PKY620T – TECH DATA

ActronAir Digital

PDF preview unavailable. Download the PDF instead.

9590-0014-03B-PKY620T-Ver-13
TECHNICAL SELECTION DATA

PKY620T

TRI-CAPACITY PACKAGE UNIT

63.00 kW
3 Phase Tri-Capacity

3 THREE PHASE TRI-CAPACITY
EC PLUG FAN

LOUVRE

LOW NOISE FAN

UNIT FEATURES

SPECIFICATION SUMMARY

· Compliant Scroll Compressors · Tri-Capacity 33% 67% 100% Capacity Stages · Dual Bi-Flow Thermostatic Expansion Valves · Full Factory Charged with R-410A Refrigerant · Return Air Filter Rails Fitted · Two Speed Outdoor Fans · Hydrophilic Blue Coat Coil Fin Protection - Indoor and Outdoor Coils · Outdoor Coils Condensate Drain Socket · Louvred Outdoor Coil Guard · External Stainless Steel Screws · Adaptive Demand Defrost · EC Variable Speed Backward Curve Plug Fan · Adjustable Indoor Airflow via Control Interface · Foil Faced Polyethylene Insulation

PACKAGE UNIT MODEL
(3) COOLING CAPACITY (kW) (3) SENSIBLE CAPACITY (kW) (4) HEATING CAPACITY (kW) (5) COOLING INPUT POWER (kW) (5) HEATING INPUT POWER (kW) EER COP (6) INDOOR AIRFLOW (l/s) - MIN. / NOMINAL / MAX.

PKY620T

(1) TOTAL (2) NETT

63.00

60.80

47.80

45.60

60.00

62.47

20.50

20.15

3.07

2.97

2.98

3.10

2500 / 3200 / 3900

UNIT OPTIONS
· Reverse Handing with Various Airflow Options · (9) Economy Starter Kit (Available on LHS / RHS only) · Outside Air Damper · Low Ambient / High Static Outdoor Fans · Compressor Soft Starters · Phase Protection · Additional Full Coil Coat Protection

OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) - LOW / HIGH OUTDOOR SOUND POWER LEVEL dB(A) - LOW / HIGH POWER SUPPLY (2) RATED LOAD AMPS (7) FULL LOAD AMPS (8) CIRCUIT BREAKER AND CABLE AMPS APPROXIMATE STARTING AMPS

60.0 / 65.0 77.0 / 82.0 400V / 3Ph+N / 50Hz
39.2 53.9 63.0 140.0

CONTROL FEATURES
ActronAir CP05 / CP10 · Auto / Cool / Heat / Fan Only Modes · 7- Day Time Clock with 2 On/Off Events per Day · 12 Programmable Special Days with 2 On/Off Events per Day · Daylight Saving Time Function · Indoor Coil Anti-Freeze Protection · HP / LP Safety Protection · Alarm Fault Data Logger · LCD Screen Displays Operating Status, Mode & Menu Information · Night Mode Function

WEIGHT (kg)

937

(1) Based on unit rating excluding indoor fan kW. (2) Measured and tested in accordance with AS/NZS 3823.1.2. (3) At 27°C DB / 19°C WB entering air temperatures and 35°C ambient. (4) At 20°C DB entering air temperature and 7°C DB / 6°C WB ambient. (5) Input power includes indoor fan kW. (6) Max. - Min. airflow application range. (7) Full Load Amps are based on compressor and fan motors' maximum expected current. (8) See Specifications sheet for cable size and circuit breaker size details. (9) Room Air Sensor needs to be relocated by the installer specific to site requirements.
Note: Use input power to estimate running cost.

CONTROL OPTIONS
ActronAir CL01-2 (BCA Compliant) - Purchased Separately · Available in White or Grey · 7- Day Time Clock with 2 On/Off Events per Day
Optional BMS Control - Purchased Separately · MODBUS 485 / BACNET 485 / BACNET TCP/IP

UNIT COMPLIANCE
· MEPS 2012 · Demand Response AS4755.3.1:2012 · BCA Compliant with CL01-2 Control Interface · EMC Compliant

Optional 3rd Party Control Inputs - Standard Inclusion R
· 0-10VDC / 24VAC / Volt Free Digital Input

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

Page 1 of 12

9590-0014-03B Ver. 13 231027

CAPACITY SELECTION DATA

PKY620T

63.00 kW
3 Phase Tri-Capacity

COOLING PERFORMANCE

AIR ENTERING

OUTDOOR INDOOR

DB - °C WB - °C

16

17

25

18 19

20 21 22

16

17

18

30

19

20

21

22

16

17

18

35

19

20

21 22

16

17

18

40

19

20

21 22

16

17

18

45

19

20

21 22

16 17

50

18 19

20

21 22

TOTAL CAPACITY
kW
64.28 65.64 67.23 69.16 71.01 72.88 75.11 61.53 62.93 64.42 66.27 68.15 69.82 71.92 58.94 59.92 61.30 63.00 64.77 66.35 68.35 56.11 56.62 57.77 59.40 61.02 62.49 64.38 52.91 52.94 53.95 55.38 56.84 58.24 59.96 49.31 49.34 49.78 50.93 52.22 53.61 55.02

20 38.67 35.37 31.96 28.52 25.09
37.51 34.18 30.81 27.42 23.98
36.20 32.88 29.52 26.14 22.70
34.69 31.45 28.11 24.75 21.31
33.10 29.88 26.57 23.22 19.79
31.35 28.17 24.88 21.54 18.13

21 41.88 38.59 35.23 31.84 28.42 17.40
40.67 37.41 34.07 30.69 27.27 23.81
39.31 36.07 32.80 29.38 25.99 22.54
37.89 34.64 31.34 28.02 24.61 21.21
35.89 33.04 29.79 26.49 23.10 19.69
34.13 31.30 28.11 24.79 21.44 18.04

22
44.61 41.75 38.44 35.12 31.67 28.19 24.72 43.40 40.58 37.29 33.97 30.55 27.08 23.62 42.08 39.26 35.98 32.67 29.27 25.86 22.41 40.55 37.78 34.57 31.27 27.92 24.50 21.02 38.93 36.22 32.98 29.71 26.36 22.99 19.57 37.13 34.06 31.23 28.02 24.70 21.31 17.92

TOTAL SENSIBLE CAPACITY - kW

AT DB TEMPERATURE ONTO INDOOR COIL - °C

23

24

25

26

27

47.65

50.60

53.49

44.93

47.55

50.53

53.42

41.64

44.80

47.43

50.43

53.36

38.34

41.46

44.65

47.29

50.35

34.94 31.49 28.01

38.14 34.72 31.31

41.33 37.96 34.57

44.48 41.18 37.80

47.45 44.31 40.99

46.43

49.35

52.24

43.60

46.36

49.33

52.21

40.45

43.63

46.27

49.23

52.14

37.17

40.32

43.46

46.15

49.15

33.80 30.38 26.94

37.02 33.63 30.20

40.18 36.85 33.45

43.33 40.04 36.69

46.00 43.18 39.86

45.07

48.00

50.79

41.96

45.01

47.97

50.76

39.12 35.91 32.55

42.17 39.04 35.77

44.94 42.18 38.89

47.89 44.81 42.03

50.79
47.80 44.68

29.14 25.71

32.39 28.97

35.60 32.22

38.76 35.43

41.85 38.60

43.58

46.43

40.52

43.54

46.43

37.70 34.48

40.42 37.61

43.44 40.31

46.40 43.34

49.22 46.34

31.15

34.36

37.48

40.59

43.26

27.73 24.35

30.95 27.61

34.22 30.87

37.34 34.08

40.45 37.21

41.91

38.89

41.89

44.74

36.11

38.81

41.82

44.71

32.90

36.01

38.70

41.73

44.70

29.60

32.78

35.91

38.61

41.64

26.26 22.82

29.50 26.14

32.68 29.34

35.79 32.57

38.88 35.68

40.04 37.12

40.04

34.02

37.05

40.03

31.17

34.24

36.96

39.96

42.85

27.92

31.08

34.16

36.86

39.87

24.58 21.18

27.83 24.44

30.96 27.67

34.07 30.87

36.77 33.93

28
56.27 53.25 50.21 47.42 44.14
55.02 52.08 49.00 46.31 43.00
50.69 47.71 44.53 41.73
49.20 46.25 43.10 40.29
47.46 44.59 41.52 38.75
42.79 39.77 36.65

29
56.21 53.15 50.04 47.25
54.97 51.95 48.86 46.09
53.56 50.65 47.57 44.85
49.13 46.13 42.95
47.47 44.50 41.40
42.70 39.66

30
59.03 56.10 53.03 49.85
54.87 51.80 48.71
49.77 49.56 46.57
51.91 49.03 45.99
47.40 44.38
45.55 42.59

HEATING PERFORMANCE

WB TEMP ON OD COIL- °C
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

16

TH

IH

39.33

36.97

41.67

38.75

44.08

40.55

46.65

41.75

49.35

42.93

52.15

44.85

54.87

48.83

57.80

54.91

60.89

60.89

64.14

64.14

67.63

67.63

71.16

71.16

74.92

74.92

78.88

78.88

82.90

82.90

HEATING CAPACITY - kW AT DB ENTERING INDOOR - °C

18

TH

IH

39.17

36.82

41.48

38.58

43.86

40.35

46.43

41.56

49.07

42.69

51.86

44.60

54.51

48.51

57.39

54.52

60.41

60.41

63.63

63.63

67.06

67.06

70.58

70.58

74.22

74.22

78.12

78.12

82.17

82.17

20

TH

IH

38.98

36.64

41.28

38.39

43.68

40.18

46.19

41.34

48.78

42.44

51.53

44.32

54.17

48.21

57.01

54.16

60.00 60.00

63.20

63.20

66.45

66.45

69.93

69.93

73.49

73.49

77.44

77.44

81.34

81.34

22

TH

IH

38.82

36.49

41.10

38.22

43.46

39.98

45.92

41.10

48.49

42.19

51.21

44.04

53.81

47.89

56.57

53.75

59.58

59.58

62.66

62.66

65.88

65.88

69.25

69.25

72.77

72.77

76.62

76.62

80.45

80.45

24

TH

IH

38.65

36.33

40.89

38.03

43.21

39.76

45.66

40.86

48.23

41.96

50.91

43.78

53.46

47.58

56.19

53.38

59.04

59.04

62.11

62.11

65.30

65.30

68.55

68.55

72.10

72.10

75.80

75.80

79.56

79.56

TH - Total Heating Capacity (kW). IH - Integrated Heating Capacity (kW)
Includes defrost losses.

AIRFLOW CORRECTION MULTIPLIER

% VARIATION INDOOR AIRFLOW (l/s) TOTAL COOLING SENSIBLE COOLING HEATING FACTOR

-22% 2500 0.956 0.884 0.985

-15% 2720 0.972 0.919 0.990

-10% 2880 0.982 0.947 0.993

-5% 3040 0.991 0.974 0.997

NOMINAL
3200 1.000 1.000 1.000

+5% 3360 1.008 1.026 1.001

+10% 3520 1.016 1.051 1.003

+15% 3680 1.023 1.077 1.005

+22% 3900 1.032 1.109 1.007

NOTES: 1. No allowance has been made for the effect of indoor fan motor. 2. Selection tables are based on nominal airflows. Correction factors must be
applied for selection away from these conditions.
R

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

Page 2 of 12

9590-0014-03B Ver. 13 231027

63.00 kW
3 Phase Tri-Capacity

INDOOR FAN DATA / FAN CURVE

PKY620T

FAN PERFORMANCE DATA

External Static Pressure (Pa)

Airflow

50

(l/s)

% Spd.

W

100

% Spd.

W

150

% Spd.

W

200

% Spd.

W

250

% Spd.

W

300

% Spd.

W

350

% Spd.

W

400

% Spd.

W

450

% Spd.

W

500

% Spd.

W

2500 48.2 869 51.5 1030 56.1 1269 59.9 1505 63.8 1765 67.9 2028 72.0 2297 75.8 2579 78.8 2875 83.2 3310

2600 49.2 905 53.3 1107 57.5 1350 61.3 1596 65.3 1864 69.5 2134 73.5 2398 76.8 2683 79.6 2973 84.6 3490

2700 50.2 941 55.1 1188 58.9 1435 62.8 1694 66.9 1965 71.1 2239 75.0 2495 77.8 2792 81.1 3096 88.1 3550

2800 52.2 1023 56.6 1275 60.3 1523 64.3 1792 68.6 2073 72.6 2346 76.1 2627 78.9 2913 83.2 3235

2900 54.1 1106 58.0 1357 61.9 1623 66.0 1900 70.4 2191 74.1 2468 77.2 2751 80.1 3032 85.5 3372

3000 55.9 1196 59.5 1446 63.5 1725 67.8 2013 71.9 2303 75.4 2580 78.5 2869 82.6 3198

3100 57.5 1284 61.2 1548 65.1 1830 69.7 2133 73.4 2406 76.9 2703 80.1 3001 84.8 3371

3200 59.1 1368 62.9 1652 67.1 1945 71.4 2238 75.0 2509 78.4 2854 82.4 3192

3300 60.9 1480 64.6 1764 69.2 2059 73.1 2355 76.6 2676 80.1 3044 84.8 3363

3400 62.7 1594 66.8 1887 71.1 2184 74.8 2486 78.3 2850 82.4 3188

3500 3600

64.5 1708 68.9 2010 72.8 2315 76.4 2641 79.9 3009 85.0 3342 66.7 1837 70.9 2144 74.6 2452 78.1 2802 82.4 3155

MOTOR / BLOWER LIMIT

3700 69.0 1975 72.8 2277 76.4 2603 79.9 2961 85.0 3315

3800 71.1 2107 74.8 2411 78.2 2769 82.5 3130

3900 73.1 2244 76.6 2578 80.0 2952 85.4 3292

NOTES: % Speed = Indoor Fan Speed Control Setting, in percent
(Value is set on the Control Interface via Service Menu *). W = Indoor Fan Power, Watts
- Data in the box indicates Factory Default Setting.
*Service Service Settings Thermoregulation Thermoregulation Gfc4
INDOOR UNIT FAN CURVE
505000

Thermoregulation
Supply Fan Minimum speed: Medium speed: Maximum speed: Supply Fan Temp. Minimum Temp. Maximum Temp.

Gfc4
48.2% 62.9% 90.0% 5.0oC 50.0oC

Set Fan Speed

445500

EXTERNAL STATIC PRESSURE (PA)

440000

MOTOR / BLOWER LIMIT

MOTOR / BLOWER LIMIT

335500

303000

80%

85% Speed

Spee9d0%

Speed

225500

75% Speed

202000

65% Speed 70% Speed

151500

60% Speed

62.9% Speed

101000

55% Speed

5050

50% Speed

00 22550000 22660000

2270000 22880000 22990000 30300000

33110000

33220000

3330000 34340000 33550000

33660000

33770000

Nominal Airflow = 3200 l/s

APPLICATION RANGE

AIRFLOW (l/s)

38380000

33990000 40400000

41401000

NOTE
Fan Performance Data and Fan Curve shown is at dry coil and with no air filters installed. Consider external static pressure drop specific to your design requirements. Airflow should be reduce with respect to the moisture content in the air. Please review filter manufacturer for application. 2.5 m/s face velocity point will occur at 4097 l/s.

R

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

Page 3 of 12

9590-0014-03B Ver. 13 231027

PACKAGE UNIT DIMENSIONS

2365 O/A

A

B

C

OUTDOOR COIL

OUTDOOR COIL

2305 O/A
YY

INDOOR COIL PLUG FAN

PKY620T

DIMENSION (H x W x D) = 1695 x 2305 x 2365 SUPPLY DUCT (H x W) = 650 x 580 RETURN DUCT = 900 x 700

490

670

OUTDOOR COIL 445

330

670 OUTDOOR COIL

CONDENSATE DRAIN 25.4 (1") BSP SOCKET

PLUG FAN INDOOR COIL
OUTDOOR COIL

OUTDOOR COIL

D

E

XX

125

1470 1695 O/A
100

ELECTRICAL ACCESS 2335
FRONT VIEW

F 120
TOP VIEWS
100
315 425

900

1600

650

385

525

580

770

700

100

2250 80

LIFTING POINT 4 x Ø 20mm

150

CONDENSATE DRAIN

25.4 (1")

BSP FEMALE THREAD

2290

SIDE VIEW

UNIT AIR HANDING CONFIGURATION
(LH / RH)

NO. OF POINTS

UNIT WEIGHT
(kg)

A

LEFT HANDING
RIGHT HANDING

6

937

139

6

937

130

CORNER WEIGHTS (kg)

B

C

D

E

188

57

186

279

207

106

192

228

CENTRE OF GRAVITY (mm)

F

XX

YY

88

1115

1060

74

63.00 kW
3 Phase Tri-Capacity

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

Page 4 of 12

R
9590-0014-03B Ver. 13 231027

ACCESS AREAS / BASE MOUNT

PKY620T

SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES

500 mm AIRFLOW ALLOWANCE

* For reverse handing, service clearance for plug fan and
airflow clearance for hood will be reversed.
** If the optional hood is not installed, 500 mm clearance is
required for service access.

1000 mm SERVICE CLEARANCE (COMPRESSOR & ELECTRICALS)

OUTDOOR COIL

OUTDOOR COIL

OUTDOOR COIL 500 mm AIRFLOW
ALLOWANCE

64

1000 mm* SERVICE CLEARANCE (PLUG FAN)

HEIGHT CLEARANCE = 1500

DUCT WORK

1000 mm FILTER ACCESS

DUCT WORK

UNIT BASE DIMENSIONS Down discharge/down return option shown below

770

MTG C-C

375

DISTANCE

770

MTG C-C

DISTANCE

375

PLUG FAN INDOOR COIL

556 mm 300 mm* AIRFLOW ALLOWANCE

300 mm OUTSIDE AIR SECTION SERVICE CLEARANCE
OPTIONAL HOOD**
800 mm
THIRD ANGLE
PROJECTION
NOTES: 1. Do not scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for mounting hole details. 2. S ervice Access Areas and Spaces for Airflow Clearances given above are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000 mm between the units or between the unit and the outside perimeter is available. 3. M inimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow. 4. U nder all circumstances, condenser air must not recirculate back onto condenser coil. Keep all clearance free of any obstructions. 5. S TACKING OF UNITS: Ensure that minimum airflow and clearances are met. 6. MTG C-C DIST = Mounting Centre to Centre Distance. 7. Use M12 bolt for feet mounting. 8. LH / RH refers to Left Hand or Right Hand location of supply air. 9. Diagrams are left handing.

63.00 kW
3 Phase Tri-Capacity

1167 MTG C-C DISTANCE

1107

32

2334 O/A

1167 MTG C-C DISTANCE

1066

64

32

64

1341

788

64

2289 O/A

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

Page 5 of 12

R
9590-0014-03B Ver. 13 231027

SOUND DATA

PKY620T

SOUND DATA
Outdoor Radiated

PKY620T-6Q1

OutdooSroRunaddiPaotewder Level (SWL)

Sound Power

Level (SWLF) an

Sound Power Level

Speed

dB(A)

Fan

Sound Power Level

Speed Low dB(A)

77.0 63

Low

High 77.0

82.0

High

82.0

Octave Band Centre Frequency (Hz), dB

125Octave B25an0d Centr5e0F0requency1k(Hz), dB 2k

125 83.8 250 76.5 500 73.8 1k

83.888.8 76.5 81.5 73.8 78.870.7

88.8

81.5

78.8

75.7

70.7 2k 75.765.9
70.9

65.94k 70.598.0
63.0

4k
58.08k 635.03.0
58.8

Sound Pressure

Level (SPL)

8Skound Pressure

Level dB(A) 53@.03m @1m

58.8---

---

---

---

Indoor Outlet
Indoor Outlet Sound Power Level (SWL)

Sound Power

Level (SWALi)rflow

Airflow SeAttiirnflgow

Setting

Li/s

Minimum

Min Nominal

Nom32in25a00l00

Max Maxi3m9u0m0

PAowSirlef/olsrounLwdevelPowSdeoBru(AnLde) vel

Octave Band Centre Frequency (Hz), dB

125Octave 2B5a0nd Centr5e0F0requency1k(Hz), dB 2k

4k

2d5B0(0A)

6731.2

125 75.5 250 72.6 500 69.2 1k 64.9 2k 60.74k 56.58k

32770710..92

77.9

8725..5582.5

72.6 79.5

79.5

69.2 76.1

76.1

64.9 71.5

71.56670..07

67.06546..45

64.55483..26

398030.2

83.2 87.287.2 85.2 85.2 81.5 81.5 76.6 76.671.8 71.869.8 69.683.0

Sound Pressure

Level (SPL)

8SkoLuenvdelPdreBs(Asu) re

53@.63m @1m

58.2------

-----

63.0---

---

OUTDOOR RADIATED

PKPYK62Y06T2-60QT1SSoouunnddPPoowweer Leveell
100.0

90.0

80.0

70.0

60.0

50.0

Low

High 40.0

125

250

500

1k

2k

4k

8k

Octave Band Centre Frequency (Hz)

INDOOR OUTLET

PKPYK62Y06T2-60QT1SSoouunnddPPoowwer Levveell
100.0

90.0

80.0

70.0

60.0

50.0

Nominal

Min

Max 40.0

125

250

500

1k

2k

4k

8k

Octave Band Centre Frequency (Hz)

63.00 kW
3 Phase Tri-Capacity
Octave Band Sound Power Level (dB) Octave Band Sound Power Level (dB)

NOTES:
Radiated sound power levels are based on ISO 3743-1.

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

Page 6 of 12

R
9590-0014-03B Ver. 13 231027

63.00 kW
3 Phase Tri-Capacity

SPECIFICATIONS

PKY620T

CONSTRUCTION
CABINET BASE CABINET TOP AND SIDES
SURFACE FINISH
INSULATION
TYPE

1.9 mm Galvanised Steel 0.9 - 1.6 mm Galvanised Steel 65 microns Baked Polyester Powder Coat
Foil Faced Polyethylene

SOUND LEVEL * dB(A)

SOUND PRESS. - Low / High

60.0 / 65.0 @ 3 m Distance

SOUND POWER LEVEL - Low / High 77.0 / 82.0

* Sound data is based on the outdoor fan's manufacturer sound level data.

ELECTRICAL
POWER SUPPLY - 50 Hz

400 Volts x 3 Phase + Neutral

VOLTAGE RANGE (min - max)

376V - 440V

FULL LOAD AMPS * - Phase 1

53.9

FULL LOAD AMPS * - Phase 2 & 3

53.9 and 53.9

RATED LOAD AMPS**

39.2

APPROX. STARTING AMPS

140.0

IP RATING

IP44

IMPORTANT - The local electricity authority may require limits on starting current and voltage drop, please check prior to purchase.
* Full Load Amps are based on compressor and fan motor's maximum expected current.
** Rated Load Amps are measured and tested in accordance with AS/NZS3823.1.2.

CABLE SIZE & CIRCUIT BREAKER SIZE Suggested minimum cable size should be used as a guide only, refer to the accordance
with the latest edition of the AS/NZS 3000 "Australian/New Zealand Wiring Rules" for more
details.

CABLE SIZE (MAIN LINE)

16.0 mm2 (SUGGESTED MINIMUM)

CIRCUIT BREAKER SIZE - Amps

63.0

OUTDOOR COIL
TUBE TYPE FIN TYPE FACE AREA (m sqr) - Coil 1 & 2 FIN SPACING (per m) - Coil 1 & 2 COIL COATING

Copper - Rifle Bore Aluminium - Corrugated 1.45 & 2.75 472 & 472 Hydrophilic Blue Coat Coil Fin Protection

OUTDOOR FAN

NUMBER OF FANS x TYPE

3 x Axial Low Noise

NUMBER OF BLADES PER FAN

5

INPUT kW / FULL LOAD AMPS

0.50 / 2.62 each fan

MOTOR TYPE / DRIVE TYPE

6 Pole External Rotor / Direct Drive

FAN SPEED CONTROL

2 Speed via Capacitor

The standard type outdoor fans fitted to this unit will accept up to 20 Pa of external static resistance.

INDOOR COIL
TUBE TYPE FIN TYPE FACE AREA (m sqr) FIN SPACING (per m) COIL COATING

Copper - Rifle Bore Aluminium - Louvre 1.64 (interlaced) 472 Hydrophilic Blue Coat Coil Fin Protection

INDOOR FAN
NUMBER OF FANS x TYPE INPUT kW / FULL LOAD AMPS MOTOR TYPE / DRIVE TYPE

1 x Backward Curve Plug Fan 2.20 / 6.0 Variable Speed EC Motor / Direct Drive

COMPRESSOR

NUMBER PER UNIT x TYPE

2 x Scroll (Hermetic)

FULL LOAD AMPS - (Comp. 1 & 2)

14.3 & 25.5

LOCKED ROTOR AMPS - (Comp. 1 & 2) 101.0 & 140.0

STARTING METHOD

D.O.L. (optional soft starter)

REFRIGERATION SYSTEM
REFRIGERANT TYPE
EXPANSION CONTROLTYPE x NO. PER UNIT
FACTORY CHARGE - (Crt. 1 & 2)

R-410A Bi-Flow TXV (Thermostatic Valve) x 2 7,200 grams & 12,700 grams

PROTECTION DEVICES
HIGH PRESSURE CUTOUT SWITCH LOW PRESSURE CUTOUT SWITCH COMPRESSOR MOTOR TEMP. INDOOR FAN OVERLOAD OUTDOOR FAN OVERLOAD SUMP HEATER WATTS - (Comp. 1 & 2)

Nonadjustable (Automatic Reset) Nonadjustable (Automatic Reset) Internal Thermal Cut-Out Full Electronic Monitoring Internal Thermal Cut-Out 30W & 90W

ELECTRIC CONTROLS
DEFROST METHOD DEFROST TYPE CONTROL CIRCUIT BREAKER
OPTIONAL THIRD PARTY BMS / CONTROLLER INPUTS

Reverse Cycle
Adaptive Demand Defrost
16.0 Amps
MODBUS 485 BACNET 485 BACNET TCP / IP 0-10VDC / 24VAC Third Party Input

OPERATING RANGE
It is essential that the unit is correctly sized for the application and operates within its recommended range of operating conditions as shown below.

MODE Cooling

RANGE
Max. Min.

INDOOR AIR INTAKE TEMPERATURE
29°C DB / 19°C WB
20°C DB / 15°C WB

OUTDOOR AIR INTAKE TEMPERATURE
50°C DB
15°C DB

Heating

Max. Min.

24°C DB 16°C DB

21°C DB / 16°C WB -10°C DB

IMPORTANT - Lower ambient available on request. Contact your nearest ActronAir office for more details.

AIR FILTER PROVISION
All return air including fresh air must have adequate filters supplied and fitted by the installing contractor. Filters are to be located in the return air filter retainer in the unit or in accessible location between the return air grille and the unit.

ActronAir does not supply or make any provisions for return air filter.

FILTER RAILS FITTED (Filters not Supplied)

FILTER SIZES - H x W x T (mm)

508 x 621 x 100

QUANTITY

4

407 x 621 x 100 2

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

Page 7 of 12

R
9590-0014-03B Ver. 13 231027

3 PHASE + NEUTRAL 400 (415) V 50 Hz SUPPLY

WIRING DIAGRAM

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

63.00 kW
3 Phase Tri-Capacity

NEUT
LINE 1 LINE 2 LINE 3
EARTH

MSCB-1 20 A

CMC-1

O/L SET 17A (620) O/L SET 19A (700)

MSCB-2

40 A

CMC-2

O/L SET 34A (620) O/L SET 36A (700)

MSCB-3 10 A

IFC-1

O/L SET 10A

CM-1 3

CM-2 3

IF-1 3 EC

Vsp / Ain1U /
I02
GND

SCREEN WIRE

Y1 GND

RSA

35 RSA

RSB

36 RSB

MOTOR TERMINAL BLOCK

DATA (SERVICE)

37 IFB ACTIVE 38 IFB NEUTRAL
IFB EARTH

240V AC OUTPUT

CB-1 16 A

33 34

22

21

20

19

MIMIC DISPLAY GND

MIMIC DISPLAY +Vdc

MIMIC DISPLAY RX-/TX-

MIMIC DISPLAY RX+/TX+

SCREEN WIRE

RJ12 PIN 6

TWISTED RJ12 PIN 5

RJ12 PIN 2

TWISTED RJ12 PIN 1

RJ12 PIN 4

TWISTED RJ12 PIN 3

HCT-1 LCT-1 RS1

LSC-1

HCT-2 LCT-2 RS2

LSC-2

HCT-2 LCT-2 RS3

LSC-3

OF-1 1
OF-2 1
OF-3 1

FT1

FT2

FIRE TRIP TERMINALS
TO USE FIRE TRIP REMOVE JUMPER BETWEEN RED TERMINALS AND CONNECT TO A NORMALLY CLOSED CONTACT - 240V AC 10A MINIMUM

RCBO 16A / 30mA

GPO N A E

250VAC 10A MAX LOAD AVAILABLE FOR GPO - SERVICE EQUIPMENT USE ONLY

PAIR

INPUTS FOR MIMIC REMOTE DISPLAY CONNECTION BY INSTALLER
NOTE: USE AWG24 (7/0.20) SHIELDED TWISTED PAIR DATA CABLE

PAIR

PAIR

OCB RS4

TO IF-1 TERMINAL

EARTH EARTH N 240VAC-N

TX 72 VA

CB-3 6 A

240V AC

24V AC

FAULT RELAY OUTPUT N/O FAULT RELAY OUTPUT N/C RELAY COMMON INPUT 21 24 21 24

LP-1 LP-2 RS5 GND Vsp / Ain1U / I02 DRM 1 INPUT DRM 2 INPUT DRM 3 INPUT REMOTE ON/OFF INPUT
STAGE 1 24V AC IN STAGE 2 24V AC IN

CMC-1 CCH-2

CCH-1

CMC-2

FINAL COMMISSIONING

FAN SETPOINT VOLTAGE

Fan Speed:

Date:

.................... V or % ....../....../.....

AH-PB CB CCH CM CMC GPO HCT HP IF IFC LCT LP LSC MSCB OCB OF R RS RV RCBO
TERM TX

LEGEND

STAGE 3 24V AC IN HEAT 24V AC IN

MULTI INPUT SELECTION TABLE

MULTI INPUT MATRIX A

DESCRIPTION SUPPLY AIR TEMP

TYPE SENSOR

B

ECONOMY MODE

DIGITAL INPUT

C

NIGHT MODE

DIGITAL INPUT

D

COMP STAGE CONTROL 0-10V ANALOGUE

E

IN-FAN SPEED CONTROL 0-10V ANALOGUE

AFTER HOURS CONTROL INPUT INSTALLATION INSTRUCTION

NOTE: CL01, CP05 & CP10 CONTROLLERS ONLY. 3RD PARTY CONTROLS REFER TO INSTALLATION MANUAL.

REMOVE LOOP WIRE

* IMPULSE PUSH BUTTON N/C
CONNECTION SHOWN * 5 SEC CONTACT BREAK REQUIRED
FOR AFTER HOURS ACTIVATION

18 AFTER HOURS 17 RTN AIR SENSOR 16 RTN AIR SENSOR (GND)

18 AFTER HOURS 17 RTN AIR SENSOR

16 RTN AIR SENSOR (GND)

15 MULTI INPUT 2

14 COMMON (GND)

13 MULTI INPUT 1

12

N/A

11 COMMON (GND)

10 REMOTE ON/OFF

9 8 7

6

5

4

3

2

1

SEE MULTI INPUT SELECTION TABLE
FOR OPTIONS
3RD PARTY CONTROL INPUTS - VOLT FREE
RELAY CONTACT REQUIRED

Page 8 of 12

PKY620T

9590-0014-03B Ver. 13 231027

Base R Model No: PKY620-700T
Description:

Variation Code: Variations:

STANDARD

B

CHANGED TERMINAL DESC.'S FOR ID FAN TO ALLOW DIFFERENT MANUFACTURERS CONNECTIONS, REMOVE DEFAULT FAN SPEED SETTINGS TABLE. SET I/D FAN O/L TO 10A

3710

JL

14-03-2023

CM100 TRI-CAPACITY CONTROL SYSTEM WIRING DIAGRAM

Rev. A

Description ORIGINAL

PCR By Date

This drawing remains the intellectual property of Actron Engineering Pty Ltd. Reproduction, modification and/or distribution are prohibited without written consent.

Drawn: Approved:

JL RL

Date: 11-01-2021 Drawing No:

Date: 14-03-2023

0515-8606

Revision Size:
B A3

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.









$ NOTE: UNIT VIEWED FROM AIR HANDLING END - SIZE AND POSITION OF RETURN & SUPPLY ARE INDICATIVE ONLY, SEE TABLE FOR ACTUAL SIZE AND POSITION FOR EACH PARTICULAR MODEL - ALL FLANGES ARE OUTSIDE DIMENSIONS - ALL FLANGES ARE RAW EDGE EXCEPT FOR DOWN SUPPLY (LD) & DOWN RETURN (D) ON PKY820-960 WHICH HAVE A 26mm INTERNAL RETURN FLANGE.
% - ALL DIMENSIONS ARE FROM OUTSIDE EDGE OF BASE
"L" "N"

"R "

"P"

LV

V

"14"

RETURN

SUPPLY

"16"

"S" "Q"

"15" "17"

TOP VIEW

"D" "B"

"2"

"4"

&

LS

LF

F









SUPPLY OUTLET DIMENSIONS

LF

LD

LS

LV

$

A B C D EFG H J K L MN P Q R S

PKY470-540 653 583 404 117 653 583 266 170 201 653 583 418 303 583 653 300 120

PKY620-700 653 583 525 117 653 583 266 170 201 653 583 524 303 653 583 265 118

PKY820-960 1203 605 469 115 1254 651 98 102 203 1203 605 467 423 1203 605 122 127

RETURN INLET DIMENSIONS

F

D

S

V

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

PKY470-540 903 703 292 98 903 703 142 106 201 903 703 360 252 903 703 140 100

%

PKY620-700 903 703 385 98 903 703 142 106 201 903 703 385 252 903 703 140 100

PKY820-960 1203 605 469 136 1254 651 98 102 203 1203 605 467 422 1203 605 122 157

"13" "11"

&
S

RETURN RETURN

"10"

"1"

RETURN

SUPPLY

"A "

"K "

SUPPLY

"9" "12"

"3"

"C "

"J" "M"

Page 9 of 12

PKY620T

LD SUPPLY

LD SUPPLY

RETURN D

'

LH SIDE

END VIEW

"H"

"F"

"6" "8"

"G"

LEGEND FOR SUPPLY POSITIONS

LD = LEFT DOWN SUPPLY

LF = LEFT FRONT SUPPLY

LS = LEFT SIDE SUPPLY

(

LV = LEFT VERTICAL SUPPLY

LEGEND FOR RETURN POSITIONS

D = RIGHT DOWN RETURN F = RIGHT FRONT RETURN S = RIGHT SIDE RETURN V = RIGHT VERTICAL RETURN

"E"

LD

D

RETURN

SUPPLY

BOTTOM VIEW

UNLESS OTHERWISE SPECIFIED

)

1. 2.

3rd ANGLE PROJECTION. DIMENSIONS IN MILLIMETRES.

3.

DO NOT SCALE.

4.

TUBE ENDS MUST BE ROUND AND OF FULL

DIAMETER.

5.

TUBE MUST BE CLEAN AND FREE FROM

BURRS INSIDE AND OUTSIDE AND SUITABLE

OF FOR SOLDERING.

6.

ALL BENDS 90 .

7.

ALL SHEETMETAL'S DIMENSIONS OUTISDE.

GENERAL TOLERANCES

(UNLESS OTHERWISE SPECIFIED)

1.

ALL TUBES

2.

HOLE DIAMETER

3.

FLAT PATTERN

4.

FOLD

5.

ANGLES & SQUARENESS

3 0.1/~0 0.5 / m 0.5 / m 1
B REV

Drawing Release DESCRIPTION

"5"

"7"

D RETURN

RH SIDE

'

S V
LV

STANDARD PKY470-960T SUPPLY & RETURN L**T VARIATIONS

F
(
LS LF
D LD

N/A DR 27/10/2023 PCR BY DATE

ActronAir Pty Ltd 5 Irvine Place Norwest Business Park Bella Vista NSW 2153 PH. +61 2 8814 4000 A.B.N. 34 002 767 240

This drawing always remains the intellectual property of Actron Engineering Pty Ltd. Copying, Modifying or Distributing without written consent is prohibited

DESCRIPTION:

DRAWING NO.

REV.

PKY470-960T-L**T B STANDARD PKY470-960T SUPPLY & RETURN L***T VARIATIONS

)

MATERIAL:

FINISH:

See Notes

See Notes

DRAWN BY:

DRAWN DATE:

APPROVED BY:

SCALE: N.T.S

DR

27/10/2023

DR

6+((7  2) 

A3 THIRD ANGLE
PROJECTION

9590-0014-03B Ver. 13 231027

63.00 kW
3 Phase Tri-Capacity

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.





$ NOTE: UNIT VIEWED FROM AIR HANDLING END - SIZE AND POSITION OF RETURN & SUPPLY ARE INDICATIVE ONLY, SEE TABLE FOR ACTUAL SIZE AND POSITION FOR EACH PARTICULAR MODEL - ALL FLANGES ARE OUTSIDE DIMENSIONS - ALL FLANGES ARE RAW EDGE EXCEPT FOR DOWN SUPPLY (LD) & DOWN RETURN (D) ON PKY820-960 WHICH HAVE A 26mm INTERNAL RETURN FLANGE.
% - ALL DIMENSIONS ARE FROM OUTSIDE EDGE OF BASE

"L" "N"

&

LS

"K"

SUPPLY

"J" "M"

LD

SUPPLY

LH SIDE
'

63.00 kW
3 Phase Tri-Capacity













SUPPLY OUTLET DIMENSIONS

LF

LD

LS

LV

$

ABCDE FGH J K LMNPQRS

PKY470-540 653 583 404 117 653 583 266 170 201 653 583 418 303 583 653 300 120

PKY620-700 653 583 524 117 653 583 266 170 201 653 583 524 303 653 583 265 118

PKY820-960 1203 605 469 116 1254 651 98 102 203 1203 605 467 423 1203 605 122 127

"R" "P" SUPPLY

LV

RETURN INLET DIMENSIONS

F

D

OA

1 2 3 4 5 6 7 8 9 18 19 20 21

%

OA

PKY470-540 903 703 295 80 NA NA NA NA NA 1197 557 138 227

"S" "Q"

PKY620-700 903 703 385 97 NA NA NA NA NA 1197 557 248 227

PKY820-960 1203 605 469 136 1254 651 98 102 203 1258 668 441 255

TOP VIEW

"D" "B"

"2" "4"

"21" "19"

RETURN

LF

F

OA

SUPPLY

LD SUPPLY

RETURN D

END VIEW

"H" "F"

"6" "8"

"3"

"1"

"20"

"18"

OA
D RETURN
RH SIDE

OUTSIDE AIR

NOTE:

ON MODELS PKY470T TO PKY700T

ECONOMISER ie "OUTSIDE AIR" IS NOT

&

AVAILABLE AS A STANDARD OPTION

WITH A "DOWN RETURN"

ONLY AVAILABLE WITH A "FRONT RETURN"

AS STANDARD.

A VR REQUEST CAN BE MADE FOR SPECIAL CONFIGURATION OF OUTSIDE AIR.

'

"A"

"C"

Page 10 of 12

"7"

"G"

PKY620T

LEGEND FOR SUPPLY POSITIONS LD = LEFT DOWN SUPPLY LF = LEFT FRONT SUPPLY LS = LEFT SIDE SUPPLY ( LV = LEFT VERTICAL SUPPLY

LEGEND FOR RETURN POSITIONS

D = RIGHT DOWN RETURN F = RIGHT FRONT RETURN OA = OUTSIDE AIR RETURN
NOTE: WEATHERHOOD IS AN OPTION

UNLESS OTHERWISE SPECIFIED

)

1. 2.

3rd ANGLE PROJECTION. DIMENSIONS IN MILLIMETRES.

3.

DO NOT SCALE.

4.

TUBE ENDS MUST BE ROUND AND OF FULL

DIAMETER.

5.

TUBE MUST BE CLEAN AND FREE FROM

BURRS INSIDE AND OUTSIDE AND SUITABLE

OF FOR SOLDERING.

6.

ALL BENDS 90 .

7.

ALL SHEETMETAL'S DIMENSIONS OUTISDE.

GENERAL TOLERANCES

(UNLESS OTHERWISE SPECIFIED)

1.

ALL TUBES

2.

HOLE DIAMETER

3.

FLAT PATTERN

4.

FOLD

5.

ANGLES & SQUARENESS

3 0.1/~0 0.5 / m 0.5 / m 1
B REV

Drawing Release DESCRIPTION

"E"

LD

D

OA

LS LV

"5"

RETURN

SUPPLY

LF

F

OA

(

BOTTOM VIEW

STANDARD PKY470-960T SUPPLY & RETURN L**T-E VARIATIONS

LD D

N/A DR 27/10/2023 PCR BY DATE

ActronAir Pty Ltd 5 Irvine Place Norwest Business Park Bella Vista NSW 2153 PH. +61 2 8814 4000 A.B.N. 34 002 767 240

This drawing always remains the intellectual property of Actron Engineering Pty Ltd. Copying, Modifying or Distributing without written consent is prohibited

DESCRIPTION:

DRAWING NO.

REV.

STANDARD PKY470-960T SUPPLY & RETURN L***T-E VARIATIONS

MATERIAL:

FINISH:

See Notes

See Notes

PKY470-960T-L**T-E

B

)

DRAWN BY:

DRAWN DATE:

APPROVED BY:

SCALE: N.T.S

DR

27/10/2023

DR

6+((7  2) 

A3 THIRD ANGLE
PROJECTION

9590-0014-03B Ver. 13 231027

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.









$ NOTE: UNIT VIEWED FROM AIR HANDLING END - SIZE AND POSITION OF RETURN & SUPPLY ARE INDICATIVE ONLY, SEE TABLE FOR ACTUAL SIZE AND POSITION FOR EACH PARTICULAR MODEL - ALL FLANGES ARE OUTSIDE DIMENSIONS - ALL FLANGES ARE RAW EDGE EXCEPT FOR DOWN SUPPLY (RD) & DOWN RETURN (D) ON PKY820-960 WHICH HAVE A 26mm INTERNAL RETURN FLANGE.
% - ALL DIMENSIONS ARE FROM OUTSIDE EDGE OF BASE
"11" "13"

"16"

"14"

V

RV

SUPPLY

RETURN

"17" 15"

"Q" "S"

TOP VIEW

"4" "2"

"B" "D"

&

S

F

RF

"R "

"P"









SUPPLY OUTLET DIMENSIONS

RF

RD

RS

RV

$

A B C D EFG H J K L MN P Q R S

PKY470-540 653 583 404 117 653 583 266 170 201 653 583 418 303 583 653 300 120

PKY620-700 653 583 524 117 653 583 266 170 201 653 583 524 303 653 583 265 118

PKY820-960 1203 605 469 115 1254 651 98 102 203 1203 605 467 423 1203 605 122 127

RETURN INLET DIMENSIONS

F

D

S

V

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

PKY470-540 903 703 292 98 903 703 142 106 201 903 703 360 252 903 703 140 100

%

PKY620-700 903 703 385 98 903 703 142 106 201 903 703 385 252 903 703 140 100

PKY820-960 1203 605 469 136 1254 651 98 102 203 1203 605 467 422 1203 605 122 157

"N" "L"

&
RS

SUPPLY RETURN

"K "

"A"

SUPPLY

RETURN

"1"

"10"

RETURN

"J" "M"

"C"

"3"

"9" "12"

Page 11 of 12

PKY620T

D RETURN

D RETURN

SUPPLY RD

RD SUPPLY

'

LH SIDE

END VIEW

RH SIDE

'

"8"

"6"

"F"

"H"

"G"

"7"

LEGEND FOR SUPPLY POSITIONS

RD = RIGHT DOWN SUPPLY

RF = RIGHT FRONT SUPPLY

RS = RIGHT SIDE SUPPLY

(

RV = RIGHT VERTICAL SUPPLY

LEGEND FOR RETURN POSITIONS

D = LEFT DOWN RETURN F = LEFT FRONT RETURN S = LEFT SIDE RETURN V = LEFT VERTICAL RETURN

"5"

D

RD

SUPPLY

RETURN

BOTTOM VIEW

UNLESS OTHERWISE SPECIFIED

)

1. 2.

3rd ANGLE PROJECTION. DIMENSIONS IN MILLIMETRES.

3.

DO NOT SCALE.

4.

TUBE ENDS MUST BE ROUND AND OF FULL

DIAMETER.

5.

TUBE MUST BE CLEAN AND FREE FROM

BURRS INSIDE AND OUTSIDE AND SUITABLE

OF FOR SOLDERING.

6.

ALL BENDS 90 .

7.

ALL SHEETMETAL'S DIMENSIONS OUTISDE.

GENERAL TOLERANCES

(UNLESS OTHERWISE SPECIFIED)

1.

ALL TUBES

2.

HOLE DIAMETER

3.

FLAT PATTERN

4.

FOLD

5.

ANGLES & SQUARENESS

3 0.1/~0 0.5 / m 0.5 / m 1
B REV

Drawing Release DESCRIPTION

"E"

SV RV

F

RF RS

(

STANDARD PKY470-960T

SUPPLY & RETURN

R**T VARIATIONS

D

RD

N/A DR 27/10/2023 PCR BY DATE

ActronAir Pty Ltd 5 Irvine Place Norwest Business Park Bella Vista NSW 2153 PH. +61 2 8814 4000 A.B.N. 34 002 767 240

This drawing always remains the intellectual property of Actron Engineering Pty Ltd. Copying, Modifying or Distributing without written consent is prohibited

DESCRIPTION:

DRAWING NO.

REV.

PKY470-960T-R**T B STANDARD PKY470-960T SUPPLY & RETURN R***T VARIATIONS

)

MATERIAL:

FINISH:

See Notes

See Notes

DRAWN BY:

DRAWN DATE:

APPROVED BY:

SCALE: N.T.S

DR

27/10/2023

DR

6+((7  2) 

A3 THIRD ANGLE
PROJECTION

9590-0014-03B Ver. 13 231027

63.00 kW
3 Phase Tri-Capacity

63.00 kW
3 Phase Tri-Capacity

ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.

Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd.

















$ NOTE: UNIT VIEWED FROM AIR HANDLING END - SIZE AND POSITION OF RETURN & SUPPLY ARE INDICATIVE ONLY, SEE TABLE FOR ACTUAL SIZE AND POSITION FOR EACH PARTICULAR MODEL - ALL FLANGES ARE OUTSIDE DIMENSIONS - ALL FLANGES ARE RAW EDGE EXCEPT FOR DOWN SUPPLY (LD) & DOWN RETURN (D) ON PKY820-960 WHICH HAVE A 26mm INTERNAL RETURN FLANGE.
% - ALL DIMENSIONS ARE FROM OUTSIDE EDGE OF BASE
"19" "21"
&
OA

OUTSIDE AIR

"18"

RETURN

RV

SUPPLY

OA
"Q" "S"
TOP VIEW
"B" "D"

F

RF

OA

SUPPLY

"C"

"A"

"R"

"P"

SUPPLY OUTLET DIMENSIONS

RF

RD

RS

RV

$

ABCDE FGH J K LMNPQRS

PKY470-540 653 583 404 117 653 583 266 170 201 653 583 418 303 583 653 300 120

PKY620-700 653 583 524 117 653 583 266 170 201 653 583 524 303 653 583 265 118

PKY820-960 1203 605 469 115 1254 651 98 102 203 1203 605 467 423 1203 605 122 127

RETURN INLET DIMENSIONS

F

D

OA

1 2 3 4 5 6 7 8 9 18 19 20 21

%

PKY470-540 903 703 295 80 NA NA NA NA NA 1197 557 138 227

PKY620-700 903 703 385 97 NA NA NA NA NA 1197 557 248 227

PKY820-960 1203 605 469 136 1254 651 98 102 203 1258 668 441 255

"N" "L"
RS

SUPPLY

NOTE:

ON MODELS PKY470T TO PKY700T

&

ECONOMISER ie "OUTSIDE AIR" IS NOT

AVAILABLE AS A STANDARD OPTION

WITH A "DOWN RETURN"

ONLY AVAILABLE WITH A "FRONT RETURN"

AS STANDARD.

A VR REQUEST CAN BE MADE FOR SPECIAL CONFIGURATION OF OUTSIDE AIR.

"K"

"M"

"20"

D

RETURN

D RETURN

SUPPLY RD

SUPPLY RD

'

LH SIDE

END VIEW

RH SIDE

'

"8" "6"

"F" "H"

"G"

"7"

"5"

LEGEND FOR SUPPLY POSITIONS OA
RD = RIGHT DOWN SUPPLY RF = RIGHT FRONT SUPPLY RS = RIGHT SIDE SUPPLY ( RV = RIGHT VERTICAL SUPPLY

LEGEND FOR RETURN POSITIONS

D = LEFT DOWN RETURN F = LEFT FRONT RETURN OA = OUTSIDE AIR RETURN
NOTE: WEATHERHOOD IS AN OPTION

UNLESS OTHERWISE SPECIFIED

)

1. 2.

3rd ANGLE PROJECTION. DIMENSIONS IN MILLIMETRES.

3.

DO NOT SCALE.

4.

TUBE ENDS MUST BE ROUND AND OF FULL

DIAMETER.

5.

TUBE MUST BE CLEAN AND FREE FROM

BURRS INSIDE AND OUTSIDE AND SUITABLE

OF FOR SOLDERING.

6.

ALL BENDS 90 .

7.

ALL SHEETMETAL'S DIMENSIONS OUTISDE.

GENERAL TOLERANCES

(UNLESS OTHERWISE SPECIFIED)

1.

ALL TUBES

2.

HOLE DIAMETER

3.

FLAT PATTERN

4.

FOLD

5.

ANGLES & SQUARENESS

3 0.1/~0 0.5 / m 0.5 / m 1
B REV

Drawing Release DESCRIPTION

D

RD

SUPPLY

RETURN

BOTTOM VIEW

"E"

RS RV

STANDARD PKY470-960T SUPPLY & RETURN R**T-E VARIATIONS

OA

F

RF
(

RD D

N/A PCR

DR 27/10/2023 BY DATE

ActronAir Pty Ltd 5 Irvine Place Norwest Business Park Bella Vista NSW 2153 PH. +61 2 8814 4000 A.B.N. 34 002 767 240

This drawing always remains the intellectual property of Actron Engineering Pty Ltd. Copying, Modifying or Distributing without written consent is prohibited

DESCRIPTION: STANDARD PKY470-960T SUPPLY & RETURN R**T-E VARIATIONS

MATERIAL: See Notes DRAWN BY:

FINISH: See Notes DRAWN DATE:

APPROVED BY:

DR

27/10/2023

DR

DRAWING NO.

REV.

PKY470-960T-R**T-E B )

SCALE: N.T.S 6+((7  2) 

A3 THIRD ANGLE
PROJECTION

Page 12 of 12

PKY620T

9590-0014-03B Ver. 13 231027


Adobe PDF Library 17.0 Adobe InDesign 19.0 (Windows)