Technical Manuals Water - Queensland Urban Utilities
WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual QUEENSLAND URBAN UTILITIES HUDDART STREET, ALDERLEY WATER BOOSTER PUMP STATION WB002 ________________________________ ELECTRICAL SWITCHBOARD OPERATION AND MAINTENANCE MANUAL Developed by: Q-Pulse Id: TMS196 J & P RICHARDSON INDUSTRIES CAMPBELL AVENUE WACOL QLD 4076 ABN 23 001 952 325 ACN 001 952 325 Ph. (07) 3271 2911 Fax. (07) 3271 3623 26/11/2012 Page 1 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd CONTENTS 1 Introduction 1.1 Operating Instructions 2 Description of Operation 2.1 Mode Selection 2.2 Manual Control 2.3 Automatic Control 3 Pumps 4 Electrical Equipment Technical Information 4.1 Circuit Breakers & Isolators 4.2 Surge Protection & Fuses 4.3 Control Devices 4.4 Instruments 4.5 Pushbuttons & Selector Switches 4.6 Terminals & Links 4.7 Telemetry & Power 4.8 Accessories 5 Switchboard Works Test Results 6 "As Constructed" Drawings 7 Service & Maintenance Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 2 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 1 INTRODUCTION These operating instructions cover the Huddart Street, Alderley Pumping Station WB002 electrical equipment supplied by J & P Richardson Industries Pty Ltd in 2011, 2012. 1.1 OPERATING INSTRUCTIONS Normal operation of the pumping station is in the automatic mode with control by means of a Master Programmable Logic Controller (PLC), which receives level signals from the Level Measurement System in the wet well/Electronic Level Relays/Float Switches. Manual operation control of the station is available by means of selector switches on the motor control switchboard. Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 3 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 2 DESCRIPTION OF OPERATION 2.1 MODE SELECTION The station can be operated either automatically or manually with mode selection being made by means of the mode selector switches mounted on each pump section of the switchboard. These selector switches are designated with the following mode selections AUTO-OFFMAN. 2.2 MANUAL CONTROL Each pumping unit can be run in manual control from the motor control centre by: - a) Selecting the "MAN" setting on the "MODE SELECTOR SWITCHES" as described in Clause 2.1 b) Starting by "START" pushbutton. c) Stopping by "STOP" pushbutton. N.B. DO NOT LEAVE IN MANUAL WHILE STATION UNATTENDED 2.3 AUTOMATIC CONTROL For automatic control of the station: - a) The "MODE SELECTOR SWITCHES" on the switchboard should be in the "AUTO" position. b) The "DUTY SELECTOR SWITCH" should be set to provide the desired pump operation sequence. The "DUTY SELECTOR SWITCH" is marked: - 1-2 2-1 The pumps should be alternated at regular intervals to ensure that each pump unit has a reasonably equal running time. The total running hours of each pump unit is displayed on the hour meter located on each pump section of the switchboard. c) The automatic Duty Selection is done via the PLC software. Refer PLC SOFTWARE Section for details. The total running hours of each pump unit is displayed on the hour meter located on each pump section of the switchboard. d) The automatic starting and stopping of the pumps is controlled by signals from the Master PLC. For NORMAL OPERATION, each of the pump selector switches should have "AUTO" mode selected. In the AUTOMATIC mode the selected Duty Pump unit will start automatically as preset by the level in the wet well. In the event of the duty pump not being capable of supplying enough flow to continue draining the wet well and the well level rises to a second preset level, then the Standby Pump unit will automatically start, to provide additional pumping. The supplementary pump unit also takes over for the respective pump duty on the occurrence of one the Duty Pump unit failing. Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 4 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 3 PUMPS SUPPLIER: MODEL: kW RATING: Grundfos 30 Blanck Street Ormeau Qld 4208 Ph: (07) 5540 6700 Fax: (07) 5540 6710 Hydro MPC-E 4xCRE45-2 7.5 Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 5 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual GRUNDFOS INSTRUCTIONS BoosterpaQ Hydro MPC Installation and operating instructions Q-Pulse Id: TMS196 26/11/2012 Page 6 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 24 months from date of installation, but not more than 30 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repairing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture. Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manufacturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions. To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions. Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed. GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE. Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction. 2 Q-Pulse Id: TMS196 26/11/2012 Page 7 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual CONTENTS 1. Symbols used in this document 2. Scope of these instructions 3. Product description 4. Nameplate 5. Software label 6. Type key 6.1 Examples of control variants 7. 7.1 7.1.1 7.1.2 7.1.3 7.1.4 7.1.5 7.2 7.3 Installation Mechanical installation Location Pipework Foundation Vibration dampers Expansion joints Electrical installation Start-up 8. Control panel 8.1 Display (pos. 1) 8.1.1 Menu line 8.1.2 Top line 8.1.3 Graphical illustration 8.1.4 Scroll bar 8.1.5 Bottom line 8.2 Buttons and indicator lights 8.2.1 Arrow to the right (pos. 2) 8.2.2 Help (pos. 3) 8.2.3 Up and down (pos. 4 and 5) 8.2.4 Plus and minus (pos. 6 and 7) 8.2.5 Esc (pos. 8) 8.2.6 Home (pos. 9) 8.2.7 Ok (pos. 10) 8.2.8 Indicator lights (pos. 11 and 12) 8.2.9 Contrast (pos. 13) 8.2.10 Back light 9. 9.1 9.2 9.3 9.4 9.4.1 9.4.2 9.4.3 9.4.4 9.4.5 9.4.6 9.4.7 9.4.8 9.5 9.5.1 9.5.2 9.5.3 9.5.4 9.5.5 9.5.6 9.6 9.6.1 9.6.2 9.6.3 9.7 9.7.1 9.7.2 9.7.3 9.7.4 9.7.5 Functions Tree of functions Overview Description of functions Status (1) Current alarms (3.1) System (1.2) Operating mode (1.2.1) Setpoint (1.2.2) Setpoint influence (1.2.3) Measured values (1.2.4) Analog inputs (1.2.5) Pump 1...6 (1.3 to 1.8) Operation (2) Operation (2) System operating mode (2.1.1) Control mode (2.1.2) Setpoints (2.1.3) Individual pump control (2.1.4) Setting of individual operating mode (2.1.4.1 to 2.1.4.6) Alarm (3) Alarm status (3) Current alarms (3.1) Alarm log (3.2) Settings (4) Primary controller (4.1) PI controller (4.1.1) Alternative setpoints (4.1.2) Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7) External setpoint influence (4.1.3) Page 4 4 4 5 5 6 6 9 9 9 9 9 9 9 10 10 12 12 12 12 12 12 12 13 13 13 13 13 13 13 13 13 13 13 14 14 17 19 19 19 19 20 20 20 21 21 21 21 22 22 23 25 25 26 27 27 32 32 32 33 33 33 34 34 9.7.6 Setting of influence function (4.1.3.2) 35 9.7.7 Primary sensor (4.1.4) 35 9.7.8 Clock program (4.1.6) 36 9.7.9 Proportional pressure (4.1.7) 36 9.7.10 S-system configuration (4.1.8) 37 9.7.11 Pump cascade control (4.2) 37 9.7.12 Min. time between start/stop (4.2.1) 38 9.7.13 Max. number of starts/hour (4.2.1) 38 9.7.14 Standby pumps (4.2.3) 38 9.7.15 Forced pump changeover (4.2.4) 39 9.7.16 Pump test run (4.2.5) 39 9.7.17 Pilot pump (4.2.6) 40 9.7.18 Pump stop attempt (4.2.7) 40 9.7.19 Pump start and stop speed (4.2.8) 41 9.7.20 Min. performance (4.2.9) 41 9.7.21 Compensation for pump start-up time (4.2.10) 42 9.7.22 Secondary functions (4.3) 42 9.7.23 Stop function (4.3.1) 42 9.7.24 Soft pressure build-up (4.3.3) 44 9.7.25 Emergency run (4.3.5) 45 9.7.26 Digital inputs (4.3.7) 45 9.7.27 Functions of digital inputs (4.3.7.1) 46 9.7.28 Analog inputs (4.3.8) 46 9.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) 47 9.7.30 Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1) 47 9.7.31 Digital outputs (4.3.9) 48 9.7.32 Functions of digital outputs (4.3.9.1 to 4.3.9.16) 48 9.7.33 Min., max. and user-defined duty (4.3.14) 49 9.7.34 Min. duty (4.3.14.1) 49 9.7.35 Max. duty (4.3.14.2) 49 9.7.36 User-defined duty (4.3.14.3) 50 9.7.37 Pump curve data (4.3.19) 50 9.7.38 Control source (4.3.20) 51 9.7.39 Fixed inlet pressure (4.3.22) 52 9.7.40 Flow estimation (4.3.23) 52 9.7.41 Monitoring functions (4.4) 52 9.7.42 Dry-running protection (4.4.1) 53 9.7.43 Dry-running protection with pressure/level switch (4.4.1.1) 53 9.7.44 Dry-running protection with pressure transmitter (4.4.1.2) 54 9.7.45 Dry-running protection with level transmitter (4.4.1.3) 54 9.7.46 Min. pressure (4.4.2) 55 9.7.47 Max. pressure (4.4.3) 55 9.7.48 External fault (4.4.4) 56 9.7.49 Limit 1 and 2 exceeded (4.4.5 and 4.4.6) 56 9.7.50 Pumps outside duty range (4.4.7) 57 9.7.51 Pressure relief (4.4.8) 57 9.7.52 Functions, CU 351 (4.5) 58 9.7.53 Display language (4.5.1) 58 9.7.54 Display units (4.5.2) 59 9.7.55 Date and time (4.5.3) 60 9.7.56 Passwords (4.5.4) 60 9.7.57 Ethernet (4.5.5) 60 9.7.58 GENIbus number (4.5.6) 61 9.7.59 Software status (4.5.9) 61 9.8 Data communication 62 9.8.1 Ethernet 62 9.8.2 GENIbus 64 10. External variable frequency drive 65 10.1 VLT 2800 65 10.2 Danfoss VLT 8000 factory settings 66 10.3 Danfoss VLT 8000 extended menu programming 66 10.4 Danfoss VLT 8000 factory settings 67 10.5 Danfoss VLT 8000 extended menu programming 67 10.6 Baldor Smart motor settings 68 10.7 VLT FC 202 69 Q-Pulse Id: TMS196 26/11/2012 3 Page 8 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 11. Fault finding chart 70 12. Maintenance 71 12.1 Pumps 71 12.2 Motor bearings 71 12.3 CU 351 71 13. Frost protection 71 14. Taking out of operation 71 15. Technical data 71 15.1 Pressure 71 15.2 Temperature 72 15.3 Relative humidity 72 15.4 Sound pressure 72 16. Electrical data 72 17. Related documents 72 18. Disposal 72 Warning Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice. 1. Symbols used in this document Warning If these safety instructions are not observed, it may result in personal injury! If these safety instructions are not observed, it Caution may result in malfunction or damage to the equipment! Note Notes or instructions that make the job easier and ensure safe operation. 2. Scope of these instructions These installation and operating instructions apply to Grundfos Hydro MPC booster systems. Hydro MPC is a range of factory-assembled booster systems, ready for installation and operation. 3. Product description As standard, Hydro MPC booster systems consist of two to six CR(E) pumps coupled in parallel and mounted on a common base frame with all the necessary fittings and a control panel. Note A diaphragm tank is required in most installations. 1 9 8 2 7 3 6 5 4 Fig. 1 Hydro MPC booster system Pos. 1 2 3 4 5 6 7 8 9 Description Control panel Nameplate Suction manifold (stainless steel) Isolating valve Base frame (stainless steel) Non-return valve Discharge manifold (stainless steel) Pressure transmitter/pressure gauge Pump Quantity 1 1 1 2 per pump 1 1 per pump 1 12 2 - 6 TM03 1171 1205 4 Q-Pulse Id: TMS196 26/11/2012 Page 9 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Hydro MPC booster systems are divided into seven groups based on control variant: Control variant Description -E -ED -ES -EF -EDF -F -S Two to six CRE pumps Two CRE pumps and up to four constant speed CR pumps One CRE pump and up to five constant speed CR pumps Two to six CR pumps connected to external variable frequency drives (VFD) Two CR pumps connected to external variable frequency drives and up to four constant speed CR pumps Up to six CR pumps connected to an external variable frequency drive. The speed-controlled operation alternates between the pumps. Two to six constant speed CR pumps See also section 6.1 Examples of control variants. Hydro MPC booster systems always includes applicationoptimised software for setting the booster system to the application in question. 4. Nameplate The nameplate of the booster system is fitted on the base frame. See position 2 in fig. 1. Pos. Description 1 Type designation 2 Model 3 Serial number 4 Supply voltage 5 Maximum operating pressure in PSI 6 Liquid temperature in °F 7 Maximum flow rate in GPM 8 Minimum head in feet 9 Number of fixed speed and/or auxiliary pumps 10 Motor power in HP for fixed speed pumps 11 Nominal voltage in volts for fixed speed pumps 12 Number of E-pumps 13 Motor power in HP for E-pumps 14 Nominal voltage in volts for E-pumps 15 Number of pilot pumps 16 Motor power in HP for pilot pump 17 Nominal voltage in volts for pilot pump 18 Order number 1924 Options 25 Enclosure type 26 Weight in lbs 27 Approval marks 28 Production location & date code 5. Software label The software label is placed on the back of the CU 351 controller. 1. Control MPC 1 2. C-MPC options 2 3. Hydro MPC 3 4. H-MPC options 4 5. Pump data 5 TM03 1741 3105 TM03 1742 3105 Fig. 2 Nameplate CONFIGURATION STEPS - PLEASE FOLLOW THE NUMBERS Fig. 3 Software label 96586126 Pos. 1 2 3 4 5 Description Control MPC - GSC file number Control MPC options - GSC file numbers Hydro MPC - GSC file number Hydro MPC options - GSC file numbers Pump data - GSC file numbers Note A GSC (Grundfos Standard Configuration) file is a configuration data file. Q-Pulse Id: TMS196 26/11/2012 5 Page 10 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 6. Type key Example Hydro MPC -ED 2 CRE 5-10 1 CR 5-10 3x460 V, 60Hz Type range Subgroups: Pumps with integrated variable frequency drive: -E, -ED, -ES Pumps with external VFD: -EF, -EDF, -F Constant speed pumps (start/stop): -S Number of pumps with integrated variable frequency drive and pump type Number of constant speed pumps and pump type Supply voltage, frequency 6.1 Examples of control variants Booster systems with motors that include an integrated variable frequency drive (CRE) Hydro MPC-E Hydro MPC booster system with three CRE pumps. Hydro MPC-ED Hydro MPC booster system with two CRE pumps and one constant speed CR pump. Hydro MPC-ES Hydro MPC booster system with one CRE pump and two constant speed CR pumps. TM03 0996 0905 TM03 0994 0905 TM03 0993 0905 PT PT PT One CRE pump in operation. H One CRE pump in operation. H One CRE pump in operation. H TM00 7995 2296 TM00 7995 2296 TM00 7995 2296 Hset Hset Hset Three CRE pumps in operation. H Q Q Q Two CRE pumps and one constant speed One CRE pump and two constant speed CR CR pump in operation. pumps in operation. H H TM00 7998 2296 TM03 0814 0505 TM00 7996 2296 Hset Hset Hset Q Q Q · The MPC-E system maintains a constant · The MPC-ED system maintains a constant · The MPC-ES system maintains a constant pressure through continuous adjustment pressure through continuous adjustment pressure through continuous adjustment of the speed of the pumps. of the speed of two CRE pumps, while the of the speed of the CRE pump. The other · The system performance is adjusted to CR pump is constant speed. pumps are cut in/out according to demand the demand through cutting in/out the · One CRE pump always starts first. If the to achieve a performance corresponding required number of pumps and through pressure cannot be maintained by the to the consumption. parallel control of the pumps in operation. pump, the second CRE pump will be cut · The CRE pump always starts first. If the · Pump changeover is automatic and in. If the two CRE pumps cannot maintain pressure cannot be maintained by the depends on load, operating hours and the pressure, the CR pump will be cut in. pump, one or both CR pumps will be cut fault. · Pump changeover is automatic and in. · All pumps in operation will run at equal depends on load, operating hours and · Changeover among the constant speed speed. fault. pumps is automatic and depends on load, operating hours and fault. 6 Q-Pulse Id: TMS196 26/11/2012 Page 11 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Booster systems with motors connected to external variable frequency drive (VFD) Hydro MPC-EF Hydro MPC booster system with three CR pumps connected to external variable frequency drives in the control panel. Hydro MPC-EDF Hydro MPC booster system with two CR pumps connected to external frequency converters in the control cabinet and one constant speed CR pump. Hydro MPC-F Hydro MPC booster system with three CR pumps connected to an external frequency converter in the control cabinet. The speed-controlled operation alternates between the pumps. TM03 1265 1505 TM03 0997 0905 TM03 0995 0905 PT PT PT One CR pump in operation. H One CR pump connected to an external variable frequency drive in operation. H One CR pump connected to an external variable frequency drive in operation. H TM00 7995 2296 TM00 7995 2296 TM00 7995 2296 Hset Three CR pumps in operation. H Hset Hset Q Q Q Two CR pumps connected to external One CR pump connected to an external variable frequency drives and one constant variable frequency drive and two constant speed CR pump in operation. speed CR pumps in operation. H H TM00 7998 2296 TM03 0814 0505 TM00 7996 2296 Hset Hset Hset Q Q Q · The MPC-EF system maintains a constant · The MPC-EDF system maintains a · The MPC-F system maintains a constant pressure through continuous adjustment constant pressure through continuous pressure through continuous adjustment of the speed of the pumps. adjustment of the speed of two CR pumps of the speed of the CR pump connected to · The system performance is adjusted to the demand through cutting in/out the required number of pumps and through connected to external variable frequency drives, while the third CR pump is constant speed. the external variable frequency drive. The speed-controlled operation alternates between the pumps. parallel control of the pumps in operation. · One CR pump connected to an external · One CR pump connected to the external · Pump changeover is automatic and depends on load, operating hours and fault. · All pumps in operation will run at equal speed. variable frequency drive always starts variable frequency drive always starts first. If the pressure cannot be maintained first. If the pressure cannot be maintained by the pump, the second CR pump by the pump, one or two constant speed connected to an external variable CR pumps will be cut in. frequency drive will be cut in. If the · Pump changeover is automatic and pressure cannot be maintained by the two depends on load, operating hours and pumps, the constant speed CR pump will fault. be cut in. · Pump changeover is automatic and depends on load, operating hours and fault. Q-Pulse Id: TMS196 26/11/2012 7 Page 12 of 382 TM03 0999 0905 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Booster system with constant speed pumps (on/off) Hydro MPC-S Hydro MPC booster system with three constant speed CR pumps. PT One constant speed CR pump in operation. H Hstop Hset Q Three constant speed CR pumps in operation. H Hstop Hset Q · Hydro MPC-S maintains a pressure differential through cutting in/out the required number of pumps. · The operating range of the pumps will lie between Hset and Hstop (cut-out pressure). · Pump changeover is automatic and depends on load, operating hours and fault. TM03 9204 3607 TM03 9203 3607 8 Q-Pulse Id: TMS196 26/11/2012 Page 13 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 7. Installation Warning Installation and operation must comply with local regulations and accepted codes of good practice. Before installation check that · the booster system corresponds to the one ordered. · no visible parts have been damaged. 7.1 Mechanical installation 7.1.1 Location The booster system must be installed in a well ventilated room to ensure sufficient cooling of the motors and control panel. Note Hydro MPC is not designed for outdoor installation unless protected and must not be exposed to direct sunlight. The booster system must have a 3 feet clearance in front and on the two sides for inspection and dismantling. 7.1.2 Pipework Arrows on the pump base show the direction of flow of water through the pump. The pipework connected to the booster system must be of adequate size. The pipes are connected to the manifolds of the booster system. Either end can be used. Apply sealing compound to the unused end of the manifold and fit the screw cap. For manifolds with flanges, fit a blanking flange with gasket. To achieve optimum operation and minimise noise and vibration, it may be necessary to consider vibration dampening of the booster system. Noise and vibration are generated by the rotations in the motor and pump and by the flow in pipework and fittings. The effect on the environment is subjective and depends on correct installation and the state of the other parts of the system. If booster system is to be installed where first customer on the line is close to the booster system, it is advisable to fit expansion joints on the suction and discharge pipes to prevent vibration being transmitted through the pipework. All nuts should be checked and re-tightened if necessary prior to start-up. The pipes must be fastened to parts of the building to ensure that they cannot move or be twisted. 7.1.3 Foundation The booster system should be positioned on an even and solid surface, for instance a concrete floor or foundation. If the booster system is not fitted with machine shoes, it must be bolted to the floor or foundation. Note As a rule the weight of a concrete foundation should be 1.5 x the weight of the booster system. 7.1.4 Vibration dampers To prevent the transmission of vibrations to buildings, it imay be necessary to isolate the booster system foundation from building parts by means of vibration dampers. The right damper varies from installation to installation, and a wrong damper may increase the vibration level. Vibration dampers should therefore be sized by the supplier of vibration dampers. If the booster system is installed on a base frame with vibration dampers, expansion joints should always be fitted on the manifolds. This is important to prevent the booster system from "hanging" in the pipework. 7.1.5 Expansion joints Expansion joints are installed to · absorb expansions/contractions in the pipework caused by changing liquid temperature · reduce mechanical strains in connection with pressure surges in the pipework · isolate mechanical structure-borne noise in the pipework (only rubber bellows expansion joints). Note Expansion joints must not be installed to compensate for inaccuracies in the pipework such as center displacement of flanges. Fit expansion joints at a distance of minimum 1 to 1 1/2 times the nominal flange diameter from the manifold on the suction as well as on the discharge side. This prevents the development of turbulence in the expansion joints, resulting in better suction conditions and a minimum pressure loss on the pressure side. At high water velocities (> 10 ft/sec) it is advisable to install larger expansion joints corresponding to the pipework. TM03 2154 3805 TM02 4981 1902 - TM02 4979 1902 1 1 2 2 Fig. 4 3 3 Sketch showing the position of expansion joints, pipe supports and machine shoes Pos. Description 1 Expansion joint 2 Pipe support and good location for system isolation valve (not shown) 3 Machine shoe Note Expansion joints, pipe supports and machine shoes shown in the figure above are not supplied with a standard booster system. Fig. 5 Examples of rubber bellows expansion joints without and with limit rods Expansion joints with limit rods can be used to minimise the forces caused by the expansion joints. Expansion joints with limit rods are always recommended for flanges larger than 6 inches. The pipework should be anchored so that it does not stress the expansion joints and the pump. Follow the supplier's instructions and pass them on to advisers or pipe installers. Q-Pulse Id: TMS196 26/11/2012 9 Page 14 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 7.2 Electrical installation Warning The electrical installation should be carried out by an authorized person in accordance with local regulations and the relevant wiring diagram. · The electrical installation of the booster system must comply with enclosure class IP54. · Make sure that the booster system is suitable for the electricity supply to which it is connected. · Make sure that the wire cross-section corresponds to the specifications in the wiring diagram. The connection of the electrical supply, transmitters and external monitoring equipment must be carried out by an authorized electrician in accordance with the NEC, local regulations and the BoosterpaQ wiring diagram. Ensure that the Hydro MPC controls and the pumps are suitable for the electricity supply on which they will be used (see Technical Data). Please read the wiring diagram carefully. According to the NEC, if the motors cannot be seen from the control panel, they must be fitted with a disconnect switch. Any BoosterpaQ that utilizes a variable frequency drive (E, ED, ES, EF, EDF, F) should be connected to an electrical supply with all phase lines electrically symmetrical with respect to ground. A "four wire wye" electrical supply with line impedance between 0.5% - 3% is recommended. If a variable frequency drive is connected to a delta transformer or if line impedance is not within the recommended 0.5% - 3%, the drive may not operate correctly and may not provide optimum performance (excessive faults, erratic behavior, or complete failure). Ask your power company or electrician to determine what type of electrical supply is present. Generator supplied power must meet public utility power quality standards. 7.3 Start-up 1. Have a qualified person check for proper power supply and plumbing connections. Make sure the main power is off. 2. Check that the air pre-charge in the diaphragm tank is 0.7 times the required discharge pressure set-point (0.9 times for MPC-S systems). System pressure must not be applied to the tank connection during the tank precharge process. If water is supplied to the tank from the system, close the tank valve and bleed off the pressure in the tank before the pressurizing process. Prime the system as follows 3. Suction pressure system (pumps are flooded at least as high as the highest part of the pumps) close all discharge manifold pump isolation valves and open all inlet manifold pump isolation valves open the vent plug on top of each pump. It is a small hex head screw in a large vent plug. Air and water will escape from the pump through a small hole in the large vent plug. When the air is out and water is flowing steadily, tighten the small hex head screw on the vent plug to stop the flow. Note If you are filling an empty piping system, do not allow the pumps to run with the discharge valves wide open as cavitation may occur. 4. Suction lift system (the water source is below the pumps or does not flood the pumps to the highest point on the pumps). close all discharge manifold pump isolation valves and open all inlet manifold pump isolation valves for suction lift applications, a foot valve must be placed on the inlet piping at the water source (tank, etc). If there is a fill point above the highest point of the pumps, you may fill the system from this point. If there is no fill point above the highest point of the pumps, remove the large vent plug on each pump. Fill each pump until the water is up to the vent plug, then replace the vent plugs. 5. Ensure all circuit breakers are in the "on" position. 6. Make sure the discharge manifold pump isolation valves are closed. Switch on main power. Caution The pumps may start at this time. 7. At this time "Start-up wizard" may now be ran. Step 8 can be skipped upon completion of "Start-up wizard". If "Start-up wizard" could not be ran or already ran proceed to step 8. 8. Run the "Start-up wizard" again by performing the following: Move top line display to "Settings". If prompted for password enter "6814", next move down to "Functions, CU 351" and press the "OK" button. Now move down to "Run wizard again" and press the "OK" button. 9. Vent the system by opening the vent plug on each pump (as in Step 3, while the pump is running starting in step 18 of the "Start-up wizard".). Venting with the pumps running ensures all air is removed from the suction piping. Do not run the system with the discharge manifold pump isolation valves closed more than five minutes to prevent over-heating of the pump liquid. 10.As pumps stop, check pump rotation. Repeat as necessary. If the area is dark, a flashlight may be required, or remove a coupling guard on each pump for better visibility. Disconnect the main power when removing coupling guards. Warning Do not touch the couplings while the pumps are turning as injury may result. Replace all coupling guards after the rotation check. Disconnect main power when removing and replacing coupling guards (or open service disconnect switches if this option was supplied). If the rotation is incorrect on any 3 phase pumps, switch any 2 of the 3 power main wires supplied to the control panel (L1, L2, L3). If that doesn't correct the rotation, call your Grundfos representative. Note If you are filling an empty piping system, do not allow the pumps to run with the discharge valves wide open as cavitation may occur. 11.Upon completion of venting pumps and checking for correct rotation you are now ready to bring the BoosterpaQ into normal operation. With the discharge manifold isolation valves still closed, partially open each pump discharge isolation valve to allow water to enter into the discharge piping of the BoosterpaQ. Continue the process of filling the discharge piping until discharge piping pressure is approximately at the desired Setpoint pressure of the BoosterpaQ. 12.Open the discharge manifold isolation valves for each pump completely. System is now ready for operation. It may be necessary to clear alarms in the fault log. Follow the steps in paragraph sections 9.6 to clear alarms. 10 Q-Pulse Id: TMS196 26/11/2012 Page 15 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual INSTALLATION AND STARTUP NOTES Q-Pulse Id: TMS196 26/11/2012 11 Page 16 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 8. Control panel 8.1 Display (pos. 1) The control panel in the front cover of the control cabinet features a display, a number of buttons and two indicator lights. The A control panel enables manual setting and monitoring of the B performance of the Hydro MPC. 2 CU 351 3 1 5 4 6 7 8 9 10 11 Fig. 6 Control panel 13 12 Key Pos. 1 2 3 4 5 6 7 8 9 10 11 12 13 Description Display Arrow to the right Help Up Down Plus Minus Esc Home Ok Indicator light, operation (green) Indicator light, fault (red) Contrast TM03 1304 1705 TM03 8947 4807 D C Fig. 7 Display design 8.1.1 Menu line The menu line (A) is illustrated in fig. 7. The display has four main menus: Status: Indication of system status Operation: Change of operating parameters such as setpoint (password option) Alarm: Alarm log for fault finding Settings: Change of settings (password option) 8.1.2 Top line The top line (B) is illustrated in fig. 7. The top line shows · the display number and title (left side) · the selected menu (left side) · the symbol in case of alarm (right side) · the symbol if the service language has been selected (right side). 8.1.3 Graphical illustration The graphical illustration (D) may show a status, an indication or other elements, depending on the position in the menu structure. The illustration may show the entire system or part of it as well as various settings. 8.1.4 Scroll bar If the list of illustration elements exceeds the display, the symbols and will appear in the scroll bar to the right. Use the and buttons to move up and down in the list. 8.1.5 Bottom line The bottom line (C) shows the date and time. 12 Q-Pulse Id: TMS196 26/11/2012 Page 17 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 8.2 Buttons and indicator lights The buttons (pos. 2 to 10 in fig. 6) on the CU 351 are active when they are illuminated. 8.2.1 Arrow to the right (pos. 2) Press the button to move to the next menu in the menu structure. If you press when the Settings menu is highlighted, you go to the Status menu. 8.2.2 Help (pos. 3) When the button is illuminated, a help text applying to the current display will appear if the button is pressed. Close the text by pressing the button. 8.2.3 Up and down (pos. 4 and 5) Press the and buttons to move up and down in lists. A text can be selected when it is in a box. If a text is marked and the button is pressed, the text above will be marked instead. If the button is pressed, the text below will be marked. If the button is pressed in the last line in the list, the first line will be marked. If the button is pressed in the first line in the list, the last line will be marked. 8.2.4 Plus and minus (pos. 6 and 7) Use the and buttons to increase and reduce values. A value is activated when the button is pressed. 8.2.5 Esc (pos. 8) Use the button to go one display back in the menu. If a value has been changed and the button is pressed, the new value will not be saved. For further information, see section 8.2.7 Ok (pos. 10). If the button is pressed before the button, the new value will be saved. For further information, see section 8.2.7 Ok (pos. 10). 8.2.6 Home (pos. 9) Press the button to return to the Status menu. 8.2.7 Ok (pos. 10) Use the button as an enter button. The button is also used to start the setting of a value. If a value has been changed and the new value will be activated. button is pressed, the 8.2.8 Indicator lights (pos. 11 and 12) The Hydro MPC control panel incorporates a green and red indicator light. The green indicator light is on when the Hydro MPC is in operation.It is flashing if the Hydro MPC has been set to stop. The red indicator light is on if there is an alarm or a warning. The fault can be identified from the alarm list. 8.2.9 Contrast (pos. 13) The contrast in the display can be changed by means of the button: 1. Press . 2. Adjust the contrast with and . 8.2.10 Back light If no button is touched for 15 minutes, the back light of the panel will be dimmed, and the first display in the Status menu will appear. Press any button to re-activate the back light. Q-Pulse Id: TMS196 26/11/2012 13 Page 18 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9. Functions 9.1 Tree of functions 1. Status 1 Status 3.1 Current alarms 3.1.1 Current alarms 1.2 System 1.2.1 Operating mode 1.2.2 Setpoint 1.2.3 Setpoint influence 1.2.4 Measured values 1.2.5 Analog inputs 1.3 Pump 1 1.4 Pump 2 1.5 Pump 3 1.6 Pump 4 1.7 Pump 5 1.8 Pump 6 2. Operation 3. Alarm 2 Operation 2.1 Further settings 2.1.1 System operating mode 2.1.2 Control mode 2.1.3 Setpoints 2.1.4 Individual pump control 2.1.4. Pump 1...6 3 Alarm status 3.1 Current alarms 3.2 Alarm log Continued on page 15 Key to the four main menus, Status, Operation, Alarm and Settings Status The Status menu shows alarms and the status of system and pumps. Note: No settings can be made in this menu. Operation In the Operation menu, the most basic parameters can be set, such as setpoint, operating mode, control mode and individual pump control. Alarm The Alarm menu gives an overview of alarms and warnings. Alarms and warnings can be reset in this menu. Settings In the Settings menu, it is possible to set various functions: · Primary controller Setting of alternative setpoints, external setpoint influence, primary sensor, clock program, proportional pressure and S-system configuration. · Pump cascade control Setting of min. time between start/stop, max. number of starts/hour, number of standby pumps, forced pump changeover, pump test run, pilot pump, pump stop attempt, pump start and stop speed, min. performance and compensation for pump start-up time. · Secondary functions Setting of stop function, soft pressure build-up, digital and analog inputs, digital outputs, emergency run, min., max. and user-defined duty, pump curve data, flow estimation, control source and fixed inlet pressure. · Monitoring functions Setting of dry-running protection, min. and max. pressure, external fault, limit 1 and 2 exceeded, pumps outside duty range and pressure relief. · Functions, CU 351 Selection of service language, main language and units. Setting of date and time, passwords, Ethernet connection, GENIbus number and software status. 14 Q-Pulse Id: TMS196 26/11/2012 Page 19 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Continued from page 16 4. Settings 4.1 Primary controller 4.1.1 PI controller 4.1.2 Alternative setpoints 4.1.3 4.1.2.1 Alternative setpoints 2...7 External setpoint influence 4.1.3.1 Set the influence function 4.1.3.2 Setting of influence function 4.1.4 4.1.6 4.1.7 4.1.8 Primary sensor Clock program Proportional pressure S-system configuration 4.2 Pump cascade control 4.2.1 Min. time between start/stop Max. number of starts/hour 4.2.3 Standby pumps 4.2.4 4.2.5 4.2.6 4.2.7 Forced pump changeover Pump test run Pilot pump Pump stop attempt 4.2.8 Pump start and stop speed 4.2.9 Min. performance 4.2.10 Compensation for pump start-up time 4.3 Secondary functions 4.3.1 Stop function 4.3.3 4.3.5 4.3.7 4.3.1.1 Stop parameters Soft pressure build-up Emergency run Digital inputs 4.3.8 Function, DI1..DI3 (CU 351), [10, 12, 14] Function, DI1..DI9 (IO 351-41), [10...46] Function, DI1..DI9 (IO 351-42), [10...46] Analog inputs Setting, analog input AI1..AI3 (CU 351), [51, 54, 57] Function, AI1...AI3 (CU 351), [51, 54, 57] Setting, AI1..AI2 (IO 351-41), [57, 60] Function, AI1..AI2 (IO 351-41), [57, 60] Setting, AI1..AI2 (IO 351-42), [57, 60] Function, AI1..A2 (IO 351-42), [57, 60] 4.3.9 Digital outputs Function, DO1 and DO2 (CU 351), [71, 74] Function, DO1...DO7 (IO 351-41), [77...88] Function, DO1...DO7 (IO 351-42), [77...88] 4.3.14 Min., max. and user-defined duty 4.3.14.1 Min. duty 4.3.14.2 Max. duty 4.3.14.3 User-defined duty 4.3.19 Pump curve data 4.3.23 Flow estimation 4.3.20 Control source 4.3.22 Fixed inlet pressure 4.3.23 Flow estimation 4.4 Monitoring functions 4.4.1 Dry-running protection 4.4.1.1 Pressure/level switch 4.4.1.2 Measurement, inlet pressure 4.4.1.3 Measurement, tank level 4.4.2 Min. pressure 4.4.3 Max. pressure 4.4.4 External fault 4.4.5 Limit 1 exceeded 4.4.6 Limit 2 exceeded 4.4.7 Pumps outside duty range 4.4.8 Pressure relief Q-Pulse Id: TMS196 26/11/2012 15 Page 20 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Continued from page 16 4. Settings 4.5 Functions, CU 351 Change language to service language (GB) Run wizard again 4.5.1 4.5.2 Display language Display units 4.5.2.1 4.5.2.2 Units for pressure Units for differential pressure 4.5.2.3 4.5.2.4 4.5.2.5 4.5.2.6 Units for head Units for level Units for flow rate Units for volume 4.5.2.7 4.5.2.8 4.5.2.9 4.5.2.10 Units for specific energy Units for temperature Units for power Units for energy 4.5.3 4.5.4 4.5.5 4.5.6 4.5.9 Date and time Password Ethernet GENIbus number Software status 16 Q-Pulse Id: TMS196 26/11/2012 Page 21 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.2 Overview Section Display and display number 9.4 Status (1) 9.4.1 Current alarms (3.1) 9.4.2 System (1.2) 9.4.3 Operating mode (1.2.1) 9.4.4 Setpoint (1.2.2) 9.4.5 Setpoint influence (1.2.3) 9.4.6 Measured values (1.2.4) 9.4.7 Analog inputs (1.2.5) 9.4.8 Pump 1...6 (1.3 to 1.8) 9.5 Operation (2) 9.5.1 Operation (2) 9.5.2 System operating mode (2.1.1) 9.5.3 Control mode (2.1.2) 9.5.4 Setpoints (2.1.3) 9.5.5 Individual pump control (2.1.4) 9.5.6 Setting of individual operating mode (2.1.4.1 to 2.1.4.6) 9.6 Alarm (3) 9.6.1 Alarm status (3) 9.6.2 Current alarms (3.1) 9.6.3 Alarm log (3.2) 9.7 Settings (4) 9.7.1 Primary controller (4.1) 9.7.2 PI controller (4.1.1) 9.7.3 Alternative setpoints (4.1.2) 9.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7) 9.7.5 External setpoint influence (4.1.3) 9.7.6 Setting of influence function (4.1.3.2) 9.7.7 Primary sensor (4.1.4) 9.7.8 Clock program (4.1.6) 9.7.9 Proportional pressure (4.1.7) 9.7.10 S-system configuration (4.1.8) 9.7.11 Pump cascade control (4.2) 9.7.12 Min. time between start/stop (4.2.1) 9.7.13 Max. number of starts/hour (4.2.1) 9.7.14 Standby pumps (4.2.3) 9.7.15 Forced pump changeover (4.2.4) 9.7.16 Pump test run (4.2.5) 9.7.17 Pilot pump (4.2.6) 9.7.18 Pump stop attempt (4.2.7) 9.7.19 Pump start and stop speed (4.2.8) 9.7.20 Min. performance (4.2.9) 9.7.21 Compensation for pump start-up time (4.2.10) 9.7.22 Secondary functions (4.3) 9.7.23 Stop function (4.3.1) 9.7.24 Soft pressure build-up (4.3.3) 9.7.25 Emergency run (4.3.5) 9.7.26 Digital inputs (4.3.7) 9.7.27 Functions of digital inputs (4.3.7.1) 9.7.28 Analog inputs (4.3.8) 9.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) 9.7.30 Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1) 9.7.31 Digital outputs (4.3.9) 9.7.32 Functions of digital outputs (4.3.9.1 to 4.3.9.16) 9.7.33 Min., max. and user-defined duty (4.3.14) 9.7.34 Min. duty (4.3.14.1) See page 19 19 19 20 20 20 21 21 21 21 22 22 23 25 25 26 27 27 32 32 32 33 33 33 34 34 35 35 36 36 37 37 38 38 38 39 39 40 40 41 41 42 42 42 44 45 45 46 46 47 47 48 48 49 49 Q-Pulse Id: TMS196 26/11/2012 17 Page 22 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Section 9.7.35 9.7.36 9.7.37 9.7.38 9.7.39 9.7.40 9.7.41 9.7.42 9.7.43 9.7.44 9.7.45 9.7.46 9.7.47 9.7.48 9.7.49 9.7.51 9.7.52 9.7.53 9.7.54 9.7.55 9.7.56 9.7.57 9.7.58 9.7.59 Display and display number Max. duty (4.3.14.2) User-defined duty (4.3.14.3) Pump curve data (4.3.19) Control source (4.3.20) Fixed inlet pressure (4.3.22) Flow estimation (4.3.23) Monitoring functions (4.4) Dry-running protection (4.4.1) Dry-running protection with pressure/level switch (4.4.1.1) Dry-running protection with pressure transmitter (4.4.1.2) Dry-running protection with level transmitter (4.4.1.3) Min. pressure (4.4.2) Max. pressure (4.4.3) External fault (4.4.4) Limit 1 and 2 exceeded (4.4.5 and 4.4.6) Pressure relief (4.4.8) Functions, CU 351 (4.5) Display language (4.5.1) Display units (4.5.2) Date and time (4.5.3) Passwords (4.5.4) Ethernet (4.5.5) GENIbus number (4.5.6) Software status (4.5.9) See page 49 50 50 51 52 52 52 53 53 54 54 55 55 56 56 57 58 58 59 60 60 60 61 61 18 Q-Pulse Id: TMS196 26/11/2012 Page 23 of 382 TM03 2293 4807 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.3 Description of functions The description of functions is based on the four main menus of the CU 351 control unit: Status, Operation, Alarm and Settings. The functions apply to all control variants unless otherwise stated. 9.4 Status (1) The first status display is shown below. This display is shown when the Hydro MPC is switched on, and it appears when the buttons of the control panel have not been touched for 15 minutes. F G H 9.4.1 Current alarms (3.1) E A Fig. 9 Current alarms Description I In this display, current unreset alarms and warnings are shown. C For further information, see sections 9.6.2 Current alarms (3.1) D B and 9.6.3 Alarm log (3.2). 9.4.2 System (1.2) TM03 8947 4807 Fig. 8 Status Description No settings can be made in this menu. The current value (process value, PV) of the control parameter, usually the discharge pressure, is shown in the upper right corner (G) together with the selected setpoint (SP) (H). The upper half of the display (A) shows a graphic illustration of the Hydro MPC booster system and part of the system. The selected measuring parameters are shown with sensor symbol and current value. In the middle of the display, an information field (I) is shown if any incidents occur. The lower display half (B) shows · the latest current alarm, if any, and the fault cause together with the fault code in brackets · system status with current operating mode and control source · pump status with current operating mode and manual/auto. Note If a fault has occurred, the symbol will be shown in the alarm line (C) together with the cause and fault code, for instance Limit 2 exceeded (191). If the fault is related to one of the pumps, the symbol will also be shown in front of the status line (D) of the pump in question. At the same time, the symbol will be flashing instead of the pump symbol (E). The symbol will be shown to the right in the top line of the display (F). As long as a fault is present, this symbol will be shown in the top line of all displays. To open a menu line, mark the line with . or , and press The display makes it possible to open status displays showing · current alarms · system status · status of each pump. Fig. 10 System Description This display shows the current operational state of the Hydro MPC booster system. It is possible to go to subdisplays showing details. The display makes it possible to open specific displays about · operating mode · setpoint · setpoint influence · measured values · analog inputs. TM03 8946 4807 Q-Pulse Id: TMS196 26/11/2012 19 Page 24 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.4.3 Operating mode (1.2.1) 9.4.4 Setpoint (1.2.2) TM03 2272 4807 TM03 2273 4807 Fig. 11 Operating mode Description Here the operating mode of the Hydro MPC booster system is shown as well as from where the Hydro MPC is controlled. Operating modes Hydro MPC has six operating modes: 1. Normal The booster system adapts its performance to the requirement. 2. Max. The pumps run at a constant high speed. Normally, all pumps run at maximum speed. 3. User-defined The pumps run at a constant speed set by the user. Usually it is a performance between Max. and Min. 4. Min. The pumps run at a constant low speed. Normally, one pump is running at a speed of 70 %. 5. Stop All pumps have been stopped. 6. Emergency run The pumps run according to the setting made in the display Emergency run (4.3.5). The performance required in the operating modes Max., Min., User-defined and Emergency run can be set in the Settings menu. See sections 9.7.33 Min., max. and user-defined duty (4.3.14) and 9.7.25 Emergency run (4.3.5). The current operating mode can be controlled from four different sources: Fault, External signal, CU 351 and Bus. Control source Hydro MPC can be set to remote control via an external bus (option). In this case, a setpoint and an operating mode must be set via the bus. In the Settings menu, it is possible to select whether the CU 351 or the external bus is to be the control source. The status of this setting is shown in the display Operating mode. Fig. 12 Setpoint Description This display shows the selected setpoint and whether it comes from the CU 351 or an external bus. The display also shows all seven possible setpoints from CU 351 (for closed- and open-loop control). At the same time, the selected setpoint is shown. As it is a status display, no settings can be made. Setpoints can be changed in the Operation menu. 9.4.5 Setpoint influence (1.2.3) Fig. 13 Setpoint influence Description The selected setpoint can be influenced by parameters. The parameters are shown as percentage from 0 to 100 % or as a pressure measured in bar. They can only reduce the setpoint, as the influence in percentage divided with 100 is multiplied with the selected setpoint: Setpointcurrent(SP) = Setpointselected × Infl.(1) × Infl.(2) × ... The display shows the parameters influencing the selected setpoint and the percentage or value of influence. Some of the possible parameters can be set in the display External setpoint influence (4.1.3). The parameter low flow boost is set as an on/off band as a percentage of the setpoint set in the display Stop function (4.3.1). The parameter is set as a percentage in the display Proportional pressure (4.1.7). Finally the resulting current setpoint (SP) is shown. TM03 8948 4807 20 Q-Pulse Id: TMS196 26/11/2012 Page 25 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.4.6 Measured values (1.2.4) 9.4.8 Pump 1...6 (1.3 to 1.8) TM03 2268 4807 TM03 2270 4807 Fig. 14 Measured values Description This display gives a general status of all measured and calculated parameters. Note The lines "Power consumption" and "Energy consumption" are only shown in Hydro MPC-E booster systems. 9.4.7 Analog inputs (1.2.5) TM03 8949 4807 Fig. 15 Analog inputs Description The display shows an overview of the analog inputs and the current measured values of each input. See sections 9.7.28 Analog inputs (4.3.8), 9.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) and 9.7.30 Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1). Fig. 16 Pump 1 Description This display shows the operational state of the individual pumps. The pumps may have different operating modes: · Auto Together with the other pumps in automatic operation, the pump is controlled by the PI controller which ensures that the booster system delivers the required performance (pressure). · Manual The pump is not controlled by the PI controller. In manual operation, the pump has one of the following operating modes: Max. The pump runs at a set maximum speed. (This operating mode can only be selected for variable-speed pumps.) Normal The pump runs at a set speed. Min. The pump runs at a set minimum speed. (This operating mode can only be selected for variable-speed pumps.) Stop The pump has been forced to stop. Besides information about the operating mode, it is possible to read various parameters in the status display, such as these: · speed (only 0 or 100 % are shown for mains-operated pumps) · power consumption (only CR(I)E pumps) · energy consumption (only CR(I)E pumps) · operating hours. 9.5 Operation (2) In this menu, the most basic parameters can be set, such as setpoint, operating mode, control mode and forced control of pumps. Q-Pulse Id: TMS196 26/11/2012 21 Page 26 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.5.1 Operation (2) Factory setting The setpoint is a value suitable for the Hydro MPC booster system in question. The factory setting may have been changed in the start-up menu. 9.5.2 System operating mode (2.1.1) A B C TM03 8950 4807 TM03 8951 4807 Fig. 17 Operation Description The column shows the setting range. In closed-loop control, it corresponds to the range of the primary sensor, here 0-16 bar. In open-loop control, the setting range is 0-100 %. At the left hand of the column, the selected setpoint 1 (A) is shown, i.e. the value set in the display. At the right hand of the column, the current setpoint (B) is shown, i.e. the setpoint acting as reference for the PI controller. If no kind of external setpoint influence has been selected, the two values will be identical. The current measured value (discharge pressure) is shown as the grey part of the column (C). See sections 9.7.5 External setpoint influence (4.1.3) and 9.7.6 Setting of influence function (4.1.3.2). Below the display is a menu line for setting of setpoint 1 and selection of operating mode, including the operating modes Normal and Stop. It is possible to select further settings: system operating mode, control mode, setpoints for closed and open loop as well as individual pump control. Setting range Setpoint: Closed-loop control: Open-loop control: Measuring range of the primary sensor 0-100 % Setting via control panel Setpoint: 1. Mark the Operation menu with . 2. Mark Setpoint 1 with or . Set the value with or . 3. Save with . Operating mode: 1. Mark the Operation menu with . 2. Mark operating mode Normal or Stop with or . Save with . Further settings: 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Select one of the settings below with : or , and press · system operating mode (see section 9.5.2) · control mode (see section 9.5.3) · setpoints (see section 9.5.4) · individual pump control (see section 9.5.6). Fig. 18 System operating mode Description Hydro MPC can be set to six different operating modes. Normal is the typical setting. See section 9.4.3 Operating mode (1.2.1). The performance of the operating modes Max., Min., Userdefined and Emergency run can be set in the Settings menu. In the display shown, it is possible to go directly to the Settings menu in order to set the pump performance or the setpoint. Setting range It is possible to select the operating modes Normal, Max., Min., User-defined, Stop and Emergency run. Setting via control panel 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Mark System operating mode with . or , and press 4. Select the desired operating mode by marking one of the lines with check boxes with or , and press . 5. In order to set the performance in min., max., user-defined duty or emergency run, mark the desired line at the bottom of the display, and press . See sections 9.7.33 Min., max. and user-defined duty (4.3.14) and 9.7.25 Emergency run (4.3.5). Factory setting Normal. 22 Q-Pulse Id: TMS196 26/11/2012 Page 27 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.5.3 Control mode (2.1.2) Open loop In open-loop control, the pumps run at a fixed speed. The pump speed is calculated from the performance set by the user (0-100 %). The pump performance in percentage is proportional with the flow rate. Open-loop control is usually used when the booster system is controlled by an external controller which controls the performance via an external signal. The external controller could for instance be a building management system connected to the Hydro MPC. In such cases, the Hydro MPC is like an actuator. See figs 22 and 23. TM03 2283 4807 TM03 2232 3905 Fig. 19 Control mode Description There are two control modes, namely closed and open loop. Examples: Closed loop The typical control mode is closed loop where the built-in PI controller ensures that the booster system delivers the discharge pressure required (setpoint). The performance is based on the setpoint set for closed loop. See figs 20 and 21. Fig. 22 Booster system with external controller (open loop) Flow rate [gpm] TM03 2391 3607 Fig. 20 Booster system controlled by built-in PI controller (closed loop) P [bar] Setpoint Time [sec] Fig. 21 Regulation curve for closed loop Setting via control panel 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Mark Control mode with or , and press . 4. Select Closed loop with or , and press . 5. Set the setpoint. See sections 9.5.4 Setpoints (2.1.3) and 9.5.1 Operation (2). TM03 2390 4105 TM03 2231 3905 0 5 Input [%] from external controller Fig. 23 Regulation curve for open loop Flow rate [gpm] 100 75 Flow rate Pump 1 50 Pump 2 Pump 3 Pump 4 25 5 50 70.7 86.6 100 Input [%] from external controller Fig. 24 Regulation curve for Hydro MPC-E in open loop TM03 9977 4807 Q-Pulse Id: TMS196 26/11/2012 23 Page 28 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Flow rate [gpm] 100 75 50 25 Flow rate Pump 1 Pump 2 Pump 3 Pump 4 5 50 70.7 86.6 100 Input [%] from external controller Fig. 25 Regulation curve for Hydro MPC-ED in open loop Flow rate [gpm] 100 75 Flow rate Pump 1 50 Pump 2 Pump 3 Pump 4 25 5 50 70.7 86.6 100 Input [%] from external controller Fig. 26 Regulation curve for Hydro MPC-ES in open loop Flow rate [gpm] 100 75 Flow rate 50 Pump 1 Pump 2 Pump 3 25 Pump 4 Input [%] from 5 50 70.7 86.6 100 external controller Fig. 27 Regulation curve for Hydro MPC-S in open loop TM03 9974 4807 TM03 9975 4807 TM03 9976 4807 Correlating open loop input setpoint percentage with number of pumps in operation. Example: MPC system with (4) pumps · Setpoint 0% to 5% = All pumps stopped One pump operation from setpoint from 5% to (1-pump/4pumps) = 50% · Two pump operation from 50% to (2-pump/4-pumps) = 70.7% · Three pump operation from 70.7% to (3-pumps/4-pumps) = 86.6% · Four pump operation from 86.6% to 100% For staging pumps off the cut-out is 2% less then cut-in. Example: staging from 4-pump to 3-pump operation will occur at 84.6% reference signal. Setting range These settings must be made in connection with open loop: · stop of the Hydro MPC booster system · selection of control mode Open loop · setting of setpoint 1, open loop · setting of external setpoint influence · selection of operating mode Normal. Setting via control panel To set an external control source to control the Hydro MPC booster system, proceed as follows: 1. Mark the Operation menu with . 2. Mark the operating mode Stop with or , and press . The check mark in the right box shows that the operation has been stopped. 3. Mark Further settings with or , and press . 4. Mark Control mode with or , and press . 5. Select Open loop with or , and press . 6. Return by pressing twice. 7. Mark Set setpoint 1, open loop with or . 8. Set the setpoint to 100 % with , and save with . 9. Mark the Settings menu with . 10.Mark Primary controller with or , and press . 11.Mark External setpoint influence with . or , and press 12.Mark Go to setting of analog input with press . or , and 13.Select the analog input with or , and press . 14.Select the range of the analog input with or , and press . The selection is indicated by a check mark. 15.Mark Measured input value with or , and press . Now the display 4.3.8.1.1 appears. 16.Select 0-100 % signal with or , and press . 17.Press to return to display 4.3.8.1. 18.Set the minimum sensor value with . or , and save with 19.Set the maximum sensor value with . or , and save with 20.Return by pressing twice. 21.Mark Input value to be influenced by with press . or , and 22.Mark 0-100 % signal with or , and press . 23.Return with . 24.Mark Set the influence function with or , and press . For details, see section 9.7.6 Setting of influence function (4.1.3.2). 25.Mark the menu line for number of points with press . or , and 24 Q-Pulse Id: TMS196 26/11/2012 Page 29 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 26.Select the required number of points with save with . or , and 27.Mark External input value (point 1) with or . 28.Set the value of the external input value with save with . or , and 29.Mark Reduce setpoint to (point 1) with or . 30.Set the value as a percentage with . or , and save with 31.Repeat 27 to 31 for all chosen points. 32.Return with . 33.Mark Filter time with or , set the time in seconds with or , and save with . 34.Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. 35.Return by pressing twice. 36.Mark the Operation menu with . 37.Mark the operating mode Normal with or , and press . The check mark in the right box shows that the operation is normal. The booster system can now be controlled by an external controller. Factory setting Closed-loop control. 9.5.4 Setpoints (2.1.3) Fig. 28 Setpoints Description In addition to the primary setpoint 1 (shown in the display 2 in the Operation menu), six alternative setpoints can be set for closedloop control. It is furthermore possible to set seven setpoints for open-loop control. As described in sections 9.7.3 Alternative setpoints (4.1.2) and 9.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7), it is possible to activate one of the alternative setpoints by means of external contacts. Setting range The setting range of setpoints for closed-loop control depends on the range of the primary sensor. See section 9.7.7 Primary sensor (4.1.4). In open loop control, the setting range is 0 - 100 %. Setting via control panel 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Mark Setpoints with or , and press . 4. Select the setpoint with or . TM03 8952 4807 TM03 8953 4807 5. Set the setpoint with or , and press . Factory setting Setpoint 1 for closed-loop control is a value suitable for the Hydro MPC in question. The alternative setpoints for closed-loop control are 3 bar. All setpoints for open-loop control are 70 %. 9.5.5 Individual pump control (2.1.4) Fig. 29 Individual pump control Description It is possible to change the operating mode from automatic operation to one of the manual operating modes. Auto The pumps are controlled by the PI controller, ensuring that the booster system delivers the required performance (pressure). Manual The pump is not controlled by the PI controller, but set to one of the following manual operating modes: · Max. The pump runs at a set maximum speed. (This operating mode can only be selected for variable-speed pumps.) · Normal The pump runs at a set speed. · Min. The pump runs at a set minimum speed. (This operating mode can only be selected for variable-speed pumps.) · Stop The pump has been forced to stop. Pumps in manual operation are not part of the normal pump cascade and speed control. The manual pumps are a "disturbance" of the normal control of Hydro MPC. If one or more pumps are in manual operation, Hydro MPC may not be able to deliver the set performance. There are two displays for the function. In the first display, the pump to be set is selected, and in the next display, the operating mode is selected. Setting range All pumps can be selected. Setting via control panel 1. Mark the Operation menu with . 2. Mark Further settings with or , and press . 3. Mark Individual pump control with or , and press . 4. Select the pump with or , and press . Q-Pulse Id: TMS196 26/11/2012 25 Page 30 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.5.6 Setting of individual operating mode (2.1.4.1 to 2.1.4.6) TM03 8954 4807 Fig. 30 Setting of individual operating mode Description This display is shown for the individual pumps and makes it possible to set an operating mode. Setting range It is possible to select Auto or Manual as well as the operating mode of the pump for manual operation - Max., Normal, Min. or Stop. For mains-operated pumps only Normal or Stop can be selected. Setting via control panel 1. Mark the Operation menu with . 2. Mark Individual pump control with or , and press . 3. Select the pump with or , and press . 4. Mark Auto or Manual with or , and press . 5. Manual: Select the operating mode with press . or , and 6. Normal: Mark Setpoint with or . Set the speed of the variable-speed pump with and press . or , Factory setting Auto. 26 Q-Pulse Id: TMS196 26/11/2012 Page 31 of 382 TM03 2291 4807 Warning( )/alarm( ) Change of operating mode to Reset of alarm Restart Set in the Settings menu Alarm code WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.6 Alarm (3) The Alarm menu gives an overview of alarms and warnings. In this menu, it is possible to reset alarms and to see the alarm log. 9.6.1 Alarm status (3) Fault Fig. 31 Alarm status Description A fault in the Hydro MPC booster system or one of the components monitored can cause an alarm or a warning . Besides the fault signal via the alarm/warning signal relay and the red indicator light on the CU 351, an alarm can also cause a change of operating mode, for instance from Normal to Stop. A warning only causes a fault indication. The table shows the possible causes of fault together with an alarm code number, and whether they result in an alarm or a warning. It also shows to what operating mode the booster system changes in case of alarm, and whether restart of the booster system and reset of the alarm is manual or automatic. The table also shows that the reaction to some of the fault causes mentioned can be set in the Settings menu. See sections 9.7.24 Soft pressure build-up (4.3.3) and 9.7.41 Monitoring functions (4.4) to 9.7.51 Pressure relief (4.4.8). Water shortage Water shortage Pressure high Pressure low Pressure relief Alarm, all pumps External fault Dissimilar sensor signals Fault, primary sensor Fault, sensor Communication fault Phase failure Undervoltage, pump Overvoltage, pump Overload, pump Overtemperature, pump Other fault, pump Internal fault, CU 351 Internal fault, IO 351 VFD not ready Fault, Ethernet Limit 1 exceeded Limit 2 exceeded Pressure build-up fault Pumps outside duty range Pilot pump fault Auto 206 Stop Man/auto X 214 Stop Auto 210 Stop Auto Man X 211 Auto X 219 Stop Auto 203 Auto X 3 Stop Man Auto 204 Stop Auto 89 Auto 88 Auto 10 Auto 2 Auto 7, 40, 42, 73 Auto 32 Auto Auto 48, 50, 51, 54 64, 65, 67 Auto 76, 83 72, Auto 83, 157 Stop Auto 83, 157 Auto 213 Auto 231, 232 Man/auto X 190 Man/auto X 191 Man/auto X 215 Man/auto X 208 Auto 216 Q-Pulse Id: TMS196 26/11/2012 27 Page 32 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Alarm (3) continued MPC alarm indication "Protocol description" 1. Phase failure, pump 2. Undervoltage Alarm code 2 7 3. Undervoltage, pump 40 4. Undervoltage, pump 42 5. Undervoltage, pump 73 6. Overvoltage, pump 32 7. Overload, associated device 48 8. Overload, associated device 50 9. Overload, associated device 51 10. Overload, associated device 54 11. Over temperature, pump 65 12. Over temperature, pump 67 Associated device and device no. Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Pump 1-6 Description/cause Remedy - 1. Check that all three power supply phases are within a 15 V window. HSD = hardware shutdown. There has been a fault, and the permissible number of restarts for the 1. Restore power supply. fault type has been exceeded. 2. Replace terminal box. a) Fault in power supply. a) Terminal box defective. a) Power supply voltage 1. Bring voltage back to is too low at start. prescribed level. a) Faulty power supply at the time of staging on a pump. 1. Restore proper power supply. a) Low supply voltage. b) Power supply failure 1. Restore proper power while motor is supply. running. a) Supply voltage is too 1. Bring voltage back to high at start. prescribed level. a) Heavy overload has caused software shutdown (SSD). 1. Check and possibly reduce load. a) MPF = motor protection function. The built-in motor 1. Check and possibly protection has reduce load/improve detected a sustained cooling. overload (MPF 60 sec. limit)> a) Heavy overload (Imax. very high). Pump blocked at start. 1. Unblock the pump. a) The built-in motor protection has 1. Check and possibly detected a transitory reduce load/improve overload (MPF 3 sec. cooling limit). a) PTC sensor in the motor has signalled over temperature. 1. Check and possibly reduce load/improve cooling. a) Terminal box has indicated over temperature. 1. Check and possibly reduce load/improve cooling. (Temperature during operation can be read via PC Tool Eproducts.) Reset Alarm/warning type1 Action type2 Auto Warning Auto Warning Auto Auto Warning Warning Auto Warning Auto Auto Warning Warning Auto Warning Auto Warning Auto Warning Auto Warning Auto Warning 28 Q-Pulse Id: TMS196 26/11/2012 Page 33 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MPC alarm indication "Protocol description" 13. Other fault, associated device 14. Limit 1 exceeded 15. Limit 2 exceeded 16. Pressure relief 17. Pressure build-up fault 18. Pumps outside duty range 19. Pilot pump fault Alarm code 76 190 191 219 215 208 216 Associated device and device no. Pump 1-6 Measured parameter Measured parameter System System System Pilot pump Description/cause Remedy Reset Alarm/warning type1 Action type2 Try to reset the fault: 1. Switch off the supply power. a) Internal communication error has occurred in the pump. 2. Wait until all diodes are out. 3. Switch on the supply power. If this does not remedy the fault, replace the terminal box. a) The measured parameter has exceeded the limit set. 1. Remove the cause of the fault. a) The measured parameter has exceeded the limit set. 1. Remove the cause of the fault. a) The monitored pressure could not be reduced sufficiently. 1. Reduce the pressure to below the limit. a) The pressure set cannot be reached within the configured 1. Check limit and pipes. time. a) The pump is running outside the defined 1. Check the system. range. a) Pilot pump fault 1. Check wires. 2. Check the pump. Auto Auto/ manual Auto/ manual Auto Auto/ manual Auto/ manual Auto Warning Alarm/warning Stop/ unchanged Alarm/warning Stop/ unchanged Warning Unchanged Alarm/warning Stop/ unchanged Warning Unchanged Warning Q-Pulse Id: TMS196 26/11/2012 29 Page 34 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MPC alarm indication "Protocol description" Alarm code Associated device and device no. Description/cause Remedy Reset Alarm/warning type1 Action type2 20. Water shortage, level 1 *Water shortage, level 1 206 a) The pre-pressure (or the level in the feed tank) is below its programmable warning limit. Auto Warning Unchanged 21. Water shortage, level 2 *Water shortage, level 2 214 a) The pre-pressure (or the level in the feed tank) is below its 1. Check the actual and the programmable corresponding settings. Auto/ warning limit. 2. Check the sensor/switch, Manual b) The pre-pressure wiring and input switch detect water according to the wiring shortage. diagram. Alarm Stop Warning Unchanged 22. Discharge pressure high *Pressure above max. 210 pressure 23. Discharge pressure low *Pressure below min. 211 pressure System a) The system pressure 3. Check the sensor/switch. Alarm is above the Auto/ Fast stop (over programmable highpressure alarm limit. Manual rule min. seq. time) a) The system pressure is below the programmable lowpressure alarm limit. Auto/ Manual Alarm/Warning Stop/ Unchanged 24. All pumps in alarm *All pumps in alarm 203 a) All pumps, set to Auto, is stopped on account of pump alarm Troubleshoot according to the alarm message/code: 1. System 2. Pumps installed Use fault fault finding for the pump. Auto Alarm Stop b) Pumps are not indicating alarm Check the Genibus wires eg. connection, polarisation. 25. External fault signal *External fault signal 003 a) External fault digital input activated. 1. Check the external signal source. 2. Check the digital input according to the wiring diagram Auto/ Manual Alarm/Warning Stop/ Unchanged 26. Inconsistency between sensors *Inconsistency between sensors a) Primary feedback 1. Check the wiring and Primary sensor value input according to the 204 sensor and/or redundant (pressure) is inconsistent with wiring diagram. 2. Check the sensor output sensor redundant feedback according to the sensor value. measured value. Auto Warning Unchanged 27. Primary sensor *Closed loop feedback sensor signal fault 089 Primary sensor a) A fault in the sensor assigned to the feed back control is detected. 1. Check the wiring and input according to the wiring diagram. 2. Check the sensor output according to the measured value. Alarm Stop b) Error in the settings Check the primary sensor of the sensor which is settings assigned to the regulator. Auto 28. Sensor fault *General (measurement) sensor signal fault 088 CU 351 IO 351 as IO module a) The signal 1. Check the wiring and (ex. 4-20 mA) from input according to the one of the analog wiring diagram. sensors is outside the 2. Check the sensor output selected signal according to the range. measured value Warning Unchanged 30 Q-Pulse Id: TMS196 26/11/2012 Page 35 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MPC alarm indication "Protocol description" Alarm code 29. CU 351 internal fault *Real time clock out of 157 order 30. Ethernet fault *Ethernet: No address 231 from DHCP server 31. Ethernet fault *Ethernet: Auto disabled 232 due to misuse 32. FLASH parameter verification error *FLASH parameter 083 verification error 33. IO 351 internal fault *Hardware fault type 2 080 34. VFD not ready *VFD not ready 213 35. Communication fault *Pump communication fault 010 36. Device alarms From device Associated device and device no. CU 351 IO 351 Pump 1-6 CU 351 Pump 1-6 IO 351 Pump 1-6 Description/cause Remedy a) The real-time clock in Replace the CU 351 CU 351 is out of order. a) No address from DHCP server 1. Communication error. 2. Please contact the a) Auto-disabled due to misuse system integrator. a) Verification error in CU 351 FLASH memory Replace the CU 351 a) IO 351 pump module See current alarms and hardware fault identify the faulty IO 351 b) IO 351 I/O module hardware fault module from the alarm message and replace the module. 1. Check for VFD alarm a) The VFD signal relay do not release the 2. Check the wiring and VFD for operation input according to the wiring diagram. See actual alarms and identify the faulty device from the alarm message. a) No GeniBus 1. Check power supply communication with a device connected to CU 351 2. Check GeniBus cable connection 3. Check, with R100, that the device GeniBus no. is correct. See actual alarms and identify the faulty device a) The device is in alarm from the alarm message. 1. Fault find according to the service instruction for the device. Reset type1 Auto Alarm/warning Action type2 Warning Unchanged 1) Reset type is either fixed as "Auto acknowledge" (Auto) or can be programmed to be Auto or manual ackknowledge (Auto/Man)*. 2) Programmable action types: - Go to operating mode "Stop" (no delay (<0.5 s) between pump disconnections). - Go to operating mode "Min". - Go to operating mode "User-defined". - Go to operating mode "Max". - Set pumps in source mode "Local". - No action (warning only) Q-Pulse Id: TMS196 26/11/2012 31 Page 36 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.6.2 Current alarms (3.1) Description Here warnings and alarms are shown. For every warning or alarm, the following is shown: · Whether it is a warning or an alarm . · Where the fault occurred. System, Pump 1, Pump 2, etc. · In case of input-related faults, the input is shown. · What the cause of the fault is, and the alarm code in brackets: Water shortage (214), Max. pressure (210), etc. · When the fault occurred: Date and time. · When the fault disappeared: Date and time. If the fault still exists, date and time are shown as --...--. The latest warning/alarm is shown at the top of the display. 9.7 Settings (4) TM03 2293 4807 TM03 2294 4807 Fig. 32 Current alarms Description This submenu shows the following: · Warnings caused by faults that still exist. · Warnings caused by faults that have disappeared, but the warning requires manual reset. · Alarms caused by faults that still exist. · Alarms caused by faults that have disappeared, but the alarm requires manual reset. All warnings and alarms with automatic reset are automatically removed from the menu when the fault has disappeared. Alarms requiring manual reset are reset in this display by pressing . An alarm cannot be reset until the fault has disappeared. For every warning or alarm, the following is shown: · Whether it is a warning or an alarm . · Where the fault occurred: System, Pump 1, Pump 2, etc. · In case of input-related faults, the input is shown. · What the cause of the fault is, and the alarm code in brackets: Water shortage (214), Max. pressure (210), etc. · When the fault occurred: Date and time. · When the fault disappeared: Date and time. If the fault still exists, date and time are shown as --...--. The latest warning/alarm is shown at the top of the display. 9.6.3 Alarm log (3.2) The alarm log can store up to 24 warnings and alarms. Fig. 33 Alarm log TM03 2292 4807 Fig. 34 Settings In the Settings menu, it is possible to set the following functions: · Primary controller Setting of PI controller, alternative setpoints, external setpoint influence, primary sensor, clock program, proportional pressure and S-system configuration. · Pump cascade control Setting of min. time between start/stop, max. number of starts/ hour, number of standby pumps, forced pump changeover, pump test run, pilot pump, pump stop attempt, pump start and stop speed, min. performance and compensation for pump start-up time. · Secondary functions Setting of stop function, soft pressure build-up, digital and analog inputs, digital outputs, emergency run, min., max. and user-defined duty, pump curve data, flow estimation, control source and fixed inlet pressure. · Monitoring functions Setting of dry-running protection, min. and max. pressure, external fault, limit 1 and 2 exceeded, pumps outside duty range and pressure relief. · Functions, CU 351 Selection of service language, main language and units. Setting of time and date, passwords, Ethernet connection, GENIbus number and software status. Usually, all these functions are set correctly when the Hydro MPC is switched on. It is only necessary to make settings in this menu if the functionality is to be expanded with for instance alternative setpoints or setpoint influence, or if the settings of the CU 351 are to be adjusted. 32 Q-Pulse Id: TMS196 26/11/2012 Page 37 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.1 Primary controller (4.1) Fig. 35 Primary controller Description In this menu section, it is possible to set the functions related to the primary controller. It is only necessary to make settings in this menu if the functionality is to be expanded with for instance alternative setpoints, external setpoint influence, clock program or proportional pressure. The following menus can be selected: · PI controller · Alternative setpoints · External setpoint influence · Primary sensor · Clock program · Proportional pressure · S-system configuration. 9.7.2 PI controller (4.1.1) TM03 8955 4807 Setting range · Gain Kp: 30 to 30. Note: For inverse control, set Kp to a negative value. · Integral time Ti: 0.1 to 3600 seconds. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark PI controller with or , and press . 4. Select the gain (Kp) with or . Set the value with or , and save with . Note: Usually it is not necessary to adjust Kp. 5. Select the integral time (Ti) with or , and press . or . Set the time with Factory setting · Kp: 0.5 · Ti: 1 second 9.7.3 Alternative setpoints (4.1.2) TM03 2383 4807 Fig. 37 Alternative setpoints Description This function makes it possible to select up to six setpoints (No 2 to 7) as alternatives to the primary setpoint (No 1). The primary setpoint (No 1) is set in the Operation menu. Every alternative setpoint can be addressed manually to a separate digital input (DI). When the contact of the input is closed, the alternative setpoint applies. If more than one alternative setpoint has been selected and they are activated at the same time, the CU 351 selects the setpoint with the lowest number. Setting range · Six setpoints, No 2 to 7. TM03 2387 4807 Fig. 36 PI controller Description Hydro MPC includes a standard PI controller which ensures that the pressure is stable and corresponds to the setpoint. It is possible to adjust the PI controller if a faster or slower reaction to changes of consumption is required. A faster reaction is obtained if Kp is increased and Ti is reduced. A slower reaction is obtained if Kp is reduced and Ti is increased. Q-Pulse Id: TMS196 26/11/2012 33 Page 38 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Factory setting No alternative setpoints have been selected. 9.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7) TM03 2384 4807 Fig. 38 Alternative setpoints 2 to 7 For each alternative setpoint, select the digital input to activate the setpoint. It is possible to set a setpoint for closed loop and for open loop. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark Alternative setpoints with or , and press . 4. Select the alternative setpoint with . or , and press 5. Mark Go to setting of digital input with or , and press . Now the display Digital inputs (4.3.7) appears. Set the input and return with . 6. Mark the menu line of the setpoint (closed or open loop) with or . 7. Set the required setpoint with or , and save with . Set both setpoints if Hydro MPC is to be controlled both in open and closed loop. Factory setting No alternative setpoints have been set. 9.7.5 External setpoint influence (4.1.3) TM03 8956 4807 Fig. 39 External setpoint influence Description This function makes it possible to adapt the setpoint by letting measuring parameters influence the setpoint. Typically an analog signal from a flow or temperature transmitter, or a similar transmitter. As an example, the setpoint can be adapted to parameters that can influence the discharge pressure or temperature of the system. The parameters which influence the performance of the booster system are shown as a percentage from 0 to 100 %. They can only reduce the setpoint, as the influence as a percentage divided with 100 is multiplied with the setpoint: Setpointcurrent(SP) = Setpointselected × Infl.(1) × Infl.(2) × ... The influence values can be set individually. A low-pass filter ensures smoothing of the measured value which influences the setpoint. This results in stable setpoint changes. Setting range The following parameters can be selected. · 0-100 % signal · Inlet pressure · Discharge pressure · External pressure · Differential pressure, pump · Differential pressure, external · Flow rate · Tank level, discharge side · Tank level, suction side · Flow pipe temperature · Return pipe temperature · Ambient temperature · Return pipe temperature, external · Differential temperature. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark External setpoint influence with . or , and press 4. Mark Input value to be influenced by with press . Now a list of available parameters appear. or , and 5. Mark the parameter which is to influence the setpoint with or , and press . 6. Return with . 7. Mark Set the influence function with or , and press . For details, see section 9.7.6 Setting of influence function (4.1.3.2). 8. Mark the menu line for number of points with press . or , and 9. Select the required number of points with save with . or , and 10.Mark External input value (point 1) with or . 11.Set the value of the external input value with save with . or , and 12.Mark Reduce setpoint to (point 1) with or . 13.Set the value as a percentage with . or , and save with 14.Repeat points 8 to 13 for all desired parameters. 15.Return with . 16.Mark Filter time with or , set the time in seconds with or , and save with . 34 Q-Pulse Id: TMS196 26/11/2012 Page 39 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 17.Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. Factory setting Setpoint influence is not activated. 9.7.6 Setting of influence function (4.1.3.2) 5. Mark the menu line for number of points with press . or , and 6. Select the required number of points with save with . or , and 7. Mark External input value (point 1) with or . 8. Set the value of the external input value with save with . or , and 9. Mark Reduce setpoint to (point 1) with or . 10.Set the value as a percentage with or , and save with . 11.Repeat points 7 to 10 for all desired parameters. Factory setting External setpoint influence is not activated. 9.7.7 Primary sensor (4.1.4) TM03 2389 4807 Fig. 40 Setting of influence function Description In this menu, you select the relation between the measuring parameter which is to influence the setpoint and the desired influence as a percentage. The relation is set by entering values in a table with maximum eight points by means of the control panel. Example with four points: Setpoint influence [%] TM03 1691 4807 4 100 80 60 3 2 40 20 1 Q [m³/h] 50 Fig. 41 Relation between setpoint influence and flow rate The control unit of the Hydro MPC draws straight lines between the points. A horizontal line is drawn from the minimum value of the relevant sensor (0 m3/h in the example) to the first point. This is also the case from the last point to the sensor's maximum value (example 50 m3/h). Setting range Two to eight points can be selected. Each point contains the relation between the value of the parameter which is to influence the setpoint and the influence of the value. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or 3. Mark External setpoint influence with . 4. Mark Set the influence function with . , and press . or , and press or , and press Fig. 42 Primary sensor Description In this display, select the control parameter of Hydro MPC and the sensor to measure the value. Usually, the control parameter is the discharge pressure which is measured by a sensor fitted on the discharge manifold and connected to analog input AI1 of the CU 351. If another control parameter is selected, the sensor must be connected to AI3 (CU 351) which is then set to one of the chosen parameters listed below. Setting range · Discharge pressure (factory setting) · Differential pressure, external · Differential pressure, pump · Series 2000, differential pressure · External pressure · Differential pressure, inlet · Differential pressure, outlet · Flow rate · Series 2000, flow rate · Flow pipe temperature · Return pipe temperature · Differential temperature · Ambient temperature · Return pipe temperature, external · 0-100 % signal · Not used. TM03 8958 4807 Q-Pulse Id: TMS196 26/11/2012 35 Page 40 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual From factory the discharge pressure sensor is connected to AI1 (CU 351). If one of the above parameters is selected, the sensor in question must be connected to AI3 (CU 351) and set in order to function as the primary sensor. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark Primary sensor with or , and press . 4. Mark Go to setting of analog input with or , and press . Now the display Analog inputs (4.3.8) appears. Select the analog input (AI) for the primary sensor, and set the parameters for this sensor. Return to display Primary sensor (4.1.4) with . 5. Select the control parameter for the primary sensor with or , and press . Note If the primary parameter is discharge pressure, AI1 (CU 351) must be set to this parameter. If the primary parameter is external pressure or flow rate, AI3 (CU 351) must be set to this parameter. Factory setting The primary parameter is discharge pressure. The sensor is connected to AI1 (CU 351). 9.7.8 Clock program (4.1.6) 5. Mark operating mode Normal or Stop with or , and press . (If Stop is selected, point 7 is skipped.) 6. Mark Setpoint, closed loop with or pressure with or , and save with . Set the . 7. Mark Time (hours, minutes) with or . 8. Set the time with or , and save with . 9. Mark day of week on which the settings are to be activated with or , and press . 10.Mark Activated with or , and press . 11.Return with . 12.Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. 13.Repeat points 4 to 11 if several events are to be activated. Note: Up to ten events can be set. Factory setting The function is deactivated. 9.7.9 Proportional pressure (4.1.7) TM03 8959 4807 TM03 8990 4807 Fig. 43 Clock program Description With this function, it is possible to set setpoints and day and time for their activation. It is also possible to set day and time for stop of the Hydro MPC system. If the clock program is deactivated, the setpoint of the program will remain active. Setting range · Activation of the function. · Activation and setting of event. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark Clock program with or , and press . 4. Mark event 1 with or , and press . Fig. 44 Proportional pressure Description The function can only be activated in pressure-controlled systems and automatically adapts the setpoint set to the current flow rate. The adaptation can be linear or square. See fig. 45. TM03 8960 4807 36 Q-Pulse Id: TMS196 26/11/2012 Page 41 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Hset Pump curve Setpoint Resultant setpoint, linear Resultant setpoint, square Starting point of proportional pressure control (Influence at 0 flow = x % of Hset) Fig. 45 Proportional pressure The function has these purposes: · to compensate for pressure losses · to reduce the energy consumption · to increase the comfort for the user. Setting range · Activation of the function. · Selection of control mode. · Setting of setpoint influence. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark Proportional pressure with or , and press . 4. Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. 5. Mark Adaptation, linear or square with press . or , and 6. Mark Influence at 0 flow with or or , and save with . . Set the value with Factory setting The function is deactivated. 9.7.10 S-system configuration (4.1.8) TM03 8524 1807 TM03 9205 3607 - TM03 9205 3607 Description The function makes it possible to invert the control of mainsoperated pumps (Hydro MPC-S). That is to set whether pumps are to be started or stopped depending on the current value. A start/stop band must be set in order to use this function. See fig. 47. Normal control: A pump is stopped when the current value becomes higher than Hset + start/stop band. And a pump is started when the current value becomes lower than Hset. See fig. 47. Inverse control: A pump is started when the current value becomes higher than Hset + start/stop band. And a pump is stopped when the current value becomes lower than Hset. See fig. 47. Normal control H [m] Inverse control H [m] Pump stops Pump starts Start/stop band Hset Pump starts Start/stop band Hset Pump stops Time [sec] Time [sec] Fig. 47 Normal and inverse control Setting range · Selection of configuration (normal or inverse control). · Setting of start/stop band. Setting via control panel 1. Mark the Settings menu with . 2. Mark Primary controller with or , and press . 3. Mark S-system configuration with . or , and press 4. Mark Inverse with or , and press . 5. Mark Start/stop band with or . Set the value with or , and save with . Factory setting Normal. 9.7.11 Pump cascade control (4.2) TM03 8961 4807 TM03 8962 4807 Fig. 46 S-system configuration Q-Pulse Id: TMS196 Fig. 48 Pump cascade control 26/11/2012 37 Page 42 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual In this menu section, it is possible to set the functions connected to pump cascade control. The following menus can be selected: · Min. time between start/stop · Max. number of starts/hour · Standby pumps · Forced pump changeover · Pump test run · Pilot pump · Pump stop attempt · Pump start and stop speed · Min. performance · Compensation for pump start-up time. 9.7.12 Min. time between start/stop (4.2.1) 9.7.13 Max. number of starts/hour (4.2.1) TM03 2367 4807 TM03 2367 4807 Fig. 49 Min. time between start/stop Description This function ensures a delay between the starting/stopping of one pump and the starting/stopping of another pump. The purpose is to prevent hunting when pumps start and stop continuously. Setting range From 1 to 3600 seconds. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with or . 3. Mark Min. time between start/stop with press . 4. Mark Min. time between start/stop with press . 5. Set the required minimum time with or . , and press or , and or , and , and save with Factory setting Minimum time between start/stop of pumps: Hydro MPC-E and -EF: 1 second Other variants: 5 seconds Fig. 50 Max. number of starts/hour Description This function limits the number of pump starts and stops per hour for the complete system. It reduces noise emission and improves the comfort of booster systems with mains-operated pumps. Each time a pump starts or stops, the CU 351 calculates when the next pump is allowed to start/stop in order not to exceed the permissible number of starts per hour. The function always allows pumps to be started to meet the requirement, but pump stops will be delayed, if needed, in order not to exceed the permissible number of starts per hour. The time between pump starts must be between the minimum time between start/stop, see section 9.7.12, and 3600/n, n being the set number of starts per hour. Setting range 1 to 1000 starts per hour. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Max. number of starts/hour with . or , and press 4. Mark Max. number of starts/hour with or , and press . 5. Set the permissible number of starts per hour with and save with . or , Factory setting Hydro MPC-E and -EF: 200 starts per hour Other variants: 100 starts per hour Note This function has no influence on Stop function (4.3.1). 9.7.14 Standby pumps (4.2.3) 38 Q-Pulse Id: TMS196 26/11/2012 Page 43 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fig. 51 Standby pumps Description This function makes it possible to limit the maximum performance of the Hydro MPC, by selecting one or more pumps as standby pumps. If a three-pump system has one standby pump, maximum two pumps are allowed to be in operation at a time. If one of the two pumps in operation has a fault and is stopped, the standby pump will be started. The performance of the booster system is thus not reduced. The status as standby pump alternates between all pumps. Setting range The number of possible standby pumps in a Hydro MPC booster system is equal to the total number of pumps in the system minus 1. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Standby pumps with or , and press . 4. Select the number of standby pumps with save with . or , and Factory setting The number of standby pumps is set to 0, i.e. function is deactivated. 9.7.15 Forced pump changeover (4.2.4) TM03 2366 4807 Description This function ensures that the pumps run for the same number of operating hours. In certain applications, the requirement remains constant for long periods and does not require all pumps to run. In such situations, pump changeover does not take place naturally, and forced pump changeover may thus be required. Once every 24 hours, the CU 351 checks if any pump running has a larger number of operating hours than pumps that are stopped. If this is the case, the pump will be stopped and replaced by a pump with a lower number of operating hours. Setting range The function can be activated/deactivated. The hour of the day at which the changeover is to take place can be set. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Forced pump changeover with . or , and press 4. Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. 5. Mark Time for changeover with , and press . 6. Set the time with or , and save with . Factory setting The function is activated. The time is set to 03:00. 9.7.16 Pump test run (4.2.5) TM03 2365 4807 TM03 2364 4807 Fig. 52 Forced pump changeover Fig. 53 Pump test run Description This function is primarily used in situations where the forced pump changeover is deactivated, and/or if the Hydro MPC is set to operating mode Stop, for instance in a period when the system is not needed. In such situations, it is important to test the pumps regularly. The function ensures that · pumps do not seize up during a long standstill due to deposits from the pumped liquid. · the pumped liquid does not decay in the pump. · trapped air is removed from the pump. The pumps start automatically one by one and run for five seconds. Q-Pulse Id: TMS196 26/11/2012 39 Page 44 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Note Pumps in the operating mode Manual are not included in the test run. If there is an alarm, the test run will not be carried out. Setting range · Not used. · Once every 24 hours. · Once every 48 hours. · Once a week. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . 3. Mark Pump test run with or 4. Select the interval with or . 5. Activate the function with . or , and press , and press . Factory setting Test runs are set to once every 24 hours. 9.7.17 Pilot pump (4.2.6) Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Pilot pump with or , and press . 4. Mark Go to setting of digital output with press . or , and 5. Select a digital output with or , and press . 6. Mark Pilot pump control with . or , and save with 7. Return by pressing twice. 8. Mark Go to setting of digital input with press . or , and 9. Select a digital input or , and press . 10.Mark Pilot pump fault with or , and save with . Factory setting The function is deactivated. 9.7.18 Pump stop attempt (4.2.7) TM03 8963 4807 TM03 8964 4807 Fig. 54 Pilot pump Description The function controls a pilot pump via a digital output. The pilot pump takes over the operation from the main pumps in periods when the consumption is so small that the stop function of the main pumps is activated. See section 9.7.23 Stop function (4.3.1). Via a digital input, the operational state of the pilot pump is monitored, i.e. whether it is operational or in a fault condition. The purpose is to · save energy · reduce the number of operating hours of the main pumps. If the pilot pump cannot keep the pressure by itself, one or more main pumps are started. If only one main pump is started and runs on/off operation, the pilot pump remains cut in. If one or more main pumps run continuously, the pilot pump is cut out. Note If the setpoint of the main pumps is changed, the setpoint of the pilot pump must be changed too. Setting range · See section 9.7.31 Digital outputs (4.3.9). · See section 9.7.26 Digital inputs (4.3.7). Fig. 55 Pump stop attempt Description The function makes it possible to set automatic stop attempts of a pump when several pumps are running. It ensures that the optimum number of pumps is always running, in terms of energy consumption. At the same time, the purpose is to avoid disturbances in connection with automatic stop of pumps. Stop attempts can either take place with a fixed interval set under Interval between stop attempts or by self learning. If self learning is selected, the interval between stop attempts will be increased if repeated attempts to stop the pump fail. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Pump stop attempt with or , and press . 4. Mark Self learning or Fixed interval with or , and press . 5. If Fixed interval is selected: 6. Mark Interval between stop attempts with or . 7. Set the interval with or , and save with . 8. Mark Activated with or , and press . The check mark in the right box shows that the function has been activated. Factory setting The function is activated. 40 Q-Pulse Id: TMS196 26/11/2012 Page 45 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.19 Pump start and stop speed (4.2.8) Description The function controls the starting and stopping of pumps. There are two options: 1. Use calculated speed This function ensures that the optimum number of pumps is always running at a desired duty point, in terms of energy consumption. The CU 351 calculates the required number of pumps and their speed. This requires that the differential pressure of the pump is measured by a differential pressure sensor or separate pressure sensors on the inlet and discharge side. When calculated speed has been selected, the CU 351 ignores the percentages set. 2. Use fixed speed The pumps are started and stopped at speeds set by the user. 1. Use calculated speed Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Pump start and stop speed with . or , and press 4. Mark Use fixed speed with or , and press . 5. Mark Start of next pump at: 1->2 with or , and press . 6. Set the speed as percentage with or , and save with . Set the other pumps in the same way. 7. Mark Instant pump stop at: 1->0 with . or , and press 8. Set the speed as percentage with or , and save with . Set the other pumps in the same way. Factory setting The function is set to calculated speed. 9.7.20 Min. performance (4.2.9) TM03 8966 4807 TM03 8967 4807 Fig. 56 Calculated pump start and stop speed Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with or . 3. Mark Pump start and stop speed with . 4. Mark Use calculated speed with or , and press or , and press , and press . 2. Use fixed speed Fig. 58 Min. performance Description This function ensures circulation in a system. Note that the stop function, if activated, can influence this function. See section 9.7.23 Stop function (4.3.1). Examples: · If 0 or 1 pump has been selected as a minimum, the stop function can stop the pump if there is no or a very small consumption. · If two or more pumps have been selected as a minimum, the stop function is not active. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with . or , and press 3. Mark Min. performance with or , and press . 4. Set Number of pumps with or , and save with . 5. Mark Speed with or and save with . . Set the speed with or , Factory setting The number of pumps is set to 1. The speed in closed loop is set to 25 %. TM03 8965 4807 Fig. 57 Fixed pump start and stop speed Q-Pulse Id: TMS196 26/11/2012 41 Page 46 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.21 Compensation for pump start-up time (4.2.10) The display makes it possible to open specific displays regarding: · Stop function (4.3.1) · Soft pressure build-up (4.3.3) · Digital inputs (4.3.7) · Analog inputs (4.3.8) · Digital outputs (4.3.9) · Emergency run (4.3.5) · Min., max. and user-defined duty (4.3.14) · Pump curve data (4.3.19) · Flow estimation (4.3.23) · Control source (4.3.20) · Fixed inlet pressure (4.3.22). 9.7.23 Stop function (4.3.1) TM03 8968 4807 Fig. 59 Compensation for pump start-up time Description The function is used for the system types -ES, -ED, -F and -EDF. The purpose is to avoid disturbances when a mains-operated pump with fixed speed is started. The function compensates for the time it takes a mains-operated pump to reach its full performance after start. The start-up time of the mains-operated pump must be known. Setting via control panel 1. Mark the Settings menu with . 2. Mark Pump cascade control with or , and press . 3. Mark Compensation for pump start-up time with or , and press . 4. Set the start-up time with or , and save with . Factory setting The start-up time is set to 0 seconds. 9.7.22 Secondary functions (4.3) Fig. 61 Stop function Description This function makes it possible to stop the last pump if there is no or a very small consumption. The purpose is to · save energy · prevent heating of shaft seal faces due to increased mechanical friction as a result of reduced cooling by the pumped liquid · prevent heating of the pumped liquid. The description of the stop function applies to all Hydro MPC booster systems with variable-speed pumps. Hydro MPC-S will have on/off control of all pumps as described in section 6.1 Examples of control variants. H TM03 2355 4807 TM03 8969 4807 TM03 1692 2705 Hset On/off band Fig. 60 Secondary functions Description Qmin Q Functions that are secondary in relation to the normal operation of the Hydro MPC booster system can be set in this display. On/off Normal operation control Secondary functions are functions that offer additional functionality. Fig. 62 On/off band 42 Q-Pulse Id: TMS196 26/11/2012 Page 47 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual When the stop function is activated, the operation of Hydro MPC is continuously monitored to detect a low flow rate. When the CU 351 detects no or a low flow rate (Q < Qmin), it changes from constant-pressure operation to on/off control of the last pump in operation. Before stopping, the pump increases the pressure to a value corresponding to Hset + 0.5 x on/off band. The pump is restarted when the pressure is Hset 0.5 x on/off band. See fig. 63. [psi] Stop A B A: Normal operation B: Pressure boosting C: Stop C B C Start Stop = Hset + 0.5 x on/off band Start = Hset 0.5 x on/off band Time [sec] Fig. 63 On/off operation The flow rate is estimated by the CU 351 when the pump is in the stop period. As long as the flow rate is lower than Qmin, the pump will run on/off. If the flow rate is increased to above Qmin, the pump returns to normal operation, Hset. Hset is equal to the current setpoint. See section 9.4.4 Setpoint (1.2.2). Detection of low flow rate Low flow rate can be detected by means of · direct flow measurement with a flowmeter or flow switch · estimation of flow rate by measurement of current pressure and speed. If the booster system is not connected to a flowmeter or flow switch, the stop function will use the estimating function. If the detection of low flow rate is based on flow estimation, a diaphragm tank of a certain size and with a certain precharge pressure is required. Diaphragm tank size Pump type CR(E) 3 CR(E) 5 CR(E) 10 CR(E) 15 CR(E) 20 CR(E) 32 CR(E) 45 CR(E) 64 CR 90 Recommended diaphragm tank size [gallons] -E 4.4 4.4 10.2 34 34 44 86 132 - -ED 4.4 4.4 10.2 34 34 44 86 132 - -ES 4.4 4.4 10.2 34 34 44 86 132 - -EF 4.4 4.4 10.2 34 34 44 86 132 132 -EDF 4.4 4.4 10.2 34 34 44 86 132 132 -F 4.4 4.4 10.2 34 34 44 86 132 132 -S 20 34 62 211 211 317 528 1056 1056 Precharge pressure Hydro MPC-E, -ED, -ES, -EF, -EDF and -F: 0.7 x setpoint. Hydro MPC-S: 0.9 x setpoint. TM03 9292 4807 TM03 9966 4807 During each flow estimation (every 2 minutes), the estimating function will disturb the discharge pressure by ±10 % of the setpoint. If this disturbance is not acceptable, the stop function must be based on direct flow measurement with a flowmeter or flow switch. The minimum flow rate can be set, i.e. the flow rate at which the booster system changes to on/off control of the last pump in operation. If both a flowmeter and a flow switch are connected, the changeover to on/off control is determined by the unit first indicating low flow rate. Setting range On/off band: Min. flow rate: 5 to 30 % 2 to 50 % of the nominal flow rate (Qnom) of one of the pumps. (Can only be set if direct flow measurement by means of flowmeter has been selected.) Setting via control panel System without flow switch or flowmeter 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Stop function with or , and press . 4. Mark Activated with or , and press . The activation is indicated by a check mark in the box. 5. Mark On/off band with or . 6. Set the on/off band with or , and save with . 7. Mark Go to setting of flow stop parameters with and press . Now the display below is shown. or , Fig. 64 Stop parameters 8. Select one of the stop parameters with or , and save with . If Customised settings are selected, the parameters shown in fig. 65 must be set. See examples below. Q-Pulse Id: TMS196 26/11/2012 43 Page 48 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 1. Mark Go to setting of analog input with or , and press . Now the display Analog inputs (4.3.8) appears. 2. Select the analog input where the flowmeter is connected, and set up the input for the flowmeter by selecting Flow rate. 3. Return to Stop function by pressing twice. 4. Mark Stop limit with or . 5. Set the value with or , and save with . Factory setting The function is activated. On/off band: 25 % Min. flow rate: 30 % of the nominal flow rate of one pump 9.7.24 Soft pressure build-up (4.3.3) TM03 8957 4807 TM03 8970 4807 Fig. 65 Customised settings Note Rule of thumb: Speed reduction = 2 x delta pressure for gradient. Example 1: Increasing the stop limit, Qmin (high flow limit) · Increase the delta pressure for gradient. · Reduce the delta time for gradient (pump stopped). · Reduce the delta time for gradient (pump running). · Increase the speed reduction. Example of increased stop limit Parameter Delta pressure for gradient Delta time for gradient (pump stopped) Delta time for gradient (pump running) Speed reduction Value 6 % 1.5 sec 2.0 sec 10 % Example 2: Reducing the stop limit, Qmin (low flow limit) · Reduce the delta pressure for gradient. · Increase the delta time for gradient (pump stopped). · Increase the delta time for gradient (pump running). · Reduce the speed reduction. Example of reduced flow limit Parameter Delta pressure for gradient Delta time for gradient (pump stopped) Delta time for gradient (pump running) Speed reduction Value 3 % 15.0 sec 25.0 sec 6 % Note The stop limit depends on the tank size. System with flow switch Make the following additional settings: 1. Mark Go to setting of digital input with or , and press . Now the display Digital inputs (4.3.7) appears. 2. Select the digital input where the flow switch is connected with or , and press . 3. Mark Flow switch with or , press and return with . Note An open contact indicates low flow. System with flowmeter Make the following additional settings: Fig. 66 Soft pressure build-up Description The function ensures a smooth start-up of systems with for instance empty pipes. Start-up takes place in two phases. See fig. 67. 1. Filling phase. The pipework is slowly filled with water. When the pressure sensor of the system detects that the pipework has been filled, phase two begins. 2. Pressure build-up phase. The system pressure is increased until the setpoint is reached. The pressure build-up takes place over a ramp time. If the setpoint is not reached within a given time, a warning or an alarm can be given, and the pumps can be stopped at the same time. H [psi] 1. Filling phase 2. Pressure build-up phase Filling time Time [sec] Ramp time Fig. 67 Filling and pressure build-up phases 44 Q-Pulse Id: TMS196 26/11/2012 Page 49 of 382 TM03 9037 3207 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Setting range · Activation of the function. · Setting of pump speed. · Setting of number of pumps. · Setting of filling pressure. · Setting of maximum filling time. · Setting of warning or alarm + stop. · Setting of ramp time for the pressure build-up phase. Setting via control panel 1. Mark the Settings menu with 2. Mark Secondary functions with or , and press . 3. Mark Soft pressure build-up with . or , and press 4. Mark Speed with or . 5. Set the value with or , and save with . 6. Mark Number of pumps with or . 7. Set the value with or , and save with . 8. Mark Filling pressure with or . 9. Set the value with or , and save with . 10.Mark Max. time with or . 11.Set the value with or , and save with . 12.Mark Warning or Alarm + stop with . or , and press 13.Mark Ramp time with or . 14.Set the value with or , and save with . 15.Mark Activated, and press . Factory setting The function is deactivated. 9.7.25 Emergency run (4.3.5) 2. Mark Secondary functions with or , and press . 3. Mark Emergency run with or , and press . 4. Mark Go to setting of digital input with press . or , and 5. Select a digital input with or , and press . 6. Mark Emergency run with or , and save with . 7. Return by pressing twice. 8. Mark Go to setting of digital output with press . or , and 9. Select a digital output with or , and press . 10.Mark Emergency run with or , and save with . 11.Return by pressing twice. 12.Mark Setpoint, emergency run with or . 13.Set the value with or , and save with . Note When this function has been set as described above, it can also be activated via the display System operating mode (2.1.1). 9.7.26 Digital inputs (4.3.7) TM03 8971 4807 TM03 2359 4807 Fig. 68 Emergency run Description When this function has been activated, the pumps will keep running regardless of warnings or alarms. The pumps will run according to a setpoint set specifically for this function. In case of sensor fault, both main and standby Caution pumps will run at 100 % speed! Setting range · Setting of digital input (9.7.26 Digital inputs (4.3.7)). · Setting of digital output (9.7.31 Digital outputs (4.3.9)). · Setting of setpoint for emergency run. Setting via control panel 1. Mark the Settings menu with Fig. 69 Digital inputs Description In this menu, the digital inputs of the CU 351 can be set. Each input, except DI1, can be activated and related to a certain function. As standard, the Hydro MPC has three digital inputs. If the Hydro MPC incorporates an IO 351B module (option), the number of digital inputs is 12. In the display, all digital inputs are shown so that their physical position in the Hydro MPC can be identified. Example DI1 (IO 351-41), [10]: DI1: (IO 351-41): [10]: Digital input No 1 IO 351, GENIbus number 41 Terminal No 10 For further information on the connection of various digital inputs, see the wiring diagram supplied with the control cabinet. Setting range The digital input to be set is selected in the display Digital inputs (4.3.7). Note DI1 (CU 351) cannot be selected. Setting via control panel 1. Mark the Settings menu with . Q-Pulse Id: TMS196 26/11/2012 45 Page 50 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 2. Mark Secondary functions with or , and press . 3. Mark Digital inputs or , and press . 4. Select the digital input with or , and press . 9.7.27 Functions of digital inputs (4.3.7.1) Fig. 70 Functions of digital inputs Description In the displays 4.3.7.1, a function can be related to the digital inputs. Setting range It is possible to select one function in each display: Function Contact activated Not used Min. duty = Operating mode Min. Max. duty User-defined duty External fault = Operating mode Max. = Operating mode Userdefined = External fault Dry-running protection Flow switch Reset of alarm Emergency run Pilot pump fault = Water shortage = Flow rate > Set switch value = Reset alarms = Operating mode Emergency run = Pilot pump fault Alternative setpoint 2 = Setpoint 2 selected Alternative setpoint 3 = Setpoint 3 selected Alternative setpoint 4 = Setpoint 4 selected Alternative setpoint 5 = Setpoint 5 selected Alternative setpoint 6 = Setpoint 6 selected Alternative setpoint 7 = Setpoint 7 selected See the relevant sections for further information about the functions. Generally, a closed contact activates the function selected. TM03 8972 4807 TM03 2356 4807 Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Digital inputs with or , and press . 4. Select the digital input with or , and press . 5. Select the desired function with or , and activate it with . The activation is indicated by a check mark in the box. Factory setting Digital input Function DI1 (CU 351) [10] DI2 (CU 351) [12] External start/stop. Open contact = stop. Note: Input No 1 cannot be changed. Monitoring of water shortage (dry-running protection). Open contact = water shortage (if the Hydro MPC is supplied with this option). Note Monitoring of water shortage requires a pressure switch connected to the Hydro MPC. 9.7.28 Analog inputs (4.3.8) Fig. 71 Analog inputs Description In this display, the analog inputs of the Hydro MPC can be set. Each input can be activated and related to a certain function. As standard, the Hydro MPC has three analog inputs. If the Hydro MPC incorporates an IO 351B module (option), the number of analog inputs is 5. In the display, all analog inputs are shown so that their physical position in the Hydro MPC can be identified. A redundant primary sensor can be fitted as back-up for the primary sensor in order to increase reliability and prevent stop of operation. Note If two sensors are to be redundant, each must have a separate analog input. Example AI1 (CU 351) [51]: AI1: (CU 351): [51]: Analog input No 1 CU 351 Terminal No 51 46 Q-Pulse Id: TMS196 26/11/2012 Page 51 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Setting range In the display Analog inputs (4.3.8), the analog input to be set is selected. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Analog inputs with or , and press . 4. Select the analog input with or , and press . 9.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) Factory setting Analog input Function AI1 (CU 351) [51] AI2 (CU 351) [54] AI3 (CU 351) [57] Discharge pressure Tank precharge pressure (if Hydro MPC is supplied with measurement of tank precharge pressure) Redundant primary sensor (if Hydro MPC is supplied with this option) 9.7.30 Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1) TM03 2357 4807 TM03 8973 4807 Fig. 72 Analog inputs Description In the displays 4.3.8.1 to 4.3.8.7, analog inputs can be set. Each display is divided into three parts: · Setting of input signal, for instance 4-20 mA · Measured input value, for instance discharge pressure · Measuring range of the sensor/signal transmitter, for instance 0-16 bar. Setting range It is possible to set the following parameters in each display: · Not used · Range of input signal, 0-20 mA, 4-20 mA, 0-10 V · Measured input value · Sensor range. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Analog inputs with or , and press . 4. Select the analog input with or , and press . 5. Mark the setting of the analog input with or , and activate it with . The activation is indicated by a check mark in the box. Note If an analog input is deactivated, the display will only show the top part, i.e. the setting of the analog input. If the input is activated, the middle part, "Measured input value", is shown. This makes it possible to relate a function to the analog input in another display. When the analog input has been related to a function, CU 351 will return to the display for setting of analog inputs. Fig. 73 Analog inputs and measured value Description In the display Analog inputs and measured value (4.3.8.1.1 to 4.3.8.7.1), a function can be related to the individual analog inputs. Setting range It is possible to select one function per analog input. · Not used · 0-100 % signal · Inlet pressure · Discharge pressure · External pressure · Differential pressure, pump · Flow rate · Tank level, discharge side · Tank level, suction side · System pressure · Differential pressure, external · Tank precharge pressure · Differential pressure, inlet · Differential pressure, outlet · Return pipe temperature, external · Flow pipe temperature · Return pipe temperature · Differential temperature · Ambient temperature · Power, pump 1 to 6 · Power, VFD. Q-Pulse Id: TMS196 26/11/2012 47 Page 52 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Analog inputs with or , and press . 4. Select the analog input with or , and press . 5. Set the range of the analog input with or . The activation is indicated by a check mark. , and press 6. Mark Measured input value with or , and press . Now the display 4.3.8.1.1 appears. 7. Select the input with or , and press . 8. Press to return to display 4.3.8.1. 9. Set the minimum sensor value with . or , and save with 10.Set the maximum sensor value with . or , and save with 9.7.31 Digital outputs (4.3.9) Fig. 74 Digital outputs Description In this display, the digital relay outputs of the Hydro MPC can be set. Each output can be activated and related to a certain function. As standard, the Hydro MPC has two digital outputs. If the Hydro MPC incorporates an IO 351B module (option), the number of digital outputs is 9. In the display, all digital outputs are shown so that their physical position in the Hydro MPC can be identified. Example DO1 (IO 351-41) [71]: DO1 (IO 351-41) [71] Digital output No 1 IO 351B, GENIbus number 41 Terminal No 71 For further information on the connection of various digital outputs, see the wiring diagram supplied with the CU 351. Setting range In the display Digital outputs (4.3.9), the digital output to be used is selected. TM03 2333 4807 TM03 8974 4807 9.7.32 Functions of digital outputs (4.3.9.1 to 4.3.9.16) Fig. 75 Functions of digital outputs Description In the displays Functions of digital outputs (4.3.9.1 to 4.3.9.16), a function can be related to the individual outputs. Setting range It is possible to select one function in each display: · No function · Operation, system · Alarm, system · Warning, system · Ready, system · Water shortage · Min. pressure · Max. pressure · Emergency run · Pilot pump control · Pressure relief valve · Operation, pump 1 to 6 · Alarm, pump 1 to 6 · Alarm, limit 1 exceeded · Warning, limit 1 exceeded · Alarm, limit 2 exceeded · Warning, limit 2 exceeded. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Digital outputs with or , and press . 4. Select the digital output with or , and press . 5. Mark the desired function with or , and activate it with . The activation is indicated by a check mark in the box. Factory setting Digital output DO1 (CU 351) [71] DO2 (CU 351) [74] Function Alarm, system Operation, system 48 Q-Pulse Id: TMS196 26/11/2012 Page 53 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.33 Min., max. and user-defined duty (4.3.14) TM03 2351 4807 Fig. 76 Min., max. and user-defined duty Description Hydro MPC is usually controlled in a closed loop to maintain a discharge pressure. In certain periods, it may be necessary to let the booster system run in open loop at a set pump performance. Setting range The CU 351 makes it possible to change between three operating modes: 1. Min. duty (4.3.14.1). 2. Max. duty (4.3.14.2). 3. User-defined duty (4.3.14.3). Note For each of these modes, the number of operating pumps and the pump performance (speed) can be set. 9.7.34 Min. duty (4.3.14.1) TM03 2354 4807 Fig. 77 Min. duty Description In all booster systems apart from Hydro MPC-S, minimum duty is only possible for variable-speed pumps. In Hydro MPC-S systems, only the number of pumps running at 100 % speed can be set. Setting range · Number of pumps in operation. · Speed as percentage (25 to 100 %) for variable-speed pumps. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Min., max. and user-defined duty with press . or , and 4. Mark Min. duty with or , and press . 5. Mark Number of pumps in operation, min. duty with or . 6. Set the number with or , and save with . 7. Mark Speed with or . 8. Set the value with or , and save with . Factory setting Number of pumps in operation during min. duty: 1 Speed as percentage for variable-speed pumps: 70 9.7.35 Max. duty (4.3.14.2) TM03 2353 4807 Fig. 78 Max. duty Description The function makes it possible for a set number of pumps to run at maximum performance when the function is activated. Setting range In this display, the number of pumps to run in the operating mode Max. can be set. All pumps run at 100 % speed. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Min., max. and user-defined duty with press . or , and 4. Mark Max. duty with or , and press . 5. Mark Number of pumps in operation at 100 % speed, max. duty with or . 6. Set the number with or , and save with . Factory setting Number of pumps in operation during max. duty: All pumps (except standby pumps) Q-Pulse Id: TMS196 26/11/2012 49 Page 54 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.36 User-defined duty (4.3.14.3) 9.7.37 Pump curve data (4.3.19) TM03 2352 4807 TM03 8975 4807 Fig. 79 User-defined duty Description In this display, it is possible to set a user-defined performance, typically a performance between min. and max. duty. The function makes it possible to set a pump performance by selecting the number of pumps to run and the speed of variablespeed pumps. This function primarily selects the variable-speed pumps. If the number of selected pumps exceeds the number of variable-speed pumps, mains-operated pumps are started too. Setting range · Number of pumps in operation. · Speed as percentage for variable-speed pumps. Note: In Hydro MPC booster systems with only variable-speed pumps, the speed can be set between 25 and 100 %; in booster systems with both variable-speed pumps and mainsoperated pumps the speed can be set between 70 and 100 %. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Min., max. and user-defined duty with press . or , and 4. Mark User-defined duty with or , and press . 5. Mark Number of pumps in operation, user-defined duty with or . 6. Set the number with or , and save with . 7. Mark Speed with or . 8. Set the value with or , and save with . Factory setting The function is not activated, as the following has been set: Number of pumps in operation during user-defined duty: 0 Fig. 80 Pump curve data Description The CU 351 has a number of functions using these pump data: · Nominal flow rate, Qnom, in m3/h · Nominal head, Hnom, in metres · Max. head, Hmax, in metres · Max. flow rate, Qmax, in m3/h · Power, Q0, 100 % speed, in kW · Power, Q0, 50 % speed, in kW · Nominal power, Pnom, in kW. Note Grundfos can supply hydraulic data for CR, CRI, CRE and CRIE pumps where GSC files can be downloaded directly to the CU 351. Note The electrical data, "Power, Q0, 100 % speed" and "Power, Q0, 50 % speed" must be entered manually. For Grundfos E-pumps, the data of input power (P1) must be entered. The data are read by means of the pump performance curves which can be found in WebCAPS on Grundfos' homepage, www.grundfos.com. See examples in figs 81 to 84. If WebCAPS is not accessible, try to bring a pump into the three duty points: Power, Q0, 100 % speed, Power, Q0, 50 % speed and Nominal power, Pnom. Read the power values in displays 1.3 to 1.8, depending on the pump. See section 9.4.8 Pump 1...6 (1.3 to 1.8). Hmax Hnom Nominal duty point TM03 9993 4807 50 Q-Pulse Id: TMS196 Qnom Qmax Fig. 81 Reading of Qnom, Hnom, Hmax and Qmax (WebCAPS) 26/11/2012 Page 55 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Duty point, Q0, 100 % speed Power, Q0, 100 % speed Fig. 82 Reading of Power, Q0, 100 % speed (WebCAPS) TM03 9994 4807 Note Qnom and Hnom are the rated duty point of the pumps and usually the duty point with the highest efficiency. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Pump curve data with or , and press . 4. Mark Nominal flow rate Qnom with or . 5. Set the value with or , and save with . 6. Mark Nominal head Hnom with or . 7. Set the value with or , and save with . 8. Mark Max. head Hmax with or . 9. Set the value with or , and save with . 10.Mark Max. flow rate Qmax with or . 11.Set the value with or , and save with . 12.Mark Power, Q0, 100 % speed with or . 13.Set the value with or , and save with . 14.Mark Power, Q0, 50 % speed with or . 15.Set the value with or , and save with . 16.Mark Nominal power Pnom with or . 17.Set the value with or , and save with . 9.7.38 Control source (4.3.20) Duty point, Q0, 50 % speed TM03 9995 4807 Power, Q0, 50 % speed TM03 2342 4807 Fig. 83 Reading of Power, Q0, 50 % speed (WebCAPS) Duty point, Nominal power, Pnom Nominal power, Pnom Fig. 84 Reading of Nominal power, Pnom (WebCAPS) TM03 9996 4807 Fig. 85 Control source Description Hydro MPC can be remote-controlled via an external bus connection (option). See section 9.8.2 GENIbus. Control of the Hydro MPC can also take place via the bus connection. For further information, see section 9.8 Data communication. In this display, the control source, CU 351 or the external bus connection, is selected. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Control source with or , and press . 4. Select the desired control source with with . or , and save Factory setting The control source is CU 351. Q-Pulse Id: TMS196 26/11/2012 51 Page 56 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.39 Fixed inlet pressure (4.3.22) TM03 8975 4807 Fig. 86 Fixed inlet pressure Description If the Hydro MPC has a fixed inlet pressure, it can be entered in this display so that the CU 351 can optimise the performance and control of the booster system. Setting range A fixed inlet pressure can be set, and the function can be activated/deactivated. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Fixed inlet pressure with or , and press . 4. Set the inlet pressure with or , and save with . 5. Mark Activated with or , and press . The activation is indicated by a check mark in the box. Factory setting The function is deactivated. 9.7.40 Flow estimation (4.3.23) The loss is caused by non-return valves and pipe bends. To improve the flow estimation of the system, it is necessary to compensate for the difference between the measured and the actual differential pressure across the pump. This is done by entering the head loss in non-return valves and pipe bends at the rated flow rate of one pump. Setting range · 2nd order QH polynomial · 5th order QH polynomial · Power polynomial, QP · Head loss. Note It is possible to select several curve types, as the CU 351 makes a priority based on the data available. Setting via control panel 1. Mark the Settings menu with . 2. Mark Secondary functions with or , and press . 3. Mark Flow estimation with or , and press . 4. Select the curve type by marking one of the lines at the selection box with or , and press . Factory setting All polynomials are selected. 9.7.41 Monitoring functions (4.4) TM03 8978 4807 Fig. 87 Flow estimation Description As described in section 9.7.37 Pump curve data (4.3.19), the CU 351 can optimise operation according to performance curves and motor data. In this display, curve types are selected which the CU 351 will use for the optimisation if they are available. At large flow rates, there may be a considerable head loss between the pump discharge flange and the pressure sensor. TM03 8977 4807 Fig. 88 Monitoring functions Description Hydro MPC has a series of functions that constantly monitor the operation of the booster system. The primary purpose of the monitoring functions is to ensure that faults do not damage pumps or the system. Setting range The following functions can be selected: · Dry-running protection (4.4.1) · Min. pressure (4.4.2) · Max. pressure (4.4.3) · External fault (4.4.4) · Limit 1 and 2 exceeded (4.4.5 and 4.4.6) · Pumps outside duty range (4.4.7) · Pressure relief (4.4.8). Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Select the function with or , and press . 52 Q-Pulse Id: TMS196 26/11/2012 Page 57 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.42 Dry-running protection (4.4.1) 9.7.43 Dry-running protection with pressure/level switch (4.4.1.1) TM03 2320 4807 TM03 2329 4807 Fig. 89 Dry-running protection Description Dry-running protection is one of the most important monitoring functions, as bearings and shaft seal may be damaged if the pumps run dry. Grundfos thus always recommends dry-running protection in connection with Hydro MPC booster systems. The function is based on monitoring of the inlet pressure or the level in a possible tank or pit on the suction side. Level switches, pressure switches or analog sensors signalling water shortage at a set level can be used. There are three different methods for detection of water shortage: · Pressure switch on suction manifold or float switch/electrode relay in the supply tank. See section 9.7.43 Dry-running protection with pressure/level switch (4.4.1.1). · Measurement of inlet pressure in the suction manifold by means of an analog pressure transmitter. See section 9.7.44 Dry-running protection with pressure transmitter (4.4.1.2). · Measurement of level in the supply tank by means of an analog level transmitter. See section 9.7.45 Dry-running protection with level transmitter (4.4.1.3). Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Dry-running protection with . or , and press 4. Select the method with or , and press . Fig. 90 Dry-running protection with pressure/level switch Description Dry-running protection can take place by means of a pressure switch on the suction manifold or a level switch in a tank on the suction side. When the contact is open, the CU 351 will register water shortage after a time delay of approx. 5 sec. It is possible to set whether the indication is to be just a warning or an alarm stopping the pumps. In the display, it is possible to set whether restart and reset of the alarm is to be automatic or manual. Setting range · Selection of digital input for the function. · Reaction in case of water shortage: Warning or alarm + stop. · Restart: Manual or automatic. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Dry-running protection with . or , and press 4. Mark Pressure/level switch with or , and press . 5. Mark Go to setting of digital input, and press . Now the display Digital inputs (4.3.7) appears. Set the input to dryrunning protection. Return with . 6. Mark Warning or Alarm + stop with with . or , and save 7. Mark Manual or Auto with or , and save with . Factory setting If the booster system is equipped with a pressure switch for dryrunning protection, it is set to alarm + stop in case of water shortage. Restart: Manual. Q-Pulse Id: TMS196 26/11/2012 53 Page 58 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.44 Dry-running protection with pressure transmitter (4.4.1.2) 9.7.45 Dry-running protection with level transmitter (4.4.1.3) TM03 8979 4807 TM03 8980 4807 Fig. 91 Dry-running protection with pressure transmitter Description Dry-running protection can take place by means of a pressure transmitter measuring the inlet pressure. It is possible to set two levels of inlet pressure: Warning and alarm + stop. In the display, it is possible to set whether restart and reset of the alarm is to be automatic or manual. Setting range · Selection of analog input for the function. · Activation of the function. · Inlet pressure level for warning. · Inlet pressure level for alarm + stop. · Restart: Manual or automatic. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Dry-running protection with . or , and press 4. Mark Measurement, inlet pressure with press . or , and 5. Mark Go to setting of analog input, and press . Now the display Analog inputs (4.3.8) appears. Set the input to Inlet pressure, and save with . Return with . 6. Mark Activated with or , and press . 7. Mark Warning with or . Set the level with and save with . or , 8. Mark Alarm + stop with or . Set the level with or , and save with . 9. Mark Manual or Auto with or , and save with . Note If one of the levels is not required, the level value must be the minimum value of the inlet pressure transmitter. This deactivates the function. Factory setting If the booster system is supplied with a pressure transmitter on the suction side, the transmitter has been set. The warning level is 0.5 bar and the alarm level 0.2 bar. The function is activated. Restart: Manual. Fig. 92 Dry-running protection with level transmitter Description Dry-running protection can take place by means of a level transmitter measuring the level in a tank on the suction side. It is possible to set two levels: Warning and alarm + stop. In the display, it is possible to set whether restart and reset of alarms is to be automatic or manual. Setting range · Selection of analog input for the function. · Activation of the function. · Tank level for warning. · Tank level for alarm + stop. · Restart: Manual or automatic. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Dry-running protection with . or , and press 4. Mark Measurement, tank level with . or , and press 5. Mark Go to setting of analog input, and press . Now the display Analog inputs (4.3.8) appears. Set the input to Tank level, suction side. Return with . 6. Mark Activated with or , and press . 7. Mark Warning with or . Set the level with and save with . or , 8. Mark Alarm + stop with or . Set the level with or , and save with . 9. Mark Manual or Auto with or , and save with . Factory setting The function is deactivated. 54 Q-Pulse Id: TMS196 26/11/2012 Page 59 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.46 Min. pressure (4.4.2) Factory setting The function is deactivated. 9.7.47 Max. pressure (4.4.3) TM03 8981 4807 TM03 8982 4807 Fig. 93 Min. pressure Description The discharge pressure can be monitored so that the CU 351 can react if the pressure becomes lower than a set minimum level for an adjustable time. The minimum pressure can be monitored if a fault indication is required in situations where the discharge pressure becomes lower than the set minimum pressure. It is possible to set whether the indication is to be just a warning or an alarm stopping the pumps. This may be desirable if Hydro MPC is used for an irrigation system where a very low discharge pressure may be due to pipe fracture and thus an extraordinarily high consumption and a very low counterpressure. In such situations, it is desirable that the booster system stops and indicates alarm. This situation will require a manual reset of alarms. It is possible to set a start-up delay ensuring that the Hydro MPC can build up pressure before the function is activated. It is also possible to set a time delay, i.e. for how long time the discharge pressure may be lower than the set minimum pressure before the alarm is activated. Setting range · Activation of the function. · Minimum pressure level within the range of the primary sensor. · Activation of stop when the pressure falls below the minimum pressure. · Time delay at start-up. · Time delay during operation. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Min. pressure with or , and press . 4. Mark Activated with or deactivate the function. , and press to activate/ 5. Mark Min. pressure with or or , and save with . . Set the pressure with 6. Mark Stop at min. pressure with or to activate/deactivate the function. , and press 7. Mark Time delay of function at start-up with the time with or , and save with . or . Set 8. Mark Time delay of function during operation with or . Set the time with or , and save with . Fig. 94 Max. pressure Description The discharge pressure can be monitored so that the CU 351 can react if the pressure becomes higher than a set maximum level. In certain installations, a too high discharge pressure may cause damage. It may therefore be necessary to stop all pumps for a short period if the pressure is too high. It is possible to set whether the Hydro MPC is to restart automatically after the pressure has dropped below the maximum level, or if the system must be reset manually. Restart will be delayed by an adjustable time. See section 9.7.12 Min. time between start/stop (4.2.1). Setting range · Activation of the function. · Maximum pressure level within the range of the primary sensor. · Manual or automatic restart after fault. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark Max. pressure with or , and press . 4. Mark Activated with or deactivate the function. , and press to activate/ 5. Mark Max. pressure with or or , and save with . . Set the pressure with 6. Mark Manual or Auto with or . Activate the function with . Factory setting The function is deactivated. Q-Pulse Id: TMS196 26/11/2012 55 Page 60 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.48 External fault (4.4.4) 9.7.49 Limit 1 and 2 exceeded (4.4.5 and 4.4.6) TM03 2313 4807 TM03 8983 4807 Fig. 95 External fault Description The function is used when the CU 351 is to be able to receive a fault signal from an external contact. In case of external fault, the CU 351 indicates warning or alarm. In case of alarm, the booster system changes to another manual operating mode, for instance Stop. Setting range · Selection of digital input for the function. · Setting of time delay from closing of the contact until the CU 351 reacts. · Reaction in case of external fault: Warning or alarm and change of operating mode. · Restart after alarm: Manual or automatic. Setting via control panel 1. Mark the Settings menu with . 2. Mark Monitoring functions with or , and press . 3. Mark External fault with or , and press . 4. Mark Go to setting of digital input with or , and press . Now the display Digital inputs (4.3.7) appears. Set the input to External fault. Return with . 5. Mark Time delay, fault indication with or time with or , and save with . . Set the 6. Mark Warning with or if only a warning is required in case of external fault. Activate the function with . 7. Select operating mode with or if the booster system is to give alarm and change operating mode in case of external fault. Activate the function with . 8. Mark Manual or Auto with with . or . Activate the function Factory setting The function is deactivated. If the function is activated, the following values have been set from factory: · Time delay: 5 seconds. · Operating mode in case of alarm: Stop. · Restart: Manual. Fig. 96 Limit 1 exceeded Description With this function, the CU 351 can monitor set limits of analog values. It will react if the values exceed the limits. Each limit can be set as a maximum or minimum value. For each of the monitored values, a warning limit and an alarm limit must be defined. The function makes it possible to monitor two different locations in a pump system at the same time. For instance the pressure at a consumer and the pump discharge pressure. This ensures that the discharge pressure does not reach a critical value. If the value exceeds the warning limit, a warning is given. If the value exceeds the alarm limit, the pumps are stopped. A delay can be set between the detection of an exceeded limit and the activation of a warning or an alarm. A delay can also be set for resetting a warning or an alarm. A warning can be reset automatically or manually. It is possible to set whether the system is to restart automatically after an alarm, or if the alarm must be reset manually. Restart can be delayed by an adjustable time. It is also possible to set a startup delay ensuring that the system reaches a steady state before the function becomes active. Setting range · Activation of an analog input for the function. · Selection of the measured value to be monitored. · Setting of limit type (min./max.). · Setting of warning limit. · Setting of alarm limit. Setting via control panel Note Analog inputs must be correctly set before the function is activated. See section 9.7.28 Analog inputs (4.3.8). 1. Mark the Settings menu with 2. Mark Monitoring functions with or , and press 3. Mark Limit 1 exceeded or Limit 2 exceeded with and press . or , 4. Mark Go to setting of analog input with press . or , and 5. Select the analog input with or , and press . 6. Mark the setting of the analog input with or , and activate it with . The activation is indicated by a check mark in the box. 56 Q-Pulse Id: TMS196 26/11/2012 Page 61 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 7. Mark Measured value with or the display 4.3.8.1.1 appears. , and press . Now 8. Select the input with or , and press . 9. Press to return to display 4.3.8.1. 10.Set the minimum sensor value with . or , and save with 11.Set the maximum sensor value with . or , and save with 12.Return by pressing twice. 13.Mark Measured value to be monitored with or ., and press . Select the input with or , and press . 14.Return with . 15.Mark Min. limit or Max. limit with . or ., and press 16.Mark Set delays with or , and press 17.Mark Time delay of function at start-up with the time with or , and save with . or . Set 18.Mark Time delay of function during operation with or . Set the time with or , and save with . 19.Mark Time delay of function at reset with or the time with or , and save with . . Set 20.Return with . 21.Mark Set warning limit with or , and press . 22.Mark Activated with or , and press . 23.Mark Warning limit with or or , and save with . . Set the value with 24.Mark Manual or Auto with with . or . Activate the function 25.Return with . 26.Mark Set alarm limit with or , and press . 27.Mark Activated with or , and press . 28.Mark Alarm limit with or . Set the value with or , and save with . 29.Mark Manual or Auto with with . or . Activate the function 30.Return with . 31.Mark Activated with the function. or , and press to activate Factory setting The function is deactivated. 9.7.50 Pumps outside duty range (4.4.7) Description The function gives a warning if the duty point of the pumps moves outside the defined range. For instance, if the inlet pressure becomes lower than a minimum permissible value, thus causing a risk of cavitation for some pump types. The warning is given with a set time delay. It is possible to set whether the warning is to be reset automatically or manually when the duty point comes within the defined duty range. It is also possible to set a relay output to be activated when the warning is given, and to be deactivated when the warning is reset. This function requires that the discharge pressure and the inlet pressure (either measured or configured) or the differential pressure of the pumps is monitored, and that CU 351 contains valid pump data from either a GSC file or from manual input. See section 9.7.37 Pump curve data (4.3.19). Setting range · Activation of the function. · Setting of manual or automatic reset. · Setting of warning delay. Setting via control panel 1. Mark the Settings menu with 2. Mark Monitoring functions with or , and press . 3. Mark Pumps outside duty range with . or , and press 4. Mark Manual or Auto with function with . or , and activate the 5. Mark Warning delay with or . Set the time with or , and save with . 6. Mark Activated with the function. or , and press to activate Factory setting The function is deactivated. 9.7.51 Pressure relief (4.4.8) TM03 8984 4807 TM03 8986 4807 Fig. 97 Pumps outside duty range Q-Pulse Id: TMS196 Fig. 98 Pressure relief 26/11/2012 57 Page 62 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Description The purpose of the function is to reduce the pressure in the pipework by opening a solenoid valve if it exceeds a set limit. If the pressure is not reduced within a given time, the solenoid valve will be closed, and a warning can be given. P [psi] 1: Solenoid valve opens. 2: Solenoid valve closes. 3: Solenoid valve opens. 4: Warning is activated. 5: Solenoid valve closes, and warning is reset. 1 23 45 Valve opening pressure Band Valve opening pressure minus band Fig. 99 Pressure relief Warning Time [sec] delay Setting range · Setting of digital output. · Setting of pressure to be monitored. · Setting of valve opening pressure. · Setting of band for valve opening pressure. · Setting of warning or alarm. · Activation of the function. Setting via control panel 1. Mark the Settings menu with 2. Mark Monitoring functions with or , and press . 3. Mark Pressure relief with or , and press . 4. Mark Go to setting of digital output with press . or , and 5. Select a digital output with or , and press . 6. Mark Pressure relief with or , and save with . 7. Return by pressing twice. 8. Mark Pressure to be monitored with . or , and press 9. Mark Discharge pressure, System pressure or External pressure with or , and save with . 10.Return with . 11.Mark Valve opening pressure with or . Set the pressure with or , and save with . 12.Mark Band, valve opening pressure with or pressure with or , and save with . . Set the 13.Mark Warning, Deactivated or Activated with and press . or , 14.Mark Delay with or . Set the time with or , and save with . (Only to be set if warning has been activated.) 15.Mark Activated with function. or , and press activate the Factory setting The function is deactivated. TM03 9206 3607 TM03 2295 4807 9.7.52 Functions, CU 351 (4.5) Fig. 100 Functions, CU 351 Description In this submenu, it is possible to make the basic settings of the CU 351. CU 351 comes with most of these settings, or they are made at start-up and normally not to be changed. The service language, English, can be activated for service purposes. If no buttons are touched for 15 minutes, the display will return to the language selected at start-up or to the language set in section 9.7.53 Display language (4.5.1). Note If the service language is selected, the symbol will be shown to the right of the top line of all displays. Setting range · Activation of service language, British English. · Re-activation of start-up wizard. (After start-up, the wizard is inactive.) · Selection of display language. · Selection of display units. · Setting date and time. · Selection of password for the menus Operation and Settings. · Setting of Ethernet communication. · Setting of GENIbus number. · Reading of software status. 9.7.53 Display language (4.5.1) TM03 8987 4807 Fig. 101 Display language 58 Q-Pulse Id: TMS196 26/11/2012 Page 63 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Description Here the language for the CU 351 display is selected. Setting range · British English · German · Danish · Spanish · Finnish · French · Greek · Italian · Dutch · Polish · Portuguese · Russian · Swedish · Chinese · Korean · Japanese · Czech · Turkish. Setting via control panel 1. Mark the Settings menu with . 2. Mark Functions, CU 351 with or , and press . 3. Mark Display language with or , and press . 4. Select language with or , and save with . Factory setting The display language is English. It can be changed at start-up. 9.7.54 Display units (4.5.2) Setting range Parameter Basic setting Possible units SI US Pressure Differential pressure Head Level Flow rate Volume Specific energy Temperature Differential temperature Power Energy bar psi kPa, MPa, mbar, bar, m, psi m psi kPa, MPa, mbar, bar, m, psi m ft m, cm, ft, in m ft m, cm, ft, in m3/h gpm m3/s, m3/h, l/s, gpm, yd3/s, yd3/min, yd3/h m3 gal l, m3, gal, yd3 kWh/m3, Wh/gal, kWh/m3 Wh/gal Wh/kgal, BTU/gal, HPh/gal °C °F K, °C, °F K KK kW HP W, kW, MW, HP kWh kWh kWh, MWh, BTU, HPh Note If units are changed from SI to US or vice versa, all individually set parameters will be changed to the basic setting in question. Setting via control panel 1. Mark the Settings menu with . 2. Mark Functions, CU 351 with or , and press . 3. Mark Units with or , and press . 4. Select the unit with or , and save with . A check mark shows that the unit has been selected. 5. Select the measuring parameter with or , and press to open the display for the measuring parameter. See the example. TM03 8988 4807 TM03 2310 4807 Fig. 102 Display units Description In this display, it is possible to select units for the various parameters. As basic setting, it is possible to select between SI and US units. It is also possible to select other units for the individual parameters. Fig. 103 Example of selection of display units 6. Select the unit with or , and save with . A check mark shows that the unit has been selected. Factory setting CU 351 has been set to US units from factory. Q-Pulse Id: TMS196 26/11/2012 59 Page 64 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.7.55 Date and time (4.5.3) 9.7.56 Passwords (4.5.4) TM03 8989 4807 TM03 2899 4807 Fig. 104 Date and time Description In this display, date and time are set as well as how they are to be shown in the display. The clock has a built-in rechargeable voltage supply which can supply the clock for up to 20 days if the voltage supply to the Hydro MPC is interrupted. If the clock is without voltage for more than 20 days, it must be set again. Setting range The date can be set as day, month and year. The time can be set as a 24-hour clock showing hours and minutes. There are three formats. Examples of format 2005-09-27 13:49 27-09-2005 13:49 9/27/2005 1:49pm It is also possible to select if Sunday or Monday is to be the first day of week. Setting via control panel 1. Mark the Settings menu with . 2. Mark Functions, CU 351 with or , and press . 3. Mark Date and time with or , and press . 4. Mark Day, Month and Year with or , and set the date with or . Save with . 5. Mark Hours and Minutes with or with or . Save with . , and set the time 6. Select the format with or , and save with . 7. Mark First day of week, Sunday or Monday with or , and save with Factory setting Local time. Note If the booster has been without voltage for more than 20 days since it left the factory, the clock may have returned to the original setting: 01-012005 0:00. Date and time may have been changed during the setting of Hydro MPC. There is no automatic changeover to/from daylight-saving time. Fig. 105 Passwords Description In this display it is possible to limit the access to the Operation and Settings menus by means of a password. If the access is limited, it is not possible to view or set any parameters in the menus. The password must consist of four digits and may be used for both menus. Note If you have forgotten the password(s), contact Grundfos. Setting via control panel 1. Mark the Settings menu with . 2. Mark Functions, CU 351 with or , and press . 3. Mark Password with or , and press . 4. Mark the password to be activated, and press . 5. Mark Enter password, and press . Now the first digit of the password is flashing. 6. Select the digit with or , and save with . Now the second digit of the password is flashing. 7. Repeat points 4 to 6 if it is necessary to activate the other password. Factory setting Both passwords are deactivated. If a password is activated, the factory setting will be "6814". 9.7.57 Ethernet (4.5.5) Fig. 106 Ethernet TM03 2298 4807 60 Q-Pulse Id: TMS196 26/11/2012 Page 65 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Description The CU 351 is equipped with an Ethernet connection for communication with a computer, either directly or via Internet. For further information, see section 9.8.1 Ethernet. 9.7.58 GENIbus number (4.5.6) 9.7.59 Software status (4.5.9) TM03 2297 4807 TM03 2296 4807 Fig. 107 GENIbus number Description CU 351 can communicate with external units via an RS-485 interface (option). For further information, see fig. 109 and section 9.8.2 GENIbus. Communication is carried out according to the Grundfos bus protocol, GENIbus, and enables connection to a building management system or another external control system. Operating parameters, such as setpoint and operating mode, can be set via the bus signal. Furthermore, status about important parameters, such as current value and input power, and fault indications can be read from the CU 351. Contact Grundfos for further information. Setting range The number can be set between 1 and 64. Setting via control panel 1. Mark the Settings menu with 2. Mark Functions, CU 351 with 3. Mark GENIbus number with 4. Select the number with or . or , and press . or , and press . , and save with . Factory setting No number is set (""). Fig. 108 Software status Description This display shows the status of the software installed in the CU 351. Furthermore, the version code and the product numbers of configuration files (GSC) read into the unit are shown. As it is a status display, no settings can be made. Q-Pulse Id: TMS196 26/11/2012 61 Page 66 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9.8 Data communication CU 351 is equipped with a hardware enabling communication with external units, such as a computer, via an external GENIbus or Ethernet connection. Third-party gateway Grundfos G100 gateway Intranet External GENIbus connection External GENIbus module (factory option) Ethernet connection Internet TM03 2044 3505 Fig. 109 Data communication via external GENIbus and Ethernet connection 9.8.1 Ethernet Ethernet is the most widely used standard for local networks (LAN). The standardisation of this technology has created some of the easiest and cheapest ways of creating communication between electrical units, for instance between computers or between computers and control units. The web server of the CU 351 makes it possible to connect a computer to the CU 351 via an Ethernet connection. The user interface can thus be exported from the CU 351 to a computer so that the CU 351 and consequently the Hydro MPC booster system can be monitored and controlled externally. Note Grundfos recommends that you protect the connection to the CU 351 according to your safety requirements in consultation with the system administrator. In order to use the web server, you must know the IP address of the CU 351. All network units must have a unique IP address in order to communicate with each other. The IP address of the CU 351 from factory is 192.168.0.102. Alternatively to the factory-set IP address, it is possible to use a dynamic assignment of IP address. This is possible by activating a DHCP (Dynamic Host Configuration Protocol) either directly in the CU 351 or via the web server. See the example in fig. 110. Fig. 110 Example of setting of Ethernet Dynamic assignment of an IP address for the CU 351 requires a DHCP server in the network. The DHCP server assigns a number of IP addresses to the electrical units and makes sure that two units do not receive the same IP address. A traditional Internet browser is used for connection to the web server of the CU 351. If you want to use the factory-set IP address, no changes are required in the display. Open the Internet browser and enter the IP address of the CU 351. TM03 2298 4807 62 Q-Pulse Id: TMS196 26/11/2012 Page 67 of 382 TM03 2047 3505 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual In order to use dynamic assignment, the function must be activated. Click Use DHCP in the menu line. A check mark next to the menu line shows that activation has been made. After activation in the display, open the Internet and enter the host name of the CU 351 instead of the IP address. The Internet browser will now try to connect to the CU 351. The host name can be read in the display, but can only be changed by either a GSC- file (configuration file) or via a web server. See Change of network setting on page 63. Note To use DHCP, a host name is required. This is the first display shown when connecting to the CU 351. Fig. 113 Network setting Change of network setting When connection to the web server of the CU 351 has been established, it is possible to change the network setting. TM03 2048 3505 Fig. 111 Connection to CU 351 Factory setting User name: admin Password: admin When user name and password have been entered, a Java Runtime Environment application starts up in the CU 351, provided that it has been installed on the computer in question. If this is not the case, but the computer is connected to Internet, then use the link on the screen to download and install the Java Runtime Environment application. Fig. 114 Change of network setting 1. Press the icon >Network admin. 2. Enter the changes. 3. Press Submit to activate the changes. TM03 2050 3505 TM03 2049 3505 Fig. 112 Display with link to the JavaScript® program The Java Runtime Environment application will then export the CU 351 user interface (including display and operating panel) to the computer screen. It is now possible to monitor and control the CU 351 from the computer. Q-Pulse Id: TMS196 26/11/2012 63 Page 68 of 382 TM03 2051 3505 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Change of password Fig. 115 Change of password 1. Press the icon >Change password. 2. Enter the new password. 3. Press Submit to activate the new password. 9.8.2 GENIbus By installing a GENIbus module it is possible to connect a CU 351 to an external network. The connection can take place via a GENIbus-based network or a network based on another protocol via a gateway. See fig. 109. For further information, contact Grundfos. The gateway may be a Grundfos G100 gateway or a third party gateway. For further information on the G100 gateway, see the G100 data booklet (publication number V7139522). 64 Q-Pulse Id: TMS196 26/11/2012 Page 69 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 10. External variable frequency drive External variable frequency drives used in Hydro MPC booster system variants -F, -EF and -EDF come with the manufacturer's factory settings. See tables below. At start-up, the factory settings must be changed to the Grundfos settings in the tables below. In order not to affect the functions of the CU 351 at optimum operation, only the parameters shown should be adjusted. Other parameters should be as set from factory. 10.1 VLT 2800 Press [QUICK MENU] + [+] to access all parameters. Parameter Function Factory setting Value or number in the display of VLT 2 Local/remote operation 3 Local reference 101 Torque characteristics 102 Motor power 103 Motor voltage 104 Motor frequency 105 Motor current 106 Rated motor speed 107 Automatic motor adaptation 128 Thermal motor protection 204 Minimum reference 205 Maximum reference 206 Ramp type 207 Ramp up time 208 Ramp down time 214 Reference function 215 Preset reference 302 Digital input 304 Digital input 305 Digital input6 323 Relay output 406 Automatic restart time 411 Switching frequency * Thermistor function used for thermal protection of LC filter. ** For information about languages available, see relevant documentation. *** Use data from the Hydro MPC booster set. Factory setting of VLT 2800 To recall the factory settings of all parameters, follow one of the procedures below: 1. Set the parameter 620 to (3). 2. Disconnect the power supply. 3. Re-connect the power supply. 4. All parameters are now factory-set except from the fault log. or 1. Disconnect the power supply. 2. Press and hold [QUICK MENU] + [+] + [CHANGE DATA] and re-connect the power supply. All parameters are now factory-set, including the fault log. Grundfos setting Function Value or number in the display of VLT Local/remote operation 0 Local reference Default Torque characteristics 2 Motor power Motor nameplate in kW Motor voltage Motor nameplate Motor frequency Motor nameplate, Hz Motor current Motor nameplate, SFA Rated motor speed Motor nameplate RPM Automatic motor adaptation 2 Thermal motor protection 4 Minimum reference 20 Hz Maximum reference 60 Hz Ramp type 2 Ramp up time 1.5 sec Ramp down time 3 sec Reference function 2 Preset reference 100 Digital input 7 Digital input 0 Digital input6 24 Relay output 1 Automatic restart time Switching frequency 10 sec 4500 Q-Pulse Id: TMS196 26/11/2012 65 Page 70 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 10.2 Danfoss VLT 8000 factory settings Press [EXTEND MENU] to access all parameters. Parameter 001 002 003 004 005 006 201 202 207 208 323 326 Function Language Motor power Motor voltage Motor frequency Motor current Motor speed Minimum frequency Maximum frequency Ramp up time Ramp down time Relay 1 function Relay 2 function Grundfos setting Value English 0 Motor nameplate Motor nameplate Motor nameplate Motor nameplate (SFA) Motor nameplate (RPM) 20 Hz 60 Hz 1.5 sec 3 sec Ready signal 1 Running 3 10.3 Danfoss VLT 8000 extended menu programming Parameter Function Grundfos setting Value 007 Large readout Frequency [Hz] 3 008 Small display readout Motor voltage [V] 16 009 Small display readout Motor current 5 010 Small display readout Power [Hp] 6 101 Torque characteristics VT low 2 113 Motor Preheater DC Current 0% 117 Motor Thermal Protection ETR Trip 1 4 208 Automatic ramp-down Disable 0 210 Reference type External/preset 2 302 Pin 18 Start 1 303 Pin 19 Reverse and start 2 304 Pin 27 Safety interlock 3 308 Pin 53 Reference 1 309 Term. 53, min. scaling 0.0 V 310 Term. 53, max. scaling 10 V 325 Relay 01, off delay 1 sec. 400 Reset function Automatic reset x 10 6 401 Automatic restart time 5 sec. 407 Switching frequency 4500 408 Interference reduction method Fixed switching freq. 0 016 Lock for data change Locked 1 66 Q-Pulse Id: TMS196 26/11/2012 Page 71 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 10.4 Danfoss VLT 8000 factory settings Press [EXTEND MENU] to access all parameters. Parameter 001 002 003 004 005 006 201 202 207 208 323 326 Function Language Motor power Motor voltage Motor frequency Motor current Motor speed Minimum frequency Maximum frequency Ramp up time Ramp down time Relay 1 function Relay 2 function Grundfos setting Value English 0 Motor nameplate Motor nameplate Motor nameplate Motor nameplate (SFA) Motor nameplate (RPM) 20 Hz 60 Hz 1.5 sec 3 sec Ready signal 1 Running 3 10.5 Danfoss VLT 8000 extended menu programming Parameter Function Grundfos setting Value 007 Large readout Frequency [Hz] 3 008 Small display readout Motor voltage [V] 16 009 Small display readout Motor current 5 010 Small display readout Power [Hp] 6 101 Torque characteristics VT low 2 113 Motor Preheater DC Current 0% 117 Motor Thermal Protection ETR Trip 1 4 208 Automatic ramp-down Disable 0 210 Reference type External/preset 2 302 Pin 18 Start 1 303 Pin 19 Reverse and start 2 304 Pin 27 Safety interlock 3 308 Pin 53 Reference 1 309 Term. 53, min. scaling 0.0 V 310 Term. 53, max. scaling 10 V 325 Relay 01, off delay 1 sec. 400 Reset function Automatic reset x 10 6 401 Automatic restart time 5 sec. 407 Switching frequency 4500 408 Interference reduction method Fixed switching freq. 0 016 Lock for data change Locked 1 Q-Pulse Id: TMS196 26/11/2012 67 Page 72 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 10.6 Baldor Smart motor settings Section Parameter Level 2 blocks Output limts Output limts Output limts Output limts Miscellaneous Motor data Motor data Level 1 blocks Preset speed Accel Min. output frequency Max. output PK current limit PWM frequency Restart aut/man Motor voltage Motor rated amps Preset speed #1 Accel #1 Decel rate Decel #1 Output Input Input V/Hz and Boost Opto output #1 Operating mode ANA CMD select V/Hz profile Grundfos setting Value 12 Hz 60 Hz Max. of drive 6 kHz Auto 230 V SFA on nameplate 60 Hz CR 3 - CR 10 CR 15 - CR 90 CR 3 - CR 10 CR 15 - CR 90 Ready #1 2 wire / 7 spd Pot. / 0-10 V 67% sqr. law 1.5 sec. 2.0 sec. 3.0 sec. 4.0 sec. 68 Q-Pulse Id: TMS196 26/11/2012 Page 73 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 10.7 VLT FC 202 Press [EXTEND MENU] to access all parameters. Parameter Function Grundfos setting Value 001 002 003 020 021 022 023 024 100 103 121 122 123 124 125 190 302 303 304 310 313 341 342 412 414 419 511 513 540.0 542.0 610 611 614 615 1400 1401 Language Motor Speed Unit Regional Settings Display Line 1.1 Display Line 1.2 Display Line 1.3 Display Line 2 Large Display Line 3 Large Configuration Mode Torque Characteristics Motor Power [HP] Motor Voltage Motor Frequency Motor Current Motor Nominal Speed Motor Thermal Protection Minimum Reference Maximum Reference Reference Function Preset Reference Reference Site Ramp 1 Ramp up Time Ramp 1 Ramp down Time Motor Speed Low Limit [Hz] Motor Speed High Limit [Hz] Max Output Frequency Terminal 19 Digital Input Terminal 29 Digital Input Function Relay Off Delay, Relay Terminal 53 Low Voltage Terminal 53 High Voltage Terminal 53 Low Ref. / Feedb. Terminal 53 High Ref. / Feedb. Switching Pattern Switching Frequency English Hz North America Small Power [hp] Small Motor Voltage Small Motor Current Frequency Speed [RMP] Open Loop Variable Torque Nameplate Nameplate Nameplate Nameplate Nameplate ETR trip 1 0.000 Hz 60.000 Hz Sum 100.00% Remote 1.50 s 3.00 s 0.0 Hz 60.0 Hz 65.0 Hz Start reversing Preset reference on Drive ready 2.00 s 0.00 V 10.00 V 20.000 Hz 60.000 Hz 60 AVM 5.0 kHz 0 1 1 1611 1612 1614 1615 1617 0 1 4 0 1 11 15 2 0 7 Factory setting of VLT FC 100 To recall the factory settings of all parameters, follow one of the procedures below: 1. Select parameter 14-22. 2. Press [OK]. 3. Select "Initialisation" (for NLCP select "2"). 4. Press [OK]. 5. Disconnect the power supply. 6. Reconnect the power supply. 7. All parameters are now factory-set, except RFI 1, protocol, address, baud rate, minimum response delay, maximum response delay, maximum inter-char delay, operating data, historic log and fault log. or 1. Disconnect the power supply. 2. Press and hold [STATUS] + [MAIN MENU] + [OK] and reconnect the power supply. 3. All parameters are now factory-set, except operating hours, the number of power-ups and overtemp's and overvolt's. Q-Pulse Id: TMS196 26/11/2012 69 Page 74 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 11. Fault finding chart Warning Before making any connections in pumps, terminal boxes or breaker cabinet, make sure that the electricity supply has been switched off for at least 5 minutes and that it cannot be accidentally switched on. Fault Possible cause Remedy Current pressure is higher than or equal to the setpoint. Wait until the pressure has dropped, or lower the pressure on the discharge side of the Hydro MPC, and check that the pumps start. Electricity supply disconnected. Connect the electricity supply. Main switch cut out. Cut in the main switch. Pumps do not run when started. Main switch is defective. Motor protection is activated. Replace the main switch. Contact Grundfos. Motor is defective. Repair or replace the motor. Pressure transmitter fault - Pressure transmitter is defective. Replace the pressure transmitter. Transmitters with 0-20 mA or 4-20 mA output signals are monitored by the Hydro MPC. - Cable is broken or short-circuited. Repair or replace the cable. The pumps start, but stop immediately. The operating pressure Dry running or no inlet pressure. is not reached. Re-establish the supply of water to the Hydro MPC. When the inlet pressure has been re-established, the pumps will restart after 15 seconds. The Hydro MPC is stopped and cannot restart. Pressure transmitter fault - Pressure transmitter is defective. - Cable is broken or short-circuited. CU 351 fault - Electricity supply disconnected. Replace the pressure transmitter. Transmitters with 0-20 mA or 4-20 mA output signals are monitored by the Hydro MPC. Repair or replace the cable. Connect the electricity supply. - CU 351 defective. Contact Grundfos. Inlet pressure is too low. Unstable water delivery from Suction pipe or pumps partly blocked by Hydro MPC (applies to unstable water impurities. supply). Pumps suck air. Check the suction pipe and possible suction strainer. Clean the suction pipes, strainer or pumps. Check the suction pipe for leakages. Pressure transmitter defective. Replace the transmitter. The valves are closed. Open the valves. Suction pipe or pumps blocked by impurities. Clean the suction pipe or pumps. Pumps are running, but deliver no water. Non-return valve blocked in closed position. Clean the non-return valve. The non-return valve must move freely. Suction pipe leaky. Check the suction pipe for leakages. Air in suction pipe or pumps. Vent and prime the pumps. Check the suction pipe for leakages. The Hydro MPC is unable to reach the setpoint. Too high consumption. Too many standby pumps selected. Pipe fracture or leakage in the system. - Reduce consumption (if possible). - Install a bigger Hydro MPC booster system. Reduce the number of standby pumps. Check the system, and repair damages, if necessary. Leakage from the shaft seal. Shaft seal is defective. Replace the shaft seal. Height adjustment of pump shaft inaccurate. Readjust the shaft height. The pumps are cavitating. Clean the suction pipe/pumps and possibly the suction strainer. Noise. The pumps do not rotate freely (friction resistance) due to inaccurate height adjustment of the pump shaft. Readjust the shaft height. Very frequent starts and stops. Wrong diaphragm tank precharge pressure. Set correct precharge pressure. 70 Q-Pulse Id: TMS196 26/11/2012 Page 75 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 12. Maintenance Warning Before starting work on the pumps, make sure that the electricity supply has been switched off. Lock the main switch with a padlock to ensure that it cannot be accidentally switched on. 12.1 Pumps Pump bearings and shaft seal are maintenance-free. 12.2 Motor bearings Motors without grease nipples are maintenance-free. Motors with grease nipples should be lubricated with a hightemperature lithium-based grease. See the instructions on the fan cover of Grundfos motors. In the case of seasonal operation (motor is idle for more than 6 months of the year), it is recommended to grease the motor when the pump is taken out of operation. 12.3 CU 351 The CU 351 is maintenance-free. It must be kept clean and dry. Protect it against direct sunlight. Furthermore, the CU 351 must not be outside the ambient temperature range. See section 15. Technical data. 13. Frost protection Pumps which are not being used during periods of frost should be drained to avoid damage. Drain the pump by loosening the vent screw in the pump head and by removing the drain plug from the base. Warning Care must be taken to ensure that the escaping water does not cause injury to persons or damage to the motor or other components. In hot water installations, special attention should be paid to the risk of injury caused by scalding hot water. Do not tighten the vent screw and replace the drain plug until the pump is to be used again. 14. Taking out of operation Switch off the main switch to take the booster system out of operation. Warning The conductors in front of the main switch are still energised. Lock the main switch with a padlock to ensure that it cannot be accidentally switched on. Individual pumps are taken out of operation by switching off the corresponding motor-protective circuit breaker, automatic circuit breaker or fuse. 15. Technical data 15.1 Pressure Inlet pressure Hydro MPC booster sets can operate with a positive inlet pressure (precharged pressure system) or with a negative inlet pressure (i.e vacuum at the inlet manifold). Calculation of the inlet pressure is recommended when · water is drawn through long pipes, · water is drawn from depths, · inlet conditions are poor. Note In this installation and operating instruction the term `inlet pressure' is defined as the pressure/ vacuum which can be measured immediately before the booster set. To avoid cavitation, make sure that there is a minimum inlet pressure on the suction side of the booster set. The minimum inlet pressure in bar can be calculated as follows: H = Pb NPSH Hf Hv Hs Pb = Barometric pressure in feet (33.9 feet at sea level). In closed systems, Pb indicates system pressure in feet. Hf = Friction loss in suction piping in feet. (At the highest flow the pump will be delivering). Hv = Vapor pressure in feet. NPSH = Net Positive Suction Head in feet. NPSH can be read from the NPSH curve at the maximum capacity at which the pump will run. (See installation and operating instructions for CR, CRI, CRN). HS = Safety margin = minimum 2 feet. If "H" is calculated as positive, the pump can operate at a suction of maximum "H" feet. If "H" is calculated as negative, an inlet pressure (psia) of minimum "H" feet is required. Maximum inlet pressure Pump 60 Hz CR(E) 5-7 CR(E) 10-3 CR(E) 15-3 CR(E) 20-3 CR(E) 32-2 CR(E) 45-2-1 CR(E) 64-2-1 CR 90-2-1 Maximum inlet pressure [psi] 145 116 145 145 58 145 145 218 Note The maximum inlet pressure is determined by the construction of the pump, such as bearing pressure. For information about other CR pump sizes, see WebCAPS on www.grundfos.com. Operating pressure As standard the maximum operating pressure is 230 psi [16 bar]. On request, Grundfos offers Hydro MPC booster systems with a maximum operating pressure higher than 230 psi [16 bar]. Q-Pulse Id: TMS196 26/11/2012 71 Page 76 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 15.2 Temperature Liquid temperature: Ambient temperature: 32 °F to +158 °F 32 °F to +104 °F 15.3 Relative humidity Max. relative humidity: 95 % 15.4 Sound pressure For sound pressure level, see the installation and operating instructions for the CR pumps. The sound pressure level for a number of pumps can be calculated as follows: Lmax = Lmax = Lpump = n= Lpump + (n 1) x 3 Maximum sound pressure level. Sound pressure level for one pump. Number of pumps. 16. Electrical data Supply voltage See nameplate of the Hydro MPC. Backup fuse See the wiring diagram supplied with the Hydro MPC. Digital inputs Open circuit voltage: Closed circuit current: Frequency range: 24 VDC 5 mA, DC 0-4 Hz Note All digital inputs are supplied with PELV voltage (Protective Extra-Low Voltage). Analog inputs Input current and voltage: Tolerance: Repetitive accuracy: Input resistance, current: Input resistance, voltage, CU 351: Input resistance, voltage, IO 351: Supply to sensor: 0-20 mA 4-20 mA 0-10 V ±3.3 % of full scale ±1% of full scale < 250 10 k ±10 % > 50 k ± 10 % 24 V, maximum 50 mA, short-circuit protected Note All analog inputs are supplied with PELV voltage (Protective Extra-Low Voltage). Digital outputs (relay outputs) Maximum contact load: Minimum contact load: 240 VAC, 2 A 5 VDC, 10 mA All digital outputs are potential-free relay contacts. Note Some outputs have a common C terminal. For further information, see the wiring diagram supplied with the Hydro MPC. Inputs for PTC sensor/thermal switch For PTC sensors to DIN 44082. Thermal switches can also be connected. Open circuit voltage: Closed circuit current: 12 VDC ±15 % 2.6 mA, DC Note Inputs for PTC sensors are electrically separated from the other inputs and outputs of the Hydro MPC. 17. Related documents Further product information about Hydro MPC booster systems can be found in the following documents. All documents are available in WebCAPS on Grundfos' homepage, www.grundfos.com. Title Frequency Publication number Product Guide Grundfos Hydro MPC Grundfos CR,CRI,CRN 60 Hz 60 Hz Installation and operating instructions CR, CRI, CRN CRE, CRIE, CRNE, CRKE, SPKE, MTRE, CHIE * 60 Hz 60 Hz Service documentation Service instructions Service kit catalog 50/60 Hz 50/60 Hz Other documentation Wiring diagram** - L-BPQ-PG-01 L-CR-PG-001 L-CP-TL-003 L-MLE-TL-02 96646712 96488862 - * Only relevant for Hydro MPC-E, -ED and -ES booster systems. ** A wiring diagram is supplied with the booster system. 18. Disposal This product or parts of it must be disposed of in an environmentally sound way: 1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop. 72 Q-Pulse Id: TMS196 26/11/2012 Subject to alterations. Page 77 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4 ELECTRICAL EQUIPMENT TECHNICAL INFORMATION 4.1 Circuit Breakers & Isolators 4.2 Surge Protection & Fuses 4.3 Control Devices 4.4 Variable Frequency Drive 4.5 Instruments 4.6 Pushbuttons & Selector Switches 4.7 Telemetry & Power 4.8 Accessories Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 78 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4.1 CIRCUIT BREAKERS & ISOLATORS Terasaki DINTMS1003 100A Metering Isolator Terasaki E125NJ100 3P 100A Moulded Case Circuit Breaker Terasaki DTCB15332C + DTLDC 3P 32A Circuit Breaker + Captive Lock Dog Terasaki DTCB10306C 3P 6A Circuit Breaker Terasaki DTCB10106C 1P 6A Circuit Breaker Terasaki DTCB10104C 1P 4A Circuit Breaker Terasaki DSRCBH-16-30A 1P 16A Residual Circuit Breaker Overload Terasaki DSRCBH-06-30A 1P 6A Residual Circuit Breaker Overload Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 79 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 1 Innovators in Protection Technology Miniature circuit breakers Din-TMS main switches 63 100 amps M6tsaoi3Tid6neC3-cDhs1m&awa0Duossi08xtiisundc0iinAlseh-i.tTaastmrmrAoacydlohnpliNsuag,raweCnseccsitcDtitesci.hnpt- n AS/NZS 60947-3 n Double break contacts n Dual function terminals busbar and cable n Padlockable handle n Handle sealable: On and Off position n Terminal protection degree IP 20 n Used as main switch (isolator) in loadcentres and distribution boards n Suits NC or CD type chassis Rating In (A) 63 No. of Poles 1 No. of Modules 1 Contacts Cat. No. 1) DINTMS631 2 2 DINTMS632 3 3 DINTMS633 80 1 1 DINTMS801 2 2 DINTMS802 3 3 DINTMS803 100 1 1 DINTMS1001 2 2 DINTMS1002 3 3 DINTMS1003 DINTMS 3 pole DINTMS 1 pole Technical data Nominal rated current Usable as mains disconnect switch Nominal breaking capacity at 415 V, cos ø = 0.95 Nominal breaking capacity at 415 V, cos ø = 0.65 Nominal voltage single pole devices Nominal voltage multipole devices Maximum allowed current during less than 1 s. Mechanical service life (complete on-off-cycle) Electrical service life, cos ø = 0.95, Un and In Short-circuit resistance with upfront fuses Short-circuit resistance without upfront fuses Protection degree Screws Terminal capacity: min. max. Making capacity 1.05 x 4, cos ø0.65 63-80-100 A yes 3 x In 3 x In 240 / 415 V 240 / 415 V 2 kA >20000 >1500 16 kA (nominal) 7 kA (peak) IP 20 Pozidrive 2 1 x 6 mm2 1 x 50 mm2 3 x Ie Accessories Auxiliary contacts Padlock attachment Page 1 - 32 to 35 1 - 45 Notes: 1) DINTMS Main switches will accept side mounting auxiliary switches only. Front mounting and terminal devices can also be fitted. 1 - 30 Q-Pulse Id: TMS196 26/11/2012 Page 80 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MCCB's Thermal magnetic type E125NJ 25kA Current rating: 12.5 125A Approvals and Tests: Standards AS/NZS 3947-2, and IEC60947-2 Interrupting capacity: Voltage AC use 380/415 DC use 250V Icu Ics 25 19 25 19 Trip unit: Adjustable thermal (0.63 Ir to 100% Ir) and adjustable magnetic (6 Im to 12 Im) Dimensions (mm) Poles H W D (less toggle) Toggle cut-out 3 155 90 68 Standard DIN Ampere Rating NRC Adj. Ir 1) Min - Max. Adj. Im 1) Min - Max. 20 12.5 - 20 120 - 240 32 20 - 32 192 - 384 50 32 - 50 300 - 600 63 40 - 63 378 - 756 100 63 - 100 600 - 1200 125 80 - 125 750 - 1500 1) NRC: Adj. Ir: Adj. Im: Nominal rated current Adjustable thermal setting Adjustable magnetic setting Cat. No. E125 NJ 3 20 E125 NJ 3 32 E125 NJ 3 50 E125 NJ 3 63 E125 NJ 3 100 E125 NJ 3 125 Replaces: XS125CJ, Note: check exact ratings or dimenions to suit your application requirement Price Schedule T2 Q-Pulse Id: TMS196 26/11/2012 6 Page 81 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs OPERATING CHARACTERISTICS THERMAL MAGNETIC PROTECTION Adjustment Dials SECTION 3 1. IR is the thermal element adjustment dial and is used to set the rated current to match the conductor rating. IR can be set between 0.63 and 1.0 times In. 2. Ii is the magnetic element adjustment dial and is used to set the short circuit tripping threshold to suit the application. Ii can be set between 6 and 12 times In on 125A and 400A frame models. Ii can be set between 6 and 13 times In on 250A frame models with ratings of 160A, 200A and 250A. Ii can be set between 6 and 12 times In on 250A frame models with ratings of 125A and less. Models, Types and Rated Currents of Thermal Elements Model S125 E125 S125 S125 H125 L125 S160 S160 S160 H160 L160 E250 S250 S250 H250 L250 E400 S400 S400 S400 H400 L400 Type -NF -NJ -NJ -GJ -NJ -NJ -NF -NJ -GJ -NJ -NJ -NJ -NJ -GJ -NJ -NJ -NJ -CJ -NJ -GJ -NJ -NJ Current Rating In (A) 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 20, 32, 50, 63, 100, 125 20, 32, 50, 63, 100, 125 20, 32, 50, 63, 100, 125 20, 32, 50, 63, 100, 125 20, 32, 50, 63, 100, 125 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 20, 32, 50, 63, 100, 125, 160 50, 63, 100, 125, 160 160 160 20, 32, 50, 63, 100, 125, 160, 200, 250 160, 200, 250 160, 200, 250 160, 250 160, 250 250, 400 250, 400 250, 400 250, 400 250, 400 250, 400 Beyond the StandardTM Q-Pulse Id: TMS196 26/11/2012 page 23 Page 82 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs OPERATING CHARACTERISTICS THERMAL MAGNETIC CHARACTERISTICS 125A Frame MCCBs SECTION 3 Q-Pulse Id: TMS196 Beyond the StandardTM 26/11/2012 page 25 Page 83 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA SELECTIVITY (DISCRIMINATION) AND CASCADE Selectivity The principle of Selectivity (Discrimination) is based upon an analysis of several circuit breaker characteristics. These include time-current (tripping) curves, peak-let-through current (Ipeak) and energy let-through (I2t). The figures stated give the maximum selectivity level with the two nominated breakers in series under short-circuit conditions. For an indication on selectivity under overloads refer to the circuit breaker tripping/characteristic curves, or use the NHP TemCurve selectivity analysis software package. Selectivity can be enhanced beyond the breaking capacity of the downstream breaker provided it is backed up by an appropriately selected upstream breaker, which should not trip (unlatch) under the stated short circuit current. Cascade Cascading is achieved by using an upstream device to assist (back-up) a downstream device in clearing a fault current. This principal is necessary should the downstream device be required to clear a prospective short circuit current greater than the devices' breaking capacity. In most cascading applications it is generally necessary for the upstream breaker to trip (unlatch), as well as the downstream breaker to give adequate back-up protection. As such, cascade is commonly used in feeding and protecting non-essential loads, such as basic lighting. For more information on selectivity and cascading please refer to the latest NHP Part C catalogue. SECTION 4 page 44 Beyond the StandardTM Q-Pulse Id: TMS196 26/11/2012 Page 84 of 382 page 45 Page 85 of 382 Beyond the StandardTM 26/11/2012 Q-Pulse Id: TMS196 S250PE H250NE S400NE S400GE H400NE L400NE E630NE S630CE S630GE TL630NE XS800SE XH800SE TL800NE XS1250SE TL1250NE XS1600SE XS2000NE XS2500NE Selectivity & Cascade Tables @ 400 / 415 V Upstream MCCBs Downstream kA MCCBs (RMS) 70 125 50 E125NJ 25 25/25 25/65 25/36 S125NJ 36 36/36 36/85 36/50 S125GJ 65 65/65 65/125 50/50 H125NJ 125 70/70 125/125 50/50 S160NJ 36 36/50 S160GJ 65 50/50 H160NJ 125 E250NJ 25 S250NJ 36 S250GJ 65 S250PE 70 H250NJ 125 H250PE 125 E400NJ 25 S400CJ 36 S400NE 50 S400NJ 50 S400GJ 70 H400NJ 125 H400NE 125 E630NE 36 E630CE 50 S630GE 70 XS630CJ 45 XS630NJ 65 XS630PJ 85 XS630SE 50 XH630SE 65 XH630PE 65 XS800NJ 65 XS800SE 50 XJ800PJ 85 XH800SE 65 XH800PE 65 XS1250SE 65 XS1600SE 85 70 125 200 36 25/50 25/65 25/85 25/36 36/65 36/85 36/125 36/36 65/70 65/125 65/150 36/36 70/70 125/125 125/200 36/36 36/65 36/85 36/125 36/36 65/70 65/125 65/150 36/36 125/125 125/200 36/36 25/65 25/85 25/36 36/85 36/125 36/36 65/125 65/150 36/36 40/125 70/150 36/36 125/125 125/200 36/36 125/125 125/200 36/36 10/25 10/36 10/36 10/36 10/36 10/36 10/36 50 25/25 36/36 50/50 50/50 36/50 50/50 50/50 25/25 36/36 50/50 50/50 50/50 50/50 10/25 10/36 10/50 10/36 10/50 10/50 10/50 SECTION 4 XX / YY Selectivity/ Cascade 70 25/50 36/65 65/70 70/70 36/50 65/70 70/70 25/50 36/65 65/70 70/70 70/70 70/70 10/50 10/65 10/50 10/70 10/70 10/70 10/70 125 25/25 36/36 65/65 70/70 36/36 65/65 70/70 25/25 36/36 65/65 70/70 70/70 70/70 10/36 10/50 10/50 10/65 10/70 10/70 10/70 50 25/36 36/50 65/50 50/50 36/36 50/50 50/50 25/25 36/36 50/50 50/50 50/50 50/50 25/25 25/36 25/50 25/50 25/50 25/50 25/50 25/36 25/50 65 25/36 36/36 65/65 65/65 36/65 50/65 50/65 25/50 36/36 50/65 50/65 50/65 50/65 25/25 25/36 25/50 25/50 25/50 25/65 25/65 25/36 25/50 125 85 125 100 85 85 25/65 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36 65/65 65/65 65/65 65/65 65/65 65/65 65/65 85/50 85/50 100/100 85/85 85/85 36/65 36/36 36/36 36/36 36/36 36/36 50/65 65/65 65/65 65/65 65/65 65/65 50/65 85/65 85/65 100/100 85/85 85/85 25/50 25/25 25/25 25/25 25/25 25/25 36/36 36/36 36/36 36/36 36/36 36/36 50/65 65/65 65/65 65/65 65/65 65/65 50/65 70/70 70/70 70/70 70/70 70/70 50/65 85/85 85/85 100/100 85/85 85/85 50/65 85/85 85/85 100/100 85/85 85/85 25/36 25/25 25/25 25/36 25/25 25/25 25/50 36/36 36/36 36/50 36/36 36/36 25/50 50/50 50/50 50/50 50/50 50/50 25/65 50/50 50/50 50/65 50/50 50/50 25/65 70/36 70/36 70/85 70/70 70/70 25/65 125/85 125/85 125/100 125/85 125/85 25/65 125/85 125/85 125/100 125/85 125/85 25/36 36/36 36/36 36/36 36/36 36/36 25/50 50/50 50/50 50/50 50/50 50/50 70/70 70/70 70/70 70/70 70/70 30/45 30/45 30/45 35/45 35/45 30/65 30/65 30/65 35/65 36/65 30/85 30/85 30/85 35/85 35/85 30/65 30/65 30/85 30/85 30/85 30/65 30/65 30/85 30/85 30/85 30/65 30/65 30/85 30/85 30/85 15/65 15/65 20/65 35/65 35/65 15/50 15/50 20/50 35/50 35/50 15/85 15/85 20/85 35/85 35/85 15/65 15/65 20/65 35/65 35/65 15/65 15/65 20/65 35/65 35/65 20/65 35/65 35/65 35/85 35/85 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA SELECTIVITY TABLES WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA CASCADE TABLES L250NJ H250NE H250NJ S250PE S250GJ S250NJ E250NJ L160NJ H160NJ S160GJ S160NJ L125NJ H125NJ S125GJ S125NJ E125NJ SECTION 4 CASCADE @ 380 415 V AC 1) Downstream kA MCCBs (RMS) 25 36 65 125 200 36 65 125 200 25 36 65 70 125 125 200 E125NJ S125NJ S125GJ H125NJ S160NJ S160GJ H160NJ S250NJ S250GJ S250PE H250NJ E400NJ S400CJ S400NJ S400GJ H400NJ 25 36 36 65 85 36 36 65 85 36 36 65 65 85 36 50 85 125 50 85 125 85 85 125 65 125 150 125 150 65 125 125 150 125 200 - 200 65 200 36 65 65 85 125 65 65 85 85 125 65 125 150 70 125 125 150 125 200 - 200 36 65 65 85 85 125 65 70 125 125 150 70 125 125 150 125 200 25 36 65 65 36 50 70 70 50 50 65 85 85 70 50 125 125 125 Note: 1) Ratings have not been verified where a dash "" is shown. All pick-up and time delay settings are to be set at a maximum for upstream MCCB's Upstream MCCBs XS1600SE XS1250SE TL800NE XH800SE XS800NJ XS800SE TL630NE S630GE S630CE E630NE L400NE L400NJ H400NJ H400NE S400GE S400GJ S400NE S400NJ S400CJ CASCADE @ 380 415 V AC 1) Downstream kA MCCBs (RMS) 36 50 70 125 200 200 36 50 70 125 65 65 65 200 65 85 E125NJ S125NJ S125GJ H125NJ S160NJ S160GJ H160NJ E250NJ S250NJ S250GJ S250PE H250NJ E400NJ S400CJ S400NJ S400GJ H400NJ 25 36 36 50 65 85 85 36 - 50 36 36 36 36 50 65 85 125 125 - 65 50 50 65 70 125 150 150 50 70 65 125 200 200 - 65 50 36 50 65 85 125 125 50 50 65 65 65 70 125 150 150 70 125 200 200 65 65 25 36 36 50 65 85 85 36 50 36 50 36 50 65 85 125 125 65 65 65 70 125 150 150 70 70 125 150 150 125 200 200 - 25 36 36 50 65 85 85 36 50 36 36 36 36 50 65 70 100 100 65 50 50 50 50 70 85 125 125 36 70 65 50 65 65 70 125 150 150 36 50 36 85 125 200 200 Note: 1) Ratings have not been verified where a dash "" is shown. All pick-up and time delay settings are to be set at a maximum for upstream MCCBs page 46 Beyond the StandardTM Q-Pulse Id: TMS196 26/11/2012 Page 86 of 382 SECTION 4 H400NJ S400GE S400GJ S400CJ S250GJ S250NJ H125NJ S125GJ S125NJ E125NJ WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA SELECTIVITY AND CASCADE TEMBREAK 2 MCCBs AND DIN-T / SAFE-T MCBs Upstream MCCB SELECTIVITY / CASCADE @ 415 V AC Downstream MCB DTCB6 DTCB10 DSRCBH / DSRCD Din-T10H DTCH15 Safe-T SRCB Amp rating 2 20 25 63 0.5 32 40 63 0.5 32 40 80 125 0.5 32 40 63 16 20 16 20 kA (RMS) 25 36 65 36 65 36 70 125 6 18/18 25/25 35/35 35/35 35/35 6 18/18 20/25 20/25 30/30 30/30 10 18/18 30/30 30/50 35/35 40/50 35/35 40/50 40/50 10 18/18 20/25 25/25 30/30 30/30 30/30 30/30 30/30 10 18/18 30/30 30/50 35/35 40/50 35/35 40/50 40/50 10 18/18 20/25 25/25 30/30 30/30 30/30 30/30 30/30 10 4/18 4/25 4/25 15/15 15/15 10/10 10/10 15 18/18 30 30/50 35/35 40/50 35/35 40/50 40/50 15 18/18 20 25/25 30/30 30/30 30/30 30/30 30/30 6 3/10 3/10 3/10 6 3/10 3/10 3/10 Guide XX / YY Selectivity Cascade Notes: All figures stated are at 400/415 V AC. Q-Pulse Id: TMS196 Beyond the StandardTM 26/11/2012 page 47 Page 87 of 382 SECTION 4 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA MOTOR STARTING TYPE 1 CO-ORDINATION TABLES Short-Circuit Co-Ordination Motor Starting Table Type `1' Terasaki MCCB's & Sprecher + Schuh KT7's DOL starting 50/65 kA @ 400/415 V to AS/NZS 60947.4.1 TYPE 1 50/65 kA Motor Size (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 5 0 10 32 60 00 Approx. amps @ 400/415 V (A) 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 21 28 34 40 55 66 80 100 130 155 200 225 270 361 Terasaki Combinations MCCB Contactor XM30PB/1.4 XM30PB/2 XM30PB/2.6 XM30PB/4.0 XM30PB/5 XM30PB/8 XM30PB/10 XM30PB/12 S125GJ/20 S125GJ/20 S125GJ/32 S125GJ/50 S125GJ/50 S125GJ/63 S125GJ/100 S125GJ/100 S125GJ/125 S125GJ/125 S250PE/250 S250PE/250 S250PE/250 S400GE/400 S400GE/400 S400GE/400 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 CA6-110 CA6-140 CA6-180 CA6-210 CA6-210 CA6-300 CA6-420 Notes: · Thermal or electronic overload relays may be used. · XM30PB MCCB's can be replaced with S125GJ/20 if required. · Combinations based on the thermal overload relay tripping before the circuit. breaker at overload currents up to the motor locked rotor current. Terasaki Combinations Overload Relay CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-45 CT 7-45 CT 7-45 CT 7-75 CT 7-75 CT 7-100 CEF 1-11/12 CEF 1-11/12 CEF 1-11/12 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 Thermal Setting (A) 1.0 - 1.6 1.0 - 1.6 1.6 - 2.4 2.4 - 4.0 2.4 - 4.0 4.0 - 6.0 6.0 - 10 6.0 - 10 10 - 16 10 - 16 16 - 24 18 - 30 30 - 45 30 - 45 45 - 60 60 - 75 70 - 90 20 - 180 20 - 180 20 - 180 160 - 400 160 - 400 160 - 400 160 - 400 Sprecher + Schuh Combinations KT7 Circuit Breaker KTA7-25S-1.0A KTA7-25S-1.6A KTA7-25S-2.5A KTA7-25S-2.5A KTA7-25S-4.0A KTA7-25S-6.3A KTA7-25S-6.3A KTA7-25S-10A KTA7-25H-16A KTA7-25H-16A KTA7-45H-20A KTA7-45H-32A KTA7-45H-45A KTA7-45H-45A KTA3-100-63A KTA3-100-90A KTA3-100-90A KTA3-160S-100A KTA3-160S-160A KTA3-160S-160A KTA3-250S-200A KTA3-250S-250A KTA3-400S-320A KTA3-400S-400A Contactor CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 CA6-110 CA6-140 CA6-180 CA6-210 CA6-250 CA6-300 CA6-420 page 48 Beyond the StandardTM Q-Pulse Id: TMS196 26/11/2012 Page 88 of 382 SECTION 4 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA MOTOR STARTING TYPE 2 CO-ORDINATION TABLES Short-Circuit Co-Ordination DOL Motor Starting Table Type `2' Terasaki MCCB's & Sprecher + Schuh KT7's DOL starting 50/65 kA @ 400/415 V to AS/NZS 60947.4.1 TYPE 2 50/65 kA Motor Size (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 Approx. amps @ 400/415 V (A) 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 21 28 34 40 55 66 80 100 130 155 200 225 270 361 Terasaki Combinations MCCB Contactor XM30PB/1.4 XM30PB/2 XM30PB/2.6 XM30PB/4.0 XM30PB/5 XM30PB/8 XM30PB/10 XM30PB/12 S125GJ/20 S125GJ/20 S125GJ/32 S125GJ/50 S125GJ/50 S125GJ/63 S125GJ/100 S125GJ/100 S125GJ/125 S250PE/160 S250PE/250 S250PE/250 S250PE/250 S400PE/400 S400PE/400 S400PE/400 CA7-9 CA7-9 CA7-9 CA7-16 CA7-16 CA7-16 CA7-30 CA7-30 CA7-30 CA7-30 CA7-30 CA7-43 CA7-43 CA7-43 CA7-72 CA7-72 CA6-105 CA6-105 CA6-140 CA6-170 CA6-210 CA6-210 CA6-300 CA6-420 Notes: · Thermal or electronic overload relays may be used. · XM30PB combinations can be replaced with S125GJ/20 and CA7-30 if required. · Combinations based on the thermal overload relay tripping before the circuit breaker at overload currents up to the motor locked rotor current. Terasaki Combinations Overload Relay CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-45 CT 7-45 CT 7-45 CT 7-75 CT 7-75 CT 7-100 CEF 1-11/12 CEF 1-11/12 CEF 1-11/12 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 Thermal Setting (A) 1.0 - 1.6 1.0 - 1.6 1.6 - 2.4 2.4 - 4.0 2.4 - 4.0 4.0 - 6.0 6.0 - 10 6.0 - 10 10 - 16 10 - 16 16 - 24 18 - 30 30 - 45 30 - 45 45 - 60 60 - 75 70 - 90 20 - 180 20 - 180 20 - 180 160 - 400 160 - 400 160 - 400 160 - 400 Sprecher + Schuh Combinations KT7 Circuit Breaker KTA7-25S-1A KTA7-25S-1.6A KTA7-25S-2.5A KTA7-25S-2.5A KTA7-25S-4A KTA7-25S-6.3A KTA7-25S-6.3A KTA7-25S-10A KTA7-25H-16A KTA7-25H-16A KTA7-45H-20A KTA7-45H-32A KTA7-45H-45A KTA7-45H-45A KTA3-100-63A KTA3-100-90A KTA3-100-90A KTA3-160S-100A KTA3-160S-160A KTA3-160S-160A KTA3-250S-200A KTA3-250S-250A KTA3-400S-320A KTA3-400S-400A Contactor CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-9 CA7-12 CA7-16 CA7-23 CA7-30 CA7-37 CA7-43 CA7-60 CA7-72 CA7-85 CA6-110 CA6-140 CA6-180 CA6-210 CA6-250 CA6-300 CA6-420 Q-Pulse Id: TMS196 Beyond the StandardTM 26/11/2012 page 49 Page 89 of 382 SECTION 4 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA MOTOR STARTING TYPE 2 CO-ORDINATION Short-Circuit Co-Ordination DOL Motor Starting Table Type `2' Terasaki MCCB's & Sprecher + Schuh KT7's DOL starting 85 kA @ 400/415 V to AS/NZS 60947.4.1 TYPE 2 85 kA Motor Size (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 Approx. amps @ 400/415 V (A) 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 21 28 34 40 55 66 80 100 130 155 200 225 270 361 Terasaki Combinations MCCB Contactor XM30PB/1.4 XM30PB/2 XM30PB/2.6 XM30PB/4.0 XM30PB/5 XM30PB/8 XM30PB/10 XM30PB/12 H125NJ/20 H125NJ/20 H125NJ/32 H125NJ/50 H125NJ/50 H125NJ/63 H125NJ/100 H125NJ/100 H125NJ/160 H160NJ/160 H250PE/250 H250PE/250 H250PE/250 H400NE/400 H400NE/400 H400NE/400 CA 7-9 CA 7-9 CA 7-9 CA 7-16 CA 7-16 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-43 CA 7-43 CA 7-43 CA 7-72 CA 7-72 CA 6-105 CA 6-105 CA 6-210 CA 6-210 CA 6-210 CA 6-210 CA 6-300 CA 6-420 Notes: · Thermal or electronic overload relays may be used. · XM30PB combinations can be replaced with H125GJ/20 and CA7-30 if required. · Combinations based on the thermal overload relay tripping before the circuit breaker at overload currents up to the motor locked rotor current. Terasaki Combinations Overload Relay CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-45 CT 7-45 CT 7-45 CT 7-75 CT 7-75 CT 7-100 CEF 1-11/12 CEF 1-11/12 CEF 1-11/12 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 Thermal Setting (A) 1.0 - 1.6 1.0 - 1.6 1.6 - 2.4 2.4 - 4.0 2.4 - 4.0 4.0 - 6.0 6.0 - 10 6.0 - 10 10 - 16 10 - 16 16 - 24 18 - 30 30 - 45 30 - 45 45 - 60 60 - 75 70 - 90 20 - 180 20 - 180 20 - 180 160 - 400 160 - 400 160 - 400 160 - 400 Sprecher + Schuh Combinations KT7 Circuit Breaker KTA7-25S-1A KTA7-25S-1.6A KTA7-25S-2.5A KTA7-25H-2.5A KTA7-25H-4A KTA7-25H-6.3A KTA7-25H-6.3A KTA7-25H-10A KTA7-45H-16A KTA7-45H-16A KTA7-45H-20A KTA7-45H-32A KTA7-45H-45A KTA7-45H-45A KTA3-100-63A KTA3-100-90A KTA3-100-90A - Contactor CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-12 CA 7-16 CA 7-23 CA 7-30 CA 7-37 CA 7-43 CA7-60 CA7-72 CA7-85 - page 50 Beyond the StandardTM Q-Pulse Id: TMS196 26/11/2012 Page 90 of 382 SECTION 4 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs APPLICATION DATA MOTOR STARTING TYPE 2 CO-ORDINATION Short-Circuit Co-Ordination DOL Motor Starting Table Type `2' Terasaki MCCB's & Sprecher + Schuh KT7's DOL starting 100 kA @ 400/415 V to AS/NZS 60947.4.1 TYPE 2 100 kA Motor Size (kW) 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 Approx. amps @ 400/415 V (A) 1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 21 28 34 40 55 66 80 100 130 155 200 225 270 361 Terasaki Combinations MCCB Contactor H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/20 H125NJ/32 H125NJ/50 H125NJ/50 H125NJ/63 H125-NJ/100 H125-NJ/100 H125-NJ/125 H250-NE/160 H250-NE/250 H250-NE/250 H250-NE/250 H400-NE/400 H400-NE/400 H400-NE/400 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-30 CA 7-43 CA 7-43 CA 7-43 CA 7-60 CA 7-72 CA 7-85 CA 6-95 CA 6-140 CA 6-140 CA 6-180 CA 6-420 CA 6-420 CA 6-420 Notes: · Thermal or electronic overload relays may be used. · Combinations based on the thermal overload relay tripping before the circuit breaker at overload currents up to the motor locked rotor current. Terasaki Combinations Overload Relay CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-24 CT 7-45 CT 7-45 CT 7-45 CT 7-75 CT 7-75 CT 7-100 CEF 1-11/12 CEF 1-11/12 CEF 1-11/12 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 CEF 1-41/42 Thermal Setting (A) 1.0 - 1.6 1.0 - 1.6 1.6 - 2.4 2.4 - 4.0 2.4 - 4.0 4.0 - 6.0 6.0 - 10 6.0 - 10 10 - 16 10 - 16 16 - 24 18 - 30 30 - 45 30 - 45 45 - 60 60 - 75 70 - 90 20 - 180 20 - 180 20 - 180 160 - 400 160 - 400 160 - 400 160 - 400 Sprecher + Schuh Combinations KT7 Circuit Breaker KTA7-25S-1A KTA7-25S-1.6A KTA7-25S-2.5A KTA7-25H-2.5A KTA7-25H-4A KTA7-25H-6.3A KTA7-25H-6.3A KTA7-25H-10A KTA7-45H-16A KTA7-45H-16A KTA7-45H-20A KTA7-45H-32A KTA7-45H-45A KTA7-45H-45A - Contactor CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-9 CA 7-12 CA 7-16 CA 7-23 CA 7-30 CA 7-37 CA 7-43 - Q-Pulse Id: TMS196 Beyond the StandardTM 26/11/2012 page 51 Page 91 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs INSTALLATION INSULATION DISTANCE IN mm (AT 440V AC MAXIMUM) Model E125 S125 S125 S125 H125 L125 S160 S160 S160 H160 L160 E250 S250 S250 S250 H250 H250 L250 E400 S400 S400 S400 S400 H400 H400 L400 L400 E630 S630 S630 Type A B1 B2 C NJ 50 10 10 0 NF 50 10 10 0 NJ 50 10 10 0 GJ 75 45 25 0 NJ 100 80 60 0 NJ 100 80 60 0 NF 50 40 30 0 NJ 50 40 30 0 GJ 100 80 60 0 NJ 100 80 60 0 NJ 100 80 60 0 NJ 50 40 30 0 NJ 50 40 30 0 GJ 100 80 30 0 PE 100 80 60 0 NJ 100 80 60 0 NE 100 80 60 0 NJ 100 80 60 0 NJ 100 80 40 0 CJ 100 80 40 0 NJ 100 80 40 0 GJ 100 80 40 0 GE 100 80 40 0 NJ 120 120 80 0 NE 120 120 80 0 NJ 120 120 80 0 NE 120 120 80 0 NE 120 100 80 0 CE 120 100 80 0 GE 120 100 80 0 D E 25 *(1) 25 *(1) 25 *(1) 25 *(1) 50 *(1) 50 *(1) 25 *(1) 25 *(1) 50 *(1) 50 *(1) 50 *(1) 25 *(1) 25 *(1) 25 *(1) 50 *(1) 50 *(1) 50 *(1) 50 *(1) 30 *(1) 30 *(1) 30 *(1) 30 *(1) 30 *(1) 80 *(1) 80 *(1) 80 *(1) 80 *(1) 80 *(1) 80 *(1) 80 *(1) *Note: (1) Insulate the exposed conductor until it overlaps the moulded case at the terminal, or the terminal cover. SECTION 6 page 78 Beyond the StandardTM Q-Pulse Id: TMS196 26/11/2012 Page 92 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs INSTALLATION TEMPERATURE RATINGS & DERATINGS Calibration Temperature: 45°C MCCB Type E125-NJ S125-NJ S125-GJ Connection Type Front Rear Plug-in H125-NJ L125-NJ Front Rear Plug-in S160-NJ S160-GJ Front Rear Plug-in H160-NJ L160-NJ E250-NJ Front Rear Plug-in Front Rear Plug-in E250-NJ S250-NJ S250-GJ H250-NJ L250-NJ E400-NJ S400-CJ S400-NJ S400-GJ H400-NJ L400-NJ Front Rear Plug-in Front Rear Plug-in Front Rear Front Rear Plug-in Front Rear Plug-in Rating at calibration temperature (50°C) 20A 32A 50A 63A 100A 125A 20A 32A 50A 63A 100A 125A 20A 32A 50A 63A 100A 125A 160A 160A 20A 32A 50A 63A 100A 125A 160A 250A 160A 250A 250A 400A 250A 400A 250A 400A Calibration Temperature: 30°C MCCB Type H250-NJ L250-NJ Connection Type Plug-in Conn. Rating at calibration temperature (30°C) 250A Rated Current (A) 50°C 55°C 60°C 19 18.5 18 31 30.5 30 48 45 43 60 57 55 97 94 90 121 117 113 19 18.5 18 31 30 29 48 47 45 61 59 57 97 95 92 121 118 114 19 18.5 18 31 30 29 48 46 44 61 59 57 97 94 91 121 117 113 156 151 146 156 151 147 19 18.5 18 31 30 29 48 46 44 61 59 57 97 94 91 121 117 113 156 151 146 243 235 227 65°C 17.5 29 41 52 87 109 17.5 28 44 55 89 111 17.5 28 42 55 88 109 141 143 17.5 28 42 55 88 109 141 219 156 151 147 143 244 237 230 223 244 237 230 223 390 380 369 358 243 237 230 223 390 381 371 361 243 237 231 224 392 384 376 368 Rated Current (A) 35°C 40°C 45°C 244 236 225 50°C 55°C 219 209 60°C 65°C 200 190 SECTION 6 MCCB Type S250-PE H250-NE S400-NE S400-GE H400-NE L400-NE Connection Type Front Rear Plug-in Front Rear Plug-in Front Rear Plug-in E630-NE S630-CE S630-GE Front Rear* Q-Pulse Id: TMS196 Rating 250A 250A 250A 400A 250A 400A 250A 400A 630A 30°C 250 35°C 250 40°C 250 Rated Current (A) 45°C 50°C 55°C 250 237.5 225 250 237.5 225 225 200 200 250 250 250 250 250 250 400 400 400 400 400 380 250 250 250 250 400 400 400 400 250 250 250 250 400 400 400 400 630 630 630 630 250 400 250 400 598.5 250 380 250 380 598.5 60°C 200 157.5 225 360 225 360 225 360 567 65°C 200 157.5 200 320 200 320 200 320 504 Beyond the StandardTM 26/11/2012 page 81 Page 93 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology TEMBREAK 2 MCCBs DIMENSIONS E125-NJ, S125-NJ, S125-GJ SECTION 7 8.5(max.) 132 17 8.5 154±1 3P 4P Interpole barrier (removable) Mounting hole 47 HL HL Operating knob CL 154 Front panel t2 24 M8 screw Preparation of conductor ø9 17(max.) max.t5 Drilling plan 3P 4P HL HL 155 134 60 14.5 21.5 90 90 30 30 30 45 75 10 Connector plug 45 8 61 45 106 5.5 164.5 28(max.) M4x0.7 Mounting screw 30 30 M4x0.7 Tapped hole Panel hinge position (hatching area) bottom view HL 100 150 200 100 150 200 90 86 HL 154 Operating knob Front panel t2 Mounting plate (max. t3.2) Drilling plan 3P 4P HL HL 103.5 Panel cutout (Front view) 4P 3P HL 5 132 134 R1 155 8 61 134 155 148 CL 15 Conductor CL overlap max. 16 Pad lock Connector plug 45 ø8.5 15 15 61 52 106 102 30 30 30 Stud can be turned 45°or 90° M4X0.7 Mounting screw 30 60 5.5 164.5 28(max.) CL 30 30 30 30 ø18 M4X0.7 Tapped hole 45 90 Panel cutout dimensions shown give an allowance of 1.5mm around the handle escutcheon. Q-Pulse Id: TMS196 Beyond the StandardTM 26/11/2012 page 85 Page 94 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Miniature circuit breakers Din-T15 series 15 kA, 20 kA, 25 kA MCBs Innovators in Protection Technology 1 n Standards AS/NZS 60947-2 n Current range 6-63 Amp 1, 2, 3 and 4 pole n Sealable and lockable handle n Modular design n Mounts on NC or CD chassis n Industrial applications 1 pole 1 module 1) In (A) Icu (kA) C - Curve 5 - 10 In 6 25 DTCB15106C 10 25 DTCB15110C 13 25 i DTCB15113C 16 25 DTCB15116C 20 25 DTCB15120C 25 25 DTCB15125C 32 20 DTCB15132C 40 20 DTCB15140C 50 15 DTCB15150C 63 15 DTCB15163C 2 pole 2 modules 1) C - Curve In (A) Icu (kA) 5 - 10 In 6 25 i DTCB15206C 10 25 DTCB15210C 13 25 i DTCB15213C 16 25 DTCB15216C 20 25 DTCB15220C 25 25 i DTCB15225C 32 20 i DTCB15232C 40 20 50 15 63 15 i DTCB15240C i DTCB15250C i DTCB15263C 3 pole 3 modules 1) 6 25 10 25 13 25 16 25 20 25 25 25 32 20 40 20 50 15 63 15 DTCB15306C DTCB15310C i DTCB15313C DTCB15316C DTCB15320C DTCB15325C DTCB15332C DTCB15340C DTCB15350C DTCB15363C 4 pole 4 modules 1) 2) 6 25 10 25 13 25 16 25 20 25 25 25 32 20 40 20 50 15 63 15 i DTCB15406C i DTCB15410C i DTCB15413C i DTCB15416C i DTCB15420C i DTCB15425C i DTCB15432C i DTCB15440C i DTCB15450C i DTCB15463C DTCB15 1 pole In (A) 1 P 2 P 3 P 4 P 6 - 63 240 V AC 240/415 V AC 240/415 V AC 240/415 V AC Shock resistance (in x, y, z direction) 20 g with shock duration of 10 ms (minimum 18 shocks) 40 g with shock duration of 5 ms (minimum 18 shocks) Vibration resistance (in x, y, z direction) 3 g in frequency range 10 to 55 Hz (operating time at least 30 mins) according to IEC 60068-2-6 Storage temperature from -55 °C to +55 °C according to VDE 0664 parts 1 and 2 Operating temperature from -25 °C to +55 °C according to VDE 0664 Parts 1 and 2. Use at 400 Hz At 400 Hz the magnetic tripping current is approximately 50 % higher than at AC 50/60 Hz Notes: 1) Refer Section 3 for kA ratings at 240/415 V. The above ratings are at 415 V AC. 2) All poles include overcurrent and short circuit protection. i Available on indent only. The LINE-side is the OFF or bottom of the MCB and connects to CD chassis tee-offs. Q-Pulse Id: TMS196 26/11/2012 Accessories Page Add-on RCD 1 - 28 to 1 - 29 Shunt trip 1 - 36 to 1 - 38 UVT 1 - 39 to 1 - 40 Auxiliary/alarm 1 - 32 to 1 - 35 Padlock bracket 1 - 45 Link bars and terminals 1 - 44 to 1 - 45 Enclosures Section 2 Busbar chassis 2 - 52 Technical data Page Technical data Section 3 Tripping characteristics 3 - 6, 3 - 8 Dimensions 3 - 24 1 - 21 Page 95 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data Din-T 15 15 kA C curve Innovators in Protection Technology 3 Q-Pulse Id: TMS196 26/11/2012 3 - 15 Page 96 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data Text for specifiers Innovators in Protection Technology MCB Series Din-T 6 and 10 n According to AS/NZS 60898 standard n For DIN rail mounting (top hat rail 35 mm) n Grid distance 35 mm n Working ambient temperature from -25 °C up to +50 °C n Approved by CEBEC, VDE, KEMA, IMQ n Lloyd listed n 1 pole is a module of 18 mm wide n Nominal rated currents are: 0.5/1/2/3/4/6/10/13/16/20/25/32/40/50/63 A n Tripping characteristics: B,C,D (B curve Din-T 10 only) n Number of poles: 1 P, 2 P, 3 P, 4 P n The short-circuit breaking capacity is: 6/10 kA, energy limiting class 3 n Terminal capacity from 1 up to 35 mm2 rigid wire or 1.5 up to 25 mm2 flexible wire n Screw head suitable for flat or Pozidrive screwdriver n Can be connected by means of both pin or fork busbars n The toggle can be sealed in the ON or OFF position n Captive locking option n Rapid closing n Both incoming and outgoing terminals have a protection degree of IP 20 and they are sealable n Isolator function thanks to Red/Green printing on the toggle n Maximum voltage between two phases; 440 V~ n Maximum voltage for utilisation in DC current: 48 V 1 P and 110 V 2 P n Two position rail clip n Mechanical shock resistance 40 g (direction x, y, z) minimum 18 shocks 5 ms half-sinusoidal acc. to IEC 60068-2-27 n Vibration resistance: 3 g (direction x, y, z) minimum 30 min. according to IEC 60068-2-6 n Extensions can be added on both left or right hand side Auxiliary contact Shunt trip Undervoltage release Motor operator Panelboard switch n Add-on RCD can be coupled MCB Series Din-T 15 n According to AS/NZS 60947.2 standard n For DIN rail mounting (top hat rail 35 mm) 3 n Working ambient temperature from -25 °C up to +50 °C n 1 pole is a module of 18 mm wide n Nominal rated currents are: 6/10/13/16/20/25/32/40/50/63 A n Tripping characteristic: C n Number of poles: 1 P, 2 P, 3 P, 4 P n Short-circuit capacity is: 15 kA n Terminal capacity from 1 up to 35 mm2 rigid wire or 1.5 up to 25 mm2 flexible wire n Screw head suitable for flat or Pozidrive screwdriver n Can be connected by means of both pin or fork busbars n The toggle can be sealed in the ON or OFF position n Captive locking option n Rapid closing n Both incoming and outgoing terminals have a protection degree of IP 20 and they are sealable n Isolator function thanks to Red/Green printing on the toggle n Maximum voltage between two phases; 440 V~ n Maximum voltage for utilisation in DC current: 48 V 1 P and 110 V 2 P n Two position rail clip n Mechanical shock resistance 40 g (direction x, y, z) minimum 18 shocks 5 ms half-sinusoidal acc. to IEC 60068-2-27 n Vibration resistance: 3 g (direction x, y, z) minimum 30 min. according to IEC 60068-2-6 n Extensions can be added on both left or right hand side Auxiliary contact Shunt trip Undervoltage release Motor operator Panelboard switch n Add-on RCD can be coupled Q-Pulse Id: TMS196 26/11/2012 3 - 19 Page 97 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Din-T MCBs + RCDs Technical data Series Standards (Aust / NZ / International) Tripping characteristics Nominal current A Calibration temperature °C Number of poles (# mod) Neutral pole protected Nominal voltage Un AC 1 P V 3 P/4 P V DC 1 P V DC 2 P V DC Frequency Hz Hz Hz Maximum service voltage Ubmax between two wires V Minimum service voltage Ubmin V Selectivity class (IEC 60898) Isolator application IEC 60947-2 Rated insulation voltage Pollution degree 2 Pollution degree 3 Impulse withstand test voltage Insulation resistance V V kV mOhm Dielectric rigidity kV Vibration resistance (in x, y, z direction) (IEC 77/16.3) Endurance Electrical at Un, In mechanical Utilisation category (IEC 60947-2) Protection degree (outside / inside, in enclosure with door) Self-extinguish degree (according to UL94) Tropicalisation (according to IEC 60068-2 / DIN 40046) °C/RH Operating temperature °C Storage temperature °C Terminal capacity Rigid cable min/max (top) mm2 Flexible cable min*/max (top) mm2 Rigid cable min/max (bottom) mm2 Flexible cable min*/max (bottom) mm2 (* Flexible cable 0.75/1/1.5 mm2 with cable lug) Torque Nm Add-on devices (side add-on) Busbar systems Accessories Auxiliary contacts UVT Shunt trip Motor operator Panelboard switch Pin (top/bottom) Fork (top/bottom) Dimensions, weights, packaging (HxDxW) 86x68xW Weight/mod. Package mm/mod. g mod. Short-circuit capacity AC (kA) IEC 60898 Icn Ics (service) Icu (ultimate) 1 P 2 P 3 P/4 P 1 P 2 P IEC 60947-2 3 P, 4 P Ics (service) NEMA AB1 (120/240V) Short-circuit capacity DC (kA) Icu (ultimate) 1 P 230/400 V 230/400 V 230/400 V 127 V 240 V 415 V 127 V 240 V 415 V 240 V 415 V 440 V 60 V IEC 60947-2 2 P Ics (service) 220 V 125 V 440 V Notes: Refer page 3 - 25 for information on Safe-T MCBs. 1) Poles in series 2) 0.5-4 A/6-25 A/32-40 A/50-63 A 3) 10 (125 V DC) Din-T10 AS/NZS 60898 IEC 60898 B, C, D B6 -63 , C/D 0.5 - 63 30 1/2/3/4 yes 240/415 415 48 110 1) 50/60 DC: mag.trip +40 % 400: mag.trip +50 % 250/440; 53/120 12; 12 3 yes 500 440 6 10,000 2.5 3 g 10,000 20,000 A IP 20/IP 40 V2 +55 °C/95 % RH -25/+55 -55/+55 1/35 0.75/25 1/35 0.75/25 4.5 yes yes yes yes yes yes/yes -/yes yes 18 120 12 AS/NZS 60898 10 10 10 75 % Icn 30 15 4 40 30 15 30 15 10 50 % Icu 30 25 30 100 % Icu Din-T10H AS/NZS 60947-2 IEC 60947-2 C, D 80 up to 125 40 1/2/3/4 Yes 240/415 415 48 110 1) 50/60 DC: mag.trip +40 % 400: mag.trip +50 % 250/440; 53/120 12; 12 yes 500 440 6 10,000 2.5 3 g 4000 20,000 A IP 20/IP 40 V2 +55 °C/95 % RH -25/+55 -55/+55 70 70 - 5 yes yes - 27 210 8 AS/NZS 60947-2 - C 10; D 7.5 4.5 C 15 C 10; D 7.5 B/C 15 C 10; D 7.5 - 100 % Icu - 10 15 100 % Icu Q-Pulse Id: TMS196 26/11/2012 Innovators in Protection Technology Din-T15 AS/NZS 60947-2 IEC 60947-2 C 0.5-63 40 1/2/3/4 Yes 240/415 415 48 110 1) 50/60 DC: mag.trip +40 % 400: mag.trip +50 % 250/440; 53/120 12; 12 yes 500 440 6 10,000 2.5 3 g 4000 20,000 A IP 20/IP 40 V2 +55 °C/95 % RH -25/+55 -55/+55 1/35 0.75/25 1/35 0.75/25 4.5 yes yes yes yes yes yes/yes -/yes yes 18 120 12 AS/NZS 60947-2 50 50/25/20/15 2) 50/50/40/30 2) 50/25/20/15 2) 50/50/40/30 2) 50/25/20/15 2) 50/20/15/10 2) 75 % Icu - 25 30 100 % Icu 3 3 - 23 Page 98 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs + RCDs Technical data Miniature circuit breakers - Din-T 6, 10, 15 / Easy-fit Dimensions in mm. 3 Miniature circuit breakers - Din-T 10H Miniature circuit breakers - Din-T DC 3 - 24 Q-Pulse Id: TMS196 26/11/2012 Page 99 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 1 Miniature circuit breakers Din-T10 series 10 kA MCB Standard AS/NZS 4898 1) Approval No. N17481 Short circuit breaking capacity - 10000 Amps Current range 0.5 - 63 Amps 1, 2, 3 and 4 pole Sealable and lockable handle Modular design Available in curve type B, C and D Mounts on CD chassis (250 A and 355 A) 1 pole 1 module DTCB10 1 pole In (A) 0.5 1 2 3 4 6 10 13 16 20 25 32 40 50 63 C Curve 5-10 In DTCB10105C DTCB10101C DTCB10102C DTCB10103C DTCB10104C DTCB10106C DTCB10110C DTCB10113C DTCB10116C DTCB10120C DTCB10125C DTCB10132C DTCB10140C DTCB10150C DTCB10163C Short circuit capacity 10 kA In (A) 0.5 - 63 1 P 240 V AC 2 P 240/415 V AC 3 P 240/415 V AC 4 P 240/415 V AC Use at DC Short circuit Max voltage 1 P 25 kA 48 V DC 2 P 2) 30 kA 110 V DC 2 pole 2 modules 0.5 1 2 4 6 10 13 16 20 25 32 40 50 63 DTCB10205C DTCB10201C DTCB10202C DTCB10204C DTCB10206C DTCB10210C DTCB10213C DTCB10216C DTCB10220C DTCB10225C DTCB10232C DTCB10240C DTCB10250C DTCB10263C Notes: 1) A range of UL standard MCBs is available on indent. (ref DTCBUL1O_ _ _ C). 2) 2 pole MCB connected in series. The line side is the "OFF" (bottom) side of the MCB, and connects to CD chassis tee-offs. i Available on indent only. Q-Pulse Id: TMS196 26/11/2012 Page 100 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 1 Miniature circuit breakers Din-T10 series 10 kA MCB (cont.) 3 pole 3 modules In (A) 0.5 1 2 4 6 10 13 16 20 25 32 40 50 63 C Curve 5-10 In i DTCB10305C i DTCB10301C DTCB10302C DTCB10304C DTCB10306C DTCB10310C i DTCB10313C DTCB10316C DTCB10320C DTCB10325C DTCB10332C DTCB10340C DTCB10350C DTCB10363C DTCB10 1 - 4 pole types 4 pole 4 modules 1) 6 DTCB10406C 10 DTCB10410C 13 i DTCB10413C 16 DTCB10416C 20 DTCB10420C 25 DTCB10425C 32 DTCB10432C 40 DTCB10440C 50 DTCB10450C 63 DTCB10463C Notes: 1) All poles include overcurrent and short circuit protection. i Available on indent only. Q-Pulse Id: TMS196 26/11/2012 Page 101 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Characteristics according to BS EN 60898 Miniature Circuit Breakers are intended for the protection of wiring installations against both overloads and short-circuits in domestic or commercial wiring installations where operation is possible by uninstructed people Rated short-circuit breaking capacity (Icn) Is the value of the short-circuit that the MCB is capable of withstanding in the following test of sequence of operations: O-t-CO. 3 Tripping characteristic curves After the test the MCB is capable, without maintenance, to withstand a dielectric strength test at a test voltage of 900 V. Moreover, the MCB shall be capable of tripping when loaded with 2.8 In within the time corresponding to 2.55 In but greater than 0.1s. Service short-circuit breaking capacity (Ics) Is the value of the short-circuit that the MCB is capable of withstanding in the following test of sequence of operations: O-t-CO-t-CO. After the test the MCB is capable, without maintenance, to withstand a dielectric strength test at a test voltage of 1500 V. Moreover, the MCB shall not trip at a current of 0.96 In. The MCB shall trip within 1h when current is 1.6 In. Magnetic release An electromagnet with plunger ensures instantaneous tripping in the event of short-circuit. The NHP Din-T range has 3 different types, following the current for instantaneous release: types B, C and D curve. Icn Test (A) current Tripping time Applications B 3 x In 5 x In 0.1<t<45 s (In32 A) 0.1<t<90 s (In>32 A) t<0.1 s Only for resistive loads eg: · electrical heating · water heater · stoves. C 5 x In 0.1<t<15 s (In32 A) Usual loads such as: 10 x In 0.1<t<30 s (In>32 A) · lighting · socket outlets t<0.1 s · small motors D 10 x In 0.1<t<4 s(**) (In32 A) Control and protection of 20 x In 0.1<t<8 s (In>32 A) circuits having important transient inrush currents t<0.1 s (large motors) Thermal release The release is initiated by a bimetal strip in the event of overload. The standard defines the range of releases for specific overload values. Reference ambient temperature is 30 °C. O - Represents an opening operation C - Represents a closing operation followed by an automatic opening. t - Represents the time interval between two successive short-circuit operations: 3 minutes. The relation between the rated short-circuit capacity (Icn) and the rated service short-circuit breaking capacity (Ics) shall be as follows: Icn (A) 6000 > 6000 10000 > 10000 Ics (A) 6000 0.75 Icn min. 6000 0.75 Icn min. 7500 In both sequences all MCBs are tested for emission of ionized gases during short-circuit (grid distance), in a safety distance between two MCBs of 35 mm when devices are installed in two different rows in the enclosure. This performance allows the use of any NHP/Terasaki enclosure. Test current 1.13 x In 1.45 x In 2.55 x In Tripping time t 1 h (In 63 A) t 2 h (In > 63 A) t < 1 h (In 63 A) t < 2 h (In > 63 A) 1 s < t < 60 s (In 32 A) 1 s < t < 120 s (In >32 A) Q-Pulse Id: TMS196 26/11/2012 Page 102 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Tripping curves according to EN 60898 The following tables show the average tripping curves of the Terasaki Din-T MCBs based on the thermal and magnetic characteristics. Curve C 3 Q-Pulse Id: TMS196 26/11/2012 Page 103 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Din-T MCBs Technical data Din-T 10 10 kA C curve Innovators in Protection Technology 3 Q-Pulse Id: TMS196 26/11/2012 Page 104 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Influence of ambient air temperature on the rated current The maximum value of the current which can flow through an MCB depends on the nominal current of the MCB, the conductor cross-section and the ambient air temperature. The values shown in the table below are for devices in free air. 3 For devices installed with other modular devices in the same switchboard, a correction factor (K) shall be applied relative to the mounting situation of the MCB, the ambient temperature and the number of main circuits in the installation. The thermal calibration of the MCBs was carried out at an ambient temperature of 30 °C. Ambient temperatures different from 30 °C influence the bimetal and this results in earlier or later thermal tripping. No of devices K 1) 2 or 3 0.9 4 or 5 0.8 6 or 9 0.7 > 10 0.6 Calculation example Within a distribution board consisting of eight 2 Pole, 16 A, `C' curve type MCBs, with an operating ambient temperature of 45 °C, which is the highest temperature the MCB can operate at without unwanted tripping? Calculation The correction factor K = 0.7, for use in an eight circuit installation: 16 A x 0.7 = 11.2 A As the MCB is working at 45 °C it shall be given another factor (90 % = 0.9): In at 45 °C = In at 30 °C x 0.9 = 11.2 A x 0.9 = 10.1 A. Note: 1) Applicable for MCBs working at maximum rated currents. Q-Pulse Id: TMS196 26/11/2012 : 1P (single pole) : mP (multi-pole) Page 105 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Din-T MCBs Technical data Innovators in Protection Technology Effects of frequency on the tripping characteristic All the MCBs are designed to work at frequencies of 50-60 Hz, therefore to work at different values, consideration must be given to the variation of the tripping characteristics. The thermal tripping does not change with variation of the frequency but the magnetic tripping values can be up to 50 % higher than the ones at 50-60 Hz. Limitation curves Let-through energy I2t The limitation capacity of an MCB in short-circuit conditions, is its capacity to reduce the value of the let-through energy that the short-circuit would be generating. Peak current Ip Is the value of the maximum peak of the short-circuit current 3 limited by the MCB. Tripping current variation 60 Hz 1 100 Hz 1.1 200 Hz 1.2 300 Hz 1.4 400 Hz 1.5 Power losses The power losses are calculated by measuring the voltage drop between the incoming and the outgoing terminals of the device at rated current. Power loss per pole In Voltage drop Energy loss (A) (V) (W) 0.5 2.230 1.115 1 1.270 1.272 2 0.620 1.240 3 0.520 1.557 4 0.370 1.488 6 0.260 1.570 8 0.160 1.242 10 0.160 1.560 13 0.155 2.011 16 0.162 2.586 20 0.138 2.760 25 0.128 3.188 32 0.096 3.072 40 0.100 4.000 50 0.090 4.500 63 0.082 5.160 80 0.075 6.000 100 0.075 7.500 125 0.076 9.500 Resistance (mOhm) 4458.00 1272.00 310.00 173.00 93.00 43.60 19.40 15.60 11.90 10.10 6.90 5.10 3.00 2.50 1.80 1.30 0.90 0.75 0.60 See following pages Q-Pulse Id: TMS196 26/11/2012 Page 106 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs Technical data Use of standard MCB for DC use For MCBs designed to be used in alternating current but used in installations in direct current, the following should be taken into consideration: For protection against overloads it is necessary to connect 3 the two poles to the MCB. In these conditions the tripping characteristic of the MCB in direct current is similar to alternating current. Use in DC selection table For protection against short-circuits it is necessary to connect the two poles to the MCB. In these conditions the tripping characteristic of the MCB in direct current is 40% higher than the one in alternating current. Use of special MCB Din-T DC for DC use. (UC = Universal current) For MCBs designed to work in both alternating and direct current, it is necessary to respect the polarity of the terminals since the device is equipped with a permanent magnet. Series Din-T 10 Rated current (A) 0.5....63 A 48 V 1 pole Icu (kA) 25 110 V 2 poles in series Icu (kA) 30 250 V 1 pole Icu (kA) - 440 V 2 poles in series Icu (kA) - Installation of Din-T DC MCBs in direct current Q-Pulse Id: TMS196 26/11/2012 Page 107 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Din-T MCBs Technical data Text for specifiers MCB Series Din-T 10 According to EN 60898 standard For DIN rail mounting according to DIN EN 50022; EN 50022; future EN 60715; IEC 60715 (top hat rail 35 mm) Grid distance 35 mm Working ambient temperature from -25 °C up to +50 °C Approved by CEBEC, VDE, KEMA, IMQ. 1 pole is a module of 18 mm wide Nominal rated currents are: 0.5/1/2/3/4/6/10/13/16/20/25/32/40/50/63 A Tripping characteristics: B,C,D (B curve Din-T 10 only). Number of poles: 1 P, 1 P+N, 2 P, 3 P, 3 P+N, 4 P The short-circuit breaking capacity is: 6/10k A, energy limiting class 3 Terminal capacity from 1 up to 35 mm2 rigid wire or 1.5 up to 25 mm2 flexible wire. Screw head suitable for flat or Pozidrive screwdriver Can be connected by means of both pin or fork busbars The toggle can be sealed in the ON or OFF position Rapid closing Both incoming and outgoing terminals have a protection degree of IP 20 and they are sealable Isolator function thanks to Red/Green printing on the toggle. Maximum voltage between two phases; 440 V~ Maximum voltage for utilisation in DC current: 48 V 1 P and 110 V 2 P Two position rail clip Mechanical shock resistance 40 g (direction x, y, z) minimum 18 shocks 5 ms half-sinusoidal acc. to IEC 60068-2-27 Vibration resistance: 3 g (direction x, y, z) minimum 30 min. according to IEC 60068-2-6 Extensions can be added on both left or right hand side Auxiliary contact Shunt trip Undervoltage release Motor operator Panelboard switch Add-on RCD can be coupled. Innovators in Protection Technology 3 Q-Pulse Id: TMS196 26/11/2012 Page 108 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Notes Din-T MCBs Technical data Series Din-T10 AS/NZS 4898 Standards (Aust / NZ / International) IEC 60898 Tripping characteristics B, C, D Nominal current A B(6-63), C/D(0.5-63) Calibration temperature °C 30 Number of poles (# mod) Neutral pole protected 1/2/3/4 yes Nominal voltage Un AC 1 P V 240/415 Frequency 3 P/4 P DC 1 P 1) 2 P (in series) 1) V 415 V DC 48 V DC 110 Hz 50/60 Hz DC: magn.trip +40% Hz 400: magn.trip +50% Maximum service voltage Ubmax between two wires V 250/440; 53/120 Minimum service voltage Ubmin Selectivity class (IEC 60898) Isolator application IEC 60947-2 V 12; 12 3 yes Rated insulation voltage Pollution degree 2 V 500 Pollution degree 3 V 440 Impulse withstand test voltage kV 6 Insulation resistance mOhm 10,000 Dielectric rigidity kV 2.5 Vibration resistance (in x, y, z direction) (IEC 77/16.3) 3 g Endurance Electrical at Un, In 10,000 mechanical 20,000 Utilisation category (IEC 60947-2) A Protection degree (outside / inside, in enclosure with door) Self-extinguish degree (according to UL94) Tropicalisation (according to IEC 60068-2 / DIN 40046) °C/RH Operating temperature °C Storage temperature °C IP 20/IP 40 V2 +55 °C/95 % RH -25/+55 -55/+55 Terminal capacity Rigid cable min/max (top) mm2 1/35 Flexible cable min*/max (top) Rigid cable min/max (bottom) mm2 0.75/25 mm2 1/35 Flexible cable min*/max (bottom) mm2 0.75/25 (* Flexible cable 0.75/1/1.5 mm2 with cable lug) Torque Nm 4.5 Add-on devices Auxiliary contacts yes (side add-on) UVT yes Shunt trip yes Motor operator yes Panelboard switch yes Busbar systems Pin (top/bottom) yes/yes Fork (top/bottom) -/yes Accessories yes Dimensions, weights, packaging (HxDxW) 86x68xW mm/mod. 18 Weight/mod. g 120 Package mod. 12 Short-circuit capacity AC (kA) AS/NZS 4898 IEC 60898 Icn Ics (service) 1 P 2 P 3 P/4 P 230/400 V 230/400 V 230/400 V 10 10 10 75 % Icn Icu (ultimate) 1 P 127 V 30 240 V 15 IEC 60947-2 415 V 4 2 P 127 V 40 240 V 30 415 V 15 3 P, 4 P 240 V 30 415 V 15 440 V 10 Ics (service) 50 % Icu NEMA AB1 (120/240V) 30 Short-circuit capacity DC (kA) Icu (ultimate) 1 P 60 V 25 IEC 60947-2 220 V - 2 P 125 V 30 Ics (service) 440 V 100 % Icu Refer pages 3 - 23, 24 for information on SAFE-T MCBs. 1) Preferred values of rated control supply voltage (IEC 60947 - 2): 24 V, 48 V, 110 V, 125 V, 250 V 2) 0.5-4 A/6-25 A/32-40 A/50-63 A 3) 10 (125 V DC) Innovators in Protection Technology 3 4) 10 (250 V DC) 5) On request. Q-Pulse Id: TMS196 26/11/2012 Page 109 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Innovators in Protection Technology Din-T MCBs + RCDs Technical data Miniature circuit breakers - Din-T 10 Dimensions in mm. 3 Q-Pulse Id: TMS196 26/11/2012 Page 110 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Miniature circuit breakers Din-Safe single pole width residual current circuit breaker (RCBO) 10 kA Innovators in Protection Technology 1 n Standards AS/NZS 61009 n Approval N17482 n One module wide (18 mm) n Short circuit, overcurrent and earth leakage protection n Short circuit protection, 10 kA n Sensitivity 30 mA, 10 mA n DIN rail mount n Suits NC or CD chassis n Type `A' residual current device n 240 V AC Trip sensitivity 10 mA 30 mA Amp rating (A) 6 10 16 20 25 32 40 6 10 16 20 25 32 40 Cat. No 1)2) i DSRCBH0610A DSRCBH1010A DSRCBH1610A DSRCBH2010A i DSRCBH2510A i DSRCBH3210A i DSRCBH4010A DSRCBH0630A DSRCBH1030A DSRCBH1630A DSRCBH2030A DSRCBH2530A DSRCBH3230A DSRCBH4030A Application The Din-Safe single pole width residual current circuit breaker will fit the standard Din-T chassis for use in NHP panelboards. The design makes it possible to provide an MCB complete with earth leakage protection in an 18 mm wide module, which allows a greater number of devices to be fitted into a distribution board. Connection diagram Operation This unit combines the overload and short circuit protection of an MCB with earth leakage protection of an RCD. The unit occupies one, sub- circuit (one pole) of the distribution board and provides single phase protection against overload, short circuit and earth leakage current. The MCB element provides thermal and magnetic tripping protection which is rated to 6 kA prospective fault current. The RCD element of the device provides core-balance detection of the difference between the active and neutral currents and amplification to provide high sensitivity. The rated residual operating current (In) is 30 mA. The white earth reference cable, in case of loss of supply neutral, ensures the device will continue to provide earth leakage protection and will operate normally upon detection of an earth leakage current. Dimensions (mm) Accessories Padlock bracket Link bars and terminals Enclosures Page 1 - 45 1 - 44 to 1 - 45 Section 2 Technical data Tripping characteristics Technical data / wiring Page Section 3 Section 3 Notes: 1) Neutral not switched. 2) Will not accept Din-T side mounting accessories. 30 mA tripping characteristics: 0.5 x IDn = no tripping, 1 x IDn = T <300 mS 2 x IDn = T <150 mS, 5 x IDn = T <40 mS Nuisance tripping may be experienced in VFD and motor starting applications refer NHP. i Available on indent only. Q-Pulse Id: TMS196 26/11/2012 1 - 25 Page 111 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4.2 SURGE PROTECTION & FUSES Critec TDS-180-4S-277 Surge Diverter Critec TDF-10A-240V Surge Reduction Filter Polyphaser Corp IS-50NX-C2 Surge Protection Unit NHP 63A Fuse + 100A Fuse Holder Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 112 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Detailed Specifications for ERICO's TDS-DINLINE SURGE DIVERTER TDS180-4S Applications Features Lightning transients and surges are a major cause of expensive electronic equip- · Robust against abnormal over-voltage ment failure and business disruption. Damage may result in loss of computers, data and communications, loss of revenue, and loss of profits. The new TDSDINLINE family of surge diverters and filters offer economical and reliable · UL1449 Edition 2 compliant protection from power transients in even the most strenuous applications. · Single phase primary protection for Transient Discriminating Technology (TDS) introduces the first quantum leap in transient suppression technology for mains powered equipment. It offers a new medium exposure sites or secondary protection applications level of safety and reliability, yet retains optimum protection levels critical for electronic equipment. TDS is an active frequency based device that discriminates between the slower mains voltages and the higher speed transients. When · Single mode protection, configurable to Ph-N, Ph-E or N-E protection transient frequencies are detected the patented TDS "Quick-Switch" technology "switches in" robust protection devices to limit the transient to safe levels. The frequency discrimination circuit controlling the TDS "Quick-Switch" ensures that · 35mm DIN rail mount, DIN 43 880 profile matches common MCBs the device is virtually immune to the effects of the 50/60Hz sustained overvoltages, allowing fault voltages of up to 480Vrms without degradation, and · 72mm width compact design fits into providing over-voltage robustness in excess of the demanding new and emerging most switch and distribution boards standards. TDS technology is essential for any site where abnormal over-voltages can occur or where the possible catastrophic failure of traditional technologies due to over- · Electronic status indicator ideal for poorly illuminated locations voltage events can not be tolerated. · Long Service life The TDS180-4S unit provides this technology in a single mode shunt-only, 72mm width module. Its unique design allows it to be configured for Ph-N or Ph-E or · Optional retrofittable TDS Alarm N-E applications. Relay for remote alarms Rated to a surge capacity of 80kA (8/20µs), internally 160kA of surge material is provided for additional robustness and to provide long service life. The unit is designed for sites with a medium risk of transients or for secondary protection applications. For the protection of high exposure sites or critical equipment higher surge rated TDS DINLINE units, or TDS MOVTECTM should be installed. Q-Pulse Id: TMS196 26/11/2012 Page 113 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Detailed specifications for ERICO's TRANSIENT DISCRIMINATING FILTER, TDF-10A SERIES Applications Features Lightning transients and surges are a major cause of expensive electronic · Compact design fits into most distribution equipment failure and business disruption. Damage may result in loss of boards and motor control centres computers, data commmunications, loss of revenue, and loss of profits. The new Transient Discriminating FilterTM family of TVSS devices offer · High efficiency filtering - ideal for the economical and reliable protection from power transients with the conven- protection of switched mode power ience of easy installation on 35mm DIN rail mountings. supplies from large dv/dt and di/dt transients · Three modes of protection L-N, L-G, N-G The TDF series has been specifically designed for process control applica- tions to protect the switched mode power supply units on devices such as · 35mm DIN rail mount - DIN 43 880 PLC controllers, SCADA systems and motor controllers. Units are avail- profile matches common MCB's able for 3A, 10A and 20A loads and in a range of clamping voltages including 30V, 150V, 275V. The range is intended for use in conjunction · LED indication and opto-isolated output with ERICO's Universal Transient Barrier UTB's to provide a coordinated for remote status monitoring approach to protection of both the power and data control circuits. · Transient Discriminating Technology ensures safe operation during abnormal The TDF is a series connected single phase surge filter providing an aggregate surge capacity of 50kA (8/20µs) - 20kA L-N & L-G and 10kA N-G. The space efficient low pass filter, provides some 65dB of attenua- over-voltage events · UL1449 Edition 2 recognized tion to voltage transients. Not only does this reduce the residual let through voltage, but it helps further reduce the steep rates of rise of voltage and current providing superior protection for sensitive electronic equipment. · Large 50kA surge capacity provides a high level of protection and long operational life · 5 year limited warranty Q-Pulse Id: TMS196 26/11/2012 Page 114 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual PROCESS CONTROL TVSS PROTECTION SPECIFICATIONS Operation: Models available Nominal line voltage Max Continuous Operating Voltage MCOV Max Load Current Input frequency Earth leakage current Protection: Max aggregate surge rating Protection modes Max surge current/mode L-N L-G N-G SPD circuit description Filter: Inductor Capacitor type Attenuation @100kHz L-N Performance: UL1449 SVR L-N ANSI/IEEE C62.41 Cat B3 - 500A ringwave Cat C1 - 3kA, 8/20µs Alarms and Indicators: Protection status indication Physical Data: Dimensions(W x D x H) Weight Enclosure material Connection means Wire size Mounting method Enclosure style Environmental rating Opearting temperature Humidity Surface finish Warranty Test standards: Approvals Surge rated to meet TDF-10A-120V 120VAC/125VDC 170Vrms 10A 50/60Hz <0.2mA TDF-10A-240V 240VAC 340Vrms 50kA 8/20µs L-N, L-G and N-G 20kA 8/20µs 20kA 8/20µs 10kA 8/20µs Series low pass LC filter Transient Discriminating Technology Thermal fusing Ferrite cored X & Y grade interference suppression polypropylene film 65dB 500V 22V 262V 700V 28V 481V Red LED, On = OK. Opto-isolated output 144mm x 88mm x x70mm 750g (approx) Flame Retardant UL94V-O Screw terminals 1.0mm2 - 6.0mm2 DIN T35 Rail DIN 43880 IP20 -30oC to +55oC 0-90% Spark eroded finish 5 years UL1449 Ed 2, UL1283 recognised, CSA22.2 C-Tick AS3260 ANSI/IEEE C62.41 Cat A, Cat B, Cat C AS/NZS 1768-1991 Cat A, B, C Part Number Description TDF-10A-120V 120V 1 phase, 50kA 8/20µs, 10A series TVSS protector TDF-10A-240V 240V 1 phase, 50kA 8/20µs, 10A series TVSS protector tdf10a.pm5 Q-Pulse Id: TMS196 26/11/2012 Page 115 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 116 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 117 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual TDS-DINLINE SURGE DIVERTER TDS180-4S SPECIFICATIONS 100 Operation: Nominal input voltage Input frequency Max. permissible abnormal over-voltage Power systems Earth leakage current Protection: Modes Let through voltage @ 3kA 8/20µs Let through voltage @ 20kA 8/20µs Surge rating 8/20µs Surge rating 10/350µs Energy rating MultipulseTM capability Aggregate surge material Alarms and Indicators: Protection status indication Alarm contacts Physicals: Environmental rating Operating conditions Enclosure style Dimensions (W x D x H) Weight Encapsulation Enclosure material Surface finish Wiring terminals Warranty Test standards: Approvals 10 Surge rated to meet 1 0.1 1 20 1000 Number of Impulses 10000 220 -277 Vrms 50/60 Hz 480 Vrms TN-C, TN-S, TN-C-S (MEN), TT <2mA Ph-N, Ph-E or N-E <720V <910V 80kA 16kA 3840J Yes 160kA 8/20µs Two, electronic. On = OK User configurable, with optional TDS-AR IP20 -35 to +55°C, 0-90% humidity DIN 43880 72 x 88 x 70mm 350g (approx.) Shockguard Flame Retardent UL94V-0 Spark eroded finish Accepts up to 6mm² 5 years UL1449 Edition 2 AS 3260, IEC 950 Certificate of suitability, Electricity Regulator ANSI/IEEE C62.41-1991 Cat A, Cat B, Cat C. ANSI/IEEE C62.45-1987 Life cycle testing. AS/NZS 1768-1991 Cat A, Cat.B, Cat C. BS 6651:1992 Cat A, Cat B. IEC801-5 Installation Class 5. IEC 61643-1 Note: Other operating voltages and frequencies are available on application. For specifications on other DINLINE products, refer to relevant Specifications Sheet. Exceeding nominal operating voltage while transient events occur may affect product life. TDS, MULTIPULSE, PROLINE, CRITEC, MOVTEC, DINLINE and SURGE REDUCTION FILTER are trademarks of ERICO. Due to a policy of continual product development, specifications are subject to change without notice. © Copyright 1998 Model Number TDS180-4S-277 Description TDS 277V 80KA SURGE SUPPRESSOR Impulse Magnitude (kA 8/20µs) TDS180.PM5 ISSUE 2.0 Q-Pulse Id: TMS196 26/11/2012 Page 118 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4.3 CONTROL DEVICES Critec DAR-275V Surge Diverter Relay Crompton Instruments 252-PSGW Phase Failure Relay Finder - 38.51 24VDC Pump Run Relay Sprecher & Schuh CS7C-40E24V Pump Relay c/w CS7-PV-22 Pump Relay Auxiliary Sprecher & Schuh CS7C-22E24V Pump Relay Multitrode MTR Level Relay Multitrode 0.2/1-`x' Level Probe Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 119 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ÝÎ×ÌÛÝ ÌÜÍñÌÜÍëðñÜßÎñÌÜÍ ÍÝ Ì®¿²-·»²¬ Ü·-½®·³·²¿¬·²¹ Í«°°®»--±® ¿²¼ Ü×ÒÔ×ÒÛ ß´¿®³ λ´¿§ ú Í«®¹» ݱ«²¬»® ß-·¿ñß«-¬®¿´·¿ Û«®±°» Ô¿¬·² ß³»®·½¿ Ò±®¬¸ ß³»®·½¿ ÌÜÍñÌÜÍëð -»®·»- ±ºº»®- ½±³°¿½¬ ÌÊÍÍ ©·¬¸ ÌÜ Ì»½¸²±´±¹§ ·² Ü×Ò »²½´±-«®»- ̸» Ü×ÒÔ×ÒÛ ß´¿®³ λ´¿§ øÜßÎ÷ ·- «-»¼ ©·¬¸ ¬¸» ¿¾±ª» ©¸»®» ¿´¿®³ ½±²¬¿½¬- ¿®» ®»¯«·®»¼ º±® ®»³±¬» -·¹²¿´·²¹ ̸» ÌÜÍóÍÝ Í«®¹» ݱ«²¬»® °®±ª·¼»- ¿ ²±²ó®»-»¬¬¿¾´» ®»½±®¼ ±º ¬¸» ²«³¾»® ±º -«®¹»- ¼·ª»®¬»¼ ̸» ÌÜÍ «²·¬- ¿®» ½±³°¿½¬ íë³³ Ü×Ò ³±«²¬·²¹ ÌÊÍÍ ¼»ª·½»-ô ·¼»¿´ º±® ·²-¬¿´´¿¬·±² ·²¬± »´»½¬®·½¿´ °¿²»´- ±® »¯«·°³»²¬ò ̸» ÌÜÍ «²·¬ °®±¬»½¬- ¿ -·²¹´» ³±¼» ©¸·´» ¬¸» ÌÜÍëð °®±¬»½¬- ÔóÒô ÔóÙ ¿²¼ ÒóÙ -·³«´¬¿²»±«-´§ò ̸» ÜßÎ øÜ×ÒÔ×ÒÛ ß´¿®³ λ´¿§÷ ½¿² ¾» ½±²²»½¬»¼ ¬± ¬¸» ÌÜÍ ±® ÌÜÚ «²·¬- ¬± °®±ª·¼» °±¬»²¬·¿´ º®»» ½¸¿²¹»ó±ª»® ¿´¿®³ ½±²¬¿½¬-ò Ó±¼»´ ׬»³ Ò«³¾»® º±® Û«®±°» Ò±³·²¿´ ʱ´¬¿¹» ˲ Ó¿¨ò ݱ²¬ò Ѱ»®¿¬·²¹ ʱ´¬¿¹» ˽ ͬ¿²¼ó±ºº ʱ´¬¿¹» Ú®»¯«»²½§ Ѱ»®¿¬·²¹ Ý«®®»²¬ à ˲ Ó¿¨ò Ü·-½¸¿®¹» Ý«®®»²¬ ׳¿¨ ׳°«´-» Ý«®®»²¬ ×·³° ß¹¹®»¹¿¬» Í«®¹» ο¬·²¹ Ю±¬»½¬·±² Ó±¼» Ì»½¸²±´±¹§ ʱ´¬¿¹» Ю±¬»½¬·±² Ô»ª»´ ˰ à ëððß èñîðk- øËÔ ÍÊÎ÷ à Ý¿¬ Þíô íµß èñîðkà îðµß èñîðkͬ¿¬«- Ü·³»²-·±²- É»·¹¸¬ Û²½´±-«®» ݱ²²»½¬·±² Ó±«²¬·²¹ Þ¿½µó«° Ѫ»®½«®®»²¬ Ю±¬»½¬·±² Ì»³°»®¿¬«®» Ø«³·¼·¬§ É¿®®¿²¬§ ß°°®±ª¿´- Í«®¹» כּ¼ ¬± Ó»»¬ Í»» °¿¹» ëê º±® -½¸»³¿¬·½ ¼·¿¹®¿³-ò ÌÜÍïìð îÍ îéé ÌÜÍïèð ìÍ îéé ÌÜÍëð îìð ÜßÎîéëÊ éððíðð éððéïð éððíðë éððçðð îìðÊ îìðÊ îìðÊ øïи îÉõÙ÷ ïïðÊ ¿²¼ îìðÊ íìðÊ íìðÊ íìðÊ îéëÊ ìèðÊ ìèðÊ ìèðÊ îéëÊ ëðñêðØ¦ ëðñêðØ¦ ëðñêðØ¦ ëðñêðØ¦ î³ß ì³ß î³ß îð³ß ìðµß èñîðk èðµß èñîðk îðµß èñîðk ÔóÙ îðµß èñîðk- ÔóÒ ïðµß èñîðk- ÒóÙ èµß ïðñíëðk ïêµß ïðñíëðk èðµß èñîðk ïêðµß èñîðk Í·²¹´» Í·²¹´» ÔóÒô ÔóÙ ú ÒóÙ ÌÜ Ì»½¸²±´±¹§ ÔóÒ èððÊ èððÊ êððÊ äéëðÊ äéîðÊ äéððÊ äçêðÊ äçïðÊ Ù®»»² ÔÛÜò ѲãÑÕò ×-±´¿¬»¼ ±°¬±ó½±«°´»® ±«¬°«¬øï÷ λ¼ñÙ®»»² ÔÛÜ-ò ݸ¿²¹»ó±ª»® ½±²¬¿½¬øî÷ îÓò ìÓò îÓò çð³³ ¨ êè³³ ¨ íê³³ çð³³ ¨ êè³³ ¨ éî³³ çð³³ ¨ êè³³ ¨ íê³³ øíòë ¨ îòê ¨ ïòì÷ øíòë ¨ îòê ¨ îòè÷ øíòë ¨ îòê ¨ ïòì÷ ø»¨½´«¼·²¹ ÝÌ÷ ðòîµ¹ øðòìì´¾÷ ðòíëµ¹ øðòéé´¾÷ ðòîµ¹ øðòìì´¾÷ Ü×Ò ìí èèðô ËÔçìÊó𠬸»®³±°´¿-¬·½ô ×Ð îð øÒÛÓßóï÷ ï³³î ¬± ê³³î øýïèßÉÙ ¬± ýïð÷ íë³³ ¬±° ¸¿¬ Ü×Ò ®¿·´ ïêóíîßò λº»® ¬± ·²¬¿´´¿¬·±² ·²¬®«½¬·±² óíëpÝ ¬± õëëpÝ øóíïpÚ ¬± õïíïpÚ÷ ðû ¬± çðû ë §»¿®- ËÔ ïììçô ÝóÌ·½µ ËÔ ïììçô ÝÍßîîòî ÝÍßîîòî ßÍ íîêðô ×ÛÝ çëð ÝÛô ÝóÌ·½µô ÒÑÓ ÝóÌ·½µô ßÍ íîêðô ÝÛ ßÒÍ×ñ×ÛÛÛ Ýêîòìïóïççï Ý¿¬ ßô Ý¿¬ Þô Ý¿¬ Ý ßÒÍ×ñ×ÛÛÛ Ýêîòìïóïççï ÌÜÝ ÍÝ éðîïëð Ó¿¨·³«³ ½±«²¬ çççç Ò±²ó®»-»¬¬¿¾´» øï÷ Ѱ¬±ó½±«°´»® ±«¬°«¬ ½¿² ¾» ½±²²»½¬»¼ ¬± ÜßÎîéëÊ ¬± °®±ª·¼» Ú±®³ Ý ¼®§ ½±²¬¿½¬øî÷ Ú±®³ Ý ã ݸ¿²¹»ó±ª»® ½±²¬¿½¬ øÚ±®³ Ý ¼®§ ½±²¬¿½¬÷ô ìððÊ¢ñíß ï³³î ¬± ê³³î øýïèßÉÙ ¬± ýïðßÉÙ÷ ½±²²»½¬·²¹ ©·®» Q-Pulse Id: TMS196 íè 26/11/2012 Page 120 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Refer catalogue F1 Relay interface module DIN rail mount Interface module with 34 series relay Ultra-slim profile, only 6.2 mm wide Integral LED and diode Simple removal of relay for replacement DIN rail mounting Contact specifications Contact configuration Rated current Rated voltage Rated load in AC 1 Rated load in AC 15 (230 V AC) Breaking capacity in DC 1 : 30/110/220 V Maximum peak current Maximum switching voltage Minimum switching load Cat. No. 38.51...V DC 38.51...V AC/DC The power in relays since 1954 TSECRRMEIWNLAELSSS Cat. No. 38.61...V DC 38.61...V AC/DC 1 C/O 6 A 250 V AC 1,500 VA 300 VA 6/0.2/0.15 A 10 A 400 V AC 500 mW Coil specifications Nominal voltage (UN) Rated power AC/DC Operation range Holding voltage AC/DC Must drop-out voltage AC/DC (50/60 Hz) AC/DC DC (50/60 Hz) AC/DC DC (50/60 Hz) AC/DC DC 24, 110, 240 6 , 12, 48 , 60 (0.2...0.9)W 0.3W (0.83...1.1) UN (0.83...1.2) UN 0.6 UN/0.6 UN 0.1 UN/0.1 UN Technical data Mechanical life AC/DC Electrical life @ rated load AC 1 Insulation between coil and contacts Ambient temperature range Protection rating Connection diagram -/10.106 60.103 6 kV -40 °C...+55 °C 9 IP 20 12 14 Accessories 11 A1 A2 93.01 Isolating plate 93.20 Jumperlink 20 way 93.64 Identification labels Notes: The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000. Available on indent only. Q-Pulse Id: TMS196 26/11/2012 Page 121 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Refer catalogue F1 Relay interface module Accessories The power in relays since 1954 Isolates varying voltages mounted in the same row. One isolating plate every four relays is recommended Reduced wiring and installation costs Cat. No. 93.01 Description Isolating plate Relay to suit 38.51, 38.61 93.20 Jumperlink 20 way 36 A, 250 V rating 38.51, 38.61 Easy identification for maintenance 93.64 Identification labels (64 tags in a pack) 38.51, 38.61 Relay dimensions (mm) 38 Series Cat. No. 38.51 Cat. No. 38.61 9 Q-Pulse Id: TMS196 26/11/2012 Page 122 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Low CS7 Profile DC Coil CS7E Industrial Control Relays with 24V DC Electronic Coil Same size as AC coil relays Draws less than 1.5W/60mA More energy efficient Standard, Master & Bifurcated models Reversible Line or Load Side Coil Terminations DIN Rail or Screw Mount Accepts most standard CS7 accessories 3-pole and 4-pole designs including Reversing Only 45mm wide (1-3/4") 24V DC Electronic Coil with integrated (built-in) diode Low Consumption DC Coils Sprecher+Schuh has expanded its line of CS7 industrial Control Relays with a new low consumption electronic coil. The 24V DC coil with low power consumption is integrated in a small relay body and draws less than 1.5 W/60mA holding power. The new design results in a shorter and more energy efficient relay, eases wiring and promotes a uniform panel appearance. Direct Control from PLC The low power consumption relay designed to control motors and other loads is especially aligned to the specific requirement of electronic control circuits. The low power consumption allows direct control through PLC's without the need for interposing relays. This means smaller power supplies which reduce panel space and cost. Q-Pulse Id: TMS196 26/11/2012 Page 123 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual CS7 with 24V DC Electronic Coil Contact Arrangement and Numbering A1 13 21 31 43 A2 14 22 32 44 A1 13 21 33 43 A2 14 22 34 44 A1 13 23 33 43 A2 14 24 34 44 A1 11 21 31 41 A2 12 22 32 42 Contacts Standard Relay Also Available Catalog NO NC Number Bifurcated Master 2 2 CS7E-22E-24E 3 1 CS7E-31E-24E 4 0 CS7E-40E-24E 0 4 CS7E-04E-24E ød Three Types of Relays · Standard relay for typical control applications · Bifurcated relay for low voltage applications · Master relay for high ampere control circuits Extremely Low Inrush Lower inrush means a smaller power supply may be used, resulting in: · Easier wiring · Uniform panel appearance · Smaller panels mean less cost Complete Accessory Compatibility Fits most standard CS7 accessories Mechanical Interlock 4-Pole Aux. d1 b b+ d2 c1 + a + c Dimension Comparison to True DC Relays a b c c1 c2 NEW! 24V DC Electronic Relay CS7E -... 45 81 80.5 75.5 6 (1-25/32) (3-3/16) (3-11/64 (3-3/32) (1/4) True DC Relays CS7C-... 45 81 106.5 101.5 6 (1-25/32) (3-3/16) (4-3/16) (4) (1/4) c+ 1 & 2-Pole Aux. Mechanical Latch ød d1 d2 2 screws 4.5 (3/16) 60 (2-23/64) 35 (1-25/64) 26mm Shorter than True DC CS7E vs. CS7C 2 screws 4.5 (3/16) 60 (2-23/64) 35 (1-25/64) 2-Pole Aux. Pneumatic Timer Coil Consumption Data Comparison Electronic DC Coil CS7E Pickup [W] 10 Holdin [W] 1.5 True DC Coil CS7C 6.5 6.5 Two Winding DC Coil CS7D 120 1.1 Smaller space requirement + lower inrush = LESS COST! 4x Less Power to Maintain CS7E vs. CS7C Electronic DC True DC 12x Less Inrush CS7E vs. CS7D Sprecher + Schuh US Division Headquarters 15910 International Plaza Dr., Houston, TX 77032 Tel: (281) 442-9000; Fax: (800) 739-7370 www.sprecherschuh.com Publication No: F-CS7E_108 Jan-2008 Q-Pulse Id: TMS196 Sprecher + Schuh Canadian Division 3610 Nashua Dr., Unit 10, Mississauga, Ontario L4V 1L2 Tel: (905) 677-7514; Fax: (905) 677-7663 26/11/2012 Page 124 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MTR/MTRA Installation & Troubleshooting 1 Introduction The MultiTrode level control relay is a solid-state electronic module in a hi-impact plastic case with a DIN rail attachment on the back, making a snap-on-snap-off installation. Any number of relays can be easily added to the DIN metal rail then wired together to form a complex pumping system that other wise may have to be controlled and operated by a programmed PLC. The relay is normally matched with the MultiTrode probe which works in conjunction with the relay and uses the conductivity of the liquid to complete an electrical circuit. 2 Electrical Overview There are 10 screw terminals on the unit. Facing the relay as shown, we look at the bottom terminals (left to right): · Lo (Charge mode). This is the point when the probe is dry the relay will turn on. · Lo (Discharge mode). This is the point when the probe in the tank is dry the relay will turn off. · Hi (Charge mode). This is the point when the probe in the tank is wet a relay will turn off · Hi (Discharge mode). This is the point when the probe in the tank is wet a relay will turn on. · C - is common earth. All earth bonding must be terminated here for correct operation. · " L " is "live" (240V AC) · " N " is "neutral" (240V AC) If the tank is plastic, or if you are conducting tests in a plastic bucket, or the vessel has no earth point inside, you must install an earth rod within the tank, vessel or bucket and make sure that it is bonded back to C on the relay unit. 3 DIP Switches 3.1 DIP Switches (See Wiring Diagram for full program functions.) 3.1.1 DIP 1 & 2 DIP 1 and 2 control the Sensitivity, in other words the cleaner the liquid the higher the sensitivity setting must be. Concentrated acids, minerals are by their own chemical composition highly conductive, so a low level of sensitivity is required, purified water is almost an insulator against electrical current flow so a higher sensitivity inside the relay is required. 3.1.2 DIP 3, 4 & 5 DIP switches 3, 4 and 5, control delay on activation. For example, in discharge mode with DIP switches 3, 4 and 5 set to 10 seconds, when the Hi point becomes wet it will activate the motor and it will take 10 seconds of continual coverage of the probe sensor to make the relay close and start the pump. This is invaluable when the probe is in a turbulent part of a well where fluid is splashing around touching the sensors momentarily, and false activation cannot be tolerated. 3.1.3 DIP 6 DIP switch 6 controls the charge/discharge function. Set "ON" for charge, and "OFF" for discharge MTR_Installation_AU+US_v1-0-0.doc Q-Pulse Id: TMS196 13-May-2005 26/11/2012 Page 1 of 4 Page 125 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MTR/MTRA Installation & Troubleshooting 3.2 Relay Contacts & their Applications 3.2.1 Contacts 15, 16 & 18 Contacts 15, 16, and 18 are used for electronic or visual notification of a change in state at the pump itself. Contacts 15, 16, and 18 are used for more advanced applications because they are a changeover relay, their state may be the same as contacts 25, 28 or the opposite. Both sets of contactors are triggered simultaneously. An example is when in discharge mode, (see Figure 1). You have a gravity flow coming in so the fluid reaches the lower sensor PB1, contacts 15 and 18 are open (15 being common to both contact 16 and 18) contacts 25 and 28 are also normally open but contacts 15 16 in this current situation are closed, whether PB1 is wet or dry is of no concern all will stay the same. The level now rises to PB2 and both relays change state, contacts 25 and 28 close to turn on the pump, contacts 15 and 16 are open, with 15 and 18 closed. In advanced applications this state change may be fed into a logic device to indicate the pump is running or the pump has stopped and perhaps light an LED or incandescent light source for visual confirmation that a change has occurred in the relay. 3.2.2 Contacts 25 & 28 Contacts 25 and 28 are used to control pump states. Contacts 25 and 28 are mostly used for turning on motors via a starting relay or solenoid, so, these sets of contacts react to the rising or falling levels of the fluid inside the tank, they will operate to turn on a pump in discharge mode when the top sensor is wet and in charge mode turn on the pump when the bottom sensor is dry. 4 Practical Overview 4.1 Discharge Mode DIP switch 6 set to "OFF" Figure 1 Discharge Mode Figure 1 shows two probes, (PB1 connected to Lo and PB2 connected to Hi). The pit is mostly underground and there is a gravity-fed inlet at the top left-hand side. The pit is empty with PB1 completely dry. Dipswitch 6 is set to "OFF." The relay operation depends on the electrical conductivity of liquid in the pit, i.e. no liquid = no current flow. The level starts to rise and covers PB1. This is a discharge operation so we do not want the relay to close and start a pump until the well is full so as the water rises it reaches PB2, the relay closes and the pump starts. The level now drops below PB2 but the pump still continues to run, the level continues to drop below PB1 the relay opens the pump stops. MTR_Installation_AU+US_v1-0-0.doc Q-Pulse Id: TMS196 13-May-2005 26/11/2012 Page 2 of 4 Page 126 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MTR/MTRA Installation & Troubleshooting 4.2 Charge Mode DIP switch 6 set to "On" Figure 2 Charge Mode Note: "C" is connected to common bonded earth. The unit will not operate correctly if not earthed. Let's look at the same relay but in a tank that is charging (DIP 6 is now on). See Figure 3, where liquid is being pumped into a tank, and discharging through a gravity feed, the tank is on steel stands "x" metres above the ground. With the tank full, PB1 and PB2 will be wet, the relay is off, and the pump has stopped. Water is slowly fed out from the bottom, and now as PB2 (HI) becomes dry nothing happens; the water now drops to below PB1 (Lo), and the pumps restarts to fill the tank. The pump will continue to fill the tank until PB2 (HI), becomes wet again. 4.3 MTRA Relay with Alarm (Discharge Applications Only) Figure 3 - MTRA Operation MTR_Installation_AU+US_v1-0-0.doc Q-Pulse Id: TMS196 13-May-2005 26/11/2012 Page 3 of 4 Page 127 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MTR/MTRA Installation & Troubleshooting The MTRA relay works in the same way as the MTR relay except the MTRA has a separate alarm output, and does not have a charge mode. The planned application is to close a contact to illuminate a warning alarm light. . Various other applications have included introducing a third probe to latch another relay. In Figure 2 we see three probes in a pit that is plastic, note the steel rod in the tank. (In a plastic vessel a steel rod must be used to create an earth return in the liquid so probes can function.) PB1, PB2, and PB3 are dry, and the relay power LED is on. When water enters the pit and wets PB1, nothing happens, water now reaches PB2 causing contacts 13 and 14 to close, the pump LED to light, and the water to drop. If, for example, the pump has its inlet partially blocked, the level continues to rise and wets PB3. This closes a separate relay that can activate a red flashing light, an audible fog horn or send a 5 volt pulse into another device with the common cause to warn human beings that a spill is due to occur. If the pumps become unclogged and PB3 becomes dry the alarm opens again and breaks the circuit that stops the light from flashing or the foghorn from sounding. 5 Most Common Installation Problems The relay requires a path between the probes to earth through the liquid. If you are testing in a plastic bucket, have installed the probe in a plastic tank or have no good earthing in the vessel you will need to install a separate earth and make sure all earth bonding comes back to the C terminal. Most problems like these are traced back to a lack of or poor earthing, or open circuits in the probe wiring. Now is the time to check the relay by using "the bridge testing line technique" remember you must simulate a fluid flow to correctly ascertain a good relay or a bad one. (All DIPswitch settings from 1 to 6 should be off.) Cut two pieces of insulated flexible copper wire one black one red 250 mm long, strip both ends back 10 mm on both cables, and join one black end and one red end. Insert the joined ends into C on the relay box, observing all safe electrical practises. You should have one black wire and one red wire free. Set your relay for discharge mode (DIP switch 6 is off) with no sensors connected to the unit, connect the red wire to Lo nothing should happen (if it does return the relay for replacement or repair*). Now connect the black wire to the Hi terminal the relay activated LED should light instantly (if it does not, the relay should be returned for repair*). 6 Troubleshooting I have checked all the DIPswitches and settings but in discharge mode as soon as the bottom sensor gets wet the pump turns on then turns off almost straight away. The installation went fine but now and again the pump will not turn on even though I am sure the probe is wet. All wiring is complete and all DIPswitches have been checked but the pump will not turn on at all. · This is the most common problem encountered with relay set up and commissioning, the probe in the bottom of the tank is wired into the Hi terminal instead of the Lo terminal. · Check the sensitivity level set on the relay, some times the level is set for foul water but due to changes in the flow the water becomes grey or clear, try changing the setting from 20K to 80K and monitor the results carefully. · If you have completed the test schedule for the relay and it passed then check the wiring to the sensors for this is now where the problem lies or in the earthing arrangements. If possible check the resistance between the sensor cable and the steel sensor on the probe to prove a solid connection. * Please contact your distributor or agent before returning any product for repair or warranty claim. MultiTrode Pty Ltd--Australia Ph: +61 7 3340 7000 Fx: +61 7 3340 7077 E-mail: sales@multitrode.com.au Sydney--Australia Ph: +61 2 9533 7735 Fx: +61 2 9533 7790 Visit www.multitrode.com.au for the latest information MTR_Installation_AU+US_v1-0-0.doc Q-Pulse Id: TMS196 13-May-2005 26/11/2012 MultiTrode Inc--USA Ph: +1 561 994 8090 Fx: +1 561 994 6282 E-mail: sales@multitrode.net Page 4 of 4 Page 128 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ͽ¸»³¿¬·½ Ü·¿¹®¿³- ÌÍÙóÍÎÚ L1 T L2 L I N L3 E N T T T L1 T L2 L E I Q T N U I E L3 P M T E N T N ÌÜÚ E Status Sense Q U I P M E N T ÜÍÜíìðñíèð öÔ PEN TNC Configuration *Only present in "L" low leakage models PE TNS Configuration *Only present in "L" low leakage models ÌÜÍ ïìð PE TT Configuration *Only present in "L" low leakage models ÌÜÍ ëð ÌÜÍ ïèð Q-Pulse Id: TMS196 ëê 26/11/2012 ©©©ò»®·½±ò½±³ Page 129 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 130 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4.4 INSTRUMENTS Endres & Hauser Promatic 50 - Flowmeter Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 131 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Brief Operating Instructions Proline Promag 50 Electromagnetic Flow Measuring System 6 8 These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope of supply. Detailed information is provided in the Operating Instructions and the additional documentation on the CD-ROM supplied. The complete device documentation consists of: · These Brief Operating Instructions · Depending on the device version: Operating Instructions and the Description of Device Functions Approvals and safety certificates Special safety instructions in accordance with the approvals for the device (e.g. explosion protection, pressure equipment directive etc.) Additional device-specific information KA00026D/06/EN/14.11 71154524 Q-Pulse Id: TMS196 26/11/2012 Page 132 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Table of contents 1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 Installation, commissioning and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.4 Safety conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.1 Transporting to the measuring point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.3 Installing the Promag L sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.4 Installing the W sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.5 Installing the Promag P sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 2.6 Installing the Promag H sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.7 Installing the transmitter housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 2.8 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 3 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 3.1 Connecting the various housing types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 3.2 Connecting the remote version connecting cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 3.3 Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 3.4 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 3.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 4 Hardware settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 4.1 Device address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 4.2 Terminating resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 5.1 Switching on the measuring device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 5.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 5.3 Navigating within the function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 5.4 Calling the Commissioning Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 5.5 Software settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 5.6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 2 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 133 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Safety instructions 1 Safety instructions 1.1 Designated use · The measuring device is to be used only for measuring the flow of conductive liquids in closed pipes. A minimum conductivity of 20 S/cm is required for measuring demineralized water. Most liquids can be measured as of a minimum conductivity of 5 S/cm. · Any use other than that described here compromises the safety of persons and the entire measuring system and is, therefore, not permitted. · The manufacturer is not liable for damage caused by improper or non-designated use. 1.2 Installation, commissioning and operation · The measuring device must only be installed, connected, commissioned and maintained by qualified and authorized specialists (e.g. electrical technicians) in full compliance with the instructions in these Brief Operating Instructions, the applicable norms, legal regulations and certificates (depending on the application). · The specialists must have read and understood these Brief Operating Instructions and must follow the instructions they contain. If you are unclear on anything in these Brief Operating Instructions, you must read the Operating Instructions (on the CD-ROM). The Operating Instructions provide detailed information on the measuring device. · The measuring device should only installed in a de-energized state free from outside loads or strain. · The measuring device may only be modified if such work is expressly permitted in the Operating Instructions (on the CD-ROM). · Repairs may only be performed if a genuine spare parts kit is available and this repair work is expressly permitted. · If performing welding work on the piping, the welding unit may not be grounded by means of the measuring device. 1.3 Operational safety · The measuring device is designed to meet state-of-the-art safety requirements, has been tested, and left the factory in a condition in which it is safe to operate. Relevant regulations and European standards have been observed. · The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to these Operating Instructions. · The information on the warning notices, nameplates and connection diagrams affixed to the device must be observed. These contain important data on the permitted operating conditions, the range of application of the device and information on the materials used. · If the device is not used at atmospheric temperatures, compliance with the relevant marginal conditions as specified in the device documentation supplied (on CD-ROM) is mandatory. · The device must be wired as specified in the wiring and connection diagrams. Interconnection must be permitted. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 3 Page 134 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Safety instructions Proline Promag 50 · All parts of the device must be included in the potential equalization of the system. · Cables, certified cable glands and certified dummy plugs must be suitable to withstand the prevailing operating conditions, such as the temperature range of the process. Housing apertures that are not used must be sealed with dummy plugs. · The device should only be used for fluids to which all the wetted parts of the device are sufficiently resistant. With regard to special fluids, including fluids used for cleaning, Endress+Hauser will be happy to assist in clarifying the corrosion-resistant properties of wetted materials. However, minor changes in temperature, concentration or in the degree of contamination in the process may result in variations in corrosion resistance. For this reason, Endress+Hauser does not accept any responsibility with regard to the corrosion resistance of wetted materials in a specific application. The user is responsible for the choice of suitable wetted materials in the process. · When hot fluid passes through the measuring tube, the surface temperature of the housing increases. In the case of the sensor, in particular, users should expect temperatures that can be close to the fluid temperature. If the temperature of the fluid is high, implement sufficient measures to prevent burning or scalding. · Hazardous areas Measuring devices for use in hazardous areas are labeled accordingly on the nameplate. Relevant national regulations must be observed when operating the device in hazardous areas. The Ex documentation on the CD-ROM is an integral part of the entire device documentation. The installation regulations, connection data and safety instructions provided in the Ex documentation must be observed. The symbol and name on the front page provides information on the approval and certification (e.g. 0 Europe, 2 USA, 1 Canada). The nameplate also bears the documentation number of this Ex documentation (XA***D/../..). · For measuring systems used in SIL 2 applications, the separate manual on functional safety (on the CD-ROM) must be observed. · Hygienic applications Measuring devices for hygienic applications have their own special labeling. Relevant national regulations must be observed when using these devices. · Pressure instruments Measuring devices for use in systems that need to be monitored are labeled accordingly on the nameplate. Relevant national regulations must be observed when using these devices. The documentation on the CD-ROM for pressure instruments in systems that need to be monitored is an integral part of the entire device documentation. The installation regulations, connection data and safety instructions provided in the Ex documentation must be observed. · Endress+Hauser will be happy to assist in clarifying any questions on approvals, their application and implementation. 4 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 135 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Safety instructions 1.4 Safety conventions # Warning! "Warning" indicates an action or procedure which, if not performed correctly, can result in injury or a safety hazard. Comply strictly with the instructions and proceed with care. " Caution! "Caution" indicates an action or procedure which, if not performed correctly, can result in incorrect operation or destruction of the device. Comply strictly with the instructions. ! Note! "Note" indicates an action or procedure which, if not performed correctly, can have an indirect effect on operation or trigger an unexpected response on the part of the device. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 5 Page 136 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 2 Installation 2.1 Transporting to the measuring point · Transport the measuring device to the measuring point in the original packaging. · Do not remove the covers or caps until immediately before installation. 2.1.1 Transporting flanged devices DN 300 ( 12") To transport the unit, use slings slung around the process connections or use lugs (if available). # Warning! Risk of injury! The device can slip. The center of gravity of the measuring device may be higher than the holding points of the slings. Always ensure that the device cannot slip or turn around its axis. A0007408 Do not lift measuring devices by the transmitter housing or the connection housing in the case of the remote version. Do not use chains as they could damage the housing. A0007409 2.1.2 Transporting flanged devices DN > 300 (> 12") Use only the metal eyes provided on the flanges to transport, lift or position the sensor in the piping. " Caution! Do not attempt to lift the sensor with the tines of a fork-lift truck beneath the metal casing! This would buckle the casing and damage the internal magnetic coils. 6 Q-Pulse Id: TMS196 26/11/2012 A0008153 Endress+Hauser Page 137 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.2 Installation conditions 2.2.1 Dimensions For the dimensions of the measuring device, see the associated Technical Information on the CD-ROM. 2.2.2 Mounting location The accumulation of air or formation of gas bubbles in the measuring tube can result in an increase in measuring errors. For this reason avoid the following mounting locations in the pipe: · At the highest point of a pipeline. Risk of air accumulating! · Directly upstream from a free pipe outlet in a down pipe. h ³ 2 x DN A0008154 Installation of pumps Do not install the sensor on the intake side of a pump. This precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. It might be necessary to use pulse dampers in systems incorporating piston pumps, piston diaphragm pumps or peristaltic pumps. Information on the measuring system's pressure tightness and resistance to vibration and shock can be found in the Operating Instructions of the CD-ROM. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 A0003203 7 Page 138 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 Partially filled pipes Partially filled pipes with gradients necessitate a drain-type configuration. The empty pipe detection (EPD) function offers additional protection by detecting empty or partially filled pipes. " Caution! Risk of solids accumulating! Do not install the sensor at the lowest point in the drain. It is advisable to install a cleaning valve. Installation in a partially filled pipe ³ 2 x DN ³ 5 x DN A0008155 Down pipes Install a siphon or a vent valve downstream of the sensor in down pipes longer than 5 meters (16 ft). This precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. This measure also prevents the system losing prime, which could cause air pockets. For information on the pressure tightness of the measuring tube lining, see the Operating Instructions on the CD-ROM. Measures for installation in a down pipe (h > 5 m/16 ft) 1 1. Vent valve 2. Siphon 2 h A0008157 8 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 139 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.2.3 Orientation An optimum orientation helps avoid gas and air accumulations and buildup in the measuring tube. The measuring device, nevertheless, supplies a range of functions and tools to measure problematic fluids correctly: · Electrode cleaning circuitry (ECC) to prevent electrically conductive deposits in the measuring tube, e.g. for fluids causing buildup · Empty pipe detection (EPD) for detecting partially filled measuring tubes, e.g. in the case of degassing fluids or varying process pressures · Exchangeable measuring electrodes for abrasive fluids (only Promag W) Vertical orientation This orientation is optimum for self-emptying piping systems and when using empty pipe detection (EPD) or open electrode detection (OED). A0008158 Horizontal orientation The measuring electrode plane should be horizontal. This prevents brief insulation of the two electrodes by entrained air bubbles. " Caution! In the case of horizontal orientation, empty pipe detection only works correctly if the transmitter housing is facing upwards. Otherwise there is no guarantee that empty pipe detection will respond if the measuring tube is only partially filled or empty. A 1 2 2 1. EPD electrode for empty pipe detection (not for Promag H, DN 2 to 15, 1/12" to ½"). 2. Measuring electrodes for signal detection 3. Reference electrode for potential equalization (not for Promag H) 3 A A0008159 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 9 Page 140 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 Inlet and outlet runs If possible, install the sensor upstream from fittings such as valves, T-pieces, elbows, etc. ³ 5 x DN ³ 2 x DN The following inlet and outlet runs must be observed in order to meet accuracy specifications: · Inlet run: 5 × DN · Outlet run: 2 × DN A0008160 2.2.4 Vibrations Secure and fix both the piping and the sensor if vibrations are severe. Measures to prevent device vibration L (L > 10 m/33 ft) " Caution! It is advisable to install the sensor and transmitter separately if vibration is excessively severe. For information on the permitted shock and vibration resistance, see the Operating Instructions on the CD-ROM. A0008161 10 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 141 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.2.5 Foundations, supports If the nominal diameter is DN 350 ( 14"), mount the sensor on a foundation of adequate load-bearing strength. " Caution! Risk of damage! Do not support the weight of the sensor on the metal casing. This would buckle the casing and damage the internal magnetic coils. A0008163 2.2.6 Length of connecting cable Comply with the following instructions in order to ensure correct measuring results: · Secure the cable run or route the cable in an armored conduit. Movement of the cable can falsify the measuring signal, particularly if the fluid conductivity is low. · Route the cable well clear of electrical machines and switching elements. · Ensure potential equalization between the sensor and transmitter, if necessary. · The permissible cable length Lmax depends on the fluid conductivity. [µS/cm] 200 100 L max Gray shaded area = permissible range Lmax = length of connecting cable in [m]/[ft] Fluid conductivity in (S/cm] 5 10 100 0 200 400 200 600 [m] L max [ft] A0008164 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 11 Page 142 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 2.3 Installing the Promag L sensor " Caution! · The protective covers mounted on the two sensor flanges (DN 50...300) are used to hold the lap joint flanges in place and to protect the PTFE liner during transportation. Consequently, do not remove these covers until immediately before the sensor is installed in the pipe. · The protective plates must always remain mounted while the device is in storage. · Make sure that the lining at the flange is not damaged or removed. a0008165 ! Note! Screws, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer. The sensor is installed between the two pipe flanges: · The requisite torques must be observed ä 13 · If grounding disks are used, follow the mounting instructions which will be enclosed with the shipment. · To comply with the device specification, a concentrical installation in the measuring section is required 2.3.1 Seals Comply with the following instructions when installing seals: · Hard rubber lining additional seals are always required! · Polyurethane lining no seals are required. · No seals are required for PFTE measuring tube lining. · For DIN flanges, only use seals to DIN EN 1514-1. · Make sure that the mounted seals do not protrude into the piping cross-section. " Caution! Risk of short circuit! Do not use electrically conductive sealing compounds such as graphite! An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal. 2.3.2 Ground cable If necessary, special ground cables can be ordered as accessories for potential equalization. 12 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 143 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.3.3 Screw tightening torques (Promag L) Please note the following: · The tightening torques listed below are for lubricated threads only. · Always tighten the screws uniformly and in diagonally opposite sequence. · Overtightening the screws will deform the sealing faces or damage the seals. · The tightening torques listed below apply only to pipes not subjected to tensile stress. Promag L tightening torques for EN (DIN) Nominal diameter EN (DIN) [mm] 50 65* 80 100 125 150 200 250 300 350 350 400 400 450 450 500 500 600 600 700 700 800 800 900 900 1000 1000 1200 1200 1400 Pressure rating [bar] PN 10/16 PN 10/16 PN 10/16 PN 10/16 PN 10/16 PN 10/16 PN 10 PN 10 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 PN 10 PN 6 Threaded fasteners 4 × M 16 8 × M 16 8 × M 16 8 × M 16 8 × M 16 8 × M 20 8 × M 20 12 × M 20 12 × M 20 12 × M 20 16 × M 20 16 × M 20 16 × M 24 16 × M 20 20 × M 24 20 × M 20 20 × M 24 20 × M 24 20 × M 27 24 × M 24 24 × M 27 24 × M 27 24 × M 30 24 × M 27 28 × M 30 28 × M 27 28 × M 33 32 × M 30 32 × M 36 36 × M 33 Max. tightening torque Hard rubber [Nm] Polyurethane [Nm] - 15 - 10 - 15 - 20 - 30 - 50 - 65 - 50 - 55 111 120 112 118 90 98 151 167 112 126 153 133 119 123 155 171 139 147 206 219 148 139 246 246 206 182 331 316 230 637 316 307 218 208 402 405 319 299 564 568 430 - PTFE [Nm] 40 22 30 42 55 90 130 90 100 - Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 13 Page 144 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 Nominal diameter EN (DIN) [mm] Pressure rating [bar] Threaded fasteners 1400 PN 10 36 × M 39 1400 PN 16 36 × M 45 1600 PN 6 40 × M 33 1600 PN 10 40 × M 45 1600 PN 16 40 × M 52 1800 PN 6 44 × M 36 1800 PN 10 44 × M 45 1800 PN 16 44 × M 52 2000 PN 6 48 × M 39 2000 PN 10 48 × M 45 2000 PN 16 48 × M 56 2200 PN 6 52 × M 39 2200 PN 10 52 × M 52 2400 PN 6 56 × M 39 2400 PN 10 56 × M 52 * Designed acc. to EN 1092-1 (not to DIN 2501) Max. tightening torque Hard rubber [Nm] Polyurethane [Nm] 654 729 440 946 1007 547 961 1108 629 1047 1324 698 1217 768 1229 618 762 417 893 1100 521 895 1003 605 1092 1261 - PTFE [Nm] - Promag L tightening torques for ANSI Nominal diameter [mm] 50 80 100 150 200 250 300 350 400 450 500 600 [inch] 2" 3" 4" 6" 8" 10" 12" 14" 16" 18" 20" 24" ANSI Pressure rating [lbs] Class 150 Class 150 Cla ss 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Threaded fasteners 4 × 5/8" 4 × 5/8" 8 × 5/8" 8 × ¾" 8 × ¾" 12 × 7/8" 12 × 7/8" 12 × 1" 16 × 1" 16 × 1 1/8" 20 × 1 1/8" 20 × 1 ¼" Max. tightening torque Hard rubber [Nm] [lbf · ft] - - - - - - - - - - - - - - 135 100 128 94 204 150 183 135 268 198 Polyurethane [Nm] [lbf · ft] 15 11 25 18 20 15 45 33 65 48 55 41 68 56 158 117 150 111 234 173 217 160 307 226 PTFE [Nm] [lbf · ft] 40 29 65 48 44 32 90 66 125 92 100 74 115 85 - - - - - - - - - - 14 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 145 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation Promag L tightening torques for AWWA Nominal diameter [mm] 700 750 800 900 1000 1050 1200 1350 1500 1650 1800 2000 2150 2300 [inch] 28" 30" 32" 36" 40" 42" 48" 54" 60" 66" 72" 78" 84" 90" AWWA Pressure rating Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Threaded fasteners 28 × 1 ¼" 28 × 1 ¼" 28 × 1 ½" 32 × 1 ½" 36 × 1 ½" 36 × 1 ½" 44 × 1 ½" 44 × 1 ¾" 52 × 1 ¾" 52 × 1 ¾" 60 × 1 ¾" 64 × 2" 64 × 2" 68 × 2 ¼" Max. tightening torque Hartgummi [Nm] [lbf · ft] 247 182 287 212 394 291 419 309 420 310 528 389 552 407 730 538 758 559 946 698 975 719 853 629 931 687 1048 773 Polyurethane [Nm] [lbf · ft] 292 215 302 223 422 311 430 317 477 352 518 382 531 392 - - - - - - - - - - - - - - PTFE [Nm] [lbf · ft] - - - - - - - - - - - - - - - - - - - - - - - - - - - - Promag L tightening torques for AS 2129 Nominal diameter [mm] 350 400 450 500 600 700 750 800 900 1000 1200 AS 2129 Pressure rating Threaded fasteners Table E Table E Table E Table E Table E Table E Table E Table E Table E Table E Table E 12 × M 24 12 × M 24 16 × M 24 16 × M 24 16 × M 30 20 × M 30 20 × M 30 20 × M 30 24 × M 30 24 × M 30 32 × M 30 Max. tightening torque Hard rubber [Nm] 203 226 226 271 439 355 559 631 627 634 727 Polyurethane [Nm] - PTFE [Nm] - Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 15 Page 146 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 Promag L tightening torques for AS 4087 Nominal diameter [mm] 350 375 400 450 500 600 700 750 800 900 1000 1200 AS 4087 Pressure rating Threaded fasteners PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 12 × M 24 12 × M 24 12 × M 24 12 × M 24 16 × M 24 16 × M 27 20 × M 27 20 × M 30 20 × M 33 24 × M 33 24 × M 33 32 × M 33 Max. tightening torque Hard rubber [Nm] 203 137 226 301 271 393 330 529 631 627 595 703 Polyurethane [Nm] - PTFE [Nm] - 16 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 147 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.4 Installing the W sensor a0008165 ! Note! Screws, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer. The sensor is installed between the two pipe flanges: · The requisite torques must be observed ä 18 · If grounding disks are used, follow the mounting instructions which will be enclosed with the shipment. · To comply with the device specification, a concentrical installation in the measuring section is required 2.4.1 Seals Comply with the following instructions when installing seals: · Hard rubber lining additional seals are always necessary. · Polyurethane lining no seals are required. · For DIN flanges, use only seals according to EN 1514-1. · Make sure that the seals do not protrude into the piping cross-section. " Caution! Risk of short circuit! Do not use electrically conductive sealing compounds such as graphite! An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal. 2.4.2 Ground cable If necessary, special ground cables can be ordered as accessories for potential equalization. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 17 Page 148 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 2.4.3 Screw tightening torques (Promag W) Please note the following: · The tightening torques listed below are for lubricated threads only. · Always tighten the screws uniformly and in diagonally opposite sequence. · Overtightening the screws will deform the sealing faces or damage the seals. · The tightening torques listed below apply only to pipes not subjected to tensile stress. Promag W tightening torques for EN (DIN) Nominal diameter [mm] 25 32 40 50 65* 65 80 80 100 100 125 125 150 150 200 200 200 250 250 250 300 300 300 350 350 350 350 400 400 400 400 450 450 EN (DIN) Pressure rating [bar] PN 40 PN 40 PN 40 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 6 PN 10 PN 16 PN 25 PN 6 PN 10 PN 16 PN 25 PN 6 PN 10 Threaded fasteners 4 × M 12 4 × M 16 4 × M 16 4 × M 16 8 × M 16 8 × M 16 8 × M 16 8 × M 16 8 × M 16 8 × M 20 8 × M 16 8 × M 24 8 × M 20 8 × M 24 8 × M 20 12 × M 20 12 × M 24 12 × M 20 12 × M 24 12 × M 27 12 × M 20 12 × M 24 16 × M 27 12 × M 20 16 × M 20 16 × M 24 16 × M 30 16 × M 20 16 × M 24 16 × M 27 16 × M 33 16 × M 20 20 × M 24 Max. tightening torque [Nm] Hard rubber Polyurethane - 15 - 24 - 31 48 40 32 27 32 27 40 34 40 34 43 36 59 50 56 48 83 71 74 63 104 88 106 91 70 61 104 92 82 71 98 85 150 134 94 81 134 118 153 138 111 120 112 118 152 165 227 252 90 98 151 167 193 215 289 326 112 126 153 133 18 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 149 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation Nominal diameter EN (DIN) [mm] Pressure rating [bar] 450 PN 16 450 PN 25 500 PN 6 500 PN 10 500 PN 16 500 PN 25 600 PN 6 600 PN 10 600 * PN 16 600 PN 25 700 PN 6 700 PN 10 700 PN 16 700 PN 25 800 PN 6 800 PN 10 800 PN 16 800 PN 25 900 PN 6 900 PN 10 900 PN 16 900 PN 25 1000 PN 6 1000 PN 10 1000 PN 16 1000 PN 25 1200 PN 6 1200 PN 10 1200 PN 16 1400 PN 6 1400 PN 10 1400 PN 16 1600 PN 6 1600 PN 10 1600 PN 16 1800 PN 6 1800 PN 10 1800 PN 16 2000 PN 6 2000 PN 10 2000 PN 16 * Designed acc. to EN 1092-1 (not to DIN 2501) Threaded fasteners 20 × M 27 20 × M 33 20 × M 20 20 × M 24 20 × M 30 20 × M 33 20 × M 24 20 × M 27 20 × M 33 20 × M 36 24 × M 24 24 × M 27 24 × M 33 24 × M 39 24 × M 27 24 × M 30 24 × M 36 24 × M 45 24 × M 27 28 × M 30 28 × M 36 28 × M 45 28 × M 27 28 × M 33 28 × M 39 28 × M 52 32 × M 30 32 × M 36 32 × M 45 36 × M 33 36 × M 39 36 × M 45 40 × M 33 40 × M 45 40 × M 52 44 × M 36 44 × M 45 44 × M 52 48 × M 39 48 × M 45 48 × M 56 Max. tightening torque [Nm] Hard rubber Polyurethane 198 196 256 253 119 123 155 171 275 300 317 360 139 147 206 219 415 443 431 516 148 139 246 246 278 318 449 507 206 182 331 316 369 385 664 721 230 637 316 307 353 398 690 716 218 208 402 405 502 518 970 971 319 299 564 568 701 753 430 398 654 618 729 762 440 417 946 893 1007 1100 547 521 961 895 1108 1003 629 605 1047 1092 1324 1261 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 19 Page 150 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 Promag W tightening torques for ANSI Nominal diameter ANSI [mm] 25 25 40 40 50 50 80 80 100 100 150 150 200 250 300 350 400 450 500 600 [inch] 1" 1" 1 ½" 1 ½" 2" 2" 3" 3" 4" 4" 6" 6" 8" 10" 12" 14" 16" 18" 20" 24" Pressure rating [lbs] Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Threaded fasteners 4 × ½" 4 × 5/8" 4 × ½" 4 × ¾" 4 × 5/8" 8 × 5/8" 4 × 5/8" 8 × ¾" 8 × 5/8" 8 × ¾" 8 × ¾" 12 × ¾" 8 × ¾" 12 × 7/8" 12 × 7/8" 12 × 1" 16 × 1" 16 × 1 1/8" 20 × 1 1/8" 20 × 1 ¼" Max. tightening torque Hard rubber Polyurethane [Nm] [lbf · ft] [Nm] [lbf · ft] - - 7 5 - - 8 6 - - 10 7 - - 15 11 35 26 22 16 18 13 11 8 60 44 43 32 38 28 26 19 42 31 31 23 58 43 40 30 79 58 59 44 70 52 51 38 107 79 80 59 101 74 75 55 133 98 103 76 135 100 158 117 128 94 150 111 204 150 234 173 183 135 217 160 268 198 307 226 Promag W tightening torques for JIS Nominal diameter [mm] 25 25 32 32 40 40 50 50 65 65 80 80 100 JIS Pressure rating 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K Threaded fasteners 4 × M 16 4 × M 16 4 × M 16 4 × M 16 4 × M 16 4 × M 16 4 × M 16 8 × M 16 4 × M 16 8 × M 16 8 × M 16 8 × M 20 8 × M 16 Max. tightening torque [Nm] Hard rubber Polyurethane - 19 - 19 - 22 - 22 - 24 - 24 40 33 20 17 55 45 28 23 29 23 42 35 35 29 20 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 151 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation Nominal diameter [mm] 100 125 125 150 150 200 200 250 250 300 300 JIS Pressure rating 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K Threaded fasteners 8 × M 20 8 × M 20 8 × M 22 8 × M 20 12 × M 22 12 × M 20 12 × M 22 12 × M 22 12 × M 24 16 × M 22 16 × M 24 Max. tightening torque [Nm] Hard rubber Polyurethane 56 48 60 51 91 79 75 63 81 72 61 52 91 80 100 87 159 144 74 63 138 124 Promag W tightening torques for AWWA Nominal diameter [mm] 700 750 800 900 1000 1050 1200 1350 1500 1650 1800 2000 [inch] 28" 30" 32" 36" 40" 42" 48" 54" 60" 66" 72" 78" AWWA Pressure rating Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Class D Threaded fasteners 28 × 1 ¼" 28 × 1 ¼" 28 × 1 ½" 32 × 1 ½" 36 × 1 ½" 36 × 1 ½" 44 × 1 ½" 44 × 1 ¾" 52 × 1 ¾" 52 × 1 ¾" 60 × 1 ¾" 64 × 2" Promag W tightening torques for AS 2129 Max. tightening torque Hard rubber [Nm] [lbf · ft] 247 182 287 212 394 291 419 309 420 310 528 389 552 407 730 538 758 559 946 698 975 719 853 629 Polyurethane [Nm] [lbf · ft] 292 215 302 223 422 311 430 317 477 352 518 382 531 392 633 467 832 614 955 704 1087 802 786 580 Nominal diameter [mm] 50 80 100 150 200 250 300 AS 2129 Pressure rating Table E Table E Table E Table E Table E Table E Table E Threaded fasteners 4 × M 16 4 × M 16 8 × M 16 8 × M 20 8 × M 20 12 × M 20 12 × M 24 Max. tightening torque [Nm] Hard rubber 32 49 38 64 96 98 123 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 21 Page 152 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 Nominal diameter [mm] 350 400 450 500 600 700 750 800 900 1000 1200 AS 2129 Pressure rating Table E Table E Table E Table E Table E Table E Table E Table E Table E Table E Table E Threaded fasteners 12 × M 24 12 × M 24 16 × M 24 16 × M 24 16 × M 30 20 × M 30 20 × M 30 20 × M 30 24 × M 30 24 × M 30 32 × M 30 Promag W tightening torques for AS 4087 Nominal diameter [mm] 50 80 100 150 200 250 300 350 375 400 450 500 600 700 750 800 900 1000 1200 AS 4087 Pressure rating Table E PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 PN 16 Threaded fasteners 4 × M 16 4 × M 16 4 × M 16 8 × M 20 8 × M 20 8 × M 20 12 × M 24 12 × M 24 12 × M 24 12 × M 24 12 × M 24 16 × M 24 16 × M 27 20 × M 27 20 × M 30 20 × M 33 24 × M 33 24 × M 33 32 × M 33 Max. tightening torque [Nm] Hard rubber 203 226 226 271 439 355 559 631 627 634 727 Max. tightening torque [Nm] Hard rubber 32 49 76 52 77 147 103 203 137 226 301 271 393 330 529 631 627 595 703 22 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 153 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.5 Installing the Promag P sensor " Caution! · The plates mounted on the two sensor flanges protect the PTFE which is turned over the flanges and, consequently, should not be removed until immediately prior to mounting the sensor. · The protective plates must always remain mounted while the device is in storage. · Make sure that the lining at the flange is not damaged or removed. ! Note! Screws, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer. The sensor is installed between the two pipe flanges: · The requisite torques must be observed ä 25 · If grounding disks are used, follow the mounting instructions which will be enclosed with the shipment. a0008165 2.5.1 Seals Comply with the following instructions when installing seals: · No seals are required for PFA or PFTE measuring tube lining. · For DIN flanges, only use seals to DIN EN 1514-1. · Make sure that the mounted seals do not protrude into the piping cross-section. " Caution! Risk of short circuit! Do not use electrically conductive sealing compounds such as graphite! An electrically conductive layer could form on the inside of the measuring tube and short-circuit the measuring signal. 2.5.2 Ground cable If necessary, special ground cables can be ordered as accessories for potential equalization. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 23 Page 154 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 2.5.3 Installing the high-temperature version (with PFA lining) The high-temperature version has a housing support for the thermal separation of sensor and transmitter. The high-temperature version is always used for applications in which high ambient temperatures are encountered in conjunction with high fluid temperatures. The high-temperature version is obligatory if the fluid temperature exceeds +150 °C. ! Note! You will find information on permissible temperature ranges in the Operating Instructions of the CD-ROM Insulation Pipes generally have to be insulated if they carry very hot fluids, in order to avoid energy losses and to prevent accidental contact with pipes at temperatures that could cause injury. Guidelines regulating the insulation of pipes have to be taken into account. " Caution! Risk of measuring electronics overheating. The housing support dissipates heat and its entire surface area must remain uncovered. Make sure that the sensor insulation does not extend past the top of the two sensor shells. Esc - + E max. A0004300 24 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 155 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.5.4 Tightening torques for threaded fasteners (Promag P) Please note the following: · The tightening torques listed below are for lubricated threads only. · Always tighten the screws uniformly and in diagonally opposite sequence. · Overtightening the screws will deform the sealing faces or damage the seals. · The tightening torques listed below apply only to pipes not subjected to tensile stress. Promag P tightening torques for EN (DIN) Nominal diameter [mm] 15 25 32 40 50 65 * 65 80 80 100 100 125 125 150 150 200 200 200 250 250 250 300 300 300 350 350 350 400 400 400 450 450 EN (DIN) Pressure rating [bar] PN 40 PN 40 PN 40 PN 40 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 16 PN 40 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 PN 25 PN 10 PN 16 Threaded fasteners 4 × M 12 4 × M 12 4 × M 16 4 × M 16 4 × M 16 8 × M 16 8 × M 16 8 × M 16 8 × M 16 8 × M 16 8 × M 20 8 × M 16 8 × M 24 8 × M 20 8 × M 24 8 × M 20 12 × M 20 12 × M 24 12 × M 20 12 × M 24 12 × M 27 12 × M 20 12 × M 24 16 × M 27 16 × M 20 16 × M 24 16 × M 30 16 × M 24 16 × M 27 16 × M 33 20 × M 24 20 × M 27 Max. tightening torque [Nm] PTFE PFA 11 26 20 41 35 52 47 65 59 43 40 43 40 53 48 53 48 57 51 78 70 75 67 111 99 99 85 136 120 141 101 94 67 138 105 110 131 200 125 179 204 188 254 380 260 330 488 235 300 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 25 Page 156 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 Nominal diameter EN (DIN) [mm] Pressure rating [bar] 450 PN 25 500 PN 10 500 PN 16 500 PN 25 600 PN 10 600 * PN 16 600 PN 25 * Designed acc. to EN 1092-1 (not to DIN 2501) Promag P tightening torques for ANSI Threaded fasteners 20 × M 33 20 × M 24 20 × M 30 20 × M 33 20 × M 27 20 × M 33 20 × M 36 Max. tightening torque [Nm] PTFE PFA 385 265 448 533 345 658 731 Nominal diameter [mm] 15 15 25 25 40 40 50 50 80 80 100 100 150 150 200 250 300 350 400 450 500 600 [inch] ½" ½" 1" 1" 1 ½" 1 ½" 2" 2" 3" 3" 4" 4" 6" 6" 8" 10" 12" 14" 16" 18" 20" 24" ANSI Pressure rating [lbs] Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 300 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Class 150 Threaded fasteners 4 × ½" 4 × ½" 4 × ½" 4 × 5/8" 4 × ½" 4 × ¾" 4 × 5/8" 8 × 5/8" 4 × 5/8" 8 × ¾" 8 × 5/8" 8 × ¾" 8 × ¾" 12 × ¾" 8 × ¾" 12 × 7/8" 12 × 7/8" 12 × 1" 16 × 1" 16 × 1 1/8" 20 × 1 1/8" 20 × 1 ¼" Max. tightening torque PTFE PFA [Nm] [lbf · ft] [Nm] [lbf · ft] 6 4 6 4 11 8 10 7 14 10 12 9 24 18 21 15 34 25 31 23 47 35 44 32 23 17 22 16 79 58 67 49 47 35 42 31 56 41 50 37 67 49 59 44 106 78 86 63 73 54 67 49 143 105 109 80 135 100 178 131 260 192 246 181 371 274 341 252 477 352 26 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 157 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation Promag P tightening torques for JIS Nominal diameter [mm] 25 25 32 32 40 40 50 50 65 65 80 80 100 100 125 125 150 150 200 200 250 250 300 300 JIS Pressure rating 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K 10K 20K Threaded fasteners 4 × M 16 4 × M 16 4 × M 16 4 × M 16 4 × M 16 4 × M 16 4 × M 16 8 × M 16 4 × M 16 8 × M 16 8 × M 16 8 × M 20 8 × M 16 8 × M 20 8 × M 20 8 × M 22 8 × M 20 12 × M 22 12 × M 20 12 × M 22 12 × M 22 12 × M 24 16 × M 22 16 × M 24 Max. tightening torque [Nm] PTFE PFA 32 27 32 27 38 38 41 37 41 37 54 46 27 23 74 63 37 31 38 32 57 46 47 38 75 58 80 66 121 103 99 81 108 72 82 54 121 88 133 212 99 183 Promag P tightening torques for AS 2129 Nominal diameter [mm] 25 50 AS 2129 Pressure rating Table E Table E Threaded fasteners 4 × M 12 4 × M 16 Max. tightening torque [Nm] PTFE 21 42 Promag P tightening torques for AS 4087 Nominal diameter [mm] 50 AS 4087 Pressure rating PN 16 Threaded fasteners 4 × M 16 Max. tightening torque [Nm] PTFE 42 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 27 Page 158 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 2.6 Installing the Promag H sensor Depending on the order specifications, the sensor is supplied with or without ready-mounted process connections. Mounted process connections are fixed to the sensor with 4 or 6 hexagonal-headed bolts. " Caution! Depending on the application and length of the pipe, the sensor may have to be supported or additionally secured. The sensor must be secured if using plastic process connections. An appropriate wall mounting kit can be ordered separately from Endress+Hauser as an accessory. 2.6.1 Seals When mounting the process connections, make sure that the seals in question are free from dirt and centered correctly. " Caution! · The screws must be securely tightened in the case of metal process connections. Together with the sensor, the process connection forms a metal connection that ensures defined seal compression. · With regard to process connections made of plastic material, comply with the max. torques for lubricated threads (7 Nm / 5.2 lbf ft). A seal must always be used between the connection and counterflange for plastic flanges. · The seals should be replaced periodically depending on the application, particularly if molded seals are used (aseptic version)! The intervals between seal replacement depend on the frequency of the cleaning cycles and the fluid and cleaning temperatures. Replacement seals can be ordered as an accessory. 2.6.2 Using and mounting grounding rings (DN 2 to 25, 1/12" to 1") In the case of process connections made of plastic (e.g. flange connections or adhesive couplings), potential equalization between the sensor and fluid must be ensured via additional grounding rings. If grounding rings are missing, this can affect accuracy or result in the destruction of the sensor due to electrochemical electrode reduction. " Caution! · Depending on the order option, appropriate plastic disks are used instead of grounding rings for the process connections. These plastic disks only act as a kind of "place holder" and do not have any potential equalization function whatsoever. In addition, they also assume an important sealing function at the sensor/connection interface. Thus, these plastic disks/seals should never be removed and should always be mounted for process connections without metal grounding rings! · Grounding rings can be ordered separately from Endress+Hauser as an accessory. When ordering, make sure that the grounding rings are compatible with the electrode material. Otherwise there is the risk that electrodes can be damaged by electrochemical corrosion! For information on materials, see the Operating Instructions on the CD-ROM. 28 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 159 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation · Grounding rings, incl. seals, are mounted inside the process connections. The face-to-face length is not affected. Installing the grounding rings 1 = Process connection hexagonal-headed bolts 2 = O-ring seals 4 = Sensor 3 = Grounding ring or plastic disk (place holder) 1 2 32 4 a0008168 a. Release the 4 or 6 hexagonal-headed bolts (1) and remove the process connection from the sensor (4). b. Remove the plastic disk (3) including the two O-ring seals (2) from the process connection. c. Insert one of the O-ring seals (2) back into the groove of the process connection. d. Place the metal grounding ring (3) into the process connection as illustrated. e. Now insert the second O-ring seal (2) into the groove of the grounding ring. f. Mount the process connection back onto the sensor. In doing so, make sure to observe the max. torques for lubricated threads (7 Nm) (5.2 lbf ft). 2.6.3 Welding the sensor into the pipe (weld nipples) " Caution! Risk of destroying the electronics! Make sure that the welding system is not grounded via the sensor or transmitter. a. Secure the sensor with a few welding points in the pipe. A welding jig suitable for this purpose can be ordered separately as an accessory. b. Release the screws on the process connection flange and remove the sensor, including the seal, from the pipe. c. Weld the process connection into the pipe. d. Mount the sensor back into the pipe. In doing so, make sure the seals are clean and correctly positioned. ! Note! · When welding is performed correctly with thin-walled pipes carrying food, the seal is not damaged by the heat even when it is mounted. It is recommended, however, to disassemble the sensor and seal. · For the disassembly work, it must be possible to open the pipe approx. 8 mm (0.31 in) in total. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 29 Page 160 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 2.7 Installing the transmitter housing 2.7.1 Turning the transmitter housing Turning the aluminum field housing Aluminum field housing for non-Ex area b £ 180° d £ 180° e a c Aluminum field housing for Zone 1 or Class I Div. 1 max. 360° b c a Nicht unötfefnreSnpannung Keeciprccouivtseratirgehtalivwehile Keecpirccuoivtseratrieghatliwvehile Nicht-eigensichere Stromkreise durch IP40-Abdeckung geschützt Non-intrinsically safe circuits Ip40 protected Boucles de courant sans sécurité intrinsèque protégées par Ip40 Ne passoouusvtrier ln'siaopnpareil Turning the stainless steel field housing f A0007540 d A0008036 For Zone 1 or Class I Div. 1: a. Release the setscrew. b. Turn the transmitter housing gently clockwise until the stop (end of the thread). c. Turn the transmitter counterclockwise (max. 360°) to the desired position. d. Retighten the setscrew. £ 180° c £ 180° a b 30 Q-Pulse Id: TMS196 26/11/2012 d e A0007661 Endress+Hauser Page 161 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.7.2 Turning the onsite display 4 x 45° b a. Press in the side latches on the display module and remove the module from the cover plate of the electronics compartment. b. Turn the display to the desired position (max. 4 × 45° in both directions) and reset it onto the cover plate of the electronics compartment. a A0007541 2.7.3 Installing the wall-mount housing " Caution! · Make sure that the ambient temperature does not exceed the permitted range. · Always install the wall-mount housing in such a way that the cable entries point downwards. Mounted directly on the wall 35 (1.38) mm (inch) 1. 2. 3. Connection compartment Securing screws M6 (max. ø 6.5 mm (0.25"); screw head max. ø 10.5 mm (0.4") Housing bores for securing screws 2 3 3 81.5 (3.2) 1 90 (3.54) 192 (7.56) A0007542 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 31 Page 162 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Installation Proline Promag 50 Pipe mounting Ø 20...70 (Ø 0.79...2.75) mm (inch) " Caution! Danger of overheating! If the device is mounted on a warm pipe, make sure that the housing temperature does not exceed +60 °C (+140 °F) which is the maximum temperature permitted. ~155 (~ 6.1) Panel mounting A0007543 +0.5 (+0.019) 0.5 (0.019) 210 (8.27) mm (inch) +0.5 (+0.019) 0.5 (0.019) 245 (9.65) ~110 (~4.33) A0007544 32 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 163 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Installation 2.8 Post-installation check · Is the measuring device damaged (visual inspection)? · Does the device correspond to specifications at the measuring point, including process temperature and pressure, ambient temperature, minimum fluid conductivity, measuring range, etc.? · Does the arrow on the sensor nameplate match the actual direction of flow through the pipe? · Is the position of the measuring electrode plane correct? · Were all screws tightened to the specified torques when the sensor was installed? · Were the correct seals used (type, material, installation)? · Are the measuring point number and labeling correct (visual inspection)? · Were the inlet and outlet runs respected? Inlet run 5 × DN Outlet run 2 × DN · Is the measuring device protected against moisture and direct sunlight? · Is the sensor adequately protected against vibration (attachment, support)? Acceleration up to 2 g by analogy with IEC 600 68-2-8 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 33 Page 164 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Wiring Proline Promag 50 3 Wiring # Warning! Risk of electric shock! Components carry dangerous voltages. · Never mount or wire the measuring device while it is connected to the power supply. · Before connecting the power supply, check the safety equipment. · Route the power supply and signal cables so they are securely seated. · Seal the cable entries and covers tight. " Caution! Risk of damaging the electronic components! · Connect the power supply in accordance with the connection data on the nameplate. · Connect the signal cable in accordance with the connection data in the Operating Instructions or the Ex documentation on the CD-ROM. In addition, for the remote version " Caution! Risk of damaging the electronic components! · Only connect sensors and transmitters with the same serial number. · Observe the cable specifications of the connecting cable Operating Instructions on the CD-ROM. ! Note! Install the connecting cable securely to prevent movement. In addition, for measuring devices with fieldbus communication " Caution! Risk of damaging the electronic components! · Observe the cable specification of the fieldbus cable Operating Instructions on the CD-ROM. · Keep the stripped and twisted lengths of cable shield as short as possible. · Screen and ground the signal lines Operating Instructions on the CD-ROM. · When using in systems without potential equalization Operating Instructions on the CD-ROM. In addition, for Ex-certified measuring devices # Warning! When wiring Ex-certified measuring devices, all the safety instructions, wiring diagrams, technical information etc. of the related Ex documentation must be observed Ex documentation on the CD-ROM. 34 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 165 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Wiring 3.1 Connecting the various housing types Wire the unit using the terminal assignment diagram inside the cover. 3.1.1 Compact version Transmitter connection: 1 Connection diagram inside the connection compartment 3 cover 4 2 Power supply cable 2 3 Signal cable or fieldbus cable 4 Optional 1 A0007545 3.1.2 Remote version (transmitter): non-Ex Zone, Ex Zone 2, Class I Div. 2 234 5 1 Transmitter connection: 1 Connection diagram inside the connection compartment cover 2 Power supply cable 3 Signal cable 4 Fieldbus cable Connecting the connecting cable ( ä 36): 5 A0012690 Sensor/transmitter connecting cable 3.1.3 Remote version (transmitter): Ex Zone 1, Class I Div. 1 3 4 2 Keeciprccuoitvseratrieghatlivwehile Ne psaosuso tuevrnirsil'oanppareil Nicht uönftfenreSnpannung Keecpirccuoitvserartieghatlivwehile 1 Transmitter connection: 1 Connection diagram inside the connection compartment cover 2 Power supply cable 3 Signal cable or fieldbus cable 4 Optional 5 1 Connecting the connecting cable ( ä 36): 5 Sensor/transmitter connecting cable A0008218 3.1.4 Remote version (sensor) Transmitter connection: 1 Connection diagram inside the connection compartment 5 1 cover Connecting cable connection: 5 A0008037 Sensor/transmitter connecting cable Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 35 Page 166 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Wiring Proline Promag 50 3.2 Connecting the remote version connecting cable 3.2.1 Connecting cable for Promag W, P and L Connecting cable termination Terminate the signal and coil current cables as shown in the figure below (Detail A). Fit the fine-wire cores with cable end ferrules (Detail B). Signal cable termination Make sure that the cable end ferrules do not touch the wire shields on the sensor side! Minimum distance = 1 mm (0.04 in), exception "GND" = green cable. Sensor Transmitter mm (inch) a* = 170 (6.69) b* = 20 (0.79) c = 80 (3.15) d = 17 (0.67) e = 8 (0.31) f = 50 (1.97) g = 1 ( 0.04) a* b* c d e f m B n g n GND nm a* b cd e m m n m GND n m n n mm (inch) a* = 100 (3.94) b = 80 (3.15) c = 50 (1.97) d = 17 (0.67) e = 8 (0.31) a0008171 m = Cable end ferrules, red, 1.0 mm (0.04"); n = Cable end ferrules, white, 0.5 mm (0.02") * = Stripping for armored cables only A A Coil current cable termination Insulate one core of the three-core cable at the level of the core reinforcement; you only require two cores for the connection. mm (inch) a* = 160 (6.3) b* = 20 (0.79) c = 70 (2.76) d = 50 (1.97) e = 8 (0.31) f = 10 (0.39) Sensor a* b* c d ef Transmitter a* b c de mm (inch) a* = 90 (3.54) b = 70 (2.76) c = 50 (1.97) d = 10 (0.39) e = 8 (0.31) m B m m m m m a0008172 m = Cable end ferrules, red, 1.0 mm (0.04"); n = Cable end ferrules, white, 0.5 mm (0.02") * = Stripping for armored cables only 36 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 167 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Wiring A A 3.2.2 Promag H connecting cable Connecting cable termination Terminate the signal and coil current cables as shown in the figure below (Detail A). Fit the fine-wire cores with cable end ferrules (Detail B). Signal cable termination Make sure that the cable end ferrules do not touch the wire shields on the sensor side! Minimum distance = 1 mm (0.04 in), exception "GND" = green cable. Sensor Transmitter mm (inch) a = 80 (3.15) b = 15 (0.59) c = 17 (0.67) d = 8 (0.31) e = 1 ( 0.04) a c d b a bc mm (inch) a = 80 (3.15) b = 50 (1.97) c = 17 (0.67) d = 8 (0.31) n n e n GND m d B m m n m GND n m n n a0008173 m = Cable end ferrules, red, 1.0 mm (0.04"); n = Cable end ferrules, white, 0.5 mm (0.02") Coil current cable termination Insulate one core of the three-core cable at the level of the core reinforcement; you only require two cores for the connection. mm (inch) a = 70 (2.76) b = 40 (1.57) c = 15 (0.59) d = 8 (0.31) Sensor a b d c Transmitter a b cd mm (inch) a = 70 (2.76) b = 50 (1.97) c = 10 (0.39) d = 8 (0.31) B m m m m m a0008175 m = Cable end ferrules, red, 1.0 mm (0.04"); n = Cable end ferrules, white, 0.5 mm (0.02") Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 37 Page 168 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Wiring Proline Promag 50 3.2.3 Connecting cable connection A B S1 E1 E2 S2GND E S Nicht uönftfenreSnpannung Keecpirccuoivtserartieghatlivwehile 6 5 7 8 4 37 36 a 42 41 Keeciprccuoitvseratrieghatlivwehile Ne psaosuso tuevrnirsil'oanppareil b c bc a b cb cb c n.c. n.c. n.c. b 5 7 4 37 E1 E2 GNDE C D E 42 41 A Transmitter housing on connection housing, remote version B Wall-mount housing on connection housing, remote version C Sensor connection housing, remote version for Promag W, P, L D Sensor connection housing, remote version for Promag H, DN 25 E Sensor connection housing, remote version for Promag H, DN 40 a Ground terminals (are provided for potential equalization connection) b Coil circuit connecting cable c Signal circuit connecting cable (electrodes) n.c. = not connected, isolated cable shields Cable colors for terminal numbers: 5/6 = brown 7/8 = white 4 = green 36/37 = yellow A0008180 38 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 169 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Wiring 3.3 Potential equalization Perfect measurement is only ensured when the medium and the sensor have the same electrical potential. Most sensors have a reference electrode installed as standard, which guarantees the required potential connection. This usually means that the use of ground disks or other measures are unnecessary. · Promag L, Promag W and Promag P Reference electrode available as standard. · Promag H No reference electrode available. There is always an electrical connection to the fluid via the metal process connection. In the case of plastic process connections, potential equalization must be ensured through the use of grounding rings. Standard situation Potential equalization takes place via the ground terminal of the transmitter when using the device in metal, grounded pipes. A0004375 ! Note! Potential equalization for other areas of application Operating Instructions on the CD-ROM. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 39 Page 170 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Wiring Proline Promag 50 3.4 Degree of protection The devices meet all the requirements for IP 67. After mounting in the field or service work, the following points have to be observed to ensure that IP 67 protection is retained: · Install the measuring device in such a way that the cable entries do not point upwards. · Do not remove the seal from the cable entry. · Remove all unused cable entries and plug them with suitable/certified drain plugs. · Use cable entries and drain plugs with a long-term operating temperature range in accordance with the temperature specified on the nameplate. Tighten the cable entries correctly. A0007549 A0007550 The cables must loop down before they enter the cable entries ("water trap"). 3.5 Post-connection check · Are cables or the device damaged (visual inspection)? · Does the supply voltage match the information on the nameplate? · Do the cables used comply with the necessary specifications? · Do the mounted cables have adequate strain relief and are they routed securely? · Is the cable type route completely isolated? Without loops and crossovers? · Only remote version: - Is the flow sensor connected to the matching transmitter electronics? - Is the connecting cable between sensor and transmitter connected correctly? · Are all screw terminals firmly tightened? · Have all the measures for grounding and potential equalization been correctly implemented? · Are all cable entries installed, firmly tightened and correctly sealed? · Cable routed as a "water trap" in loops? · Are all the housing covers installed and securely tightened? In addition, for measuring devices with fieldbus communication: · Are all the connecting components (T-boxes, junction boxes, connectors, etc.) connected with each other correctly? · Has each fieldbus segment been terminated at both ends with a bus terminator? · Has the max. length of the fieldbus cable been observed in accordance with the specifications? · Has the max. length of the spurs been observed in accordance with the specifications? · Is the fieldbus cable fully shielded and correctly grounded? 40 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 171 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Hardware settings 4 Hardware settings This section only deals with the hardware settings needed for commissioning. All other settings (e.g. output configuration, write protection, etc.) are described in the associated Operating Instructions on the CD-ROM. ! Note! No hardware settings are needed for measuring devices with HART or FOUNDATION Fieldbus-type communication. 4.1 Device address Has to be set for measuring devices with the following communication methods: · PROFIBUS DP/PA The device address can be configured via: · Miniature switches see description below · Local operation see Software settings section ä 48 Addressing via miniature switches # Warning! Risk of electric shock! Risk of damaging the electronic components! · All the safety instructions for the measuring device must be observed and all the warnings heeded ä 34. · Use a workspace, working environment and tools purposely designed for electrostatically sensitive devices. # Warning! Switch off the power supply before opening the device. W E N O W E N O W E N O W E N O W E N O W E N O a. Loosen the cheese head screw of the securing clamp with an Allen key (3 mm) 1 2 3 4 1 2 3 4 1 2 3 4 b. Unscrew cover of the electronics compartment from the transmitter housing. c. Loosen the securing screws of the display module and remove the onsite display (if present). c a b d 1 2 3 4 1 2 3 4 1 2 3 4 A0007551 d. Set the position of the miniature switches on the I/O board using a sharp pointed object. Installation is the reverse of the removal procedure. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 41 Page 172 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Hardware settings Proline Promag 50 PROFIBUS OFF ON 1 1 2 2 3 4 4 8 a 1 16 2 32 3 64 4 b 1 2 c 3 4 OFF ON OFF 1 2 3 4 1 2 3 4 1 2 3 4 OFF A0007552 Device address range: 0 to 126 Factory setting: 126 a. Miniature switches for device address Example shown: 1+16+32 = device address 49 b. Miniature switches for the address mode (method of addressing): OFF (factory setting) = software addressing via local operation/operating program ON = hardware addressing via miniature switches c. Miniature switches not assigned. 42 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 173 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Hardware settings 4.2 Terminating resistors ! Note! If the measuring device is used at the end of a bus segment, termination is required. This can be performed in the measuring device by setting the terminating resistors on the I/O board. Generally, however, it is recommended to use an external bus terminator and not perform termination at the measuring device itself. Has to be set for measuring devices with the following communication methods: · PROFIBUS DP Baudrate 1.5 MBaud Termination can be performed at the measuring device, see graphic Baudrate > 1.5 MBaud An external bus terminator must be used # Warning! Risk of electric shock! Risk of damaging the electronic components! · All the safety instructions for the measuring device must be observed and all the warnings heeded ä 34. · Use a workspace, working environment and tools purposely designed for electrostatically sensitive devices. Setting the terminating switch SW1 on the I/O board: ON - ON - ON - ON 1 2 3 4 1 2 3 4 1 2 3 4 W E N O W E N O W E N O W E N O W E N O W E N O W E N O 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 +5V SW 1 1 2 3 4 OFF ON 390 W 220 W 390 W A0007556 Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 43 Page 174 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Commissioning Proline Promag 50 5 Commissioning 5.1 Switching on the measuring device On completion of the installation (successful post-installation check), wiring (successful post-connection check) and after making the necessary hardware settings, where applicable, the permitted power supply (see nameplate) can be switched on for the measuring device. When the power supply is switched on, the measuring device performs a number of power-up checks and device self-checks. As this procedure progresses the following messages can appear on the onsite display: Display examples: PROMAG 50 START-UP Æ DEVICE SOFTWARE V XX.XX.XX Æ SYSTEM OK OPERATION Start-up message Displays the current software Beginning of operation The measuring device starts operating as soon as the startup procedure is complete. Various measured values and/or status variables appear on the display. ! Note! If an error occurs during startup, this is indicated by an error message. The error messages that occur most frequently when a measuring device is commissioned are described in the Troubleshooting section ä 48. 44 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 175 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Commissioning 5.2 Operation 5.2.1 Display elements 3 4 1 +48.25 xx/yy 2 +3702.6 x Display lines/fields 1. Main line for primary measured values 2. Additional line for additional measured variables/status variables 3. Current measured values 4. Engineering units/time units A0007557 5.2.2 Operating elements Esc -+ 1 2 Operating keys E 1. () Minus key for entering, selecting 2. (+) Plus key for entering, selecting 3. Enter key for calling the function matrix, saving 3 When the +/ keys are pressed simultaneously (Esc): A0007559 · Exit the function matrix step-by-step: · > 3 sec. = cancel data input and return to the measured value display 5.2.3 Displaying error messages 1. Type of error: 1 P XXXXXXXXXX 5 P = Process error, S = System error 2. Error message type: 2 #000 00:00:05 $ = Fault message, ! = Notice message 3. Error number 3 4 4. Duration of the last error that occurred: Hours: Minutes: Seconds A0007561 5. Error designation List of all error messages, see associated Operating Instructions on the CD-ROM Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 45 Page 176 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Commissioning Proline Promag 50 5.3 Navigating within the function matrix Esc -+ Esc E q+ Esc r+ >3s mE o E + q EEEE p n + E E A0007562 1. F Enter the function matrix (starting with measured value display) 2. P Select the group (e.g. OPERATION) F Confirm selection 3. N Select function (e.g. LANGUAGE) 4. P Enter code 50 (only for the first time you access the function matrix) F Confirm entry P Change function/selection (e.g. ENGLISH) F Confirm selection 5. Q Return to measured value display step by step 6. Q > 3 s Return immediately to measured value display 46 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 177 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Proline Promag 50 Commissioning 5.4 Calling the Commissioning Quick Setup All the functions needed for commissioning are called up automatically with the Quick Setup. The functions can be changed and adapted to the process in question. 1. F Enter the function matrix (starting with measured value display) 2. P Select the group QUICK SETUP F Confirm selection 3. QUICK SETUP COMMISSIONING function appears. 4. Intermediate step if configuration is blocked: P Enter the code 50 (confirm with F ) and thus enable configuration 5. P Go to Commissioning Quick Setup 6. P Select YES F Confirm selection 7. F Start Commissioning Quick Setup 8. Configure the individual functions/settings: Via P-key, select option or enter number Via F-key, confirm entry and go to next function Via Q-key, return to Setup Commissioning function (settings already made are retained) ! Note! Observe the following when performing the Quick Setup: · Configuration selection: Select the ACTUAL SETTING option · Unit selection: This is not offered again for selection after configuring a unit · Output selection: This is not offered again for selection after configuring an output · Automatic configuration of the display: select YES Main line = Mass flow Additional line = Totalizer 1 Information line = Operating/system conditions · If asked whether additional Quick Setups should be executed: select NO All the available functions of the measuring device and their configuration options as well as additional Quick Setups, if available, are described in detail in the "Description of Device Functions" Operating Instructions. The related Operating Instructions can be found on the CD-ROM. The measuring device is ready for operation on completion of the Quick Setup. Endress+Hauser Q-Pulse Id: TMS196 26/11/2012 47 Page 178 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Commissioning Proline Promag 50 5.5 Software settings 5.5.1 Device address Has to be set for measuring devices with the following communication methods: · PROFIBUS DP/PA device address range 0 to 126, factory setting 126 The device address can be configured via: · Miniature switches see Hardware settings ä 41 · Local operation see description below ! Note! The COMMISSIONING SETUP must be executed before setting the device address. Calling the Communication Quick Setup 1. F Enter the function matrix (starting with measured value display) 2. P Select the group QUICK SETUP F Confirm selection 3. N Select the QUICK SETUP COMMUNICATION function 4. Intermediate step if configuration is blocked: P Enter the code 50 (confirm with F ) and thus enable the configuration 5. P Go to Communication Quick Setup 6. P Select YES; F confirm selection 7. F Start Communication Quick Setup 8. Configure the individual functions/settings: Via P-key, select option or enter number Via F-key, confirm entry and go to next function Via Q-key, return to Setup Commissioning function (settings already made are retained) All the available functions of the measuring device and their configuration options as well as additional Quick Setups, if available, are described in detail in the "Description of Device Functions" Operating Instructions. The related Operating Instructions can be found on the CD-ROM. The measuring device is ready for operation on completion of the Quick Setup. 5.6 Troubleshooting A complete description of all the error messages is provided in the Operating Instructions on the CD-ROM. ! Note! The output signals (e.g. pulse, frequency) of the measuring device must correspond to the higher-order controller. 48 Q-Pulse Id: TMS196 26/11/2012 Endress+Hauser Page 179 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4.5 PUSHBUTTONS & SELECTOR SWITCHES Sprecher & schuh D5P-MTS34-3LX025 Stop pushbutton Kraus & Naimer CAD11-A201-600-FT2 Local / Remote Switch Kraus & Naimer CAD11-A212 Engraved "FIRE-OFF-CONTROL" Selector Switch Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 180 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual D7P-MT64-PX01S D7M-MK44-MX01S D7 Control and indication products 22.5 mm Complete emergency stop operators - panel & enclosed type Emergency stop operators 2 Choice of "Auto Break" or standard normally closed contacts 30, 40 or 60 mm mushroom head Extra security key release Pushbutton & Key operated types Description Contact Twist To Reset/Standard contact blocks 30 mm Operator 40 mm Operator 60 mm Operator Key To Reset/Standard contact blocks 40 mm Operator Twist To Reset/"Auto Break" Safety contact blocks 30 mm Operator 40 mm Operator 60 mm Operator Key To Reset/"Auto Break" Safety contact blocks 40 mm Operator Plastic body Cat. No. 1) D7P-MT34-PX01 D7P-MT44-PX01 D7P-MT64-PX01 D7P-MK44-PX01 D7P-MT34-PX01S D7P-MT44-PX01S D7P-MT64-PX01S D7P-MK44-PX01S Metal body Price $ Cat. No. 1) Price $ D7M-MT34-MX01 D7M-MT44-MX01 D7M-MT64-MX01 D7M-MK44-MX01 D7M-MT34-MX01S D7M-MT44-MX01S D7M-MT64-MX01S D7M-MK44-MX01S D71YM1 D71MM1 Enclosed emergency stop operators Modern low profile enclosures Supplied complete Metric cable entry 20 mm Plastic or Metal enclosures Dimensions in (mm) Description Contact Plastic enclosures with emergency stop "Twist To Reset" operator Yellow enclosure 40 mm plastic operator Plastic enclosures with emergency stop "Twist Key To Reset" operator Yellow enclosure 40 mm plastic operator Metal enclosures with emergency stop "Twist To Reset" operator Grey enclosure 40 mm metal operator Metal enclosures with emergency stop "Twist Key To Reset" operator Grey enclosure 40 mm metal operator Cat. No. D71YM1 D71YM4 D71MM1 D71MM4 Note: 1) Add suffix "bx" for special box/hang-sell packaging eg: D7P-MT34-PX01bx Price $ Price Schedule `A2' Q-Pulse Id: TMS196 GST not included 26/11/2012 2 - 9 Page 181 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual D7 Control and indication products 22.5 mm Industrial control switches emergency stop operators 2 D7P-MT44 D7M-MT64 Panel mounted front and rear elements D7PMT Plastic, twist to release emergency stop Protection class IP 66 operators Individually packaged 2 D7MMT Metal, twist to release emergency stop operators 2 part ordering 1 D7PLMT Plastic, twist to release illuminated emergency stop operators D7MLMT Metal, twist to release illuminated emergency stop operators 1 Mushroom operators Description Nonilluminated Plastic Cat. No. Nonilluminated Metal Price $ Cat. No. Illuminated Plastic Price $ Cat. No. Illuminated Metal Price $ Cat. No. 30 mm Red operator D7P-MT34 D7M-MT34 - - 40 mm Red operator D7P-MT44 D7M-MT44 D7P-LMT44 D7M-LMT44 60 mm Red operator D7P-MT64 D7M-MT64 D7P-LMT64 D7M-LMT64 Price $ D7P-MK44 D7PMK D7MMK Description Plastic key-release emergency stop operators Metal key-release emergency stop operators Nonilluminated Plastic Cat. No. 40 mm Red operator D7P-MK44 Nonilluminated Metal Price $ Cat. No. D7M-MK44 Price $ D7PX / D7PQ Pre-assembled clip-on rear elements with plastic coupling plate D7MX / D7MQ Pre-assembled clip-on rear elements with metal coupling plate Contact/lamp blocks 3) 2 Description 1 N/O contact block 1 N/C contact block 1 N/O and 1 N/C contact block Safety "Auto Break" 1 N/C contact block 1 N/O and 1 N/C contact block and integrated LED lamp block Screw Cat. No. D7PX10 D7PX01 D7PX11 Spring clamp Price $ Cat. No. D7PQ10 D7PQ01 D7PQ11 Metal screw Price $ Cat. No. D7MX10 D7MX01 D7MX11 Metal spring clamp Price $ Cat. No. D7MQ10 D7MQ01 D7MQ11 Price $ D7PX01S - D7MX01S - D7PN1) 2)X11 D7PQ1) 2)Q11 D7MN1) 2)X11 D7MQ 1) 2)Q11 Notes: 1) enter voltage 24V AC/DC = 3, 120V AC = 5, 240V AC = 7 2) enter lamp colour C = clear (incandescent), R = Red LED, G = Green LED, Y = Yellow LED, W = White LED, B = Blue LED - Example D7PN3RX11 = 24 V AC/DC RED integrated LED lamp block (Price shown is for 110/240 VAC) 3) Safety "Auto Break" and additional contact blocks available refer page 2-34 Price Schedule `A2' 2 - 10 Q-Pulse Id: TMS196 GST not included 26/11/2012 Page 182 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual D7 Control and indication products 22.5 mm Technical information Front-of-Panel (Operators) 1) Mechanical Ratings Vibration (assembled to panel) (G) Shock (G) Degree of protection 2) Mechanical durability per 10,000,000 Cycles EN 60947 (Annex C) 1,000,000 Cycles 500,000 Cycles 300,000 Cycles Operating forces (N) (typical with one contact block) Operating torque (typical application with one contact block) Environmental Temperature range (operating) 3) Temperature range (short-term storage) Humidity (N-m) (°C) (°C) (%) Plastic (D7P) Metal (D7M) Tested at 10...2000 Hz, 1.52 mm displacement (peak-to-peak) max./G max. for 3 hr duration, no damage Tested at 1/2 cycle sine wave for 11 ms; no damage at 100 G UL Type 3/3R/4/4X/12/13 (IP 65/66) UL Type 3/3R/4/12/13 (IP 65/66) Pushbuttons, momentary mushroom Multi-function Push-pull mushroom E-stops, selector switches Flush/extended = 5N E-stop = 36N Mushroom = 9N Selector switch = 0.25 N-m -25...+70 °C (-13...+158 °F) -25...+85 °C (-13...+185 °F) 50...95% RH from 25...60 °C (77...140 °F) per: procedure IV of MIL-STD-810C, Method 507.1 cycling test 2 Back-of-Panel (Components) 1) Electrical Ratings Standard contact block rating Low voltage contact block 4) Thermal current Wire capacity Insulation voltage (A) Screw terminal (AWG) Spring-clamp terminal (AWG) (Ui) Dielectric strength (minimum) External Standard short blocks circuit Low voltage protection contact blocks Electrical shock protection AC 15, DC 13 to EN 60947-5-1 and UL 508, 17 V, 5 mA min. A600,Q600 600 V AC 5 V, 1 mA DC min. C300, R150, AC 15, DC 13 to EN 60947-5-1 and UL 508 10 A max. enclosed (40 °C ambient) to UL 508, EN 60947-5-1 #18...12 AWG (0.75...2.5 mm 2) Max. (2) #14 AWG or (1) #12 AWG #18...14 AWG (0.75...1.5 mm 2) Ui = 680 V (screw terminal) Ui = 300 V (screwless terminal) (V) 2200 V for one minute 10 A type gL/gG cartridge fuse to EN 60269-2-1 or gN (Class J to UL 248-8 or Class C to UL 348-4) 6 A type gL/gG cartridge fuse to EN 60269-2-1 or gN (Class J to UL 248-8 or Class C to UL 348-4) Finger-safe conforming to IP2X Notes: 1) Performance data given in this publication is provided only as a guide for the user in determining suitability and do not constitute a performance warranty of any kind. Such data may represent the results of accelerated testing at elevated stress levels, and the user is responsible for correlating the data to actual application requirements. 2) Momentary mushroom operators are IP 65, multi-function operators have no Type 13 rating. Plastic operators with keys have no Type 4X rating. 3) Operating temperatures below 0 °C (32 °F) are based on the absence of freezing moisture and liquids. 4) Low voltage contacts are recommended for applications below 17 V, 5 mA. Q-Pulse Id: TMS196 26/11/2012 2 - 49 Page 183 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual D7 Control and indication products 22.5 mm Technical information 2 Back-of-Panel (Operators) 1), continued Mechanical Ratings Vibration (assembled to panel) (G) Shock (G) Contact durability per EN 60947-5-1 (Annex C) Contact N/O operation N/C N/O E.M. N/C L.B. Opening forces (typical) (N) 10...2000 Hz, 1.52 mm displacement (peak-to-peak) max./10 G max. 6 hr Tested at 1/2 cycle sine wave for 11 ms and no damage at 100 G max. 10,000,000 cycles Slow make, double break Slow make, double break (positive opening) Early make, double break Late break, double break (positive opening) 3.4 N: each single circuit contact block 5...6.6 N: each dual circuit contact block Note: 1) Performance data given in this publication is provided only as a guide for the user in determining suitability and do not constitute a performance warranty of any kind. Such data may represent the results of accelerated testing at elevated stress levels, and the user is responsible for correlating the data to actual application requirements. Rated operating current Ie 24 V 48 V 110 V 220 V 230/240 V AC 1 10 A 10 A AC 15 8A 8A 6A 3A 3A 380 V 400 V 415 V 500 V 690 V AC 1 AC 15 2.5 A 2 A 2.2 A 1.5 A 0.75 A Rated operating current Ie, continued DC 13 24 V 48 V 110 V 125 V 220 V -01, -10 3 A 1.5 A 0.2 A 0.6 A 0.1 A -01, -E10 1.3 A 0.4 A 0.13 A 0.13 A 65 mA DC 13 250 V 400 V 440 V 500 V 600 V -01, -10 0.3 A 0.2 A 0.04 A 0.15 A 0.13 A -01, -E10 65 mA 26 mA 26 mA Short-circuit withstand without welding 10 A slow (DT, gG) Switching rate 6000 operations/hour Fuse rating permissible rated current fast (D, gF) 16 A slow (DT, gG) 10 A Versions Panel mounting -01 -10 O1L 10E . 1 . 2 .3 .4 .5 .6 .7 .8 Snap-on to coupling plate 2 contact levels up to 3 contact blocks per contact level Base mounting -01 -10 O1L 10E . 1 . 2 .3 .4 .5 .6 .7 .8 Snap-on to the inside of the enclosure base or onto a DIN rail, or secure with two screwed fixing straps 3 contact blocks in one contact level possible Possibilities to combine (Panel mounting) Maximum of 6 contact blocks can be combined Electrical life AC 11 0.1 A 1 A 2 A 3 A No. of operations (millions) 10 3 1 0.5 Contact duty electronic circuit (H-type- bridges) positive opening for: D7X01, D7BX01 Contact travel D7 Terminal marking according to DIN EN 50 013 Terminals 0.75...2.5 mm2 18...12 AWG 2 - 50 Q-Pulse Id: TMS196 open closed 26/11/2012 Page 184 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual D7 Control and indication products 22.5 mm Technical information Back-of-Panel (Components) 1), continued 2 Lamp elements D7-DOC Versions D7-DOC D7-N_ D7-Q_ X1 X2 Standard element Operating voltage max. 250 V D7-BN_ D7-N D7-BN D7-Q X1 Panel or base mount Small overall depth Easy to wire Screw or spring connection X2 Technical information D7-DOC Lamp socket Lamp rating max Insulation voltage Terminal marking Terminals Ba9s 2 W (2.6 W for pilot lights) Ui 250 V according to DIN EN 50 013 Screw / spring 0.75...2.5 mm2 D7-N D7-BN D7-Q LED Module Ratings Nominal Voltage 24 V AC 24 V DC 120 V AC 240 V AC Range 10...29 V AC 10...30 V DC 70...132 V AC 180...264 V AC Current Draw 31 mA 24 mA 25 mA 22 mA Frequency 50/60 Hz DC 50/60 Hz 50/60 Hz Q-Pulse Id: TMS196 26/11/2012 2 - 51 Page 185 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual D7 Control and indication products 22.5 mm Material listing 2 Component For use with Panel gasket All operators Diaphragm seal Illuminated pushbutton, non-illuminated pushbutton K-seal Selector switch, key selector switch, push/twist-to-release E-stop, key E-stop, push/pull mushroom Diaphragm retainer, return spring I Illuminated pushbutton, non-illuminated pushbutton, momentary mushroom, push/twist-to-release E-stop, key E-stop, push/pull mushroom Return spring II Reset, selector switch, key selector switch Button cap/mushroom head Non-illuminated pushbutton, momentary mushroom, reset, push/twist-to-release E-stop, key E-stop, push/pull mushroom, multi-function 2 colour moulded button insert Non-illuminated pushbutton Lens Multi-function Lens knob Illuminated pushbutton, illuminated momentary mushroom, illuminated selector switch Plastic bezel/bushing I Non-illuminated pushbutton, illuminated pushbutton, momentary mushroom, selector switch, key selector switch, push/twist-to-release E-stop, key E-stop, push/pull mushroom, multi-function Plastic bezel/bushing II, jam nut, knob Reset, non-illuminated selector switch, pilot light Metal bezel/bushing All metal operators Diffuser Illuminated pushbutton, pilot light Legend frames - Plastic mounting ring All plastic operators Metal mounting ring All metal operators Plastic coupling plate - Metal coupling plate - Plastic enclosures - Metal enclosure - Terminal screws LED module, incandescent module, contact blocks Terminals LED module, incandescent module, contact blocks Screwless LED module, incandescent module, contact blocks Lamp socket Incandescent module Housing Incandescent module, LED module Low voltage terminals Contact blocks Low voltage spanner Contact blocks Spanner Contact blocks Material used Nitrile Automotive acceptable silicone Nitrile Stainless steel Zinc coated music wire PBT/polycarbonate blend PBT/polycarbonate blend Acetal Polyamide Glass-filled polyamide Glass-filled polyamide Zinc Polycarbonate Glass-filled nylon Glass-filled polyamide Chromated zinc Glass-filled nylon Chromated zinc + stainless steel PBT/polycarbonate blend Aluminium Zinc-plated steel with chromate Brass with silver-nickel contacts Stainless steel Brass Glass-filled nylon Gold-plated brass with silver-nickel contacts Gold-plated brass with silver-nickel contacts Brass with silver-nickel contacts 2 - 52 Q-Pulse Id: TMS196 26/11/2012 Page 186 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual D7 Control and indication products 22.5 mm Technical information Back-of-Panel (Components) 1), continued Illumination LED dominant wavelength Green Red Yellow Blue White LED luminous intensity Green Red Yellow Blue White Incandescent maximum wattage Environmental Temperature range (operating) 2) Temperature range (short-term storage) Humidity (nm) (mcd) (W) (°C) (°C) (%) Materials Springs Electrical contacts Terminals Standard Low voltage Screw Screwless Plastic (D7P) 525 nm 629 nm 590 nm 470 nm Metal (D7M) 890 mcd 890 mcd 690 mcd 193 mcd 412 mcd 1W -25...+70 °C (-13...+158 °F) -25...+85 °C (-13...+185 °F) tested at 50...95 % relative humidity from 25...60 °C (77...140 °F) per: procedure IV of MIL-STD-810C, Method 507.1 cycling test Stainless steel and zinc coated music wire Silver-nickel Gold-plated over silver Brass Silver-plated copper Environmental approval note: Front elements UL Recognised; Complete assemblies UL Approved. See Table A2 (below) for your application. This table is extracted from Sprecher + Schuh's UL 508A file and can be used to determine which D7 pilot device is approved for a particular enclosure type. Enclosure type 2 3 3R 3S 4 4X 6 6P 11 12, 12K 13 TABLE A2 - Openings in enclosure Openings may be closed by equipment marked... 2, 3, 3R, 3S, 4, 4X, 6, 6P, 11, 12, 12K, 13 3, 3R, 3S, 4, 4X, 6, 6P 3, 3R, 3S, 4, 4X, 6, 6P 3, 3R, 3S, 4, 4X, 6, 6P 4, 4X, 6, 6P 4X 6, 6P 6P 11 12, 12K, 13 13 Product certification Certifications Standards Terminal identification Shipping approvals UL. UR, CSA, CCC, CE NEMA ICS-5; UL 508, EN 418, EN 60947-1, EN 60947-5-1, EN 60947-5-5 IEC 60947-1 RINA, LR, ABS Notes: 1) Performance data given in this publication is provided only as a guide for the user in determining suitability and do not constitute a performance warranty of any kind. Such data may represent the results of accelerated testing at elevated stress levels, and the user is responsible for correlating the data to actual application requirements. 2) Operating temperatures below 0 °C (32 °F) are based on the absence of freezing moisture and liquids. 2 Q-Pulse Id: TMS196 26/11/2012 2 - 53 Page 187 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 188 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 189 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 190 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 191 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 192 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 193 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 194 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 195 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 196 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4.6 TERMINALS & LINKS Phoenix Contact UT4-HESI LED 24 (5x20) Fused Terminal with LED 24v Phoenix Contact M205 Fuse Cartridges Phoenix Contact UT4-MT P/P Disconnect Terminals Phoenix Contact UT4-MTD-PE/S Earth Terminals Phoenix Contact UBE Group Marker Carrier Phoenix Contact PS6 Test Plug Adapter Phoenix Contact SZS 0.6x3.5 Screw Driver Phoenix Contact FBS Plug-In Bridge Phoenix Contact MSTB 2.5/20-ST-2.08 Disconnect Plugs Phoenix Contact UMSTBVKZ 2.5/20-G-5.08 Disconnect Blocks Phoenix Contact KGS-MSTB 2.5/20 Cable Housing Phoenix Contact CP-MSTB + CR-MSTB Coding Pins D&L 2DLA18 18 Hole Neutral Link D&L 2DLAE18 18 Hole Earth Link D&L DLBE12 12 Hole Instrument Earth Link Clipsal L7 7 Hole Link Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 197 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-HESI (5X20) Order No.: 3046032 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046032 Fuse modular terminal block, Connection method: Screw connection, Cross section: 0.14 mm²- 6 mm², AWG: 26 - 10, Nominal current: 6.3 A, Nominal voltage: 500 V, Width: 6.2 mm, Fuse type: G / 5 x 20, Fuse type: Glass, Mounting type: NS 35/7,5, NS 35/15, Color: black Commercial data EAN Pack Customs tariff Weight/Piece Catalog page information 4017918956578 50 pcs. 85369010 0.018103 KG Page 44 (CL-2009) Technical data General Number of levels Number of connections Color 1 2 black Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 1 / 5 May 6, 2009 Page 198 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-HESI (5X20) Order No.: 3046032 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046032 Insulating material PA Inflammability class acc. to UL 94 V0 Dimensions Width Length Height NS 35/7,5 Height NS 35/15 6.2 mm 57.8 mm 73 mm 80.5 mm Technical data Fuse Fuse type Rated surge voltage Pollution degree Surge voltage category Insulating material group Connection in acc. with standard Nominal current IN Nominal voltage UN G / 5 x 20 Glass 4 kV 3 III I IEC 60947-7-3 6.3 A 500 V (if used as fuse terminal block) 500 V (if used as disconnect terminal block) Connection data Conductor cross section solid min. Conductor cross section solid max. Conductor cross section stranded min. Conductor cross section stranded max. Conductor cross section AWG/kcmil min. Conductor cross section AWG/kcmil max Conductor cross section stranded, with ferrule without plastic sleeve min. Conductor cross section stranded, with ferrule without plastic sleeve max. Conductor cross section stranded, with ferrule with plastic sleeve min. Conductor cross section stranded, with ferrule with plastic sleeve max. 2 conductors with same cross section, solid min. 2 conductors with same cross section, solid max. 0.14 mm² 6 mm² 0.14 mm² 6 mm² 26 10 0.14 mm² 4 mm² 0.14 mm² 4 mm² 0.14 mm² 1.5 mm² PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 2 / 5 May 6, 2009 Page 199 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-HESI (5X20) Order No.: 3046032 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046032 2 conductors with same cross section, stranded min. 2 conductors with same cross section, stranded max. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. Type of connection Stripping length Internal cylindrical gage Screw thread Tightening torque, min Tightening torque max 0.14 mm² 1.5 mm² 0.14 mm² 1.5 mm² 0.5 mm² 2.5 mm² Screw connection 9 mm A4 M3 0.6 Nm 0.8 Nm Certificates / Approvals Certification CSA Nominal voltage UN Nominal current IN AWG/kcmil CUL Nominal voltage UN Nominal current IN AWG/kcmil UL Nominal voltage UN Nominal current IN AWG/kcmil PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 CB, CSA, CUL, DNV, GL, KEMA, LR, UL 600 V 6.3 A 26-10 600 V 6.3 A 26-10 600 V 6.3 A 26-10 26/11/2012 Page 3 / 5 May 6, 2009 Page 200 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-HESI (5X20) Order No.: 3046032 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046032 Drawings Application drawing Fuse terminal blocks in interconnected arrangement, block consisting of 5 fuse terminal blocks Circuit diagram Fuse terminal block in single arrangement, block consisting of one fuse terminal block and 4 feed-through terminal blocks PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 4 / 5 May 6, 2009 Page 201 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ð´»¿-» ²±¬» ¬¸¿¬ ¬¸» ¼¿¬¿ ¹·ª»² ¸»®» ¸¿- ¾»»² ¬¿µ»² º®±³ ¬¸» ±²´·²» ½¿¬¿´±¹ò Ú±® ½±³°®»¸»²-·ª» ·²º±®³¿¬·±² ¿²¼ ¼¿¬¿ô °´»¿-» ®»º»® ¬± ¬¸» «-»® ¼±½«³»²¬¿¬·±² ¿¬ ¸¬¬°æññ©©©ò¼±©²´±¿¼ò°¸±»²·¨½±²¬¿½¬ò½±³ò ̸» Ù»²»®¿´ Ì»®³¿²¼ ݱ²¼·¬·±²- ±º Ë-» ¿°°´§ ¬± ײ¬»®²»¬ ¼±©²´±¿¼-ò Û¨¬®¿½¬ º®±³ ¬¸» ±²´·²» ½¿¬¿´±¹ ˲·ª»®-¿´ ¬»®³·²¿´ ¾´±½µ ©·¬¸ -½®»© ½±²²»½¬·±²ô ½®±--»½¬·±²æ ðòïì ó ì ³³n ô ßÉÙæ îê ó ïðô ©·¼¬¸æ êòî ³³ô ½±´±®æ Ù®¿§ Ñ®¼»® Ò±ò Ñ®¼ ¼»-·¹²¿¬·±² ÛßÒ Ð¿½µ Ý«-¬±³- ¬¿®·ºº Ý¿¬¿´±¹ °¿¹» ·²º±®³¿¬·±² Ì»½¸²·½¿´ ¼¿¬¿ Ù»²»®¿´ Ò«³¾»® ±º ´»ª»´Ò«³¾»® ±º ½±²²»½¬·±²Ý±´±® ײ-«´¿¬·²¹ ³¿¬»®·¿´ ײº´¿³³¿¾·´·¬§ ½´¿-- ¿½½ò ¬± ËÔ çì íðìêïíç ËÌ ìóÓÌ ìðïéçïèçéëëêî ëð н-ò èëíêçðïð п¹» îð øÒÌÕóîððë÷ ï î ¹®¿§ Ðß Êð ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» ïñé ß«¹ ïîô îððë Page 202 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ü·³»²-·±²É·¼¬¸ Ô»²¹¬¸ Ø»·¹¸¬ ÒÍ íëñéôë Ø»·¹¸¬ ÒÍ íëñïë êòî ³³ ëêòè ³³ ìéòë ³³ ëë ³³ Ì»½¸²·½¿´ ¼¿¬¿ Ó¿¨·³«³ ´±¿¼ ½«®®»²¬ כּ¼ -«®¹» ª±´¬¿¹» ݱ²¬¿³·²¿¬·±² ½´¿-Í«®¹» ª±´¬¿¹» ½¿¬»¹±®§ ײ-«´¿¬·²¹ ³¿¬»®·¿´ ¹®±«° ݱ²²»½¬·±² ·² ¿½½ò ©·¬¸ -¬¿²¼¿®¼ Ò±³·²¿´ ½«®®»²¬ ×Ò Ò±³·²¿´ ª±´¬¿¹» ËÒ Ñ°»² -·¼» °¿²»´ ïê ß è µÊ í ××× × ×ÛÝñ Ü×Ò ÊÜÛ ïê ß ëðð Ê ²»·² ݱ²²»½¬·±² ¼¿¬¿ ݱ²¼«½¬±® ½®±-- -»½¬·±²ô ®·¹·¼ ³·²ò ðòïì ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±²ô ®·¹·¼ ³¿¨ò ê ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´» ³·²ò ðòïì ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±²ô º´»¨·¾´» ³¿¨ò ì ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±² ßÉÙñµ½³·´ ³·²ò îê ݱ²¼«½¬±® ½®±-- -»½¬·±² ßÉÙñµ½³·´ ³¿¨ ïð ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´»ô ©·¬¸ º»®®«´» ©·¬¸±«¬ °´¿-¬·½ -´»»ª» ³·²ò ðòîë ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´»ô ©·¬¸ º»®®«´» ©·¬¸±«¬ ì ³³n °´¿-¬·½ -´»»ª» ³¿¨ò ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´»ô ©·¬¸ º»®®«´» ©·¬¸ °´¿-¬·½ ðòîë ³³n -´»»ª» ³·²ò ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´»ô ©·¬¸ º»®®«´» ©·¬¸ °´¿-¬·½ ì ³³n -´»»ª» ³¿¨ò î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô -±´·¼ ³·²ò ðòïì ³³n î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô -±´·¼ ³¿¨ò ïòë ³³n î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´»ô ³·²ò ðòïì ³³n î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´» ³¿¨ò ïòë ³³n î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´»ô ÌÉ×Ò ðòë ³³n º»®®«´»- ©·¬¸ °´¿-¬·½ -´»»ª»ô ³·²ò î ½±²¼«½¬±®- ©·¬¸ ·¼»²¬·½¿´ ½®±-- -»½¬·±²ô º´»¨·¾´» ÌÉ×Ò îòë ³³n º»®®«´»- ©·¬¸ °´¿-¬·½ -´»»ª»ô ³¿¨ò î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´»ô º»®®«´»- ðòîë ³³n ©·¬¸±«¬ °´¿-¬·½ -´»»ª» ³·²ò î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´»ô º»®®«´»- ïòë ³³n ©·¬¸±«¬ °´¿-¬·½ -´»»ª»ô ³¿¨ò ̧°» ±º ½±²²»½¬·±² ͽ®»© ½±²²»½¬·±² ͬ®·°°·²¹ ´»²¹¬¸ ç ³³ ײ¬»®²¿´ ½§´·²¼®·½¿´ ¹¿¹» ßì ͽ®»© ¬¸®»¿¼ Óí Ì·¹¸¬»²·²¹ ¬±®¯«»ô ³·² ðòê Ò³ ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» îñé ß«¹ ïîô îððë Page 203 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ý»®¬·º·½¿¬»- ÝËÔ Ò±³·²¿´ ª±´¬¿¹» ËÒ Ò±³·²¿´ ½«®®»²¬ ×Ò ßÉÙñµ½³·´ ËÔ Ò±³·²¿´ ª±´¬¿¹» ËÒ Ò±³·²¿´ ½«®®»²¬ ×Ò ßÉÙñµ½³·´ êðð Ê ïê ß îêóïð êðð Ê ïê ß îêóïð ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» íñé ß«¹ ïîô îððë Page 204 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ü®¿©·²¹- Ý·®½«·¬ ¼·¿¹®¿³ ß°°®±ª¿´ ´±¹± ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» ìñé ß«¹ ïîô îððë Page 205 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ ß½½»--±®·»- ׬»³ ß--»³¾´§ ðèðïéêî ïîðéêìð ïîðéêëí ïîðéêêê ðèðïéíí ðèðïêèï ïîðïéëê ïîðïèçë ïîðéêéç ïîðéêèî ïîðéêçë ïîðïéíð ïîðïéïì ïîðïéçè Þ®·¼¹»íðíðííê íðíðîìî íðíðîëë íðíðíìç íðíðîéï íðíðíêë íðìéðêð Ü»-·¹²¿¬·±² Ü»-½®·°¬·±² ÒÍ íëñ éôë ÝË ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñ éôë ÐÛÎÚ éëëÓÓ ÒÍ íëñ éôë ÐÛÎÚ çëëÓÓ ÒÍ íëñ éôë ÐÛÎÚ ïïëëÓÓ ÒÍ íëñ éôë ÐÛÎÚ îðððÓÓ ÒÍ íëñ éôë ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñïë ßÔ ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñïë ÝË ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñïë ÐÛÎÚ éëëÓÓ ÒÍ íëñïë ÐÛÎÚ çëëÓÓ ÒÍ íëñïë ÐÛÎÚ ïïëëÓÓ ÒÍ íëñïë ÐÛÎÚ îðððÓÓ ÒÍ íëñïë ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñïëóîôí ËÒÐÛÎÚ îðððÓÓ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ݱ°°»®ô «²°»®º±®¿¬»¼ô ¸»·¹¸¬ éòë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ éòë ³³ô ´»²¹¬¸ éëë ³³ ÒÍíë Ü×Ò ®¿·´ô ¸»·¹¸¬ éòë ³³ô ´»²¹¬¸ çëë ³³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ éòë ³³ô ´»²¹¬¸ ïïëë ³³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô °»®º±®¿¬»¼ô ¸»·¹¸¬ éòë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô «²°»®º±®¿¬»¼ô ¸»·¹¸¬ éòë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ Ü×Ò ®¿·´ô ¼»»°ó¼®¿©²ô ¸·¹¸ °®±º·´»ô «²°»®º±®¿¬»¼ô ïòë ³³ ¬¸·½µô ³¿¬»®·¿´æ ß´«³·²«³ô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸ î ³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ݱ°°»®ô «²°»®º±®¿¬»¼ô ïòë ³³ ¬¸·½µô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ ïë ³³ô ´»²¹¬¸ éëë ³³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ ïë ³³ô ´»²¹¬¸ çëë ³³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ ïë ³³ô ´»²¹¬¸ ïïëë ³³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô °»®º±®¿¬»¼ô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô «²°»®º±®¿¬»¼ô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô «²°»®º±®¿¬»¼ô îòí ³³ ¬¸·½µô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ ÚÞÍ îóê ÚÞÍ íóê ÚÞÍ ìóê ÚÞÍ ëóê ÚÞÍ ïðóê ÚÞÍ îðóê ÎÞ ËÌ ïðóøîôëñì÷ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô îó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô íó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô ìó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô ëó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô ïðó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô îðó °±-òô ½±´±®æ λ¼ λ¼«½·²¹ ¾®·¼¹»ô º±® ½±²²»½¬·±² º®±³ ËÌ ï𠬱 ËÌ ì ±® ËÌ îôë ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» ëñé ß«¹ ïîô îððë Page 206 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ó¿®µ·²¹ ðèïïîîè ïðëïðïê ëðêðçíë ïðëðìçç ÈóÐÛÒ ðôíë ÆÞ êôÔÙÍæÚÑÎÌÔòÆßØÔÛÒ ÆÞ êñÉØóïððæËÒÞÛÜÎËÝÕÌ ÆÞ êæÍÑñÝÓÍ Ó¿®µ»® °»² ©·¬¸±«¬ ·²µ ½¿®¬®·¼¹»ô º±® ³¿²«¿´ ´¿¾»´·²¹ ±º ³¿®µ»®-ô ´¿¾»´·²¹ »¨¬®»³»´§ ©·°»ó°®±±ºô ´·²» ¬¸·½µ²»-- ðòíë ³³ Æ¿½µ -¬®·°ô ïðó-»½¬·±²ô °®·²¬»¼ ¸±®·¦±²¬¿´´§æ ©·¬¸ ¬¸» ²«³¾»®-ô ïó ïðô ïïóî𠻬½ò «° ¬± ççïóïðððô ½±´±®æ ©¸·¬» Æ¿½µ -¬®·°ô «²°®·²¬»¼æ Ú±® ·²¼·ª·¼«¿´ ´¿¾»´·²¹ ©·¬¸ ÓóÐÛÒô ÆÞóÌ ±® ÝÓÍ -§-¬»³ô ´¿®¹» ¾¿¬½¸ô -«ºº·½·»²¬ º±® ´¿¾»´·²¹ ïðð𠬻®³·²¿´ ¾´±½µ-ô º±® ¿ ¬»®³·²¿´ ©·¼¬¸ ±º êòî ³³ô ½±´±®æ ɸ·¬» Æ¿½µ -¬®·°ô ïðó-»½¬·±²ô ¼·ª·-·¾´»ô -°»½·¿´ °®·²¬·²¹ô ³¿®µ·²¹ ¿½½±®¼·²¹ ¬± ½«-¬±³»® ®»¯«·®»³»²¬- д«¹ñß¼¿°¬»® ðîðïêèç ÓÐÍóר ÞË ðîðïêéê ÓÐÍóר ÎÜ ðîðïêêí ÓÐÍóר ÉØ ðîðïéìì ÓÐÍóÓÌ íðíðçîë Ðß×óì íðíðççê ÐÍóê Ì»-¬ °´«¹ô ½±²-·-¬·²¹ ±ºæ Ó»¬¿´ °¿®¬ º±® îòí ³³ ¼·¿³»¬»® -±½µ»¬ ¸±´» Ì»-¬ ¿¼¿°¬»®ô º±® ì ³³ ¼·¿³»¬»® ¬»-¬ °´«¹ ÐÍ ¿²¼ -¿º»¬§ ¬»-¬ °´«¹ô ³¿µ»- ½±²¬¿½¬ ·² ¬¸» ¾®·¼¹» -¸¿º¬ Ó±¼«´¿® ¬»-¬ °´«¹ô º±® ·²¼·ª·¼«¿´ ¿--»³¾´§ ±º ¬»-¬ °´«¹ -¬®·°-ô º±® ËÌô ÍÌô ÜÌ ¿²¼ ÏÌ ¬»®³·²¿´ ¾´±½µ-ô ½¿² ¾» ´¿¾»´»¼ ©·¬¸ ÆÞÚ êô ½±´±®æ λ¼ ̱±´ïîðëðëí ÍÆÍ ðôêÈíôë ͽ®»©¼®·ª»®ô ¾´¿¼»¼ô ³¿¬½¸»- ¿´´ -½®»© ¬»®³·²¿´ ¾´±½µ- «° ¬± ìòð ³³n ½±²²»½¬·±² ½®±-- -»½¬·±²ô ¾´¿¼»æ ðòê ¨ íòë ³³ô ©·¬¸±«¬ ÊÜÛ ¿°°®±ª¿´ ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» êñé ß«¹ ïîô îððë Page 207 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 The figure shows a 10-position version of the product Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn Commercial data GTIN (EAN) sales group Pack Customs tariff Weight/Piece Catalog page information 4017918029623 E111 50 pcs. 85366990 0.01727 KG Page 198 (CC-2009) Technical data Dimensions / positions Pitch Dimension a Number of positions Screw thread Tightening torque, min 5.08 mm 45.72 mm 10 M3 0.5 Nm Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 1 / 8 Jun 30, 2010 Page 208 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Tightening torque max Technical data Insulating material group Rated surge voltage (III/3) Rated surge voltage (III/2) Rated surge voltage (II/2) Rated voltage (III/2) Rated voltage (II/2) Connection in acc. with standard Nominal current IN Nominal voltage UN Nominal cross section Maximum load current Insulating material Inflammability class acc. to UL 94 Internal cylindrical gage Stripping length Nominal voltage, UL/CUL Use Group B Nominal current, UL/CUL Use Group B Nominal voltage, UL/CUL Use Group D Nominal current, UL/CUL Use Group D Connection data Conductor cross section solid min. Conductor cross section solid max. Conductor cross section stranded min. Conductor cross section stranded max. Conductor cross section stranded, with ferrule without plastic sleeve min. Conductor cross section stranded, with ferrule without plastic sleeve max. Conductor cross section stranded, with ferrule with plastic sleeve min. Conductor cross section stranded, with ferrule with plastic sleeve max. Conductor cross section AWG/kcmil min. Conductor cross section AWG/kcmil max 0.6 Nm I 4 kV 4 kV 4 kV 320 V 630 V EN-VDE 12 A 250 V 2.5 mm² 12 A (with 2.5 mm2 conductor cross section) PA V0 A3 7 mm 250 V 12 A 300 V 10 A 0.2 mm² 2.5 mm² 0.2 mm² 2.5 mm² 0.25 mm² 2.5 mm² 0.25 mm² 2.5 mm² 24 12 PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 2 / 8 Jun 30, 2010 Page 209 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 2 conductors with same cross section, solid min. 2 conductors with same cross section, solid max. 2 conductors with same cross section, stranded min. 2 conductors with same cross section, stranded max. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. Minimum AWG according to UL/CUL Maximum AWG according to UL/CUL 0.2 mm² 1 mm² 0.2 mm² 1.5 mm² 0.25 mm² 1 mm² 0.5 mm² 1.5 mm² 30 12 Certificates / Approvals Certification CSA Nominal voltage UN Nominal current IN AWG/kcmil CUL Nominal voltage UN Nominal current IN AWG/kcmil UL Nominal voltage UN Nominal current IN AWG/kcmil CB, CSA, CUL, GOST, UL, VDE-PZI 300 V 10 A 28-12 300 V 10 A 30-12 300 V 10 A 30-12 PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 3 / 8 Jun 30, 2010 Page 210 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Accessories Item Designation Bridges 1733172 EBP 3- 5 1733185 EBP 4- 5 1733198 EBP 5- 5 1733208 EBP 6- 5 General 1733169 1783740 EBP 2- 5 KGS-MSTB 2,5/10 Marking 1051993 0805108 B-STIFT SK 5,08/2,8:SO 0804293 SK 5,08/3,8:FORTL.ZAHLEN 0803883 SK U/2,8 WH:UNBEDRUCKT Plug/Adapter 1734634 CP-MSTB Tools 1205053 SZS 0,6X3,5 Description Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 3 Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 4 Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 5 Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 6 Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 2 Cable housing, Number of positions: 10, Dimension a: 50 mm, Color: green Marker pen, for manual labeling of unprinted Zack strips, smearproof and waterproof, line thickness 0.5 mm Marker card, special printing, self-adhesive, labeled acc. to customer requirements, 14 identical marker strips per card, max. 25-position labeling per strip, color: White Marker card, printed horizontally, self-adhesive, 12 identical decades marked 1-10, 11-20 etc. up to 91-(99)100, sufficient for 120 terminal blocks Unprinted marker cards, DIN A4 format, pitch as desired, selfadhesive, with 50 stamped marker strips, 185 mm strip length, can be labeled with the CMS system or manually with the M-PEN Keying profile, is inserted into the slot on the plug or inverted header, red insulating material Screwdriver, bladed, matches all screw terminal blocks up to 4.0 mm² connection cross section, blade: 0.6 x 3.5 mm, without VDE approval PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 4 / 8 Jun 30, 2010 Page 211 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Additional products Item Designation General 1823927 ICC 2,5/10-STZ-5,08 1762457 MDSTB 2,5/10-G1-5,08 1762583 MDSTBV 2,5/10-G1-5,08 1770795 1757323 1768024 1765030 MSTB 2,5/10-G-5,08-LA MSTBA 2,5/10-G-5,08 MSTBA 2,5/10-G-5,08-LA MSTBHK 2,5/10-G-5,08 1788800 MSTBVK 2,5/10-G-5,08 1788619 MVSTBU 2,5/10-GB-5,08 1769544 1767452 3002034 SMSTB 2,5/10-G-5,08 SMSTBA 2,5/10-G-5,08 UK 3-MSTB-5,08 Description Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Corresponding male crimp contacts with current [A] and conductor cross section range [mm²] data: 10A/ICC-MT 0,5-1,0 (3190577); 10A/ICC-MT 0,5-1,0 BA (3190603); 12A/ICC-MT 1,5-2,5 (3190580); 12A/ICCMT 1,5-2,5 BA (3190593). BA = Bandkontakte Header, Nominal current: 10 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering, In combination with MVSTB or FKCV plug components, both an MVSTBW (or FKCVW) and an MVSTBR plug (or FKCVR) must be used. Combination with TMSTBP plug components is not possible! Header, Nominal current: 10 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering, In combination with MVSTB or FKCV plug components, both an MVSTBW (or FKCVW) and an MVSTBR plug (or FKCVR) must be used. Combination with TMSTBP plug components is not possible! Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Assembly: Soldering Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Assembly: Soldering Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: DIN rail Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: DIN rail Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Direct mounting Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering Feed-through modular terminal block, Type of connection: Special and hybrid connection, Screw connection, Cross section: 0.2 mm² - 4 mm², AWG 24 - 12, Width: 5.08 mm, Color: gray, Mounting type: NS 32, NS 35/15, NS 35/7,5 PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 5 / 8 Jun 30, 2010 Page 212 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 3002076 3002102 3002063 3002131 3002144 3002173 2770888 1876615 2770846 1788198 1873016 UK 3-MVSTB-5,08 UK 3-MVSTB-5,08-LA 24RD UK 3-MVSTB-5,08/EK UK 3D-MSTBV-5,08 UK 3D-MSTBV-5,08-LA 24RD UK 3D-MSTBV-5,08/EK UKK 3-MSTB-5,08 UKK 3-MSTB-5,08-PE UKK 3-MSTBVH-5,08 UMSTBVK 2,5/10-G-5,08 ZFKK 1,5-MSTBV-5,08 Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 32, NS 35/15, NS 35/7,5, Pitch: 5.08 mm, Width: 5.1, Color: gray Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 32, NS 35/15, NS 35/7,5, Pitch: 5.08 mm, Width: 5.08, Color: gray Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 35/7,5, NS 35/15, NS 32, Pitch: 5.08 mm, Width: 5.1, Color: blue Feed-through modular terminal block, Type of connection: Special and hybrid connection, Screw connection, Cross section: 0.2 mm² - 4 mm², AWG 24 - 12, Width: 5.08 mm, Color: gray, Mounting type: NS 32, NS 35/15, NS 35/7,5 Feed-through modular terminal block, Type of connection: Screw connection, Screw connection, Number of positions: 1, Cross section: 0.2 mm² - 4 mm², AWG 24 - 12, Width: 5.1 mm, Color: gray, Mounting type: NS 32, NS 35/15, NS 35/7,5 Feed-through modular terminal block, Type of connection: Screw connection, Screw connection, Cross section: 0.2 mm² - 4 mm², AWG 24 - 12, Width: 5.1 mm, Color: blue, Mounting type: NS 32, NS 35/15, NS 35/7,5 End cover, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 35/7,5, NS 35/15, NS 32, Pitch: 5.08 mm, Width: 5.08, Color: gray Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 320 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 35/7,5, NS 35/15, NS 32, Pitch: 5.08 mm, Width: 5.08, Color: green-yellow Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 35/7,5, NS 35/15, NS 32, Pitch: 5.08 mm, Width: 5.08, Color: gray Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: DIN rail Feed-through modular terminal block, Connection method: Special and hybrid connection, MSTB plug entry, Cross section: 0.2 mm² - 2.5 mm², Width: 5.1 mm, Color: gray PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 6 / 8 Jun 30, 2010 Page 213 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Diagrams/Drawings Dimensioned drawing PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 7 / 8 Jun 30, 2010 Page 214 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual FBS 10-8 Order No.: 3030323 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3030323 Cross connector/jumper for modular terminal block, Number of positions: 10, Color: red Commercial data EAN Pack Customs tariff Weight/Piece Catalog page information 4017918188634 10 pcs. 85389099 0.01955 KG Page 330 (CL-2009) Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 1 / 2 Oct 23, 2009 Page 215 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual SZF 1-0,6X3,5 Order No.: 1204517 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1204517 Screwdriver, blade: 0.6 x 3.5 x 100 mm, length 180 mm Commercial data GTIN (EAN) sales group Pack Customs tariff Weight/Piece Catalog page information Technical data General Length (b) Width (a) Design 4017918018948 C200 10 pcs. 82054000 0.0368 KG Page 8 (NTK-2010) Product notes WEEE/RoHS-compliant since: 11/01/2008 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. 181 mm 26 mm Phillips PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 1 / 3 Jun 30, 2010 Page 216 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual SZF 1-0,6X3,5 Order No.: 1204517 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1204517 Blade thickness Blade width Blade height Weight Test standard Certificates / Approvals 0.6 mm 3.5 mm 100 mm 34 g DIN 5264 Certification Diagrams/Drawings Dimensioned drawing GOST PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 2 / 3 Jun 30, 2010 Page 217 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual PS-6/2,3MM RD Order No.: 3038736 The illustration shows the version PS-5/2,3 MM RD Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3038736 Test plugs, Color: red Commercial data GTIN (EAN) sales group Pack Customs tariff Weight/Piece Catalog page information 4017918904166 A691 10 pcs. 85369010 0.00143 KG Page 449 (CL-2009) Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 1 / 2 Jun 30, 2010 Page 218 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UBE/D + ES/KMK 3 Order No.: 1004076 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1004076 Terminal strip marker carriers for marking terminal group, for mounting on the terminal strip NS 32 or NS 35/7.5, lettering field size: 40 x 17 mm Commercial data EAN Pack Customs tariff Weight/Piece 4017918011888 10 pcs. 85369010 0.0105 KG Product notes WEEE/RoHS-compliant since: 03/18/2004 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. Technical data General Color Base element material Inflammability class acc. to UL 94 Ambient temperature (operation) Components gray PA V2 -40 °C ... 100 °C free from silicone and halogen PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 1 / 2 May 7, 2009 Page 219 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 Feed-through modular terminal block, Type of connection: Screw connection, Cross section: 0.14 mm² - 6 mm², AWG 26 - 10, Width: 6.2 mm, Color: gray, Mounting type: NS 35/7,5, NS 35/15 Commercial data EAN Pack Customs tariff Weight/Piece Catalog page information Technical data General Number of levels Number of connections Color 4017918956592 50 pcs. 85369010 0.011431 KG Page 56 (CL-2009) 1 2 gray Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 1 / 7 Mar 24, 2010 Page 220 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 Insulating material PA Inflammability class acc. to UL 94 V0 Dimensions Width Length Height NS 35/7,5 Height NS 35/15 6.2 mm 57.8 mm 47.5 mm 55 mm Technical data Maximum load current Rated surge voltage Pollution degree Surge voltage category Insulating material group Connection in acc. with standard Nominal current IN Nominal voltage UN Open side panel 41 A (with 6 mm2 conductor cross section) 8 kV 3 III I IEC 60947-7-1 32 A 800 V ja Connection data Conductor cross section solid min. Conductor cross section solid max. Conductor cross section stranded min. Conductor cross section stranded max. Conductor cross section AWG/kcmil min. Conductor cross section AWG/kcmil max Conductor cross section stranded, with ferrule without plastic sleeve min. Conductor cross section stranded, with ferrule without plastic sleeve max. Conductor cross section stranded, with ferrule with plastic sleeve min. Conductor cross section stranded, with ferrule with plastic sleeve max. 2 conductors with same cross section, solid min. 2 conductors with same cross section, solid max. 2 conductors with same cross section, stranded min. 0.14 mm² 6 mm² 0.14 mm² 6 mm² 26 10 0.14 mm² 4 mm² 0.14 mm² 4 mm² 0.14 mm² 1.5 mm² 0.14 mm² PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 2 / 7 Mar 24, 2010 Page 221 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 2 conductors with same cross section, stranded max. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. Type of connection Stripping length Internal cylindrical gage Screw thread Tightening torque, min Tightening torque max 1.5 mm² 0.5 mm² 2.5 mm² 0.14 mm² 1.5 mm² Screw connection 9 mm A4 M3 0.6 Nm 0.8 Nm Certificates / Approvals Certification Certification Ex: CSA Nominal voltage UN Nominal current IN AWG/kcmil CUL Nominal voltage UN Nominal current IN AWG/kcmil UL Nominal voltage UN Nominal current IN AWG/kcmil PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 CB, CSA, CUL, DNV, GL, LR, UL, VDE-PZI IECEx, KEMA-EX 600 V 30 A 26-10 600 V 30 A 26-10 600 V 30 A 26-10 26/11/2012 Page 3 / 7 Mar 24, 2010 Page 222 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 Accessories Item Designation Description Assembly 3022276 3047141 0801762 1207640 1207653 1207666 0801733 0801681 1201756 1201895 1207679 1207682 1207695 1201730 1201714 1201798 CLIPFIX 35-5 Snap-on end bracket, for NS 35/7.5 or NS 35/15 DIN rail, can be fitted with Zack strip ZB 5 and ZBF 5, terminal strip marker KLM 2 and KLM, parking facility for FBS...5, FBS...6, KSS 5, KSS 6, width: 5,15 mm, color: gray D-UT 2,5/4-TWIN End cover, Width: 2.2 mm, Color: gray NS 35/ 7,5 CU UNPERF 2000MM DIN rail, material: Copper, unperforated, height 7.5 mm, width 35 mm, length: 2 m NS 35/ 7,5 PERF 755MM NS 35 DIN rail, height 7.5 mm, length 755 mm NS 35/ 7,5 PERF 955MM NS35 DIN rail, height 7.5 mm, length 955 mm NS 35/ 7,5 PERF 1155MM NS 35 DIN rail, height 7.5 mm, length 1155 mm NS 35/ 7,5 PERF 2000MM DIN rail, material: Steel, galvanized and passivated with a thick layer, perforated, height 7.5 mm, width 35 mm, length: 2 m NS 35/ 7,5 UNPERF 2000MM DIN rail, material: Steel, unperforated, height 7.5 mm, width 35 mm, length: 2 m NS 35/15 AL UNPERF 2000MM DIN rail, deep-drawn, high profile, unperforated, 1.5 mm thick, material: Aluminum, height 15 mm, width 35 mm, length 2 m NS 35/15 CU UNPERF 2000MM DIN rail, material: Copper, unperforated, 1.5 mm thick, height 15 mm, width 35 mm, length: 2 m NS 35/15 PERF 755MM NS 35 DIN rail, perforated, height 15 mm, length 755 mm NS 35/15 PERF 955MM NS 35 DIN rail, perforated, height 15 mm, length 955 mm NS 35/15 PERF 1155MM NS 35 DIN rail, perforated, height 15 mm, length 1155 mm NS 35/15 PERF 2000MM DIN rail, material: Steel, perforated, height 15 mm, width 35 mm, length: 2 m NS 35/15 UNPERF 2000MM DIN rail, material: Steel, unperforated, height 15 mm, width 35 mm, length: 2 m NS 35/15-2,3 UNPERF 2000MM DIN rail, material: Steel, unperforated, 2.3 mm thick, height 15 mm, width 35 mm, length: 2 m Bridges 3030336 3030242 3030255 3030349 3030271 3030365 3032224 FBS 2-6 FBS 3-6 FBS 4-6 FBS 5-6 FBS 10-6 FBS 20-6 FBS 50-6 Cross connector/bridge, Number of positions: 2, Color: red Cross connector/bridge, Number of positions: 3, Color: red Cross connector/bridge, Number of positions: 4, Color: red Cross connector/bridge, Number of positions: 5, Color: red Cross connector/bridge, Number of positions: 10, Color: red Cross connector/bridge, Number of positions: 20, Color: red Cross connector/bridge, Number of positions: 50, Color: red PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 4 / 7 Mar 24, 2010 Page 223 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 3047060 Marking 1051993 0811228 1051016 1051032 1051029 1051045 1050499 1051003 RB UT 10-(2,5/4) B-STIFT X-PEN 0,35 ZB 6,LGS:FORTL.ZAHLEN ZB 6,LGS:GLEICHE ZAHLEN ZB 6,QR:FORTL.ZAHLEN ZB 6,QR:GLEICHE ZAHLEN ZB 6:SO/CMS ZB 6:UNBEDRUCKT Plug/Adapter 0201731 MPS-IH BK 0201702 MPS-IH GN 0201676 MPS-IH RD 0201663 MPS-IH WH 0201744 MPS-MT 3030925 PAI-4 3030996 PS-6 Tools 1205053 SZS 0,6X3,5 Diagrams/Drawings Circuit diagram Cross connector/bridge, Number of positions: 2, Color: red Marker pen, for manual labeling of unprinted Zack strips, smearproof and waterproof, line thickness 0.5 mm Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35 mm Zack strip, 10-section, printed horizontally: with the numbers, 1-10, 11-20 etc. up to 991-1000, color: white Zack marker strip, labeled horizontally: 10-section, with identical numbers, 1/1/1, 2/2/2 etc. up to 1000/1000/1000, color: white Zack strip, 10-section, printed vertically: with consecutive numbers, 1-10, 11-20 a.s.o. up to 991-1000, color: white Zack marker, labeled vertically: 10-section, with identical numbers, 1/1/1, 2/2/2 etc. up to 1000/1000/1000, color: White Zack strip, 10-section, divisible, special printing, marking according to customer requirements Zack strip, unprinted, strips with 10 labels for individual labeling with M-PEN or CMS system, for terminal block width: 6.2 mm, color: white Insulating sleeve, for MPS metal part, Color: black Insulating sleeve, for MPS metal part, Color: green Insulating sleeve, Color: red Insulating sleeve, for MPS metal part, Color: white Metal part Test adapter, Color: gray Test adapter, Color: red Screwdriver, bladed, matches all screw terminal blocks up to 4.0 mm² connection cross section, blade: 0.6 x 3.5 mm, without VDE approval PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 5 / 7 Mar 24, 2010 Page 224 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Module no:0921011 LabelId:0921011 Operator:Phoenix 15:22:45, Donnerstag, 28. Juni 2001 ST-SI-UK 4 HCAE Description Light indicator: Voltage [V AC/DC] Current [mA] Fuse plug, for cartridge fuse inserts 5 x 20 mm, 26.5 mm high, color: black Fuse plug, as above, however with light indicator: 5 - 15 2 - 7.5 15 - 30 3.5 - 7.5 30 - 60 2.5 - 5.5 110 - 250 0.5 - 1 Technical data Insulation material Inflammability class acc. to UL 94 Temperature indices RTI / Ti Approval data (UL and CSA) Nom. voltage / nom. current 1) With single arrangements. 2) Max. power dissipation see info. Type Pcs. Order No. Pkt. ST-SI-UK 4 ST-SILED 12-UK 4 ST-SILED 24-UK 4 ST-SILED 60-UK 4 ST-SILA 250-UK 4 Imax.: 6.3 A 1) 2) 09 21 01 1 50 Imax.: 6.3 A 1) 2) 09 21 02 4 50 6.3 A 1) 2) 09 21 03 7 50 6.3 A 1) 2) 09 21 04 0 50 6.3 A 1) 2) 09 21 05 3 50 UL: [V] / [A] CSA: [V] / [A] PA V2 130 / 120 300 / 6.3 300 / 10 Phoenix Contact Elektronischer Katalog Q-Pulse Id: TMS196 26/11/2012 Page 1 / 1 Page 225 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual SZF 1-0,6X3,5 Order No.: 1204517 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1204517 Screwdriver, blade: 0.6 x 3.5 x 100 mm, length 180 mm Commercial data GTIN (EAN) sales group Pack Customs tariff Weight/Piece Catalog page information Technical data General Length (b) Width (a) Design 4017918018948 C200 10 pcs. 82054000 0.0368 KG Page 8 (NTK-2010) Product notes WEEE/RoHS-compliant since: 11/01/2008 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. 181 mm 26 mm Phillips PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 1 / 3 Jun 30, 2010 Page 226 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual SZF 1-0,6X3,5 Order No.: 1204517 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1204517 Blade thickness Blade width Blade height Weight Test standard Certificates / Approvals 0.6 mm 3.5 mm 100 mm 34 g DIN 5264 Certification Diagrams/Drawings Dimensioned drawing GOST PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 2 / 3 Jun 30, 2010 Page 227 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 The figure shows a 10-position version of the product Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn Commercial data GTIN (EAN) sales group Pack Customs tariff Weight/Piece Catalog page information 4017918029623 E111 50 pcs. 85366990 0.01727 KG Page 198 (CC-2009) Technical data Dimensions / positions Pitch Dimension a Number of positions Screw thread Tightening torque, min 5.08 mm 45.72 mm 10 M3 0.5 Nm Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 1 / 8 Jun 30, 2010 Page 228 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Tightening torque max Technical data Insulating material group Rated surge voltage (III/3) Rated surge voltage (III/2) Rated surge voltage (II/2) Rated voltage (III/2) Rated voltage (II/2) Connection in acc. with standard Nominal current IN Nominal voltage UN Nominal cross section Maximum load current Insulating material Inflammability class acc. to UL 94 Internal cylindrical gage Stripping length Nominal voltage, UL/CUL Use Group B Nominal current, UL/CUL Use Group B Nominal voltage, UL/CUL Use Group D Nominal current, UL/CUL Use Group D Connection data Conductor cross section solid min. Conductor cross section solid max. Conductor cross section stranded min. Conductor cross section stranded max. Conductor cross section stranded, with ferrule without plastic sleeve min. Conductor cross section stranded, with ferrule without plastic sleeve max. Conductor cross section stranded, with ferrule with plastic sleeve min. Conductor cross section stranded, with ferrule with plastic sleeve max. Conductor cross section AWG/kcmil min. Conductor cross section AWG/kcmil max 0.6 Nm I 4 kV 4 kV 4 kV 320 V 630 V EN-VDE 12 A 250 V 2.5 mm² 12 A (with 2.5 mm2 conductor cross section) PA V0 A3 7 mm 250 V 12 A 300 V 10 A 0.2 mm² 2.5 mm² 0.2 mm² 2.5 mm² 0.25 mm² 2.5 mm² 0.25 mm² 2.5 mm² 24 12 PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 2 / 8 Jun 30, 2010 Page 229 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 2 conductors with same cross section, solid min. 2 conductors with same cross section, solid max. 2 conductors with same cross section, stranded min. 2 conductors with same cross section, stranded max. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. Minimum AWG according to UL/CUL Maximum AWG according to UL/CUL 0.2 mm² 1 mm² 0.2 mm² 1.5 mm² 0.25 mm² 1 mm² 0.5 mm² 1.5 mm² 30 12 Certificates / Approvals Certification CSA Nominal voltage UN Nominal current IN AWG/kcmil CUL Nominal voltage UN Nominal current IN AWG/kcmil UL Nominal voltage UN Nominal current IN AWG/kcmil CB, CSA, CUL, GOST, UL, VDE-PZI 300 V 10 A 28-12 300 V 10 A 30-12 300 V 10 A 30-12 PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 3 / 8 Jun 30, 2010 Page 230 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Accessories Item Designation Bridges 1733172 EBP 3- 5 1733185 EBP 4- 5 1733198 EBP 5- 5 1733208 EBP 6- 5 General 1733169 1783740 EBP 2- 5 KGS-MSTB 2,5/10 Marking 1051993 0805108 B-STIFT SK 5,08/2,8:SO 0804293 SK 5,08/3,8:FORTL.ZAHLEN 0803883 SK U/2,8 WH:UNBEDRUCKT Plug/Adapter 1734634 CP-MSTB Tools 1205053 SZS 0,6X3,5 Description Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 3 Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 4 Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 5 Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 6 Insertion bridge, fully insulated, for plug connectors with 5.0 or 5.08 mm pitch, no. of positions: 2 Cable housing, Number of positions: 10, Dimension a: 50 mm, Color: green Marker pen, for manual labeling of unprinted Zack strips, smearproof and waterproof, line thickness 0.5 mm Marker card, special printing, self-adhesive, labeled acc. to customer requirements, 14 identical marker strips per card, max. 25-position labeling per strip, color: White Marker card, printed horizontally, self-adhesive, 12 identical decades marked 1-10, 11-20 etc. up to 91-(99)100, sufficient for 120 terminal blocks Unprinted marker cards, DIN A4 format, pitch as desired, selfadhesive, with 50 stamped marker strips, 185 mm strip length, can be labeled with the CMS system or manually with the M-PEN Keying profile, is inserted into the slot on the plug or inverted header, red insulating material Screwdriver, bladed, matches all screw terminal blocks up to 4.0 mm² connection cross section, blade: 0.6 x 3.5 mm, without VDE approval PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 4 / 8 Jun 30, 2010 Page 231 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Additional products Item Designation General 1823927 ICC 2,5/10-STZ-5,08 1762457 MDSTB 2,5/10-G1-5,08 1762583 MDSTBV 2,5/10-G1-5,08 1770795 1757323 1768024 1765030 MSTB 2,5/10-G-5,08-LA MSTBA 2,5/10-G-5,08 MSTBA 2,5/10-G-5,08-LA MSTBHK 2,5/10-G-5,08 1788800 MSTBVK 2,5/10-G-5,08 1788619 MVSTBU 2,5/10-GB-5,08 1769544 1767452 3002034 SMSTB 2,5/10-G-5,08 SMSTBA 2,5/10-G-5,08 UK 3-MSTB-5,08 Description Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Corresponding male crimp contacts with current [A] and conductor cross section range [mm²] data: 10A/ICC-MT 0,5-1,0 (3190577); 10A/ICC-MT 0,5-1,0 BA (3190603); 12A/ICC-MT 1,5-2,5 (3190580); 12A/ICCMT 1,5-2,5 BA (3190593). BA = Bandkontakte Header, Nominal current: 10 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering, In combination with MVSTB or FKCV plug components, both an MVSTBW (or FKCVW) and an MVSTBR plug (or FKCVR) must be used. Combination with TMSTBP plug components is not possible! Header, Nominal current: 10 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering, In combination with MVSTB or FKCV plug components, both an MVSTBW (or FKCVW) and an MVSTBR plug (or FKCVR) must be used. Combination with TMSTBP plug components is not possible! Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Assembly: Soldering Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Assembly: Soldering Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: DIN rail Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: DIN rail Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Direct mounting Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering Header, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: Soldering Feed-through modular terminal block, Type of connection: Special and hybrid connection, Screw connection, Cross section: 0.2 mm² - 4 mm², AWG 24 - 12, Width: 5.08 mm, Color: gray, Mounting type: NS 32, NS 35/15, NS 35/7,5 PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 5 / 8 Jun 30, 2010 Page 232 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 3002076 3002102 3002063 3002131 3002144 3002173 2770888 1876615 2770846 1788198 1873016 UK 3-MVSTB-5,08 UK 3-MVSTB-5,08-LA 24RD UK 3-MVSTB-5,08/EK UK 3D-MSTBV-5,08 UK 3D-MSTBV-5,08-LA 24RD UK 3D-MSTBV-5,08/EK UKK 3-MSTB-5,08 UKK 3-MSTB-5,08-PE UKK 3-MSTBVH-5,08 UMSTBVK 2,5/10-G-5,08 ZFKK 1,5-MSTBV-5,08 Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 32, NS 35/15, NS 35/7,5, Pitch: 5.08 mm, Width: 5.1, Color: gray Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 32, NS 35/15, NS 35/7,5, Pitch: 5.08 mm, Width: 5.08, Color: gray Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 35/7,5, NS 35/15, NS 32, Pitch: 5.08 mm, Width: 5.1, Color: blue Feed-through modular terminal block, Type of connection: Special and hybrid connection, Screw connection, Cross section: 0.2 mm² - 4 mm², AWG 24 - 12, Width: 5.08 mm, Color: gray, Mounting type: NS 32, NS 35/15, NS 35/7,5 Feed-through modular terminal block, Type of connection: Screw connection, Screw connection, Number of positions: 1, Cross section: 0.2 mm² - 4 mm², AWG 24 - 12, Width: 5.1 mm, Color: gray, Mounting type: NS 32, NS 35/15, NS 35/7,5 Feed-through modular terminal block, Type of connection: Screw connection, Screw connection, Cross section: 0.2 mm² - 4 mm², AWG 24 - 12, Width: 5.1 mm, Color: blue, Mounting type: NS 32, NS 35/15, NS 35/7,5 End cover, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 35/7,5, NS 35/15, NS 32, Pitch: 5.08 mm, Width: 5.08, Color: gray Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 320 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 35/7,5, NS 35/15, NS 32, Pitch: 5.08 mm, Width: 5.08, Color: green-yellow Feed-through modular terminal block, Nominal current: 12 A, Nominal voltage: 250 V, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Mounting type: NS 35/7,5, NS 35/15, NS 32, Pitch: 5.08 mm, Width: 5.08, Color: gray Plug component, Nominal current: 12 A, Rated voltage (III/2): 320 V, Pitch: 5.08 mm, Color: green, Metal surface: Sn, Assembly: DIN rail Feed-through modular terminal block, Connection method: Special and hybrid connection, MSTB plug entry, Cross section: 0.2 mm² - 2.5 mm², Width: 5.1 mm, Color: gray PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 6 / 8 Jun 30, 2010 Page 233 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual MSTB 2,5/10-ST-5,08 Order No.: 1757093 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1757093 Diagrams/Drawings Dimensioned drawing PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 7 / 8 Jun 30, 2010 Page 234 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual FBS 10-8 Order No.: 3030323 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3030323 Cross connector/jumper for modular terminal block, Number of positions: 10, Color: red Commercial data EAN Pack Customs tariff Weight/Piece Catalog page information 4017918188634 10 pcs. 85389099 0.01955 KG Page 330 (CL-2009) Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 1 / 2 Oct 23, 2009 Page 235 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual PS-6/2,3MM RD Order No.: 3038736 The illustration shows the version PS-5/2,3 MM RD Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3038736 Test plugs, Color: red Commercial data GTIN (EAN) sales group Pack Customs tariff Weight/Piece Catalog page information 4017918904166 A691 10 pcs. 85369010 0.00143 KG Page 449 (CL-2009) Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT Inc., USA http://www.phoenixcon.com Q-Pulse Id: TMS196 26/11/2012 Page 1 / 2 Jun 30, 2010 Page 236 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ð´»¿-» ²±¬» ¬¸¿¬ ¬¸» ¼¿¬¿ ¹·ª»² ¸»®» ¸¿- ¾»»² ¬¿µ»² º®±³ ¬¸» ±²´·²» ½¿¬¿´±¹ò Ú±® ½±³°®»¸»²-·ª» ·²º±®³¿¬·±² ¿²¼ ¼¿¬¿ô °´»¿-» ®»º»® ¬± ¬¸» «-»® ¼±½«³»²¬¿¬·±² ¿¬ ¸¬¬°æññ©©©ò¼±©²´±¿¼ò°¸±»²·¨½±²¬¿½¬ò½±³ò ̸» Ù»²»®¿´ Ì»®³¿²¼ ݱ²¼·¬·±²- ±º Ë-» ¿°°´§ ¬± ײ¬»®²»¬ ¼±©²´±¿¼-ò Û¨¬®¿½¬ º®±³ ¬¸» ±²´·²» ½¿¬¿´±¹ ˲·ª»®-¿´ ¬»®³·²¿´ ¾´±½µ ©·¬¸ -½®»© ½±²²»½¬·±²ô ½®±--»½¬·±²æ ðòïì ó ì ³³n ô ßÉÙæ îê ó ïðô ©·¼¬¸æ êòî ³³ô ½±´±®æ Ù®¿§ Ñ®¼»® Ò±ò Ñ®¼ ¼»-·¹²¿¬·±² ÛßÒ Ð¿½µ Ý«-¬±³- ¬¿®·ºº Ý¿¬¿´±¹ °¿¹» ·²º±®³¿¬·±² Ì»½¸²·½¿´ ¼¿¬¿ Ù»²»®¿´ Ò«³¾»® ±º ´»ª»´Ò«³¾»® ±º ½±²²»½¬·±²Ý±´±® ײ-«´¿¬·²¹ ³¿¬»®·¿´ ײº´¿³³¿¾·´·¬§ ½´¿-- ¿½½ò ¬± ËÔ çì íðìêïíç ËÌ ìóÓÌ ìðïéçïèçéëëêî ëð н-ò èëíêçðïð п¹» îð øÒÌÕóîððë÷ ï î ¹®¿§ Ðß Êð ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» ïñé ß«¹ ïîô îððë Page 237 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ü·³»²-·±²É·¼¬¸ Ô»²¹¬¸ Ø»·¹¸¬ ÒÍ íëñéôë Ø»·¹¸¬ ÒÍ íëñïë êòî ³³ ëêòè ³³ ìéòë ³³ ëë ³³ Ì»½¸²·½¿´ ¼¿¬¿ Ó¿¨·³«³ ´±¿¼ ½«®®»²¬ כּ¼ -«®¹» ª±´¬¿¹» ݱ²¬¿³·²¿¬·±² ½´¿-Í«®¹» ª±´¬¿¹» ½¿¬»¹±®§ ײ-«´¿¬·²¹ ³¿¬»®·¿´ ¹®±«° ݱ²²»½¬·±² ·² ¿½½ò ©·¬¸ -¬¿²¼¿®¼ Ò±³·²¿´ ½«®®»²¬ ×Ò Ò±³·²¿´ ª±´¬¿¹» ËÒ Ñ°»² -·¼» °¿²»´ ïê ß è µÊ í ××× × ×ÛÝñ Ü×Ò ÊÜÛ ïê ß ëðð Ê ²»·² ݱ²²»½¬·±² ¼¿¬¿ ݱ²¼«½¬±® ½®±-- -»½¬·±²ô ®·¹·¼ ³·²ò ðòïì ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±²ô ®·¹·¼ ³¿¨ò ê ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´» ³·²ò ðòïì ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±²ô º´»¨·¾´» ³¿¨ò ì ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±² ßÉÙñµ½³·´ ³·²ò îê ݱ²¼«½¬±® ½®±-- -»½¬·±² ßÉÙñµ½³·´ ³¿¨ ïð ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´»ô ©·¬¸ º»®®«´» ©·¬¸±«¬ °´¿-¬·½ -´»»ª» ³·²ò ðòîë ³³n ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´»ô ©·¬¸ º»®®«´» ©·¬¸±«¬ ì ³³n °´¿-¬·½ -´»»ª» ³¿¨ò ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´»ô ©·¬¸ º»®®«´» ©·¬¸ °´¿-¬·½ ðòîë ³³n -´»»ª» ³·²ò ݱ²¼«½¬±® ½®±-- -»½¬·±² º´»¨·¾´»ô ©·¬¸ º»®®«´» ©·¬¸ °´¿-¬·½ ì ³³n -´»»ª» ³¿¨ò î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô -±´·¼ ³·²ò ðòïì ³³n î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô -±´·¼ ³¿¨ò ïòë ³³n î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´»ô ³·²ò ðòïì ³³n î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´» ³¿¨ò ïòë ³³n î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´»ô ÌÉ×Ò ðòë ³³n º»®®«´»- ©·¬¸ °´¿-¬·½ -´»»ª»ô ³·²ò î ½±²¼«½¬±®- ©·¬¸ ·¼»²¬·½¿´ ½®±-- -»½¬·±²ô º´»¨·¾´» ÌÉ×Ò îòë ³³n º»®®«´»- ©·¬¸ °´¿-¬·½ -´»»ª»ô ³¿¨ò î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´»ô º»®®«´»- ðòîë ³³n ©·¬¸±«¬ °´¿-¬·½ -´»»ª» ³·²ò î ½±²¼«½¬±®- ©·¬¸ -¿³» ½®±-- -»½¬·±²ô º´»¨·¾´»ô º»®®«´»- ïòë ³³n ©·¬¸±«¬ °´¿-¬·½ -´»»ª»ô ³¿¨ò ̧°» ±º ½±²²»½¬·±² ͽ®»© ½±²²»½¬·±² ͬ®·°°·²¹ ´»²¹¬¸ ç ³³ ײ¬»®²¿´ ½§´·²¼®·½¿´ ¹¿¹» ßì ͽ®»© ¬¸®»¿¼ Óí Ì·¹¸¬»²·²¹ ¬±®¯«»ô ³·² ðòê Ò³ ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» îñé ß«¹ ïîô îððë Page 238 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ý»®¬·º·½¿¬»- ÝËÔ Ò±³·²¿´ ª±´¬¿¹» ËÒ Ò±³·²¿´ ½«®®»²¬ ×Ò ßÉÙñµ½³·´ ËÔ Ò±³·²¿´ ª±´¬¿¹» ËÒ Ò±³·²¿´ ½«®®»²¬ ×Ò ßÉÙñµ½³·´ êðð Ê ïê ß îêóïð êðð Ê ïê ß îêóïð ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» íñé ß«¹ ïîô îððë Page 239 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ü®¿©·²¹- Ý·®½«·¬ ¼·¿¹®¿³ ß°°®±ª¿´ ´±¹± ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» ìñé ß«¹ ïîô îððë Page 240 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ ß½½»--±®·»- ׬»³ ß--»³¾´§ ðèðïéêî ïîðéêìð ïîðéêëí ïîðéêêê ðèðïéíí ðèðïêèï ïîðïéëê ïîðïèçë ïîðéêéç ïîðéêèî ïîðéêçë ïîðïéíð ïîðïéïì ïîðïéçè Þ®·¼¹»íðíðííê íðíðîìî íðíðîëë íðíðíìç íðíðîéï íðíðíêë íðìéðêð Ü»-·¹²¿¬·±² Ü»-½®·°¬·±² ÒÍ íëñ éôë ÝË ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñ éôë ÐÛÎÚ éëëÓÓ ÒÍ íëñ éôë ÐÛÎÚ çëëÓÓ ÒÍ íëñ éôë ÐÛÎÚ ïïëëÓÓ ÒÍ íëñ éôë ÐÛÎÚ îðððÓÓ ÒÍ íëñ éôë ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñïë ßÔ ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñïë ÝË ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñïë ÐÛÎÚ éëëÓÓ ÒÍ íëñïë ÐÛÎÚ çëëÓÓ ÒÍ íëñïë ÐÛÎÚ ïïëëÓÓ ÒÍ íëñïë ÐÛÎÚ îðððÓÓ ÒÍ íëñïë ËÒÐÛÎÚ îðððÓÓ ÒÍ íëñïëóîôí ËÒÐÛÎÚ îðððÓÓ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ݱ°°»®ô «²°»®º±®¿¬»¼ô ¸»·¹¸¬ éòë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ éòë ³³ô ´»²¹¬¸ éëë ³³ ÒÍíë Ü×Ò ®¿·´ô ¸»·¹¸¬ éòë ³³ô ´»²¹¬¸ çëë ³³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ éòë ³³ô ´»²¹¬¸ ïïëë ³³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô °»®º±®¿¬»¼ô ¸»·¹¸¬ éòë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô «²°»®º±®¿¬»¼ô ¸»·¹¸¬ éòë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ Ü×Ò ®¿·´ô ¼»»°ó¼®¿©²ô ¸·¹¸ °®±º·´»ô «²°»®º±®¿¬»¼ô ïòë ³³ ¬¸·½µô ³¿¬»®·¿´æ ß´«³·²«³ô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸ î ³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ݱ°°»®ô «²°»®º±®¿¬»¼ô ïòë ³³ ¬¸·½µô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ ïë ³³ô ´»²¹¬¸ éëë ³³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ ïë ³³ô ´»²¹¬¸ çëë ³³ ÒÍ íë Ü×Ò ®¿·´ô ¸»·¹¸¬ ïë ³³ô ´»²¹¬¸ ïïëë ³³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô °»®º±®¿¬»¼ô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô «²°»®º±®¿¬»¼ô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ Ü×Ò ®¿·´ô ³¿¬»®·¿´æ ͬ»»´ô «²°»®º±®¿¬»¼ô îòí ³³ ¬¸·½µô ¸»·¹¸¬ ïë ³³ô ©·¼¬¸ íë ³³ô ´»²¹¬¸æ î ³ ÚÞÍ îóê ÚÞÍ íóê ÚÞÍ ìóê ÚÞÍ ëóê ÚÞÍ ïðóê ÚÞÍ îðóê ÎÞ ËÌ ïðóøîôëñì÷ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô îó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô íó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô ìó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô ëó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô ïðó °±-òô ½±´±®æ λ¼ д«¹ó·² ¾®·¼¹» º±® ½®±--ó½±²²»½¬·±²- ·² ¬¸» ¬»®³·²¿´ ½»²¬»®ô îðó °±-òô ½±´±®æ λ¼ λ¼«½·²¹ ¾®·¼¹»ô º±® ½±²²»½¬·±² º®±³ ËÌ ï𠬱 ËÌ ì ±® ËÌ îôë ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» ëñé ß«¹ ïîô îððë Page 241 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ËÌ ìóÓÌ Ó¿®µ·²¹ ðèïïîîè ïðëïðïê ëðêðçíë ïðëðìçç ÈóÐÛÒ ðôíë ÆÞ êôÔÙÍæÚÑÎÌÔòÆßØÔÛÒ ÆÞ êñÉØóïððæËÒÞÛÜÎËÝÕÌ ÆÞ êæÍÑñÝÓÍ Ó¿®µ»® °»² ©·¬¸±«¬ ·²µ ½¿®¬®·¼¹»ô º±® ³¿²«¿´ ´¿¾»´·²¹ ±º ³¿®µ»®-ô ´¿¾»´·²¹ »¨¬®»³»´§ ©·°»ó°®±±ºô ´·²» ¬¸·½µ²»-- ðòíë ³³ Æ¿½µ -¬®·°ô ïðó-»½¬·±²ô °®·²¬»¼ ¸±®·¦±²¬¿´´§æ ©·¬¸ ¬¸» ²«³¾»®-ô ïó ïðô ïïóî𠻬½ò «° ¬± ççïóïðððô ½±´±®æ ©¸·¬» Æ¿½µ -¬®·°ô «²°®·²¬»¼æ Ú±® ·²¼·ª·¼«¿´ ´¿¾»´·²¹ ©·¬¸ ÓóÐÛÒô ÆÞóÌ ±® ÝÓÍ -§-¬»³ô ´¿®¹» ¾¿¬½¸ô -«ºº·½·»²¬ º±® ´¿¾»´·²¹ ïðð𠬻®³·²¿´ ¾´±½µ-ô º±® ¿ ¬»®³·²¿´ ©·¼¬¸ ±º êòî ³³ô ½±´±®æ ɸ·¬» Æ¿½µ -¬®·°ô ïðó-»½¬·±²ô ¼·ª·-·¾´»ô -°»½·¿´ °®·²¬·²¹ô ³¿®µ·²¹ ¿½½±®¼·²¹ ¬± ½«-¬±³»® ®»¯«·®»³»²¬- д«¹ñß¼¿°¬»® ðîðïêèç ÓÐÍóר ÞË ðîðïêéê ÓÐÍóר ÎÜ ðîðïêêí ÓÐÍóר ÉØ ðîðïéìì ÓÐÍóÓÌ íðíðçîë Ðß×óì íðíðççê ÐÍóê Ì»-¬ °´«¹ô ½±²-·-¬·²¹ ±ºæ Ó»¬¿´ °¿®¬ º±® îòí ³³ ¼·¿³»¬»® -±½µ»¬ ¸±´» Ì»-¬ ¿¼¿°¬»®ô º±® ì ³³ ¼·¿³»¬»® ¬»-¬ °´«¹ ÐÍ ¿²¼ -¿º»¬§ ¬»-¬ °´«¹ô ³¿µ»- ½±²¬¿½¬ ·² ¬¸» ¾®·¼¹» -¸¿º¬ Ó±¼«´¿® ¬»-¬ °´«¹ô º±® ·²¼·ª·¼«¿´ ¿--»³¾´§ ±º ¬»-¬ °´«¹ -¬®·°-ô º±® ËÌô ÍÌô ÜÌ ¿²¼ ÏÌ ¬»®³·²¿´ ¾´±½µ-ô ½¿² ¾» ´¿¾»´»¼ ©·¬¸ ÆÞÚ êô ½±´±®æ λ¼ ̱±´ïîðëðëí ÍÆÍ ðôêÈíôë ͽ®»©¼®·ª»®ô ¾´¿¼»¼ô ³¿¬½¸»- ¿´´ -½®»© ¬»®³·²¿´ ¾´±½µ- «° ¬± ìòð ³³n ½±²²»½¬·±² ½®±-- -»½¬·±²ô ¾´¿¼»æ ðòê ¨ íòë ³³ô ©·¬¸±«¬ ÊÜÛ ¿°°®±ª¿´ ÐØÑÛÒ×È ÝÑÒÌßÝÌ Ù³¾Ø ú ݱò ÕÙ ¸¬¬°æññ©©©ò°¸±»²·¨½±²¬¿½¬ò½±³ Q-Pulse Id: TMS196 26/11/2012 п¹» êñé ß«¹ ïîô îððë Page 242 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 Feed-through modular terminal block, Type of connection: Screw connection, Cross section: 0.14 mm² - 6 mm², AWG 26 - 10, Width: 6.2 mm, Color: gray, Mounting type: NS 35/7,5, NS 35/15 Commercial data EAN Pack Customs tariff Weight/Piece Catalog page information Technical data General Number of levels Number of connections Color 4017918956592 50 pcs. 85369010 0.011431 KG Page 56 (CL-2009) 1 2 gray Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 1 / 7 Mar 24, 2010 Page 243 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 Insulating material PA Inflammability class acc. to UL 94 V0 Dimensions Width Length Height NS 35/7,5 Height NS 35/15 6.2 mm 57.8 mm 47.5 mm 55 mm Technical data Maximum load current Rated surge voltage Pollution degree Surge voltage category Insulating material group Connection in acc. with standard Nominal current IN Nominal voltage UN Open side panel 41 A (with 6 mm2 conductor cross section) 8 kV 3 III I IEC 60947-7-1 32 A 800 V ja Connection data Conductor cross section solid min. Conductor cross section solid max. Conductor cross section stranded min. Conductor cross section stranded max. Conductor cross section AWG/kcmil min. Conductor cross section AWG/kcmil max Conductor cross section stranded, with ferrule without plastic sleeve min. Conductor cross section stranded, with ferrule without plastic sleeve max. Conductor cross section stranded, with ferrule with plastic sleeve min. Conductor cross section stranded, with ferrule with plastic sleeve max. 2 conductors with same cross section, solid min. 2 conductors with same cross section, solid max. 2 conductors with same cross section, stranded min. 0.14 mm² 6 mm² 0.14 mm² 6 mm² 26 10 0.14 mm² 4 mm² 0.14 mm² 4 mm² 0.14 mm² 1.5 mm² 0.14 mm² PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 2 / 7 Mar 24, 2010 Page 244 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 2 conductors with same cross section, stranded max. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. Type of connection Stripping length Internal cylindrical gage Screw thread Tightening torque, min Tightening torque max 1.5 mm² 0.5 mm² 2.5 mm² 0.14 mm² 1.5 mm² Screw connection 9 mm A4 M3 0.6 Nm 0.8 Nm Certificates / Approvals Certification Certification Ex: CSA Nominal voltage UN Nominal current IN AWG/kcmil CUL Nominal voltage UN Nominal current IN AWG/kcmil UL Nominal voltage UN Nominal current IN AWG/kcmil PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 CB, CSA, CUL, DNV, GL, LR, UL, VDE-PZI IECEx, KEMA-EX 600 V 30 A 26-10 600 V 30 A 26-10 600 V 30 A 26-10 26/11/2012 Page 3 / 7 Mar 24, 2010 Page 245 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 Accessories Item Designation Description Assembly 3022276 3047141 0801762 1207640 1207653 1207666 0801733 0801681 1201756 1201895 1207679 1207682 1207695 1201730 1201714 1201798 CLIPFIX 35-5 Snap-on end bracket, for NS 35/7.5 or NS 35/15 DIN rail, can be fitted with Zack strip ZB 5 and ZBF 5, terminal strip marker KLM 2 and KLM, parking facility for FBS...5, FBS...6, KSS 5, KSS 6, width: 5,15 mm, color: gray D-UT 2,5/4-TWIN End cover, Width: 2.2 mm, Color: gray NS 35/ 7,5 CU UNPERF 2000MM DIN rail, material: Copper, unperforated, height 7.5 mm, width 35 mm, length: 2 m NS 35/ 7,5 PERF 755MM NS 35 DIN rail, height 7.5 mm, length 755 mm NS 35/ 7,5 PERF 955MM NS35 DIN rail, height 7.5 mm, length 955 mm NS 35/ 7,5 PERF 1155MM NS 35 DIN rail, height 7.5 mm, length 1155 mm NS 35/ 7,5 PERF 2000MM DIN rail, material: Steel, galvanized and passivated with a thick layer, perforated, height 7.5 mm, width 35 mm, length: 2 m NS 35/ 7,5 UNPERF 2000MM DIN rail, material: Steel, unperforated, height 7.5 mm, width 35 mm, length: 2 m NS 35/15 AL UNPERF 2000MM DIN rail, deep-drawn, high profile, unperforated, 1.5 mm thick, material: Aluminum, height 15 mm, width 35 mm, length 2 m NS 35/15 CU UNPERF 2000MM DIN rail, material: Copper, unperforated, 1.5 mm thick, height 15 mm, width 35 mm, length: 2 m NS 35/15 PERF 755MM NS 35 DIN rail, perforated, height 15 mm, length 755 mm NS 35/15 PERF 955MM NS 35 DIN rail, perforated, height 15 mm, length 955 mm NS 35/15 PERF 1155MM NS 35 DIN rail, perforated, height 15 mm, length 1155 mm NS 35/15 PERF 2000MM DIN rail, material: Steel, perforated, height 15 mm, width 35 mm, length: 2 m NS 35/15 UNPERF 2000MM DIN rail, material: Steel, unperforated, height 15 mm, width 35 mm, length: 2 m NS 35/15-2,3 UNPERF 2000MM DIN rail, material: Steel, unperforated, 2.3 mm thick, height 15 mm, width 35 mm, length: 2 m Bridges 3030336 3030242 3030255 3030349 3030271 3030365 3032224 FBS 2-6 FBS 3-6 FBS 4-6 FBS 5-6 FBS 10-6 FBS 20-6 FBS 50-6 Cross connector/bridge, Number of positions: 2, Color: red Cross connector/bridge, Number of positions: 3, Color: red Cross connector/bridge, Number of positions: 4, Color: red Cross connector/bridge, Number of positions: 5, Color: red Cross connector/bridge, Number of positions: 10, Color: red Cross connector/bridge, Number of positions: 20, Color: red Cross connector/bridge, Number of positions: 50, Color: red PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 4 / 7 Mar 24, 2010 Page 246 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-MTD Order No.: 3046184 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046184 3047060 Marking 1051993 0811228 1051016 1051032 1051029 1051045 1050499 1051003 RB UT 10-(2,5/4) B-STIFT X-PEN 0,35 ZB 6,LGS:FORTL.ZAHLEN ZB 6,LGS:GLEICHE ZAHLEN ZB 6,QR:FORTL.ZAHLEN ZB 6,QR:GLEICHE ZAHLEN ZB 6:SO/CMS ZB 6:UNBEDRUCKT Plug/Adapter 0201731 MPS-IH BK 0201702 MPS-IH GN 0201676 MPS-IH RD 0201663 MPS-IH WH 0201744 MPS-MT 3030925 PAI-4 3030996 PS-6 Tools 1205053 SZS 0,6X3,5 Diagrams/Drawings Circuit diagram Cross connector/bridge, Number of positions: 2, Color: red Marker pen, for manual labeling of unprinted Zack strips, smearproof and waterproof, line thickness 0.5 mm Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35 mm Zack strip, 10-section, printed horizontally: with the numbers, 1-10, 11-20 etc. up to 991-1000, color: white Zack marker strip, labeled horizontally: 10-section, with identical numbers, 1/1/1, 2/2/2 etc. up to 1000/1000/1000, color: white Zack strip, 10-section, printed vertically: with consecutive numbers, 1-10, 11-20 a.s.o. up to 991-1000, color: white Zack marker, labeled vertically: 10-section, with identical numbers, 1/1/1, 2/2/2 etc. up to 1000/1000/1000, color: White Zack strip, 10-section, divisible, special printing, marking according to customer requirements Zack strip, unprinted, strips with 10 labels for individual labeling with M-PEN or CMS system, for terminal block width: 6.2 mm, color: white Insulating sleeve, for MPS metal part, Color: black Insulating sleeve, for MPS metal part, Color: green Insulating sleeve, Color: red Insulating sleeve, for MPS metal part, Color: white Metal part Test adapter, Color: gray Test adapter, Color: red Screwdriver, bladed, matches all screw terminal blocks up to 4.0 mm² connection cross section, blade: 0.6 x 3.5 mm, without VDE approval PHOENIX CONTACT Deutschland GmbH http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 5 / 7 Mar 24, 2010 Page 247 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UBE/D + ES/KMK 3 Order No.: 1004076 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=1004076 Terminal strip marker carriers for marking terminal group, for mounting on the terminal strip NS 32 or NS 35/7.5, lettering field size: 40 x 17 mm Commercial data EAN Pack Customs tariff Weight/Piece 4017918011888 10 pcs. 85369010 0.0105 KG Product notes WEEE/RoHS-compliant since: 03/18/2004 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. Technical data General Color Base element material Inflammability class acc. to UL 94 Ambient temperature (operation) Components gray PA V2 -40 °C ... 100 °C free from silicone and halogen PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 1 / 2 May 7, 2009 Page 248 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-HESI (5X20) Order No.: 3046032 Extract from the online catalog http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046032 Fuse modular terminal block, Connection method: Screw connection, Cross section: 0.14 mm²- 6 mm², AWG: 26 - 10, Nominal current: 6.3 A, Nominal voltage: 500 V, Width: 6.2 mm, Fuse type: G / 5 x 20, Fuse type: Glass, Mounting type: NS 35/7,5, NS 35/15, Color: black Commercial data EAN Pack Customs tariff Weight/Piece Catalog page information 4017918956578 50 pcs. 85369010 0.018103 KG Page 44 (CL-2009) Technical data General Number of levels Number of connections Color 1 2 black Product notes WEEE/RoHS-compliant since: 01/01/2003 http:// www.download.phoenixcontact.com Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation. The General Terms and Conditions of Use apply to Internet downloads. PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 1 / 5 May 6, 2009 Page 249 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-HESI (5X20) Order No.: 3046032 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046032 Insulating material PA Inflammability class acc. to UL 94 V0 Dimensions Width Length Height NS 35/7,5 Height NS 35/15 6.2 mm 57.8 mm 73 mm 80.5 mm Technical data Fuse Fuse type Rated surge voltage Pollution degree Surge voltage category Insulating material group Connection in acc. with standard Nominal current IN Nominal voltage UN G / 5 x 20 Glass 4 kV 3 III I IEC 60947-7-3 6.3 A 500 V (if used as fuse terminal block) 500 V (if used as disconnect terminal block) Connection data Conductor cross section solid min. Conductor cross section solid max. Conductor cross section stranded min. Conductor cross section stranded max. Conductor cross section AWG/kcmil min. Conductor cross section AWG/kcmil max Conductor cross section stranded, with ferrule without plastic sleeve min. Conductor cross section stranded, with ferrule without plastic sleeve max. Conductor cross section stranded, with ferrule with plastic sleeve min. Conductor cross section stranded, with ferrule with plastic sleeve max. 2 conductors with same cross section, solid min. 2 conductors with same cross section, solid max. 0.14 mm² 6 mm² 0.14 mm² 6 mm² 26 10 0.14 mm² 4 mm² 0.14 mm² 4 mm² 0.14 mm² 1.5 mm² PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 2 / 5 May 6, 2009 Page 250 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-HESI (5X20) Order No.: 3046032 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046032 2 conductors with same cross section, stranded min. 2 conductors with same cross section, stranded max. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. Type of connection Stripping length Internal cylindrical gage Screw thread Tightening torque, min Tightening torque max 0.14 mm² 1.5 mm² 0.14 mm² 1.5 mm² 0.5 mm² 2.5 mm² Screw connection 9 mm A4 M3 0.6 Nm 0.8 Nm Certificates / Approvals Certification CSA Nominal voltage UN Nominal current IN AWG/kcmil CUL Nominal voltage UN Nominal current IN AWG/kcmil UL Nominal voltage UN Nominal current IN AWG/kcmil PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 CB, CSA, CUL, DNV, GL, KEMA, LR, UL 600 V 6.3 A 26-10 600 V 6.3 A 26-10 600 V 6.3 A 26-10 26/11/2012 Page 3 / 5 May 6, 2009 Page 251 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UT 4-HESI (5X20) Order No.: 3046032 http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=3046032 Drawings Application drawing Fuse terminal blocks in interconnected arrangement, block consisting of 5 fuse terminal blocks Circuit diagram Fuse terminal block in single arrangement, block consisting of one fuse terminal block and 4 feed-through terminal blocks PHOENIX CONTACT GmbH & Co. KG http://www.phoenixcontact.de Q-Pulse Id: TMS196 26/11/2012 Page 4 / 5 May 6, 2009 Page 252 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual CLIPSAL NEUTRAL-ACTIVE-METER LINKS CLIPSAL NEUTRAL / ACTIVE / METER LINKS Clipsal Links are produced from Impact Resistant materials to prevent cracking in transit or during installation. The transparent covers enable you to check wiring and locate the sealing screw at a glance. The sealing screw (nylon with brass insert) resists stripping. Voltage and amperage ratings are clearly marked on both the cover and brass bar. All links are available with black or red covers and bases for neutral, active or meter applications as required by local authorities. T-Type - 500 Volt 140 Ampere L4T35 500V 140A 4 Hole Neutral Link with two screws per tunnel. Black base and cover. L4T35R 500V 140A 4 Hole Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 28mm. 1 tunnel 8.7mm diameter accommodate 1 x 25mm2 cable. 3 tunnels 7.7mm diameter accommodate 1 x 25mm2 cable. Certificate of Suitability No. CS2252N. L4T35R Mini Links with Cover 500V 100A 2 screws per tunnel. L5 500V 100A 5 Hole Neutral Link with two screws per tunnel. Black base and cover. L5R 500V 100A 5 Hole Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 46mm. 3 tunnels, 6.3mm diameter accommodate 1 x 16mm2. 2 tunnels, 5.8mm diameter accommodate 1 x 16mm2. L5BW 500V 110A 5 Hole Back Wiring Neutral Link with two screws per tunnel. Black base and cover. L5BWR 500V 110A 5 Hole Back Wiring Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 46mm. 5 tunnels, 7mm diameter accommodate 1 x 25mm2. Transparent black cover, with cut outs. L6R 500V 100A 6 Hole Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 46mm. 3 tunnels, 6.3mm diameter accommodate 1 x 16mm2 cable. 3 tunnels, 5.8mm diameter accommodate 1 x 16mm2 cable. L6/25 500V 110A 6 Hole Neutral Link with 2 screws per tunnel. Black base and cover. L6/25R 500V 110A 6 Hole Active Link. Red base and cover. Dimensions: 65 x 46 x 43mm. Mounting centres: 46mm. 2 tunnels, 7.5mm diameter accommodate 2 x 25mm2 cable. 1 tunnel, 5.5mm diameter accommodates 1 x 16mm2 cable. 3 tunnels, 4.7mm diameter accommodate 3 x 10mm2 cable. Transparent black cover with cut-outs. L7 500V 100A 7 Hole Neutral Link with two screws per tunnel. Black base and cover. L6 500V 100A 6 Hole Neutral Link with 21 two screws per tunnel. Black base and cover. L7 Q-Pulse Id: TMS196 26/11/2012 Page 253 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4.7 TELEMETRY & POWER Schneider SCADAPACK ES Telemetry Unit Clipsal 2015/15 + 90B 1Phase 15A Outlet Mennekes 3658 3Phase +N+E Inlet Powerbox PB251-24CM - 24VDC 10A Power Supply Yuasa NP7-12FR 12v 7Ah Battery Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 254 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual SCADAPack 330E | 334E Smart RTU Q-Pulse Id: TMS196 26/11/2012 Page 255 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 1 Built on a native DNP3 architecture, the SCADAPack 330E and 334E feature high-performance 32-bit processing, highspeed LAN, serial and USB communications, integrated power supply, advanced power-management, and a wide range of digital and analog I/O in a cost-effective, compact Smart RTU. The level 4 compliant DNP3 protocol comes with optional AGA12 encryption to improve message security for critical operations, and support for the open protocols of Modbus and IEC60870-5 is also offered. The SCADAPack 330E / 334E can be programmed locally or remotely using the IEC61131-3 programming language and is optionally configurable directly from ClearSCADA host software. This product offers a small footprint, enabling compact mounting enclosures for applications where space is at a premium. The SCADAPack 330E is well suited for applications that require a communications hub but no I/O, while the SCADAPack 334E adds a variety of integrated I/O. Note that the SCADAPack 334E has the same I/O offering as the SCADAPack 314E but includes an Ethernet port and a third serial port. Q-Pulse Id: TMS196 26/11/2012 Page 256 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 2 Product Data Sheet SCADAPack 330E | 334E Specifications P330E: 5210 controller board only Controller Processors · CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer · Microcontroller co-processor, 20 MHz clock Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM Non-Volatile RAM CMOS SRAM with lithium battery retains contents for 2 years with no power Event Logging Capacity 20,000 events Maximum Database Points 1,000 typical I/O Counter Inputs · 1, 0-10Hz or 0-5kHz (dry contact) · 2, 0-10kHz (turbine or dry contact) Communications Serial Ports COM1, COM2 · RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or · RS-485 port, 2-wire, half duplex Serial Port COM3 · RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 Serial Protocols DNP3 Slave, DNP3 Master, IEC60870-5-101 Slave, IEC60870-5-103 Master, Modbus RTU Master, Modbus RTU Slave, DF1 Ethernet Port RJ45, 10/100BaseT Ethernet Protocols DNP3 in TCP Master/Slave, DNP3 in UDP Master/Slave, Modbus/TCP Client and Server, IEC60870-5-104 Slave, NTP Server, Telnet Server, FTP Server, BOOTP Server USB Peripheral Port USB 2.0 compliant "B"-type receptacle, DNP3 protocol Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2 General I/O Terminations 6-pole removable terminal block, 12 to 22AWG, 15A contacts Dimensions 5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep Packaging Corrosion resistant zinc-plated steel with black enamel paint Environment 5% RH to 95%, non-condensing, 40°C (40°F) to 70°C (158°F) Power Input · 11 - 30VDC, 3.5W typical · Add 25 to 100mW when enabling the LEDs · 12W at 24V maximum, 5V supply fully loaded Warranty 3 years on parts and labor Certifications Hazardous Locations North America Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the requirements of: · CSA Std. C22.2 No. 213-M1987 - Hazardous Locations. · UL Std. No. 1604 - Hazardous (Classified) Locations. Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions. Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions. 1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.controlmicrosystems.com. Q-Pulse Id: TMS196 26/11/2012 Page 257 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 3 Product Data Sheet SCADAPack 330E | 334E Specifications P334E: 5210 controller board and integrated 5607 I/O board Controller Processors · CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer · Microcontroller co-processor, 20 MHz clock Memory 16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM Non-Volalite RAM CMOS SRAM with lithium battery retains contents for 2 years with no power Event Logging Capacity 20,000 events Maximum Database Points 1,000 typical I/O Analog Inputs 8, 0-20/4-20mA / 0-5/0-10V (15-bit) software configurable Analog Outputs · Standard: None · 2, 0-20/4-20mA (12-bit) with optional 5305 on 5607 I/O board Digital I/O · 16, 12/24V, 48V, 115/125V, 240V digital inputs · 10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive), DC solid state rating: 3A, 60 VDC Counter Inputs 1, 0-10Hz or 0-5kHz (dry contact); 2, 0-10kHz (turbine or dry contact) Communications Serial Ports COM1, COM2 · RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or · RS-485 port, 2-wire, half duplex Serial Port COM3 RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control Baud Rates 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 Serial Protocols DNP3 Slave, DNP3 Master, IEC60870-5-101 Slave, IEC60870-5-103 Master, Modbus RTU Master, Modbus RTU Slave, DF1 Ethernet Port RJ45, 10/100BaseT Ethernet Protocols DNP3 in TCP Master/Slave, DNP3 in UDP Master/Slave, Modbus/TCP Client and Server, IEC60870-5-104 Slave, NTP Server, Telnet Server, FTP Server, BOOTP Server USB Peripheral Port USB 2.0 compliant "B"-type receptacle, DNP3 protocol Wireless1 Spread spectrum radio at 900MHz2 and 2.4GHz2 General I/O Terminations 5, 6 and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts Dimensions 5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep Packaging Corrosion resistant zinc-plated steel with black enamel paint Environment Power 5210 Controller Board 5% RH to 95%, non-condensing, 40°C (40°F) to 70°C (158°F) · 11 - 30VDC, 8.5W typical · Add 25 to 100mW when enabling the LEDs · 12W at 24V maximum, 5V supply fully loaded 5607 I/O Module · 11 - 30VDC, 10.3mA plus analog outputs · 325mA (max.) at 5V required from 5210 controller board Warranty 3 years on parts and labor Certifications Hazardous Locations North America Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the requirements of: · CSA Std. C22.2 No. 213-M1987 - Hazardous Locations. · UL Std. No. 1604 - Hazardous (Classified) Locations. Hazardous Locations - Europe ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions. Hazardous Locations IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions. 1 Available only with optional integrated wireless modules or with stand-alone wireless modules. 2 Not applicable in all countries. Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.controlmicrosystems.com. Q-Pulse Id: TMS196 26/11/2012 Page 258 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 4 Product Data Sheet SCADAPack 330E | 334E Model Code Model P330 P334 Code E Code A B Code 5 6 Code 5 Code A Code A B C D E F G H I Code 0 1 Code 0 1 2 A B C D E J K L P334-EA55-AB00 represents a sample code for a SCADAPack 334E with 12V dry contact relay outputs Select: Controller SCADAPack 330E , 32 Bit controller, 3 Accumulators SCADAPack 334E, with Model 5607 I/O board, comes with above I/O plus 8 Analog I/P, 16 Digital I/P and 10 Digital O/P Select: Platform E Firmware platform (Configuration Software included), executes two IEC61131-3 kernels, Workbench required Select: SCADA Security None AGA-12 SCADA Encryption Security Select: Protocol Option Modbus, DNP3, DF1, Modbus/TCP, TCP/IP, IEC 60870-5-101/104 Slave (included in all controllers) Adds IEC 60870-5-103 Master, Protection Relay Protocol (for data transmission with IEDs) Select: License Option DNP3 Data Concentrator License (limit of 500 points from 10 IEDs), supports multiple DNP3 Masters (up to 3 Masters) Select: Analog Inputs P330 : None P334 : adds 8 selectable as 0-20mA, 4-20mA, 0-5V or 0-10V Select: Digital Inputs/Outputs P330 : None P334 : 16 Digital Inputs (12/24V) and 10 Dry Contact Relay outputs P334 : 16 Digital Inputs (48V) and 10 Dry Contact Relay outputs P334 : 16 Digital Inputs (120V) and 10 Dry Contact Relay outputs P334 : 16 Digital Inputs (240V) and 10 Dry Contact Relay outputs P334 : 16 Digital Inputs (12/24V) and 10 Solid State Relay outputs, ATEX Certified (with no Integrated radio) P334 : 16 Digital Inputs (48V) and 10 Solid State Relay outputs P334 : 16 Digital Inputs (120V) and 10 Solid State Relay outputs P334 : 16 Digital Inputs (240V) and 10 Solid State Relay outputs Select: Analog Outputs None P334 only : 2 channel Analog Output option, 0-20 mA Select: Integrated Communication Interfaces None FreeWave & MDS Radios (requires one RS232 port) 900Mhz FreeWave Spread Spectrum Radio 2.4GHz FreeWave Spread Spectrum Radio 900MHz MDS Spread Spectrum Radio Trio Radios - 900MHz (requires one RS232 port) 900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC) 900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS) 900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL) 900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ) Trio Radios - 2.4GHz (requires one RS232 port) 2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE) 2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA) 2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA) © 2011 Schneider Electric. All rights reserved - August 2011 Telemetry & Remote SCADA Solutions | www.controlmicrosystems.com Q-Pulse Id: TMS196 26/11/2012 Document Number M01018 Page 259 of 382 HOW TO ORDER SWITCHED SOCKET OUTLETS WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual HOW TO ORDER SWITCHED SOCKET OUTLETS Switched Socket Outlets are often referred to as GPOs (General Purpose Outlets), Powerpoints or Power Outlets. So that there is no confusion, the description `Switched Socket Outlets' will be used throughout this brochure. Single and Twin Socket Outlets are available in 2000 Series in horizontal and vertical formats. Catalogue Numbers will vary depending on the number of sockets and whether the product is horizontally or vertically mounted. This number indicates the number of switched sockets included in the product. The plate size remains the same for both single and twin switched socket outlets, only the number of switches and sockets vary. 2015V The letter `V' indicates that the product is vertically mounted. Where there is no letter `V', the product is horizontally mounted. Single Horizontal Single Vertical Twin Horizontal Twin Vertical 2015 2015V Please note: Single Automatically Switched Socket Outlets are also available (Catalogue Number 2010 - Page 28). Special Features and Options 2000 Series Switched Socket Outlets may also be ordered with special features, including an extra switch mechanism, safety shutters, neons, double pole switched versions, deep plate format products and more. Please see the main part of the brochure for Combination (Page 30) and Automatic (Page 28) versions with special features. Ordering Colours When ordering Switched Socket Outlets, colour variations also have to be taken into consideration, as the Catalogue Number will change depending on the colour of the product. Each colour has its own `code', for example, the code for White Electric is `WE' and the code for Cream is `CM'. The Catalogue Number for a 2000 Series Twin Switched Socket Outlet in White Electric is 2025,WE. Refer to `2000 Series Colours' on page 12 for colour options and their corresponding codes. 2025 Q-Pulse Id: TMS196 26/11/2012 2025V 11 Page 260 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual COMBINATION SWITCHED SOCKET OUTLETS STANDARD SIZE TWIN SWITCHED SOCKET OUTLETS - HORIZONTALLY MOUNTED Cat. No. Length Width Depth Mounting Centres 2025, 2025S, 2025N, 2025L, 2025XA, 116mm 76mm 28mm 84mm apart A 2025XAN, 2025FO 2025QC 116mm 76mm 31mm 84mm apart 2025SM 116mm 76mm 30mm 84mm apart B 2025V3/30PF 290mm 116mm 13mm See template 2025 A Twin Switched Socket Outlet, 250V/10A. C 2025S A Twin Switched Socket Outlet, 250V/10A, with safety shutters. 2025N B Twin Switched Socket Outlet, 250V/10A, with safety shutters and neons. D 2025L C Twin Switched Socket Outlet, 250V/10A, with round earth pin. 2025QC 2025FO 2025V3/30PF A Twin Switched Socket Outlet, 250V/10A, Quick Connect. D Twin Switched Socket Outlet, 250V/10A, printed with `NOT PROTECTED BY SAFETY SWITCH. FRIDGE/FREEZER ONLY'. E "PowertainmentTM" Six Socket Outlets, F-Type Pay TV Outlet in 2000/4 Surround, 250V/10A. E F 2025XA F Twin Switched Socket Outlet, 250V/10A, with removable extra switch. 2025XAN G Twin Switched Socket Outlet, 250V/10A with safety shutters, neons and removable extra switch. G 2025SM H Twin Switched Socket Outlet, 250V/10A, with surface mounting kit. 33 2025XAS F Twin Switched Socket Outlet, 250V/10A, with removable extra switch and safety shutters. H All models accommodate 4 x 2.5mm² cables. 30 Series Switch Terminals accommodate 3 x 2.5mm² on the 2025XA and 2025XAN. All models have a base projection of 13mm, except for 2025QC which has a base projection of 14mm. * Refer to Page 62 for more information on "PowertainmentTM". * Refer to Page 53 for mounting templates. Q-Pulse Id: TMS196 26/11/2012 Page 261 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual SCHEMATIC WIRING DIAGRAMS Standard Pattern Mounting Twin Combination 2025 2025V SCHEMATIC WIRING DIAGRAMS Twin Switched Sockets with Extra Switch Earth Leakage Protected Twin Switched Sockets 2025XA 2025VXA 2025RC 52 Q-Pulse Id: TMS196 26/11/2012 Page 262 of 382 SECURITY WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual PB251 Series 220-330 WATTS DC UPS Features · Ultra-low noise output · Independent battery charging output · DC output OK & battery OK alarms & LEDs · Battery-LVD and alarm · Over-temperature protection · Battery fuse fail LED Specifications INPUT Voltage: Line regulation: Current: Inrush current: Frequency: OUTPUT Voltage Current Load regulation Current limit type - load cct Current limit type - batt. cct Short circuit protection Over-voltage protection Ripple & noise 100 MHz bandwidth ENVIRONMENTAL Operating temperature Over-temperature protection Cooling requirement Efficiency 190 to 264 vac, or 190 to 400VDC 0.2%typical 1.4A maximum 10A maximum 45 to 65 Hz See table See table 0.5%typical Constant current Constant current Indefi nite, auto-resetting 17.5 to 20V latching (13.8Vdc output) 31.5 to 39V latching (27.6Vdc output) 28mVp-p (13.8Vdc output) 55mVp-p (27.6Vdc output) 0 to 70oC ambient with derating, 5...90% relative humidity (non-condensing) Automatic & auto-resetting Natural convection 80% minimum Selection Table STANDARDS & APPROVALS Safety EMC Complies with AS/NZS 60950, class 1, NSW Office of Fair Trading Approval N20602 Emissions comply with AS/NZS CISPR11, Group 1, Class B. Complies with ACA EMC Scheme, Safety & EMC Regulatory Compliance Marked Isolation i/p-o/p i/p-ground o/p-ground 4242VDC for 1 minute 2121VDC for 1 minute 707VDC for 1 minute ALARMS & BATTERY FUNCTIONS Converter ON/OK alarm Indicated by voltage-free changeover relay contacts & green LED ON=PSU OK Battery low (& fuse) alarm 10.2 to 12.6V for 12V battery, adjustable 20.4 to 25.2V for 24V battery, adjustable Indicated by voltage-free changeover relay contacts & green LED: ON=BATT OK Low voltage disconnect Charger over-load protection 9.6 to 12V for 12V battery, adjustable 19.2 to 24V2 for 4V battery, adjustable Auto-resetting electronic circuit breaker Reverse polarity protection Internal battery fuse Battery to load voltage drop MECHANICAL 0.2 to. 0.25V typical Case size 264 L x 172 W x 67 H mm Case size with heatsink 264 L x 186 W x 67 H mm Rack size 232 D x 19" W x 2RU H Weight 1.9 kg Weight with heatsink 2.1 kg Weight (rack mounted version) 5.5 kg MODEL NUMBER PB251-12CM PB251-12CM-H PB251-24CM PB251-24CM-H PB251-12RML PB251-12B PB251-24RML 322 VDC 13.8V 13.8V 27.6V 27.6V 13.8V 13.8V 27.6V OUTPUT ILOAD 16A 20A 11A 12A 20A 20A 12A IBATT 2A 2A 2A 2A 4A 4A 2A OUTPUT POWER 220W 275W 300W 330W 275W 275W 330W Note: Non standard battery charging current available on request. ie PB251-12CM-H-10 for 10A. Q-Pulse Id: TMS196 26/11/2012 Page 263 of 382 SECURITY WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual PB251 Series 275-330 WATTS DC UPS Technical Illustrations Q-Pulse Id: TMS196 Your dependable power partner www.powerbox.com.au 26/11/2012 323 Page 264 of 382 Data Sheet WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual NP SERIES - NP7-12 Reliability is your Security Utilizing the latest advance design Oxygen Recombination Technology, Yuasa have applied their 80 years of experience in the lead acid battery field to produce the optimum design of Sealed Lead Acid batteries. FEATURES Superb recovery from deep discharge. Electrolyte suspension system. Gas Recombination. Multipurpose: Float or Cyclic use. Usable in any orientation Superior energy density. Lead calcium grids for extended life. Manufactured World wide. Application specific designs. Technical Features Sealed Construction Yuasa's unique construction and sealing technique ensures no electrolyte leakage from case or terminals. Electrolyte Suspension System All NP batteries utilize Yuasa's unique electrolyte suspension system incorporating a microfine glass mat to retain the maximum amount of electrolyte in the cells. The electrolyte is retained in the separator material and there is no free electrolyte to escape from the cells. No gels or other contaminants are added. Control of Gas Generation The design of Yuasa's NP batteries incorporates the very latest oxygen recombination technology to effectively control the generation of gas during normal use. Low Maintenance Operation Due to the perfectly sealed construction and the recombination of gasses within the cell, the battery is almost maintenance free. Terminals Terminals NP batteries are manufactured using a range of terminals which vary in size and type. Please refer to details as shown. Operation in any Orientation The combination of sealed construction and Yuasa's unique electrolyte suspension system allows operation in any orientation, with no loss of performance or fear of electrolyte leakage. Valve Regulated Design The batteries are equipped with a simple, safe low pressure venting system which releases excess gas and automatically reseals should there be a build up of gas within the battery due to severe overcharge. Note. On no account should the battery be charged in a sealed container. General Specifications Layout Nominal Capacity (Ah) 20hr to 1 .75vpc 30ºC 1 0hr to 1 .75vpc 20ºC 5hr to 1.70vpc 20ºC 1 hr to 1 .60vpc 20ºC Voltage Energy Density (Wh.L.20hr) Specific Energy (Wh.kg.20hr) Int. Resistance (m.Ohms) Maximum discharge (A) Short Circuit current (A) Dimensions (mm) Length Width Height overall Weight (Kg) Terminal Layout Terminal Torque Nm NP7-12 7 6.4 5.9 4.2 12 91 32 25 40/75 210 151 65 97.5 2.65 A/D 4 - Q-Pulse Idw: TMwS1w96 .yuasabatteries.com 26/11/2012 NP Page 265 of 382 Data Sheet WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual NP SERIES - NP7-12 Lead Calcium Grids The heavy duty lead calcium alloy grids provide an extra margin of performance and life in both cyclic and float applications and give unparalleled recovery from deep discharge. Long Cycle Service Life Depending upon the average depth of discharge, over a thousand discharge/charge cycles can be expected. Float Service Life The expected service life is five years in float standby applications. Separators The use of the special separator material provides a very efficient insulation between plates preventing inter-plate short circuits and prohibiting the shedding of active materials. Long shelf Life The extremely low self discharge rate allows the battery to be stored for extended periods up to one year at normal ambient temperatures with no permanent loss of capacity. Operating Temperature Range The batteries can be used over a broad temperature range permitting considerable flexibility in system design and location. Charge 15°C to 50°C Discharge 20°C to 60°C Storage 20°C to 50°C (fully charged battery) Q-Pulse Id: TMS196 Yuasa Battery Inc. 2901 Montrose Ave Laureldale, PA 19605 www.yuasabatteries.com Registered number 1548820 Cat. No. NP7-12 January 0286/11/2012 Distributed by Page 266 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 4.8 ACCESSORIES Wavecom GSM - Modem Trio Datacom DR900-06A02-D0 - Radio Powerbox VTA12SC24 24v/13.8VDC Converter (Radio) Innovative Energies IE XR/MV-8 24v/9VDC Converter (GSM) RF Industries TLA2000 - Antenna Trio Datacom Yagi Ant13al - Antenna Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 267 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Plug and Play Wireless CPU® FASTRACK Supreme User Guide Reference: WA_DEV_Fastrk_UGD_001 Revision: 001e Date: 5 june, 2007 Supports Open AT® embedded ANSI C applications confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 1 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 268 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Document History Revision 001 001a 001b 001c 001d 001e Date 9 February, 07 23 February, 2007 21 May, 07 1 Jun, 07 4 Jun, 07 5 Jun, 07 List of revisions First Issue Update DC cable GPIO mapping, add AutoShutDown Add detail of IES, RTC and serial port autoshutdown Change to Quad Band Update label/packaging photo Comment confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 2 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 269 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Overview Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 The FASTRACK Supreme 10 and FASTRACK Supreme 20 are discrete, rugged cellular Plug & Play Wireless CPU® offering state-of-the-art GSM/GPRS (and EGPRS for FASTRACK Supreme 20) connectivity for machine to machine applications. Proven for reliable, stable performance on wireless networks worldwide, Wavecom's latest generation of FASTRACK Supreme continues to deliver rapid time to market and painless integration. Having comparable size with the previous M1306B generation, and updated with new features, the FASTRACK Supreme offers an Internal Expansion Socket (IES) interface accessible for customer use. Expanding application features is easy without voiding the warrantee of the FASTRACK Supreme by simply plugging in of an Internal Expansion Socket Module (IESM) board. Fully certified, the quad band 850/900/1800/1900 MHz FASTRACK Supreme 10 offers GPRS Class 10 capability and FASTRACK Supreme 20 offers GPRS/EGPRS Class 10 capability. Both support a powerful open software platform (Open AT®). Open AT® is the world's most comprehensive cellular development environment, which allows embedded standard ANSI C applications to be natively executed directly on the Wireless CPU®. FASTRACK Supreme is controlled by firmware through a set of AT commands. This document describes the FASTRACK Supreme and gives information on the following topics: · general presentation, · functional description, · basic services available, · technical characteristics, · installing and using the FASTRACK Supreme, · user-level troubleshooting. · recommended accessories to be used with the product. Note: This document covers the FASTRACK Supreme Plug & Play alone and does not include The programmable capabilities provided via the use of Open AT® Software Suites. The development guide for IESM for expanding the application feature through the IES interface. For detailed, please refer to the documents shown in the "Reference documents" section. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 3 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 270 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual RoHS Directive Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 The FASTRACK Supreme is now compliant with RoHS Directive 2002/95/EC, which sets limits for the use of certain restricted hazardous substances. This directive states that "from 1st July 2006, new electrical and electronic equipment put on the market does not contain lead, mercury, cadmium, hexavalent chromium, polybrominated biphenyls (PBB), and polybrominated diphenyl ethers (PBDE)". Plug & Plays which are compliant with this directive are identified by the RoHS logo on their label. Disposing of the product This electronic product is subject to the EU Directive 2002/96/EC for Waste Electrical and Electronic Equipment (WEEE). As such, this product must not be disposed off at a municipal waste collection point. Please refer to local regulations for directions on how to dispose off this product in an environmental friendly manner. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 4 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 271 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Cautions Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Information furnished herein by WAVECOM is accurate and reliable. However, no responsibility is assumed for its use. Please read carefully the safety recommendations given in Section 9 for an application based on FASTRACK Supreme Plug & Play. Trademarks ®, WAVECOM®, Wireless CPU®, Open AT® and certain other trademarks and logos appearing on this document, are filed or registered trademarks of Wavecom S.A. in France or in other countries. All other company and/or product names mentioned may be filed or registered trademarks of their respective owners. Copyright This manual is copyrighted by WAVECOM with all rights reserved. No part of this manual may be reproduced in any form without the prior written permission of WAVECOM. No patent liability is assumed with respect to the use of their respective owners. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 5 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 272 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Web Site Support General information about Wavecom and its range of products: Specific support is available for the FASTRACK Supreme Plug & Play Wireless CPU®: Open AT® Introduction: Developer community for software and hardware: www.wavecom.com TBD www.wavecom.com/OpenAT www.wavecom.com/forum confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 6 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 273 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Contents Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 DOCUMENT HISTORY ......................................................................................................................................2 OVERVIEW ........................................................................................................................................................3 CAUTIONS .........................................................................................................................................................5 TRADEMARKS ..................................................................................................................................................5 COPYRIGHT ......................................................................................................................................................5 WEB SITE SUPPORT ........................................................................................................................................6 CONTENTS ........................................................................................................................................................7 LIST OF FIGURES ...........................................................................................................................................11 LIST OF TABLES.............................................................................................................................................12 1 REFERENCES .........................................................................................................................................13 1.1 Reference Documents.........................................................................................................................13 1.1.1 Open AT® Software Documentation ..........................................................................................13 1.1.2 AT Software Documentation......................................................................................................13 1.1.3 Firmware Upgrade Documents..................................................................................................13 1.1.4 Delta between M1306B Documents..........................................................................................13 1.1.5 IESM Related Documents .........................................................................................................13 1.2 Abbreviations .......................................................................................................................................14 2 PACKAGING ............................................................................................................................................17 2.1 Contents ..............................................................................................................................................17 2.2 Packaging Box.....................................................................................................................................18 2.3 Production Labelling ............................................................................................................................19 3 GENERAL PRESENTATION ...................................................................................................................20 3.1 Description...........................................................................................................................................20 3.2 External Connections ..........................................................................................................................22 3.2.1 Connectors ................................................................................................................................22 3.2.1.1 Antenna Connector ............................................................................................................22 3.2.1.2 Power Supply Connector ...................................................................................................22 3.2.1.3 Sub HD 15-pin Connector..................................................................................................23 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 7 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 274 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 3.2.1.4 IES Connector....................................................................................................................25 3.2.2 Power supply cable ...................................................................................................................29 4 FEATURES AND SERVICES...................................................................................................................31 4.1 Basic Features and Services...............................................................................................................31 4.2 Additional NEW Features ....................................................................................................................34 4.2.1 Support Additional GSM850/PCS1900 Bands ..........................................................................34 4.2.2 IES Interface for Easy Expansion of Application Features........................................................34 4.2.3 Serial Port Auto Shut Down or Improving Power Consumption ................................................34 4.2.4 Real Time Clock (RTC) for Saving Date and Time ...................................................................34 4.2.5 SIM Card Lock Feature .............................................................................................................35 5 USING THE FASTRACK SUPREME PLUG & PLAY .............................................................................36 5.1 Getting Started.....................................................................................................................................36 5.1.1 Mount the FASTRACK Supreme...............................................................................................36 5.1.2 Set up the FASTRACK Supreme ..............................................................................................36 5.1.3 Check the communication with the FASTRACK Supreme........................................................37 5.1.4 Reset the FASTRACK Supreme ...............................................................................................37 5.2 Specific Recommendations when Using the FASTRACK Supreme on Trucks ..................................38 5.2.1 Recommended Power Supply Connection on Trucks...............................................................38 5.2.2 Technical Constraints on Trucks ...............................................................................................38 5.3 FASTRACK Supreme Operational Status...........................................................................................39 5.4 Echo Function Disabled.......................................................................................................................40 5.5 Verify the Received Signal Strength....................................................................................................41 5.6 Check the Pin Code Status .................................................................................................................41 5.7 Switch between EU/US Band(s)..........................................................................................................41 5.8 Check the Band(s) Selection ...............................................................................................................42 5.9 Verify the FASTRACK Supreme Network Registration .......................................................................43 5.10 Main AT Commands for the Plug & Play .............................................................................................44 5.11 Firmware Upgrade Procedure .............................................................................................................45 6 TROUBLESHOOTING .............................................................................................................................46 6.1 No Communication with the FASTRACK Supreme through the Serial Link .......................................46 6.2 Receiving "ERROR" Message.............................................................................................................46 6.3 Receiving "NO CARRIER" Message ...................................................................................................47 7 FUNCTIONAL DESCRIPTION .................................................................................................................50 7.1 Architecture..........................................................................................................................................50 7.2 EU and US Bands................................................................................................................................51 7.2.1 General Presentation.................................................................................................................51 7.2.2 AT COMMAND for Bands Switch ..............................................................................................51 7.3 Power Supply.......................................................................................................................................51 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 8 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 275 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 7.3.1 7.3.2 Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 General Presentation.................................................................................................................51 Protections.................................................................................................................................51 7.4 RS232 Serial Link ................................................................................................................................51 7.4.1 General Presentation.................................................................................................................51 7.4.2 Autobauding Mode ....................................................................................................................52 7.4.3 Pin Description...........................................................................................................................53 7.4.4 Serial Port Auto shut down Feature ..........................................................................................53 7.5 General Purpose Input/Output (GPIO) ................................................................................................54 7.6 BOOT...................................................................................................................................................54 7.7 RESET.................................................................................................................................................54 7.7.1 General presentation .................................................................................................................54 7.7.2 Reset Sequence ........................................................................................................................55 7.8 Audio....................................................................................................................................................56 7.8.1 Microphone Inputs .....................................................................................................................56 7.8.2 Speaker Outputs........................................................................................................................57 7.9 Real Time Clock (RTC) .......................................................................................................................58 7.10 FLASH LED 58 8 TECHNICAL CHARACTERISTICS..........................................................................................................59 8.1 Mechanical Characteristics..................................................................................................................59 8.2 Electrical Characteristics .....................................................................................................................61 8.2.1 Power Supply.............................................................................................................................61 8.2.2 Power Consumption ..................................................................................................................62 8.2.3 Audio Interface ..........................................................................................................................65 8.2.4 General Purpose Input/Output...................................................................................................66 8.2.5 SIM Interface .............................................................................................................................66 8.2.6 RESET Signal............................................................................................................................66 8.2.7 RF Characteristics .....................................................................................................................67 8.2.7.1 Frequency Ranges.............................................................................................................67 8.2.7.2 RF Performances...............................................................................................................68 8.2.7.3 External Antenna ...............................................................................................................69 8.3 Environmental Characteristics.............................................................................................................69 8.4 Conformity ...........................................................................................................................................72 8.5 Protections...........................................................................................................................................72 8.5.1 Power Supply.............................................................................................................................72 8.5.2 Overvoltage ...............................................................................................................................73 8.5.3 Electrostatic Discharge..............................................................................................................73 8.5.4 Miscellaneous ............................................................................................................................73 9 SAFETY RECOMMENDATIONS .............................................................................................................74 9.1 General Safety.....................................................................................................................................74 9.2 Vehicle Safety......................................................................................................................................74 9.3 Care and Maintenance ........................................................................................................................75 9.4 Your Responsibility ..............................................................................................................................75 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 9 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 276 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 10 RECOMMENDED ACCESSORIES..........................................................................................................76 11 ONLINE SUPPORT ..................................................................................................................................77 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 10 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 277 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual List of Figures Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 Figure 1: Complete package contents..............................................................................................................17 Figure 2: Packaging box...................................................................................................................................18 Figure 3: Production Label ...............................................................................................................................19 Figure 4: FASTRACK Supreme general description ........................................................................................20 Figure 5: FASTRACK Supreme holding bridles ...............................................................................................21 Figure 6: SMA connector for antenna connection ............................................................................................22 Figure 7: Power supply connector ....................................................................................................................23 Figure 8: Sub HD 15-pin connector ..................................................................................................................24 Figure 9: IES connector for feature expansion.................................................................................................26 Figure 10: Power supply cable .........................................................................................................................29 Figure 11: SIM card lock feature ......................................................................................................................35 Figure 12: FASTRACK Supreme mounting......................................................................................................36 Figure 13: Recommended power supply connection on trucks........................................................................38 Figure 14: Example of electrical connection which may dramatically damage the FASTRACK Supreme ......39 Figure 15: Functional architecture ....................................................................................................................50 Figure 16: RS232 Serial Link signals ...............................................................................................................52 Figure 17: Reset sequence diagram ................................................................................................................56 Figure 18: Dimensioning diagram.....................................................................................................................60 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 11 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 278 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual List of Tables Fastrack Supreme User Guide WA_DEV_Fastrk_UGD_001 . Table 1: Power supply connector pin description.............................................................................................23 Table 2: Sub HD 15-pin connector description.................................................................................................24 Table 3: IES Connector Description .................................................................................................................27 Table 4: Basic features of the FASTRACK Supreme.......................................................................................31 Table 5: FASTRACK Supreme operational status ...........................................................................................40 Table 6: Values of received signal strength .....................................................................................................41 Table 7: AT+CPIN Responses .........................................................................................................................41 Table 8: AT+WMBS Band Selection ................................................................................................................42 Table 9: AT+WMBS Responses.......................................................................................................................42 Table 10: Values of network registration ..........................................................................................................43 Table 11: Main usual AT commands for the Plug & Play .................................................................................44 Table 12: Solutions for no connection with FASTRACK Supreme through serial link .....................................46 Table 13: Solutions for "NO CARRIER" message............................................................................................48 Table 14: Interpretation of extended error code ...............................................................................................49 Table 15: Mechanical characteristics ...............................................................................................................59 Table 16: Electrical characteristics ...................................................................................................................61 Table 17: Effects of power supply defect..........................................................................................................61 Table 18: Power consumption (1*) ...................................................................................................................62 Table 19: Audio parameters caracteristics .......................................................................................................65 Table 20: Microphone inputs internal audio filter characteristics .....................................................................65 Table 21: Recommended characteristics for the microphone: .........................................................................65 Table 22: Recommended characteristics for the speaker: ...............................................................................66 Table 23: Operating conditions.........................................................................................................................66 Table 24: SIM card characteristics ...................................................................................................................66 Table 25: Electrical characteristics ...................................................................................................................66 Table 26: Operating conditions.........................................................................................................................67 Table 27: Frequency ranges.............................................................................................................................67 Table 28: Receiver and transmitter RF performances .....................................................................................68 Table 29: External antenna characteristics ......................................................................................................69 Table 30: Ranges of temperature.....................................................................................................................69 Table 31: Environmental standard constraints .................................................................................................70 Table 32: List of recommended accessories....................................................................................................76 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 12 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 279 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 1 References Fastrack Supreme User Guide References 1.1 Reference Documents For more details, several reference documents may be consulted. The Wavecom reference documents are provided in the Wavecom documents package contrary to the general reference documents, which are not Wavecom owned. 1.1.1 Open AT® Software Documentation [1] Getting started with Open AT® (Ref.WM_ASW_OAT_CTI_001) [2] Open AT® Tutorial (Ref.WM_ASW_OAT_UGD_001) [3] Tools Manual (Ref. WM_ASW_OAT_UGD_003) [4] Open AT® Programming Guide (Ref. TBD) [5] Open AT® Customer Release Note (Ref. WM_ASW_OAT_DVD_00062) Remark: The document above is for Open AT3.12 and FASTRACK Supreme will use new release of Open AT4.21. Reference document not yet available and TBC. 1.1.2 AT Software Documentation [6] AT commands interface Guide for X51 (Ref. WM_ASW_OAT_UGD_00016) [7] Customer Release Note X51 (Ref. WM_ASW_OAT_DVD_00120) Remark: The document above is for X51 and FASTRACK Supreme will use new release of FW6.63. Reference document not yet available and TBC. 1.1.3 Firmware Upgrade Documents [8] Firmware upgrade procedure (Ref. WM_SW_GEN_UGD_001) 1.1.4 Delta between M1306B Documents [9] Delta between M1306B and FASTRACK Supreme (Ref. WA_DEV_Fastrk_UGD_004) 1.1.5 IESM Related Documents [10] IESM Product Technical Specification (Ref. WA_DEV_Fastrk_PTS_001) [11] IESM-GPS+USB User Guide (Ref. WA_DEV_Fastrk_UGD_002) [12] IESM-GPS+USB Installation Guide (Ref. WA_DEV_Fastrk_UGD_003) [13] IESM-IO+USB Installation Guide (Ref. WA_DEV_Fastrk_UGD_005) [14] IESM-IO+USB User Guide (Ref. WA_DEV_Fastrk_UGD_006) confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 13 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 280 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide References Note: New versions of software may be available. Wavecom recommends customers to check the web site for the latest documentation. 1.2 Abbreviations Abbreviation AC ACM AMR AT CLK CMOS CS CTS dB dBc dBi dBm DC DCD DCE DCS DSR DTE DTMF DTR EEPROM EFR E-GSM EMC EMI ESD ETSI FIT FR Definition Alternating Current Accumulated Call Meter Adaptive Multi-Rate ATtention (prefix for Wireless CPU® commands) CLocK Complementary Metal Oxide Semiconductor Coding Scheme Clear To Send Decibel Decibel relative to the Carrier power Decibel relative to an Isotropic radiator Decibel relative to one milliwatt Direct Current Data Carrier Detect Data Communication Equipment Digital Cellular System Data Set Ready Data Terminal Equipment Dual Tone Multi-Frequency Data Terminal Ready Electrically Erasable Programmable Read-Only Memory Enhanced Full Rate Extended GSM ElectroMagnetic Compatibility ElectroMagnetic Interference ElectroStatic Discharges European Telecommunications Standards Institute Series of connectors (micro-FIT) Full Rate confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 14 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 281 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Abbreviation FTA GCF GND GPIO GPRS GSM HR I IEC IES IESM IMEI I/O LED MAX ME MIC Micro-Fit MIN MNP MO MS MT NOM O Pa PBCCH PC PCL PDP PIN PLMN PUK RF Fastrack Supreme User Guide References Definition Full Type Approval Global Certification Forum GrouND General Purpose Input Output General Packet Radio Service Global System for Mobile communications Half Rate Input International Electrotechnical Commission Internal Expansion Socket Internal Expansion Socket Module International Mobile Equipment Identification Input / Output Light Emitting Diode MAXimum Mobile Equipment MICrophone Family of connectors from Molex MINimum Microcom Networking Protocol Mobile Originated Mobile Station Mobile Terminated NOMinal Output Pascal (for speaker sound pressure measurements) Packet Broadcast Control CHannel Personal Computer Power Control Level Packet Data Protocol Personal Identity Number Public Land Mobile Network Personal Unblocking Key Radio Frequency confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 15 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 282 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Abbreviation RFI RI RMS RTS RX SIM SMA SMS SNR SPL SPK SRAM TCP/IP TDMA TU TUHigh TX TYP VSWR Fastrack Supreme User Guide References Definition Radio Frequency Interference Ring Indicator Root Mean Square Request To Send Receive Subscriber Identification Module SubMiniature version A RF connector Short Message Service Signal-to-Noise Ratio Sound Pressure Level SpeaKer Static RAM Transmission Control Protocol / Internet Protocol Time Division Multiple Access Typical Urban fading profile Typical Urban, High speed fading profile Transmit TYPical Voltage Stationary Wave Ratio confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 16 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 283 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 2 Packaging Fastrack Supreme User Guide Packaging 2.1 Contents The complete package content of the FASTRACK Supreme consists of (see): · one packaging box (A), · one FASTRACK Supreme (B), · two holding bridles (C), · one power supply cable with fuse integrated (D) · a mini notice (E) with: a summary of the main technical features, safety recommendations, EC declaration of conformity. Figure 1: Complete package contents confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 17 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 284 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 2.2 Packaging Box Fastrack Supreme User Guide Packaging The packaging box is a carton box (see) with the following external dimensions: · width: 54.5 mm, · height: 68 mm, · length: 108 mm. A packaging label is slicked on the packaging box cover and supports the: · WAVECOM logo, · Product reference (Supreme), · CE marking · 15-digit IMEI code · Open AT® Logo · RoHS logo · WEEE logo The packaging label dimensions are: · height: 40 mm, · length: 65 mm. Figure 2: Packaging box confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 18 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 285 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Packaging 2.3 Production Labelling A production label (see Figure 3) located at the FASTRACK Supreme back side gives the following information: · product reference (FASTRACK Supreme 10 or FASTRACK Supreme 20), · part number (WM19183), · CE marking, · 15-digit IMEI code, · OpenAT® logo Figure 3: Production Label confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 19 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 286 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 3 General Presentation Fastrack Supreme User Guide General Presentation 3.1 Description The FASTRACK Supreme description is given in the Figure 4 below. Micro-Fit connector Screw for Back Plate Back Plate SIM card inside SIM connector Lock switch of SIM connector IES connector for expanding feature, like GPS, USB, I/O expander... Refer to Section 3.2.1.4 Removed Screw for Back Plate Sub HD connector SMA connector Back Cap GSM LED Indicator Back Cap with 5 screws Removed Back Plate Figure 4: FASTRACK Supreme general description confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 20 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 287 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide General Presentation CAUTION: Users are free to remove the back plate for IESM board plug in/unplug without voiding the warrantee of the FASTRACK Supreme. However, the warrantee will be voided if unscrewing any screw of the back cap. In addition, two holding bridles are provided to tighten the FASTRACK Supreme on a support. Holding bridles Figure 5: FASTRACK Supreme holding bridles confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 21 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 288 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 3.2 External Connections 3.2.1 Connectors Fastrack Supreme User Guide General Presentation 3.2.1.1 Antenna Connector The antenna connector is a SMA type connector for a 50 RF connection. SMA connector for antenna connection Figure 6: SMA connector for antenna connection 3.2.1.2 Power Supply Connector The power supply connector is a 4-pin Micro FIT connector for: · external DC Power Supply connection, · GPIOs connection (two General Purpose Input/Output signals available). confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 22 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 289 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 1 2 Fastrack Supreme User Guide General Presentation 3 4 Figure 7: Power supply connector Table 1: Power supply connector pin description Pin # Signal I/O 1 V+BATTERY I I/O type Power supply Description Battery voltage input: 5.5 V Min. 13.2 V Typ. 32 V Max. Reset State Comment High current 2 GND Power supply Ground 3 GPIO21 I/O 2V8 General Purpose Input/output Undefined Not mux 4 GPIO25 I/O 2V8 General Purpose Input/output Z Multiplex with INT1 Warning: Both pin 3 and pin 4 are used by GPIO interface. It is strictly prohibited to connect them to any power supply at the risk of damage to the FASTRACK Supreme. 3.2.1.3 Sub HD 15-pin Connector The Sub D high density 15-pin connector is used for: · RS232 serial link connection, · Audio lines (microphone and speaker) connection, · BOOT and RESET signal connection. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 23 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 290 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide General Presentation 54321 10 9 8 7 6 15 14 13 12 11 Figure 8: Sub HD 15-pin connector Pin # 1 2 3 4 5 6 7 8 9 Table 2: Sub HD 15-pin connector description Signal (CCITT / EIA) CDCD/CT109 CTXD/CT103 BOOT I/O I/O type O STANDARD RS232 I STANDARD RS232 I CMOS Description RS232 Data Carrier Detect RS232 Transmit serial data Boot CMIC2P CMIC2N CRXD/CT104 CDSR/CT107 CDTR/CT108-2 GND I Analog I Analog O STANDARD RS232 O STANDARD RS232 I STANDARD RS232 - GND Microphone positive line Microphone negative line RS232 Receive serial data RS232 Data Set Ready RS232 Data Terminal Ready Ground Comment This signal must not be connected. Its use is strictly reserved to Wavecom or competent retailers. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 24 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 291 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Pin # 10 11 12 13 14 15 Signal (CCITT / EIA) CSPK2P CCTS/CT106 CRTS/CT105 CRI/CT125 RESET CSPK2N I/O I/O type Fastrack Supreme User Guide General Presentation Description Comment O Analog Speaker positive line O STANDARD RS232 RS232 Clear To Send I STANDARD RS232 RS232 Request To Send O STANDARD RS232 RS232 Ring Indicator I/O Schmitt Supreme Plug & Play reset Active low O Analog Speaker negative line 3.2.1.4 IES Connector The IES connector is a 50 pins board-to-board connector for expanding application features like GPS, USB, I/O expander... Currently there are already 3 IESM boards available for customer to expand the FASTRACK Supreme features immediately. They are: IESM-GPS+USB+I/O IESM-GPS+USB IESM-USB+I/O For detail, please refer to Document in Section 1.1.5. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 25 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 292 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide General Presentation For sales and support, please contact Wavecom sales/FAE or your distributor. Pin 2 Pin 1 Pin 50 Pin 49 Figure 9: IES connector for feature expansion confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 26 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 293 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide General Presentation Pin Number 1 2 3 4 5 6 7 8 9 Signal Name Nominal Mux GND GND GPIO4 COL0 GPIO5 COL1 GPIO6 COL2 GPIO7 COL3 VPAD-USB USB-DP USB-DM 10 GSM-1V8* 11 GSM-2V8* 12 BOOT 13 ~RESET 14 AUX-ADC 15 ~SPI1-CS GPIO31 16 SPI1-CLK GPIO32 17 SPI1-I GPIO30 18 SPI1-IO GPIO29 19 SPI2-CLK GPIO32 20 SPI2-IO GPIO33 21 ~SPI2-CS GPIO35 22 SPI2-I GPIO34 23 CT104RXD2 GPIO15 24 CT103-TXD2 GPIO14 25 ~CT106CTS2 GPIO16 26 ~CT105RTS2 GPIO17 Table 3: IES Connector Description I/O type Voltage I/O* Reset State Description Dealing with unused pins Ground Ground C8 GSM-1V8 I/O Pull-up Keypad column 0 NC C8 GSM-1V8 I/O Pull-up Keypad column 1 NC C8 GSM-1V8 I/O Pull-up Keypad column 2 NC C8 GSM-1V8 I/O Pull-up Keypad column 3 NC VPAD-USB I USB Power supply input NC VPAD-USB I/O USB Data NC VPAD-USB I/O GSM-1V8 O GSM-1V8 O GSM-1V8 I C4 GSM-1V8 I/O A2 Analog I C1 GSM-2V8 O C1 GSM-2V8 O C1 GSM-2V8 I C1 GSM-2V8 I/O C1 GSM-2V8 O C1 GSM-2V8 I/O C1 GSM-2V8 O C1 GSM-2V8 I C1 GSM-1V8 O C1 GSM-1V8 I C1 GSM-1V8 O C1 GSM-1V8 I USB Data NC 1.8V Supply Output (for GPIO pull-up only) 2.8V Supply Output (for GPIO pull-up only) Not Used NC NC Add a test point / a jumper/ a switch to VCC_1V8 (Pin 10) in case Download Specific mode is used (See product specification for details) RESET Input NC or add a test point Analog to Digital Input Pull to GND Z SPI1 Chip Select NC Z SPI1 Clock NC Z SPI1 Data Input NC Z SPI1 Data Input / Output NC Z SPI2 Clock NC Z SPI2 Data Input / Output NC Z SPI2 Chip Select NC Z SPI2 Data Input NC Z Auxiliary RS232 Receive Add a test point for firmware upgrade (TXD2) Pull-up to Z Auxiliary RS232 Transmit VCC_1V8 with 100k and add a test point for firmware update Z Auxiliary RS232 Clear To (CTS2) Add a test point Send for firmware update Z Auxiliary RS232 Request (RTS2) Pull-up to To Send VCC_1V8 with 100k and add a test point for confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 27 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 294 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Pin Number Signal Name Nominal Mux 27 GPIO8 COL4 28 GPIO26 SCL 29 GPIO19 30 GPIO27 SDA 31 GPIO20 32 INT0 GPIO3 33 GPIO23 ** 34 GPIO22 ** 35 ~CT108-2DTR1 GPIO41 36 PCM-SYNC 37 PCM-IN 38 PCM-CLK 39 PCM-OUT 40 AUX-DAC 41 VCC-2V8 42 GND 43 DC-IN 44 DC-IN 45 GND 46 4V 47 4V 48 GND 49 GND 50 GND I/O type C8 A1 C1 A1 C1 C1 C1 C1 C1 C5 Fastrack Supreme User Guide General Presentation Voltage I/O* Reset State Description Dealing with unused pins GSM-1V8 I/O Pull-up Keypad column 4 firmware update NC Open Drain O Z I²C Clock NC GSM-2V8 I/O Z NC Open Drain I/O Z I²C Data NC GSM-2V8 I/O Undefined GSM-1V8 I Z Interruption 0 Input GSM-2V8 I/O Z NC If INT0 is not used, it should be configured as GPIO NC GSM-2V8 GSM-2V8 GSM-1V8 I/O Z I Z O Pull-down Main RS232 Data Terminal Ready PCM Frame Synchro NC (DTR1) Pull-up to VCC_2V8 with 100k NC GSM-1V8 I Pull-up PCM Data Input NC GSM-1V8 O Pull-down PCM Clock NC GSM-1V8 O Pull-up PCM Data Output NC Analog O Digital to Analog Output NC VCC_2V8 O LDO 2.8V Supply Output NC DC-IN from 5.5V~32VDC O DC-IN from 5.5V~32VDC O Ground DC voltage input through Micro-Fit connector NC DC voltage input through Micro-Fit connector NC Ground 4V O 4V O 4V DC/DC converter Output NC 4V DC/DC converter Output NC Ground Ground Ground confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 28 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 295 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 3.2.2 Power supply cable Fastrack Supreme User Guide General Presentation Figure 10: Power supply cable confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 29 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 296 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Component Micro-Fit connector 4-pin Cable Wire Fastrack Supreme User Guide General Presentation Characteristics Part number: MOLEX 43025-0400 Cable length: 1.5 m Core: tinned copper 24 x 0.2 mm Section: 0.75 mm2 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 30 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 297 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 4 Features and Services Fastrack Supreme User Guide Features and Services 4.1 Basic Features and Services Basic features of the FASTRACK Supreme and available services are summarized in the table below. Table 4: Basic features of the FASTRACK Supreme Features Open AT® GSM850 / GSM900 DCS1800 / PCS1900 Open AT® programmable: Native execution of embedded standard ANSI C applications, Custom AT command creation, Custom application library creation, Standalone operation. Standard 850MHz / 900 MHz. 1800 MHz / 1900MHz E-GSM compliant. Output power: class 4 (2W). Output power: class 1 (1W). Fully compliant with ETSI GSM phase 2 + Fully compliant with ETSI GSM phase 2 + small MS. small MS. GPRS Class 10. PBCCH support. Coding schemes: CS1 to CS4. Compliant with SMG31bis. Embedded TCP/IP stack. EGPRS Output power: 0.5W Output power: 0.4W (for Class 10. FASTRACK Supreme 20 PBCCH support. only) Coding schemes: MCS1 to MCS9. Compliant with SMG31bis. Embedded TCP/IP stack. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 31 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 298 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Features Interfaces SMS Data Fax Audio Fastrack Supreme User Guide Features and Services GSM850 / GSM900 DCS1800 / PCS1900 RS232 (V.24/V.28) Serial interface supporting: Baud rate (bits/s): 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 230400, 460800 and 921600. Autobauding (bits/s): from 1200 to 921600. 2 General Purpose Input/Output gates (GPIOs) available. 1.8 V / 3 V SIM interface. AT command set based on V.25ter and GSM 07.05 & 07.07. Open AT® interface for embedded application. Open AT® Plug-In Compatible. Text & PDU. Point to point (MT/MO). Cell broadcast. Data circuit asynchronous. Transparent and Non Transparent modes. Up to 14.400 bits/s. MNP Class 2 error correction. V42.bis data compression. Automatic fax group 3 (class 1 and Class 2). Echo cancellation Noise reduction Telephony. Emergency calls. Full Rate, Enhanced Full Rate, Half Rate operation and Adaptive Multi-Rate (FR/EFR/HR/AMR). Dual Tone Multi Frequency function (DTMF). confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 32 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 299 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Features GSM850 / GSM900 GSM supplement services Call forwarding. Call barring. Multiparty. Call waiting and call hold. Calling line identity. Advice of charge. USSD Other DC power supply Real Time Clock with calendar Complete shielding For other detailed technical characteristics, refer to Section 8. Fastrack Supreme User Guide Features and Services DCS1800 / PCS1900 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 33 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 300 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 4.2 Additional NEW Features Fastrack Supreme User Guide Features and Services 4.2.1 Support Additional GSM850/PCS1900 Bands Apart from GSM900/DCS1800, the FASTRACK Supreme Plug & Play now supports also the GSM850/PCS1900 bands. FASTRACK Supreme is fully compliant to PTCRB and FCC also. 4.2.2 IES Interface for Easy Expansion of Application Features The FASTRACK Supreme Plug & Play offers a 50 pin Internal Expansion Socket (IES) Interface accessible for customer use. It is the additional interface which is easy for customers to expand their application features without voiding the warrantee of the FASTRACK Supreme, by simply plugging in an Internal Expansion Socket Module (IESM) board through the matting connector of the IES interface. Thanks to the flexible IES interface, customers are ready to expand the application features by plugging in the corresponding Internal Expansion Socket Module (IESM) of GPS, I/O expander..., etc. For brief description of the interface, please refer to Section 3.2.1.4. For technical detail, please refer to Document [11] or contact your Wavecom distributor or Wavecom FAE. 4.2.3 Serial Port Auto Shut Down or Improving Power Consumption In order to save power consumption when there is no data communication between the Plug & Play and the DTE, FASTRACK Supreme has now implement the Serial Port Auto Shut Down feature. User can activate or deactivate the Serial Port Auto Shut Down mode by simple AT-command. For detail, please refer to Section 7.3.4. 4.2.4 Real Time Clock (RTC) for Saving Date and Time The FASTRACK Supreme has now implemented the Real Time Clock for saving date and time when the Plug & Play is unplugged from the DC power supply through the DC power cable. For detail, please refer to Section 7.8. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 34 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 301 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Features and Services 4.2.5 SIM Card Lock Feature The FASTRACK Supreme has now implemented a SIM connector having a carrier with lock. This helps ensuring the user to have proper SIM card insertion and locked before proper use of GSM network. SIM card is inserted but not locked. GSM network is SIM card is inserted and being locked properly. not ready for use. Only emergency call 112 is GSM network is ready for use. possible. Figure 11: SIM card lock feature confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 35 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 302 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play 5 Using the FASTRACK Supreme Plug & Play 5.1 Getting Started 5.1.1 Mount the FASTRACK Supreme To mount the FASTRACK Supreme on its support, bind it using the holding bridles as shown in the Figure 12 below. Figure 12: FASTRACK Supreme mounting For the drill template, refer to Figure 18. 5.1.2 Set up the FASTRACK Supreme To set up the FASTRACK Supreme, perform the following operations: · Insert the SIM card into the SIM card holder of the FASTRACK Supreme. · Lock the SIM card by sliding the lever towards the SIM card. · Connect the antenna to the SMA connector. · Connect both sides of the serial and control cable (15-pin Sub HD connector on the FASTRACK Supreme side). · Connect the power supply cable to the external power supply source. Note: For automotive application, it is recommended to connect the V+BATTERY line of the FASTRACK Supreme directly to the battery positive terminal. · Plug the power supply cable into the FASTRACK Supreme and switch on the external power supply source. · The FASTRACK Supreme is ready to work. Refer to Section 5.10 for the description of AT commands used to configure the FASTRACK Supreme. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 36 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 303 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play 5.1.3 Check the communication with the FASTRACK Supreme To check the communication with the FASTRACK Supreme, do the following operations: · Connect the RS232 link between the DTE (port COM) and the FASTRACK Supreme (DCE). · Configure the RS232 port of the DTE as follows: Bits per second: 115.200 bps, Data bits: 8, Parity: None, Stop bits: 1, Flow control: hardware. · Using a communication software such as a HyperTerminal, enter the AT command. The response of the FASTRACK Supreme must be OK displayed in the HyperTerminal window. · If the communication cannot be established with the FASTRACK Supreme, do the following: Check the RS232 connection between the DTE and the FASTRACK Supreme (DCE), Check the configuration of the port COM used on the DTE. · Example of AT commands which can be used after getting started the FASTRACK Supreme: AT+CGMI: FASTRACK Supreme answer is "WAVECOM MODEM" when serial link is OK. AT+CPIN=xxxx: to enter a PIN code xxxx (if activated). AT+CSQ: to verify the received signal strength. AT+CREG?: to verify the registration of the FASTRACK Supreme Plug & Play on the network. ATD<phone number>;: to initiate a voice call. ATH: to hang up (end of call). For further information on these AT commands and their associated parameters, refer to "AT Commands Interface Guide" [6]. 5.1.4 Reset the FASTRACK Supreme To reset the FASTRACK Supreme, a hardware reset signal is available on pin 14 of the Sub HD 15-pin connector (RESET). The FASTRACK Supreme reset is carried out when this pin is low for at least 200 s. Warning This signal has to be considered as an emergency reset only. For further details on the FASTRACK Supreme reset, refer to Section 7.7. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 37 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 304 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play 5.2 Specific Recommendations when Using the FASTRACK Supreme on Trucks Warning: The power supply connection of the FASTRACK Supreme must NEVER be directly connected to the truck battery. 5.2.1 Recommended Power Supply Connection on Trucks All trucks have a circuit breaker on the exterior of the cabin. The circuit breaker is used for safety reasons: if a fire blazes in the trucks, (for example, on the wiring trunk) the driver may cut the current source to avoid any damage (explosion). The circuit breaker is connected to the truck ground, most often associated with the fuse box. Most of truck circuit breakers do not cut the Positive Supply line of the battery, but cut the ground line of the later. FASTRACK Suprem e Figure 13: Recommended power supply connection on trucks Figure 13 gives the recommended power supply connection where the ground connection of the FASTRACK Supreme is not directly connected to the battery but is connected after the Circuit Breaker (on the truck ground or the fuse box). 5.2.2 Technical Constraints on Trucks It is highly not recommended to connect directly the power supply on the battery rather than on the circuit breaker. The FASTRACK Supreme may be damaged when starting the truck if the circuit breaker is switched OFF (in this case, the truck ground and the battery ground will be connected through the FASTRACK Supreme as shown in the figure below). confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 38 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 305 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play FASTRACK Supreme Figure 14: Example of electrical connection which may dramatically damage the FASTRACK Supreme Figure 14 gives an example of electrical connection which may dramatically damage the FASTRACK Supreme when its ground connection is directly connected to the battery ground. In this example, when the circuit breaker is switched OFF, the current flows through the FASTRACK Supreme and powers the electrical circuit of the truck (for example, dashboard). Furthermore, when the Starter Engine command will be used, it will destroy the cables or the FASTRACK Supreme. Since the internal tracks are not designed to support high current (up to 60 A when starting the truck), they will be destroyed. 5.3 FASTRACK Supreme Operational Status The FASTRACK Supreme operational status is given by the red LED status located next to the SIM connector on the FASTRACK Supreme panel. The Table 5 below gives the meaning of the various statuses available. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 39 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 306 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play Table 5: FASTRACK Supreme operational status LED Status LED light activity FASTRACK Supreme Plug & Play status ON LED ON permanent FASTRACK Supreme is switched ON but not registered on the network LED Flashing slowly FASTRACK Supreme is switched ON and registered on the network, but no communication is in progress (Idle mode) LED Flashing rapidly FASTRACK Supreme is switched ON and registered on the network, and a communication is in progress OFF LED OFF FASTRACK Supreme is switched OFF, or Flash LED is disabled* by the user. * : Flash LED can be disabled by user when in Slow Standby mode in order to save power consumption. For detail, please refer to Section 7.9. 5.4 Echo Function Disabled If no echo is displayed when entering an AT command, that means: · The "local echo" parameter of your communication software (such as HyperTerminal) is disabled. · The FASTRACK Supreme echo function is disabled. To enable the FASTRACK Supreme echo function, enter the ATE1. When sending AT commands to the FASTRACK Supreme by using a communication software, it is recommended: · to disable the "local echo" parameter of your communication software (such as HyperTerminal), · to enable the FASTRACK Supreme echo function (ATE1 command). In a Machine To Machine communication with the FASTRACK Supreme, it is recommended to disable the FASTRACK Supreme echo function (ATE0 command) in order to avoid useless CPU processing. For further information on ATE0 and ATE1 commands, refer to "AT Commands Interface Guide" [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 40 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 307 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 5.5 Verify the Received Signal Strength Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play The FASTRACK Supreme establishes a call only if the received signal is sufficiently strong. To verify the received signal strength, do the following operations: · Using a communication software such as HyperTerminal, enter the AT command AT+CSQ. The response returned has the following format: +CSQ: <rssi>,<ber> with: · <rssi> = received signal strength indication, · <ber> = channel bit error rate. · Verify the <rssi> value returned using the Table 6 below. Table 6: Values of received signal strength Value of received signal strength indication (<rssi>) 0 - 10 Interpretation of the received signal strength Insufficient(*) 11 - 31 Sufficient(*) 32 - 98 99 (*) Based on general observations. Not defined No measure available For further information on AT commands, refer to "AT Commands Interface Guide" [6]. 5.6 Check the Pin Code Status To check that the pin code has been entered, use a communication software such as a HyperTerminal, then enter AT+CPIN? command. The table below gives the main responses returned: Table 7: AT+CPIN Responses AT+CPIN response (*) +CPIN: READY Interpretation Code PIN has been entered +CPIN: SIM PIN Code PIN has not been entered (*)For further information on the other possible responses and their meaning, refer to "AT Commands Interface Guide" [6]. 5.7 Switch between EU/US Band(s) To switch between EU/US band(s) for the FASTRACK Supreme, use a communication software such as a HyperTerminal, then enter AT+WMBS=<band>[,<param>] command. The table below gives the commands for various band(s) selection: confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 41 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 308 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play Table 8: AT+WMBS Band Selection AT+WMBS response (*) AT+WMBS=0,x Interpretation Select mono band mode 850MHz. AT+WMBS=1,x AT+WMBS=2,x AT+WMBS=3,x AT+WMBS=4,x AT+WMBS=5,x Select mono band mode extended 900MHz Select mono band mode 1800MHz Select mono band mode 1900MHz Select dual band mode 850/1900MHz Select dual band mode extended 900MHz/1800MHz AT+WMBS=6,x Select dual band mode extended 900MHz/1900MHz (*)For further information on the other possible responses and their meaning, refer to "AT Commands Interface Guide" [6]. Remark: x=0 : The Plug & Play will have to be reset to start on specified band(s). x=1 : The change is effective immediately. This mode is forbidden while in communication and during Plug & Play initialization. Refer to "AT Commands Interface Guide" [6] for further information on AT commands. 5.8 Check the Band(s) Selection To check the band selection for the FASTRACK Supreme, use a communication software such as a HyperTerminal, then enter AT+WMBS? command. The table below gives the main responses returned: Table 9: AT+WMBS Responses AT+WMBS response (*) +WMBS: 0,x Interpretation Mono band mode 850MHz is selected +WMBS: 1,x Mono band mode extended 900MHz is selected +WMBS: 2,x Mono band mode 1800MHz is selected +WMBS: 3,x Mono band mode 1900MHz is selected +WMBS: 4,x Dual band mode 850/1900MHz are selected +WMBS: 5,x Dual band mode extended 900MHz/1800MHz are selected +WMBS: 6,x Dual band mode extended 900MHz/1900MHz are selected (*)For further information on the other possible responses and their meaning, refer to "AT Commands Interface Guide" [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 42 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 309 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play 5.9 Verify the FASTRACK Supreme Network Registration 1. Make sure a valid SIM card has been previously inserted and locked in the FASTRACK Supreme SIM card holder. 2. Using a communication software such as a HyperTerminal, enter the following AT commands: a. AT+CPIN=xxxx to enter PIN code xxxx. b. AT+WMBS? To check the current band setting in the Plug & Play c. AT+WMBS=<Band>[,<param>] To switch band/mode when needed d. AT+CREG?. To ascertain the registration status. The format of the returned response is as follows: +CREG: <mode>,<stat> with: · <mode> = unsolicited registration message configuration, · <stat> = registration state. 3. Verify the state of registration according the returned value given in the table below. Table 10: Values of network registration Returned Value (*) Network registration <mode>,<stat> +CREG: 0,0 No (not registered) +CREG: 0,1 Yes (registered, home network) +CREG: 0,5 Yes (registered, roaming) (*)For further information on the other returned values and their meaning, refer to "AT Commands Interface Guide" [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 43 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 310 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play If the FASTRACK Supreme is not registered, perform the following procedure: · Check the connection between the FASTRACK Supreme and the antenna. · Verify the signal strength to determine the received signal strength (refer to Section 5.5). Note: For information on AT command relating to the network registration in GPRS mode, and in particular: CGREG, CGCLASS, CGATT, refer to "AT Commands Interface Guide" [6]. 5.10 Main AT Commands for the Plug & Play The table below lists the main AT commands required for starting the Plug & Play. For other AT commands available or further information on the AT commands, refer to "AT Commands Interface Guide" [6]. Table 11: Main usual AT commands for the Plug & Play Description AT commands Check for selected AT+WMBS? band(s) Band(s) switch AT+WMBS=<Band> AT+WMBS=<Band>,0 AT+WMBS=<Band>,1 Enter PIN Code AT+WMBS=<Band> AT+CPIN=xxxx (xxxx = PIN code) Network registration checking AT+CREG? FASTRACK Supreme Plug & Play response Comment +WMBS:<Band>,<ResetFlag> Current selected band OK mode is return OK Band switch is accepted, Plug & Play has to be reset for change to be effective OK Band switch is accepted, Plug & Play has to be reset for change to be effective OK Band switch is accepted and GSMS stack restarted +CME ERROR: 3 Band not allowed OK PIN Code accepted. +CME ERROR: 16 Incorrect PIN Code (with +CMEE = 1 mode) (1*) +CME ERROR: 3 PIN code already entered (with +CMEE = 1 mode) (1*) +CREG: 0,1 FASTRACK Supreme Plug & Play registered on the network. +CREG: 0,2 FASTRACK Supreme Plug & Play not registered on the network, registration attempt. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 44 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 311 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Description Receiving an incoming call Initiate a call Initiate an emergency call Communication loss Hang up AT commands ATA Fastrack Supreme User Guide Using the FASTRACK Supreme Plug & Play FASTRACK Supreme Plug & Play response Comment +CREG: 0,0 FASTRACK Supreme Plug & Play not registered on the network, no registration attempt. OK Answer the call. ATD<phone number>; OK (Don't forget the « ; » at the end for « voice » call) +CME ERROR: 11 +CME ERROR: 3 ATD112; OK (Don't forget the « ; » at the end for « voice » call) NO CARRIER Communication established. PIN code not entered (with +CMEE = 1 mode). AOC credit exceeded or a communication is already established. Communication established. ATH OK Store the AT&W OK parameters in EEPROM The configuration settings are stored in EEPROM. (1*) The command "AT+CMEE=1" switch to a mode enabling more complete error diagnostics. 5.11 Firmware Upgrade Procedure The firmware upgrade procedure is used to update the firmware embedded into the FASTRACK Supreme. That procedure consists in downloading the firmware into internal memories through the RS232 serial link available on the SUB-D 15-pin connector. Refer to "Firmware upgrade procedure" [8] for a detailed description of this procedure. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 45 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 312 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 6 Troubleshooting Fastrack Supreme User Guide Troubleshooting This section of the document describes possible problems encountered when using the FASTRACK Supreme and their solutions. To review other troubleshooting information, refer the `FAQs' (Frequently Asked Questions) page at www.wavecom.com or use the following link: http://www.wavecom.com/support/faqs.php 6.1 No Communication with the FASTRACK Supreme through the Serial Link If the FASTRACK Supreme does not answer to AT commands through the serial link, refer to the table below for possible causes and solutions. Table 12: Solutions for no connection with FASTRACK Supreme through serial link If the Supreme returns Nothing then ask Is the FASTRACK Supreme powered correctly? Is the serial cable connected at both sides? Does the serial cable follow correctly pin assignment shown in paragraph 3.2.1.2. Nothing or non- Is the communication program significant characters properly configured on PC? Is there another program interfering with the communication program (i.e. Conflict on communication port access) Action Make sure the external power supply is connected to the FASTRACK Supreme and provides a voltage in the range of 5.5 V to 32 V. Check the serial cable connection Connect the cable by following pin assignment given in paragraph 3.2.1.1. Ensure the setting of the communication program is fit to setting of FASTRACK Supreme. FASTRACK Supreme factory setting is: Data bits = 8 Parity = none Stop bits = 1 Baud = 115 200 bps. Flow control = hardware Close the interfering program. 6.2 Receiving "ERROR" Message The FASTRACK Supreme returns an "ERROR" message (in reply to an AT command) in the following cases: confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 46 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 313 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Troubleshooting · AT command syntax is incorrect: check the command syntax (refer to "AT Commands Interface Guide" [6]), · AT command syntax is correct, but transmitted with wrong parameters: · Enter the AT+CMEE=1 command in order to change the error report method to the verbose method, which includes the error codes. · Enter again the AT command which previously caused the reception of "ERROR" message in order to get the Mobile Equipment error code. When the verbose error report method is enabled, the response of the FASTRACK Supreme in case of error is as follows: · Either +CME ERROR: <error result code>, · Or +CMS ERROR: <error result code>. Refer to "AT Commands Interface Guide" [6] for error result code description and further details on the AT +CMEE command. Note: It is strongly recommended to always enable the verbose error report method to get the Mobile Equipment error code (enter AT +CMEE=1 command). 6.3 Receiving "NO CARRIER" Message If the FASTRACK Supreme returns a "NO CARRIER" message upon an attempted call (voice or data), then refer to the table below for possible causes and solutions. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 47 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 314 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Troubleshooting Table 13: Solutions for "NO CARRIER" message If the Supreme returns... "NO CARRIER" Then ask... Is the received signal strong enough? Is the FASTRACK Supreme registered on the network? Is the antenna properly connected? Is the band selection correction? "NO CARRIER" (when Is the semicolon (;) entered immediately trying to issue a voice after the phone number in the AT communication) command? Action... Refer to section 5.5 to verify the strength of the received signal. Refer to section 5.9 to verify the registration. Refer to section 8.2.7.3 for antenna requirements. Refer to Section 7.2 for band switch Ensure that the semicolon (;) is entered immediately after the phone number in the AT command. e.g. ATD######; "NO CARRIER" (when Is the SIM card configured for data / fax trying to issue a data calls? communication) Configure the SIM card for data / fax calls (Ask your network provider if necessary). Is the selected bearer type supported by the Ensure that the selected bearer type called party? is supported by the called party. Is the selected bearer type supported by the Ensure that the selected bearer type network? is supported by the network. If no success, try bearer selection type by AT command: AT+CBST=0,0,3 If the FASTRACK Supreme returns a "NO CARRIER" message, you may have the extended error code by using AT command AT+CEER. Refer to the table below for interpretation of extended error code. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 48 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 315 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Troubleshooting Table 14: Interpretation of extended error code Error Code 1 16 17 18 19 21 22 31 50 Diagnostic Unallocated phone number Normal call clearing User busy No user responding User alerting, no answer Call rejected Number changed Normal, unspecified Requested facility not subscribed 68 ACM equal or greater than ACMmax 252 Call barring on outgoing calls 253 Call barring on incoming calls 3, 6, 8, 29, 34, 38, 41, 42, 43, 44, 47, 49, 57, 58, 63, 65, 69, 70, 79, 254 Network causes Hint Check your subscription (data subscription available?). Credit of your pre-paid SIM card expired. See "AT Commands Interface Guide" [6] for further details or call network provider. Note: For all other codes, and/or details, see AT commands documentation [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 49 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 316 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 7 Functional Description Fastrack Supreme User Guide Functional Description 7.1 Architecture FASTRACK Supreme Plug & Play BOOT RESET Microphone Speaker SUB HD 15 pins GPIO-21 GPIO-25 V+BATT GROUND Micro-FIT 4 pins RS232 Interface VCC Audio Interface VCC SMA Microphone Internal Quik Wireless CPU® Q2687 Speaker Operating Status DC / DC VCC Power Supply 50 pin IES Interface SIM card Holder Figure 15: Functional architecture confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 50 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 317 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 7.2 EU and US Bands Fastrack Supreme User Guide Functional Description 7.2.1 General Presentation The FASTRACK Supreme is a quad band Plug & Play. It supports either EU bands (EGSM900/DCS1800) or US bands (GSM850/ PCS1900), depending on the band setting within the Plug & Play. Users are free to switch between EU bands and US bands by simple AT commands when the selected bands are supported. 7.2.2 AT COMMAND for Bands Switch EU/US band is easily switched/checked by AT command AT+WMBS. For detail, please refer to Section 5.7 and 5.8. 7.3 Power Supply 7.3.1 General Presentation The FASTRACK Supreme is supplied by an external DC voltage (V+BATTERY) from +5.5 V to +32 V at 2.2 A. Main regulation is made with an internal DC/DC converter in order to supply all the internal functions with a DC voltage. Correct operation of the FASTRACK Supreme in communication mode is not guaranteed if input voltage (V+BATTERY) falls below 5.5 V. Note: The minimum input voltage specified here is at the FASTRACK Supreme input. Be careful of the input voltage decrease caused by the power cable. See paragraph 8.2.1 for more information. 7.3.2 Protections The FASTRACK Supreme is protected by a 800 mA / 250 V fuse directly bonded on the power supply cable. The FASTRACK Supreme is also protected against voltage over +32 V. Filtering guarantees: · EMI/RFI protection in input and output, · Signal smoothing. 7.4 RS232 Serial Link 7.4.1 General Presentation The RS232 interface performs the voltage level adaptation (V24/CMOS V24/V28) between the internal FASTRACK Supreme Plug & Play (DCE) and the external world (DTE). confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 51 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 318 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Functional Description The RS232 interface is internally protected (by ESD protection) against electrostatic surges on the RS232 lines. Filtering guarantees: · EMI/RFI protection in input and output, · Signal smoothing. Signals available on the RS232 serial link are: · TX data (CT103/TX), · RX data (CT104/RX), · Request To Send (CT105/RTS), · Clear To Send (CT106/CTS), · Data Terminal Ready (CT108-2/DTR), · Data Set Ready (CT107/DSR), · Data Carrier Detect (CT109/DCD), · Ring Indicator (CT125/RI). FASTRACK Supreme (DCE) CT103 / TX CT104 / RX CT105 / RTS CT106 / CTS CT107 / DSR CT108-2 / DTR CT109 / DCD CT125 / RI DTE Figure 16: RS232 Serial Link signals RS232 interface has been designed to allow flexibility in the use of the serial interface signals. However, the use of TX, RX, CTS and RTS signals is mandatory, which is not the case for DTR, DSR, DCD and RI signals which can be not used. 7.4.2 Autobauding Mode The autobauding mode allows the FASTRACK Supreme to detect the baud rate used by the DTE connected to the RS232 serial link. Autobauding mode is controlled by AT commands. See "AT Commands Interface Guide" [6] for details on this function. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 52 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 319 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 7.4.3 Pin Description Fastrack Supreme User Guide Functional Description Signal CTXD/CT103 CRXD/CT104 CRTS/CT105 CCTS/CT106 CDSR/CT107 CDTR/CT108-2 CDCD/CT109 CRI/CT125 CT102/GND Sub HD connector I/O I/O type Pin number RS232 STANDARD Description 2 I TX Transmit serial data 6 O RX Receive serial data 12 I RTS Request To Send 11 O CTS Clear To Send 7 O DSR Data Set Ready 8 I DTR Data Terminal Ready 1 O DCD Data Carrier Detect 13 O RI Ring Indicator 9 GND Ground 7.4.4 Serial Port Auto shut down Feature The UART1 can be shut down when there is no activity between the DTE and the FASTRACK Supreme Plug & Play. This can help for improving power consumption performance. Serial Port Auto shut down feature is easily controlled by AT command AT+WASR. AT+WASR=1 for entering the serial port auto shut down mode AT+WASR=0 for exiting the serial port auto shut down mode Refer to "AT Commands Interface Guide" [6] for further information on AT commands. CAUTION: GPIO24 is reserved for serial port auto shut down feature. It is prohibited for customer use. Improper access to GPIO24 by customer may lead to unexpected behavior on UART1 performance. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 53 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 320 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 7.5 General Purpose Input/Output (GPIO) Fastrack Supreme User Guide Functional Description The FASTRACK Supreme provides two General Purpose Input / Output lines available for external use: GPIO21 and GPIO25. These GPIOs may be controlled by AT commands: · AT+WIOW for a write access to the GPIO value, when the GPIO is used as an output, · AT+WIOR for a read access to the GPIO value, when the GPIO is used as an input. Refer to "AT Commands Interface Guide" [6] for further information on AT commands. After reset, both GPIOs are configured as inputs. The AT+WIOM command has to be used to change this configuration (refer to "AT Commands Interface Guide" [6] for further details). Signal GPIO21 GPIO25 Power Supply connector (4-pin Micro-Fit) 3 4 Pin description I/O I/O Voltage Reset state Description Mulitplex with I/O 2V8 Undefined General Purpose I/O No mux I/O 2V8 Z General Purpose I/O INT1 Notes: · The power supply cable may need to be modified due to the GPIO signals (GPIO21 & GPIO25) available on the 4-pin Micro-FIT connector of the FASTRACK Supreme. · The previous generation M1306B have GPIO4 and GPIO5 being replaced by GPIO21 and GPIO25 respectively, for which both are of LOW level at reset state. 7.6 BOOT This signal must not be connected. Its use is strictly reserved to Wavecom or competent retailers. Caution: Previous generation M1306B has BOOT signal of HIGH level at 2.8V. But the FASTRACK Supreme now of 1.8V BOOT instead. 7.7 RESET 7.7.1 General presentation This signal is used to force a reset procedure by providing low level during at least 200 µs. This signal must be considered as an emergency reset only. A reset procedure is automatically driven by an internal hardware during the power-up sequence. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 54 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 321 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Functional Description This signal may also be used to provide a reset to an external device. It then behaves as an output. If no external reset is necessary, this input may be left open, if used (emergency reset), it has to be driven either by an open collector or an open drain output: · RESET pin 14 = 0, for FASTRACK Supreme Reset, · RESET pin 14 = 1, for normal mode. Signal RESET Sub HD 15-Pin connector Pin number 14 Pin description I/O I/O type I/O Open Drain Voltage 1V8 Description FASTRACK Supreme Reset Caution: Previous generation M1306B has RESET signal of HIGH level at 2.8V. But the FASTRACK Supreme now of 1.8V RESET instead. Additional comments on RESET: The RESET process is activated either by the external RESET signal or by an internal signal (coming from a RESET generator). This automatic reset is activated at Power-up. The FASTRACK Supreme remains in RESET mode as long as the RESET signal is held low. Caution: This signal should be used only for "emergency" reset. A software reset is always preferred to a hardware reset. Note: See "AT Commands Interface Guide" [6] for further information on software reset. 7.7.2 Reset Sequence To activate the "emergency" reset sequence, the RESET signal has to be set to low for 200 s minimum. As soon as the reset is done, the AT interface answers "OK" to the application. For this, the application must send AT. If the application manages hardware flow control, the AT command may be sent during the initialization phase. Another solution is to use the AT+WIND command to get an unsolicited status from the FASTRACK Supreme. For further details, refer to AT commands "AT Commands Interface Guide" [6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 55 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 322 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual ~ RESET Fastrack Supreme User Guide Functional Description STA TE OF TH E W ireless W ireless CPU CPU REA D Y RESET m od e IBB+ RF= 2 0 t o 40m A Rt = M in 1 :2 0 0 s or Typ2 = 40m s Ct = Typ :34 m s W ireless CPU ON IBB+ RF< 1 2 0 m A w it h ou t loc u p d at e AT an sw ers " OK" W ireless CPU REA D Y SIM an d n etw ork d ep en d en t Figure 17: Reset sequence diagram 7.8 Audio Audio interface is a standard one for connecting a phone handset. Echo cancellation and noise reduction features are also available to improve the audio quality in case of hand-free application. 7.8.1 Microphone Inputs The microphone inputs are differential ones in order to reject common mode noise and TDMA noise. They already include the convenient biasing for an electret microphone (0.5 mA and 2 Volts) and are ESD protected. This electret microphone may be directly connected to these inputs allowing an easy connection to a handset. The microphone impedance must be around 2 k. AC coupling is already embedded in the Wireless CPU®. The gain of the microphone inputs is internally adjusted and may be tuned from 30 dB to 51 dB using an AT +VGT command (refer to AT commands documentation [6]). Signal CMIC2P CMIC2N Pin description Sub D 15-pin Pin # 4 5 I/O I/O type I Analog I Analog Description Microphone positive input Microphone negative input confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 56 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 323 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Functional Description 7.8.2 Speaker Outputs This connection is differential to reject common mode noise and TDMA noise. Speaker outputs are connected to internal push-pull amplifiers and may be loaded down between 32 to 150 Ohms and up to 1 nF (see details in table Speaker gain vs Max output voltage, in "AT Commands Interface Guide" [6]). These outputs may be directly connected to a speaker. The output power may be adjusted by step of 2 dB. The gain of the speaker outputs is internally adjusted and may be tuned using an AT +VGR command (refer to AT commands documentation [6]). Pin description Signal Sub D 15-pin Pin # I/O I/O type Description CSPK2P CSPK2N 10 O Analog Speaker positive output 15 O Analog Speaker negative output confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 57 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 324 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Functional Description 7.9 Real Time Clock (RTC) The FASTRACK Supreme has now implemented the Real Time Clock for saving date and time when the Plug & Play is unplugged from the DC power supply through the DC power cable. Item Min Typical Max Charging Time start from fully discharged to fully charged 940 min RTC Time Period* Guarantee Non-guarantee 2475 min 5225 min Remark: The RTC time period is measured from the RTC battery is fully charged before being unplugged from the DC power source. 7.10 FLASH LED The FASTRACK Supreme has a red LED indicator to show the status of the GSM network. For detail description of the various status, please refer to Section 5.3. However, during operation mode of Slow Standby, there will be no network registration and so the red LED indicator will always be ON. It is possible for user to deactivate the LED indication during Slow Standby mode, in order to reduce power consumption. The Flash LED can be deactivated by AT command at+whcnf=1,0 The Flash LED can be activated by AT command at+whcnf=1,1 However, the new setting will be taken into account only after a restart. For detail, please refer to Document[6]. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 58 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 325 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 8 Technical Characteristics Fastrack Supreme User Guide Technical Characteristics 8.1 Mechanical Characteristics Dimensions Overall Dimension Weight Volume Housing Table 15: Mechanical characteristics 73 x 54.5 x 25.5 mm (excluding connectors) 88 x 54.5 x 25.5 mm 80 grams (FASTRACK Supreme only) < 120 grams (FASTRACK Supreme + bridles + power supply cable) 101.5 cm3 Aluminum profiled The next page gives the dimensioning diagram of the FASTRACK Supreme including the clearance areas to take into account for the FASTRACK Supreme installation. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 59 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 326 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Figure 18: Dimensioning diagram confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 60 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 327 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 8.2 Electrical Characteristics Fastrack Supreme User Guide Technical Characteristics 8.2.1 Power Supply Table 16: Electrical characteristics Operating Voltage ranges 5.5 V to 32 V DC. Maximum current 480 mA Average at 5.5V. 2.1 A Peak at 5.5 V. (TBC) Note: The FASTRACK Supreme is permanently powered once the power supply is connected. The following table describes the consequences of over-voltage and under-voltage with the FASTRACK Supreme. Warning: All the input voltages specification described in this Section are at the FASTRACK Supreme input. While powering the FASTRACK Supreme, take into account the input drop caused by the power cable. With the delivered cable, this input drop is around 700 mV at 5.5 V and 220 mV at 32V. Table 17: Effects of power supply defect If the voltage falls below 5.5 V, is over 32 V (Transient peaks), Is over 32 V (continuous overvoltage) then the GSM communication is not guaranteed. the FASTRACK Supreme guarantees its own protection. the protection of the FASTRACK Supreme is done by the fuse (the supply voltage is disconnected). The fuse is a 800 mA / 250 V FAST-ACTING 5*20mm. See Section 10 for recommended references. The following table provides information on power consumption of the FASTRACK Supreme, assuming an operating temperature of +25 °C and using a 3 V SIM card. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 61 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 328 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.2.2 Power Consumption The following table provides information on power consumption of the FASTRACK Supreme, assuming an operating temperature of +25 °C and using a 3 V SIM card. GSM GPRS Class 2 I peak I avg I peak I avg I peak I avg I peak I avg Table 18: Power consumption (1*) Power Consumption in E-GSM 900/DCS 1800 MHz - GPRS class 10 E-GSM 900 GSM900: During TX bursts @ PCL5 DCS1800 : During TX bursts @ PCL0 @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900 : Average @ PCL5 DCS1800 : Average @ PCL0 @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900: During 1TX bursts @ PCL5 DCS1800 : During 1TX bursts @ PCL0 @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900 : Average 1TX/1RX @PCL5 DCS1800 : Average 1TX/1RX @PCL0 @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900: During 2TX bursts @ PCL5 (Gamma 3) DCS1800 : During 2TX bursts @ PCL0 (Gamma 2) @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900 : Average 2TX/3RX @ PCL5 (Gamma 3) DCS1800 : Average 2TX/3RX @ PCL0 (Gamma 2) @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900: During 1TX bursts @ PCL8 (Gamma 6) DCS1800 : During 1TX bursts @ PCL2 (Gamma 5) @ 5.5V @ 13.2V @ 32V TBC TBC TBC GSM900 : Average 1TX/1RX @ PCL8 (Gamma 6) DCS1800 : Average 1TX/1RX @ PCL2 (Gamma 5) @ 5.5V @ 13.2V @ 32V TBC TBC TBC DCS 1800 TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC GPRS Class 10 EGPRS Class 2 confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 62 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 329 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Power Consumption in E-GSM 900/DCS 1800 MHz - GPRS class 10 E-GSM 900 EGPRS Class 10 I peak GSM900: During 2TX bursts @ PCL8 (Gamma 6) DCS1800 : During 2TX bursts @ PCL2 (Gamma 5) @ 5.5V @ 13.2V @ 32V GSM900 : Average 2TX/3RX @ PCL8 (Gamma 6) I avg DCS1800 : Average 2TX/3RX @ PCL2 (Gamma 5) @ 5.5V @ 13.2V @ 32V I avg in Fast Idle mode Page 9 (2*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V I avg in Slow Idle mode Page 9 (3*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V I avg in Fast Standby mode (4*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V TBC TBC TBC TBC TBC TBC 33 TBC TBC 17 TBC TBC 23 TBC TBC 5 TBC TBC 52 TBC TBC 35 TBC TBC DCS 1800 TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 63 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 330 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Power Consumption in E-GSM 900/DCS 1800 MHz - GPRS class 10 E-GSM 900 I avg in Slow Standby mode (with FLASH LED activated) (4*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V 24 TBC TBC 8 TBC TBC I avg in Slow Standby mode (with FLASH LED deactivated) (4*) Serial port auto shut down deactivated @ 5.5V @ 13.2V @ 32V @ 5.5V Serial port auto shut down activated @ 13.2V @ 32V TBC TBC TBC 4 TBC TBC DCS 1800 TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC (1*):The power consumption might vary by 5 % over the whole operating temperature range (-20 °C to +55 °C). (2*): In this Mode, the RF function is active and the FASTRACK Supreme synchronized with the network, but there is no communication. (3*): In this Mode, the RF function is disabled, but regularly activated to keep the synchronization with the network. This Mode works only when the DTE send AT command to shut down the serial link by software approach (DTE turns DTR in inactive state). (4*): In this Mode, the RF function is disabled, and there is no synchronization with the network. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 64 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 331 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.2.3 Audio Interface The audio interface is available through the Sub HD 15-pin connector. Table 19: Audio parameters caracteristics Audio parameters Min Typ Max Microphone input current @2 V/2 k 0.5 Absolute microphone input voltage 100 Speaker output current 150 //1 nF 16 Absolute speaker impedance 32 50 Impedance of the speaker amplifier output in 1 differential mode Unit Comments mA mVpp AC voltage mA +/-10 % Table 20: Microphone inputs internal audio filter characteristics Frequency 0-150 Hz 150-180 Hz 180-200 Hz 200-3700 Hz >4000 Hz < -22 dB < -11 dB < -3 dB 0 dB < -60 dB Gain Table 21: Recommended characteristics for the microphone: Feature Value Type Electret 2 V / 0.5 mA Impedance Z = 2 k Sensitivity -40 dB to 50 dB SNR > 50 dB Frequency response compatible with the GSM specifications confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 65 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 332 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Table 22: Recommended characteristics for the speaker: Feature Value Type 10 mW, electro-magnetic Impedance Z = 32 to 50 Sensitivity 110 dB SPL min. (0 dB = 20 µPa) Frequency response compatible with the GSM specifications 8.2.4 General Purpose Input/Output Both GPIO21 and GPIO25 may be interfaced with a component that comply with 3 Volts CMOS levels. Table 23: Operating conditions Parameter I/O type Min Typ Max VIL CMOS VIH CMOS VOL CMOS VOH CMOS IOH IOL Clamping diodes are present on I/O pads. 1.96 V 2.4 V 0.84 V 0.4 V 4mA -4mA Condition IOL = -4 mA IOH = 4 mA 8.2.5 SIM Interface SIM card Table 24: SIM card characteristics 1.8V / 3 V 8.2.6 RESET Signal Table 25: Electrical characteristics Parameter Input Impedance ( R )* Input Impedance ( C ) *Internal pull-up Min Typ Max Unit 330K k 10n nF confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 66 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 333 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Table 26: Operating conditions Parameter Minimum Typ Maximum Unit ~RESET time (Rt) 1 200 µs ~RESET time (Rt) 2 at power up only 20 40 100 ms Cancellation time (Ct) 34 ms VH VIL VIH * VH: Hysterisis Voltage 0.57 0 1.33 V 0.57 V V 1 This reset time is the minimum to be carried out on the ~RESET signal when the power supply is already stabilized. 2 This reset time is internally carried out by the Wireless CPU power supply supervisor only when the Wireless CPU power supplies are powered ON. 8.2.7 RF Characteristics 8.2.7.1 Frequency Ranges Table 27: Frequency ranges Characteristic Frequency TX Frequency RX GSM 850 824 to 849 MHz 869 to 894 MHz E-GSM 900 880 to 915 MHz 925 to 960 MHz DCS 1800 1710 to 1785 MHz 1805 to 1880 MHz PCS 1900 1850 to 1910 MHz 1930 to 1990 MHz confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 67 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 334 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.2.7.2 RF Performances RF performances are compliant with the ETSI recommendation GSM 05.05. The RF performances for receiver and transmitter are given in the table below. Table 28: Receiver and transmitter RF performances Receiver E-GSM900/GSM850 Reference Sensitivity -104 dBm Static & TUHigh DCS1800/PCS1900 Reference Sensitivity -102 dBm Static & TUHigh Selectivity @ 200 kHz > +9 dBc Selectivity @ 400 kHz > +41 dBc Linear dynamic range 63 dB Co-channel rejection >= 9 dBc Transmitter Maximum output power (E-GSM 900/GSM850) at ambient temperature 33 dBm +/- 2 dB Maximum output power (DCS1800/PCS1900) at ambient temperature 30 dBm +/- 2 dB Minimum output power (E-GSM 900/GSM850) at ambient temperature 5 dBm +/- 5 dB Minimum output power (DCS1800/PCS1900) at ambient temperature 0 dBm +/- 5 dB confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 68 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 335 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.2.7.3 External Antenna The external antenna is connected to the FASTRACK Supreme via the SMA connector. The external antenna must fulfill the characteristics listed in the table below. Table 29: External antenna characteristics Antenna frequency range Quad-band GSM 850/GSM900/DCS1800/PCS1900 MHz Impedance 50 Ohms nominal DC impedance 0 Ohm Gain (antenna + cable) 0 dBi VSWR (antenna + cable) 2 Note: Refer to Section 10 for recommended antenna. 8.3 Environmental Characteristics The FASTRACK Supreme Plug & Play is compliant with the following operating class. To ensure the proper operation of the FASTRACK Supreme, the temperature of the environment must be within a specific range as described in the table below. Table 30: Ranges of temperature Conditions Operating / Class A Operating / Class B Storage Temperature range -20 °C to +55°C -30 °C to +85°C -40 °C to +85°C Function Status Classification: Class A: The FASTRACK Supreme remains fully functional, meeting GSM performance criteria in accordance with ETSI requirements, across the specified temperature range. Class B: The FASTRACK Supreme remains fully functional, across the specified temperature range. Some GSM parameters may occasionally deviate from the ETSI/PTCRB specified requirements and this deviation does not affect the ability of the FASTRACK Supreme to connect to the cellular network and function fully, as it does within the Class A range. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 69 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 336 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics The detailed climatic and mechanics standard environmental constraints applicable to the FASTRACK Supreme are listed in the table below: Environmental Tests Table 31: Environmental standard constraints Environmental Classes (IEC TR 60721-4) (IEC 60721-3) Tests Standards Storage (IEC 60721-3-1) Class IE13 Transportation (IEC 60721-3-2) Class IE23 Operation Stationary (IEC 60721-3-3) Class IE35 Non-Stationary (IEC 60721-3-7) Class IE73 Cold Dry heat Change of temperature IEC 60068-2-1 : Ab/Ad IEC 60068-2-2 : Bb/Bd IEC 60068-2-14 : Na/Nb Damp heat IEC 60068-2-56 : Cb Damp heat, cyclic 60068-2-30 : Db Variant 1 or 2 Vibration (sinusoidal) IEC 60068-2-6 : Fc Vibration (random) IEC 60068-2-64 : Fh Shock (half-sine) IEC 60068-2-27 : Ea Bump Free fall IEC 60068-2-29 : Eb ISO 4180-2 Drop and topple IEC 60068-2-31 : Ec -25°C, 16 h +70°C, 16 h -33°C to ambient 2 cycles, t1=3 h 1 °C.min-1 +30°C, 93% RH 96 h +40°C, 90% to 100% RH One cycle Variant 2 1-200 Hz 2 m.s-2 0,75 mm 3 axes 10 sweep cycles - - - - - -40°C, 16 h -5°C, 16 h +70°C, 16 h +55°C, 16 h -40°C to ambient 5 cycles, t1=3 h t2<3 min +40°C, 93% RH 96 h minimum +55°C, 90% to 100% RH Two cycles Variant 2 1-500 Hz 10 m.s-2 3,5 mm 3 axes 10 sweep cycles 10-100 Hz / 1,0 m2.s-3 100-200 Hz / -3 dB.octave-1 200-2000 Hz / 0,5 m2.s-3 3 axes 30 min - 250 m.s-2 6 ms 50 bumps vertical direction Two falls in each specified attitude -5°C to ambient 2 cycles, t1=3 h 0,5 °C.min-1 +30°C, 93% RH, 96 h +30°C, 90% to 100% RH Two cycles Variant 2 1-150 Hz 2 m.s-2 0,75 mm 3 axes 5 sweep cycles 50 m.s-2 6 ms 3 shocks 6 directions - - One drop on relevant corner One topple about each bottom edge - -5°C, 16 h +55°C, 16 h -5°C to ambient 5 cycles, t1=3 h t2<3 min +30°C, 93% RH, 96 h +40°C, 90% to 100% RH Two cycles Variant 1 1-500 Hz 10 m.s-2 3,5 mm 3 axes 10 sweep cycles 150 m.s-2 11 ms 3 shocks 6 directions - 2 falls in each specified attitude 0,025 m (<1kg) One drop on each relevant corner One topple on each of 4 bottom edges confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 70 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 337 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics Notes: Short description of Class IE13 (For more information see standard IEC 60721-3-1) "Locations without controlled temperature and humidity, where heating may be used to raise low temperatures, locations in buildings providing minimal protection against daily variations of external climate, prone to receiving rainfall from carrying wind". Short description of Class IE23 (For more information, see standard IEC 60721-3-2) "Transportation in unventilated compartments and in conditions without protection against bad weather, in all sorts of trucks and trailers in areas of well developed road network, in trains equipped with buffers specially designed to reduce shocks and by boat". Short description of Class IE35 (For more information see standard IEC 60721-3-3) "Locations with no control on heat or humidity where heating may be used to raise low temperatures, to places inside a building to avoid extremely high temperatures, to places such as hallways, building staircases, cellars, certain workshops, equipment stations without surveillance". Short description of Class IE73 (For more information see standard IEC 60721-3-7) "Transfer to places where neither temperature nor humidity are controlled but where heating may be used to raise low temperatures, to places exposed to water droplets, products can be subjected to ice formation, these conditions are found in hallways and building staircases, garages, certain workshops, factory building and places for industrial processes and hardware stations without surveillance". Warning: The specification in the above table applies to the FASTRACK Supreme product only. Customers are advised to verify that the environmental specification of the SIM Card used is compliant with the FASTRACK Supreme environmental specifications. Any application must be qualified by the customer with the SIM Card in storage, transportation and operation. The use of standard SIM cards may drastically reduce the environmental conditions in which the Product can be used. These cards are particularly sensible to humidity and temperature changes. These conditions may produce oxidation of the SIM card metallic layers and cause, in the long term, electrical discontinuities. This is particularly true in left alone applications, where no frequent extraction/insertion of the SIM card is performed. In case of mobility when the application is moved through different environments with temperature variations, some condensation may appear. These events have a negative impact on the SIM and may favor oxidation. If the use of standard SIM card, with exposition to the environmental conditions described above, can not be avoided, special care must be taken in the integration of the final application in order to minimize the impact of these conditions. The solutions that may be proposed are: · Lubrication of the SIM card to protect the SIM Contact from oxidation. · Putting the FASTRACK Supreme Plug & Play in a waterproof enclosure with desiccant bags. Lubrication of the SIM card had been tested by Wavecom (using Tutela Fluid 43EM from MOLYDUVAL) and gives very good results. If waterproof enclosure with a desiccant solution is used, check with your desiccant retailer the quantity that must be used according to the enclosure dimensions. Ensure humidity has been removed before sealing the enclosure. Any solution selected must be qualified by the customer on the final application. To minimize oxidation problem on the SIM card, its manipulation must be done with the greatest precautions. In particular, the metallic contacts of the card must never be touched with bare fingers or any matter which confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 71 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 338 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics may contain polluted materials liable to produce oxidation (such as, e.g. substances including chlorine). In case a cleaning of the Card is necessary, a dry cloth must be used (never use any chemical substance). 8.4 Conformity The complete product complies with the essential requirements of article 3 of R&TTE 1999/5/EC Directive and satisfied the following standards: Domain Safety standard Efficient use of the radio frequency spectrum EMC Global Certification Forum Certification Criteria PTCRB FCC IC Applicable standard EN 60950 (ed.1999) EN 301 419-(v 4.1.1) EN 301 511 (V 7.0.1) EN 301 4891 (edition 2002) EN 301 489-7 (edition 2002) GCF-CC V3.13.0 8.5 Protections 8.5.1 Power Supply The FASTRACK Supreme is protected by a 800 mA / 250 V fuse directly bonded on the power supply cable. The model of fuse used is: FSD 800 mA / 250 V FAST-ACTING. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 72 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 339 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Technical Characteristics 8.5.2 Overvoltage The FASTRACK Supreme is protected against voltage over +32 V. When input voltages exceed +32 V, the supply voltage is disconnected in order to protect the internal electronic components from an overvoltage. 8.5.3 Electrostatic Discharge The FASTRACK Supreme withstands ESD according to IEC 1000-4-2 requirements for all accessible parts of the FASTRACK Supreme except the RF part: · 8 kV of air discharge, · 4 kV of contact discharge. 8.5.4 Miscellaneous Filtering guarantees: · EMI/RFI protection in input and output, · Signal smoothing. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 73 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 340 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 9 Safety recommendations Fastrack Supreme User Guide Safety recommendations 9.1 General Safety It is important to follow any special regulations regarding the use of radio equipment due in particular to the possibility of radio frequency (RF) interference. Please follow the safety advice given below carefully. Switch OFF your Wireless CPU®: · When in an aircraft. The use of cellular telephones in an aircraft may endanger the operation of the aircraft, disrupt the cellular network and is illegal. Failure to observe this instruction may lead to suspension or denial of cellular telephone services to the offender, or legal action or both, · When at a refueling point, · When in any area with a potentially explosive atmosphere which could cause an explosion or fire, · In hospitals and any other place where medical equipment may be in use. Respect restrictions on the use of radio equipment in: · Fuel depots, · Chemical plants, · Places where blasting operations are in progress, · Any other area where signalization reminds that the use of cellular telephone is forbidden or dangerous. · Any other area where you would normally be advised to turn off your vehicle engine. There may be a hazard associated with the operation of your FASTRACK Supreme Plug & Play close to inadequately protected personal medical devices such as hearing aids and pacemakers. Consult the manufacturers of the medical device to determine if it is adequately protected. Operation of your FASTRACK Supreme Plug & Play close to other electronic equipment may also cause interference if the equipment is inadequately protected. Observe any warning signs and manufacturers' recommendations. The FASTRACK Supreme Plug & Play is designed for and intended to be used in "fixed" and "mobile" applications: "Fixed" means that the device is physically secured at one location and is not able to be easily moved to another location. "Mobile" means that the device is designed to be used in other than fixed locations and generally in such a way that a separation distance of at least 20 cm (8 inches) is normally maintained between the transmitter's antenna and the body of the user or nearby persons. The FASTRACK Supreme Plug & Play is not designed for and intended to be used in portable applications (within 20 cm or 8 inches of the body of the user) and such uses are strictly prohibited. 9.2 Vehicle Safety Do not use your FASTRACK Supreme Plug & Play while driving, unless equipped with a correctly installed vehicle kit allowing 'Hands-Free' Operation. Respect national regulations on the use of cellular telephones in vehicles. Road safety always comes first. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 74 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 341 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Fastrack Supreme User Guide Safety recommendations If incorrectly installed in a vehicle, the operation of FASTRACK Supreme Plug & Play telephone could interfere with the correct functioning of vehicle electronics. To avoid such problems, make sure that the installation has been performed by a qualified personnel. Verification of the protection of vehicle electronics should form part of the installation. The use of an alert device to operate a vehicle's lights or horn on public roads is not permitted. 9.3 Care and Maintenance Your FASTRACK Supreme Plug & Play is the product of advanced engineering, design and craftsmanship and should be treated with care. The suggestion below will help you to enjoy this product for many years. Do not expose the FASTRACK Supreme Plug & Play to any extreme environment where the temperature or humidity is high. Do not use or store the FASTRACK Supreme Plug & Play in dusty or dirty areas. Its moving parts (SIM holder for example) can be damaged. Do not attempt to disassemble the Wireless CPU®. There are no user serviceable parts inside. Do not expose the FASTRACK Supreme Plug & Play to water, rain or spilt beverages. It is not waterproof. Do not abuse your FASTRACK Supreme Plug & Play by dropping, knocking, or violently shaking it. Rough handling can damage it. Do not place the FASTRACK Supreme Plug & Play alongside computer discs, credit or travel cards or other magnetic media. The information contained on discs or cards may be affected by the Wireless CPU®. The use of third party equipment or accessories, not made or authorized by Wavecom may invalidate the warranty of the Wireless CPU®. Do contact an authorized Service Center in the unlikely event of a fault in the Wireless CPU®. 9.4 Your Responsibility This FASTRACK Supreme Plug & Play is under your responsibility. Please treat it with care respecting all local regulations. It is not a toy. Therefore, keep it in a safe place at all times and out of the reach of children. Try to remember your Unlock and PIN codes. Become familiar with and use the security features to block unauthorized use and theft. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 75 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 342 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 10 Recommended Accessories Fastrack Supreme User Guide Recommended Accessories Accessories recommended by Wavecom for the FASTRACK Supreme are given in the table below. Table 32: List of recommended accessories Designation Part number 1140.26 Quad-band antenna MA112VX00 MCA1890 MH/PB/SMA m SMA/FME adaptor Antenna Power adaptor (Europe) EGSTDW P2 EF9W3 24W Out:12 V - 2A In: 100 to 240 V 50/60 Hz 550 mA Mounted with micro-fit connector Fuse F800L250V Supplier ALLGON MAT Equipement HIRSCHMANN PROCOM EGSTDW (for power adaptor) MOLEX (for micro-fit connector)* Shanghai Fullness IESM GPS + USB M13SUE01 WAVECOM IESM IO + USB M13SUE02 WAVECOM IESM IO + USB + GPS M13SUE03 * Information not available for this preliminary version. WAVECOM confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 76 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 343 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual 11 Online Support Fastrack Supreme User Guide Online Support Wavecom provides an extensive range on online support which includes the following areas of Wavecom's wireless expertise: · the latest version of this document · new versions of our Operating System user guides · comprehensive support for Open AT® · regulatory certifications · carrier certifications · application notes To gain access to this support, simply visit our web site at www.wavecom.com or click on the desire link in Page. Privileged access via user login is provided to Wavecom authorized distributors. confidential © This document is the sole and exclusive property of WAVECOM. Not to be distributed or divulged without prior written agreement. WA_DEV_Fastrk_UGD_001 Page: 77 / 77 5 june, 2007 Q-Pulse Id: TMS196 26/11/2012 Page 344 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 345 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 346 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual DC/DC SWITCHING POWER SUPPLY DC INPUT 12,24,48, 110 SINGLE OUTPUT 25WATTS VTA-SCx/VTA-SD SERIES General Description Dimension: 85W × 135L × 31H DC INPUT: 12V Input Characteristics Unit Input Voltage Input Voltage Range Input Current(typ) Inrush Current *1 Efficiency (typical) *2 MTBF Switching Frequency DC INPUT: 24V Input Characteristics Vdc Vdc A A % H kHz Unit Input Voltage Input Voltage Range Input Current(typ) Inrush Current *1 Efficiency (typical) *2 MTBF Switching Frequency DC INPUT: 48V Input Characteristics Vdc Vdc A A % H kHz Unit Input Voltage Vdc Input Voltage Range Vdc Input Current(typ) A Inrush Current *1 A Efficiency (typical) *2 % MTBF H Switching Frequency kHz DC INPUT: 110V Input Characteristics Unit Input Voltage Input Voltage Range Input Current(typ) Inrush Current *1 Efficiency (typical) *2 MTBF Switching Frequency Vdc Vdc A A % H kHz VTA05SC12 2.9 72 60 Fix. VTA05SC24 1.34 75 60 Fix. VTA05SC48 0.68 78 60 Fix. VTA05SD 0.30 76 80 Fix. Features 1. Variety of Models 2. Chassis mount type 3. Compact and High Efficiency VTA12SC12 2.92 72 60 Fix. VTA15SC15 DC 12V DC 9.2V-16V 2.87 Not Specified 74 880'000 60 Fix. VTA24SC12 3.0 73 60 Fix. VTA48SC12 2.63 76 60 Fix. VTA12SC24 1.33 78 60 Fix. VTA15SC24 DC 24V DC 19-32V 1.36 Not Specified 79 880'000 60 Fix. VTA24SC24 1.34 78 60 Fix. VTA48SC24 1.28 82 60 Fix. VTA12SC48 0.66 80 60 Fix. VTA15SC48 DC 48V DC 38-63V 0.65 Not Specified 82 860'000 60 Fix. VTA24SC48 0.67 82 60 Fix. VTA48SC48 0.6 84 60 Fix. VTA12SD 0.29 78 80 Fix. VTA15SD DC 110V DC 85-140V 0.30 Not Specified 78 790'000 80 Fix. VTA24SD 0.31 78 80 Fix. VTA48SD 0.28 78 80 Fix. ETA USA 16170 Vineyard Blvd. Suite 180, Morgan Hill, CA 95037 Phone: 1-800-ETA-POWER, (408) 778-2793 Fax: (408) 779-2753 Q-Pulse Id: TMS196 26/11/2012 Visit us at: www.eta-usa.com email at: sales@eta-usa.com Page 347 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual VTA-SC / VTA-SD Output Models Characteristic Unit VTA05SCx / SD VTA12SCx / SD VTA15SCx / SD VTA24SCx / SD VTA48SCx / SD Output Voltage V Output Current A Voltage Adjust Range V 5 12 15 24 48 5.0 2.1 1.7 1.1 0.5 +/-10% of Rated Output Voltage(at no load within input range) Ripple Noise(max) *3 mVpp 100 170 200 290 530 Rise up time mS 100mS(maximum) at 25 and rated input/output Hold up time mS 10mS Regulation a. Line Regulation (max) mV 40 96 120 192 384 b. Load Regulation (max) mV 45 108 135 216 432 c. Temperature °C Coefficient *4 d. Drift(maximum) *5 mV 40 0.03%/ 75 90 135 255 e. Dynamic Load mV 150 Regulation (typ.) *6 f. Recovery Time *6 mS 360 450 720 0.5mS 1440 Conditions: *1 at cold start *2 at rated input/output *3 measured by a bayonet probe at the output connector at a 0 to 100MHz bandwidth *4 at 0 to +50 *5 for 7hour period after 1hour warm-up at 25 and rated input/output *6 when output current changed between 25% and 75% of rated output current rapidly at rated input Environmental Specification Operating Temperature Operating Humidity Storage Temperature Storage Humidity Withstanding Voltage Isolation Resistance Vibration Shock Cooling Functions Over current Protection Over voltage Protection Remote Sense Remote On/Off Reverse Voltage Protection Line Conduction Noise Weight [g](typical) Dimension [mm] 0 to +50 85%RH(non-condensing) -20 to +85°C - Primary-Secondary AC1,500Vfor 1minute (Vin=110 2000) Primary-Frame Ground AC1,500V for 1minute (Vin=110 2000) Secondary-Frame Ground AC500V for 1minute Primary-Secondary-Frame Ground 50M(minimum) by DC500V insulation tester 5-10Hz:10mm double amplitude,10-55Hz:19.6m/s2,20minutes' period for 60minutes each along X,Y,Z axes(non-operating) 294m/s2 Convection Current Limiting with automatic recovery Output shutdown not available not available by internal fuse Not specified 380 G 85W × 135L × 31H ETA USA 16170 Vineyard Blvd. Suite 180, Morgan Hill, CA 95037 Phone: 1-800-ETA-POWER, (408) 778-2793 Fax: (408) 779-2753 Q-Pulse Id: TMS196 26/11/2012 Visit us at: www.eta-usa.com email at: sales@eta-usa.com Page 348 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual BLOCK DIAGRAM DIMENSION DIAGRAM (mm) EFFICIENCY CURVE OCP CURVE ETA USA 16170 Vineyard Blvd. Suite 180, Morgan Hill, CA 95037 Phone: 1-800-ETA-POWER, (408) 778-2793 Fax: (408) 779-2753 Q-Pulse Id: TMS196 26/11/2012 Visit us at: www.eta-usa.com email at: sales@eta-usa.com Page 349 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Cellular Transit Antenna The TLA2000 is an ideal antenna solution for GSM data applications in both fixed and mobile situations. Designed to offer true dual band performance the TLA2000 is ready for use with the latest GSM (GPRS) modems. With a high impact resistant vacuum formed ABS radome and neoprene mounting gasket, the TLA2000 can be used for indoor or outdoor applications. · Applications include public vending machines, ATM kiosks and industrial automotive use · Designed for use on conductive or nonconductive surfaces · TLA3000 model incorporates integrated GPS antenna Typical VSWR response GSM900 2.5 2.4 2.3 2.2 2.1 2.0 1.9 1.8 1.7 1.6 1.5 -35 +35 Typical VSWR response GSM1800 -85 +85 890-960 MHz 1710-1880 MHz TLA2000 TLA3000 TLA2000/3000 Typical E-Plane response @ 890MHz Electrical Model No. Gain dBi Frequency MHz Power W Tuned Bandwidth Tuning Mechanical Model No. Construction Diameter mm Height mm Mounting Cable and Connector TLA2000/3000 2 890 - 960 / 1710 - 1880 10 Entire specified band @<2.5:1 VSWR Pre-tuned TLA2000 TLA3000 White Geloy ASA radome 135 61 (including gasket) M4 hardware (not included) 500mm low loss 9014 RG58 type Cellular: 5m 9014 RG58 type - FME connector GPS: 5m low loss RG174 type - MCX connector GPS Specifications Fo Operation Temperature Storage Temperature System Gain at Fo Impedance Polarization VSWR at Fo Noise Figure at Fo Power Input Power Consumption Power Input Over-Current 1575.42 MHz -40 to +85°C -40 to +100°C 28dBi including cable and filter losses 50 Ohm RHCP 1.5:1 <1.8 dB max. +2.5Vdc to +12Vdc input, Auto Switching 11mA to 13mA (max) Reverse Polarity Short Circuit Shutdown Thermal over-current shutdown >+150°C www.rfi.com.au Q-Pulse Id: TMS196 26/11/2012 109 Page 350 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UHF Directional Yagi Antennas 300-600 MHz YB Series YB6 YB16 The YB Series are high gain yagi antennas which will provide excellent point to point communication in RF control, short or long haul link and other applications calling for highly directional antennas. YB Series antennas exhibit narrow beamwidths and high front to back ratios to help minimise potential interference to and from other systems. The feed element of each antenna is of full folded dipole construction thus offering maximum bandwidth and reliability. The dipole element is welded to the boom to ensure low intermodulation performance and maximum durability. The passive elements are through mounted to the circular boom section and welded at each side to further minimise the potential for both corrosion and generation of intermodulation products. The alodined protective finish provides a conductive surface to ensure effective earthing of the antenna when mounting. Constructed with 2 to 16 elements, YB Series yagi antennas offer a choice of gain and beamwidth characteristics and can be configured in stacks or bays for higher gain applications in either horizontally or vertically polarised systems. Application details on phasing and mounting yagi antennas are included in the technical notes section of this catalogue. Yagi antennas rest at ground potential to provide excellent lightning protection and reduced precipitation static noise. Termination is via an 'N' female coaxial connector fitted to a short Durathene cable tail. Durathene polyethylene jacketed cable provides superior resistance to weathering and abrasion and is less susceptible to bird attack than standard PVC sheathed cables. For extreme climatic or corrosive applications, the stainless steel YBSS Series or black ruggedised RDA Series yagis should be considered. · All welded construction for maximum and reliable performance · Narrow beamwidths & high front to back ratios effective in reducing interference · Alodine finish provides an excellent conductive surface for earthing · Can be configured in stacks or bays for higher gain applications using PH and PHE series phasing harnesses Bracing kit available Part No. M-4528 54 Q-Pulse Id: TMS196 26/11/2012 www.rfi.com.au Page 351 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UHF Directional Yagi Antennas Typical VSWR response (YB03-99) YB03-99 - E Plane 300-600 MHz YB Series YB03-99 - H Plane Typical VSWR response (YB6-61) YB6-61 - E Plane YB6-61 - H Plane Electrical Model Number Nominal Gain dBi (dBd) Frequency MHz Tuned Bandwidth VSWR (Return Loss) Nominal Impedance Vertical Beamwidth Horizontal Beamwidth Front / Back Ratio dB Input Power W YB02-99 YB03-99 5 (3) 8 (6) 300 - 600 350 - 600 5% 77° 63° 161° 98° 9 13 YB6-65 400 - 420 YB6-61 YB6-62 11 (9 ) 450 - 480 480 - 520 Full band <1.5 :1 (14dB) 50 47° 56° 18 (Typical) 100 YB6-75 580 - 600 Mechanical Model Number Construction Length m Weight kg Termination Mounting Area Suggested Clamps Projected No ice Area cm² With ice Wind Load (Thrust) @ 160km/h N Wind Gust Rating km/h Torque @160 km/h Nm YB02-99 0.6 0.4 283 676 33 6 YB03-99 0.7 0.5 337 811 40 10 YB6-65 YB6-61 YB6-62 All welded aluminium with alodined finish 0.9 1.0 0.8 0.7 0.7 0.6 N female with short 9008 cable tail 100mm x 25mm diam. alodined aluminium 1 X UNV 485 477 394 1169 1099 967 57 56 47 >240 22 24 16 YB6-75 0.8 0.6 349 857 41 13 YB6-99 350 - 600 5% YB6-99 1.3 0.8 600 1367 71 42 www.rfi.com.au Q-Pulse Id: TMS196 26/11/2012 55 Page 352 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual UHF Directional Yagi Antennas 300-600 MHz YB Series Typical VSWR response (YB9-61) YB9-61 - E Plane YB9-61 - H Plane Typical VSWR response (YB16-70) YB16-70 - E Plane YB16-70 - H Plane Electrical Model Number Nominal Gain dBi (dBd) Frequency MHz Tuned Bandwidth VSWR (Return Loss) Nominal Impedance Vertical Beamwidth Horizontal Beamwidth Front / Back Ratio dB Input Power W YB9-65 YB9-61 YB9-62 YB9-99 YB16-65 YB16-70 YB16-71 YB16-63 YB16-72 YB16-99 13 (11) 14 (12) 400 - 420 450 - 480 480 - 520 400 - 600 400 - 420 450 - 470 470 - 490 480 - 500 500 - 520 400 - 600 Full band 5.0% Full band 5.0% <1.5 :1 (14dB) 50 46° 42° 34° 54° 48° 36° 18 (Typical) 100 Mechanical Model Number Construction Length m Weight kg Termination Mounting Area Suggested Clamps Projected No ice Area cm² With ice Wind Load (Thrust) @ 160km/h N Wind Gust Rating km/h Torque @160 km/h Nm YB9-65 2.0 1.2 859 2078 102 207 92 YB9-61 YB9-62 YB9-99 YB16-65 YB16-70 YB16-71 YB16-63 YB16-72 All welded aluminium with alodined finish 1.8 1.6 2.0 2.5 2.3 2.3 2.2 2.2 1.0 1.0 1.2 1.7 1.5 1.5 1.4 1.4 N female with short 9008 cable tail 100mm x 25mm diam. alodined aluminium 1 X UCR1 1 X UCR1 + 1 x M-4528 bracing kit 771 694 859 1186 1048 1030 989 981 1842 1640 2078 2983 2666 2617 2530 2507 YB16-99 2.5 1.7 1186 2983 91 82 102 141 124 122 117 116 141 220 240 207 147 165 165 173 173 147 75 60 92 165 130 128 117 116 165 56 Q-Pulse Id: TMS196 26/11/2012 www.rfi.com.au Page 353 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 5 SWITCHBOARD WORKS TEST RESULTS Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 354 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 355 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 356 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 357 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 358 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 359 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 360 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 361 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 362 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 6 "AS CONSTRUCTED" DRAWINGS Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 363 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 364 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 365 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 366 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 367 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 368 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 369 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 370 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 371 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 372 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 373 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 374 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 375 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 376 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 377 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 378 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 379 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 380 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual Q-Pulse Id: TMS196 26/11/2012 Page 381 of 382 WB002 Water Booster Pump Station - Electrical Switchboard - Operation and Maintenance Manual J & P Richardson Industries Pty Ltd 7 SERVICE & MAINTENANCE This product is designed to operate under specific environmental, supply and load conditions. Should these conditions change, consult a licenced electrician or electrical engineer before operating this product. These procedures are to be performed only by a licenced electrician as they may expose live equipment. The Switchgear and Controlgear Assembly is essentially maintenance free, however the following safety measures and routine maintenance is recommended. Where fitted, ensure cabinet vents and filters are clear and clean. During operation, ensure all doors and covers are secure and closed. All faults are to be investigated and repaired by an appropriately licenced electrician. All components to be operated in accordance with manufacturers data. The protective devices within switchboards are designed to operate in the event of a short circuit or overload condition. In the event of these devices operating under such conditions the device or devices must be inspected and tested by a suitably trained person to ascertain its condition prior to reconnecting the protective device to the supply. Periodic checks should ensure The switchboard is clean and free of any contaminants, which could reduce the insulation properties of the switchboard. All entries are sealed to ensure no vermin can enter. There is no evidence of overheating, arcing or moisture. The earthing system is maintained and is adequate to allow correct operation of protective devices. Insulation resistance is maintained to appropriate levels. Check terminations for correct tension. Test operation of protective devices. Re-calibrate instrument loops as required. Refer to AS-CONSTRUCTED electrical drawings for details of protection equipment settings. No special tools or equipment are required to perform routine maintenance. Q-Pulse Id: TMS196 Revision 0 26/11/2012 Date: 2 July 2012 Page 382 of 382ScanSoft PDF Create! 6