Original Instruction
This document is the original installation manual. This section details the accessory parts included with the installation manual. WARNING: CAUTION: Select a location where air circulates evenly. Avoid: In environments with high humidity (dew-point temperature 23°C or higher), such as during the rainy season or in ceilings with tiles/slated roofs, or near fresh air intakes: [Reference] Condensation test conditions: Indoor side: 27°C dry bulb, 24°C wet bulb; Air volume: Low; Operation time: 4 hours. Reserve adequate space for installation and service. Diagrams illustrate required clearances for air discharge, inspection openings, and service access (for filter maintenance). Specific dimensions (A, B) are provided for different model series: The filter cleaning notification term can be adjusted via the remote controller. Refer to the "Filter sign setting" in the Applicable Controls section for setup methods. CAUTION: Strictly follow these guidelines to prevent unit damage and injury: Diagrams show external dimensions and hanging bolt pitch: A table provides specific dimensions for models: Consider piping and wiring when determining unit location and orientation. Install hanging bolts after location is set, referring to external views for pitch dimensions. For existing ceilings, lay drain pipes, refrigerant pipes, and control wires before hanging the unit. Procure hanging bolts, washers, and nuts separately. Recommended specifications: M10 or W3/8 hanging bolts (4 pcs), M10 or W3/8 nuts (12 pcs), M10 washers (8 pcs). Treatment of ceiling: Consult your constructor or interior finish contractor for ceiling structure details. Reinforce ceiling foundation and ensure the installed ceiling is level to prevent vibration. REQUIREMENT: Hang the unit horizontally to prevent drain overflow. Install within specified dimensions. Use a level gauge. Diagrams show front and side views for setting the unit horizontally, ensuring the drain pipe connecting port is lower than the opposite side by up to 5 mm, and air intake/discharge sides are within 5 mm of each other. CAUTION: Push rails until latches click. Diagrams illustrate the process, noting that covers for UP0241-UP0301 units are not identical and may need to be reversed. CAUTION: Ensure proper drainage and apply heat insulation to prevent condensation. Improper piping can cause water leakage. Diagrams show correct piping with downward slope and support brackets, and incorrect piping with arched shape or traps. Locally procured materials are required: Insert the flexible drain hose into the upper drain pipe of the main unit as far as it will go and secure it with a hose band. Do not use adhesive. Diagrams show the connection and required dimensions. Diagrams illustrate moving the drain cap and the setup. For situations where a down-gradient cannot be secured, drain-up piping is possible: Diagrams show drain up setup dimensions. During test run, verify proper water drainage and check for leaks at pipe connections. Also, listen for abnormal sounds from the drain pump motor. Check drainage during heating operation as well. Pour water following the diagram. During cooling operation, check for drainage from the connecting port and for leaks. Diagrams show the electrical connections for testing. Manufacture ducts locally according to the dimensions provided for different model series (UP005-UP018, UP024-UP030, UP036-UP056) and air intake configurations (Under air intake, Back air intake). Dimensions are given in millimeters. CAUTION: Use only the provided flare nuts to prevent refrigerant gas leakage. Use seamless phosphorous de-oxidized copper pipe. Wall thickness requirements: 0.8 mm or more for 6.35, 9.52, 12.7 mm; 1.0 mm or more for 15.88 mm. REQUIREMENT: For long refrigerant pipes, install support brackets every 2.5-3 m to prevent abnormal sounds. CAUTION: IMPORTANT 4 POINTS FOR PIPING WORK: These vary depending on the outdoor unit. Refer to the outdoor unit's Installation Manual for details. A table lists pipe sizes (gas and liquid sides) for different model series: Projection margin in flaring (B): 0-0.5 mm for 6.4, 9.5 mm pipes (conventional tool); 1.0-1.5 mm for 12.7, 15.9 mm pipes (conventional tool). Flaring diameter size (A): CAUTION: Do not scratch the flared part's inner surface. Check for scratches, deformation, chips, etc. Do not apply refrigerating machine oil to the flare surface. For R32/R410A with conventional tools, pull out approx. 0.5 mm more than for R22. The sealed gas is at atmospheric pressure; a "whooshing" sound upon flare nut removal is normal. Use specified tightening torques: R32/R410A pressure is higher. Use a torque wrench. Incorrect connections can cause gas leaks and refrigeration cycle trouble. CAUTION: Overtightening may crack the nut. Perform vacuuming from the outdoor unit's charge port using a vacuum pump. Refer to the outdoor unit manual. Do not use the sealed refrigerant for evacuation. REQUIREMENT: Use tools exclusively for R32 or R410A. Add R32 or R410A refrigerant as specified in the outdoor unit manual. Use a scale for accurate charging. REQUIREMENT: Incorrect refrigerant amounts can damage the compressor. Record pipe length and added refrigerant on the F-GAS label. Refer to the outdoor unit manual for airtight testing, vacuum drying, and refrigerant addition. CAUTION: Do not supply power to the indoor unit until airtight test and vacuuming are complete. Open the outdoor unit valve fully using a 4 mm hexagonal wrench. Check for gas leaks using a leak detector or soap water at pipe connections and valve caps. REQUIREMENT: Use a leak detector specifically for HFC refrigerants (R32, R134a, R410A, etc.). WARNING: CAUTION: REQUIREMENT: Power supply wire and communication wires are procured locally. Follow the table for power supply specifications. Insufficient capacity can lead to overheating or burnout. Refer to the outdoor unit manual for power capacity and wire specifications. REQUIREMENT: Upon first use, allow time for the remote controller to become available after power-on. Automatic address setup may take up to 10 minutes. Outdoor unit operation may take up to 10 minutes after power-on. All units are factory-set to [STANDARD]. Settings may need adjustment using a wired remote controller. Remote controller model name: RBC-ASCU11-E Basic procedure: Stop the air conditioner before making settings. CAUTION: Only set the Code No. shown in the table. Setting incorrect Code Nos. may result in operational issues or product trouble. Refer to "Fan characteristics" for external static pressure settings. Set tap changes based on duct requirements. Follow the basic operation procedure (1-6). Specify Code No. [5d]. Select SET DATA for external static pressure from the table: Note: Settings are based on SW501-1 and SW501-2 being OFF. Incorrect settings may cause a "P12" fan motor error. External static pressure can also be set using DIP switches on the wireless reception part's circuit board or the indoor microcomputer circuit board. Refer to the wireless remote controller kit manual for details. The filter sign notification term can be adjusted based on installation conditions. Follow the basic operation procedure (1-7). Specify Code No. [01]. Select SET DATA for the filter sign term from the table: The filter sign may not be available with all remote controllers. To improve heating performance in challenging installations, raise the heating detection temperature. Use circulators or other devices to circulate warm air. Follow the basic operation procedure (1-6). Specify Code No. [06]. Select SET DATA for detection temperature shift from the table: To have the remote controller sense room temperature instead of the indoor unit's sensor, follow the basic operation procedure (1-6). Specify Code No. [32]. Select SET DATA from the table: If the display flashes, the remote controller sensor may be defective. Select [0000] or replace the controller. A single remote controller can manage up to 8 or 16 units (depending on the outdoor unit). Only wired remote controllers support group control; wireless controllers do not. For fan operation on an individual unit, turn off power, short circuit CN72 on the circuit board, then turn power back on. Set operation mode to "fan". Release CN72 short circuit after the test run. Operate the unit as usual via the remote controller. Refer to the Owner's Manual for details. A forced test run can be executed even if the unit stops due to thermostat-OFF. The forced test run releases after 60 minutes. CAUTION: Do not use forced test run for purposes other than testing, as it places excessive load on devices. Stop the air conditioner before making settings. Regular cleaning and maintenance of indoor and outdoor units are recommended for efficient operation and extended product life. Annual maintenance is advised for units operated long hours. Check outdoor units for rust/scratches and treat them. For units operating 8+ hours daily, clean every 3 months. Professional cleaning is recommended. Failure to maintain units can lead to poor performance, freezing, water leakage, and compressor failure. This inspection should be performed by a qualified installer or service person. A table details parts, inspection methods, and maintenance actions: If a problem occurs, the OFF timer indicator will alternately show the check code and the indoor unit number where the problem occurred. You can check the troubleshooting history (up to 4 incidents) during operation or when stopped. Checking history during OFF timer operation cancels the timer. CAUTION: Do not press the Menu button for over 10 seconds in history mode, as this deletes the entire history. Press ON/OFF to return to regular mode. If the unit is operating, it will continue until ON/OFF is pressed again. Operation status can be monitored via the wired remote controller's LCD, the outdoor unit's 7-segment display, or the wireless remote controller's sensor block display. This self-diagnosis function helps identify errors. A comprehensive list of check codes, their display methods (wired remote, outdoor unit, wireless remote), auxiliary codes, operation status indicators (Operation, Timer, Ready, Flash), check code names, and judging devices (Remote controller, Indoor unit, Inverter, I/F) is provided. This list covers various communication, sensor, motor, compressor, and system faults. A table lists specifications for different models: Notice codes are used in TC2U-Link communication to alert users to conditions requiring caution or maintenance. The notice code mark (spanner symbol) will appear on the remote controller or central controller display. The air conditioner can operate normally even when a notice code is displayed. Up to 5 notice codes can be displayed simultaneously. This section includes declarations from CARRIER AIR CONDITIONING (THAILAND) CO., LTD. and Carrier Solutions UK Ltd. regarding the compliance of the Super Modular Multi System Air Conditioner series (including Mini-Super Modular Multi System) with relevant directives and regulations. It lists manufacturer details, TCF holder information, generic denomination, model/type, and commercial names. The declaration is dated May 2, 2024, and states it becomes invalid if unauthorized modifications are made. Existing R22 and R410A piping can be reused for inverter R32 product installations, provided certain conditions are met. WARNING: Confirm pipe strength and condition locally. Pipes must be: Existing pipes should not be reused if: Pipe diameter and thickness table: Specifies minimum thickness for R32/R410A pipes based on outer diameter. When opening pipes for extended periods, cure them to prevent rust formation from condensation. Pinching or taping is recommended. Rooms must be designed so that refrigerant gas concentration does not exceed set limits in case of leaks. Specific limits apply for R32 and R410A refrigerants, with calculation methods provided. NOTE 1: For multi-system devices, consider amounts per independent device. NOTE 2: Standards for minimum room volume are provided, considering partitions and ventilation openings. NOTE 3: System compliance with IEC60335-2-40 Ed6 is confirmed. Before delivery, check and record the address and setup of each installed indoor unit on a check sheet. This sheet is crucial for post-installation maintenance. The check sheet includes fields for Room name, Model, Indoor unit address (Line, Indoor, Group, Central control), and Various setup options (External static pressure, Filter sign lighting time, Detected temp. shift value). It also has sections for checking if specific settings have been changed from default and if optional parts have been incorporated.1 Accessory Parts
Accessory Parts List
Part Name Qty Shape Usage Installation Manual 1 This manual For hand over to customers Heat insulating pipe 2 For heat insulation of pipe connecting section Washer 8 For hanging-down unit Hose band 1 For connecting drain pipe Flexible hose 1 For adjusting center of drain pipe Heat insulator 1 For heat insulation of drain connecting section Filter stopper 1 For fixing the filter Safety Manual 1 For hand over directly to the customer Filter Fixing Rails
Part name Qty UP005~ UP018 UP024~ UP030 UP036~ UP056 Filter fixing rail 1 (700 L) 1 2 2 2 Filter fixing rail 2 (700 L) 1 2 2 2 Filter fixing rail 3 (490 L) 1 2 2 2 Filter fixing rail 4 (490 L) 1 2 2 2 2 Selection of installation place
Avoid installing in the following places
Installation under high-humidity atmosphere
Installation space
Filter cleaning sign term setting
3 Installation
External dimensions
Installation of hanging bolt
Installation of indoor unit
Mounting filter rails and filters
Changing from back air intake to under air intake
4 Drain piping
Pipe material, size and insulator
Connecting drain pipe
Gravitational drainage
Drain up
Check the draining
When the electrical and wiring work has been completed
When the electrical and wiring work has not been completed
5 Duct design
Arrangement
6 Refrigerant piping
Refrigerant piping
Permissible piping length and height difference
Pipe size
Connecting refrigerant piping
Flaring
Work using double spanner
Evacuation
Refrigerant amount to be added
Airtight test / Air purge, etc.
Open the valve fully
Gas leak check
7 Electrical connection
Power supply wire and communication wires specifications
Indoor unit power supply
8 Applicable controls
Applicable controls setup (settings at the site)
External static pressure settings
Setting up on the circuit board of the indoor unit
Filter sign setting
To secure better effect of heating
Remote controller sensor
Group control
9 Test run
Before test run
Requirements for turning thermostat OFF
Execute a test run
Wired remote controller
Wireless remote controller
When a test run is not performed properly
10 Maintenance
Periodic Maintenance
Inspection before maintenance (Once a year)
Maintenance List
11 Troubleshooting
Confirmation and check
Troubleshooting history and confirmation
Check method
Check code list
12 Specifications
13 Notice code
How to check Notice code No.
Notice code list
Declaration of Conformity
14 Appendix
Work instructions
Basic conditions needed to reuse existing pipes
Restrictions for use of existing pipes
Curing of pipes
Warnings on Refrigerant Leakage
Check of concentration limit
Confirmation of indoor unit setup
Indoor unit setup check sheet