable polyester filter media S Filter "springs" out for easy access - no tools required S Newly improved filter rack area - filter door insulation added for an improved air seal
2
MODEL NUMBER NOMENCLATURE
1 2 3 4 5 6 7 8 9 10 11 12 FE4 ANB0 0 2 0 0 0
Product F = Fan Coil
Type E = Evolutionr, VS, Puronr Refrigerant
Position 4 = Multi-poise 5 = Upflow / Downflow
Series A
Electrical N = 208/230v, 1ph-60 Hz
Coil Type T00 = Tin-plated 000 = Copper L00 = Aluminum
Capacity 002 = 18-36,000 003 = 24-42,000 004 = 24-42,000 005 = 30-48,000 006 = 36-60,000
Cabinet / Insulation B = Modular F = Single piece
Use of the AHRI Certified TM Mark indicates a manufacturer's participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
3
004 -
4
DIMENSIONS
UNIT SIZE
FE4A 002 FE4A 003 FE4A 003* FE4A 005 FE4A 005* FE4A 006* FE5A 004* * Modular Cabinet
A in 42-11/16 53-7/16 53-7/16 53-7/16 53-7/16 59-3/16 59-3/16
mm 1084 1357 1357 1357 1357 1503 1503
B
in
mm
17-5/8
448
21-1/8
537
21-1/8
537
21-1/8
537
21-1/8
537
24-11/16
627
24-11/16
627
C
in
mm
15-3/4
400
19-1/4
489
19-1/4
489
19-1/4
489
19-1/4
489
22-3/4
578
22-3/4
578
D
in .
mm
15-5/8
397
19-1/8
486
19-1/8
486
19-1/8
486
19-1/8
486
22-11/16
576
22-11/16
576
E
in
mm
10-3/4
273
19-3/16
487
19-3/16
487
19-1/2
495
19-1/2
495
25-1/4
641
25-1/4
641
H*
in
mm
--
--
--
--
28-5/16
719
--
--
28-5/16
719
34-1/16
865
34-1/16
865
5
DIMENSIONS
UNIT
FE4A FE4A FE4A FE4A FE4A FE4A FE5A * Modular Cabinet
SIZE
002 003 003* 005 005* 006* 004*
F
in
mm
18-9/16
472
26-15/16
684
26-15/16
684
27-1/4
692
27-1/4
692
32-15/16
837
32-15/16
837
G
in
mm
18-1/4
464
27-1/2
699
27-1/2
699
26-15/16
684
26-15/16
684
32-5/8
829
32-5/8
829
COIL CONFIGURATION
Slope
"A"
--
Yes
Yes
--
Yes
--
--
Yes
--
Yes
--
Yes
--
Yes
SHIPPING WEIGHT lb / kg 135 / 61 150 / 68 150 / 68 172 / 78 172 / 78 207 / 94 200 / 91
ORDERING NO.
FE4ANF002000 FE4ANF002T00 FE4ANF002L00 FE4ANF003000 FE4AN(B,F)003T00 FE4AN(B,F)003L00 FE4ANF005000 FE4AN(B,F)005T00 FE4AN(B,F)005L00 FE4ANB006000 FE4ANB006T00 FE4ANB006L00
FE5ANB004T00 FE5ANB004L00
PHYSICAL DATA
FIELD-INSTALLED HEAT (kW)
5, 8, 9, 10, 15, 20 5, 8, 9, 10, 15, 18, 20 5, 8, 9, 10, 15, 18, 20, 24, 30 8, 9, 10, 15, 18, 20, 24, 30 5, 8, 9, 10, 15, 18, 20
NOMINAL COOLING CA
PACITY (BTUH)
Height
DIMENSIONS Width
18,000 to
36,000
42-11/16-in10 17-5/8-in 448
84 mm
mm
24,000 to
42,000
53-7/16-in 21-1/8-in 537
1357 mm
mm
30,000 to
48,000
53-7/16-in 21-1/8-in 537
1357 mm
mm
36,000 to
60,000
59-3/16-in 24-11/16-in
1503 mm
627 mm
24,000 to
42,000
59-3/16-in 24-11/16-in
1503 mm
627 mm
Depth
22-1/16-in 560 mm
22-1/16-in 560 mm
22-1/16-in 560 mm
22-1/16-in 560 mm
22-1/16-in 560 mm
SHIPPING WEIGHT
lb / kg
135 lb 61 kg
150 lb 68 kg
172 lb 78 kg
207 lb 94 kg
200 lb 91 kg
MODEL
SIZE
002
COIL
Refrigerant Metering Device
TXV Size
2 Ton
Configuration
A
Rows--Fins/In.
Face Area (Sq Ft)
3.46
MATCHES OUTDOOR UNIT SIZES
Nominal Cooling Tons
1.5, 2, 2.5, 3
FAN
Air Discharge
CFM/Ton (Nominal Clg/Htg)
Motor HP (ECM)
1/2
Filter 21-1/2-in (546 mm) x
16-3/8-in (417 mm)
CABINET CONFIGURATION OPTIONS
1-piece
SPECIFICATIONS
FE4A
003
005
006
PuronR Refrigerant (R-410A) TXV
3 Ton
4 Ton
Slope
A
3 / 14.5
3.46
5.93
5 Ton A
7.42
2, 2.5, 3, 3.5
2.5, 3, 3.5, 4
3, 3.5, 4, 5
Upflow, Downflow, Horizontal
350+
1/2
1/2
19-7/8-in (505 mm)
19-7/8-in (505 mm)
3/4
23-5/16-in (592 mm)
1-piece / Modular 1-piece / Modular
Modular
FE5A 004
3 Ton A
7.42
2, 2.5, 3, 3.5
Upflow, Downflow
3/4 23-5/16-in
(592 mm)
Modular
6
PERFORMANCE DATA
AIRFLOW DELIVERY -- COOLING, HEATING, ELECTRIC HEATING MODES
The FE4 and FE5A fan coils will provide airflow at a rate that is requested by the Integrated System User Interface during air conditioning or heat pump heating (without electric heat) modes. The nominal airflow for both heating and cooling modes is 350 cfm/ton nominal size of the outdoor unit installed. The airflow actually requested by the User Interface is modified by its internal algorithms for zoning, comfort or efficiency concerns. Refer to the
documentation for the User Interface for more information on how the User Interface controls the fan coil. Safe operation of electric heaters requires airflow delivery at or above the minimum CFM for electric heater application listed in the chart below. The fan coil will adjust its airflow delivery to maintain safe airflow as operating mode and staging conditions require.
FE4A/FE5A FAN COIL AIRFLOW DELIVERY CHART (CFM) -- ELECTRIC HEATING MODELS
MODEL FE4A OUTDOOR UNIT CAPACITY BTUH 5
ELECTRIC HEATER kW RANGE
9
10
15
20
EMERGENCY
625
625
675
775
950
18,000
625
625
675
--
--
002
24,000
650
725
775
900
--
30,000
800
875
875
925
1125
36,000
975
975
975
1025 1125
EMERGENCY
675
700
775
850
1050
24,000
675
875
875
1100 1150
003
30,000
800
875
875
1100 1150
36,000
975
975
1025 1150 1250
42,000
1125
1125 1125 1150 1350
EMERGENCY
675
700
775
850
1050
30,000
800
875
875
1100 1150
005
36,000
975
975
1025 1150 1250
42,000
1125
1125 1125 1150 1250
48,000
1305
1305 1305 1305 1350
EMERGENCY
1050
1050 1050 1050 1125
36,000
1050
1050 1100 1350 1350
006
42,000
1125
1125 1150 1350 1350
48,000
1300
1300 1300 1350 1500
60,000
1625
1625 1625 1625 1750
MODEL FE5A OUTDOOR UNIT CAPACITY BTUH 5
ELECTRIC HEATER kW RANGE
9
10
15
20
EMERGENCY
675
775
775
900
1125
24,000
975
975
975
--
--
004
30,000
1050
1050 1100 1125
--
36,000
1050
1050 1100 1350 1350
42,000
1125
1125 1150 1350 1350
Note 1: Emergency - Air conditioner with electric heater application, or emergency heat. Note 2: These airflows are minimum airflows as UL listed. Note 3: Dashed entry indicates that the heater/fan coil/outdoor unit combination is not approved. Do not apply.
24
-- -- -- -- --
-- -- -- -- --
1400 -- -- --
1500
1750 -- --
1750 1750
24
-- -- -- -- --
30
-- -- -- -- --
-- -- -- -- --
1425 -- -- --
1600
1750 -- --
1750 1750
30
-- -- -- -- --
7
ACCEPTABLE DUCT CONDITIONS
0.7
0.6
0.5
SUPPLY STATIC PRESSURE (in wc)
0.4 ACCEPTABLE RANGE
0.3
0.2
TOO HIGH RETURN STATIC PRESSURE (DIFFICULT TO MAKE TRAP)
0.1
0
0
0.1
0.2
0.3
0.4
0.5
0.6
RETURN STATIC PRESSURE (in wc)
A07273
For satisfactory operation (specifically making dry secondary trap), subject fan coils must be installed with duct systems which fall within the "Acceptable Range" illustrated above.
MINIMUM RPM TABLE
MAXIMUM STATIC TABLE
MODEL
SYSTEM SIZES
CFM RANGE
MIN RPM
MODEL
AIRFLOW DELIVERY
AVAILABLE STATIC PRESSURE
FE4ANF002 FE4AN(B,F)003 FE4AN(B,F)005
FE4ANB006 FE5ANB004
018, 024, 030, 036 024, 030, 036, 042 030, 036, 042, 048 036, 042, 048, 060 024, 030, 036, 042
150 - 1200 300 200 - 1400 285 250 - 1600 275 500 - 2000 275 500 - 1400 275
FE4ANF002
525 CFM 700 CFM 875 CFM 1050 CFM 1200 CFM
1.00 in wc 1.00 in wc 1.00 in wc 0.80 in wc 0.60 in wc
700 CFM
1.00 in wc
875 CFM
1.00 in wc
FE4AN(B,F)003
1050 CFM 1225 CFM
1.00 in wc 1.00 in wc
1400 CFM
0.80 in wc
875 CFM
1.00 in wc
1050 CFM
1.00 in wc
FE4AN(B,F)005
1225 CFM 1400 CFM
1.00 in wc 1.00 in wc
1600 CFM
0.50 in wc
1050 CFM
1.00 in wc
1225 CFM
1.00 in wc
FE4ANB006
1400 CFM 1750 CFM
1.00 in wc 1.00 in wc
2000 CFM
0.60 in wc
700 CFM
1.00 in wc
875 CFM
1.00 in wc
FE5ANB004
1050 CFM 1225 CFM
1.00 in wc 1.00 in wc
1400 CFM
1.00 in wc
8
GROSS COOLING CAPACITIES (MBTUH)
INDOOR COIL
SATURATED TEMPERATURE LEAVING EVAPORATOR (_F / _C)
AIR
35 / 2
40 / 4
45 / 7
50 / 10
55 / 13
CFM EWB
TC
SHC BF
TC
SHC BF
TC
SHC BF
TC
SHC BF
TC
SHC BF
FE4ANF002
72/22 40.19 19.65 0.00 36.23 17.59 0.00 31.86 15.48 0.00 27.00 13.31 0.00 21.65 11.11 0.00
500 67/19 32.99 19.92 0.01 28.96 17.79 0.01 24.52 15.62 0.01 19.64 13.40 0.01 14.28 11.17 0.01
62/17 26.44 20.11 0.01 22.36 17.93 0.01 17.93 15.73 0.01 13.56 13.56 0.03 11.28 11.28 0.19
72/22 49.76 24.23 0.00 44.85 21.76 0.00 39.40 19.20 0.00 33.36 16.55 0.01 26.66 13.83 0.01
650 67/19 40.90 24.80 0.01 35.90 22.22 0.01 30.37 19.55 0.02 24.27 16.82 0.02 17.58 14.06 0.02
62/17 32.84 25.24 0.02 27.75 22.56 0.02 22.25 19.85 0.02 17.13 17.13 0.06 14.25 14.25 0.21
72/22 61.99 30.08 0.00 55.87 27.15 0.00 49.04 24.04 0.01 41.48 20.80 0.02 33.10 17.46 0.02
875 67/19 51.08 31.23 0.03 44.83 28.09 0.03 37.91 24.84 0.03 30.23 21.47 0.03 21.83 18.03 0.03
62/17 41.11 32.14 0.03 34.76 28.88 0.03 27.91 25.53 0.04 22.04 22.04 0.10 18.33 18.33 0.25
72/22 67.83 32.91 0.00 61.10 29.76 0.00 53.66 26.40 0.02 45.36 22.89 0.03 36.17 19.27 0.03
1000 67/19 55.96 34.39 0.04 49.12 31.01 0.04 41.53 27.48 0.04 33.11 23.83 0.04 23.88 20.06 0.04
62/17 45.09 35.62 0.04 38.13 32.08 0.04 30.69 28.43 0.05 24.54 24.54 0.12 20.40 20.40 0.27
72/22 77.77 37.84 0.00 70.13 34.30 0.03 61.59 30.55 0.05 52.04 26.60 0.05 41.42 22.50 0.05
1250 67/19 64.36 40.02 0.06 56.52 36.24 0.06 47.77 32.27 0.06 38.04 28.12 0.06 27.46 23.81 0.07
62/17 51.98 41.92 0.06 44.00 37.93 0.06 35.61 33.77 0.08 29.12 29.12 0.16 24.20 24.20 0.30
FE4ANF003
72/22 43.01 20.98 0.00 38.69 18.78 0.00 33.92 16.51 0.00 28.64 14.18 0.00 22.85 11.81 0.01
600 67/19 35.27 21.34 0.01 30.88 19.04 0.01 26.07 16.71 0.01 20.79 14.34 0.01 15.03 11.95 0.01
62/17 28.24 21.59 0.01 23.81 19.25 0.01 19.05 16.90 0.02 14.56 14.56 0.05 12.11 12.11 0.21
72/22 53.83 26.15 0.00 48.40 23.49 0.00 42.36 20.71 0.00 35.72 17.83 0.02 28.38 14.89 0.02
800 67/19 44.23 26.92 0.02 38.71 24.10 0.02 32.61 21.20 0.03 25.91 18.24 0.03 18.65 15.26 0.03
62/17 35.47 27.49 0.03 29.87 24.58 0.03 23.89 21.65 0.03 18.67 18.67 0.09 15.51 15.51 0.24
72/22 63.07 30.60 0.00 56.66 27.57 0.00 49.58 24.36 0.02 41.76 21.04 0.03 33.10 17.62 0.03
1000 67/19 51.91 31.82 0.04 45.41 28.58 0.04 38.24 25.24 0.04 30.31 21.78 0.04 21.76 18.29 0.05
62/17 41.71 32.80 0.04 35.12 29.43 0.04 28.13 26.00 0.05 22.41 22.41 0.12 18.60 18.60 0.27
72/22 71.01 34.48 0.00 63.77 31.12 0.02 55.79 27.57 0.04 46.95 23.88 0.05 37.18 20.08 0.05
1200 67/19 58.54 36.17 0.05 51.21 32.59 0.05 43.10 28.87 0.06 34.13 25.02 0.06 24.47 21.08 0.06
62/17 47.12 37.60 0.06 39.70 33.86 0.06 31.89 30.00 0.07 25.83 25.83 0.15 21.43 21.43 0.29
72/22 77.95 37.95 0.01 70.07 34.31 0.04 61.29 30.47 0.06 51.54 26.47 0.06 40.78 22.33 0.07
1400 67/19 64.44 40.15 0.07 56.37 36.28 0.07 47.43 32.24 0.07 37.54 28.04 0.07 26.89 23.69 0.08
62/17 51.95 42.08 0.07 43.78 37.99 0.08 35.30 33.73 0.09 28.95 28.95 0.19 24.01 24.01 0.32
FE5ANB004
72/22 40.42 19.84 0.00 36.59 17.80 0.00 32.35 15.70 0.00 27.64 13.54 0.00 22.39 11.33 0.00
600 67/19 33.22 20.00 0.00 29.31 17.90 0.00 24.99 15.74 0.00 20.19 13.53 0.00 14.87 11.27 0.00
62/17 26.67 20.11 0.00 22.69 17.95 0.00 18.31 15.75 0.00 13.60 13.54 0.00 11.29 11.29 0.17
72/22 52.07 25.46 0.00 47.19 22.92 0.00 41.75 20.28 0.00 35.66 17.53 0.00 28.84 14.70 0.00
800 67/19 42.88 25.89 0.00 37.88 23.24 0.00 32.31 20.49 0.00 26.10 17.66 0.00 19.18 14.75 0.00
62/17 34.51 26.21 0.00 29.39 23.46 0.00 23.73 20.64 0.00 17.81 17.81 0.01 14.85 14.85 0.18
72/22 62.54 30.48 0.00 56.75 27.53 0.00 50.25 24.45 0.00 42.94 21.21 0.00 34.73 17.84 0.00
1000 67/19 51.63 31.28 0.00 45.66 28.17 0.01 38.98 24.93 0.01 31.49 21.55 0.01 23.12 18.06 0.01
62/17 41.65 31.91 0.01 35.51 28.66 0.01 28.71 25.30 0.01 21.89 21.89 0.03 18.26 18.26 0.19
72/22 71.89 34.94 0.00 65.33 31.70 0.00 57.89 28.24 0.00 49.50 24.59 0.00 40.06 20.76 0.00
1200 67/19 59.49 36.20 0.01 52.68 32.73 0.01 45.02 29.06 0.01 36.39 25.22 0.01 26.71 21.21 0.01
62/17 48.10 37.22 0.01 41.07 33.55 0.01 33.27 29.72 0.01 25.77 25.77 0.05 21.51 21.51 0.20
72/22 80.24 38.94 0.00 73.00 35.45 0.00 64.73 31.69 0.00 55.41 27.69 0.01 44.86 23.46 0.01
1400 67/19 66.53 40.71 0.01 58.99 36.93 0.01 50.47 32.91 0.02 40.84 28.66 0.02 29.98 24.20 0.02
62/17 53.91 42.17 0.02 46.10 38.14 0.02 37.43 33.92 0.02 29.46 29.46 0.07 24.60 24.60 0.22
FE4ANF005
72/22 57.24 28.01 0.00 51.64 25.08 0.00 45.46 22.08 0.00 38.59 19.00 0.00 30.99 15.85 0.00
750 67/19 46.98 28.35 0.00 41.29 25.33 0.00 35.01 22.24 0.00 28.09 19.09 0.00 20.47 15.90 0.01
62/17 37.67 28.59 0.01 31.89 25.50 0.01 25.61 22.37 0.01 19.28 19.28 0.02 16.05 16.05 0.19
72/22 69.68 33.97 0.00 62.89 30.52 0.00 55.32 26.92 0.00 46.89 23.21 0.00 37.57 19.40 0.00
950 67/19 57.29 34.68 0.01 50.33 31.06 0.01 42.64 27.33 0.01 34.14 23.51 0.01 24.80 19.63 0.01
62/17 45.99 35.21 0.01 38.92 31.47 0.01 31.24 27.68 0.01 23.90 23.90 0.04 19.89 19.89 0.20
72/22 80.80 39.28 0.00 72.96 35.40 0.00 64.17 31.32 0.00 54.37 27.06 0.01 43.48 22.66 0.01
1150 67/19 66.56 40.46 0.02 58.50 36.34 0.02 49.54 32.05 0.02 39.60 27.64 0.02 28.70 23.15 0.02
62/17 53.51 41.36 0.02 45.29 37.07 0.02 36.38 32.70 0.02 28.26 28.26 0.07 23.51 23.51 0.22
72/22 97.47 47.29 0.00 88.05 42.83 0.00 77.49 38.05 0.01 65.68 33.04 0.02 52.41 27.78 0.02
1500 67/19 80.52 49.40 0.03 70.85 44.58 0.03 60.01 39.53 0.03 47.89 34.25 0.03 34.64 28.83 0.04
62/17 64.96 51.12 0.03 55.02 46.04 0.03 44.30 40.80 0.04 35.27 35.27 0.10 29.34 29.34 0.25
72/22 105.61 51.26 0.00 95.43 46.52 0.01 84.03 41.43 0.03 71.21 36.06 0.03 56.82 30.42 0.03
1700 67/19 87.38 53.92 0.04 76.93 48.80 0.04 65.20 43.40 0.04 52.01 37.70 0.04 37.60 31.83 0.05
62/17 70.60 56.17 0.04 59.87 50.74 0.04 48.32 45.08 0.05 38.96 38.96 0.13 32.40 32.40 0.27
FE4ANB006
72/22 76.01 37.07 0.00 68.82 33.39 0.00 60.76 29.56 0.00 51.72 25.55 0.00 41.64 21.42 0.00
1050 67/19 62.63 37.91 0.01 55.22 34.04 0.01 46.97 30.03 0.01 37.78 25.89 0.01 27.60 21.64 0.01
62/17 50.40 38.54 0.01 42.81 34.53 0.01 34.49 30.41 0.01 26.28 26.28 0.03 21.90 21.90 0.19
72/22 89.66 43.58 0.00 81.26 39.43 0.00 71.77 35.02 0.00 61.13 30.39 0.00 49.17 25.55 0.01
1300 67/19 74.04 45.04 0.01 65.36 40.60 0.01 55.62 35.94 0.01 44.72 31.09 0.01 32.62 26.09 0.01
62/17 59.73 46.18 0.01 50.78 41.52 0.02 40.97 36.70 0.02 31.77 31.77 0.06 26.48 26.48 0.21
72/22 110.09 53.41 0.00 99.92 48.64 0.00 88.41 43.46 0.01 75.38 37.95 0.02 60.66 32.13 0.02
1750 67/19 91.28 56.16 0.02 80.74 50.96 0.03 68.83 45.42 0.03 55.35 39.55 0.03 40.35 33.42 0.03
62/17 73.94 58.45 0.03 63.04 52.91 0.03 51.08 47.08 0.03 40.82 40.82 0.10 34.04 34.04 0.24
72/22 121.19 58.89 0.00 110.14 53.79 0.01 97.57 48.25 0.02 83.25 42.30 0.03 67.02 35.98 0.03
2050 67/19 100.75 62.56 0.04 89.24 56.99 0.04 76.15 51.01 0.04 61.30 44.63 0.04 44.72 37.88 0.04
62/17 81.81 65.71 0.04 69.88 59.72 0.04 56.88 53.37 0.05 46.27 46.27 0.12 38.60 38.60 0.26
72/22 126.10 61.36 0.00 114.71 56.14 0.02 101.67 50.45 0.03 86.78 44.32 0.03 69.87 37.76 0.04
2200 67/19 104.99 65.51 0.04 93.05 59.79 0.04 79.44 53.62 0.04 63.97 47.02 0.04 46.71 40.00 0.05
62/17 85.35 69.12 0.04 72.98 62.94 0.05 59.55 56.35 0.06 48.85 48.85 0.14 40.75 40.75 0.27
9
CFM - Cubic Ft per Minute
EWB - Entering Wet Bulb (_F / _C)
SHC - Gross Sensible Capacity 1000 Btuh BF - Bypass Factor
NOTES: 1. Contact manufacturer for cooling capacities at conditions other
than shown in table.
2. Formulas:
Leaving db = entering db -sensible heat cap.
1.09 x CFM
Leaving wb = wb corresponding to enthalpy of air leaving coil (hlwb) hlwb = hewb -total capacity (Btuh)
4.5 x CFM
where hewb = enthalpy of air entering coil. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 80_F db temperature of air entering coil. Below 80_F db, subtract (Correction Factor x CFM) from SHC. Above 80_F db, add (Correction Factor x CFM) to SHC.
4. Bypass Factor = 0 indicates no psychometric solution. Use by pass factor of next lower EWB for approximation.
LWB - Leaving Wet Bulb (_F / _C) TC - Gross Cooling Capacity 1000 Btuh MBH - 1000 Btuh
SHC CORRECTION FACTOR
BYPASS FACTOR
0.10 0.20 0.30
ENTERING AIR DRY-BULB TEMPERATURE (_F)
79 78 77
76
75
Under 75
81 82 83 84 85
Over 85
Correction Factor
.098 1.96 2.94 3.92 4.91 Use formula
0.87 1.74 2.62 3.49 4.36
shown
0.76 1.53 2.29 3.05 3.82
below
Interpolation is permissible. Correction Factor = 1.09 x (1 - BF) x (db - 80)
ESTIMATED SOUND POWER LEVEL (dBA)
MODEL SIZE
CONDITIONS
OCTAVE BAND CENTER FREQUENCY
CFM
ESP
63
125
250
500
1000
2000
4000
400
0.25
61.0
57.0
55.0
50.0
48.0
46.0
42.0
600
0.25
62.7
58.7
56.7
51.7
49.7
47.7
43.7
800
0.25
64.0
60.0
58.0
53.0
51.0
49.0
45.0
FE4ANF002
1000
0.25
65.0
61.0
57.0
56.0
52.0
50.0
46.0
1200
0.25
65.8
61.8
57.8
56.8
52.8
50.8
46.8
1400
0.25
66.4
62.4
58.4
57.4
53.4
51.4
47.4
400
0.25
61.0
57.0
55.0
50.0
48.0
46.0
42.0
600
0.25
62.7
58.7
56.7
51.7
49.7
47.7
43.7
800
0.25
64.0
60.0
58.0
53.0
51.0
49.0
45.0
FE4ANF003
1000
0.25
65.0
61.0
59.0
54.0
52.0
50.0
46.0
1200
0.25
65.8
61.8
59.8
54.8
52.8
50.8
46.8
1400
0.25
66.4
62.4
58.4
57.4
53.4
51.4
47.4
1600
0.25
67.0
63.0
59.0
58.0
54.0
52.0
48.0
600
0.25
62.7
58.7
56.7
51.7
49.7
47.7
43.7
800
0.25
64.0
60.0
58.0
53.0
51.0
49.0
45.0
1000
0.25
65.0
61.0
59.0
54.0
52.0
50.0
46.0
FE5ANB004
1200
0.25
65.8
61.8
59.8
54.8
52.8
50.8
46.8
1400
0.25
66.4
62.4
60.4
55.4
53.4
51.4
47.4
1600
0.25
67.0
63.0
61.0
56.0
54.0
52.0
48.0
400
0.25
61.0
57.0
55.0
50.0
48.0
46.0
42.0
600
0.25
62.7
58.7
56.7
51.7
49.7
47.7
43.7
800
0.25
64.0
60.0
58.0
53.0
51.0
49.0
45.0
FE4ANF005
1000
0.25
65.0
61.0
59.0
54.0
52.0
50.0
46.0
1200
0.25
65.8
61.8
59.8
54.8
52.8
50.8
46.8
1400
0.25
66.4
62.4
58.4
57.4
53.4
51.4
47.4
1600
0.25
67.0
63.0
59.0
58.0
54.0
52.0
48.0
600
0.25
62.7
58.7
56.7
51.7
49.7
47.7
43.7
800
0.25
64.0
60.0
58.0
53.0
51.0
49.0
45.0
1000
0.25
65.0
61.0
59.0
54.0
52.0
50.0
46.0
1200
0.25
65.8
61.8
59.8
54.8
52.8
50.8
46.8
FE4ANB006
1400
0.25
66.4
62.4
60.4
55.4
53.4
51.4
47.4
1600
0.25
67.0
63.0
61.0
56.0
54.0
52.0
48.0
1800
0.25
67.5
63.5
59.5
58.5
54.5
52.5
48.5
2000
0.25
68.0
64.0
60.0
59.0
55.0
53.0
49.0
2150
0.25
68.3
64.3
60.3
59.3
55.3
53.3
49.3
*Est. sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook, chapter 52, p. 52.7.
AIRFLOW PERFORMANCE CORRECTION FACTORS
HEATER kW
ELEMENTS
STATIC PRESSURE CORRECTION (in wc)
Sizes 002005
Size 006
0
0
+.02
+.03
5
1
+.01
+.02
8, 10
2
0
0
9, 15
3
.02
.03
20
4
.04
.06
18, 24, 30
6
.06
.10
The airflow performance table was developed using fan coils with 10kW electric heaters (2 elements) in the units. For fan coils with heaters made up of a different
number of elements, the external available static at a given CFM from the table may be corrected by adding or subtracting pressure. Use table for this correction.
10
FACTORY-INSTALLED FILTER STATIC PRESSURE DROP (in wc)
MODEL
CFM
FE4A
400
600
800
1000
1200
1400
1600
002
0.020
0.044
0.048
0.072
0.100
--
--
003
--
0.020
0.035
0.051
0.070
0.092
--
005
--
--
0.035
0.051
0.070
0.092
0.120
006
--
--
--
0.038
0.053
0.070
0.086
MODEL
CFM
FE5A
400
600
800
1000
1200
1400
1600
004
--
0.015
0.026
0.038
0.053
0.070
--
1800 -- -- --
0.105
1800 --
2000 -- -- --
0.133
2000 --
AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (in wc) AT INDICATED AIRFLOW (DRY TO WET COIL)
MODEL
CFM
FE4A
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
002
0.012
0.016
0.022
0.028
0.034
0.040
0.049
--
--
--
--
003
--
0.026
0.034
0.042
0.052
0.063
0.075
0.083
0.091
0.098
0.110
005
--
0.006
0.008
0.010
0.012
0.015
0.017
0.020
0.023
0.027
0.030
CFM
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
006
0.013
0.016
0.018
0.020
0.023
0.027
0.030
0.034
0.039
0.044
0.048
MODEL
CFM
FE5A
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
004
0.004
0.005
0.007
0.009
0.011
0.013
0.016
0.018
0.020
0.023
--
NOTE: Subtract the above pressure drop corrections from unit airflow data when that component or condition is used. The remaining external static pressure will be available for the duct system.
UNITS WITHOUT ELECTRIC HEAT
UNIT SIZE
VOLTS-PHASE
FLA
MIN CKT AMPS
BRANCH CIRCUIT
Min Wire Size Awg*
Fuse/Ckt Bkr Amps
002
208/230-1
4.3
5.4
14
15
003
208/230-1
4.3
5.4
14
15
005
208/230-1
4.3
5.4
14
15
004, 006
208/230-1
6.8
8.5
14
15
* Use copper wire only to connect unit. If other than uncoated (non-plated) 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used consult applicable tables of the National Electric Code (ANSI/NFPA 70).
NOTE: If branch circuit wire length exceeds 100-ft (30.5 m), consult NEC 210-19a to determine maximum wire length. Use 2% voltage drop.
FLA -- Full Load Amps
ACCESSORY ELECTRIC HEATERS
HEATER PART NO.
kW @ 240V
VOLTS/ PHASE
KFCEH0501N05
5
230/1
KFCEH0901N10
10
230/1
KFCEH3001F15
15
230/1
KFCEH3201F20
20
230/1
KFCEH2901N09
9
230/1*
KFCEH1601315
15
230/3
KFCEH3401F24
24
230/3
KFCEH3501F30
30
230/3
KFCEH2401C05
5
230/1
KFCEH2601C10
10
230/1
KFCEH3101C15
15
230/1
KFCEH3301C20
20
230/1
* Field convertible to 3 phase.
{ These heaters field convertible to single phase.
STAGES (kW OPERATING)
5 10 5, 15 5, 20 3, 9 5, 15 8, 16, 24 10, 20, 30 5 10 5, 15 5, 20
INTERNAL CIRCUIT PROTECTION
FAN COIL SIZE USED
WITH
HEATING CAP. @ 230V
INTELLIGENT HEAT CAPABLE (kW OPERATING)
None
All
15,700
--
None
All
31,400
--
Fuses**
All
47,100
5, 10, 15
Fuses**
All
62,800
5, 10, 15, 20
None
All
28,300
3, 6, 9
None
All
47,100
--
Fuses
005, 006
78,500
8, 16, 24
Fuses
005, 006
94,200
10, 20, 30
Ckt Bkr
All
15,700
--
Ckt Bkr
All
31,400
--
Ckt Bkr
All
47,100
5, 10, 15
Ckt Bkr
All
62,800
5, 10, 15, 20
** Single point wiring kit required for these heaters in Canada.
Blower motor heat not included.
ELECTRIC HEATER INTERNAL PROTECTION
HEATER kW 5 8 9 10 15 15 18 20 24 30
* All circuit breakers are 2 pole.
PHASE 1 1 1/3 1 1 3 3 1 3/1 3/1
FUSES QTY / SIZE -- -- -- --
2/30, 2/60 -- -- 4/60 6/60 6/60
CKT BKR QTY / SIZE* 1/60 1/60 -- 1/60 2/60 -- -- 2/60 -- --
11
ACCESSORY ELECTRIC HEATER ELECTRICAL DATA
HEATER PART NO.
kW
P H A S E
INTERNAL CIRCUIT PROTEC
TION
240v
208v
KFCEH0501N05
5
3.8
1
None
KFCEH2401C05
5
3.8
1
Ckt Bkr
KFCEH0801N08
8
6.0
1
None
KFCEH2501C08
8
6.0
1
Ckt Bkr
KFCEH2901N09*
9
6.8
1
None
KFCEH2901N09*
9
6.8
3
None
KFCEH0901N10
10
7.5
1
None
KFCEH2601C10
10
7.5
1
Ckt Bkr
KFCEH3001F15* 1
15
11.3
1
Fuse
KFCEH3101C15*
15
11.3
1
Ckt Bkr
KFCEH1601315
15
11.3
3
None
KFCEH2001318
18
13.5
3
None
KFCEH3201F20* 1
20
15.0
1
Fuse
KFCEH3301C20*
20
15.0
1
Ckt Bkr
24
18.0
3
KFCEH3401F24*
24
18.0
1
Fuse Fuse
30
22.5
3
KFCEH3501F30*
30
22.5
1
Fuse Fuse
HEATER AMPS 208/230V
Single Circuit
18.1/20.0 18.1/20.0 28.9/32.0 28.9/32.0 32.8/36.0 18.8/20.8 36.2/40.0 36.2/40.0 54.2/59.9
-- 31.3/34.6 37.6/41.5 72.3/79.9
-- 50.1/55.4 86.7/95.5 62.6/69.2 109.0/120.0
Dual Circuit
L1,L2
L3,L4
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
36.2/40.0
18.1/20.0
36.2/40.0
18.1/20.0
--
--
--
--
36.2/40.0
36.2/40.0
36.2/40.0
36.2/40.0
--
--
--
--
--
--
--
--
Min Ampacity 208/230V**
Single Circuit
Dual Circuit
L1,L2
L3,L4
31.2/33.5
--
--
31.2/33.5
--
--
44.7/48.5
--
--
44.7/48.5
--
--
49.5/53.5
--
--
32.0/34.5
--
--
53.8/58.5
--
--
53.8/58.5
--
--
76.3/83.4
53.8/58.5
22.7/25.0
--
53.8/58.5
22.7/25.0
47.7/51.8
--
--
55.5/60.4
--
--
98.9/108.4
53.8/58.5
45.3/50.0
--
53.8/58.5
45.3/50.0
71.2/77.8
--
--
116.9/127.9
--
--
86.8/95.0
--
--
144.8/158.5
--
--
Min Wire Size (AWG) 208/230V
Single Circuit
Dual Circuit
L1,L2
L3,L4
8/8
--
--
8/8
--
--
8/8
--
--
8/8
--
--
8/6
--
--
8/8
--
--
6/6
--
--
6/6
--
--
4/4
6/6
10/10
--
6/6
10/10
8/6
--
--
6/6
--
--
3/2
6/6
8/8
--
6/6
8/8
4/4
--
--
1/1
--
--
3/3
--
--
0/00
--
--
BRANCH CIRCUIT
Min Gnd Wire Size 208/230V
Single Circuit
Dual Circuit
L1,L2
L3,L4
10/10
--
--
10/10
--
--
10/10
--
--
10/10
--
--
10/10
--
--
10/10
--
--
10/10
--
--
10/10
--
--
8/8
10/10
10/10
--
10/10
10/10
10/10
--
--
10/8
--
--
8/6
10/10
10/10
--
10/10
10/10
8/8
--
--
6/6
--
--
8/8
--
--
6/6
--
--
Max Fuse/Ckt Bkr Amps 208/230V
Single Circuit
Dual Circuit
L1,L2
L3,L4
35/35
--
--
35/35
--
--
45/50
--
--
45/50
--
--
50/60
--
--
35/35
--
--
60/60
--
--
60/60
--
--
80/90
60/60
25/25
--
60/60
25/25
50/60
--
--
60/70
--
--
100/110
60/60
50/50
--
60/60
50/50
80/80
--
--
125/150
--
--
90/100
--
--
150/175
--
--
Max Wire Length 208/230V (ft)
Single Circuit
Dual Circuit
L1,L2
L3,L4
85/88
--
--
85/88
--
--
59/60
--
--
59/60
--
--
54/87
--
--
83/85
--
--
78/80
--
--
78/80
--
--
88/89
78/80
75/76
--
78/80
75/76
56/90
--
--
76/77
--
--
85/109
78/80
59/59
--
78/80
59/59
94/95
--
--
115/116
--
--
97/98
--
--
117/150
--
--
FIELD MULTIPOINT WIRING OF 24-AND 30-kW SINGLE PHASE
12
HEATER PART NO.
P
kW
H
A
S
240V 208V E
HEATER AMPS 208/230V
L1,L2
L3,L4
L5,L6
MIN AMPACITY 208/230V**
L1,L2
L3,L4
L5,L6
MIN WIRE SIZE (AWG) 208/230V
L1,L2 L3,L4 L5,L6
MIN GND WIRE SIZE 208/230V
MAX FUSE/CKT BKR AMPS
208/230V
L1,L2 L3,L4 L5,L6
MAX WIRE LENGTH 208/230V (FT)
L1,L2 L3,L4 L5,L6
KFCEH3401F24 *
24
18.0
1 28.9/32.0 28.9/32.0 28.9/32.0 44.7/48.5 36.2/40.0 36.2/40.0
8/8
8/8
8/8
10/10
45/50 40/40 40/40 59/60 73/73
73/73
KFCEH3501F30 *
30
22.5
1 36.2/40.0 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 45.3/50.0
6/6
8/8
8/8
10/10
60/60 50/50 50/50 78/80 59/59
59/59
* Heaters are Intelligent Heat capable when used with the FE fan coil and Zone Perfect Plust or Evolution Controlt. { Field convertible to 1 phase, single or multiple supply circuit. } Field convertible to 3 phase. ** Includes blower motor amps of largest fan coil used with heater. {{ Copper wire must be used. If other than uncoated (non-plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of
the National Electric Code (ANSI/NFPA 70). }} Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%. NOTES: 1. Single circuit application of F15 and F20 heaters requires single-point wiring kit accessory.
ACCESSORIES
REQUIRED ACCESSORY
ITEM
Evolutionr Connext Control with Integrated Wi-Fi
or
1.
Evolutionr Connext Control Wi-Fi
with bundled router
or
Evolutionr Connext Control
ACCESSORY PART NO.*
SYSTXBBECC01
SYSTXBBECW01
SYSTXBBECN01
FAN COIL SIZE USED WITH All
All All
ADDITIONAL ACCESSORIES
ITEM
2.
Evolutionr Series 4 Zone Board
3.
Evolutionr Series Smart Sensor
4.
Evolutionr Remote Room Sensor
5.
Evolutionr Series Network Interface Module
6.
Disconnect Kit
7.
Downflow Base Kit
8.
Downflow Conversion Kit
9.
Single-Point Wiring Kit
10.
Filter Kit (12 Pack)
11.
Filter Media Cabinet
12.
Media Filter Cartridges
13.
Evolutionr Series Air Purifier
14.
PVC Condensate Trap Kit (50 pack)
15.
Air Cleaner 240-volt Conversion Kit
16.
Downflow/Horizontal Conversion Gasket Kit
17.
Horizontal Water Management Kit (25 pack)
18.
Standard Filter Rack Kit
19.
Hydronic Relay Interface Kit
20.
Door Gasket Kit **
ACCESSORY PART NO.*
SYSTXBB4ZC01 SYSTXBBSMS01-D
SYSTXBBRRS01 SYSTXBBNIM01 KFADK0201DSC KFACB0201CFB KFACB0301CFB KFACB0401CFB KFADC0201SLP KFADC0401ACL KFASP0101SPK KFAFK0212MED KFAFK0312LRG KFAFK0412XXL FNCCABBB0017 FNCCABBB0021 FNCCABBB0024 FILBBFNC0017 FILBBFNC0021 FILBBFNC0024 GAPABXBB1620 GAPABXBB2020 GAPABXBB2024 KFAET0150ETK KEAVC0201240 KFAHD0101SLP KFAHC0125AAA KFAFR0101FRM KFAFR0201FRM KFAFR0301FRM KFAFR0401FRM KFAIF0101HWC
344994-751
FAN COIL SIZE USED WITH
All All All All Cooling controls and heaters 3- through 10-kW 002 003, 005 004, 006 003 002, 004, 005, 006 Only with 15- and 20-kW Fused Heaters 002 003, 005 004, 006 002 003, 005 004, 006 002 003, 005 004, 006 002 003, 005 004, 006 All All All All NA 002 003, 005 004, 006 All All
* Factory authorized and listed, field installed. ** This kit is for replacement of factory installed gaskets if they are damaged or removed from the fan coil.
13
ACCESSORIES (CONT.)
Accessory Kits Description Suggested and Required Use 1. Evolutionr Connext Control with Integrated Wi-Fi
Deluxe programmable wall-mounted system control with integrated Wi-Fi. or Evolutionr Connext Control Wi-Fi with bundled router Deluxe programmable wall-mounted system control with integrated Wi-Fi. Sold bundled with Wi-Fi router or Evolutionr Connext Control Deluxe programmable wall-mounted system control without remote access.
2. Evolutionr 4 Zone Board 4-Zone Damper Control Module wall-mounted control. REQUIRED USE: For all four-zone systems. For systems with 5 to 8 zones, a second Damper Control Module is required.
3. Evolutionr Smart Sensor Wall control used to monitor temperature and/or fan control. SUGGESTED USE: For use in zone systems.
4. Evolutionr Remote Room Sensor Wired remote temperature sensor for zone control. SUGGESTED USE: For use in zone systems..
5. Evolutionr Series Network Interface Module Connects Heat Recovery and Energy Recovery Ventilators on non-zoning applications and non-communicating 2-speed units. REQUIRED USE: For non-zoned systems installed with HRV or ERV, Hybrid Heat with non-communicating heat pumps or non- communicating 2-speed units.
6. Disconnect Kit The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely. SUGGESTED USE: Units for 3- through 10-kW electric resistance heaters and cooling controls.
7. Downflow Base Kit This kit is designed to provide a 1-in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides a gap-free seal with the floor. REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
8. Downflow Conversion Kit Fan coils are shipped from the factory for upflow or horizontal-left applications. Downflow conversion kits provide proper condensate water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A-coils. REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
9. Single Point Wiring Kit The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run 2 heavy-gauge, high-voltage wires into the fan coil rather than 4 light-gauge, high-voltage wires. SUGGESTED USE: Fan coils with 15- and 20-kW fused heaters only.
10. Filter Kit (12 pack) The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevents them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and, in turn, the efficiency of the system. SUGGESTED USE: To replace filters in fan coils. REQUIRED USE: All units unless a filter grille is used.
11. Filter Media Cabinet This cabinet is mounted to the fan coil on the return air end and designed to slip over the outer fan coil casing. The cabinets are insulated using the same insulation as production fan coils. They are designed for the removal of particulates from indoor air using FILCCFNC00(14, 17, 21, 24) media filter cartridges. SUGGESTED USE: All fan coils.
12. Media Filter Cartridges These fan coil media filter cartridge kits are designed for the removal of particles from indoor air. The cartridge is installed in the return air duct next to the air handler or further upstream. SUGGESTED USE: All fan coils.
13. Evolutionr Series Air Purifier The Evolution Series Air Purifier wires directly to fan coil and requires no duct transitions with Bryant units. It comes with an airflow sensor. SUGGESTED USE: All fan coils.
14. Condensate Drain Trap Kit This kit consists of 50 PVC condensate traps. Each trap is pre-formed and ready for field installation. This deep trap helps the system make and hold proper condensate flow even during blower initiation. SUGGESTED USE: All fan coils.
15. Air Cleaner 240-volt Conversion Kit The AIRA electronic air cleaner comes ready for 115-v operation. REQUIRED USE: This kit is required when running 240-volt circuit to air cleaner.
14
ACCESSORIES (CONT.)
16. Downflow/Horizontal Conversion Gasket Kit This kit provides the proper gasketing of units when applied in either a downflow or horizontal application. REQUIRED USE: Fan coils in either downflow or horizontal applications.
17. Horizontal Water Management Kit This kit provides proper installation of fan coils under conditions of high static pressure and high relative humidity. SUGGESTED USE: All fan coils (except FE5 and FF1).
18. Standard Filter Rack Kit This kit mounts in fan coil filter rack area and modifies the existing filter rack to support standard 1-in. filter sizes. SUGGESTED USE: Fan coils using standard filter sizes.
19. Hydronic Relay Interface Kit This kit provides interface of the FE4 and FE5 fan coils with Hydronic Heat equipment. NOTE: Electric heat cannot be used with Hydronic Interface Relay Kit. SUGGESTED USE: All FE4 and FE5 fan coils installed with hydronic heat.
20. Door Gasket Kit This kit consists of specific adhesive-backed foam strips which are applied to the unit door and frame, limiting air leakage.
15
NOTES: ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------ ------------------------------------------------------------------------------------