SMARTEH LPC-2.DX1 Longo Programmable Controller User Manual
File info: application/pdf · 17 pages · 928.74KB
USER MANUAL
Digital output modules | Smarteh
https://www.smarteh.com/wp-content/uploads/2020/12/225dx123001001 lpc2 dx1 usrman
NEW LPC-2.DX1 | 1DO (NO) relay output modul with inrush current protection
Extracted Text
USER MANUAL Longo programmable controller LPC-2.DX1 Relay module Version 2 SMARTEH d.o.o. / Poljubinj 114 / 5220 Tolmin / Slovenia / Tel.: +386(0)5 388 44 00 / e-mail: info@smarteh.si / www.smarteh.si Longo programmable controller LPC-2.DX1 Written by SMARTEH d.o.o. Copyright � 2024, SMARTEH d.o.o. User Manual Document Version: 2 May, 2024 i Longo programmable controller LPC-2.DX1 STANDARDS AND PROVISIONS: Standards, recommendations, regulations and provisions of the country in which the devices will operate, must be considered while planning and setting up electrical devices. Work on 100 .. 240 V AC network is allowed for authorized personnel only. DANGER WARNINGS: Devices or modules must be protected from moisture, dirt and damage during transport, storing and operation. WARRANTY CONDITIONS: For all modules LONGO LPC-2 � if no modifications are performed upon and are correctly connected by authorized personnel � in consideration of maximum allowed connecting power, warranty of 24 months is valid from the date of sale to the end buyer, but not more than 36 months after delivery from Smarteh. In case of claims within warranty time, which are based on material malfunctions the producer offers free replacement. The method of return of malfunctioned module, together with description, can be arranged with our authorized representative. Warranty does not include damage due to transport or because of unconsidered corresponding regulations of the country, where the module is installed. This device must be connected properly by the provided connection scheme in this manual. Misconnections may result in device damage, fire or personal injury. Hazardous voltage in the device can cause electric shock and may result in personal injury or death. NEVER SERVICE THIS PRODUCT YOURSELF! This device must not be installed in the systems critical for life (e.g. medical devices, aircrafts, etc.). If the device is used in a manner not specified by the manufacturer, the degree of protection provided by the equipment may be impaired. Waste electrical and electronic equipment (WEEE) must be collected separately! LONGO LPC-2 complies to the following standards: � EMC: EN 61000-6-3:2007 + A1:2011, EN 61000-6-1:2007, EN 61000- 3-2:2006 + A1:2009 + A2: 2009, EN 61000-3-3:2013 � LVD: IEC 61010-1:2010 (3rd Ed.), IEC 61010-2-201:2013 (1st Ed.) Smarteh d.o.o. operates a policy of continuous development. Therefore we reserve the right to make changes and improvements to any of the products described in this manual without any prior notice. MANUFACTURER: SMARTEH d.o.o. Poljubinj 114 5220 Tolmin Slovenia ii Longo programmable controller LPC-2.DX1 Longo programmable controller LPC-2.DX1 1 ABBREVIATIONS................................................................................1 2 DESCRIPTION...................................................................................2 3 FEATURES.......................................................................................3 4 OPERATION.....................................................................................4 4.1 SmartehIDE Parameters...............................................................5 5 INSTALLATION..................................................................................6 5.1 Connection scheme....................................................................6 5.2 Mounting instructions.................................................................8 6 TECHNICAL SPECIFICATIONS................................................................10 7 MODULE LABELING...........................................................................11 8 CHANGES .....................................................................................12 9 NOTES..........................................................................................13 iii Longo programmable controller LPC-2.DX1 1 ABBREVIATIONS DC AC RX TX UART NO PLC Direct Current Alternating Current Receive Transmit Universal Asynchronous Receiver-Transmitter Normally Open Programmable Logic Controller 1 Longo programmable controller LPC-2.DX1 2 DESCRIPTION LPC-2.DX1 is a relay output module with inrush current protection and galvanic isolated output. It can be used in a wide range of operation. It is suitable to be used with inductive or capacitive loads (e.g. reflectors, contractors, motors). LED indicates active signal present on module output and fuse status. LPC-2.DX1 is controlled and powered from the main module (e.g. LPC-2.MU1, LPC-2.MC9, ...) via Right internal bus. 2 Longo programmable controller LPC-2.DX1 3 FEATURES Figure 1: LPC-2.DX1 module Table 1: Technical data Relay digital output with make contacts (NO), inrush current limited, galvanic isolated Signal LED Blown fuse detection Supplied from main module Small dimensions and standard DIN EN50022-35 rail mounting 3 Longo programmable controller LPC-2.DX1 4 OPERATION LPC-2.DX1 module can be controlled from main PLC module (e.g. LPC-2.MC9, LPC-2.MM1). Module parameters can be read or written via Smarteh IDE software. LPC-2.DX1 module can also be controlled by the remote input output main module (e.g. LPC-2.MU1). WARNING: Upon activation of the output, current flows through the NTC thermistor, limiting inrush current. Consequently, the NTC thermistor heats up during output activation. To ensure reliable operation, the time between output cycles must be sufficient to allow the NTC thermistor to cool down completely. The software-defined minimum time delay between output deactivation and reactivation is set to 20 seconds. However, this timeout value is not intended to be the maximum limit. It serves as a reminder to consider the cooling requirements of the NTC thermistor when designing the operational cycle of your application. Refer to the included time graph for a visual representation of the output ON delay (toff) after device power up and the ON delay (toff) between output cycles. In case the temperature measured by the measuring NTC thermistor exceeds 80�C, the output will be deactivated. Figure 2: Output ON-delay 4 Longo programmable controller LPC-2.DX1 4.1 SmartehIDE Parameters Input Internal temperature [DX1_x_ai_internal_temp]: Internal temperature measurement on the PCB. Type: UINT Raw to engineering data: 0 .. 65535 0 .. 655.35 �C Fuse status [DX1_x di_fuse_status]: Fuse digital input status. Type: BOOL Raw to engineering data: 0 Fuse blown 1 Fuse OK Output Relay digital output [DX1_x_do_out]: Relay digital output status. Type: BOOL Raw to engineering data: 0 Digital output OFF 1 Digital output ON 5 Longo programmable controller LPC-2.DX1 5 INSTALLATION 5.1 Connection scheme Figure 3: Connection scheme Table 2: IN IN.3 IN.4 L Power supply input � line, 100 .. 240 V AC, 50/60 Hz N Power supply input � neutral, 100 .. 240 V AC, 50/60 Hz Table 3: OUT OUT.1 L1 OUT.2 N1 Power supply output � line, 100 .. 240 V AC, 50/60 Hz Power supply output � neutral, 100 .. 240 V AC, 50/60 Hz Table 4: Fuse Fuse 4A (T-slow) Cartridge fuse 5x20 mm Table 5: LED LED: green Status LED ON: Output switched ON and power on output OFF: Output switched OFF and no power on output Blinking: No power on output, fuse blown or no voltage on input 6 Longo programmable controller LPC-2.DX1 Table 6: K1 Internal BUS Data & DC power supply Connection to I/O module Table 7: K2 Internal BUS Data & DC power supply Connection to I/O module 7 Longo programmable controller LPC-2.DX1 5.2 Mounting instructions Figure 4: Housing dimensions 9 0 9 5 3 6 18 60 � Dimensions in millimeters. All connections, module attachments and assembling must be done while module is not connected to the main power supply. Mounting instructions: 1. Switch OFF main power supply. 2. Mount LPC-2.DX1 module to the provided place inside an electrical panel (DIN EN50022-35 rail mounting). 3. Mount other LPC-2 modules (if required). Mount each module to the DIN rail first, then attach modules together through K1 and K2 connectors. 4. Connect input and output wires according to the connection scheme in Figure 2. 5. Switch ON main power supply. Dismount in reverse order. For mounting/dismounting modules to/from DIN rail a free space of at least one module must be left on the DIN rail. NOTE: LPC-2 main module should be powered separately from other electrical appliance connected to LPC-2 system. Signal wires must be installed separately from power and high voltage wires in accordance with general industry electrical installation standard. 8 Longo programmable controller LPC-2.DX1 Figure 5: Minimum clearances The clearances above must be considered before module mounting. Figure 6: Fuse replacement 9 Longo programmable controller LPC-2.DX1 6 TECHNICAL SPECIFICATIONS Table 8: Technical specifications Power supply Max. power consumption Rated input voltage Maximum operating current SW-defined minimum OFF time1 Fuse Connection type Dimensions (L x W x H) Weight Ambient temperature Ambient humidity Maximum altitude Mounting position Transport and storage temperature Pollution degree Overvoltage category Electrical equipment Protection class From the main module via internal bus 0.5 W 100 .. 240 V AC, 50/60 Hz 4 A 20 s 4 A (T-slow), 250 V, Cartridge fuse 5x20 mm screw type connectors for stranded wire 0.75 to 2.5 mm2 90 x 18 x 60 mm 70 g 0 to 50 �C max. 95 %, no condensation 2000 m vertical -20 to 60 �C 2 II Class II (double insulation) IP 30 1 Software-defined minimum time between switching off and switching on the output again. 10 Longo programmable controller LPC-2.DX1 7 MODULE LABELING Figure 7: Label Label (sample): XXX-N.ZZZ P/N: AAABBBCCDDDEEE S/N: SSS-RR-YYXXXXXXXXX D/C: WW/YY Label description: 1. XXX-N.ZZZ - full product name. XXX-N - Product family ZZZ - product 2. P/N: AAABBBCCDDDEEE - part number. AAA - general code for product family, BBB - short product name, CCDDD - sequence code, � CC - year of code opening, � DDD - derivation code, EEE � version code (reserved for future HW and/or SW firmware upgrades). 3. S/N: SSS-RR-YYXXXXXXXXX - serial number. SSS � short product name, RR � user code (test procedure, e.g. Smarteh person xxx), YY � year, XXXXXXXXX � current stack number. 4. D/C: WW/YY - date code. � WW � week and � YY � year of production. Optional 1. MAC 2. Symbols 3. WAMP 4. Other 11 Longo programmable controller LPC-2.DX1 8 CHANGES The following table describes all the changes to the document. Date 10.05.24 V. Description 1 The initial version, issued as LPC-2.DX1 module UserManual. 12 Longo programmable controller LPC-2.DX1 9 NOTES 13