bd14f-vsd-hd 109z0250 r134a 12-24vdc 06-2022 desd100w802 BD1.4F-VSD-HD Heavy Duty Direct Current Compressor R134a, 12/24V DC
General Code number (without electronic unit) Electronic unit - Variable Speed Approvals Compressors on pallet
109Z0250 101N2130, 30 pcs: 101N2131
180
Application
Application
Evaporating temperature
°C
Voltage range
VDC
Max. condensing temperature continuous (short) °C
Max. winding temperature continuous (short)
°C
LBP/MBP/HBP -30 to 15
9.6 - 17 / 19 - 34 60 (70)
125 (135)
Cooling requirements
Application
LBP
MBP
HBP
32°C
S
S
S
38°C
S
S
S
43°C
S
S
S
Remarks on application:
HD (Heavy Duty) version of the BD1.4F-VSD which can handle extreme vibrations.
S = Static cooling normally sufficient O = Oil cooling
F1 = Fan cooling 1.5 m/s (compressor compartment temperature
equal to ambient temperature)
F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent = not applicable in this area
Motor Motor type Speed Resistance, all 3 windings (25°C)
permanet magnet, brushless DC
rpm
variable speed
m
210
Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit
cm3
1.41
cm3
75 (polyolester)
g
70
cm3
500
kg
2.1/0.11
Standard battery protection settings (refer to 101N2130 Instructions for optional settings)
Voltage (0.1 steps)
Min. value Default Max. value
12V
± 0.3V DC, all values
Cut out Cut in diff.
VDC 9.6
10.4
17
VDC 0.5
1.3
10
24V
± 0.3V DC, all values
Cut out Cut in diff.
VDC 19
21.3
27
VDC 0.5
1.3
10
Dimensions Height
Suction connector Process connector Discharge connector Connector tolerance
mm A
96.25
B
91.25
B1
88.00
B2
25.20
location/I.D. mm | angle C
6.2 | 25°
material | comment
Cu-plated steel | Al cap
location/I.D. mm | angle D
6.2 | 25°
material | comment
Cu-plated steel | Al cap
location/I.D. mm | angle E
5.0 | 0°
material | comment
Cu-plated steel | Al cap
I.D. mm ±0.09, on 5.0 +0.12/+0.20
June 2022
DES.D.100.W8.02
1/2
Capacity (EN 12900 Household/CECOMAF)
rpm \ °C -30 -25 -23.3 -20 -15 -10
2,000
9 11 15 22 31
2,500 7 13 15 20 30 41
3,000 9 16 19 26 37 51
3,500 10 20 23 31 45 61
4,000 12 23 27 36 52 71
12V DC, static cooling -5 0 5 7.2 10 42 54 69 76 86 55 70 87 96 109 67 85 105 116 131 80 101 124 137 154 92 116 144 158 178
Capacity (ASHRAE LBP)
12V DC, static cooling
rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5 7.2 10
2,000
12 14 19 28 39 52 68 86 95 107
2,500 9 16 19 25 37 51 68 87 109 120 135
3,000 11 20 24 32 47 64 84 106 131 144 163
3,500 13 24 29 39 56 76 99 125 155 170 192
4,000 15 29 34 45 65 88 114 144 179 197 222
Power consumption
rpm \ °C -30 -25 -23.3 -20 -15 -10
2,000
16 17 19 22 25
2,500 16 20 21 24 28 32
3,000 19 24 26 29 34 39
3,500 23 29 31 35 41 47
4,000 27 34 36 41 48 55
12V DC, static cooling -5 0 5 7.2 10 29 34 40 42 43 37 42 48 50 52 45 50 57 59 61 53 59 66 69 72 61 68 76 79 83
Current consumption (for 24V applications the following must be halfed)
rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5 7.2
2,000
1.25 1.33 1.48 1.74 2.02 2.32 2.65 2.74 2.85
2,500 1.25 1.53 1.63 1.83 2.15 2.48 2.84 3.22 3.69 3.84
3,000 1.49 1.84 1.96 2.20 2.59 2.98 3.40 3.82 4.38 4.56
3,500 1.77 2.19 2.34 2.63 3.07 3.53 4.00 4.47 5.06 5.26
4,000 2.08 2.58 2.75 3.08 3.59 4.10 4.63 5.16 5.87 6.07
10 3.00 4.00 4.77 5.51 6.31
COP (EN 12900 Household/CECOMAF)
rpm \ °C -30 -25 -23.3 -20 -15 -10
2,000
0.59 0.66 0.81 1.03 1.24
2,500 0.43 0.64 0.72 0.86 1.08 1.29
3,000 0.45 0.67 0.74 0.89 1.10 1.30
3,500 0.46 0.68 0.75 0.89 1.10 1.30
4,000 0.45 0.68 0.75 0.89 1.09 1.30
12V DC, static cooling -5 0 5 7.2 10 1.43 1.60 1.72 1.83 1.99 1.48 1.67 1.83 1.94 2.10 1.50 1.69 1.84 1.97 2.14 1.51 1.70 1.88 1.99 2.15 1.50 1.70 1.88 1.99 2.14
COP (ASHRAE LBP)
12V DC, static cooling
rpm \ °C -30 -25 -23.3 -20 -15 -10 -5 0 5 7.2 10
2,000
0.74 0.83 1.01 1.29 1.55 1.79 2.01 2.17 2.31 2.52
2,500 0.54 0.80 0.89 1.07 1.34 1.60 1.84 2.08 2.29 2.43 2.64
3,000 0.57 0.84 0.93 1.11 1.37 1.62 1.87 2.11 2.35 2.47 2.70
3,500 0.58 0.85 0.94 1.11 1.36 1.62 1.87 2.12 2.36 2.49 2.69
4,000 0.58 0.85 0.94 1.11 1.36 1.61 1.87 2.12 2.36 2.50 2.68
watt Operational errors (TOOL4COOL® or LED flashes)
15 106 134 161
Error code or LED flashes
Error type Can be read out in the software TOOL4COOL®
6 Thermostat failure
(If the NTC thermistor is short-circuit or has no connection,
190
the electronic unit will enter manual mode).
218
5 Thermal cut-out of electronic unit
watt 15 132 167 201 237 272
watt
(If the refrigeration system has been too heavily loaded, or if the ambient temperature is high, the electronic unit will run too hot).
4 Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 1,850 rpm).
3 Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
15
2 Fan over-current cut-out
45
(The fan loads the electronic unit with more than
54
0.65A ). peak
63
1 Battery protection cut-out
77
(The voltage is outside the cut-out setting).
90 Wire Dimensions DC
A 15 3.28 4.20 5.09 5.89
Size
Cross AWG
section
[mm2] [Gauge]
2.5
12
4
12
6
10
Max. length* 12V operation
[m]
[ft.]
2.5
8
4
13
6
20
Max. length* 24V operation
[m]
[ft.]
5
16
8
26
12
39
6.63
10
8
10
33
20
66
W/W 15 2.36 2.46 2.54 2.47 2.42
*Length between battery and electronic unit
Accessories for BD1.4F-VSD-HD
Code number
Bolt joint for one compressor
Ø:16 mm 118-1917
Bolt joint in quantities
Ø:16 mm 118-1918
Snap-on in quantities
Ø:16 mm 118-1919
Terminal cover for electronic unit
105N9120
Automoblie fuse DIN 7258
12V: 15A
Not
24V: 15A deliverable
W/W Main switch
min. 20A from Secop
15 2.98 3.10 3.20 3.11 3.05
Test conditions
Condensing temperature Ambient temperature Suction gas temperature Liquid temperature
EN 12900 CECOMAF
55°C 32°C 32°C no subcooling
ASHRAE LBP 54.4°C 32°C 32°C 32°C
Fuse Main switch
Spade connectors 6.3 mm | 1/4 in.
+
+
Fan
Power supply
LED
Secop Gateway
105N9518 V01.02
www.secop.com Made in Germany
* Don`t connect when using D/I on BD-Products
1 U+* D/I C 2 UBAT LIN C
USB-C
USB Comm.
Secop Gateway
non PC option PC option (TOOL4COOL®)
LED connected to Gateway connected to UBAT, D/I, and C
+ and D/I
NTC resistor mech. Thermostat
t°
option 2
option 1
IN FAN OUT 12/24V DC
101N2130
+
F+ F
D/I
C
T
C
P
R1
S
R2
8910-2
R1 = speed/battery protection R2 = setpoint non PC option (resistors)
refer to 101N2130 Instructions for details
Secop accepts no responsibility for possible errors in catalogs, brochures, and other printed material. Secop reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary to specifications already agreed. All trademarks in this material are the property of the respective companies. Secop and the Secop logotype are trademarks of Secop GmbH. All rights reserved. www.secop.com
2/2
DES.D.100.W8.02
June 2022