Instruction Manual for IDEC models including: HS1C-P, Interlock Plug Unit with Door Lock

IDEC HS1C-P Plug Unit Catalog

HS1C-P, Plug Unit, Interlock Plug, Unit with door lock

IDEC

IDEC HS1C-P Plug Unit Catalog

4 days ago — Interlock plugs with door lock mechanism for high level safety management. • Installing the actuator on the guard door and the interlock.


File Info : application/pdf, 6 Pages, 585.64KB

IDEC-HS1C-P-Plug-Unit-Catalog ?context=bWFzdGVyfGRvY3VtZW50c3w1OTk2OTN8YXBwbGljYXRpb24vcGRmfGRvY3VtZW50cy9oYzgvaDM0LzkxNjQxOD
HS1C-P Interlock Plug Unit with Door Lock
Interlock plugs with door lock mechanism for high level safety management.
· Installing the actuator on the guard door and the interlock switch on the machine, the guard door can be auto-locked mechanically .
· Removing the interlock plug maintains the interrupted status of load circuit and control circuit .
· Solenoid type and non-solenoid type available · Solenoid type has a lock mechanism . Lock mechanism pre-
vents removal of interlock plug during machine operation, and allows for removal after the machine has stopped, with solenoid energization signal . · Flexible installation: The actuator can be inserted into two direction . · Rugged die-cast aluminum housing · UL listed, c-UL listed .

Interlock Plug Unit

Solenoid With solenoid (24V DC) Without solenoid

Part No . HS1C-P44Z- HS1C-P04Z-

· Specify an indicator color code in place of  in the Part No . G: green, R: red
· Key wrench for TORX screws (HS9Z-T1) is supplied . · Actuator is not supplied and must be ordered separately .

Actuators

Description

Part No .

Straight Actuator

HS9Z-A1

Right-angle Actuator

HS9Z-A2

Angle Adjustable Actuator (for hinged doors)

HS9Z-A3

Key wrench for TORX screws

HA9Z-T1

Ratings
Circuit

Model

HS1C-P44Z HS1C-P04Z

Main Circuit

Rated Insulation Voltage (Ui) 250V (100% duty cycle) Rated Thermal Current (Ith) 10A

Rated Insulation Voltage (Ui) 250V

Rated Thermal Current (Ith) 3A

Monitor Circuit

Rated Operating Voltage (Ue) Rated Operating Current (Ie)

250V AC
0 .1A 250V AC/ 30V DC (resistive load)

3A (250V AC/ 30V DC) (resistive load)

Solenoid Unit
Rated Voltage Rated Current
Coil Resistance
Pickup Voltage Dropout Voltage Maximum Continuous Applicable Voltage Maximum Continuous Applicable Time Power Consumption

24V DC 260 mA 95 (at 20°C) Rated voltage × 90% maximum (at 20°C) Rated voltage × 10% minimum (at 20°C) Rated voltage × 110%
Continuous 6 .3W

Indicator

Rated Voltage Rated Current Light Source Lens Color

24V DC 10 mA LED G (green), R (red)

· The lens cannot be replaced .

122

Specifications

Main Circuit
Applicable Standards Auxiliary Circuit
Applicable Standards for Use Operating Temperature Relative Humidity Storage Temperature Pollution Degree Insulation Resistance Contact Resistance
Dielectric Strength
Shock Resistance
Vibration Resistance
Operating Frequency Mechanical Life Actuator Retention Force Interlock Plug Strength Mounting Screw Weight (approx .)

UL508 (UL listed) CSA C22 .2, No . 14 (c-UL listed) UL498 CSA C22 .2 No . 182 .1 UL508 (UL listed) CSA C22 .2, No . 14 (c-UL listed)
EN 1088
­20 to +50°C (no freezing) 45 to 85% (no condensation) ­40 to +80°C (no freezing) 3 100 M minimum (500V DC megger)
100 m maximum (initial value) Between live and dead metal parts: 2000V, 1 minute Between terminals of the same poles: 1000V, 1 minute Damage limits: 1000 m/s2 Operating extremes: 10 to 55 Hz, amplitude 0 .5 mm minimum Damage limits: 30 Hz, amplitude 1 .5 mm minimum 900 operations per hour (actuator, plug) 30,000 operations minimum (actuator, plug) 1500N minimum Rotational strength when locked: 5 N·m M5 × 4 720g (HS1C-P44Z-)

Part No. Development
H S 1 C - P 4 4 Z - R

Solenoid 4: With 0: Without
Indicator Rated Voltage 4: 24V DC

PL2 Indicator Color G: Green, R: Red
Housing Color Z: Beige only

Dimensions
109 76 59 44
6.5 ±1* 35

8.5 ±1 *

HS1C-P
HS1C-P Interlock Plug Unit with Door Lock

Conduit Port
G1/2

106

74

42

47

ø5.2

ø5.4

23.5 26

125

10

36.5

75

4

49.5

4

45

R2.7

2

68.8

1.5

7.5

31.2 * Actuator center position
22 40

9

23.5 26

54.3

Slot Plug (Note)

40

4

4-M5 Screws

42

47

Mounting Hole Layout

5.5

Note: Plug the unused actuator entry slot using the slot plug supplied with the interlock switch . · Use four mounting screws to mount the interlock switch according to the mounting hole layout .

Actuator Dimensions
Straight Actuator HS9Z-A1

9

49.3

2-M6 Screws

R3.2

18.3 1

Right-angle Actuator HS9Z-A2

2-M6 Screws

20 11
7.4

41.5 10.5
1

Angle-adjustable Actuator HS9Z-A3
18 Stopper Film (Note)

29.2 43 29.2 44 58 72 58

40

22

22

43

29.2

40 22

22

2

Actuator

7.4

Mounting

Holes

Actuator Actuator Cover Mounting

R3.2

(red)

Holes

4.1

Actuator Cover (red) (Note)
2

5 20

R 3.2

2

Door Hinge

Angle Adjustment Screw (M3 hexagon socket head screw)
30

2-M6 Screws
Actuator Mounting Holes

4.1 33 max. 12 (21)
1 2
20°

90°

Note: The actuator cover and actuator stop films are supplied with the actuator and used when adjusting the actuator position . Remove the actuator cover and actuator stop film after the actuator position is determined .

123

HS1C-P Interlock Plug Unit with Door Lock

Circuit Diagrams and Operating Characteristics

With Solenoid

Interlock Switch Status

Status 1
· Door closed · Interlock plug is
installed · Solenoid de-
energized

Status 2
· Door closed · Interlock plug is
installed · Solenoid energized

Status 3
· Door closed · Interlock plug is
removed · Solenoid energized

Status 4
· Door closed · Interlock plug is
removed · Solenoid de-
energized

Status 5
· Door open · Interlock plug is
removed · Solenoid de-
energized

Door

Monitor Circuit

Monitor Circuit

Monitor Circuit

Monitor Circuit

Monitor Circuit

1

1

1

1

1

2

2

2

2

2

3

3

3

3

3

Main Circuit

Main Circuit

Main Circuit

Main Circuit

Main Circuit

Circuit Diagram

4
Interlock Plug 5

4
Interlock Plug 5

4
Interlock Plug 5

4 Interlock Plug
5

4
Interlock Plug 5

Solenoid Power

Solenoid Power

Solenoid Power

Solenoid Power

Solenoid Power

6 7

6
Microswitch turns on when the solenoid is energized.
7

6
Microswitch turns on when the solenoid is energized.
7

6
Microswitch maintaines ON status when the plug is removed. 7

6
Microswitch maintaines ON status when the plug is removed. 7

8

8

8

Main Circuit Monitor Circuit Solenoid Power
Remarks

3-4: Closed 1-2: Open
5-6: Power OFF

3-4: Closed 1-2: Closed
5-6: Power ON

· Door locked · Interlock plug is
retained (cannot turn) · Machine can operate

· Door locked · Interlock plug can be
removed by turning · Machine can operate

3-4: Open 1-2: Closed
5-6: Power ON
· Door can be opened · Interlock plug is
removed · Machine cannot
operate

8
3-4: Open 1-2: Closed
5-6: Power OFF
· Door can be opened · Interlock plug is
removed · Machine cannot
operate

8 3-4: Open 1-2: Closed 5-6: Power OFF
· Machine cannot operate

Without Solenoid

Interlock Switch Status

Status 1
· Door closed · Interlock plug is
installed

Status 2
· Door closed · Interlock plug is
removed

Status 3
· Door open · Interlock plug is
removed

Door

Main Monitor Circuit Circuit Main Monitor Circuit Circuit Main Monitor Circuit Circuit

Circuit Diagram

1 2 3 4 Interlock Plug 5 6

1 2 3 4 Interlock Plug 5 6

1 2 3 4 Interlock Plug 5 6

7

7

7

Main Circuit Monitor Circuit
Remarks

8
3-4: Closed 1-2: Open
· Door locked · Interlock plug can be
turned to remove · Machine can operate

8
3-4: Open
1-2: Open · Door can be opened · Interlock plug is
removed · Machine cannot
operate

8
3-4: Open 1-2: Closed
· Interlock plug is removed
· Machine cannot operate

124

HS1C-P
HS1C-P Interlock Plug Unit with Door Lock

Safety Precautions
· Do not install the interlock plug unit with door lock in the place subject to oil or water . Electric shocks or fire hazard may be caused if the interlock plug is operated when the plug part is contaminated with oil or water .
· Interlock plug units with door lock are used to ensure the safety of operators who carry the plugs . Provide only one plug to a guard . Otherwise the hostage control function is lost, endangering the operators . Ensure complete safety management so that the function is maintained .

· In order to avoid electric shocks or fire, turn power off before installation, removal, wire connection, maintenance, or inspection of the interlock plug unit .
· Do not disassemble or modify the interlock plug unit with door lock Also do not disable the function of interlock plug unit intentionally . Otherwise a malfunction or an accident may occur .
· Do not install the actuator in a location where a human body may come into contact . Otherwise injury may occur .

Instructions
· The plug of HS1P interlock plug units resemble the HS2P plug, however, these plugs are not interchangeable . Do not use the plugs of other types, otherwise the interlock plug units will be damaged . The plugs can be distinguished with the handle color . HS1P: black (sane as HS1C-P) HS2P: aluminum color
· Regardless of door types, do not use the interlock plug unit as a door stop . Install a mechanical door stop at the end of the door to protect the interlock plug unit against excessive force . If excessive force is applied to the plug, especially to the direction of removing the plug, solenoid operation failure may occur even though the solenoid is energized, resulting in unlocking failure .
· Do not apply excessive shock to the interlock plug unit when opening or closing the door . A shock to the interlock plug unit exceeding 1,000 m/s2 may cause damage to the interlock plug unit .
· Regardless of door types, do not use the interlock plug unit as a door lock . Install a separate lock using a latch or other measures .
· The solenoid has polarity . Make sure of the correct polarity when wiring . Do not apply overvoltage, otherwise the solenoid will be burnt .
· When wiring, unscrew the cover only . Unnecessary loosening of other screws may cause a malfunction of the interlock plug unit .
Cover
· The cover uses special screws which cannot be removed or tightened by general drivers . Use the special wrench supplied with the interlock plug unit .
· While connecting to the conduit port, prevent foreign objects from entering the interlock plug unit, such as dust and liquids .
· If the operating atmosphere is contaminated, use a protective cover to prevent the entry of foreign objects into the interlock plug unit through the actuator entry slots .
· Entry of a considerable amount of foreign objects into the interlock plug unit may affect the mechanism of the interlock plug unit and cause a malfunction .
· Actuator retention force is 1500N (static load) . When larger force is expected, add a system using interlock switch without lock (ex . HS1B) and sensor in order to detect door opening and to stop the machine .
· Plug the unused actuator entry slot using the slot plug supplied with the interlock plug unit .
· Do not store the interlock plug unit in a dusty, humid, or organic-gas atmosphere .

· Make sure that the interlock plug unit is not energized when removing or installing the plug (after operating the emergency stop button shown in the circuit example shown below) . Do not start or stop the machine by plug removal/installation, otherwise the interlock plug unit may fail .

Interlock Plug

+

Circuit Example

Start

R

R

Stop Emergency Stop Switch

Interlock Plug

R

L Load

­

Note 1: When using the main circuit on AC, connect emergency stop switch to Line, and interlock plug unit to Neutral .
Note 2: When using the main circuit on DC, connect to the + line with emergency stop switch first followed by the interlock plug unit .
Manual Unlocking
The HS1C-P allows manual unlocking of the actuator to precheck proper entry of the actuator into the slot as well as for emergency use such as a power failure . · Remove the screw located on the front of the interlock plug
unit using the special wrench supplied with the interlock plug unit . Insert a small screwdriver into the screw hole and push the lever inside as shown below until the key is unlocked . · Turn and remove the plug . · After unlocking, ensure to install the screw .
Interlock Plug Unit

Plug

Screwdriver

125

HS1C-P Interlock Plug Unit with Door Lock

Instructions
Minimum Radius of Hinged Door
· When using the interlock plug unit for a hinged door, refer to the minimum radius of doors shown below . For the doors with small minimum radius, use angle adjustable actuators (HS9Z-A3) .
Note: Because deviation or dislocation of hinged door may occur in actual applications, make sure of the correct operation before installation .
HS9Z-A2 Actuator
· When the door hinge is on the extension line of the interlock plug unit surface:

Minimu2m30Rmamdius

Minim1u3m0

Radius mm

Door Hinge

· When the door hinge is on the extension line of the actuator mounting

surface:

HS9Z-A2 Actuator

Minimu4m00Ramdmius Minimu2m40Rmadmius

Door Hinge
HS9Z-A3 Actuator
· When the door hinge is on the extension line of the interlock plug unit surface:

Min5im0ummmRadius

· When the door hinge is on the extension line of the actuator mounting

surface:

HS9Z-A3 Actuator

Applicable Crimping Terminal

Terminal Nos. 7, 8

Ground Terminal: E

3.6 min.

3.5 max.

3.5 min.

3.8 max.

6.9 max. 7.6 max.

ø3.6 min.

ø4.1 min.

· Use an insulation tube on the crimping terminal

Approx. 4 mm Wire

Applicable Crimping Terminal

Insulation Tube

Terminal No. 1 to 6
· Direct wiring using either solid or stranded wires . · When using stranded wires, make sure that loose wires do not
cause short circuit . Also, do not solder the terminal to prevent loose wires .

When using Ferrules

Ferrules (Phoenix Contact)

Part No . AI 0 .75-8 GY AI 1 .0-8 RD AI 1 .5-8 BK

Applicable Wire 0 .5 to 0 .75 mm2 0 .75 to 1 .0 mm2 1 .0 to 1 .5 mm2

Crimping Tool: CRIMPFOX UD6

Applicable Wire Size

· Terminal Nos . 1, 2, 5, 6, 7, 8: 0 .5 to 0 .75 mm2

· Terminal Nos . 3, 4, E:

1 .0 to 1 .25 mm2

Installing the Interlock Plug Unit
Mount the interlock plug unit on a fixed machine or guard, and mount the actuator on the hinged door . Do not mount both safety plug unit and actuator on the hinged doors, otherwise malfunction will occur .

Aplication on Sliding Doors

Min8im0 ummmRadius
Actuator Angle Adjustment
· Using the angle adjustment screw, the actuator angle can be adjusted (refer to the dimensional drawing) . Adjustable angle: 0 to 20°
· The larger the adjusted angle of the actuator, the smaller the applicable radius of the door opening .
· After installing the actuator, open the door . Then adjust the actuator so that its edge can be inserted properly into the actuator entry slot of the interlock switch .
· Recommended tightening torque of angle adjustment screw: 0 .8 N·m
· After adjusting the actuator angle, apply Loctite to the adjustment screw so that the screw will not loosen .

Door

HS1C-P Interlock Plug Unit
Latch

HS9Z-A1 Actuator
Door Stop

Application on Hinged Doors Door Latch

HS1C-P Interlock Plug Unit

HS9Z-A2 Actuator

HS9Z-A1 Actuator

126

HS1C-P
HS1C-P Interlock Plug Unit with Door Lock

Instructions
Applicable Cable Glands
· Use IP67 cable gland .
G1/2
9 mm max.
When Using Flexible Conduits (Example) · Flexible conduit example: VF-03 (Nihon Flex) · Metal gland example:
(G1/2) RLC-103 (Nihon Flex)
When Using Multi-core Cables (Example) · Plastic cable gland:
(G1/2) SCS-10* (Seiwa Electric) · Metal cable gland:
(G1/2) ALS-16 (Nihon Flex) · Different cable glands are used depending on the cable
sheath outside diameter . When purchasing a cable gland, confirm that the cable gland is applicable to the cable sheath outside diameter .
Recommended Tightening Torque of Mounting Screws · Interlock switch: 4 .5 to 5 .5 N·m (four M5 screws) · Actuator (HS9Z-A1/A2/A3): 4 .5 to 5 .5 N·m (two M6
screws) · Mounting bolts must be provided by users . · The above recommended tightening torques of the
mounting screws are the values confirmed with hex socket head bolts . When other screws are used and tightened to a smaller torque, make sure that the screws do not come loose after mounting .

30 mm max.

Cable Lead-in Length and Wiring Examples

Terminal No .

1

2

3

Cable

4

Length

5

L1 (mm)

6

7

8

E

Wire Stripping Length L2 (mm)

Conduit Port





30±2 45±2

30±2 50±2

25±2 55±2

25±2 60±2

30±2 65±2

30±2 70±2

65±2 35±2

65±2 110±2

85±2 45±2

7±1

L1

Gland Interlock Switch

L2

Note: Wire the interlock switches according to the following examples .

When using Conduit Port 

When using Conduit Port 

Note: When wiring the ground (E) terminal, connect in the solid line direction only. Do not connect in the dotted line direction.

127