RG10 Series Wireless Remote Controller
TABLE OF CONTENTS
- HANDLING THE REMOTE CONTROLLER
- FUNCTION BUTTONS
- REMOTE CONTROLLERS
- SERVICE INQUIRY CODES
INTRODUCTION
This service manual provides the necessary information to use the service functions on the RG10 series wireless remote controller. Use the TABLE OF CONTENTS to locate a desired topic.
NOTE: Remote part number can be found on the back of the wireless remote.
TYPE: RG10
HANDLING THE REMOTE CONTROLLER
Remote Controller Location
Keep the remote controller within a distance where its signals can reach the indoor unit's receiver (not to exceed 26 ft. (8m)).
Replacing Batteries
The remote controller uses two alkaline dry batteries (AAA).
- Slide the battery compartment cover off, according to the arrow direction, then replace the old batteries with new batteries.
- Insert the new batteries. Ensure the batteries are installed correctly, based on their (+) and (-) polarities.
- Slide the battery compartment cover back into position.
NOTES:
- Do not mix old and new batteries or batteries of different types.
- Do not leave the batteries in the remote controller if the remote is not going to be used for 2 or 3 months.
- Dispose old batteries in the appropriate recycle bins.
Remote Controller Specification
MODELS | Rated Voltage | Signal Receiving Range | Environment |
---|---|---|---|
RG10L(2HS)/BGEFU1 RG10A(B2S)/BGEFU1 RG10B(B1)/BGEFU1 RG10A5(B1)/BGCEFU1 RG10A4(B1)/BGEFU1 | 3.0V (dry batteries AAA) | 26 ft. (8m) | 23°F (-5°C) ~ 140°F (60°C) |
FUNCTION BUTTONS
Before you use your new system, familiarize yourself with the remote controller. The following is a brief introduction of the remote controller.
- ON/OFF
- Turns the unit on or off.
- TEMP ∧
- Increases temperature in 1°F (0.5°C) increments. Max. temperature is 86°F (30°C).
- NOTE: Press together ✓ & buttons at the same time for 3 seconds will alternate the temperature display between the °C & °F.
- SET
- Scrolls through operation functions as follows: Breeze away()→Active clean()→Fresh()→Sleep()→Follow Me(8)→AP mode ()→ Breeze away() → The selected symbol flashes on the display area, press the OK to confirm.
- TEMP ∨
- Decreases temperature in 1°F (0°C) increments. Min. temperature is 60°F (16°C).
- FAN SPEED
- Selects fan speeds in the following order: AU→20% → 40%-60%→80% → 100%. Press the TEMP ∧ or ∨ to increase/decrease the fan speed in 1% increments.
- SWING
- Starts and stops the horizontal louver movement. Hold down for 2 seconds to initiate vertical louver auto swing feature.
- MODE
- Scrolls through operation modes as follows: AUTO → COOL → DRY → HEAT → FAN
- Eco Intelligent eye
- Use to detect inhabitant's activities in the room to save energy.
- OK
- Use to confirm the selected functions.
- TIMER
- Set the timer to turn unit on or off
- ECO/GEAR
- Press to enter the energy efficient mode in a sequence of the following: ECOGEAR(75%) → GEAR(50%)→ Previous setting mode →ECO
- HUMIDITY
- Adjust the room humidity during Dry operation in a range of 35%~85%. Press to increase the humidity in 5% increments. NOTE: After setting, the humidity settings appear on the screen.
- LED
- Turns the indoor unit's LED display and air conditioner buzzer on and, off, which creates a comfortable and quiet environment. If you press and hold LED for 5 seconds, it displays the return air temperature at the unit versus the set point temperature.
- BOOST
- Enables the unit to reach the preset temperature in shortest possible time.
NOTE: To alternate between °C and °F, buttons must be pressed gently, otherwise the remote will not recognize the command.
REMOTE CONTROLLERS
Accessing the INQUIRY Mode
- Simultaneously press ON/OFF and FAN SPEED for 8 seconds.
- The remote is now in the INQUIRY mode.
- The remote control remains in the INQUIRY mode for 1 minute if no other button is pressed.
- While in the INQUIRY Mode, the remote display cancels all icons except AUTO, COOL, DRY, HEAT and Battery Strength.
- The remote control digital display defaults to 0 upon entering the INQUIRY mode.
- In the INQUIRY mode, each digital code (from 0 to 30) is accessed by pressing the UP or DOWN arrows.
- The INQUIRY information appears on the high wall indoor unit display in approximately 1 second after accessing the digital code. Press OK to send as well.
- In the INQUIRY mode, all other buttons and operations are invalid except for UP, DOWN and OK or the operation to exit the INQUIRY mode.
Remote Controller Service Mode Functions
Note: While in the INQUIRY mode, refer to the following instructions to enter SERVICE mode for the applicable codes.
Below is a list of INQUIRY modes and serviceable functions.
- Before using the remote's service functions, turn OFF the indoor unit with the remote.
- Turn OFF the power to the outdoor unit for 2 minutes. Turn the power back ON.
- Remove the batteries from the remote and wait for the remote screen to clear. Within 30 seconds of replacing the batteries, use UP or DOWN to scroll through the INQUIRY modes.
- To enter the SERVICE mode for an applicable INQUIRY mode, press ON/OFF for 2 seconds.
- After SERVICE adjustments have been made, press ON/OFF for 2 seconds to exit the SERVICE mode and return to the INQUIRY mode.
- Once operations in the INQUIRY mode are complete, press ON/OFF and FAN SPEED for 2 seconds to exit. All buttons on the remote controller are disabled for 60 seconds.
- To ensure changes are locked, power down the outdoor unit for three (3) minutes after all the service mode changes are made.
SERVICE INQUIRY CODES
CODE | INQUIRY | INQUIRY DESCRIPTION | SERVICE/ INQUIRY | FOR SERVICE, PRESS ON/OFF FOR 2 SECONDS TO: | SELECTION GUIDE/NOTES |
---|---|---|---|---|---|
0 | Error Code Check | SERVICE AND INQUIRY | Review error memory function. Displays "Ch". Press OK to send the query error code memory. | 0. Memory settings are off 1. Memory settings are on | |
1 | T1 | Indoor Ambient Temperature | SERVICE AND INQUIRY | Change the power off memory selection. This feature determines whether the unit memorizes the set conditions prior to a power failure. Displays "Ch". Press OK to return the current setting. Press UP or DOWN to cycle through settings 1 and 0. | 1. Stop the fan 2. Minimum fan speed 3. Set speed 4. intermittent fan-off 4 minutes/on 1 min 5. Terminate after run time of 10 mins 6. Terminate after run time of 15 mins 7. Terminate after run time of 20 mins 8. Terminate after run time of 30 mins 9. Terminate after run time of 40 mins 10. Terminate after run time of 50 mins 11. Terminate after run time of 60 mins |
2 | T2 | Indoor Coil Temperature | SERVICE AND INQUIRY | Change the option to control the indoor fan operation after reaching the set temperature. Displays "Ch". Press OK to return the current setting. Press UP or DOWN to cycle through settings 1 through 11. Next, press OK to confirm the selection. | CH - COOLING and HEATING: AUTO, COOLING, DRY, HEATING and FAN modes available HH - HEATING Only: HEATING and FAN modes available CC-COOLING without AUTO: COOLING, DRY and FAN modes available nU - COOLING and HEATING without AUTO: COOLING, DRY, HEATING and FAN modes available |
3 | T3 | Outdoor Coil Temperature | SERVICE AND INQUIRY | Change the option to control the COOLING and HEATING modes available for use on the unit. Press UP or DOWN to cycle through the settings CH, HH, CC or nU. Press OK to confirm. | Only available on ducted/40MBAA units. Refer to the ducted/40MBAA installation manuals for Fan performances at varying static pressures for airflow settings. |
4 | T4 | Outdoor Ambient Temperature | SERVICE AND INQUIRY | Change the selection of the lowest set temperature. NOTE: Temperature range is 60°F ~ 75°F (16°C~24°C). Press UP or DOWN to select temperature setting. Press OK to confirm. | |
5 | TP (T5) | Compressor Discharge Temperature | SERVICE AND INQUIRY | Change the selection of the highest set temperature. NOTE: Temperature range is 77°F ~ 86°F (25°C ~ 30°C). Press UP or DOWN to select the temperature setting. Press OK to confirm. | |
6 | FT | Compressor target frequency | INQUIRY ONLY | Change the static pressure selection. | |
7 | Fr | Compressor run frequency | INQUIRY ONLY | ||
8 | dL | Unit amperage | SERVICE AND INQUIRY | Displays "Ch". Press OK to return the current setting. Press UP or DOWN to cycle through settings 0 through 4 or AF (constant air volume test). Press OK to confirm. | Multiple the display number by 8 to calculate the actual RPM |
9 | Uo | Unit voltage | INQUIRY ONLY | ||
10 | Sn | Capacity test (special usage) | INQUIRY ONLY | ||
11 | Ss | Not available | INQUIRY ONLY |
CODE | INQUIRY | INQUIRY DESCRIPTION | SERVICE/ INQUIRY | FOR SERVICE, PRESS ON/OFF FOR 2 SECONDS TO: | SELECTION GUIDE/NOTES |
---|---|---|---|---|---|
12 | Pr | Indoor fan speed | SERVICE AND INQUIRY | Change the heating frequency lower limit selection. Displays "Ch". Press OK to return the current heating minimum frequency limit selection code. Press UP and DOWN to select the minimum heating frequency limit value. Press OK to confirm. | The value is measured in dBm. The display values are 0, 1, 2, 3 and 4 (4 is the highest and 0 is the lowest) |
13 | Lr | Electronic Expansion Valve (EEV) opening | SERVICE AND INQUIRY | Change the maximum operating frequency of T4 Cooling Only intervals. Displays "Ch". Press OK to return the current operating frequency code of the T4 Cooling Only intervals. Press UP or DOWN to select the limit value and then press OK. | Available in INQUIRY mode for the high tier/new mid tier units that have an RH sensor. |
14 | ir | Indoor fan speed | INQUIRY ONLY | Multiple the display number by 8 to calculate the actual RPM | |
15 | HU | Relative Humidity Setpoint compensation temperature | INQUIRY ONLY | ||
16 | TT | Dust concentration (not used) | INQUIRY ONLY | ||
17 | dT | INQUIRY ONLY | |||
18 | WIFI | Wi-Fi signal strength | INQUIRY ONLY | Change the cooling frequency upper limit selection in Hz. Displays "Ch". Press OK to return the current frequency limit. Press UP or DOWN to select the preferred frequency upper limit value (in Hz). Press OK to confirm. | For example, the unit may be factory set to fluctuate between 40 and 84 Hz. If set to 50, the unit will now be limited to operating between 40 and 50 Hz. |
19 | Not available | SERVICE ONLY | |||
20 | OT | Indoor fan target frequency | SERVICE AND INQUIRY | Change the heating frequency upper limit selection in Hz. Displays "Ch"; press OK to return the current frequency limit. Press UP or DOWN to select the preferred frequency upper limit value (in Hz). Press OK to confirm. | For example, the unit may be factory set to fluctuate between 40 and 84 Hz. If set to 50, the unit is limited to operating between 40 and 50 Hz. |
21 | Cooling Temperature Compensation | SERVICE ONLY | Change the cooling temperature compensation value. Displays "Ch". Press OK to return the current temperature compensation value code. Press UP or DOWN to select the cooling temperature difference compensation value. Press OK to confirm. | This setting is used to adjust for temperature differences due to the height of the unit install. The offset value can be set at a range of -6° to +6°. | |
22 | Heating Temperature Compensation | SERVICE ONLY | Change the heating temperature compensation value. Displays "Ch". Press OK to return the current temperature compensation value code. Press UP or DOWN to select the heating temperature difference compensation value. Press OK to confirm. | This setting is used to adjust for temperature differences due to the height of unit installation. The offset value can be set at a range of -6° to +6°. | |
23 | Maximum Cooling Fan Speed | SERVICE ONLY | Change the maximum cooling fan speed setting as it relates to RPM. Displays "Ch". Press OK to return the current maximum cooling fan speed setting. Press UP or DOWN to select the maximum cooling fan speed. Press OK to confirm. | For example, the unit may be factory set to fluctuate between 300 and 1000 RPM. If set to 800, the unit is limited to operating between 300 and 800 RPM. |
CODE | INQUIRY | INQUIRY DESCRIPTION | SERVICE/ INQUIRY | FOR SERVICE, PRESS ON/OFF FOR 2 SECONDS TO: | SELECTION GUIDE/NOTES |
---|---|---|---|---|---|
24 | Minimum Cooling Fan Speed | SERVICE ONLY | NOTE: Changing this setting is not recommended as it may trigger unit protection protocols. Displays "Ch". Press OK to return the current minimum cooling fan speed setting. Press UP or DOWN to select the minimum cooling fan speed. Press OK to confirm. | For example, the unit may be factory set to fluctuate between 300 and 1000 RPM. If set to 500, the unit is limited to operating between 500 and 1000 RPM. | |
25 | Maximum Heating Fan Speed | SERVICE ONLY | Change the maximum heating fan speed setting as it relates to RPM. Displays "Ch". Press OK to return the current maximum heating fan speed setting. Press UP or DOWN to select the maximum heating fan speed. Press OK to confirm. | For example, the unit may be factory set to fluctuate between 300 and 1000 RPM. If set to 800, the unit will now be limited to operating between 300 and 800 RPM. | |
26 | Minimum Heating Fan Speed | SERVICE ONLY | Note: Changing this setting is not recommended as it may trigger unit protection protocols. Displays "Ch". Press OK to return the current minimum heating fan speed setting. Press UP or DOWN to select the minimum heating fan speed. Press OK to confirm. | For example, the unit may be factory set to fluctuate between 300 and 1000 RPM. If set to 500, the unit is limited to operating between 500 and 1000 RPM. | |
27 | Not available | ||||
28 | --- | Not available | |||
29 | --- | Not available | |||
30 | --- | Not available |
File Info : application/pdf, 8 Pages, 474.33KB
DocumentDocumentRelated Documents
![]() | Carrier RG10 Series Wireless Remote Controller Service Manual Service manual for the Carrier RG10 Series wireless remote controller, providing detailed information on functions, specifications, service inquiry codes, and troubleshooting for various RG10 models. |
![]() | Carrier Remote Controller Owner's Manual This manual provides comprehensive instructions for operating your Carrier remote controller, covering basic and advanced functions, button descriptions, and screen indicators for optimal use of your air conditioning unit. |
![]() | Carrier Remote Controller Owner's Manual Comprehensive owner's manual for the Carrier Remote Controller, detailing specifications, functions, and operation for various models. |
![]() | Carrier D5FUAAH Crossover Air Handler Owner's Manual Comprehensive owner's manual for the Carrier D5FUAAH Crossover Air Handler, covering installation, operation, maintenance, and troubleshooting for models 18 to 60. |
![]() | Carrier 45MUHAQ Crossover Air Handler Owner's Manual - Operation, Maintenance, and Safety Guide This comprehensive owner's manual provides essential information for the Carrier 45MUHAQ Crossover Air Handler, covering safe operation, detailed instructions, maintenance procedures, troubleshooting tips, and error code explanations for optimal performance and longevity. |
![]() | Carrier Remote Controller Owner's Manual This manual provides instructions for operating the Carrier remote controller for air conditioning units, covering quick start, display and buttons, basic functions, and advanced features. |
![]() | Carrier Remote Controller Owner's Manual This owner's manual provides comprehensive instructions for the Carrier remote controller, covering quick start, display and button functions, basic operations, and advanced features. Learn how to operate your Carrier air conditioning system efficiently and effectively. |
![]() | Carrier 45VMV048A---3 Vertical AHU Submittal Data Submittal data for the Carrier 45VMV048A---3 Vertical Air Handler Unit (AHU), including performance specifications, electrical data, physical dimensions, standard features, and optional accessories. |