53018 G3.book

e451217

ACPS-610/E


File Info : application/pdf, 48 Pages, 1.99MB

PDF preview unavailable. Download the PDF instead.

ba-fire-53018 ?download=false
Addressable Charger/Power Supply
ACPS-610/E
Manual
Document 53018 Rev: G3 08/08/19 ECN: 18-0305

Fire Alarm & Emergency Communication System Limitations

While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!

An automatic fire alarm system--typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notification capability--can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system--typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication methods--can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http:// www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
· Barriers such as closed or partially closed doors, walls, chimneys, even wet or humid areas may inhibit particle or smoke flow.
· Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
· Smoke particles may be blown away from detectors by air outlets, such as air conditioning vents.
· Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rateof-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
· An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
· Voice messaging systems must be designed to meet intelligibility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
· Language and instructional requirements must be clearly disseminated on any local displays.
· Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
· Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
· In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep the entire life safety system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled as required by National and/or local fire codes and should be performed by authorized professional life safety system installers only. Adequate written records of all inspections should be kept.
Limit-D2-2016

2

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/ 32-120º F and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Units with a touchscreen display should be cleaned with a dry, clean, lint free/microfiber cloth. If additional cleaning is required, apply a small amount of Isopropyl alcohol to the cloth and wipe clean. Do not use detergents, solvents, or water for cleaning. Do not spray liquid directly onto the display.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.

Precau-D2-11-2017

FCC Warning

WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense.

Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.

HARSHTM, NISTM, and NOTI·FIRE·NETTM are all trademarks; and Acclimate® PlusTM, eVance®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®, Honeywell®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ChromeTM and GoogleTM are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

3

Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
· Product name and version number (if applicable) · Printed manual or online Help · Topic Title (for online Help) · Page number (for printed manual) · Brief description of content you think should be improved or corrected · Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

4

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Table of Contents
Section 1: Introduction ..................................................................................................................................................... 7 1.1: Features..............................................................................................................................................................................................................7 1.2: Specifications.....................................................................................................................................................................................................7 1.2.1: CPS-24 Board .........................................................................................................................................................................................7 1.2.2: Main Control Unit...................................................................................................................................................................................7 1.3: Installation Standards and Codes.......................................................................................................................................................................8 1.3.1: UL 864 9th and 10th Edition ..................................................................................................................................................................8 1.4: Related Documentation .....................................................................................................................................................................................9 1.5: Notes, Cautions, and Warnings..........................................................................................................................................................................9 1.6: Board Layout ...................................................................................................................................................................................................10 1.7: LED Indicators.................................................................................................................................................................................................11
Section 2: Installation ..................................................................................................................................................... 13 2.1: Mounting Options............................................................................................................................................................................................13 2.1.1: In a CAB-PS1 Cabinet..........................................................................................................................................................................13 2.1.2: In a CAB-4 or EQ Series Backbox .......................................................................................................................................................13 2.1.3: In a BB-25 Cabinet ...............................................................................................................................................................................15 2.1.4: In a BB-100 Cabinet ............................................................................................................................................................................16 2.1.5: In a BB-200 Cabinet .............................................................................................................................................................................16 2.2: UL Power-limited (Class 2) Wiring Requirements..........................................................................................................................................17 2.3: Connecting the Power Supply to AC Power....................................................................................................................................................18 2.4: Installing and Connecting the Batteries .........................................................................................................................................................19 2.4.1: Setting the Charger ...............................................................................................................................................................................19 2.4.2: Connecting the Power Supply to Two Batteries:..................................................................................................................................19 2.4.3: Connecting the Power Supply to Four Batteries: .................................................................................................................................20 2.4.4: Connecting Multiple Power Supplies (Separate Batteries) ..................................................................................................................20 2.4.5: Connecting Multiple Power Supplies (One Set of Batteries) ...............................................................................................................21 2.5: UPS Trouble Connections................................................................................................................................................................................22 2.6: Connecting NAC and Power Outputs..............................................................................................................................................................22 2.7: Connecting to the SLC.....................................................................................................................................................................................22 2.8: External Coding and Synchronization .............................................................................................................................................................22
Section 3: Configuration and Programming ................................................................................................................. 23 3.1: SLC Addressing ...............................................................................................................................................................................................23 3.1.1: Determining SLC Address Consumption .............................................................................................................................................23 3.1.2: Setting the Base Address ......................................................................................................................................................................23 3.2: Programming the ACPS-610 ...........................................................................................................................................................................24 3.2.1: Installing the Configuration Software ..................................................................................................................................................25 3.2.2: Establishing the Hardware Connection ................................................................................................................................................26 3.2.3: Working Offline....................................................................................................................................................................................26 3.2.4: Working Online ..................................................................................................................................................................................26 3.2.5: Downloading to the ACPS-610 ............................................................................................................................................................27 3.2.6: ACPS-610 Configuration......................................................................................................................................................................27 3.2.7: Output Configuration............................................................................................................................................................................28 3.2.8: Global Settings......................................................................................................................................................................................29 3.3: Configuring the FACP .....................................................................................................................................................................................32 3.3.1: Software Type ID Codes ......................................................................................................................................................................32 3.4: Two Stage Alert/Evacuation (Canada Only)....................................................................................................................................................32 3.4.1: Addressing in Two-Stage Mode ...........................................................................................................................................................32 3.4.2: Two Stage Panel Programming (V24.xx and lower)............................................................................................................................33 3.4.3: Two Stage Panel Programming (V25.xx and higher)...........................................................................................................................33
Section 4: Applications................................................................................................................................................... 35 4.1: NAC Outputs ...................................................................................................................................................................................................35 4.2: Power Outputs .................................................................................................................................................................................................35 4.3: Class B Initiating Device Circuit .....................................................................................................................................................................36 4.4: Synchronization ...............................................................................................................................................................................................36
Section 5: Power Supply Calculations .......................................................................................................................... 40 5.1: DC Current Draw Calculations........................................................................................................................................................................40 5.1.1: Calculating the Maximum Secondary Power Non-Fire Alarm Current Draw .....................................................................................42 5.1.2: Calculating the Maximum Secondary Power Fire Alarm Current Draw .............................................................................................42 5.2: Calculating the Battery Requirements .............................................................................................................................................................43

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

5

Table of Contents
5.2.1: Calculating the Battery Capacity ..........................................................................................................................................................43 5.2.2: Calculating the Battery Size .................................................................................................................................................................44 Index ................................................................................................................................................................................. 45

6

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Section 1: Introduction
The ACPS-610/E is an addressable power supply and battery charger with 24 VDC outputs. It operates in FlashScan® or CLIP (Classic Interface Protocol) mode, and has built-in strobe synchronization. Its four outputs may be independently configured to drive Notification Appliance Circuits (NACs--constant, coded, or synchronized) or to provide auxiliary power (resettable, door holder, or general purpose).
1.1 Features
· Addressable by any CLIP or FlashScan Fire Alarm Control Panel (FACP) · Strobe/NAC Synchronization with System Sensor SpectrAlert® and SpectrAlert® AdvanceTM Series horns and strobes, or Gentex
or Wheelock horns and strobes. (Use only devices from the same manufacturer in each system). · NAC synchronization with UZC-256 (Universal Zone Coder) · NAC wiring can be Class A or Class B · Combined output provides up to 6.0 A total (or up to 10.0 A total when charger is disabled).
­ Each output, configured as a NAC, provides 1.5 Amps ­ Each output, configured as Power, provides 1.5 Amps with charger enabled and 2.5 Amps with charger disabled. · Auxiliary Outputs: 24V @ 0.5A and 5V @ 0.15A · Power-limited (Class 2) outputs · Charges 12 to 200 AH batteries · Isolated Signaling Line Circuit (SLC) interface · Brownout detection · Battery charger supervision · Battery voltage supervision · Disconnect of deeply-discharged battery (low battery disconnect) · Selectable charger current · AC loss detection and AC loss delay reporting · Switch-selectable Ground Fault Detection Zero (0) from any output to Earth will cause Ground Fault Detection · Occupies between 5 and 14 addresses on an SLC, depending on configuration · Selectable Canadian Two-stage option/Canadian Trouble reporting · UL 864 10th edition compliant · Configure databases, upgrade firmware, and upload/download to the power supply via USB port ­ J3 Requires PC or laptop with USB port and PK-PPS programming application
1.2 Specifications
The ACPS-610 is comprised of two boards; the main control unit (the larger rear board), and the CPS-24 (the smaller front board). See Figure 1.1.
1.2.1 CPS-24 Board
 AC Power - TB1
ACPS-610 ­ 120 VAC 50/60 Hz input, 5.0 A max. ACPS-610E ­ 220 - 240 VAC 50/60 Hz input, 2.5 A max. Maximum 12 AWG (3.31 mm2) with 600 VAC insulation. Fuse: 8 amps, 250V, 5 x 20 mm, Fast-Acting, ceramic. Notifier P/N 12117.
 Secondary Power (Battery) Charging Circuit - TB3
Current-limited, sealed lead-acid battery charger which will charge 12 to 200 AH batteries. Utilizes wire sizes 10-14 AWG. (5.26 mm.2 ­ 2.08 mm.2) Charging current: 2.0 A, 5.0 A, or OFF (Software selectable) Based on battery size programming. Charging voltage: 27.6 VDC (nominal) To calculate expected standby operating times, see Section 5.2 on page 43. When AC Power is lost, the deeply-discharged battery cutoff protection will be invoked at 17 volts. The power supply will be disconnected from the batteries. The power supply's normal operation will be restored when AC power returns.
 Secondary Power 5V and 24V AUX outputs - TB2
Power-limited (Class 2): 24V @ 0.5A, 5V @ 0.15A Utilizes wire sizes 12-18 AWG (3.31 mm2 - 2.08 mm2)
1.2.2 Main Control Unit
 Output Circuits - TB3, TB4, TB5, TB6
­ NAC Output · Nominal voltage: 24 VDC, regulated · 1.5 A maximum for any output circuit configured as a NAC.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

7

Introduction

Installation Standards and Codes

· At alarm current level with 12-18 AWG, no more than a 1.2 V drop at the end of the circuit, or sized to provide the minimum rated operation voltage of the appliances used.
­ Output Power Circuit, resettable, door holder, and general power. · Nominal voltage: 24 VDC, special applications. · 1.5 A max. with charger enabled. · 2.5 A max with charger disabled. · Maximum ripple voltage: 200 mV p-p. · 12-18 AWG, no more than a 1.2 V drop at the end of the circuit, or sized to provide the minimum rated operation voltage of the appliances used.
Zero (0) ohms from any output to earth ground will cause ground fault detection. Refer to the Device Compatibility Document for compatible devices, 24 VDC detectors, and notification appliances.
 SLC Circuit - TB2
Average SLC current is 1.0 mA. The maximum resistance of the SLC wiring from any device to the FACP should not exceed 50 ohms. Utilizes wire sizes 12-18 AWG (3.31 mm.2 ­ 0.821 mm.2)
 UZC - TB1
24 VDC coded input (UZC or Sync Signal) Utilizes wire sizes 12 ­ 22 AWG (3.31 mm.2 ­ 0.326 mm.2) twisted pair wire
 Full Speed USB 2.0 - J3
USB Type B connector

1.3 Installation Standards and Codes

The ACPS-610/E complies with the following standards:
NFPA 72 National Fire Alarm Code
Underwriters Laboratories:
· UL 864 Standard for Control Units and Accessories for Fire Alarm Systems · UL 2572 Standard for Mass Notification Systems Underwriters Laboratories of Canada (ULC):
· ULC-S527-11: Standard of Control Units for Fire Alarm Systems · ULC-S524: Standard for the Installation of Fire Alarm Systems In addition, the installer should be familiar with the following standards:
· NEC Article 300 Wiring Methods · NEC Article 760 Fire Protective Signaling Systems · Applicable Local and State Building Codes · Requirements of the Local Authority Having Jurisdiction · The Canadian Electrical Code, Part 1

1.3.1 UL 864 9th and 10th Edition
· Per the UL Continuing Certification Program, UL 864 9th edition fire alarm control equipment will retain certification after the rollout of UL 10th edition (12/2/2018).
· Installations of UL 864 10th Edition certified equipment are permitted to use UL864 9th Edition certified equipment when approved by the local Authority Having Jurisdiction (AHJ).
For product compliance, refer to the UL/ULC listing cards located on the UL online certification directory. http://iq.ulprospector.com
The following products have not received UL 864 9th or 10th Edition certification and may only be used in retrofit applications. Operation of the ACPS-610/E with products not tested for UL 864 9th or 10th Editions have not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).

· AFP-100 · AM2020/AFP-1010 · ICM-4/E

· AFP-200 · NFS-640

· AFP-300/400 · NFS-3030

8

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Related Documentation

Introduction

1.4 Related Documentation
To obtain a complete understanding of specific features of the ACPS-610, or to become familiar with functions in general, make use of the documentation listed in Table 1.1.

Title

Document Number

AFP-100 Instruction Manual AFP-200 Instruction Manual AFP-300/AFP-400 Installation, Operations, and Programming Manuals AM2020/AFP1010 FACP NFS-320 Installation, Operations, and Programming Manuals NFS-640 Installation, Operations, and Programming Manuals NFS2-640 Installation, Operations, and Programming Manuals NFS-3030 FACP Installation, Operations, and Programming Manuals NFS2-3030 FACP Installation, Operations, and Programming Manuals NCA Network Control Annunciator NCA-2 Network Control Annunciator NCD Network Control Display Marine-EQTM System Product Installation Document SLC Wiring Instruction Manual Veri-Fire Tools Installation CD Device Compatibility Document UZC Universal Zone Coder Installation, Programming Manuals

51010 15511 50253, 50259, 50260 15088 52745, 52747, 52746 51332, 51334, 51333 52741, 52743, 52742 51330, 51345, 51344 52544, 52546, 52545 51482 52482 LS10210-051NF-E 54756 51253 VERFIRE-TCD 15378 15216, 15976

BB-100/200 Cabinet Installation Instructions CAB-3/CAB-4 Series Installation Instructions BB-25 Cabinet Installation Instructions BB-55 Cabinet Installation Instructions Power Supply Programming Utility

51981 15330 50898 50295 PK-PPS

Table 1.1 Related Documentation

NOTE: Unless otherwise indicated, when used in this manual, ACPS-610 refers to both the ACPS-610 and ACPS-610E.
1.5 Notes, Cautions, and Warnings
This manual contains notes, cautions, and warnings to alert the reader as follows: NOTE: Supplemental information for a topic, such as tips and references.

CAUTION: A BRIEF IDENTIFIER STATING THE NATURE OF THE HAZARD.
! INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS, RUNTIME ERRORS, OR
EQUIPMENT DAMAGE. WARNING: A BRIEF IDENTIFIER STATING THE NATURE OF THE HAZARD.
! INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE EQUIPMENT DAMAGE,
IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL INJURY.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

9

Battery Connections (TB3)
ACPS-610_newboard.wmf

Introduction

Board Layout

1.6 Board Layout
The ACPS-610 is comprised of two boards; the main control unit (the larger rear board), and the CPS-24 board (the smaller front board). Figure 1.1 below illustrates the layouts for these boards. Figure 1.2 illustrates the positions of the LEDs.

Output 3

Class A Return

Out 3 COM ­ Out 3 +24V + Out 3 COM ­ Out 3 +24V +

Output 1

Output 2
Class A Return

Out 2 COM ­ Out 2 +24V + Out 2 COM ­ Out 2 +24V +

Class A Return

Out 1 COM ­ Out 1 +24V + Out 1 COM ­ Out 1 +24V +

SLC Address Slider Switch
(SW3 )
SLC Address Rotary Switch (SW2)
USB Port (J3)

UZC or Synch input
+­
SLC B +­
SLC A +­

Output 4 + +24V ­ COM

Class A Return

­+

+24V COM

Accessories Outputs (TB2)

+24V Com Com

+5V

BATT + BATT ­
Ground Fault Switch (SW1)

HOT NEUT
EARTH GROUND
AC Fuse (F4)

Figure 1.1 The ACPS-610 Board Layout

10

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

LED Indicators

Introduction

1.7 LED Indicators
There are 23 LEDs that indicate various conditions and troubles. The following table lists and describes each. Figure 1.2 on page 12 shows the location of the LEDs on the PC boards.

Reference
2 3 4
5 6 7

8,9 10
Main Control Unit
11, 12 13

14, 15 16

CPS-24

17, 18 1 2
3 4 5 6

LED Name
STATUS* RESET GEN TBL*
SLCRX SLCTX OUT1 TBL*
OUT1 Active OUT2 TBL*
OUT2 Active OUT3 TBL*
OUT3 Active OUT4 TBL*
OUT4 Active Logic Power TROUBLE
EARTH FAULT AC
+24V Aux +5V Aux

Color
Green Yellow Yellow
Green Green Yellow
Green/Red Yellow
Green/Red Yellow
Green/Red Yellow
Green/Red Green Yellow
Yellow Green Green Green

Description
Slow blink (1x/sec.) during normal operation.
Illuminates during on Power Up and ACPS-610 CPU reset. Blinking reset
indicates trouble, call technical service.
Steady glow indicates trouble, except as noted below:
· Slow blink (1x/sec.)SLC Address Out of Range · Fast blink (5x/sec.) Program Mode · 1 blink, pause and repeat CPS-24 Communication Failure · 2 blinks, pause and repeat UZC Sync Signal Loss
Blinks when data is received from the SLC.
Blinks when data is transmitted to the SLC.
· SteadyIn Current Limit · Steady (with fast blinking GEN TBL) RAM Test Failure
­ Call Technical Service. · Fast blink (5x/sec.) Hardware Failure · 1 blink, pause and repeat Open · 2 blinks, pause and repeat Short
Glows green when output is active +24V power. Glows red when output is active NAC.
· SteadyIn Current Limit · Steady (with fast blinking GEN TBL) Revision ID Mismatch
­ Download compatible firmware (see page 27). · Fast blink (5x/sec.) Hardware Failure · 1 blink, pause and repeat Open · 2 blinks, pause and repeat Short
Glows green when output is +24V power. Glows red when output is active NAC.
· SteadyIn Current Limit. · Steady (with fast blinking GEN TBL) Corrupt Application
­ Download application (see page 27). · Fast blink (5x/sec.) Hardware Failure · 1 blink, pause and repeat Open · 2 blinks, pause and repeat Short
Glows green when output is active +24V power. Glows red when output is active NAC.
· SteadyIn Current Limit · Steady (with fast blinking GEN TBL) Corrupt Database
­ Download database (see page 27). · Fast blink (5x/sec.) Hardware Failure · 1 blink, pause and repeat Open · 2 blinks, pause and repeat Short
Glows green when output is active +24V power. Glows red when output is active NAC.
Illuminates when logic power is active (normal condition).
Blinks, pauses and repeats; as specified below, when the following troubles occur:
­ AC Failure ...................................................................... 1 blink ­ High Battery .............................................................................2 blinks ­ Low Battery..............................................................................3 blinks ­ Charger Failure.........................................................................4 blinks
Illuminates when a ground fault is detected.
Illuminates when there is AC power.
Illuminates when output is active +24V power.
Illuminates when output is active +5V power.

Table 1.2 LED Indicators

* STATUS, GENERAL and OUTPUT TROUBLE LEDS steady when database/firmware download is in process. Do not disconnect power or the USB cable during this time!
 Disconnect the output and wait for 10 seconds. Then, reset the Power Supply by disconnecting the battery and AC power. If the problem persists, replace the ACPS-610.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

11

Introduction

LED 4: GENTBL

LED 3: RESET

LED 2: STATUS

LED 5: SLCRX LED 6: SLCTX

LED Indicators

LED 18: ALARM LED 17: POWER LED 16: TROUBLE
LED 15: ALARM LED 14: POWER LED 13: TROUBLE
LED 11: ALARM LED 12: POWER LED 10: TROUBLE
LED 9: ALARM LED 8: POWER LED 7: TROUBLE

ACPS-610LEDsnewa.wmf ACPS-610LEDsBIG.cdr

LED 6: +5V AUX LED 1: LOGICPWR LED 2: TROUBLE LED 3: EARTH FAULT LED 4: AC LED 5: +24V AUX
Figure 1.2 LED Indicator Locations

12

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Section 2: Installation

WARNING: HIGH VOLTAGES PRESENT!
! USE EXTREME CAUTION WHEN WORKING WITH THE ACPS-610. HIGH VOLTAGE AND AC LINE-CONNECTED
CIRCUITS ARE PRESENT IN THIS POWER SUPPLY. TURN OFF AND REMOVE ALL POWER SOURCES. TO REDUCE THE RISK OF ELECTRIC SHOCK, MAKE SURE TO PROPERLY GROUND THE ACPS-610. INSTALL THE SNAP-ON COVER FOR TB1 AFTER WIRING.

2.1 Mounting Options
2.1.1 In a CAB-PS1 Cabinet
The ACPS-610 mounts in a CAB-PS1 cabinet. Two 12 amp-hour batteries fit into the bottom of this cabinet along with the ACPS-610. The chassis is fastened to the two top right studs with two keps nuts, included (P/N 36045).
When replacing an ACPS-2406 with an ACPS-610 in an existing CAB-PS1, a replacement door (P/N DR-PS1) must be used. The current door will not close and could cause damage to the equipment if attempted.

Fasten the ACPS610 chassis to the backbox using the studs with two # 4-40 keps nuts, included, (P/N 36045) at these positions.

acps610cabps1.cdr

Figure 2.1 CAB-PS1 Mounting
2.1.2 In a CAB-4 or EQ Series Backbox
CAB-4 Series
The ACPS-610 mounts in the lower left of a CAB-4 Series enclosure. The ACPS-610 should be mounted on the left of the enclosure when it will be connected to 26AH batteries that are located in the same cabinet. It can also be mounted in any row of the CAB-4 enclosures using a CHS-6 or CHS-PS chassis. Two 12V, 12AH batteries can be mounted in the CHS-BH chassis. Refer to "Chassis" on page 14 for more information.
Mount the ACPS-610 in the lower left of any CAB-4 Series cabinet.
Lower the power supply over the cabinet's support brackets and fasten to the backbox with two # 6-32 self-threading screws, included, at the indicated positions.

ACPS610cab4.wmf

Figure 2.2 CAB-4 Series Backbox

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

13

Installation

Mounting Options

EQ Series Cabinets
The ACPS-610 mounts on a CHS-6 or CHS-PS chassis into any EQ Series cabinet row. Two 12V, 12AH batteries can be mounted in the CHS-BH chassis. Refer to "Chassis" on page 14 for more information.

ACPS610-EQCAB.wmf

Figure 2.3 EQ Series Backbox

Chassis

When the power supply can not be mounted in the cabinet's lowest row, use the CHS-6 (see Figure 2.4) or CHS-PS (see Figure 2.5) to mount it in any other row of the CAB-4 or EQ Series enclosures.
If batteries for the ACPS-610 are not mounted in the bottom of the cabinet, a CHS-BH battery holder chassis may be used. It can hold two 12V, 12 AH batteries, and mounts on the CHS-PS chassis (see Figure 2.6). Note that the ACPS-610 and CHS-BH both occupy the right-hand space on a CHS-PS chassis, and so can not be mounted together on the same chassis.

The ACPS-610 will require the left two of the three CHS-6 chassis spaces.

Fasten the power supply to the chassis with two #4-40 hex nuts, included, at these positions.

ACPS-610

ACPS-610-chs6.wmf

CHS-6

ACPS-610/CHS-6

Figure 2.4 CHS-6 Chassis

14

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Mounting Options

Installation

chs-ps_acps610.wmf

The ACPS-610 will require the righthand space on the CHS-PS chassis.
CHS-PS
Figure 2.5 CHS-PS Chassis

Fasten the power supply to the CHS-PS chassis with two #6-32 hex nuts, included, at these positions.
ACPS-610

The CHS-BH battery holder chassis can hold two 12V, 12 AH batteries. It requires the right-hand space on the CHS-PS chassis.
NOTE: The CHS-BH and the ACPS-610 can not be mounted in the same CHS-PS chassis, as both require the right side for mounting.

CHS-PS

Fasten the battery holder to the CHS-PS chassis at these two points with two #6-32 hex nuts, included, at these positions.

chs-ps_chs-bh.wmf

CHS-BH
Figure 2.6 CHS-PS Chassis with CHS-BH
2.1.3 In a BB-25 Cabinet
The ACPS-610 mounts in the left side of a BB-25 cabinet. Two 26 amp-hour batteries fit into the right side of the cabinet. A BB-100 or BB-200 cabinet is required for batteries larger than 26 amp-hour.
Fasten the power supply to the backbox with two # 8-32 self-threading screws, included, (P/N 38132) at the indicated positions.

ACPS-610_BB25.wmf

Figure 2.7 BB-25 Cabinet Mounting

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

15

Installation

Mounting Options

2.1.4 In a BB-100 Cabinet
The ACPS-610 mounts in a BB-100 cabinet. Two 55 or 100 amp-hour batteries fit into the bottom of this cabinet under the ACPS-610. The power supply is fastened directly to the unpainted section of the backbox using the two provided keps nuts.

Fasten the ACPS-610 chassis to the backbox using the two # 4-40 keps nuts, included, (P/N 36045) at these positions.

WARNING: HEAVY LOAD!
! THE TOTAL WEIGHT OF A FULLY LOADED
BB-100 WILL EXCEED 175 POUNDS. ADDITIONAL SUPPORT MAY BE REQUIRED WHEN MOUNTING THIS CABINET TO A WALL. SEE BB-100/200 CABINET INSTALLATION INSTRUCTIONS FOR MORE INFORMATION.

ACPS-610_BB100_2Batt.wmf

Figure 2.8 BB-100 Mounting
2.1.5 In a BB-200 Cabinet
Fasten the ACPS-610 chassis to the backbox using the two # 4-40 keps nuts, included, (P/N 36045) at these positions.

WARNING: HEAVY LOAD!
! THE TOTAL WEIGHT OF A FULLY
LOADED BB-200 WILL EXCEED 300 POUNDS. ADDITIONAL SUPPORT MAY BE REQUIRED WHEN MOUNTING THIS CABINET TO A WALL. SEE BB-100/200 CABINET INSTALLATION INSTRUCTIONS FOR MORE INFORMATION.

ACPS-610_BB200_4Batt.wmf

Figure 2.9 BB-200 Mounting The ACPS-610 mounts in a BB-200 cabinet with four 100 amp-hour batteries (two on the top shelf and two on the bottom). The power supply is fastened directly to the unpainted section of the backbox with two keps nuts.

16

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

ACPS-610_WIRECAB3.wmf CAB3WiringSide.cdr
ACPS-610_WireBB25.wmf

UL Power-limited (Class 2) Wiring Requirements

Installation

2.2 UL Power-limited (Class 2) Wiring Requirements

Power-limited (Class 2) wiring must remain separated from nonpower-limited wiring by at least 0.25 in. (6.4 mm), and must enter the enclosure through different knockouts. Install tie wraps and adhesive squares to secure the wiring. Figures 2.10 and 2.11 show samples of power-limited (Class 2) and nonpower-limited wiring configurations in different cabinets.
Terminal block and pin connections are illustrated in Figure 1.1.

TB3: Nonpower-limited and supervised

SLC and Output Circuit Wiring: Power-limited (Class 2), regulated, and filtered. Supervised except for TB1: UZC+, UZC­. Outputs 1-4 supervised in NAC configuration only.

TB1: AC Primary Power Wiring Nonpower-limited and supervised

Figure 2.10 BB-25 Cabinet: Power-limited (Class 2) Wiring Example, with Two Battery Wiring

TB3: Nonpower-limited and supervised Ground fault detection and internal charger disabled. See page 21.
Power-limited (Class 2) circuit

SLC and Output

Circuit Wiring:

Side-View

Power-limited (Class

2), regulated, and

filtered. Supervised

except for TB1: UZC+,

UZC­.

Outputs 1-4

supervised in NAC

configuration only.

Power-limited (Class 2) circuits

Nonpowerlimited circuits

TB1: AC Primary

Power Wiring Nonpower-limited

AC

and supervised

Figure 2.11 CAB-4 Series Cabinet: Power-limited (Class 2) Wiring Example

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

17

Installation

Connecting the Power Supply to AC Power

WARNING: RISK OF ELECTRICAL SHOCK!
! REMOVE ALL POWER SOURCES TO EQUIPMENT WHILE CONNECTING ELECTRICAL COMPONENTS. LEAVE THE
EXTERNAL, MAIN POWER BREAKER OFF UNTIL INSTALLATION OF THE ENTIRE SYSTEM IS COMPLETE.
WARNING: RISK OF EQUIPMENT DAMAGE!
! SEVERAL SOURCES OF POWER CAN BE CONNECTED TO THE CONTROL PANEL AND/OR POWER SUPPLY.
BEFORE SERVICING THE CONTROL PANEL, DISCONNECT ALL SOURCES OF INPUT POWER INCLUDING THE BATTERY. WHILE ENERGIZED, THE CONTROL PANEL AND ASSOCIATED EQUIPMENT CAN BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES, OR INTERCONNECTING CABLES.
2.3 Connecting the Power Supply to AC Power
TB1 (CPS-24) - Primary AC power source ­ 120 VAC, 50/60 Hz, 5.0 A (ACPS-610E uses 220-240 VAC, 50/60 Hz, 2.5 A) from line voltage source. The ACPS-610 requires connection to a separate dedicated AC branch circuit. Follow these guidelines when connecting the AC branch circuit:
· Label the branch circuit "Fire Alarm". · Connect the branch circuit to the line side of the main power feed of the protected premises. · Do not power other non fire alarm equipment from the fire alarm branch circuit. · Run the AC branch circuit wire continuously, without any disconnect devices, from the power source to the power supply. · Overcurrent protection for the AC branch circuit must comply with Article 760 of the National Electrical Codes, as well as local
codes. · Use 12­14 AWG (3.31 mm2 ­ 2.08 mm2) wire with 600 VAC insulation for the AC branch circuit.
Connect primary power as follows:
1.Turn off the circuit breaker at the main power distribution panel. 2.Connect the earth ground terminal (TB1- EARTH) to a solid earth ground (a metallic, cold water pipe may be suitable in some installations). This connection is vital in reducing the panel's susceptibility to transients generated by lightning and electrostatic discharge. 3.Connect the primary power neutral line to terminal marked NEUTRAL and the primary power AC line to terminal marked HOT.

acps-610_AC.cdr

Figure 2.12 AC Power Connection

18

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Installing and Connecting the Batteries

Installation

2.4 Installing and Connecting the Batteries
WARNING: RISK OF SEVERE BURNS!
! BATTERIES CONTAIN SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES, AND CAN
DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION. WARNING: RISK OF EQUIPMENT DAMAGE!
! DO NOT CONNECT THE BATTERY INTERCONNECT CABLES, INCLUDED, (P/N 75560, 75561, OR 71070) AT THIS
TIME. LEAVE THE BATTERY INTERCONNECT CABLES DISCONNECTED UNTIL AFTER INITIAL SYSTEM POWERUP. WARNING: RISK OF EQUIPMENT DAMAGE!
! TO AVOID CONTACT WITH METAL CABINET, ALWAYS INSTALL TERMINAL BOLTS TOWARDS THE CENTER OF THE
BATTERY. SEE FIGURE 2.13.

TerminalBolts.wmf

Figure 2.13 Terminal Bolt Installation
TB3 (CPS-24) - Secondary power source ­ 24 VDC from batteries installed in the appropriate enclosure. Secondary (battery) power is required to support the system during loss of primary power. Certain system designs may require connecting two or four batteries to the power supply, connecting multiple power supplies to each other, or connecting one set of batteries to multiple power supplies. Always use wire size 10-14 AWG. (5.26 mm.2 ­ 2.08 mm.2), and install the power supply and the batteries in the appropriate enclosures, as described in Section 2.1. Use PK-PPS to select the appropriate battery charger current for the system's battery capacity. See page 28 and pages 43­44 for more information.
2.4.1 Setting the Charger
The ACPS-610 battery charger will charge 12 to 200 AH lead-acid batteries. Use PK-PPS to select the appropriate battery charger current for the system's battery capacity from four settings: 2 A, 5 A, or DISABLE CHARGER. Select 2 A to charge 12 to 55 AH batteries. Set the charger to 5 A when the power supply will be charging a system that requires 56 to 200 AH. Select DISABLE CHARGER when the power supply will set for continuous output or when the batteries will be charged by an external charger (See page 21). See Section 3.2, "Programming the ACPS-610" for more information on programming via PK-PPS. Refer to Section 5.2, "Calculating the Battery Requirements", on page 43 for more information on determining your system's battery capacity.
2.4.2 Connecting the Power Supply to Two Batteries:
1. Use PK-PPS to set the charger to the appropriate current for the system's battery capacity. 2. Connect one cable from TB3 (BATT IN +) on the power supply to the positive (+) terminal of one battery. 3. Connect another cable from TB3 (BATT IN -) on the power supply to the negative (­) terminal of the other battery. 4. Only after initial system power-up, connect a battery interconnect cable between the negative (-) terminal on the first battery to
the positive (+) terminal on the second battery.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

19

Installation To determine battery requirements, refer to Section 5.2 of this manual.

Installing and Connecting the Batteries

acps-610_2Batt.cdr

TB3
Figure 2.14 Connecting Two Batteries to the Power Supply
2.4.3 Connecting the Power Supply to Four Batteries:
1. Use PK-PPS to set the charger to the appropriate battery charger current for the system's battery capacity. 2. Continue the connection from the occupied positive (+) battery terminal to the positive (+) terminal of the next unconnected battery. 3. Continue the connection from the occupied negative (­) battery terminal to the negative (­) terminal of the remaining unconnected
battery. 4. Only after initial system power-up, connect the two pairs of batteries. Use two battery interconnect cables to tie each unoccupied
negative (­) terminal to an unoccupied positive (+) terminal, as shown in Figure 2.15. To determine battery requirements, refer to Section 5 of this manual.

acps-610_4Batt.cdr

TB3

Figure 2.15 Connecting Four Batteries to the Power Supply
NOTE: Use a ring terminal to attach two cables to one battery terminal.
2.4.4 Connecting Multiple Power Supplies (Separate Batteries)
This application may be used when you want a single power supply to monitor for ground fault for multiple power supplies. Follow these guidelines when connecting multiple power supplies:
· Disable Ground Fault detection at all power supplies except one. See Figure 1.1 on page 10. For proper supervision the power supply with the enabled ground fault detection must be connected to the SLC.
· Connect common bond wire between the main power supply and power supplies with disabled ground fault detection. · Connect battery interconnect cables only after initial system power-up. Refer to "Installing and Connecting the Batteries" on
page 19. To determine ACPS-610 battery requirements, refer to Section 5.2 on page 43 in this manual. Refer to the specific power supply manual(s) and/or Device Compatibility Document for further information and instructions.
CAUTION: RISK OF POSSIBLE EQUIPMENT DAMAGE.
! TO MAINTAIN PROPER SUPERVISION, AUXILIARY SUPPLIES USED TO POWER PANEL CIRCUITS, SUCH AS THE
ICM-4/E, MUST BE CONNECTED TO THE SAME BATTERIES AS THE MAIN POWER SUPPLY. FAILURE TO DO SO MAY RESULT IN EQUIPMENT DAMAGE.

20

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Installing and Connecting the Batteries
To Batteries

To Batteries

Installation

acps-610_MultiPS.wmf

ACPS-610

Compatible UL/ULC­Listed Power Supply

Figure 2.16 Connecting Multiple Power Supplies with Common Bond Wire

2.4.5 Connecting Multiple Power Supplies (One Set of Batteries)
Certain system designs may require connecting multiple power supplies to one set of batteries. Follow these guidelines when connecting multiple power supplies:
· For proper supervision, enable only the charger directly connected to the batteries. Disable all other chargers. · Confirm that the enabled charger has the capacity to charge the total load of the selected battery configuration. · Use PK-PPS to set the charger to the appropriate battery charger current for the system's battery capacity. · Disable Ground Fault detection at all power supplies except one. See Figure 1.1 on page 10.
For proper supervision the power supply with the enabled ground fault detection must be connected to the SLC. · All power supply to power supply connections must be in conduit and the total battery connection must be less than
20 feet (6.09 meters) from the enabled power supply. · Connect battery interconnect cables only after initial system power-up. Refer to "Installing and Connecting the Batteries" on
page 19. To determine battery requirements, refer to Section 5.2, "Calculating the Battery Requirements" in this manual.
Refer to the specific power supply manual(s) and/or Device Compatibility Document for further information and instructions.
CAUTION: RISK OF POSSIBLE EQUIPMENT DAMAGE.
! TO MAINTAIN PROPER SUPERVISION, AUXILIARY SUPPLIES USED TO POWER PANEL CIRCUITS, SUCH AS THE
ICM-4/E, MUST BE CONNECTED TO THE SAME BATTERIES AS THE MAIN POWER SUPPLY. FAILURE TO DO SO MAY RESULT IN EQUIPMENT DAMAGE.

Compatible UL/ULC­Listed Power Supply
Internal Charger disabled

Compatible UL/ULC­Listed Power Supply
Internal Charger disabled

ACPS-610
Internal Charger enabled Refer to Section 2.4.1.

AMPS24_MultiPS.cdr

Figure 2.17 Connecting Multiple Power Supplies (One Set of Batteries)

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

21

Installation

UPS Trouble Connections

2.5 UPS Trouble Connections
When a UPS is required, use a monitor module with a trouble Type ID to convey a trouble signal to the FACP.
SLC to panel or next device

To normally closed UPS AC loss contacts.

SLC from panel or previous device

47K EOL Resistor ELR-47K

Monitor Module*

*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for type V and type H modules.

Figure 2.18 UPS Trouble Connections

2.6 Connecting NAC and Power Outputs
TB3, TB4, TB5, TB6 - Outputs 1 through 4. Power-limited (Class 2). Supervised when in NAC configuration. Combined output provides up to 6.0 A total (or up to 10.0 A total with charger disabled). All the outputs are independently configurable as NAC (constant, coded, or synchronized) or Power (resettable, door holder, or general purpose). Each output provides 1.5 A maximum current when configured as a NAC, 1.5 A maximum current when configured as Power with the charger enabled, and 2.5 A maximum current when configured as Power with the charger disabled. With all power sources off, connect wiring. Refer to Section 4 of this manual for application suggestions. NACs may be wired as Class A or Class B.
2.7 Connecting to the SLC
TB2 - Supervised and power-limited (Class 2). With all power sources off, connect the power supply from TB2 to the SLC interface.
Refer to the SLC Wiring Manual for more information.

Optional 4-wire Return Loop Class A

SLC A
­ +

SLC B
+ ­

To SLC Interface

acps-610_TB2-SLC.cdr

Figure 2.19 Connecting to the SLC Interface TB2
2.8 External Coding and Synchronization
Power-limited (Class 2) and non-supervised. UZC input is used to sync or code outputs from an external source. TB1 provides support for external coding sources such as UZC-256 (pulsed 24V) or coded NAC output, or it can be an external sync input for strobe circuits. With all power sources off, connect wiring. Refer to Section 4 of this manual for applications suggestions.

22

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Section 3: Configuration and Programming

3.1 SLC Addressing
When the ACPS-610 communicates via the SLC, the installer must reserve sequential SLC addresses (an address block) equal to the number of addresses that will be consumed by the ACPS-610. Determining the size of the address block and setting the SLC base address is described in this section.

3.1.1 Determining SLC Address Consumption
Depending on how it is configured, an ACPS-610 can occupy a minimum of 5 and a maximum of 14 addresses on an SLC. When programming is complete, the ACPS-610's programming application, PK-PPS, displays the resulting SLC address consumption in its summary section. See Section 3.2, "Programming the ACPS-610" for more information.

Description Monitor General ACPS-610 Output #1 ACPS-610 Output #2 ACPS-610 Output #3 ACPS-610 Output #4

SLC Address* B
B + 1 B + 2 B + 3 B + 4

Signal Silence

NEXT

Monitor AC Fail (Canada only) Monitor Battery (Canada only) Monitor Earth Fault (Canada only) Monitor Charger (Canada only)

NEXT NEXT NEXT NEXT

Two Stage Output #1 Two Stage Output #2 Two Stage Output #3 Two Stage Output #4

NEXT NEXT NEXT NEXT

Table 3.1 ACPS-610 SLC Addresses

* Addresses within shaded areas are assigned in blocks and cannot be assigned independently.  B = SLC Base Address.  SLC addresses depend upon configuration. NEXT = last address in power supply sequence +1.

NOTE: Addresses included in the address block must be programmed points in the FACP whether or not the output points are actually used. Even though some of the 14 possible ACPS-610 addresses may be skipped, none of the addresses in the FACP address block may be skipped.

3.1.2 Setting the Base Address
The base address is the first address used in an SLC address block. Combine the SLC Address rotary switch (SW2) and slider switch (SW3) settings to determine the base address (B). The base address will be a number that ends in zero or five and the rest of the address block will progress sequentially from that number until all the addresses in the block are consumed.

NOTE: The lowest base address for the ACPS-610 is 05. Do not use FACP addresses 00 through 04 for the ACPS-610.

The SLC Address Rotary Switch (SW2)
The SLC address rotary switch (SW2) determines the address decade. Each number on the dial represents the ten addresses of a decade. Turning the arrow until it points at a number selects that number's decade.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

23

Configuration and Programming

Programming the ACPS-610

For example:

Pointing the arrow at the 1 selects the "one" address decade, beginning at 10.

or

Pointing the arrow at the 12 selects the "twelve" address decade, beginning at 120.

rotarysw2404.cdr

The SLC Address Slider Switch (SW3)
Use the SLC address slider switch (SW3) to further define the SLC base address. While an address' decade is defined by the rotary switch, this slider determines whether the base address (B) will end in a zero or a five. Sliding the switch towards the 0 selects a base address that ends with a zero. Sliding the switch towards the 5 selects a base address that ends with a five.
For example: Slide the switch towards the 0, as shown in the illustration to the left, to select an initial address that ends in zero. Since the rotary switch defines the decade, if the rotary switch were to point at 8, the base address in this address block would be 80. or Slide the switch towards the 5, as shown in the illustration to the left, to select an initial address that ends in five. Since the rotary switch defines the decade, if the rotary switch were to point at 8, the base address in this address block would be 85.
Figure 3.1 below gives two examples of setting the base address with both rotary and slider switch settings.

acps-610_SW3.cdr

SW2 ROTARY SWITCH SETTING

SW3 SLIDER SWITCH
POSITION

SLC BASE ADDRESS

005

SLC ADDRESSES SELECTED
with maximum fourteen ACPS-610
Addresses
005-018

120

120-133

acps-610_addrot3.cdr acps-610_addrot1.cdr acps-610_sw31.cdr acps-610_sw32.cdr

Figure 3.1 SLC Address Selection
3.2 Programming the ACPS-610
Use PK-PPS to program the ACPS-610's global functions and individual outputs. With PK-PPS, you can configure and download the ACPS-610 database and update firmware. You can modify a power supply's configuration online, or offline, on a database that can be downloaded at a later date.

24

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Programming the ACPS-610

Configuration and Programming

3.2.1 Installing the Configuration Software

Minimum Requirements
· Windows XP Professional with SP2, or Windows 2000 with SP4. · PC or Laptop with USB 2.0 port.
Installation
1. Log in. The user must have Administrative privileges. 2. Exit out of the NFN Gateway if it is running in the system tray. 3. Insert the CD into the PC's CD drive. 4. Double click on the file PPS.exe on the CD. 5. Follow the instructions of the PPS installation wizard to completion. 6. Connect the ACPS-610 to the PC via the USB cable. (See Section 3.2.2.) Wait for the operating system to detect the new
hardware. 7. Follow the set of steps in Table 3.2 below that are specific to your operating system.
.

Windows XP Professional with SP2

Windows 2000 with SP4

1. On the Found New Hardware Wizard window, select "No, 1. On the Found New Hardware Wizard window, click Next.

not this time". Click Next.

2. Select "Search for a suitable driver for my device". Click

2. Select "Install from a list or specific location". Click Next.

Next.

3. Select "Search for the best driver in these locations". Clear 3. Under optional search locations, select "Specify a

the check box next to "Search removable media" and set

location". Clear all other check boxes. Click Next.

the check mark next to "Include this location in the search". Click Browse.

4.

On the window that pops up, click the Browse button and select the file

4. On the Browse For Folder pop-up window, select the

C:\ProgrammingKit\PowerSupply\USB Drivers\HfsUsb.inf.

folder C:\ProgrammingKit\PowerSupply\USB Drivers. Click

Click Open.

OK.

5. Click OK on the pop-up window.

5. Click Next.

6. Click Next. This will install the driver.

6. On the Hardware Installation window that warns "The software has not passed Windows Logo testing...", click

7. Click Finish.

Continue Anyway.

7. Click Finish.

Table 3.2 Operating System Instructions

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

25

Configuration and Programming

Programming the ACPS-610

WARNING: POWER SUPPLY DISABLED!
! THE POWER SUPPLY IS OUT OF SERVICE DURING DATABASE/FIRMWARE UPLOAD AND DOWNLOADS.
WARNING: RISK OF IRREVERSIBLE LOSS OF PROGRAMMING DATA!
! STEADY STATUS, GENERAL AND OUTPUT TROUBLE LEDS INDICATE THAT A DATABASE/FIRMWARE DOWNLOAD
IS STILL IN PROCESS. DO NOT DISCONNECT POWER OR THE USB CABLE DURING THIS TIME! DISONNECT USB CABLE ONLY AFTER PROGRAMMING IS COMPLETE.
3.2.2 Establishing the Hardware Connection
NOTE: Before connecting PK-PPS to the power supply, exit out of the NFN GATEWAY if it is running in the system tray.
Connect a standard USB cable from the PC's USB port to the ACPS610's USB interface (J3). When the download is complete, the unit automatically reboots and returns to normal operation.

ACPS-610_USB.cdr

Figure 3.2 The ACPS-610 USB Interface (J3)
3.2.3 Working Offline
If your PC is not connected to a power supply, you may create or edit ACPS-610 databases. These databases can be saved and downloaded at a later date.
To create a new database, select NEW from the FILE menu, then select ACPS-610. To edit an existing database, select OPEN from the FILE menu, then select ACPS-610.
3.2.4 Working Online
NOTE: Before connecting PK-PPS to the power supply, exit out of the NFN GATEWAY if it is running in the system tray.
NOTE: Start the PK-PPS utility before connecting to the power supply.
In addition to creating and opening databases on your local drive, you may modify any ACPS-610 that is directly connected to your PC with the PK-PPS programming utility. When you are in the program and you are connected via the USB to a power supply, that power supply is represented by the icon in the left window. Click on this icon to see the power supply's current configuration and version information (Figure 3.3). When you right-click on the ACPS-610 icon, you have three work options:
SAVE Select this option to save the power supply's current configuration as a database file (*.pdb) on your local drive. MODIFY Select this option to edit the power supply's current configuration. After you make all of your changes, your new database will overwrite the one in the ACPS-610. You will also have the option to save this database to your local drive. DOWNLOAD Select this option to download a database, application, or bootloader file to the power supply. See Section 3.2.5.

26

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Programming the ACPS-610

Configuration and Programming

PK-PPS_Currentb.jpg

Power Supply Icon

Database and Firmware Version Information

Figure 3.3 PK-PPS: Current Database
3.2.5 Downloading to the ACPS-610
1. Check to make sure that the PC is connected to the ACPS-610 (Section 3.2.2). 2. Right click on the ACPS-610 icon, select DOWNLOAD and choose the type of application you wish to download or select
Download from the Operation menu. You may download a program database file (*.pdb), an application file (*.hex), or a bootloader file (*.hex). 3. Use the Browse button to navigate to the file you wish to download. 4. Open the file to download it to the ACPS-610. 5. Disconnect USB cable AFTER programming is complete.
3.2.6 ACPS-610 Configuration
PK-PPS sets parameters for the ACPS-610 and all of its outputs. Selections must be made in order shown below. Lower level options will not be available until upper level options have been selected. The worksheet's summary section displays all selections. When programming is complete, PK-PPS displays the SLC address consumption that is result of your selections.

PK-PPS_Label.jpg

Figure 3.4 PK-PPS: Label
Label
For greater ease of identification, you may create a label for each power supply. Labels may have a maximum of 40 characters.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

27

Configuration and Programming

Programming the ACPS-610

Figure 3.5 PK-PPS: Battery Charger
Battery Charger
Choose the appropriate battery charger current for the system's battery capacity. Refer to Section 5.2, "Calculating the Battery Requirements", on page 43 for more information on determining your system's battery capacity. There are three charger current options. Select 2A CHARGE to charge 12 to 55 AH batteries. Select 5A CHARGE to charge 56 to 200 AH batteries. Select DISABLE CHARGER when the power supply will not be connected to any batteries or when the batteries will be powered by an external charger (See page 22).
NOTE: When the battery charger is disabled, the power output continuous current is 2.5 Amps.
3.2.7 Output Configuration
Output circuits one through four can be programmed independently with these worksheets. Each output may be configured as either a NAC, a power circuit, or a door holder.

PK-PPS_NACOut.jpg

Figure 3.6 PK-PPS: Output Configuration

28

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Programming the ACPS-610

Configuration and Programming

NAC
NOTE: Active NACs will disable the power supply's charger.
Choose the type of NAC output for each circuit. CONSTANT The output goes active in Alarm and provides steady voltage with no code or sync. CODED The output provides a coded signal. The code type can be determined internally or by an external source. See "Coding Type" on page 29. SYNCHRONIZED The output provides a synchronized signal. Signal synchronization can be determined internally or by an external source. See "Synchronization" on page 30. NOTE: Do not place strobes from any manufacturer onto a coded output. For example SpectrAlert or SpectrAlert Advance Series horns and strobes can not be synchronized with a UZC-256 or any coded output.
Power
Choose whether the output will supply non-resettable or resettable power.
Door Holder
Select delay time conditions from the drop down menu. Choose INSTANT RELEASE for a delay of zero seconds, DELAY 30 SECONDS for a thirty second delay before the doors are released, or NEVER RELEASE to keep all doors open.
WARNING: RISK OF BODILY INJURY!
! ALL OUTPUTS THAT ARE CONFIGURED AS A RELEASING DOOR HOLDER ("INSTANT RELEASE" OR "DELAY 30
SECONDS") MUST BE PROGRAMMED AT THE FACP AS A NON-SILENCEABLE SLC POINT. SEE THE FACP MANUAL FOR MORE INFORMATION.
3.2.8 Global Settings

PK-PPS_CodeTypes.jpg

Figure 3.7 PK-PPS: Coding Type
Coding Type
Code type is a global setting that applies to all NAC outputs configured as CODED. (See Section 3.2.6 on page 27.) NAC codes can be generated internally or they can come from an external source via the power supply's UZC sync input (TB1). Choose the internal or external coding for all coded NAC outputs.
EXTERNAL (UZC): The NAC sends a signal that is determined by an external source via the power supply's UZC sync input (TB1). Select this option when the power supply will be connected (via TB1) to an external coded signal. This option will not be available if the UZC is already configured to accept a synchronized signal. MARCH TIME: The NAC sends a pulsed signal of 120 PPM (Pulses Per Minute). TEMPORAL: The NAC sends a pulsed signal in a pattern of three cycles of 0.5s on/off followed by 1.5s off. Temporal is the standard NFPA 72 evacuation pattern. CANADIAN:
TWO STAGE 1: The NAC sends a two-stage signal of Alert tone followed by a temporal pattern.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

29

Configuration and Programming

Programming the ACPS-610

TWO STAGE 2: The NAC sends a two-stage signal of Alert tone followed by 120 PPM (March
Time).
TWO STAGE 3: The NAC sends a two-stage signal of Alert tone followed by a continuous tone.

PK-PPS_Sync.jpg

Figure 3.8 PK-PPS: Synchronization
Synchronization
Select the protocol for synchronized outputs. Select USE EXTERNAL SYNC (UZC), when the power supply will be connected (via TB1) to an external sync source. The external sync source must be an FACP or power supply manufactured by the same manufacturer as the ACPS-610. This is a non-supervised connection. This option will not be available if the UZC is already configured to accept a coded signal (See "Coding Type" on page 29). If no external sync is selected or there is a loss of signal, the ACPS-610 will generate an internal sync pattern based upon the selection from the INTERNAL/BACKUP SYNC dropdown menu.  Silenceable Select this option to silence all synchronized NACs when signal silence is activated. Use this option with Gentex, System Sensor and Wheelock synchronized devices. If any output address is configured as "non-silenceable" at the panel, the horns will mute, but the strobes will remain active when silenced. If any output address is configured as "silenceable" at the panel, both horns and strobes will become inactive when silenced. Making outputs silenceable adds an additional SLC address (see Section 3.1.1 on page 23). This extra address is specifically for Signal Silence only. The Signal Silence SLC address should be configured in the panel as a "silenceable output", activated by CBE.
CAUTION: ALL SYNCHRONIZED POWER SUPPLIES MUST HAVE THE SAME PROTOCOL!
! FOR SYNCHRONIZED MASTER/SLAVE OPERATION: WHEN A SYNCHRONIZED SIGNAL IS SUPPLIED TO THE UZC
CONNECTIONS OF TB1, THE SAME PROTOCOL MUST ALSO BE PROGRAMMED AT THE SLAVE ACPS-610 AS PROGRAMMED AT THE MASTER ACPS-610. THIS WILL ENSURE OPERATION OF ALL SYNCHRONIZED OUTPUTS OF THE SLAVE ACPS-610 SHOULD SIGNAL LOSS OCCUR OF THE SYNCHRONIZATION INPUT (UZC CONNECTIONS) AT TB1.

30

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Programming the ACPS-610

Configuration and Programming

PK-PPS_TroubleReport.jpg

Figure 3.9 PK-PPS: Trouble Reporting
Trouble Reporting
Select the trouble reporting option. When the power supply is configured for US trouble reporting options, the panel will report a trouble message at the base address. Choose a US AC Fail Delay time (0, 2 HOURS, 8 HOURS, or 16 HOURS) from the drop-down menu. In FlashScan systems, the panel will display the specific trouble type (AC Fail, Battery Low, Battery High, Earth Fault, or Charger Failure) at the power supply's base address. In CLIP systems, the panel will only display a general trouble at the power supply's base address. When the power supply is configured for Canadian trouble reporting, the panel displays a specific trouble message for the AC Fail, Battery, Earth Fault, and Charger Fail addresses (See Table 3.1). If a Canadian code type is selected, trouble reporting will be set automatically to Canadian.

PK-PPS_Summary.jpg

Figure 3.10 PK-PPS: Summary
Summary
The Summary screen displays all of your previous selections and the resulting SLC address consumption. Review this summary screen before downloading and ensure that the proper number of consecutive addresses are reserved. You may use the BACK button to edit any of your selections. Click the FINISH button to save your changes to the database.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

31

Configuration and Programming

Configuring the FACP

3.3 Configuring the FACP

3.3.1 Software Type ID Codes
ACPS-610 points must be programmed at the FACP with Software Type ID codes. Refer to the panel programming manual for specific Software Type ID codes. Table 3.4 below gives general categories of codes that may be used for the AFP-100, AFP-200, AFP-300/400, AFC-600, AM2020/AFP-1010 FACPs. See the specific FACP manual for more information.

Point Type Trouble Points
NAC Points +24V Relay
Points

Allowable Software Type ID Codes Software Type ID Codes for trouble monitors Software Type ID Codes for supervised NAC circuits
Software Type ID Codes for relay circuits

Table 3.3 Software Type Codes

Table 3.4 Software Type ID Codes, AFP-100, AFP-200, AFP-300/400, AFC-600, AM2020/AFP-1010

Table 3.6 below categorizes codes used with the NFS FACPs.

Point Type

Module Type

NFS-3030/NFS2-3030

Type Code Label

FlashScan Type

NFS-640 NFS2-640 NFS-320
Type Code Label

VeriFire Tools for NFS3030/NFS2-3030, NFS640/NFS2-640, and NFS-320

Type Code Label

FlashScan Type

Trouble Points Monitor Power Monitr PS Mon

Power Monitr

Power Monitr PS Monitor

NAC Points

Control Control

PS Control Control

Control

PS Control

+24V Relay

Control Relay

PS Relay

Relay

Relay

PS Relay

Table 3.5

Table 3.6 NFS-3030/NFS2-3030, NFS-640/NFS2-640, NFS-320 Software Type Codes

NOTE: When a UPS is used, program the associated monitor module with a trouble point Type ID from Table 3.4.
3.4 Two Stage Alert/Evacuation (Canada Only)
3.4.1 Addressing in Two-Stage Mode
Two Stage Alert/Evacuation is a mode option for use in Canada only, with the NFS-3030/NFS2-3030, NFS-640/NFS2-640, NFS-320, or AM2020/AFP1010. In this mode each coded NAC output operates in one of two stages: alert or evacuation. The alert stage generates a pulsing output of 20 pulses per minute: the evacuation stage generates an output in the NFPA Temporal Pattern (Canadian 1), March Time--120 ppm--(Canadian 2), or a continuous tone (Canadian 3). Select the Two Stage mode from the Coding Type worksheet (page 29). Any individual ACPS-610 output circuits must be set to the coded NAC option on the corresponding Output Configuration Worksheet in PK-PPS (page 28). When the ACPS-610 is set to two-stage, each output circuit uses two control addresses, even if the circuit is not configured for two-stage (i.e. not a coded NAC). The installer should ascertain that an appropriate block of consecutive FACP addresses is available prior to addressing an ACPS-610 in Two Stage. Table 3.1 on page 23 shows Two Stage addressing and address consumption. The first address for each output does one of three things: 1. If the output is a coded NAC, activating the first associated address activates Stage 1 (alert). 2. If the output is a synchronized NAC, activating the first associated address turns the output on. 3. If the output is a Door Holder, activating the first address turns the output off (instantly, in 30 seconds, or never ­ depending upon
configuration. (See page 29). 4. If the output is a +24V power output, activating the first associated address has no effect, but the address must be in communication
with the panel. The second address for each output does the following: 1. If the output is a coded NAC, activating the second associated address activates stage 2 (evacuation). Note that the first address
must also be activated. 2. If the output is a synchronized NAC, activating the second associated address has no effect but the address must be in
communication with the panel. 3. If the output is a Door Holder, activating the second associated address has no effect, but the address must be in communication
with the panel. 4. If the output is a +24V power output, activating the second associated address has no effect, but the address must be in
communication with the panel.

32

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Two Stage Alert/Evacuation (Canada Only)

Configuration and Programming

3.4.2 Two Stage Panel Programming (V24.xx and lower)
All second stage timing is controlled by the FACP. All addresses must be programmed in the FACP. Null control-by-event (CBE) should be employed for unused second-stage points. Figure 3.11 illustrates the panel CBE programming.
Physical Connection

General Alarm

L1M1 FCM Type APND

L1M2 FCM Type FORC
OR(L1M1)

L1M3
FMM Type NON
A
Tracking = YES

Z200 Z200 = DEL(00.05.00(L1M3))

Z201 Z201 = SDEL(00.00.00(Z200))

EVAC Outputs

ALERT Outputs

CBE for EVAC Outputs = OR(Z2,Z201) CBE for ALERT Outputs = OR(Z1)

Z1 = Zone programmed to activate the alert stage. Z2 = Zone programmed to activate the evacuation stage in the event of a second alarm.

Figure 3.11 Canadian Two Stage for the NFS-3030/NFS2-3030
The sequence of operations is as follows. · A general alarm activates FCM L1M1 (Type code APND). · L1M2, which has been programmed via CBE for OR(L1M1), activates (Type code FORC). · L1M3 (Type code NONA) physically monitors L1M2 contacts. L1M3 activates. · Software Zone Z200 (RZON) is programmed to activate after a 5 minute delay with the equation Z200 = DEL(00.05.00(L1M3)).
Z200 will clear (or never activate) if L1M1 is acknowledged or if the system is reset before the 5 minute timer expires. · Software Zone Z201 (RZON) is programmed to activate after a 0 delay when Z200 activates. Z201 will only clear from a system
reset. · Alert Software Zone Z1 will activate when the Z1 equation is satisfied. ALERT = OR(Z1). A CBE (Control-by-event) in this
equation refers to any local CBE that is programmed into this point. It could be a CBE that programs four cross-zoned detectors, for example. · EVAC Software Zone Z2 will activate when the Z2 equation is satisfied. EVAC = OR(Z2, Z201). The CBE in this equation refers to any local CBE that is programmed into this point. It could be a CBE that programs four or more cross-zoned detectors, for example. Refer to the programming section of the FACP manual for more information on programming.
3.4.3 Two Stage Panel Programming (V25.xx and higher)
All two stage timing is controlled by the FACP. All addresses must be programmed in the FACP.
NFS2-640 and NFS-320
The following programming is required for Two-Stage Notification when using an ACPS-610 with an NFS2-640 or NFS-320 running V25.xx or higher software: · Panel Programming:
Regional Setting - Canada

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

33

Configuration and Programming

Two Stage Alert/Evacuation (Canada Only)

· Two-Stage Timer setting enabled (3 or 5 minutes) · Alert Stage:
Logic Zone - OR(ZF37,ZF38,ZF39) - mapped to the output(s) dedicated to Alert · Evacuation Stage:
Logic Zone - OR(ZF38) - mapped to the output(s) dedicated to Evacuation
NFS2-3030
The following programming is required for Two-Stage Notification when using an ACPS-610 with an NFS2-3030 running V25.xx or higher software:
· Panel Programming: Regional Setting - Canada
· Two-Stage Timer setting enabled (3 or 5 minutes) · Alert Stage:
An output(s) mapped to Special Function Zones ZF37, ZF38, and ZF39 or A Logic Zone - OR(ZF37,ZF38,ZF39) - mapped to the output(s) dedicated to Alert · Evacuation Stage: An output(s) mapped to Special Function Zone ZF38 or A Logic Zone - OR(ZF38) - mapped to the output(s) dedicated to Evacuation
The sequence of operations is as follows:
1. An alarm is initiated on the fire panel: ­ Special Function Zone ZF37 activates. ­ The output(s) programmed for Alert activates. ­ The Two-Stage timer begins.
2. Depending on panel programming, the Alert Stage will continue for the duration of the Two-Stage timer (3 or 5 minutes). Note: If a Signal Silence or System Reset is performed during the timer duration, ZF37 will deactivate and the output(s) mapped to the Alert Logic Zone will turn off.
3. Once the Alert Stage has expired: ­ Special Function Zone ZF37 deactivates. ­ The output(s) activated during the Alert Stage will remain active. ­ Special Function Zone ZF38 activates. ­ The output(s) programmed for Evacuation activate.
4. Outputs mapped to the Alert Logic Zone and the Evacuation Logic Zone will remain active until a Signal Silence or System Reset is performed, or an annunciator control point programmed as an Alarm Signal Cancel is activated.
Refer to the FACP's Programming and Operation manuals for additional information.

34

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

4.1 NAC Outputs *

Section 4: Applications

* Use listed end-of-line

resistor, P/N

ELR-2.2K (included),

to terminate Class B

*

*

*

NAC. ELRs are not used when Class A

return is wired.

acps-610_gppwr.cdr acps-610_nac.cdr

TB3

TB4

TB5

TB6

Note: The NAC outputs shown above are in a non-coded configuration.

Figure 4.1 Four NAC Outputs

NOTE: Active NACs will disable the power supply's charger.
4.2 Power Outputs

Power Output Circuit 1 Class B

Power Output Circuit 2 Class B
-OUT1
+OUT1

-OUT2 +OUT2

+OUT3 -OUT3

Power Output Circuit 3 Class B

+OUT4 -OUT4

Power Output Circuit 4
Class B

TB3

TB4

TB5

TB6

Note: The output is power-limited (Class 2) and nonsupervised. Use an end-of-line relay to supervise.

Figure 4.2 General Purpose Power Output

CAUTION: RISK OF EQUIPMENT DAMAGE!
! WHEN THE BATTERY CHARGER IS DISABLED, EACH POWER OUTPUT CONTINUOUS CURRENT IS 2.5 AMPS.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

35

Applications
4.3 Class B Initiating Device Circuit

Class B Initiating Device Circuit
UL listed power supervision relay (shown in energized state)
End-of-Line Resistor 47K ohm
Four-wire smoke detector

acps-610_smokdetapptyph.wmf

Four-wire smoke detector

SLC from last device

SLC to next device
Resettable 24 VDC power

FMM-1

*If the SLC device does not match the one in this figure, refer to the SLC manual appendix, which contains wiring conversion charts for type V and type H modules.

ACPS-610

Figure 4.3 Class B IDC
4.4 Synchronization
The ACPS-610 provides synchronization to Gentex, System Sensor SpectrAlert and SpectrAlert Advance Series, and Wheelock strobes and horns. When the ACPS-610 is set for synchronization, these NAC devices will flash and/or sound together. The ACPS-610 can also provide synchronization for bells and horns when used with a UZC-256 Universal Zone Coder if the NAC output is configured for coded signals only.
NOTE: Do not place strobes from any manufacturer onto a coded output. For example SpectrAlert and SpectrAlert Advance Series horns and strobes can not be synchronized with a UZC-256 or any coded output.

36

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Synchronization Refer to the following figures for application illustrations.

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Figure 4.4 Supervised Parallel Master/Slave Synchronization Connections

SLC from FACP or previous Device on
SLC

SLC
Sync Riser

ACPS-610

P/N ELR-2.2K (2.2K ohm endof-line resistor),

SLC
Sync Riser

To Next Device on SLC
P/N R-2.2K (2.2K ohm end-of-line resistor),

ACPS-610

P/N ELR-2.2K (2.2K ohm endof-line resistor),

ACPS-610

acps-610_Sync.cdr

NOTE:
· Application drawing is typical for System Sensor SpectrAlert and SpectrAlert Advance Series horns/strobes. This application may be used for Gentex or Wheelock electronically synchronized devices via PK-PPS programming.
· Do not "T-tap" sync riser. · The wiring from the FACP shall be within 20 feet (6.1 m) in conduit in the same room. · 50 ohm maximum loop resistance per sync riser. (Figure 4.4 shows one sync riser.) · In this configuration (synchronized power supplies connected in parallel by a sync riser), there
is a maximum of 50 parallel slaves. · For more information, see Figure 4.6.

Applications

37

Applications

+
38

UZC-256 Sync Feeder

The wiring from the FACP shall be within 20 feet (6.1 m) in conduit in the same room. See the UZC Installation Manual for more information on the applications that require power supervision.

+ +

-
SLC

+24V power source

-

-

--

+

+

NO COM NC NO COM NC
UZC-256

SLC

FACP

ALARM POLARITIES SHOWN

Sync Riser
SLC

SLC to Next Device

+ - +- +-

+ACPS-610

P/N ELR-2.2K (2.2 K ohm end-of-line resistor)

ACPS-610

P/N ELR-2.2K (2.2 K ohm end-of-line

P/N

- +

ELR-2.2K (2.2 K ohm

end-of-line

ACPS-610

P/N ELR-2.2K (2.2 K ohm end-of-line

ACPS-610_UZC.cdr
Figure 4.5 Supervised Synchronization Wiring Using UZC-256
ACPS-610/E Manual -- P/N 53018:G3 08/08/19

NOTE:
· Do not use visual devices on coded NAC outputs. · Do not put NAC devices on the UZC-256 Sync Feeder. · The wiring from the FACP shall be within 20 feet (6.1 m) in conduit in the same room. See the UZC
Installation Manual for more information on the applications that require power supervision. · The UZC-256 is compatible with Notifier control panels except the AFP-100 and AFP-200. · 50 ohm maximum loop resistance per sync riser. (Figure 4.5 shows one sync riser.) · For more information, see Figure 4.6.

Synchronization

Synchronization
ACPS-

Applications
To next floor

Output 1 Output 2 Output 3 Output 4 UZC Input

Output 4 Output 3 Output 2 Output 1 UZC Input

ACPS-610
SLC
Notification Zone

Up to 50

W

power

A

ELR

L

L

THIRD FLOOR

ACPS-610
SLC
Notification Zone

Output 1 Output 2 Output 3 Output 4 UZC Input

Out Out Out Out
UZC Input

ACPS-610
SLC
Notification Zone

W

ELR

A

Up to 50

L

power

L

ACPS-610
SLC

SECOND FLOOR

Notification Zone

Sync Riser

Output 1 Output 2 Output 3 Output 4 UZC Input

Output 4 Output 3 Output 2 Output 1 UZC Input

From FACP or last device
on

ACPS-610 SLC
Notification Zone

W

ELR

A

ELR

L

L

FIRST FLOOR

ACPS-610
SLC
Notification Zone

NOTE:
1. The NAC output devices from one power supply must be partitioned with walls and/or floors from the next power supplies and their NAC output devices.
2. Use only devices from the same manufacturer in each system. 3. 50 ohm maximum loop resistance per sync riser. (Figure 4.6 shows one continuous sync riser.)

Figure 4.6 Supervised Parallel Connection (Typical)

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

39

Section 5: Power Supply Calculations
Calculations must be done to determine standby and alarm DC current loads. Ampere-hour requirements must be calculated as well to determine battery size. In the following section, the term "secondary" refers to the ACPS-610's backup batteries: the term "primary" is reserved for the ACPS610's primary source of power, 120 VAC 50/60 Hz power or 220-240 VAC 50/60 Hz power. The term "standby" refers to the output current required when no fire alarm is present. The term "alarm" refers to the output current required when a fire alarm is present.
5.1 DC Current Draw Calculations
The ACPS-610 provides filtered 24VDC power that may be used for operating Notification Appliance Circuits (4 x 1.5 A) or other external devices (4 x 1.5 A with charger enabled or 4 x 2.5 A with charger disabled). The power for operating external devices is limited. Use Tables 5.1through 5.5 to determine if external loading is within the capabilities of the power supply. 1. Enter the current draw values for each output into Tables 5.1 through 5.4. Refer to the Device Compatibility document and the
device manufacturer's data sheets packaged with each device to find the standby and alarm current draws to use in these tables. 2. Enter the Standby Current Total and the Alarm Current Total from each of these four tables into Table 5.5, and add the figures in
Column A and Column B to determine total DC current draw.
NOTE: Columns A and B of Tables 5.1 through 5.5 are not battery calculations. They are current calculations to confirm whether the ACPS-610 can output enough DC current to support its devices during standby and alarm conditions.

OUTPUT 1

CATEGORY

COLUMN A Standby Current (amps)

COLUMN B Alarm Current (amps)

Qty X current draw=

Total

Qty X current draw=

Total

Power Supervision Relays

X

=

A

X

=

A

(EOLR-1)

4-Wire Smoke Detectors

X

=

A

X

=

A

4-Wire Smoke Detectors

X

=

A

X

=

A

Annunciators

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Notification Appliances

Not Applicable

X

=

A

Notification Appliances

X

=

A

Notification Appliances

X

=

A

Sum each column for totals

Output 1

A

Output 1

A

Standby Current

Alarm Current

Draw total:

Draw total:

Table 5.1 DC Current Draw Calculations, ACPS-610 Output 1

OUTPUT 2

CATEGORY

COLUMN A Standby Current (amps)

Qty X current draw=

Total

COLUMN B Alarm Current (amps)

Qty X current draw=

Total

Power Supervision Relays (EOLR-1)

X

=

A

X

=

A

4-Wire Smoke Detectors

X

=

A

X

=

A

4-Wire Smoke Detectors

X

=

A

X

=

A

Annunciators

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Table 5.2 DC Current Draw Calculations, Output 2

40

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

DC Current Draw Calculations

Power Supply Calculations

OUTPUT 2

CATEGORY

COLUMN A Standby Current (amps)

Qty X current draw=

Total

COLUMN B Alarm Current (amps)

Qty X current draw=

Total

Notification Appliances

X

=

A

Notification Appliances

Not Applicable

X

=

A

Notification Appliances

X

=

A

Output 2

Output 2

Sum each column for totals

Standby Current

A

Alarm Current

A

Draw total:

Draw total:

Table 5.2 DC Current Draw Calculations, Output 2

OUTPUT 3

CATEGORY

COLUMN A Standby Current (amps)

Qty X current draw=

Total

COLUMN B Alarm Current (amps)

Qty X current draw=

Total

Power Supervision Relays (EOLR-1)

X

=

A

X

=

A

4-Wire Smoke Detectors

X

=

A

X

=

A

4-Wire Smoke Detectors

X

=

A

X

=

A

Annunciators

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Notification Appliances

X

=

A

Notification Appliances

Not Applicable

X

=

A

Notification Appliances

X

=

A

Output 3

Output 3

Sum each column for totals

Standby Current

A

Alarm Current

A

Draw total:

Draw total:

Table 5.3 DC Current Draw Calculations, Output 3

OUTPUT 4

CATEGORY

COLUMN A Standby Current (amps)

COLUMN B Alarm Current (amps)

Qty X current draw=

Total

Qty X current draw=

Total

Power Supervision Relays (EOLR-1)

X

=

A

X

=

A

4-Wire Smoke Detectors

X

=

A

X

=

A

4-Wire Smoke Detectors

X

=

A

X

=

A

Annunciators

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Auxiliary Devices

X

=

A

X

=

A

Table 5.4 DC Current Draw Calculations, Output 4

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

41

Power Supply Calculations

DC Current Draw Calculations

OUTPUT 4

CATEGORY

COLUMN A Standby Current (amps)

Qty X current draw=

Total

COLUMN B Alarm Current (amps)

Qty X current draw=

Total

Auxiliary Devices

X

=

A

X

=

A

Notification Appliances

X

=

A

Notification Appliances

Not Applicable

X

=

A

Notification Appliances

X

=

A

Output 4

Output 4

Sum each column for totals

Standby Current

A

Alarm Current

A

Draw total:

Draw total:

Table 5.4 DC Current Draw Calculations, Output 4

Column A Standby Current (amps)

Column B Alarm Current
(amps)

ACPS-610 Power Supply Output 1 (Enter Totals from Table 5.1) Output 2 (Enter Totals from Table 5.2) Output 3 (Enter Totals from Table 5.3) Output 4 (Enter Totals from Table 5.4) Auxiliary 24V output
Sum each column for totals

Standby Current Draw
total:

0.13 A

A

A

A

A

0.5 A

A

Alarm Current

Draw total:

0.13 A

A

A

A

A

0.5

A

A

Note: STANDBY CURRENT TOTAL cannot exceed 6.0A/10.0A or 1.5 A/2.5 A. for any single output. ALARM CURRENT TOTAL cannot exceed 6.0 A or 1.5 A for any single output.
Table 5.5 Total ACPS-610 DC Current Draw Calculations

5.1.1 Calculating the Maximum Secondary Power Non-Fire Alarm Current Draw

Use the table below to determine the maximum current requirements of the secondary power source during non-fire alarm, standby conditions. The result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table 5.8 to determine the size of the batteries needed for the fire alarm system.
Results taken from the table below assume that, while in a non-fire alarm condition, batteries must feed the ACPS-610 (and any additional supplies) with the maximum rated power each supply can provide.

Device

Quantity

Alarm Current (in amps)

Alarm Current, from Table 5.5, col A

=

Additional Load

[ ]

X

=

Sum Column for Secondary Non-Fire Alarm Load

=

Total Current/Type

Table 5.6 Maximum Secondary Power Non-Fire Alarm Current Draw

5.1.2 Calculating the Maximum Secondary Power Fire Alarm Current Draw
Use the table below to determine the maximum current requirements of the secondary power source during fire alarm conditions. The result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table 5.8 to determine the size of the batteries needed for the fire alarm system.
Results taken from the table below assume that, while in a fire alarm condition, batteries must feed the ACPS-610 (and any additional supplies) with the maximum rated power each supply can provide.

42

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Calculating the Battery Requirements

Power Supply Calculations

Device

Quantity

Alarm Current (in amps)

Alarm Current, from Table 5.5, col B

=

Additional Load

[ ]

X

=

Sum Column for Secondary Fire Alarm Load

=

Total Current/Type

Table 5.7 Maximum Secondary Power Fire Alarm Current Draw

5.2 Calculating the Battery Requirements

5.2.1 Calculating the Battery Capacity

Use this table to determine the battery capacity needed for the system:

Current (amps) Secondary Non-Fire
Alarm (Standby) Current
(from Table 5.6)

X

Time (hours) Required

Required Standby Time (hours)

= _________AH

________________ Secondary Fire Alarm
Load (from Table 5.7)

X

________________

Required Fire Alarm Time (minutes):*

= __________AH

________________

X

________________

Sum Column for Total Secondary Amp Hours calculated

Multiply by the derating factor x 1.2 (See Note 6)

Battery Size ­ Total Secondary Amp Hours Required

= __________AH = __________AH = __________AH
= __________AH

* Following are decimal conversions for standard numbers of minutes:

5 minutes

0.084

10 minutes

0.167

15 minutes

0.250

30 minutes

0.5

60 minutes

1.0

120 minutes

2.0

Table 5.8 Secondary Power Standby and Fire Alarm Load

The following notes apply to Table 5.8:

1. NFPA 72 Local, Proprietary, Central Station, and Remote Station systems system requires 24 hours of standby power followed by 5 minutes in alarm.
2. NFPA 72 Auxiliary systems require 60 hours or standby power followed by 5 minutes in alarm. 3. Batteries installed in a system powered by an automatic starting engine generator need to provide at least 4 hours of standby power. 4. Emergency voice/alarm communications systems require 2 hours of operation in the alarm condition. Due to the sporadic nature of
voice operation, however, NFPA 72 permits 15 minutes of operation at a maximum connected load to equal 2 hours of normal use. 5. If the total exceeds 200 AH, an Uninterruptable Power Supply with sufficient amp-hour capacity is needed. The Uninterruptable
Power Supply must be UL-listed for Fire-Protective Signaling. (.Refer to pages 22 and 32 for trouble connections and FACP programming) 6. The following battery derating factors must be used for Canadian installations using an ACPS-610 charger. Derating factors are subject to local AHJ approval. · For 12 - 26 AH capacity, use derating factor of 1.2 · For 55 AH capacity, use derating factor of 1.8 · For 100 ­ 200 AH capacity, use derating factor of 2.5

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

43

Power Supply Calculations

Calculating the Battery Requirements

5.2.2 Calculating the Battery Size

Use this table to choose the battery size, in amp-hours, needed to support the fire alarm system. The ACPS-610 can charge batteries from 12 to 200 AH. Select batteries that meet or exceed the Total Amp-Hours calculated in Table 5.8 and that are within the acceptable battery charger range. Write the amp-hours requirements on the Protected Premises label.

Battery Size

Voltage Rating

12 AH

12 volts

26 AH

12 volts

55 AH

12 volts

100 AH

12 volts

Number Required
two
two
two for 55 AH four for 110 AH two for 100 AH four for 200 AH

Part Number* BAT-12120 BAT-12260 BAT-12550 BAT-121000

Backbox
(Order Part Number) CAB-PS1, SBB-A4, SBB-B4,
SBB-C4, SBB-D4, BB-25 SBB-A4, SBB-B4,
SBB-C4, SBB-D4, BB-25 NFS-LBB
BB-100 BB-100
BB-200

Table 5.9 Selecting the Battery Size

* Manufactured to our specifications by WUHAN SOTA ENERTECH, INC.  Red version available for some models. Check for availability.

NOTE: Battery size is limited to 12 AH minimum to 200 AH maximum using the internal ACPS-610 battery charger.

44

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Index

Numerics
2.2K ohm end-of-line resistor 37 24VDC 40
resettable 36 47K ohm end-of-line resistor 36 8/8/19 added Class B to Power Output circuits per Ted I - JKS 35
A
AC loss detection, delay 7 AC Power 7 ACPS-2406 replacement 13
Address block 23, 24
address block 23 address decade 23 Addressing 23
Rotary switch, setting address with 23 SLC addresses 23 SW3,setting address with 24 AFP-100 38 AFP-200 38 Alarm DC current loads 40 AM2020/AFP1010 32 Ampere hour requirement calculations 40
Applications 35­38
Class B IDC 36 General Purpose Power 35 NAC Outputs 35 Supervised Master/Slave Synch, non-cod-
ed 37 Supervised Synch Using UZC-256 38 Auxiliary output 7 auxiliary output 7
B
Base address 23 last digit 0 or 5 24 lowest for AMPS-24 23
Base address, Setting the 23, 24 Batteries 7, 13, 15, 16, 19
Size determination 40
Battery calculations 42­44 Battery charger 7, 19, 44
Battery/battery charger supervision 7 BB-100/200 Cabinet 9
BB-25 Cabinet 9, 15
BB-55 Cabinet 9 Bells, synchronization of 36 Board Layout 10 Brownout detection 7
C
CAB-3/4 Series Cabinet 17
CAB-4 Series Backbox 9, 13, 17
CAB-PS1 Cabinet 13 Charge Selection Switch (SW4) 19 Class B Initiating Device Circuit 36 CLIP (Classic Interface Protocol) 7 Control-by-event (CBE) 33

CPS-24/E power supply board Specifications 7
Current Draw Calculations 40­42
D
DR-PS1 13
E
Electronic Signal Silence virtual address 23
EQ Series Backbox 13
F
FlashScan® 7 FMM-1 36
G
General Purpose Power 22
Gentex 7, 36, 37
Ground Fault Detection 7
Ground fault detection 11, 20, 21
H hex nuts 14, 15
horns 7 Horns, synchronization of 36
I
Installation in a BB-100 Cabinet 16 in a BB-200 Cabinet 16 in a BB-25 Cabinet 15 in a CAB-4 Series Backbox 13 in a CAB-PS1 Cabinet 13
Installation Standards and Codes 8
K keps nuts 13, 16
L
LED Indicators 11
M
Monitor AC Fail 23 Monitor Battery 23 Monitor Earth Fault 23 Monitor General 23
N
NACs
coded 7, 22 non-coded 7, 22
Output applications 35
P
Panel Programming 32 Panel Programming Requirements

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Software Type ID Codes 32 Power 7
AC Power 18 DC Power 19 Installation steps 18 Power Supervision Relay 36 Power Supply Calculations 40
Power supply calculations 42­44
R
Rotary Switch 23 setting address decade 23
S
Selectable charger current see also Charge Selection Switch
self-threading screws 15 SLC 22
Address Selection 24 determining address block size 23 Snap-on cover 13 Software Type ID Codes 32 Specifications 7 Output Circuits 7 Primary Power 7 Secondary Power (Battery) Charging Cir-
cuit 7
SpectrAlert® AdvanceTM Series 7, 36, 37 can not be synchronized with UZC-256 29,
36
SpectrAlert® Series 7, 36, 37 can not be synchronized with UZC-256 29,
36 Standby DC current load 40
Strobes 7, 36 do not use on coded output 29, 36
use of SpectrAlert® Series in application 37
Supervised Parallel Connection 39 SW3 24
Synchronization 7, 36
See also NACs, Strobes, UZC-256
System current draws 42­44
System Sensor 36
T
Temporal Pattern 32 Trouble Reporting 31 T-tapping 37
Two Stage 32, 33
Control-by-event (CBE) programming 33 Output circuits set to coded NAC 32 Panel Programming
V24.xx or lower 33 V25.xx or higher 33 sequence of operations 33 Two-Stage Alert/Evacuation 32 Type ID Codes 32
45

Index
U USB 7, 8, 25
cable 11, 25, 26 UZC-256 (Universal Zone Coder) 7, 36
panel compatiblilty 38
W Wheelock 7, 36, 37
Wire size 8
Wiring 17­21
Nonpower-limited 17 Outputs 1 through 4 and UZC-256 connec-
tions 22 Power-limited 17

46

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

Manufacturer Warranties and Limitation of Liability

Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009). The Products manufactured and sold by Manufacturer are date stamped at the time of production. Manufacturer does not warrant Products that are not manufactured by it in its Northford, Connecticut facility but assigns to its Distributor, to the extent possible, any warranty offered by the manufacturer of such product. This warranty shall be void if a Product is altered, serviced or repaired by anyone other than Manufacturer or its authorized Distributors. This warranty shall also be void if there is a failure to maintain the Products and the systems in which they operate in proper working conditions.

MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY

AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH

RESPECT TO THE PRODUCTS, TRADEMARKS, PROGRAMS AND SERVICES

RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION,

INFRINGEMENT, TITLE, MERCHANTABILITY, OR

FITNESS FOR ANY

PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY

PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS

A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS

PRODUCTS.

This document constitutes the only warranty made by Manufacturer with respect to its products and replaces all previous warranties and is the only warranty made by Manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. Manufacturer does not represent that its products will prevent any loss by fire or otherwise.

Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion, each part returned by its authorized Distributor and acknowledged by Manufacturer to be defective, provided that such part shall have been returned to Manufacturer with all charges prepaid and the authorized Distributor has completed Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.

Warn-HL-08-2009.fm

ACPS-610/E Manual -- P/N 53018:G3 08/08/19

47

NOTIFIER 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 www.notifier.com



References

Acrobat Distiller 19.0 (Windows)