ActronAir Digital
TECHNICAL SELECTION DATA PKY620T TRI-CAPACITY PACKAGE UNIT 63.00 kW 3 Phase Tri-Capacity 3 THREE PHASE TRI-CAPACITY EC PLUG FAN LOUVRE LOW NOISE FAN UNIT FEATURES SPECIFICATION SUMMARY · Compliant Scroll Compressors · Tri-Capacity 33% 67% 100% Capacity Stages · Dual Bi-Flow Thermostatic Expansion Valves · Full Factory Charged with R-410A Refrigerant · Return Air Filter Rails Fitted · Two Speed Outdoor Fans · Hydrophilic Blue Coat Coil Fin Protection - Indoor and Outdoor Coils · Outdoor Coils Condensate Drain Socket · Louvred Outdoor Coil Guard · External Stainless Steel Screws · Adaptive Demand Defrost · EC Variable Speed Backward Curve Plug Fan · Adjustable Indoor Airflow via Control Interface · Foil Faced Polyethylene Insulation PACKAGE UNIT MODEL (3) COOLING CAPACITY (kW) (3) SENSIBLE CAPACITY (kW) (4) HEATING CAPACITY (kW) (5) COOLING INPUT POWER (kW) (5) HEATING INPUT POWER (kW) EER COP (6) INDOOR AIRFLOW (l/s) - MIN. / NOMINAL / MAX. PKY620T (1) TOTAL (2) NETT 63.00 60.80 47.80 45.60 60.00 62.47 20.50 20.15 3.07 2.97 2.98 3.10 2500 / 3200 / 3900 UNIT OPTIONS · Reverse Handing with Various Airflow Options · (9) Economy Starter Kit (Available on LHS / RHS only) · Outside Air Damper · Low Ambient / High Static Outdoor Fans · Compressor Soft Starters · Phase Protection · Additional Full Coil Coat Protection OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) - LOW / HIGH OUTDOOR SOUND POWER LEVEL dB(A) - LOW / HIGH POWER SUPPLY (2) RATED LOAD AMPS (7) FULL LOAD AMPS (8) CIRCUIT BREAKER AND CABLE AMPS APPROXIMATE STARTING AMPS 60.0 / 65.0 77.0 / 82.0 400V / 3Ph+N / 50Hz 39.2 53.9 63.0 140.0 CONTROL FEATURES ActronAir CP05 / CP10 · Auto / Cool / Heat / Fan Only Modes · 7- Day Time Clock with 2 On/Off Events per Day · 12 Programmable Special Days with 2 On/Off Events per Day · Daylight Saving Time Function · Indoor Coil Anti-Freeze Protection · HP / LP Safety Protection · Alarm Fault Data Logger · LCD Screen Displays Operating Status, Mode & Menu Information · Night Mode Function WEIGHT (kg) 937 (1) Based on unit rating excluding indoor fan kW. (2) Measured and tested in accordance with AS/NZS 3823.1.2. (3) At 27°C DB / 19°C WB entering air temperatures and 35°C ambient. (4) At 20°C DB entering air temperature and 7°C DB / 6°C WB ambient. (5) Input power includes indoor fan kW. (6) Max. - Min. airflow application range. (7) Full Load Amps are based on compressor and fan motors' maximum expected current. (8) See Specifications sheet for cable size and circuit breaker size details. (9) Room Air Sensor needs to be relocated by the installer specific to site requirements. Note: Use input power to estimate running cost. CONTROL OPTIONS ActronAir CL01-2 (BCA Compliant) - Purchased Separately · Available in White or Grey · 7- Day Time Clock with 2 On/Off Events per Day Optional BMS Control - Purchased Separately · MODBUS 485 / BACNET 485 / BACNET TCP/IP UNIT COMPLIANCE · MEPS 2012 · Demand Response AS4755.3.1:2012 · BCA Compliant with CL01-2 Control Interface · EMC Compliant Optional 3rd Party Control Inputs - Standard Inclusion R · 0-10VDC / 24VAC / Volt Free Digital Input ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. Page 1 of 12 9590-0014-03B Ver. 13 231027 CAPACITY SELECTION DATA PKY620T 63.00 kW 3 Phase Tri-Capacity COOLING PERFORMANCE AIR ENTERING OUTDOOR INDOOR DB - °C WB - °C 16 17 25 18 19 20 21 22 16 17 18 30 19 20 21 22 16 17 18 35 19 20 21 22 16 17 18 40 19 20 21 22 16 17 18 45 19 20 21 22 16 17 50 18 19 20 21 22 TOTAL CAPACITY kW 64.28 65.64 67.23 69.16 71.01 72.88 75.11 61.53 62.93 64.42 66.27 68.15 69.82 71.92 58.94 59.92 61.30 63.00 64.77 66.35 68.35 56.11 56.62 57.77 59.40 61.02 62.49 64.38 52.91 52.94 53.95 55.38 56.84 58.24 59.96 49.31 49.34 49.78 50.93 52.22 53.61 55.02 20 38.67 35.37 31.96 28.52 25.09 37.51 34.18 30.81 27.42 23.98 36.20 32.88 29.52 26.14 22.70 34.69 31.45 28.11 24.75 21.31 33.10 29.88 26.57 23.22 19.79 31.35 28.17 24.88 21.54 18.13 21 41.88 38.59 35.23 31.84 28.42 17.40 40.67 37.41 34.07 30.69 27.27 23.81 39.31 36.07 32.80 29.38 25.99 22.54 37.89 34.64 31.34 28.02 24.61 21.21 35.89 33.04 29.79 26.49 23.10 19.69 34.13 31.30 28.11 24.79 21.44 18.04 22 44.61 41.75 38.44 35.12 31.67 28.19 24.72 43.40 40.58 37.29 33.97 30.55 27.08 23.62 42.08 39.26 35.98 32.67 29.27 25.86 22.41 40.55 37.78 34.57 31.27 27.92 24.50 21.02 38.93 36.22 32.98 29.71 26.36 22.99 19.57 37.13 34.06 31.23 28.02 24.70 21.31 17.92 TOTAL SENSIBLE CAPACITY - kW AT DB TEMPERATURE ONTO INDOOR COIL - °C 23 24 25 26 27 47.65 50.60 53.49 44.93 47.55 50.53 53.42 41.64 44.80 47.43 50.43 53.36 38.34 41.46 44.65 47.29 50.35 34.94 31.49 28.01 38.14 34.72 31.31 41.33 37.96 34.57 44.48 41.18 37.80 47.45 44.31 40.99 46.43 49.35 52.24 43.60 46.36 49.33 52.21 40.45 43.63 46.27 49.23 52.14 37.17 40.32 43.46 46.15 49.15 33.80 30.38 26.94 37.02 33.63 30.20 40.18 36.85 33.45 43.33 40.04 36.69 46.00 43.18 39.86 45.07 48.00 50.79 41.96 45.01 47.97 50.76 39.12 35.91 32.55 42.17 39.04 35.77 44.94 42.18 38.89 47.89 44.81 42.03 50.79 47.80 44.68 29.14 25.71 32.39 28.97 35.60 32.22 38.76 35.43 41.85 38.60 43.58 46.43 40.52 43.54 46.43 37.70 34.48 40.42 37.61 43.44 40.31 46.40 43.34 49.22 46.34 31.15 34.36 37.48 40.59 43.26 27.73 24.35 30.95 27.61 34.22 30.87 37.34 34.08 40.45 37.21 41.91 38.89 41.89 44.74 36.11 38.81 41.82 44.71 32.90 36.01 38.70 41.73 44.70 29.60 32.78 35.91 38.61 41.64 26.26 22.82 29.50 26.14 32.68 29.34 35.79 32.57 38.88 35.68 40.04 37.12 40.04 34.02 37.05 40.03 31.17 34.24 36.96 39.96 42.85 27.92 31.08 34.16 36.86 39.87 24.58 21.18 27.83 24.44 30.96 27.67 34.07 30.87 36.77 33.93 28 56.27 53.25 50.21 47.42 44.14 55.02 52.08 49.00 46.31 43.00 50.69 47.71 44.53 41.73 49.20 46.25 43.10 40.29 47.46 44.59 41.52 38.75 42.79 39.77 36.65 29 56.21 53.15 50.04 47.25 54.97 51.95 48.86 46.09 53.56 50.65 47.57 44.85 49.13 46.13 42.95 47.47 44.50 41.40 42.70 39.66 30 59.03 56.10 53.03 49.85 54.87 51.80 48.71 49.77 49.56 46.57 51.91 49.03 45.99 47.40 44.38 45.55 42.59 HEATING PERFORMANCE WB TEMP ON OD COIL- °C -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 16 TH IH 39.33 36.97 41.67 38.75 44.08 40.55 46.65 41.75 49.35 42.93 52.15 44.85 54.87 48.83 57.80 54.91 60.89 60.89 64.14 64.14 67.63 67.63 71.16 71.16 74.92 74.92 78.88 78.88 82.90 82.90 HEATING CAPACITY - kW AT DB ENTERING INDOOR - °C 18 TH IH 39.17 36.82 41.48 38.58 43.86 40.35 46.43 41.56 49.07 42.69 51.86 44.60 54.51 48.51 57.39 54.52 60.41 60.41 63.63 63.63 67.06 67.06 70.58 70.58 74.22 74.22 78.12 78.12 82.17 82.17 20 TH IH 38.98 36.64 41.28 38.39 43.68 40.18 46.19 41.34 48.78 42.44 51.53 44.32 54.17 48.21 57.01 54.16 60.00 60.00 63.20 63.20 66.45 66.45 69.93 69.93 73.49 73.49 77.44 77.44 81.34 81.34 22 TH IH 38.82 36.49 41.10 38.22 43.46 39.98 45.92 41.10 48.49 42.19 51.21 44.04 53.81 47.89 56.57 53.75 59.58 59.58 62.66 62.66 65.88 65.88 69.25 69.25 72.77 72.77 76.62 76.62 80.45 80.45 24 TH IH 38.65 36.33 40.89 38.03 43.21 39.76 45.66 40.86 48.23 41.96 50.91 43.78 53.46 47.58 56.19 53.38 59.04 59.04 62.11 62.11 65.30 65.30 68.55 68.55 72.10 72.10 75.80 75.80 79.56 79.56 TH - Total Heating Capacity (kW). IH - Integrated Heating Capacity (kW) Includes defrost losses. AIRFLOW CORRECTION MULTIPLIER % VARIATION INDOOR AIRFLOW (l/s) TOTAL COOLING SENSIBLE COOLING HEATING FACTOR -22% 2500 0.956 0.884 0.985 -15% 2720 0.972 0.919 0.990 -10% 2880 0.982 0.947 0.993 -5% 3040 0.991 0.974 0.997 NOMINAL 3200 1.000 1.000 1.000 +5% 3360 1.008 1.026 1.001 +10% 3520 1.016 1.051 1.003 +15% 3680 1.023 1.077 1.005 +22% 3900 1.032 1.109 1.007 NOTES: 1. No allowance has been made for the effect of indoor fan motor. 2. Selection tables are based on nominal airflows. Correction factors must be applied for selection away from these conditions. R ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. Page 2 of 12 9590-0014-03B Ver. 13 231027 63.00 kW 3 Phase Tri-Capacity INDOOR FAN DATA / FAN CURVE PKY620T FAN PERFORMANCE DATA External Static Pressure (Pa) Airflow 50 (l/s) % Spd. W 100 % Spd. W 150 % Spd. W 200 % Spd. W 250 % Spd. W 300 % Spd. W 350 % Spd. W 400 % Spd. W 450 % Spd. W 500 % Spd. W 2500 48.2 869 51.5 1030 56.1 1269 59.9 1505 63.8 1765 67.9 2028 72.0 2297 75.8 2579 78.8 2875 83.2 3310 2600 49.2 905 53.3 1107 57.5 1350 61.3 1596 65.3 1864 69.5 2134 73.5 2398 76.8 2683 79.6 2973 84.6 3490 2700 50.2 941 55.1 1188 58.9 1435 62.8 1694 66.9 1965 71.1 2239 75.0 2495 77.8 2792 81.1 3096 88.1 3550 2800 52.2 1023 56.6 1275 60.3 1523 64.3 1792 68.6 2073 72.6 2346 76.1 2627 78.9 2913 83.2 3235 2900 54.1 1106 58.0 1357 61.9 1623 66.0 1900 70.4 2191 74.1 2468 77.2 2751 80.1 3032 85.5 3372 3000 55.9 1196 59.5 1446 63.5 1725 67.8 2013 71.9 2303 75.4 2580 78.5 2869 82.6 3198 3100 57.5 1284 61.2 1548 65.1 1830 69.7 2133 73.4 2406 76.9 2703 80.1 3001 84.8 3371 3200 59.1 1368 62.9 1652 67.1 1945 71.4 2238 75.0 2509 78.4 2854 82.4 3192 3300 60.9 1480 64.6 1764 69.2 2059 73.1 2355 76.6 2676 80.1 3044 84.8 3363 3400 62.7 1594 66.8 1887 71.1 2184 74.8 2486 78.3 2850 82.4 3188 3500 3600 64.5 1708 68.9 2010 72.8 2315 76.4 2641 79.9 3009 85.0 3342 66.7 1837 70.9 2144 74.6 2452 78.1 2802 82.4 3155 MOTOR / BLOWER LIMIT 3700 69.0 1975 72.8 2277 76.4 2603 79.9 2961 85.0 3315 3800 71.1 2107 74.8 2411 78.2 2769 82.5 3130 3900 73.1 2244 76.6 2578 80.0 2952 85.4 3292 NOTES: % Speed = Indoor Fan Speed Control Setting, in percent (Value is set on the Control Interface via Service Menu *). W = Indoor Fan Power, Watts - Data in the box indicates Factory Default Setting. *Service Service Settings Thermoregulation Thermoregulation Gfc4 INDOOR UNIT FAN CURVE 505000 Thermoregulation Supply Fan Minimum speed: Medium speed: Maximum speed: Supply Fan Temp. Minimum Temp. Maximum Temp. Gfc4 48.2% 62.9% 90.0% 5.0oC 50.0oC Set Fan Speed 445500 EXTERNAL STATIC PRESSURE (PA) 440000 MOTOR / BLOWER LIMIT MOTOR / BLOWER LIMIT 335500 303000 80% 85% Speed Spee9d0% Speed 225500 75% Speed 202000 65% Speed 70% Speed 151500 60% Speed 62.9% Speed 101000 55% Speed 5050 50% Speed 00 22550000 22660000 2270000 22880000 22990000 30300000 33110000 33220000 3330000 34340000 33550000 33660000 33770000 Nominal Airflow = 3200 l/s APPLICATION RANGE AIRFLOW (l/s) 38380000 33990000 40400000 41401000 NOTE Fan Performance Data and Fan Curve shown is at dry coil and with no air filters installed. Consider external static pressure drop specific to your design requirements. Airflow should be reduce with respect to the moisture content in the air. Please review filter manufacturer for application. 2.5 m/s face velocity point will occur at 4097 l/s. R ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. Page 3 of 12 9590-0014-03B Ver. 13 231027 PACKAGE UNIT DIMENSIONS 2365 O/A A B C OUTDOOR COIL OUTDOOR COIL 2305 O/A YY INDOOR COIL PLUG FAN PKY620T DIMENSION (H x W x D) = 1695 x 2305 x 2365 SUPPLY DUCT (H x W) = 650 x 580 RETURN DUCT = 900 x 700 490 670 OUTDOOR COIL 445 330 670 OUTDOOR COIL CONDENSATE DRAIN 25.4 (1") BSP SOCKET PLUG FAN INDOOR COIL OUTDOOR COIL OUTDOOR COIL D E XX 125 1470 1695 O/A 100 ELECTRICAL ACCESS 2335 FRONT VIEW F 120 TOP VIEWS 100 315 425 900 1600 650 385 525 580 770 700 100 2250 80 LIFTING POINT 4 x Ø 20mm 150 CONDENSATE DRAIN 25.4 (1") BSP FEMALE THREAD 2290 SIDE VIEW UNIT AIR HANDING CONFIGURATION (LH / RH) NO. OF POINTS UNIT WEIGHT (kg) A LEFT HANDING RIGHT HANDING 6 937 139 6 937 130 CORNER WEIGHTS (kg) B C D E 188 57 186 279 207 106 192 228 CENTRE OF GRAVITY (mm) F XX YY 88 1115 1060 74 63.00 kW 3 Phase Tri-Capacity ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. Page 4 of 12 R 9590-0014-03B Ver. 13 231027 ACCESS AREAS / BASE MOUNT PKY620T SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES 500 mm AIRFLOW ALLOWANCE * For reverse handing, service clearance for plug fan and airflow clearance for hood will be reversed. ** If the optional hood is not installed, 500 mm clearance is required for service access. 1000 mm SERVICE CLEARANCE (COMPRESSOR & ELECTRICALS) OUTDOOR COIL OUTDOOR COIL OUTDOOR COIL 500 mm AIRFLOW ALLOWANCE 64 1000 mm* SERVICE CLEARANCE (PLUG FAN) HEIGHT CLEARANCE = 1500 DUCT WORK 1000 mm FILTER ACCESS DUCT WORK UNIT BASE DIMENSIONS Down discharge/down return option shown below 770 MTG C-C 375 DISTANCE 770 MTG C-C DISTANCE 375 PLUG FAN INDOOR COIL 556 mm 300 mm* AIRFLOW ALLOWANCE 300 mm OUTSIDE AIR SECTION SERVICE CLEARANCE OPTIONAL HOOD** 800 mm THIRD ANGLE PROJECTION NOTES: 1. Do not scale drawing. All dimensions are in mm unless specified. Refer to corresponding unit dimensional drawing for mounting hole details. 2. S ervice Access Areas and Spaces for Airflow Clearances given above are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000 mm between the units or between the unit and the outside perimeter is available. 3. M inimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow. 4. U nder all circumstances, condenser air must not recirculate back onto condenser coil. Keep all clearance free of any obstructions. 5. S TACKING OF UNITS: Ensure that minimum airflow and clearances are met. 6. MTG C-C DIST = Mounting Centre to Centre Distance. 7. Use M12 bolt for feet mounting. 8. LH / RH refers to Left Hand or Right Hand location of supply air. 9. Diagrams are left handing. 63.00 kW 3 Phase Tri-Capacity 1167 MTG C-C DISTANCE 1107 32 2334 O/A 1167 MTG C-C DISTANCE 1066 64 32 64 1341 788 64 2289 O/A ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. Page 5 of 12 R 9590-0014-03B Ver. 13 231027 SOUND DATA PKY620T SOUND DATA Outdoor Radiated PKY620T-6Q1 OutdooSroRunaddiPaotewder Level (SWL) Sound Power Level (SWLF) an Sound Power Level Speed dB(A) Fan Sound Power Level Speed Low dB(A) 77.0 63 Low High 77.0 82.0 High 82.0 Octave Band Centre Frequency (Hz), dB 125Octave B25an0d Centr5e0F0requency1k(Hz), dB 2k 125 83.8 250 76.5 500 73.8 1k 83.888.8 76.5 81.5 73.8 78.870.7 88.8 81.5 78.8 75.7 70.7 2k 75.765.9 70.9 65.94k 70.598.0 63.0 4k 58.08k 635.03.0 58.8 Sound Pressure Level (SPL) 8Skound Pressure Level dB(A) 53@.03m @1m 58.8--- --- --- --- Indoor Outlet Indoor Outlet Sound Power Level (SWL) Sound Power Level (SWALi)rflow Airflow SeAttiirnflgow Setting Li/s Minimum Min Nominal Nom32in25a00l00 Max Maxi3m9u0m0 PAowSirlef/olsrounLwdevelPowSdeoBru(AnLde) vel Octave Band Centre Frequency (Hz), dB 125Octave 2B5a0nd Centr5e0F0requency1k(Hz), dB 2k 4k 2d5B0(0A) 6731.2 125 75.5 250 72.6 500 69.2 1k 64.9 2k 60.74k 56.58k 32770710..92 77.9 8725..5582.5 72.6 79.5 79.5 69.2 76.1 76.1 64.9 71.5 71.56670..07 67.06546..45 64.55483..26 398030.2 83.2 87.287.2 85.2 85.2 81.5 81.5 76.6 76.671.8 71.869.8 69.683.0 Sound Pressure Level (SPL) 8SkoLuenvdelPdreBs(Asu) re 53@.63m @1m 58.2------ ----- 63.0--- --- OUTDOOR RADIATED PKPYK62Y06T2-60QT1SSoouunnddPPoowweer Leveell 100.0 90.0 80.0 70.0 60.0 50.0 Low High 40.0 125 250 500 1k 2k 4k 8k Octave Band Centre Frequency (Hz) INDOOR OUTLET PKPYK62Y06T2-60QT1SSoouunnddPPoowwer Levveell 100.0 90.0 80.0 70.0 60.0 50.0 Nominal Min Max 40.0 125 250 500 1k 2k 4k 8k Octave Band Centre Frequency (Hz) 63.00 kW 3 Phase Tri-Capacity Octave Band Sound Power Level (dB) Octave Band Sound Power Level (dB) NOTES: Radiated sound power levels are based on ISO 3743-1. ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. Page 6 of 12 R 9590-0014-03B Ver. 13 231027 63.00 kW 3 Phase Tri-Capacity SPECIFICATIONS PKY620T CONSTRUCTION CABINET BASE CABINET TOP AND SIDES SURFACE FINISH INSULATION TYPE 1.9 mm Galvanised Steel 0.9 - 1.6 mm Galvanised Steel 65 microns Baked Polyester Powder Coat Foil Faced Polyethylene SOUND LEVEL * dB(A) SOUND PRESS. - Low / High 60.0 / 65.0 @ 3 m Distance SOUND POWER LEVEL - Low / High 77.0 / 82.0 * Sound data is based on the outdoor fan's manufacturer sound level data. ELECTRICAL POWER SUPPLY - 50 Hz 400 Volts x 3 Phase + Neutral VOLTAGE RANGE (min - max) 376V - 440V FULL LOAD AMPS * - Phase 1 53.9 FULL LOAD AMPS * - Phase 2 & 3 53.9 and 53.9 RATED LOAD AMPS** 39.2 APPROX. STARTING AMPS 140.0 IP RATING IP44 IMPORTANT - The local electricity authority may require limits on starting current and voltage drop, please check prior to purchase. * Full Load Amps are based on compressor and fan motor's maximum expected current. ** Rated Load Amps are measured and tested in accordance with AS/NZS3823.1.2. CABLE SIZE & CIRCUIT BREAKER SIZE Suggested minimum cable size should be used as a guide only, refer to the accordance with the latest edition of the AS/NZS 3000 "Australian/New Zealand Wiring Rules" for more details. CABLE SIZE (MAIN LINE) 16.0 mm2 (SUGGESTED MINIMUM) CIRCUIT BREAKER SIZE - Amps 63.0 OUTDOOR COIL TUBE TYPE FIN TYPE FACE AREA (m sqr) - Coil 1 & 2 FIN SPACING (per m) - Coil 1 & 2 COIL COATING Copper - Rifle Bore Aluminium - Corrugated 1.45 & 2.75 472 & 472 Hydrophilic Blue Coat Coil Fin Protection OUTDOOR FAN NUMBER OF FANS x TYPE 3 x Axial Low Noise NUMBER OF BLADES PER FAN 5 INPUT kW / FULL LOAD AMPS 0.50 / 2.62 each fan MOTOR TYPE / DRIVE TYPE 6 Pole External Rotor / Direct Drive FAN SPEED CONTROL 2 Speed via Capacitor The standard type outdoor fans fitted to this unit will accept up to 20 Pa of external static resistance. INDOOR COIL TUBE TYPE FIN TYPE FACE AREA (m sqr) FIN SPACING (per m) COIL COATING Copper - Rifle Bore Aluminium - Louvre 1.64 (interlaced) 472 Hydrophilic Blue Coat Coil Fin Protection INDOOR FAN NUMBER OF FANS x TYPE INPUT kW / FULL LOAD AMPS MOTOR TYPE / DRIVE TYPE 1 x Backward Curve Plug Fan 2.20 / 6.0 Variable Speed EC Motor / Direct Drive COMPRESSOR NUMBER PER UNIT x TYPE 2 x Scroll (Hermetic) FULL LOAD AMPS - (Comp. 1 & 2) 14.3 & 25.5 LOCKED ROTOR AMPS - (Comp. 1 & 2) 101.0 & 140.0 STARTING METHOD D.O.L. (optional soft starter) REFRIGERATION SYSTEM REFRIGERANT TYPE EXPANSION CONTROLTYPE x NO. PER UNIT FACTORY CHARGE - (Crt. 1 & 2) R-410A Bi-Flow TXV (Thermostatic Valve) x 2 7,200 grams & 12,700 grams PROTECTION DEVICES HIGH PRESSURE CUTOUT SWITCH LOW PRESSURE CUTOUT SWITCH COMPRESSOR MOTOR TEMP. INDOOR FAN OVERLOAD OUTDOOR FAN OVERLOAD SUMP HEATER WATTS - (Comp. 1 & 2) Nonadjustable (Automatic Reset) Nonadjustable (Automatic Reset) Internal Thermal Cut-Out Full Electronic Monitoring Internal Thermal Cut-Out 30W & 90W ELECTRIC CONTROLS DEFROST METHOD DEFROST TYPE CONTROL CIRCUIT BREAKER OPTIONAL THIRD PARTY BMS / CONTROLLER INPUTS Reverse Cycle Adaptive Demand Defrost 16.0 Amps MODBUS 485 BACNET 485 BACNET TCP / IP 0-10VDC / 24VAC Third Party Input OPERATING RANGE It is essential that the unit is correctly sized for the application and operates within its recommended range of operating conditions as shown below. MODE Cooling RANGE Max. Min. INDOOR AIR INTAKE TEMPERATURE 29°C DB / 19°C WB 20°C DB / 15°C WB OUTDOOR AIR INTAKE TEMPERATURE 50°C DB 15°C DB Heating Max. Min. 24°C DB 16°C DB 21°C DB / 16°C WB -10°C DB IMPORTANT - Lower ambient available on request. Contact your nearest ActronAir office for more details. AIR FILTER PROVISION All return air including fresh air must have adequate filters supplied and fitted by the installing contractor. Filters are to be located in the return air filter retainer in the unit or in accessible location between the return air grille and the unit. ActronAir does not supply or make any provisions for return air filter. FILTER RAILS FITTED (Filters not Supplied) FILTER SIZES - H x W x T (mm) 508 x 621 x 100 QUANTITY 4 407 x 621 x 100 2 ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. Page 7 of 12 R 9590-0014-03B Ver. 13 231027 3 PHASE + NEUTRAL 400 (415) V 50 Hz SUPPLY WIRING DIAGRAM ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. 63.00 kW 3 Phase Tri-Capacity NEUT LINE 1 LINE 2 LINE 3 EARTH MSCB-1 20 A CMC-1 O/L SET 17A (620) O/L SET 19A (700) MSCB-2 40 A CMC-2 O/L SET 34A (620) O/L SET 36A (700) MSCB-3 10 A IFC-1 O/L SET 10A CM-1 3 CM-2 3 IF-1 3 EC Vsp / Ain1U / I02 GND SCREEN WIRE Y1 GND RSA 35 RSA RSB 36 RSB MOTOR TERMINAL BLOCK DATA (SERVICE) 37 IFB ACTIVE 38 IFB NEUTRAL IFB EARTH 240V AC OUTPUT CB-1 16 A 33 34 22 21 20 19 MIMIC DISPLAY GND MIMIC DISPLAY +Vdc MIMIC DISPLAY RX-/TX- MIMIC DISPLAY RX+/TX+ SCREEN WIRE RJ12 PIN 6 TWISTED RJ12 PIN 5 RJ12 PIN 2 TWISTED RJ12 PIN 1 RJ12 PIN 4 TWISTED RJ12 PIN 3 HCT-1 LCT-1 RS1 LSC-1 HCT-2 LCT-2 RS2 LSC-2 HCT-2 LCT-2 RS3 LSC-3 OF-1 1 OF-2 1 OF-3 1 FT1 FT2 FIRE TRIP TERMINALS TO USE FIRE TRIP REMOVE JUMPER BETWEEN RED TERMINALS AND CONNECT TO A NORMALLY CLOSED CONTACT - 240V AC 10A MINIMUM RCBO 16A / 30mA GPO N A E 250VAC 10A MAX LOAD AVAILABLE FOR GPO - SERVICE EQUIPMENT USE ONLY PAIR INPUTS FOR MIMIC REMOTE DISPLAY CONNECTION BY INSTALLER NOTE: USE AWG24 (7/0.20) SHIELDED TWISTED PAIR DATA CABLE PAIR PAIR OCB RS4 TO IF-1 TERMINAL EARTH EARTH N 240VAC-N TX 72 VA CB-3 6 A 240V AC 24V AC FAULT RELAY OUTPUT N/O FAULT RELAY OUTPUT N/C RELAY COMMON INPUT 21 24 21 24 LP-1 LP-2 RS5 GND Vsp / Ain1U / I02 DRM 1 INPUT DRM 2 INPUT DRM 3 INPUT REMOTE ON/OFF INPUT STAGE 1 24V AC IN STAGE 2 24V AC IN CMC-1 CCH-2 CCH-1 CMC-2 FINAL COMMISSIONING FAN SETPOINT VOLTAGE Fan Speed: Date: .................... V or % ....../....../..... AH-PB CB CCH CM CMC GPO HCT HP IF IFC LCT LP LSC MSCB OCB OF R RS RV RCBO TERM TX LEGEND STAGE 3 24V AC IN HEAT 24V AC IN MULTI INPUT SELECTION TABLE MULTI INPUT MATRIX A DESCRIPTION SUPPLY AIR TEMP TYPE SENSOR B ECONOMY MODE DIGITAL INPUT C NIGHT MODE DIGITAL INPUT D COMP STAGE CONTROL 0-10V ANALOGUE E IN-FAN SPEED CONTROL 0-10V ANALOGUE AFTER HOURS CONTROL INPUT INSTALLATION INSTRUCTION NOTE: CL01, CP05 & CP10 CONTROLLERS ONLY. 3RD PARTY CONTROLS REFER TO INSTALLATION MANUAL. REMOVE LOOP WIRE * IMPULSE PUSH BUTTON N/C CONNECTION SHOWN * 5 SEC CONTACT BREAK REQUIRED FOR AFTER HOURS ACTIVATION 18 AFTER HOURS 17 RTN AIR SENSOR 16 RTN AIR SENSOR (GND) 18 AFTER HOURS 17 RTN AIR SENSOR 16 RTN AIR SENSOR (GND) 15 MULTI INPUT 2 14 COMMON (GND) 13 MULTI INPUT 1 12 N/A 11 COMMON (GND) 10 REMOTE ON/OFF 9 8 7 6 5 4 3 2 1 SEE MULTI INPUT SELECTION TABLE FOR OPTIONS 3RD PARTY CONTROL INPUTS - VOLT FREE RELAY CONTACT REQUIRED Page 8 of 12 PKY620T 9590-0014-03B Ver. 13 231027 Base R Model No: PKY620-700T Description: Variation Code: Variations: STANDARD B CHANGED TERMINAL DESC.'S FOR ID FAN TO ALLOW DIFFERENT MANUFACTURERS CONNECTIONS, REMOVE DEFAULT FAN SPEED SETTINGS TABLE. SET I/D FAN O/L TO 10A 3710 JL 14-03-2023 CM100 TRI-CAPACITY CONTROL SYSTEM WIRING DIAGRAM Rev. A Description ORIGINAL PCR By Date This drawing remains the intellectual property of Actron Engineering Pty Ltd. Reproduction, modification and/or distribution are prohibited without written consent. Drawn: Approved: JL RL Date: 11-01-2021 Drawing No: Date: 14-03-2023 0515-8606 Revision Size: B A3 ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. $ NOTE: UNIT VIEWED FROM AIR HANDLING END - SIZE AND POSITION OF RETURN & SUPPLY ARE INDICATIVE ONLY, SEE TABLE FOR ACTUAL SIZE AND POSITION FOR EACH PARTICULAR MODEL - ALL FLANGES ARE OUTSIDE DIMENSIONS - ALL FLANGES ARE RAW EDGE EXCEPT FOR DOWN SUPPLY (LD) & DOWN RETURN (D) ON PKY820-960 WHICH HAVE A 26mm INTERNAL RETURN FLANGE. % - ALL DIMENSIONS ARE FROM OUTSIDE EDGE OF BASE "L" "N" "R " "P" LV V "14" RETURN SUPPLY "16" "S" "Q" "15" "17" TOP VIEW "D" "B" "2" "4" & LS LF F SUPPLY OUTLET DIMENSIONS LF LD LS LV $ A B C D EFG H J K L MN P Q R S PKY470-540 653 583 404 117 653 583 266 170 201 653 583 418 303 583 653 300 120 PKY620-700 653 583 525 117 653 583 266 170 201 653 583 524 303 653 583 265 118 PKY820-960 1203 605 469 115 1254 651 98 102 203 1203 605 467 423 1203 605 122 127 RETURN INLET DIMENSIONS F D S V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 PKY470-540 903 703 292 98 903 703 142 106 201 903 703 360 252 903 703 140 100 % PKY620-700 903 703 385 98 903 703 142 106 201 903 703 385 252 903 703 140 100 PKY820-960 1203 605 469 136 1254 651 98 102 203 1203 605 467 422 1203 605 122 157 "13" "11" & S RETURN RETURN "10" "1" RETURN SUPPLY "A " "K " SUPPLY "9" "12" "3" "C " "J" "M" Page 9 of 12 PKY620T LD SUPPLY LD SUPPLY RETURN D ' LH SIDE END VIEW "H" "F" "6" "8" "G" LEGEND FOR SUPPLY POSITIONS LD = LEFT DOWN SUPPLY LF = LEFT FRONT SUPPLY LS = LEFT SIDE SUPPLY ( LV = LEFT VERTICAL SUPPLY LEGEND FOR RETURN POSITIONS D = RIGHT DOWN RETURN F = RIGHT FRONT RETURN S = RIGHT SIDE RETURN V = RIGHT VERTICAL RETURN "E" LD D RETURN SUPPLY BOTTOM VIEW UNLESS OTHERWISE SPECIFIED ) 1. 2. 3rd ANGLE PROJECTION. DIMENSIONS IN MILLIMETRES. 3. DO NOT SCALE. 4. TUBE ENDS MUST BE ROUND AND OF FULL DIAMETER. 5. TUBE MUST BE CLEAN AND FREE FROM BURRS INSIDE AND OUTSIDE AND SUITABLE OF FOR SOLDERING. 6. ALL BENDS 90 . 7. ALL SHEETMETAL'S DIMENSIONS OUTISDE. GENERAL TOLERANCES (UNLESS OTHERWISE SPECIFIED) 1. ALL TUBES 2. HOLE DIAMETER 3. FLAT PATTERN 4. FOLD 5. ANGLES & SQUARENESS 3 0.1/~0 0.5 / m 0.5 / m 1 B REV Drawing Release DESCRIPTION "5" "7" D RETURN RH SIDE ' S V LV STANDARD PKY470-960T SUPPLY & RETURN L**T VARIATIONS F ( LS LF D LD N/A DR 27/10/2023 PCR BY DATE ActronAir Pty Ltd 5 Irvine Place Norwest Business Park Bella Vista NSW 2153 PH. +61 2 8814 4000 A.B.N. 34 002 767 240 This drawing always remains the intellectual property of Actron Engineering Pty Ltd. Copying, Modifying or Distributing without written consent is prohibited DESCRIPTION: DRAWING NO. REV. PKY470-960T-L**T B STANDARD PKY470-960T SUPPLY & RETURN L***T VARIATIONS ) MATERIAL: FINISH: See Notes See Notes DRAWN BY: DRAWN DATE: APPROVED BY: SCALE: N.T.S DR 27/10/2023 DR 6+((7 2) A3 THIRD ANGLE PROJECTION 9590-0014-03B Ver. 13 231027 63.00 kW 3 Phase Tri-Capacity ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. $ NOTE: UNIT VIEWED FROM AIR HANDLING END - SIZE AND POSITION OF RETURN & SUPPLY ARE INDICATIVE ONLY, SEE TABLE FOR ACTUAL SIZE AND POSITION FOR EACH PARTICULAR MODEL - ALL FLANGES ARE OUTSIDE DIMENSIONS - ALL FLANGES ARE RAW EDGE EXCEPT FOR DOWN SUPPLY (LD) & DOWN RETURN (D) ON PKY820-960 WHICH HAVE A 26mm INTERNAL RETURN FLANGE. % - ALL DIMENSIONS ARE FROM OUTSIDE EDGE OF BASE "L" "N" & LS "K" SUPPLY "J" "M" LD SUPPLY LH SIDE ' 63.00 kW 3 Phase Tri-Capacity SUPPLY OUTLET DIMENSIONS LF LD LS LV $ ABCDE FGH J K LMNPQRS PKY470-540 653 583 404 117 653 583 266 170 201 653 583 418 303 583 653 300 120 PKY620-700 653 583 524 117 653 583 266 170 201 653 583 524 303 653 583 265 118 PKY820-960 1203 605 469 116 1254 651 98 102 203 1203 605 467 423 1203 605 122 127 "R" "P" SUPPLY LV RETURN INLET DIMENSIONS F D OA 1 2 3 4 5 6 7 8 9 18 19 20 21 % OA PKY470-540 903 703 295 80 NA NA NA NA NA 1197 557 138 227 "S" "Q" PKY620-700 903 703 385 97 NA NA NA NA NA 1197 557 248 227 PKY820-960 1203 605 469 136 1254 651 98 102 203 1258 668 441 255 TOP VIEW "D" "B" "2" "4" "21" "19" RETURN LF F OA SUPPLY LD SUPPLY RETURN D END VIEW "H" "F" "6" "8" "3" "1" "20" "18" OA D RETURN RH SIDE OUTSIDE AIR NOTE: ON MODELS PKY470T TO PKY700T ECONOMISER ie "OUTSIDE AIR" IS NOT & AVAILABLE AS A STANDARD OPTION WITH A "DOWN RETURN" ONLY AVAILABLE WITH A "FRONT RETURN" AS STANDARD. A VR REQUEST CAN BE MADE FOR SPECIAL CONFIGURATION OF OUTSIDE AIR. ' "A" "C" Page 10 of 12 "7" "G" PKY620T LEGEND FOR SUPPLY POSITIONS LD = LEFT DOWN SUPPLY LF = LEFT FRONT SUPPLY LS = LEFT SIDE SUPPLY ( LV = LEFT VERTICAL SUPPLY LEGEND FOR RETURN POSITIONS D = RIGHT DOWN RETURN F = RIGHT FRONT RETURN OA = OUTSIDE AIR RETURN NOTE: WEATHERHOOD IS AN OPTION UNLESS OTHERWISE SPECIFIED ) 1. 2. 3rd ANGLE PROJECTION. DIMENSIONS IN MILLIMETRES. 3. DO NOT SCALE. 4. TUBE ENDS MUST BE ROUND AND OF FULL DIAMETER. 5. TUBE MUST BE CLEAN AND FREE FROM BURRS INSIDE AND OUTSIDE AND SUITABLE OF FOR SOLDERING. 6. ALL BENDS 90 . 7. ALL SHEETMETAL'S DIMENSIONS OUTISDE. GENERAL TOLERANCES (UNLESS OTHERWISE SPECIFIED) 1. ALL TUBES 2. HOLE DIAMETER 3. FLAT PATTERN 4. FOLD 5. ANGLES & SQUARENESS 3 0.1/~0 0.5 / m 0.5 / m 1 B REV Drawing Release DESCRIPTION "E" LD D OA LS LV "5" RETURN SUPPLY LF F OA ( BOTTOM VIEW STANDARD PKY470-960T SUPPLY & RETURN L**T-E VARIATIONS LD D N/A DR 27/10/2023 PCR BY DATE ActronAir Pty Ltd 5 Irvine Place Norwest Business Park Bella Vista NSW 2153 PH. +61 2 8814 4000 A.B.N. 34 002 767 240 This drawing always remains the intellectual property of Actron Engineering Pty Ltd. Copying, Modifying or Distributing without written consent is prohibited DESCRIPTION: DRAWING NO. REV. STANDARD PKY470-960T SUPPLY & RETURN L***T-E VARIATIONS MATERIAL: FINISH: See Notes See Notes PKY470-960T-L**T-E B ) DRAWN BY: DRAWN DATE: APPROVED BY: SCALE: N.T.S DR 27/10/2023 DR 6+((7 2) A3 THIRD ANGLE PROJECTION 9590-0014-03B Ver. 13 231027 ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. $ NOTE: UNIT VIEWED FROM AIR HANDLING END - SIZE AND POSITION OF RETURN & SUPPLY ARE INDICATIVE ONLY, SEE TABLE FOR ACTUAL SIZE AND POSITION FOR EACH PARTICULAR MODEL - ALL FLANGES ARE OUTSIDE DIMENSIONS - ALL FLANGES ARE RAW EDGE EXCEPT FOR DOWN SUPPLY (RD) & DOWN RETURN (D) ON PKY820-960 WHICH HAVE A 26mm INTERNAL RETURN FLANGE. % - ALL DIMENSIONS ARE FROM OUTSIDE EDGE OF BASE "11" "13" "16" "14" V RV SUPPLY RETURN "17" 15" "Q" "S" TOP VIEW "4" "2" "B" "D" & S F RF "R " "P" SUPPLY OUTLET DIMENSIONS RF RD RS RV $ A B C D EFG H J K L MN P Q R S PKY470-540 653 583 404 117 653 583 266 170 201 653 583 418 303 583 653 300 120 PKY620-700 653 583 524 117 653 583 266 170 201 653 583 524 303 653 583 265 118 PKY820-960 1203 605 469 115 1254 651 98 102 203 1203 605 467 423 1203 605 122 127 RETURN INLET DIMENSIONS F D S V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 PKY470-540 903 703 292 98 903 703 142 106 201 903 703 360 252 903 703 140 100 % PKY620-700 903 703 385 98 903 703 142 106 201 903 703 385 252 903 703 140 100 PKY820-960 1203 605 469 136 1254 651 98 102 203 1203 605 467 422 1203 605 122 157 "N" "L" & RS SUPPLY RETURN "K " "A" SUPPLY RETURN "1" "10" RETURN "J" "M" "C" "3" "9" "12" Page 11 of 12 PKY620T D RETURN D RETURN SUPPLY RD RD SUPPLY ' LH SIDE END VIEW RH SIDE ' "8" "6" "F" "H" "G" "7" LEGEND FOR SUPPLY POSITIONS RD = RIGHT DOWN SUPPLY RF = RIGHT FRONT SUPPLY RS = RIGHT SIDE SUPPLY ( RV = RIGHT VERTICAL SUPPLY LEGEND FOR RETURN POSITIONS D = LEFT DOWN RETURN F = LEFT FRONT RETURN S = LEFT SIDE RETURN V = LEFT VERTICAL RETURN "5" D RD SUPPLY RETURN BOTTOM VIEW UNLESS OTHERWISE SPECIFIED ) 1. 2. 3rd ANGLE PROJECTION. DIMENSIONS IN MILLIMETRES. 3. DO NOT SCALE. 4. TUBE ENDS MUST BE ROUND AND OF FULL DIAMETER. 5. TUBE MUST BE CLEAN AND FREE FROM BURRS INSIDE AND OUTSIDE AND SUITABLE OF FOR SOLDERING. 6. ALL BENDS 90 . 7. ALL SHEETMETAL'S DIMENSIONS OUTISDE. GENERAL TOLERANCES (UNLESS OTHERWISE SPECIFIED) 1. ALL TUBES 2. HOLE DIAMETER 3. FLAT PATTERN 4. FOLD 5. ANGLES & SQUARENESS 3 0.1/~0 0.5 / m 0.5 / m 1 B REV Drawing Release DESCRIPTION "E" SV RV F RF RS ( STANDARD PKY470-960T SUPPLY & RETURN R**T VARIATIONS D RD N/A DR 27/10/2023 PCR BY DATE ActronAir Pty Ltd 5 Irvine Place Norwest Business Park Bella Vista NSW 2153 PH. +61 2 8814 4000 A.B.N. 34 002 767 240 This drawing always remains the intellectual property of Actron Engineering Pty Ltd. Copying, Modifying or Distributing without written consent is prohibited DESCRIPTION: DRAWING NO. REV. PKY470-960T-R**T B STANDARD PKY470-960T SUPPLY & RETURN R***T VARIATIONS ) MATERIAL: FINISH: See Notes See Notes DRAWN BY: DRAWN DATE: APPROVED BY: SCALE: N.T.S DR 27/10/2023 DR 6+((7 2) A3 THIRD ANGLE PROJECTION 9590-0014-03B Ver. 13 231027 63.00 kW 3 Phase Tri-Capacity 63.00 kW 3 Phase Tri-Capacity ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice. Please check prior to purchase. Copyright © 2016 Actron Engineering Pty. Ltd. $ NOTE: UNIT VIEWED FROM AIR HANDLING END - SIZE AND POSITION OF RETURN & SUPPLY ARE INDICATIVE ONLY, SEE TABLE FOR ACTUAL SIZE AND POSITION FOR EACH PARTICULAR MODEL - ALL FLANGES ARE OUTSIDE DIMENSIONS - ALL FLANGES ARE RAW EDGE EXCEPT FOR DOWN SUPPLY (LD) & DOWN RETURN (D) ON PKY820-960 WHICH HAVE A 26mm INTERNAL RETURN FLANGE. % - ALL DIMENSIONS ARE FROM OUTSIDE EDGE OF BASE "19" "21" & OA OUTSIDE AIR "18" RETURN RV SUPPLY OA "Q" "S" TOP VIEW "B" "D" F RF OA SUPPLY "C" "A" "R" "P" SUPPLY OUTLET DIMENSIONS RF RD RS RV $ ABCDE FGH J K LMNPQRS PKY470-540 653 583 404 117 653 583 266 170 201 653 583 418 303 583 653 300 120 PKY620-700 653 583 524 117 653 583 266 170 201 653 583 524 303 653 583 265 118 PKY820-960 1203 605 469 115 1254 651 98 102 203 1203 605 467 423 1203 605 122 127 RETURN INLET DIMENSIONS F D OA 1 2 3 4 5 6 7 8 9 18 19 20 21 % PKY470-540 903 703 295 80 NA NA NA NA NA 1197 557 138 227 PKY620-700 903 703 385 97 NA NA NA NA NA 1197 557 248 227 PKY820-960 1203 605 469 136 1254 651 98 102 203 1258 668 441 255 "N" "L" RS SUPPLY NOTE: ON MODELS PKY470T TO PKY700T & ECONOMISER ie "OUTSIDE AIR" IS NOT AVAILABLE AS A STANDARD OPTION WITH A "DOWN RETURN" ONLY AVAILABLE WITH A "FRONT RETURN" AS STANDARD. A VR REQUEST CAN BE MADE FOR SPECIAL CONFIGURATION OF OUTSIDE AIR. "K" "M" "20" D RETURN D RETURN SUPPLY RD SUPPLY RD ' LH SIDE END VIEW RH SIDE ' "8" "6" "F" "H" "G" "7" "5" LEGEND FOR SUPPLY POSITIONS OA RD = RIGHT DOWN SUPPLY RF = RIGHT FRONT SUPPLY RS = RIGHT SIDE SUPPLY ( RV = RIGHT VERTICAL SUPPLY LEGEND FOR RETURN POSITIONS D = LEFT DOWN RETURN F = LEFT FRONT RETURN OA = OUTSIDE AIR RETURN NOTE: WEATHERHOOD IS AN OPTION UNLESS OTHERWISE SPECIFIED ) 1. 2. 3rd ANGLE PROJECTION. DIMENSIONS IN MILLIMETRES. 3. DO NOT SCALE. 4. TUBE ENDS MUST BE ROUND AND OF FULL DIAMETER. 5. TUBE MUST BE CLEAN AND FREE FROM BURRS INSIDE AND OUTSIDE AND SUITABLE OF FOR SOLDERING. 6. ALL BENDS 90 . 7. ALL SHEETMETAL'S DIMENSIONS OUTISDE. GENERAL TOLERANCES (UNLESS OTHERWISE SPECIFIED) 1. ALL TUBES 2. HOLE DIAMETER 3. FLAT PATTERN 4. FOLD 5. ANGLES & SQUARENESS 3 0.1/~0 0.5 / m 0.5 / m 1 B REV Drawing Release DESCRIPTION D RD SUPPLY RETURN BOTTOM VIEW "E" RS RV STANDARD PKY470-960T SUPPLY & RETURN R**T-E VARIATIONS OA F RF ( RD D N/A PCR DR 27/10/2023 BY DATE ActronAir Pty Ltd 5 Irvine Place Norwest Business Park Bella Vista NSW 2153 PH. +61 2 8814 4000 A.B.N. 34 002 767 240 This drawing always remains the intellectual property of Actron Engineering Pty Ltd. Copying, Modifying or Distributing without written consent is prohibited DESCRIPTION: STANDARD PKY470-960T SUPPLY & RETURN R**T-E VARIATIONS MATERIAL: See Notes DRAWN BY: FINISH: See Notes DRAWN DATE: APPROVED BY: DR 27/10/2023 DR DRAWING NO. REV. PKY470-960T-R**T-E B ) SCALE: N.T.S 6+((7 2) A3 THIRD ANGLE PROJECTION Page 12 of 12 PKY620T 9590-0014-03B Ver. 13 231027Adobe PDF Library 17.0 Adobe InDesign 19.0 (Windows)