MDA Scientific Midas® Gas Detector

1. Introduction
The Midas® gas detector is an extractive gas sampling system that draws a sample locally or from a remote point to a sensor cartridge that is located inside the detector's chassis. A wide range of toxic, flammable and oxygen gas sensor cartridges are available that enable detection of gases used or generated in the Semiconductor and other manufacturing industries. The Midas® gas detector is comprised of 4 main parts: the main chassis, the mounting bracket assembly, the sensor cartridge and the unit cover. Diagram 1 details the Midas® general arrangement. Additionally there are optional Pyrolyzer modules required for the detection of NF3 and PFCs and an optional LonWorks® interface is available. This Quick Start Guide provides basic installation, setup and operation information for the main detector unit. For more detailed information on other features and options, please refer to the Midas® Operating Manual.
Diagram 1. Midas® general arrangement exploded view
? ??????? ??????????????? ? ? ? ?????????????????????????????????????????????????????????????????????????????????????????????? ?
3

2. Mounting Details
The Midas® gas detector has an integral mounting bracket assembly that is easily mounted to a suitable vertical surface such as a wall, tool housing, mounting plate on a pole etc.
Drill Template

Drill 2x M4 holes (0.15 8in)

58.50mm (2.3 in)

Note When reproducing this diagram, be sure to check dimensional accuracy before drilling.
4

2. Mounting Details (cont'd)
The following steps and diagrams show how to separate the mounting bracket assembly from the main chassis and mount it on a vertical flat surface.
1. Unscrew the thumbscrew located on the front panel. 2. Remove the cover by pulling it forwards off the main chassis. On new Midas®
units, be sure to remove the internal packing card securing the pump. Failure to remove this packing will result in damage to the Midas® unit. (See diagram below) 3. Unscrew the two retaining screws located at the bottom front of the chassis. 4. Holding the mounting bracket assembly with one hand use the other to carefully pull the main chassis forward to disconnect it from the mounting bracket assembly. 5. Using the drill template provided drill two holes 2.3 in (58.50mm) vertically apart for 2 x round head M4 screws. 6. Partially screw the fixings into the mounting surface. 7. Place the mounting bracket assembly over the screws so they pass through the mounting holes and then slide down to locate in the slots. 8. Tighten the screws to secure the mounting bracket assembly.
Diagram 3. Mechanical installation

Removing cover chassis

loosen

mounting bracket

thsheIMipppPRuimOinengmRpstpoTamAvrloloeaNtdteiTinuoctlnNteeiorObnnTraffIolrCoremE !

cover

Chassis Mounting Screws
Internal packing card Remove before use.

5

2. Mounting Details (cont'd)
chassis Removing chassis

mounting bracket

thsheIMipppPRuimOinengmRpstpoTamAvrloloeaNtdteiTinuoctlnNteeiorObnnTraffIolrCoremE !

Internal packing card Remove before use.

Attaching Bracket with screws on a flat surface
screws

mounting bracket

Optional DIN Rail Mounting

DIN Rail Bracket (MIDAS-A-036)
Spacer Bracket

2x M4 Screws Secures Midas® to Spacer Bracket
6

4x M3 Screws Secures DIN Rail Bracket to Spacer Bracket

3. Electrical Installation

Access for the electrical wires to the terminal module is made via the PG16 cable gland located at the bottom of the mounting bracket assembly. The cable gland can be removed and replaced with a suitable conduit fitting if required. The wire routing of a typical installation is shown in the diagram below.

Diagram 4. Simplified Schematic

Diagram 5. Wiring Diagram4

4-20mA Analog Output Terminals

Relay NO/NC Jumpers
Relay Contact Terminals

Power Switch

Cable Gland

Ethernet Cable

The terminals used are suitable for conductors of 24 to 14 AWG (0.5 to 1.8mm Dia.). The use of 16 AWG (1.5 mm Dia.) conductors is recommended.
If Power over Ethernet (PoE) is used to power the device, then 24 VDC power must not also be connected to the device, (or conversely if 24 VDC is used to power the Midas®, then electrical power via the Ethernet port must not be applied). Failure to observe this requirement may cause damage to the gas detection system and will not be covered by the standard warranty.
When connecting the wires ensure that the power switch is in the off position.

7

4. Refitting the Main Chassis
The main chassis can be refitted to the mounting bracket assembly using the following steps.
1. Align the PCB at the top rear of the main chassis with the connector located at the top of the mounting bracket assembly
2. At the same time align the two tubes at the bottom rear of the main chassis with the two tubes located on the bottom of the mounting bracket assembly.
3. Slide the chassis backwards on the mounting bracket assembly so that the PCB and connector and tubes engage simultaneously. (See diagram below).
4. Ensure the PCB, connector and tubes are fully engaged by firmly pushing the main chassis horizontally backward on the mounting bracket assembly (WARNING: DO NOT PUSH ON THE LCD AS THIS MAY CAUSE DAMAGE).
5. Align the two fixing screws located at the bottom of the chassis with the screw threads on the mounting bracket assembly.
6. Tighten the screws to secure the chassis to the mounting bracket assembly. Diagram 4. Simplified Schematic
CONNECTOR PCB
TUBES
8

5. Installing the Sensor Cartridge

The Midas® sensor cartridge is supplied separately and needs to be fitted to the detector's main chassis. The following steps and diagrams detail the procedure for installing the sensor cartridge for the first time. This procedure is carried out with the power off and the detector cover removed.
1. Verify the part number and type of sensor cartridge is correct for your application, then remove sensor cartridge from packaging.
2. Remove cap from cartridge.
3. Add label for secondary gases (if necessary). 4. Align pins at the top of the sensor cartridge with the socket in the sensor cartridge
chamber. 5. Carefully push the sensor cartridge into the sensor cartridge chamber until fully
seated.
6. Lock the sensor cartridge in place using the tabs on either side of the sensor cartridge to secure the cartridge to the main chassis.
7. Switch the power switch on the terminal module to the `on' position. 8. Reattach the detector cover by aligning the slots on either side with the locating
tabs on the mounting bracket assembly. 9. Push the cover horizontally until fully seated. 10. Tighten the thumbscrew on the front panel.
Diagram 6. Installing the sensor cartridge

chassis

Gas Semnsiodr aCsartridge NITUPRSNsONezGe: b:lMElwy0NIe2D:Ng30TAeF47RSr34-Ia0-5FSn96La--6UH2ly70OFt0i0cXRs6IDE
cartridge

How cover is fitted

?????????????????????????????????????? slots

tighten

cartridge fitted
tabs
Note:
In a first-time start up, an F49 or F88 fault code may be displayed; there is no actual fault and the fault message can be cleared by depressing the `X' button for a few seconds. To properly activate the Midas® with a cartridge for the first time:
· When "ChAngE gAS" or "FIrSt CELL" scrolls on the display, hit the `3' on the Midas® front panel.
· When the "reboot" completes then press and hold the "X" to clear any latched fault(s). · Confirm that the green LED is flashing. · Confirm that the yellow and red LEDs are off. · Confirm the display shows a concentration of zero (as appropriate). The cartridge has now been accepted by the Midas® as the correct type. If the above steps were not performed at initial start-up, then remove the cartridge and cycle power. Once the Midas® has completed the "reboot" process, install the cartridge to be used and repeat the steps above.

9

6. Diagnostics

Fault Code

Description

m9

Simulated Maintenance Fault

m10 Over range.

Condition

Recovery

User has generated a simulated fault.

Reset simulated fault.

A large concentration has been detected. The Midas® requires an independent confirmation that the gas hazard is gone.

Supply known clean air to the Midas® and clear this fault.

m11

User calibration expired

m12

Cartridge expires soon.

m13 Flow low.

m14 Interferent present.

m15

Temperature near limit.

m16 Baseline fault.

m17 Inhibit timeout.

The user specified calibration interval has elapsed.

Perform zero and span calibrations. Increase span calibration period.

Cartridge is old and will expire soon.

Replace the cartridge with a new cartridge.

Midas® is no longer able to regulate flow.
An interferent is degrading the ability of the Midas® to detect gas.

Check filters and pump. Check application.

Temperature within 2° Celsius of limit.

Check installation environment.

Sensor baseline has drifted.

Check for background gas concentration, temperature or humidity fluctuations. Perform zero calibration. Replace cartridge.

Transmitter has been in inhibit mode too long.

Resume monitoring or increase timeout value.

F39 Simulated Fault F40 Sensor overdosed. F41 Baseline fault. F42 Calibration expired.

User has generated a simulated fault.

Reset simulated fault.

Sensor has been exposed to high gas concentrations for long periods.
Sensor baseline has drifted.

Replace cartridge.
Check for background gas concentration, temperature or humidity fluctuations. Perform zero calibration. Replace cartridge

Too long since last calibration.

Replace or calibrate the cartridge.

F43 Cartridge expired.

Cartridge is too old.

Replace cartridge.

F44 Cell failure.

Cartridge has failed ReflexTM check.

Replace cartridge.

F45 Stabilization timeout. Cartridge has failed to stabilize.

If temperature or humidity shocks exist, precondition the cartridge.
Check for background gas concentration. Replace cartridge.

F46

Cartridge analog failure.

Electronic Failure Gas concentration greater than full scale.

Replace cartridge.

F47

Cartridge memory invalid.

Checksum error.

Replace cartridge.

F48 Cartridge absent.

No communications.

Reseat cartridge. Replace cartridge.

F49 Cartridge wrong type. Cartridge type found to be incorrect after boot-up. Replace cartridge or press `3' accept if correct.

F80

Temperature limits exceeded.

F81 Flow fail.

Temperature is outside limits Flow < 70% of nominal for 15 seconds.

F82

Excessive electrical noise.

Internal electronics repeatedly noisy.

Check installation environment.
Check filters. Check for kinked tubing. Replace pump.
Check grounding of Midas® chassis. Check termination of cable shields. Relocate the Midas® further from noise sources. Add ferrite inductors to cables.

10

Fault Code

Description

F83 Pyrolyzer fail.

Condition Pyrolyzer fails to heat.

F84 Misc. transmitter fault. Transmitter is defective.

Recovery
Check electrical connection to pyrolyzer. Replace pyrolyzer.
Service or replace Midas®.

F86 Coprocessor fail

Coprocessor is damaged.

Contact Honeywell Analytics Service.

F87

Pyrolyzer temp limits exceeded

Pyrolyzer temperature exceeded.

Clean pyrolyzer cooling vents. Contact Honeywell Analytics Service.

F88 Pyrolyzer heater fail Pyrolyzer heater failed.

Replace the pyrolyzer. Contact Honeywell Analytics Service.

F89

Pyrolyzer power unreg

Target power not achieved within specified time span.

If 24VDC power check, 21.6 < V in < 26.4 Contact Honeywell Analytics Service. Replace pyrolyzer.

F90

Pyrolyzer heater mismatch

Requires High Temperature Pyrolyzer (MIDASA-HTP)

Contact Honeywell Analytics Service.

F91

HTP module required

Check that MIDAS-S-CFX or MIDAS-E-CFX is installed for the high temperature pyrolyzer version

Change to HT Pyrolyzer

Data value: 0x0800 0P3 pyrolyzer failed to get up to temperature

Replace pyrolyzer heater

F92

0P3 pyrolyzer module Data value: 0x1000

failure

0P3 pyrolyzer flow is out-of-range

Check flow connections between Midas and 0P3 pyrolyzer

Data value: others 0P3 pyrolyzer internal failure

Contact Honeywell Analytics Service.

"Hot" and "Cool" messages are informational events that can be generated under two conditions: 1. Immediately after the detector powers up. 2. When the state changes from cool to hot or hot to cool.

"Hot" means the temperature inside the cartridge is at 40°C or above. "Cool" means the temperature inside the cartridge is below 40°C. In both cases the event data field will list the actual temperature at the time of the event.

11

Find out more www.honeywellanalytics.com
Americas Honeywell Analytics 405 Barclay Boulevard Lincolnshire, IL 60069 Tel: +1 847 955 8200 Toll free: +1 800 538 0363 Fax: +1 847 955 8208 detectgas@honeywell.com
Europe, Middle East, and Africa Life Safety Distribution AG(LSD) Javastrasse 2 8604 Hegnau Switzerland Tel: +41 (0)44 943 4300 Fax: +41 (0)44 943 4398 gasdetection@honeywell.com
Technical Services ha.global.service@honeywell.com www.honeywell.com
Asia Pacific Honeywell Analytics Asia Pacific #508, Kolon Science Valley (1) 187-10 Guro-Dong, Guro-Gu Seoul, 152-729 Korea Tel: +82 (0)2 6909 0300 Fax: +82 (0)2 2025 0388 analytics.ap@honeywell.com

honeywell
MIDAS-A-020 Rev 4.0 February 2013 © 2013 Honeywell Analytics



References

Adobe InDesign CS6 (Windows) Adobe PDF Library 10.0.1