Growatt Off Grid MPV Solar Inverter User Manual

Model Series: Split Phase 4KW-12KW
Version: 1.0

Information on this Manual

Validity

This manual is valid for the following devices:

Scope

This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations.

Target Group

This document is intended for qualified persons and end users. Tasks that do not require any particular qualification can also be performed by end users. Qualified persons must have the following skills:

Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. CAUTION: Only qualified personnel can install this device with battery.
  2. Before using the unit, read all instructions and caution marks on the unit, understand the batteries, and all appropriate sections of this manual.
  3. CAUTION: To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  4. NEVER cause AC output and DC input short circuit. Do not connect to the mains when DC input short circuits.
  5. NEVER charge a frozen battery.
  6. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  7. To reduce risk of electric shock, disconnect all wiring before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk, such as dropping a tool to spark or short circuit batteries or other electrical parts, could cause an explosion.
  9. For optimum operation of this off-grid solar inverter, please follow required specifications to select appropriate cable size. It is very important to correctly operate this off-grid solar inverter.
  10. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
  11. GROUNDING INSTRUCTIONS: This off-grid solar inverter should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please contact your local dealer or service center for maintenance.

Introduction

Hybrid Power System

This is a multifunctional split-phase output off-grid solar inverter, integrated with an MPPT solar charge controller, a low-frequency pure sine wave inverter, and a UPS function module in one machine, which is perfect for off-grid backup power and self-consumption applications.

The whole system also needs other devices to achieve complete running, such as PV modules, a generator, or a utility grid. Please consult with your system integrator for other possible system architectures depending on your requirements. The WiFi / GPRS module is a plug-and-play monitoring device to be installed on the inverter. With this device, users can monitor the status of the PV system from the mobile phone or from the website anytime, anywhere.

Diagram Description (Hybrid Power System): A diagram illustrates the Hybrid Power System. On the left, a Solar Panel, Utility Grid, and Generator are shown, each connected via lines labeled L1 and L2 to the central inverter unit. The inverter is also connected to a Battery. From the inverter, connections go to a WiFi/GPRS module, which links to the Internet and ShinePhone/ShineServer. The inverter also outputs power to Home Loads, with lines labeled 120V and 240V, and N (Neutral).

Features

Product Overview

The product overview shows the front and rear panels of the inverter. The front panel features an ON/OFF power switch, LCD display, Status indicator, Charging indicator, Fault indicator, and Function buttons. The rear panel includes connections for Battery (+/-), Fan, Dry contact, Remote control port, WiFi/GPRS device port, USB port, BMS (optional), RS485 (optional), AC input switch, AC input, AC output switch, AC output, and PV input.

Component List:

  1. ON/OFF power switch
  2. LCD display
  3. Status indicator
  4. Charging indicator
  5. Fault indicator
  6. Function buttons
  7. Battery "-"
  8. Battery "+"
  9. Fan
  10. Dry contact
  11. Remote control port
  12. WiFi/GPRS device port
  13. USB port
  14. BMS (optional)
  15. RS485 (optional)
  16. AC input switch
  17. AC input
  18. AC output switch
  19. AC output
  20. PV input

Installation

Unpacking and Inspection

Before installation, please inspect the unit. Ensure nothing inside the package is damaged. The package should contain:

Preparation

Before connecting all wiring, remove the bottom cover by unscrewing eight screws.

Mounting the Unit

Consider the following points before selecting an installation location:

Diagram Description (Mounting): Diagrams show recommended mounting clearances (e.g., 80cm, 50cm) and dimensions for the inverter. The 4-6KW models require 400mm width and 180mm height clearance, while 8-12KW models require 420mm width and 240mm height clearance. The text "SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY" is prominently displayed.

Install the unit by screwing in the six setscrews.

Battery Connection

CAUTION: For safety and regulatory compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Over-current protection is always requested.

WARNING: All wiring must be performed by a qualified person. Using appropriate cable for battery connection is crucial for system safety and efficient operation.

Recommended battery cable and terminal size:

ModelBattery VoltageWire Gage/min
4kw48V1*2AWG
5kw48V1*1AWG
6kw48V2*3AWG
8kw48V2*2AWG
10kw48V2*1AWG
12kw48V3*2AWG

Steps for Battery Connection:

  1. Assemble battery ring terminals based on the recommended cable and terminal size.
  2. Connect all battery packs as required. It is suggested to use at least a 200Ah capacity battery for 4KW~6KW models and at least a 400Ah capacity battery for 8KW~12KW models.
  3. Insert the ring terminal of the battery cable flatly into the battery connector of the inverter. Ensure the bolts are tightened with a torque of 2-3 Nm. Verify correct polarity at both the battery and the inverter/charge, and ensure ring terminals are tightly screwed to the battery terminals.

WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.

CAUTION: Do not place anything between the flat part of the inverter terminal and the ring terminal, as this may cause overheating.

CAUTION: Do not apply anti-oxidant substance on the terminals before they are connected tightly.

CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).

Lithium Battery Connection

If using a lithium battery with Growatt SPF series products, ensure it is a configured lithium battery. Lithium batteries typically have an RJ45 port for BMS communication and a power cable.

Steps for Lithium Battery Connection:

  1. Assemble battery ring terminals based on recommended battery cable and terminal size (refer to Lead acid section 3.4.1 for details).
  2. Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and tighten bolts to 2-3 Nm. Ensure correct polarity and secure connections.
  3. Connect the RJ45 end of the battery to the BMS communication port of the inverter.
  4. Connect the other end of the RJ45 to the battery communication port.

Note: For lithium batteries, ensure the BMS communication cable is connected between the battery and the inverter. The battery type must be set to "lithium battery" in the inverter settings.

Lithium Battery Communication and Setting

To enable communication with the battery BMS, set the battery type to "LI" in Program 05. This will switch the LCD to Program 51 for protocol selection. The inverter supports four RS485 protocols; Basic Protocol 1 is defined by Growatt, while others are customized. Consult Growatt for questions regarding BMS communication.

BMS Port Pin Assignment:

Connect the RJ45 cable from the battery to the inverter's BMS communication port, ensuring a Pin-to-Pin connection. The inverter BMS port pin assignment is as follows:

Pin numberBMS port
1RS485B
2RS485A
3--
4--
5--
6--
7--
8--

Diagram Description (BMS Port): A diagram shows a standard 8-pin connector labeled "87654321", indicating the pin numbering for the BMS port.

LCD Setting (Battery Type)

To connect the battery BMS, set the battery type to "LI" in Program 05. After setting "LI", Program 51 will appear to choose the battery type.

Battery Type Options (Program 05):

Lithium Battery BMS Communication Protocol Options (Program 51): L01, L02, L03, L04.

Note: When the battery type is set to "LI", settings for options 12, 13, and 21 will display percentages. The Maximum charge current cannot be modified by the user when the battery type is "LI". If communication fails, the inverter will cut off output.

Related Programs for Lithium Batteries:

AC Input/Output Connection

CAUTION: Before connecting to the AC input power source, install a separate AC breaker between the inverter and the power source. This ensures secure disconnection during maintenance and protection from over-current. Recommended AC breaker specs: 40A for 4KW~6KW, 80A for 8KW~12KW.

CAUTION: There are two terminal blocks marked "IN" and "OUT". Do NOT mis-connect input and output connectors.

WARNING: All wiring must be performed by a qualified personnel. Using the proper recommended cable size for AC input connection is very important for system safety and efficient operation.

Suggested cable requirement for AC wires:

ModelGaugeTorque Value
4KW/5KW10 AWG1.4~ 1.6 Nm
6KW/8KW8 AWG1.4~ 1.6 Nm
10KW/12KW6 AWG1.6~ 1.8 Nm

AC Wiring Diagrams:

Single phase with 240V output:

Single phase with 120V output:

Diagram Description (AC Wiring): Diagrams illustrate AC input and output connections for 4-6KW and 8-12KW models, showing terminal blocks for AC INPUT (HOT1, HOT2), AC OUTPUT (HOT1, N, HOT2), and PV INPUT (+/-). Wire colors are indicated: Ground (yellow-green), L (brown or black), N (blue).

Steps for AC Input/Output Connection:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten terminal screws. Connect the PE protective conductor first.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

  1. Insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws. Connect the PE protective conductor first.
  2. Make sure the wires are securely connected.

CAUTION: Important Ensure AC wires are connected with correct polarity. Reversing L and N wires may cause utility short-circuiting during parallel operation.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart to balance refrigerant gas. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if the appliance has a time-delay function before installation. Otherwise, this inverter may trigger an overload fault and cut off output to protect the appliance, but sometimes internal damage may still occur.

PV Connection

CAUTION: Before connecting PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING: All wiring must be performed by a qualified personnel. Using the proper recommended cable size for PV module connection is very important for system safety and efficient operation.

Recommended PV cable size and torque:

ModelTypical AmperageCable SizeTorque
4KW/5KW/6KW80A8AWG1.6~1.8 Nm
8KW/10KW/12KW120A8AWG1.6~1.8 Nm

PV Module Selection:

When selecting PV modules, consider the following parameters:

  1. The open-circuit voltage (Voc) of PV modules must not exceed the max. PV array open-circuit voltage of the inverter.
  2. The open-circuit voltage (Voc) of PV modules should be higher than the min. battery voltage.

Solar Charging Mode Parameters:

ParameterValue
INVERTER MODEL4KW/5KW/6KW/8KW/10KW/12KW
Max. PV Array Open Circuit Voltage250Vdc
PV Array MPPT Voltage Range60~245Vdc
Min. battery voltage for PV charge34Vdc

Steps for PV Module Connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check the correct polarity of the connection cable from PV modules and PV input connectors. Connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
  3. Make sure the wires are securely connected.

Diagram Description (PV Wiring): Diagrams show PV input terminals for 4-6KW (MPPT 80A) and 8-10KW/12KW (MPPT 120A) models. Each model shows PV1 INPUT and PV2 INPUT terminals with '+' and '-' markings, indicating polarity. A 3mm maximum insulation strip length is indicated.

Communication Connection

Use the supplied communication cable to connect the inverter to a PC. Insert the bundled CD into a computer and follow the on-screen instructions to install the monitoring software. For detailed software operation, refer to the software's user manual on the CD.

Dry Contact Signal

There is one dry contact (3A/250VAC) available on the rear panel. It can be used to send a signal to a generator when the battery voltage reaches a warning level.

Dry Contact Port States:

Unit StatusConditionDry contact port: NC & CDry contact port: NO & C
Power OffUnit is off and no output is powered.CloseOpen
Output is off and no output is powered.CloseOpen
Power On (Output is powered from Battery or solar)Program 01 set as Utility: Battery voltage< Low DC warning voltageOpenClose
Program 01 set as Utility: Battery voltage> Setting value in Program 13 or battery charging reaches floating stageCloseOpen
Program 01 is set as SBU or Solar first: Battery voltage< Setting value in Program 12OpenClose
Program 01 is set as SBU or Solar first: Battery voltage> Setting value in Program 13 or battery charging reaches floating stageCloseOpen

Electrical Performance

AC Charger

The inverter is equipped with an active PFC (Power Factor Correction) multistage battery charger. The PFC feature controls the power used to charge batteries to achieve a power factor close to 1. When AC voltage is in the range of 154~260VAC, the charging current is 100%. The inverter offers strong charging current, up to 100A for the 12KW model, adjustable from 10A~100A, which is beneficial for small capacity battery banks.

Charging Stages:

Diagram Description (Charging Stages): A graph shows three stages: Bulk (Constant Current), Absorption (Constant Voltage), and Maintenance (Floating). It plots Battery Voltage (per cell) and Charging Current (%) against Time, illustrating the transitions between stages.

AC Charging Current:

ModelBattery VoltageMax. AC Charging Current
4KW48V40A
5KW48V50A
6KW48V60A
8KW48V70A
10KW48V80A
12KW48V100A

Operation

Power ON/OFF

Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the case) to turn the unit on.

Operation and Display Panel

The operation and display panel is on the front of the inverter and includes a LCD display, three indicators, and four function keys to show operating status and input/output power information.

Panel Components:

  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons

Diagram Description (Operation Panel): A diagram shows the front panel with indicators labeled AC/INV, CHG, and FAULT, and a LCD display area. Below the display are four function buttons: ESC, UP, DOWN, ENTER.

LED Indicator Status:

LED IndicatorColorStatusMessages
AC/INVGreenSolid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Buttons:

ButtonDescription
ESCTo exit setting mode.
UPTo go to previous selection.
DOWNTo go to next selection.
ENTERTo confirm the selection in setting mode or enter setting mode.

LCD Display Icons

The LCD display shows various information icons. The display can be switched by pressing the "UP" or "DOWN" keys.

Input Source Information:

Configuration Program and Fault Information:

Output Information:

Battery Information:

Battery Status vs. LCD Display:

StatusBattery voltageLCD Display
Constant Current mode / Constant Voltage mode<2V/cell4 bars will flash in turns.
2 ~ 2.083V/cellBottom bar will be on and the other three bars will flash in turns.
2.083 ~ 2.167V/cellBottom two bars will be on and the other two bars will flash in turns.
> 2.167 V/cellBottom three bars will be on and the top bar will flash.
Floating mode. Batteries are fully charged.--4 bars will be on.

Load Percentage:

In battery mode, battery capacity is presented. The load level is indicated by 0-24%, 25-49%, 50-74%, and 75-100%.

Load PercentageBattery VoltageLCD Display
Load >50%< 1.717V/cell[Icon: Battery 1/4 full]
1.717V/cell ~ 1.8V/cell[Icon: Battery 2/4 full]
1.8 ~ 1.883V/cell[Icon: Battery 3/4 full]
> 1.883 V/cell[Icon: Battery 4/4 full]
50%> Load > 20%< 1.817V/cell[Icon: Battery 1/4 full]
1.817V/cell ~ 1.9V/cell[Icon: Battery 2/4 full]
1.9 ~ 1.983V/cell[Icon: Battery 3/4 full]
> 1.983[Icon: Battery 4/4 full]
Load < 20%< 1.867V/cell[Icon: Battery 1/4 full]
1.867V/cell ~ 1.95V/cell[Icon: Battery 2/4 full]
1.95 ~ 2.033V/cell[Icon: Battery 3/4 full]
> 2.033[Icon: Battery 4/4 full]

Load Information:

Mode Operation Information:

Mute Operation:

LCD Setting Programs

To enter setting mode, press and hold the ENTER button for 3 seconds. Use "UP" or "DOWN" to select programs, and "ENTER" to confirm or "ESC" to exit.

Setting Programs:

ProgramDescriptionSetting Option
01
Output source priority:
To configure load
power source priority
Solar firstSolar energy provides power to the loads as first priority. If solar energy is not sufficient, battery energy supplies power. Utility provides power only when solar energy is unavailable or battery voltage drops to low-level warning or program 12 setting.
Utility first (default)Utility provides power as first priority. Solar and battery energy supply power only when utility power is unavailable.
SBU prioritySolar energy provides power as first priority. If solar energy is insufficient, battery energy supplies power. Utility provides power only when battery voltage drops to low-level warning or program 12 setting.
02
Maximum charging
current: To configure total
charging current for solar
and utility chargers.
(Max. charging current =
utility charging current +
solar charging current)
  • 12KW model: default 80A, 10A~180A Settable
  • 10KW model: default 80A, 10A~160A Settable
  • 8KW model: default 80A, 10A~150A Settable
  • 6KW model: default 80A, 10A~140A Settable
  • 5KW model: default 80A, 10A~130A Settable
  • 4KW model: default 80A, 10A~120A Settable

(If Li is selected in program 5, this program cannot be set up)

03
AC input voltage range
APL (default)If selected, acceptable AC input voltage range will be within 154~272VAC.
UPSIf selected, acceptable AC input voltage range will be within 184~272VAC.
05
Battery type
AGM (Default)--
Flood--
User-DefinedIf "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 19, 20 and 21.
User-Defined 2 (Suitable for lithium battery when no communicating with BMS)If 'US2' is selected, battery charge voltage and low DC cut-off voltage can be set up in program 19, 20 and 21.
Lithium (Only suitable when communicate with BMS)The lithium battery BMS communication protocol options: L01, L02, L03, L04...
06
Auto restart when
overload occurs
Restart disable (default)--
Restart enable--
08
Output voltage
230V / 240V (default)--
220V / 208V--
09
Output frequency
50Hz (default)--
60Hz--
11
Maximum utility
charging current
  • 12KW model: default 30A, 10A~100A Settable
  • 10KW model: default 30A, 10A~80A Settable
  • 8KW model: default 30A, 10A~70A Settable
  • 6KW model: default 30A, 10A~60A Settable
  • 5KW model: default 30A, 10A~50A Settable
  • 4KW model: default 30A, 10A~40A Settable

(If Li is selected in program 5, this program cannot be set up)

12
Setting voltage point
back to utility source
when selecting "SBU
priority" or "Solar
first" in program 01
48V model: default 46.0V, 44.0V~51.2V settable--
Lithium battery mode: default 40%, 5%~50% settable--
13
Setting voltage point
back to battery mode
when selecting "SBU
priority" or "Solar
first" in program 01
48V model: default 54.0V, 48.0V~58.0V Settable--
48V Li mode: default 80%, 60%~100% settable--
14
Charger source priority:
To configure charger
source priority
Solar firstIf this off-grid solar inverter is working in Line, Standby or Fault mode, charger source can be programmed as below: Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.
Utility first (default)Utility will charge battery as first priority. Solar energy will charge battery only when utility power is not available.
Solar and UtilitySolar energy and utility will both charge battery.
Only SolarSolar energy will be the only charger source no matter utility is available or not. If this off-grid solar inverter is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient.
15
Alarm control
Alarm on (default) / Alarm off--
16
Backlight control
Backlight on (default) / Backlight off--
17
Beeps while primary
source is interrupted
Alarm on (default) / Alarm off--
19
C.V. charging voltage
If self-defined is
selected in program 5,
this program can be set
up
48V model: default 56.4V, 48.0V~58.4V Settable--
20
Floating charging
voltage.
If self-defined is
selected in program 5,
this program can be set
up
48V model: default 54.0V, 48.0V~58.4V Settable--
21
Low DC cut-off
voltage.
If self-defined is
selected in program
5, this program can
be set up
48V model: default 42.0V, 40.0V~48.0V Settable
Lithium battery mode: default 20%, 5%~50% settable
--
22
RS485
Communication Address
Default 001, 001-255 Settable--
23
Battery equalization
If "Flooded" or "User-Defined" is selected in program this program can be set up.--
24
Battery equalization
voltage
48.0V model: default 58.4V, 48~60V settable--
25
Battery equalized time
Setting range is from 5min to 900min. Increment of each click is 1min.--
26
Battery equalized timeout
Setting range is from 5min to 900min. Increment of each click is 1 min.--
27
Equalization interval
Setting range is from 1 to 30 days. Increment of each click is 1 day.--
28
Equalization
immediately
activated
If equalization function is enabled in program 23, this program can be set up. If "Enable" is selected, it activates battery equalization immediately. If "Disable" is selected, it cancels equalization until the next scheduled time based on program 27.--

Display Setting

The LCD display information switches in turns by pressing the "UP" or "DOWN" key. The selectable information order is: input voltage, input frequency, PV voltage, MPPT charging current, MPPT charging power, battery voltage, output voltage, output frequency, load percentage, load in VA, load in Watt, DC discharging current, main CPU Version, and second CPU Version.

LCD Display Examples:

Operating Mode Description

This section describes the different operating modes of the inverter and their corresponding LCD displays.

Operation modeDescriptionLCD display
Standby mode /Power saving mode
Note: In Standby mode, the inverter is not turned on yet, but it can charge the battery without AC output.
No output is supplied by PV; still can charge batteries.When utility grid connected, no charging; PV can charge.
Line ModePriority for utility drive the loading solar priority charging. The unit will provide output power from the mains. It will also charge the battery at line mode.Charging by PV energy / Charging by utility.
Battery ModeThe unit will provide output power from battery and PV power.Power from battery and PV energy. / Power from battery only.

Fault Reference Code

This section lists fault codes, their corresponding events, and the icon displayed on the unit.

Fault CodeFault EventIcon on
01Fan is not working.[Icon: 01-]
02Over temperature[Icon: 02-]
03Battery voltage is too high[Icon: 03-]
04Battery voltage is too low[Icon: 04-]
05Output short circuited or over temperature is detected by internal converter components[Icon: 05-]
06Output voltage is abnormal.[Icon: 06-]
07Output voltage is too high.[Icon: 07-]
20BMS communication loss[Icon: 20-]
51Over current or surge[Icon: 51-]

Warning Indicator

This section lists warning codes, their corresponding events, audible alarms, and flashing icons.

Warning CodeWarning EventAudible AlarmIcon flashing
10Battery low voltageBeep twice every second[Icon: 10°]
11Overload on bypassBeep once every second[Icon: 11°]
12Solar controller over temperatureBeep once every second[Icon: 12°]
51MPPT over currentBeep once every second[Icon: 51°]
54PV input over voltageBeep once every second[Icon: 54°]
58AC output low voltageBeep once every second[Icon: 58°]
59MPPT Bat over temperatureBeep once every second[Icon: 59°]
60External MPPT communication WarningBeep once every second[Icon: 60°]
61External MPPT consistent WarningBeep once every second[Icon: 61°]

Battery Equalization

The equalization function is added to the charge controller to reverse the buildup of negative chemical effects like stratification (where acid concentration is greater at the bottom than the top) and to remove sulfate crystals from battery plates. If unchecked, sulfation reduces battery capacity. Periodic equalization is recommended.

How to Apply Equalization Function:

Enable the battery equalization function in monitoring LCD setting Program 43 first. Then, apply the function using one of the following methods:

  1. Setting equalization interval in Program 47.
  2. Activating equalization immediately in Program 48.

When to Equalize:

In the float stage, when the set equalization interval (battery equalization cycle) is reached, or when equalization is activated immediately, the controller enters the Equalize stage.

Diagram Description (Equalize Stage): A graph shows the voltage profile over time during charging stages: BULK, ABSORPTION, FLOAT, and EQUALIZE. The Equalize voltage is shown to be higher than the Float voltage.

Equalize Charging Time and Timeout:

In the Equalize stage, the controller supplies maximum power to charge the battery until it reaches the battery equalization voltage. Constant-voltage regulation then maintains this voltage. The battery remains in the Equalize stage until the set battery equalized time is reached.

If the battery voltage does not reach the equalization voltage point by the time the battery equalized time expires, the charge controller will extend the equalization time. If the battery voltage is still lower than the equalization voltage when the battery equalized timeout setting is exceeded, the charge controller will stop equalization and return to the float stage.

Diagram Description (Equalize Charging Time/Timeout): Graphs illustrate the Equalize stage, showing how "Equalize Charging Time" and "Equalize Charging Timeout" affect the duration and completion of the equalization process based on battery voltage reaching the target equalization voltage.

Trouble Shooting

This section provides solutions for common problems encountered with the inverter.

ProblemLCD/LED/BuzzerExplanation / Possible CauseWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
1. The battery voltage is far too low. (<1.4V/Cell)
2. Battery polarity is connected reversed.
1. Check if batteries and the wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Fan faultReplace the fan.
No response after power on.No indication.Internal temperature of component is over 90°C.Check if the air flow of the unit is blocked or the ambient temperature is too high.
Buzzer beeps continuously and red LED is on.Fault code 01Battery is over-charged.Return to repair center.
Fault code 02The battery voltage is too high.Check if spec and quantity of batteries are meet requirements.
Fault code 03The battery voltage is too low.Check if wiring is connected well and remove abnormal load.
Fault code 04Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 05Output abnormal (Inverter voltage below than 180Vac or is higher than 290Vac)1. Reduce the connected load.
2. Return to repair center.
Fault code 06/58Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 07BMS communication failed1. Check the BMS communication wire to see if it's well connected.
2. Check the transceiver signal.
Fault code 20Over current or surgeRestart the unit, if the error happens again, please return to repair center.
Fault code 51----

Specifications

Detailed specifications for the Growatt Off Grid MPV Solar Inverter series are provided below.

MODELSPF 4000T DVM-MPVSPF 5000T DVM-MPVSPF 6000T DVM-MPVSPF 8000T DVM-MPVSPF 10000T DVM-MPVSPF 12000T DVM-MPV
Battery voltage48VDC
INVERTER OUTPUT
Rated Power4KW5KW6KW8KW10KW12KW
Surge Rating (20ms)12KW15KW18KW24KW30KW36KW
WaveformPure sine wave/ same as input (bypass mode)
Nominal Output Voltage104V-110V-115V-120Vac / 208V-220V-230V-240Vac(+/-10% RMS)
Output Frequency50Hz/60Hz (+/-0.3 Hz)
Inverter Efficiency(Peak)>85%
Line Mode Efficiency>95%
Power Factor1.0
SOLAR CHARGER
Maximum PV Charge Current80A120A
DC Voltage48V
Maximum PV Array Power5000W7000W
MPPT Operating Voltage(VDC)60-245V
Max. PV Array Open Circuit Voltage250VDC
Maximum Efficiency>98%
DC Input
Low DC Cut-Off Voltage (Only Lead Acid)@load<20%: 42.0V; @20%≤load<50%: 40.8V; @load≥50%: 38.4V
Low DC Warning Voltage (Only Lead Acid)@load<20%: 44.0V; @20%≤load<50%: 42.8V; @load≥50%: 40.4V
Low DC Warning Return Voltage (Only Lead Acid)48V
Low DC Warning SOC (Only Li)Low DC Cut-off Soc +5%
Low DC Warning Return SOC (Only Li)Low DC Cut-off Soc +15%
Low DC Cut-off SOC (Only Li)Default 20%, 5%~50% Settable
Cold Start SOC (Only Li)>Cut-off Soc+10%
High DC Recovery Voltage58VDC
High DC Cut-Off VoltageAGM:60V, FLD:62V, USE or Li Mode: C.V. Voltage + 4.0V
AC INPUT
Voltage230VAC
Selectable Voltage Range154~272VAC(for appliances ), 184~272VAC(for UPS)
Frequency Range50Hz/60Hz (Auto sensing)
Maximum Charge Current40A50A60A70A80A100A
BYPASS & PROTECTION (Grid & Generator)
Typical Transfer Time10ms(max)
Overload Protection (SMPS Load)Circuit breaker
Output Short Circuit ProtectionCircuit breaker
MECHANICAL SPECIFICATIONS
Dimensions (W*H*D)540*360*218mm650*380*225mm
Net Weight (Solar CHG) kg384145646675
OPERATING ENVIRONMENT
Operation Temperature Range0°C to 40°C
Storage Temperature-15°C to 60°C

PDF preview unavailable. Download the PDF instead.

5f63033fb11f1 Microsoft Office Word 2007 Microsoft Office Word 2007

Related Documents

PreviewGrowatt SPF Series Off-Grid Solar Inverter User Manual: 4KW-12KW Split Phase
Comprehensive user manual for Growatt SPF Series Off-Grid MPV Solar Inverters (4KW-12KW, Split Phase). Covers installation, operation, safety, troubleshooting, and specifications for efficient solar energy management.
PreviewGrowatt SPF 6000 ES Plus: New Generation Off-Grid PV Inverter
Explore the Growatt SPF 6000 ES Plus, a new generation off-grid PV inverter offering higher yield, scalability, flexibility, smart management, and reliable performance for solar energy storage systems. Features dual MPP trackers, powerful PV input, and multiple work modes.
PreviewGROWATT SPF 3500 ES & 5000 ES Off-Grid Solar Inverter User Manual
Comprehensive user manual for the GROWATT SPF 3500 ES and SPF 5000 ES off-grid solar inverters, covering installation, operation, troubleshooting, and parallel configurations for reliable solar power solutions.
PreviewCertificate of Conformity: Growatt SPF 5000 ES PV Off-grid Inverter
Official Certificate of Conformity for the Growatt SPF 5000 ES PV Off-grid inverter, issued by Shenzhen Nore Testing Center Co., Ltd., confirming compliance with Low Voltage Directive 2014/35/EU and standards EN 62109.
PreviewGrowatt SPH 10000TL-HU-US Grid-Hybrid Inverter User Manual
User manual providing detailed information on the Growatt SPH 10000TL-HU-US Grid-Hybrid Inverter, covering installation, operation, system configuration, and troubleshooting for optimal performance.
PreviewGrowatt CP500TL-S / CP630TL-S Solar Inverter Datasheet
Technical specifications and features for the Growatt CP500TL-S and CP630TL-S solar inverters, highlighting high efficiency, grid management, and protection features.
PreviewGrowatt SPF Series PV Off-grid Inverter Installation and Operation Manual
This comprehensive manual from Growatt provides essential guidance for the installation, operation, and troubleshooting of the Growatt SPF Series of PV Off-grid Inverters. It covers safety precautions, system architecture, connection procedures, operational features, specifications, and warranty information for models SPF3000, SPF5000, and SPF3000 PLUS.
PreviewGrowatt Energy Storage Configuration Quick Check List
A quick reference guide for configuring Growatt Battery Ready and ARK HV Energy Storage Systems, detailing compatibility and component requirements for various models including APX HV, ARK HV, ARK XH, ARK LV, and AXE LV systems.