
Безымянный-2
User manual NIBE F730
108106
User manual NIBE F730
1x230 V
Exhaust air heat pump
LEK
UHB EN 1803-2 431388
Quick guide
Navigation
Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce)
A detailed explanation of the button functions can be found on page 12.
How to scroll through menus and make different settings is described on page 17.
Set the indoor climate
INDOOR CLIMATE
HOT WATER
2X
HEAT PUMP
INFO
The mode for setting the indoor temperature is accessed by pressing the OK button twice, when in the start mode in the main menu. Read more about the settings on page 31.
Increase hot water volume
1X
2X
To temporarily increase the amount of hot water, first turn the control knob to mark menu 2 (water droplet) and then press the OK button twice. Read more about the settings on page 48.
In event of disturbances in comfort
If a disturbance in comfort of any type occurs there are some measures that can be taken before you need to contact your installer. See page 73 for instructions.
Table of Contents
1 Important information
4
Installation data
4
Safety information
5
Serial number
7
Country specific information
7
F730 An excellent choice
9
2 The heat pump the heart of the house
10
Heat pump function
11
Contact with F730
12
Maintenance of F730
22
3 F730 at your service
31
Set the indoor climate
31
Set the hot water capacity
48
Get information
53
Adjust the heat pump
57
4 Disturbances in comfort
72
Info-menu
72
Manage alarm
72
Troubleshooting
73
5 Technical data
76
6 Glossary
77
Item register
81
Table of Contents |
NIBE F730 3
1 Important information
Installation data
Product Serial number Installation date Installer
F730
No. Name
Fact. Set sett.
1.1 temperature (curve offset) 0
1.9.1 heating curve (curve
9
slope)
Accessories
Extra shunt ECS 40/41 Room unit RMU 40
1.9.3 min. flow line temp.
20
5.1.5 fan sp. exhaust air (nor- 75% mal)
5.3.17 fan speed outdoor air 100%
Installed electrical output Max
Serial number must always be given
Certification that the installation is carried out according to instructions in the accompanying installer manual and applicable regulations.
Date
__________________ Signed _________________________
4
Chapter 1 | Important information
NIBE F730
Safety information
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. Rights to make any design or technical modifications are reserved. ©NIBE 2017.
NOTE
F730 must be installed via an isolator switch with a minimum breaking gap of 3 mm.
NOTE
If the supply cable is damaged, only NIBE, its service representative or similar authorised person may replace it to prevent any danger and damage.
NOTE
Do not start the heat pump, if there is a risk that the water in the system has frozen.
Chapter 1 | Important information
NIBE F730 5
Symbols
NOTE
This symbol indicates danger to person or machine .
Caution
This symbol indicates important information about what you should observe when maintaining your installation.
TIP
This symbol indicates tips on how to facilitate using the product.
6
Chapter 1 | Important information
NIBE F730
Serial number
The serial number can be found at the bottom right of the front cover and in the info menu (menu 3.1).
Serial number
Caution
You need the product's (14 digit) serial number for servicing and support.
Country specific information
Great Britain
This installation is subject to building regulation approval, notify the local Authority of intention to install. Use only manufacturer's recommended replacement parts.
Nibe is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimise safety, efficiency and performance.
Benchmark is managed and promoted by the Heating and Hotwater Industry Council. For more information visit www.centralheating.co.uk
Warranty and insurance information
Thank you for installing a new NIBE heat pump in your home.
NIBE heat pumps are manufactured in Sweden to the very highest standard so we are pleased to offer our customers a comprehensive guarantee.
The product is guaranteed for 24 months for parts and labour from the date of installation or 33 months from the date of manufacture, whichever is the shorter.
Chapter 1 | Important information
NIBE F730 7
The NIBE guarantee is based on the unit being installed and commissioned by a NIBE accredited installer, serviced every year and the Benchmark documents completed. Where this condition is not met, any chargeable spare parts or components issued within the applicable guarantee period still benefit from a 12 month warranty from the date of issue by the manufacturer.
We recommend the installer completes and returns as soon as possible, your guarantee registration card or completes the guarantee form on the NIBE website www.nibe.co.uk.
Please ensure that the installer has fully completed the Benchmark Checklist in the end of the Installation Instructions supplied with the product and that you have signed to say that you have received a full and clear explanation of its operation. The installer is legally required to complete a commissioning checklist as a means of complying with the appropriate Building Regulations (England and Wales).
All installations must be notified to Local Area Building Control either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer who should, on receipt, write the Notification Number on the Benchmark Checklist.
This product should be serviced regularly to optimise its safety, efficiency and performance. The service engineer should complete the relevant Service Record on the Benchmark Checklist after each service.
The Benchmark Checklist may be required in the event of any warranty work and as supporting documentation relating to home improvements in the optional documents section of the Home Information Pack.
8
Chapter 1 | Important information
NIBE F730
F730 An excellent choice
F730 is part of a new generation of heat pumps, which have been introduced to supply your home with inexpensive and environmentally friendly heating. Heat production is safe and economical with integrated hot water heater, immersion heater, circulation pump and control system.
The heat pump can be connected to an optional low temperature heat distribution system. e.g. radiators, convectors or underfloor heating. It is also prepared for connection to several different accessories, for example climate systems with different temperatures.
F730 is equipped with a control computer for good comfort, good economy and safe operation. Clear information about status, operation time and all temperatures in the heat pump are shown on the large and easy to read display. This means, for example, that external unit thermometers are not necessary.
Excellent properties for F730:
Inverter controlled compressor
The heat pump has an inverter controlled compressor that automatically adapts itself optimally and economically to your house and supplies your installation with renewable energy.
Integrated water heater
There is a water heater integrated in the heat pump, which is insulated with environmentally friendly cellular plastic for minimal heat loss.
Scheduling the indoor comfort and hot water
Heating and hot water as well as ventilation, can be scheduled for each day of the week or for longer periods (vacation).
Display with user instructions
The heat pump has a large display with easy-to-understand menus that facilitate setting a comfortable climate.
Simple troubleshooting
In the event of a fault, the heat pump display shows what happened and the actions to be taken.
Chapter 1 | Important information
NIBE F730 9
2 The heat pump the heart of the house
A
1
22 °C
0 °C
B
C
2D
80 °C
5 °C
0 °C
Evaporator
Compressor
Expansion valve
F
Condenser E G
55 °C
45 °C
3 H
VRuemnstliulafttion air
RKöeldfrmigeedriuamnt HVäermateinbägramreedium OUtueltudfot or air
10
Chapter 2 | The heat pump the heart of the house
NIBE F730
Heat pump function
This exhaust air heat pump uses the heat that is in the building's ventilation air to heat up the accommodation. The conversion of the air's energy to heating occurs in three different circuits. Free heating energy is retrieved from the outgoing air (1) from the accommodation and transported to the heat pump. The heat pump increases the retrieved heat's low temperature to a high temperature in the refrigerant circuit, (2). The heat is distributed around the house in the heating medium circuit (3).
Ventilation air
A The hot air is transferred from the rooms to the heat pump via the house
ventilation system. Outdoor air is only used if necessary.
B The fan then routes the air to the heat pump's evaporator. Here, the air
releases the heating energy and the air's temperature drops significantly. The cold air is then blown out of the house. Refrigerant circuit
C A liquid, a refrigerant, circulates in a closed system in the heat pump which
also passes the evaporator. The refrigerant has a very low boiling point. In the evaporator the refrigerant receives the heat energy from the ventilation air and starts to boil.
D The gas that is produced during boiling is routed into an electrically
powered compressor. When the gas is compressed, the pressure increases and the gas's temperature increases considerably, from -5°C to approx. 100 °C.
E From the compressor, the gas is forced into a heat exchanger, condenser,
where it releases heat energy to the heat pump's heating section, whereupon the gas is cooled and condenses to liquid form again.
F As the pressure is still high, the refrigerant can pass an expansion valve,
where the pressure drops so that the refrigerant returns to its original temperature. The refrigerant has now completed a full cycle. It is routed to the evaporator again and the process is repeated. Heat medium circuit
G The heat energy that the refrigerant produces in the condenser is retrieved
by the climate system's water, heating medium, which is heated to 55 °C (supply temperature).
H The heating medium circulates in a closed system and transports the heated
water's heat energy to the heat pump's integrated hot water heater and the radiators/heating coils of the house.
I The heat pump's integrated water heater is in the heating section. The
heating medium heats the hot water.
The temperatures are only examples and may vary between different installations and time of year.
Chapter 2 | The heat pump the heart of the house
NIBE F730 11
Contact with F730
Display unit
INDOOR CLIMATE
HOT WATER
A Display B Status lamp
HEAT PUMP
INFO
C OK button
D Back button
E Control knob
F730
F Switch G USB port
There is a display unit on the front of the heat pump, which is used to communicate with F730.. Here you: switch on, switch off or set the heat pump in emergency mode.
sets the indoor climate and hot water as well as adjusts the heat pump to your needs.
receive information about settings, status and events.
see different types of alarms and receive instructions about how they are to be rectified.
A Display Instructions, settings and operational information are shown on the display. You can easily navigate between the different menus and options to set the comfort or obtain the information you require.
The temperatures are only examples and may vary between different installations and time of year.
12
Chapter 2 | The heat pump the heart of the house
NIBE F730
B
Status lamp
The status lamp indicates the status of the heat pump. It:
lights green during normal operation.
lights yellow in emergency mode.
lights red in the event of a deployed alarm.
C
OK button
The OK button is used to:
confirm selections of sub menus/options/set values/page in the start guide.
D Back button The back button is used to: go back to the previous menu. change a setting that has not been confirmed.
E
Control knob
The control knob can be turned to the right or left. You can:
scroll in menus and between options.
increase and decrease the values.
change page in multiple page instructions (for example help text
and service info).
F
Switch
The switch assumes three positions:
On ( )
Standby ( )
Emergency mode ( )
Emergency mode must only be used in the event of a fault on the heat pump. In this mode, the compressor switches off and the immersion heater engages. The heat pump display is not illuminated and the status lamp illuminates yellow.
Chapter 2 | The heat pump the heart of the house
NIBE F730 13
G USB port The USB port is hidden beneath the plastic badge with the product name on it.
The USB port is used to update the software.
Visit http://www.nibeuplink.com and click the "Software" tab to download the latest software for your installation.
14
Chapter 2 | The heat pump the heart of the house
NIBE F730
Menu system
Outdoor temperature
Indoor temperature - (if room sensors are installed)
INDOOR CLIMATE
HOT WATER Hot water temp.
HEAT PUMP
SERVICE
Temporary lux (if activated)
Information about operation
INFO
Estimated amount of hot water
Menu 1 Menu 2 Menu 3 Menu 4
INDOOR CLIMATE Setting and scheduling the indoor climate. See page 31.
HOT WATER Setting and scheduling hot water production. See page 48.
INFO Display of temperature and other operating information and access to the alarm log. See page 53.
HEAT PUMP Setting time, date, language, display, operating mode etc. See page 57.
Chapter 2 | The heat pump the heart of the house
NIBE F730 15
Symbols in the display The following symbols can appear in the display during operation.
Symbol Description This symbol appears by the information sign if there is information in menu 3.1 that you should note.
These two symbols indicate whether the compressor or addition is blocked in F730. These can, for example, be blocked depending on which operating mode is selected in menu 4.2, if blocking is scheduled in menu 4.9.5 or if an alarm has occurred that blocks one of them.
Blocking the compressor.
Blocking additional heat.
This symbol appears if periodic increase or lux mode for the hot water is activated.
This symbol indicates whether "holiday setting" is active in 4.7.
This symbol indicates whether F730 has contact with Uplink.
This symbol indicates the actual speed of the fan if the speed has changed from the normal setting.
16
Chapter 2 | The heat pump the heart of the house
NIBE F730
INDOOR CLIMATE
Menu number marked sub menu HOT WATER
Name and menu number main menu
INDOOR CLIMATE 1
Symbol main menu
HEAT PUMP Marked main menu
INFO Symbols sub menus
temperature ventilation scheduling advanced
normal off
Name sub menus
Status information sub menus
Operation
To move the cursor, turn the control knob to the left or the right. The marked position is white and/or has a turned up tab.
Selecting menu
To advance in the menu system select a main menu by marking it and then pressing the OK button. A new window then opens with sub menus. Select one of the sub menus by marking it and then pressing the OK button.
Chapter 2 | The heat pump the heart of the house
NIBE F730 17
Selecting options
economy normal luxury
comfort mode2.2
Alternative
In an options menu the current selected option is indicated by a green tick.
To select another option: 1. Mark the applicable option. One of the options is pre-selected
(white). 2. Press the OK button to confirm the selected option. The selected
option has a green tick.
18
Chapter 2 | The heat pump the heart of the house
NIBE F730
Setting a value
time
date
day month year
time & date4.4
24 h 12 h
Values to be changed
To set a value: 1. Mark the value you want to set using the control knob. 2. Press the OK button. The background of the value becomes
green, which means that you have accessed the setting mode. 3. Turn the control knob to the right to increase the value and to
the left to reduce the value. 4. Press the OK button to confirm the value you have set. To change
and return to the original value, press the Back button.
Chapter 2 | The heat pump the heart of the house
NIBE F730 19
Use the virtual keyboard
Different keyboards
In some menus where text may require entering, a virtual keyboard is available.
Depending on the menu, you can gain access to different character sets which you can select using the control knob. To change character table, press the Back button. If a menu only has one character set the keyboard is displayed directly.
When you have finished writing, mark "OK" and press the OK button.
20
Chapter 2 | The heat pump the heart of the house
NIBE F730
Scroll through the windows
A menu can consist of several windows. Turn the control knob to scroll between the windows.
Current menu window
Number of windows in the menu
Scroll through the windows in the start guide
language 4.6 Arrows to scroll through window in start guide
1. Turn the control knob until one of the arrows in the top left corner (at the page number) has been marked.
2. Press the OK button to skip between the steps in the start guide.
Help menu
In many menus there is a symbol that indicates that extra help is If theavstaairlat gbuleid. e is left on this page it closes
automatically in
To access the help text:
60 min
1. Use the control knob to select the help symbol. 2. Press the OK button.
The help text often consists of several windows that you can scroll between using the control knob.
Chapter 2 | The heat pump the heart of the house
NIBE F730 21
Maintenance of F730
F730 can be installed separately or as one unit. The images in this manual show F730 installed as one unit.
Regular checks
NOTE
Service and maintenance may only be carried out by competent and qualified personnel, such as NIBE service engineers or other qualified specialists.
Your heat pump requires minimal maintenance after commissioning. However, it is recommended that your installation is checked and serviced annually by qualified personnel. This is to ensure the continued efficient operation of your heat pump, and that the warranty remains valid during the warranty period. If something unusual occurs, messages about the malfunction appear in the display in the form of different alarm texts. See alarm management on page 72.
Service hatch
The vent valves etc. are behind the service hatch. Remove the hatch by pulling it towards you.
LLEEKK
22
Chapter 2 | The heat pump the heart of the house
NIBE F730
Cleaning the ventilation devices The building's ventilation devices should be cleaned regularly with, for example, a small brush to maintain the correct ventilation. The device settings must not be changed.
NOTE
If you take down more than one ventilation device for cleaning, do not mix them up.
Cleaning the air filter Clean the F730's air filter regularly, how often depends on the amount of dust in the ventilation air. Select what is most suitable for your heat pump. You will receive a reminder about filter cleaning in the display. The default setting for the reminder is every three months, however, if the power to F730 is interrupted the countdown begins again. 1. Switch off the heat pump. 2. Remove the upper front cover by pulling straight out. 3. Pull out the filter cassette. 4. Take out the filter and shake/vacuum off any dirt. Do not use water
or other liquids for cleaning. 5. Check the condition of the filter. 6. Carry out assembly in reverse order. Even if the filter appears clean, dirt collects in it and this affects the efficiency of the filter. Therefore, replace it after approx. 2 years. New filters can be ordered via the installer. Filter
LEK
Chapter 2 | The heat pump the heart of the house
NIBE F730 23
Check pressure F730 has a pressure gauge which shows the heating system pressure. The pressure should be between 0.5 and 1.5 bar, but varies during temperature changes. If the pressure drops to 0 or rises to 2.5 frequently, contact your installer for troubleshooting.
Pressure gauge
LEK
LEK
24
Chapter 2 | The heat pump the heart of the house
NIBE F730
Safety valves F730 has three safety valves, two for the water heater and one for the climate system. The water heater's safety valve sometimes releases a little water after hot water usage. This is because the cold water, which enters the water heater, expands when heated causing the pressure to rise and the safety valve to open. The climate system's safety valve must be completely closed and must not normally release any water.
NOTE
Do not remove or adjust any components that are part of this pressurised water heater. Contact your installer!
NOTE
If this pressurised water heater develops a fault, e.g. a flow of hot water from the overflow pipe, turn the heat pump off and contact your installer.
Cleaning the overflow cup Condensation forms when the heat pump is working. This condensation is led off and collected in an overflow cup. In addition to water, a certain amount of dust and particles also collect in the overflow cup.
Overflow cup
LEK
LEK
Regularly check that the overflow cup and any floor drains are not blocked; water must be able to run through freely. Clean, if necessary.
Chapter 2 | The heat pump the heart of the house
NIBE F730 25
Reset alarm "High condensation water level" If the overflow cup or the overflow section becomes blocked F730 displayes an alarm. In association with the alarm , the compressor in the heat pump switches off to prevent further condensation. The smaller overflow cup must be emptied for the alarm to be reset and the compressor restarted. Reset the alarm as follows: 1. Pull out the tab on the smaller overflow cup slightly.
LEK
2. Lift up the cup.
LEK
3. Drain the water. 4. Check and clean the larger overflow cup and/or the overflow cup
section. 5. Reinstall the smaller cup. 6. Select "reset alarm" in the display.
26
Chapter 2 | The heat pump the heart of the house
NIBE F730
Filling the climate system
If the pressure is too low, increase as follows: 1. Open the filler valves . The heating section and the rest of the climate
system are filled with water.
Filler valve 1
Venting valve
Pressure meter
LEK
LEK
Filler valve 2
Bleed valves
Venting the climate system
In event of repeated filling of the climate system or if bubbling sounds are heard from the heat pump the system may need venting. This is carried out as follows:
1. Turn off the power supply to the heat pump.
2. Vent the heat pump via the vent valves and the rest of the climate system via the relevant vent valves.
3. Keep topping up and venting until all air has been removed and the pressure is correct.
NOTE
The vent hoses from the container must be drained of water before air can be released. This means that the system is not necessarily vented despite the flow of water when the vent valves are opened.
Therefore hold the vent valves open at least 5 seconds.
Chapter 2 | The heat pump the heart of the house
NIBE F730 27
Saving tips
Your heat pump installation produces heat and hot water. This occurs via the control settings you made.
Factors that affect the energy consumption are, for example, indoor temperature, hot water consumption, the insulation level of the house and whether the house has many large window surfaces. The position of the house, e.g. wind exposure is also an affecting factor.
Even the house ventilation affects the energy consumption. It is therefore important to perform a ventilation adjustment shortly after installing the heat pump. When adjusting ventilation, a ventilation technician sets the house ventilation device, outdoor air damper and the fan in F730 according to the projected values of the house.
Also remember:
During the adjustment period (winter time) all thermostat valves should be fully open. The heat pump's heating settings are then adjusted so that the correct indoor temperature is obtained, in most rooms, regardless of the outdoor temperature. In rooms where a lower temperature is required, the thermostat valves are lowered to the desired level. After a few months, the remaining thermostats can be lowered slightly to avoid an increase of the room temperature due to solar radiation, stove heat etc. Further reductions may be required later on.
You can lower the temperature when away from the house by scheduling "holiday setting" in menu 4.7. See page 66 for instructions.
If you activate "Hot water Economy", less energy is used.
Power consumption
Increasing the indoor temperature one degree increases the energy consumption by approx. 5%.
Domestic electricity
In the past it has been calculated that an average Swedish household has an approximate annual consumption of 5000 kWh domestic electricity/year. In today's society it is usually between 6000-12000 kWh/year.
Equipment
Normal Output (W)
TV (Operation: 5 h/day, Standby: 19 h/day)
Operation 200
Standby 2
Appr. ann. consump (kWh)
380
28
Chapter 2 | The heat pump the heart of the house
NIBE F730
Equipment
Normal Output (W)
Digital box (Operation: 5 h/day, Standby:
11
10
19 h/day)
DVD (Operation: 2 h/week)
15
5
TV games console (Operation: 6 h/week) 160
2
Radio/stereo (Operation: 3 h/day)
40
1
Computer incl. screen (Operation: 3 h/day, 100
2
standby 21 h/day)
Bulb (Operation 8 h/day)
60
-
Spot light, Halogen (Operation 8 h/day)
20
-
Cooling (Operation: 24 h/day)
100
-
Freezer (Operation: 24 h/day)
120
-
Stove, hob (Operation: 40 min/day)
1500
-
Stove, oven (Operation: 2 h/week)
3000
-
Dishwasher, cold water connection (Opera- 2000
-
tion 1 time/day)
Washing machine (Operation: 1 times/day) 2000
-
Tumble drier (Operation: 1 times/day)
2000
-
Vacuum cleaner (Operation: 2 h/week)
1000
-
Engine block heater (Operation: 1 h/day, 4 400
-
months a year)
Passenger compartment heater (Operation: 800
-
1 h/day, 4 months a year)
Appr. ann. consump (kWh) 90
45 67 50 120
175 58 165 380 365 310 730
730 730 100 50
100
These values are approximate example values.
Example: A family with 2 children live in a house with 1 flat-screen TV, 1 digital box, 1 DVD player, 1 TV games console, 2 computers, 3 stereos, 2 bulbs in the WC, 2 bulbs in the bathroom, 4 bulbs in the kitchen, 3 bulbs outside, a washing machine, tumble drier, fridge, freezer, oven, vacuum cleaner, engine block heater = 6240 kWh domestic electricity/year
Energy meter
Check the accommodation's energy meter regularly, preferably once a month. This will indicate any changes in power consumption.
Newly built houses usually have twin energy meters, use the difference to calculate your domestic electricity.
Chapter 2 | The heat pump the heart of the house
NIBE F730 29
New builds
Newly built houses undergo a drying out process for a year. The house can then consume significantly more energy than it would thereafter. After 1-2 years the heating curve should be adjusted again, as well as the offset heating curve and the building's thermostat valves, because the heating system, as a rule, requires a lower temperature once the drying process is complete.
30
Chapter 2 | The heat pump the heart of the house
NIBE F730
3 F730 at your service
Menu 1.1
Set the indoor climate
Overview
Sub-menus
For the menu INDOOR CLIMATE there are several sub-menus. Status information for the relevant menu can be found on the display to the right of the menus.
temperature Setting the temperature for the climate system. The status information shows the set values for the climate system.
INDOOR CLIMATE 1
temperature ventilation scheduling advanced
normal off
ventilation Setting the fan speed. The status information shows the selected setting.
scheduling Scheduling heating and ventilation. Status information "set" is displayed if you set a schedule but it is not active now, "holiday setting" is displayed if the vacation schedule is active at the same time as the schedule (the vacation function is prioritised), "active" displays if any part of the schedule is active, otherwise it displays "off".
advanced Setting of heat curve, adjusting with external contact, minimum value for supply temperature, room sensor and night cooling.
temperature
Set the temperature (with room sensors installed and activated):
temperature heating1.1.1
heating Setting range: 5 30 °C Default value: 20
The value in the display appears as a temperature in °C if the climate system is controlled by a room sensor.
Chapter 3 | F730 at your service
NIBE F730 31
Caution
A slow heat-releasing heating system, such as for example, underfloor heating, may not be suitable for control using the heat pump's room sensor.
To change the room temperature, use the control knob to set the desired temperature in the display. Confirm the new setting by pressing the OK button. The new temperature is shown on the right-hand side of the symbol in the display.
Setting the temperature (without room sensors activated):
Setting range: -10 to +10 Default value: -1
The display shows the set values for heating (curve offset). To increase or reduce the indoor temperature, increase or reduce the value on the display. Use the control knob to set a new value. Confirm the new setting by pressing the OK button. The number of steps the value has to be changed to achieve a degree change of the indoor temperature depends on the heating installation. One step is usually enough but in some cases several steps may be required. Setting the desired value. The new value is shown on the right-hand side of the symbol in the display.
Caution
An increase in the room temperature can be slowed by the thermostats for the radiators or under floor heating. Therefore, open the thermostats fully, except in those rooms where a cooler temperature is required, e.g. bedrooms.
If the exhaust air temperature falls below 6 °C the compressor is blocked and electric additional heat is permitted. Heat is not recovered from the exhaust air when the compressor is blocked.
32
Chapter 3 | F730 at your service
NIBE F730
TIP
Wait 24 hours before making a new setting, so that the room temperature has time to stabilise.
If it is cold outdoors and the room temperature is too low, increase the curve slope in menu 1.9.1.1 by one increment.
If it is cold outdoors and the room temperature is too high, reduce the curve slope in menu 1.9.1.1 by one increment.
If it is warm outdoors and the room temperature is too low, increase the value in menu 1.1.1 by one increment.
If it is warm outdoors and the room temperature is too high, reduce the value in menu 1.1.1 by one increment.
Menu 1.2
ventilation
Setting range: normal and speed 1-4 Default value: normal
normal (50%) speed 1 (0%) speed 2 (40%) speed 3 (80%) speed 4 (100%)
ventilation1.2
The ventilation in the accommodation can be temporarily increased or reduced here. When you have selected a new speed a clock starts a count down. When the time has counted down the ventilation speed returns to the normal setting. If necessary, the different return times can be changed in menu 1.9.6. The fan speed is shown in brackets (in percent) after each speed alternative.
TIP
If longer time changes are required use the holiday function or scheduling.
Chapter 3 | F730 at your service
NIBE F730 33
Menu 1.3
scheduling
In the menu scheduling indoor climate (heating/ventilation) is scheduled for each weekday.
You can also schedule a longer period during a selected period (vacation) in menu 4.7.
scheduling 1.3
heating
off
ventilation
off
Menu 1.3.1
heating
Increases or decreases in the accommodation temperature can be scheduled here for up to three time periods per day. If a room sensor is installed and activated the desired room temperature (°C) is set during the time period. Without an activated room sensor the desired change is set (of setting in menu 1.1). One step is usually enough to change the room temperature by one degree, but in some cases several steps may be required.
Activated
Schedule
System
SCHEDULING HEATING 1.3.1 schedule 1 schedule 2 schedule 3
activated
system
all mon tues wed thur fri sat sun
21:30 - 06:00 20.5°
Day
Time period
Adjusting
Conflict
Schedule: The schedule to be changed is selected here.
Activated: Scheduling for the selected period is activated here. Set times are not affected at deactivation.
34
Chapter 3 | F730 at your service
NIBE F730
System: Which climate system the schedule is for is selected here. This alternative is only displayed if more than one climate system is present.
Chapter 3 | F730 at your service
NIBE F730 35
Day: Select which day or days of the week the schedule is to apply to here. To remove the scheduling for a particular day, the time for that day must be reset by setting the start time to the same as the stop time. If the line "all" is used, all days in the period are set for these times. Time period: The start and stop time for the selected day for scheduling are selected here. Adjusting: How much the heating curve is to be offset in relation to menu 1.1 during scheduling is set here. If the rooms sensor is installed the desired room temperature is set in °C. Conflict: If two settings conflict with each other a red exclamation mark is displayed.
TIP
If you wish to set similar scheduling for every day of the week start by filling in "all" and then changing the desired days.
TIP
Set the stop time earlier than the start time so that the period extends beyond midnight. Scheduling then stops at the set stop time the day after.
Scheduling always starts on the date that the start time is set for.
Caution
Changes of temperature in accommodation take time. For example, short time periods in combination with underfloor heating will not give a noticeable difference in room temperature.
If the exhaust air temperature falls below 6 °C the compressor is blocked and electric additional heat is permitted. When the compressor is blocked heat is not recovered from the exhaust air.
Menu 1.3.3
ventilation
Increases or decreases in the ventilation to the accommodation can be scheduled here for up to two time periods per day.
36
Chapter 3 | F730 at your service
NIBE F730
Activated
Schedule
SCHEDULING VENTILATION 1.3.3
schedule 1 schedule 2
activated
all mon tues wed thur fri sat sun
21:30 - 06:00
speed 3
Day
Time period
Adjusting
Conflict
Schedule: The schedule to be changed is selected here.
Activated: Scheduling for the selected period is activated here. Set times are not affected at deactivation.
Day: Select which day or days of the week the schedule is to apply to here. To remove the scheduling for a particular day, the time for that day must be reset by setting the start time to the same as the stop time. If the line "all" is used, all days in the period are set for these times.
Time period: The start and stop time for the selected day for scheduling are selected here.
Adjusting: The desired fan speed is set here.
Conflict: If two settings conflict with each other a red exclamation mark is displayed.
TIP
If you wish to set similar scheduling for every day of the week start by filling in "all" and then changing the desired days.
Chapter 3 | F730 at your service
NIBE F730 37
TIP Set the stop time earlier than the start time so that the period extends beyond midnight. Scheduling then stops at the set stop time the day after. Scheduling always starts on the date that the start time is set for.
Caution A significant change over a longer period of time may cause poor indoor environment and worse operating economy.
Menu 1.9
advanced
Menu advanced has orange text and is intended for the advanced user. This menu has several sub-menus.
heating curve Setting the heating curve slope.
advanced 1.9
heating curve external adjustment min. flow line temp.
external adjustment Setting the heat curve offset when the external contact is connected.
min. flow line temp. Setting minimum permitted flow line temperature.
room sensor settings fan return time own curve
room sensor settings Settings regarding the room sensor.
fan return time Fan return time settings in the event of temporary ventilation speed change.
own curve Setting own heat curve.
point offset Setting the offset of the heating curve at a specific outdoor temperature.
night cooling Setting night cooling.
38
Chapter 3 | F730 at your service
NIBE F730
Menu 1.9.1
heating curve
heating curve Setting range: 0 - 15 Default value: 5
system
heating curve 1.9.1.1
flow temperature °C
outdoor temp. °C
The prescribed heating curve for your house can be viewed in the menu heating curve . The task of the heating curve is to give an even indoor temperature, regardless of the outdoor temperature, and thereby energy efficient operation. It is from this heating curve that the heat pump's control computer determines the temperature of the water to the heating system, supply temperature, and therefore the indoor temperature. Select the heating curve and read off how the supply temperature changes at different outdoor temperatures here.
SFurapmplelydntienmgspteemrpaetruereatur (°C)
80
70
60
50
40
30
0
0
10
0
Steeper curve slope
-10
-20
-30
-40
Outdoor Utetemtepmeprearatuturre (°C)
Curve coefficient
The slope of the heating curve indicates how many degrees the supply temperature is to be increased/reduced when the outdoor temperature drops/increases. A steeper slope means a higher supply temperature at a certain outdoor temperature.
The optimum slope depends on the climate conditions in your location, if the house has radiators or under floor heating and how well insulated the house is.
The heating curve is set when the heating installation is installed, but may need adjusting later. Thereafter the heating curve should not need further adjustment.
Chapter 3 | F730 at your service
NIBE F730 39
Caution
In the event of making fine adjustments for the indoor temperature, the heat curve must be offset up or down instead, this is done in menu 1.1 temperature .
SFurapmplelydntienmgspteemrpaetruereatur (°C)
80
70
60
50
40
30
0
0
10
0
Offset heating curve
-10
-20
-30
-40
Outdoor Utetemtepmeprearatuturre (°C)
Curve offset
An offset of the heating curve means that the supply temperature changes by the same amount for all the outdoor temperatures, e.g. that a curve offset of +2 steps increases the supply temperature by 5 °C at all outdoor temperatures.
SFurapmplelydntienmgspteemrpaetruereatur (°C)
80
70 60 Maximum value
50
40
30
0
0
10
0
Minimum value
-10
-20
-30
-40
Outdoor Utetemtepmeprearatuturre (°C)
Flow line temperature maximum and minimum values
Because the flow line temperature cannot be calculated higher than the set maximum value or lower than the set minimum value the heating curve flattens out at these temperatures.
Caution
Underfloor heating systems are normally max flow line temperature set between 35 and 45 °C.
Check the max temperature for your floor with your installer/floor supplier.
The figure at the end of the curve indicates the curve slope. The figure beside the thermometer gives the curve offset. Use the control knob to set a new value. Confirm the new setting by pressing the OK button. Curve 0 is an own heating curve created in menu 1.9.7.
40
Chapter 3 | F730 at your service
NIBE F730
To select another heat curve (slope):
NOTE
If you only have one heating system, the number of the curve is already marked when the menu window opens.
1. Select the system (if more than one) for which the heat curve is to be changed.
2. When the system selection has been confirmed the heat curve number is marked.
3. Press the OK button to access the setting mode 4. Select a new heating curve. The heating curves are numbered from 0
to 15, the greater the number, the steeper the slope and the greater the supply temperature. Heating curve 0 means that own curve (menu 1.9.7) is used. 5. Press the OK button to exit the setting.
To read off a heating curve: 1. Turn the control knob so that the ring on the shaft with the outdoor
temperature is marked. 2. Press the OK button. 3. Follow the grey line up to the heat curve and out to the left to read
off the value for the supply temperature at the selected outdoor temperature. 4. You can now select to take read outs for different outdoor temperatures by turning the control knob to the right or left and read off the corresponding flow temperature. 5. Press the OK or Back button to exit read off mode.
Chapter 3 | F730 at your service
NIBE F730 41
TIP
Wait 24 hours before making a new setting, so that the room temperature has time to stabilise.
If it is cold outdoors and the room temperature is too low, increase the curve slope by one increment.
If it is cold outdoors and the room temperature is too high, lower the curve slope by one increment.
If it is warm outdoors and the room temperature is too low, increase the curve offset by one increment.
If it is warm outdoors and the room temperature is too high, lower the curve offset by one increment.
Menu 1.9.2
external adjustment
climate system
Setting range: -10 to +10.
Or desired room temperature if the room sensor is installed. See illustration.
Default value: 0
external adjustment1.9.2
climate system 1
°C
climate system 2
climate system 3
°C
climate system 4
Connecting an external contact, for example, a room thermostat or a timer allows you to temporarily or periodically raise or lower the room temperature while heating. When the contact is on, the heating curve offset is changed by the number of steps selected in the menu. If a room sensor is installed and activated the desired room temperature (°C) is set.
If there is more than one climate system the setting can be made separately for each system.
42
Chapter 3 | F730 at your service
NIBE F730
Menu 1.9.3
min. flow line temp.
heating Setting range: 20-70 °C Default value: 20 °C
min. flow line temp.1.9.3
climate system 1 climate system 2 climate system 3 climate system 4
20 °C 20 °C 20 °C 20 °C
Set the minimum temperature on the supply temperature to the climate system. This means that F730 never calculates a temperature lower than that set here. If there is more than one climate system the setting can be made separately for each system.
TIP
The value can be increased if you have, for example, a cellar that you always want to heat, even in summer.
You may also need to increase the value in "stop heating" menu 4.9.2 "auto mode setting".
Chapter 3 | F730 at your service
NIBE F730 43
Menu 1.9.4
room sensor settings
factor system Setting range: 0.0 - 6.0 Default value: 2.0
room sensor settings 1.9.4
control room sensor syst 1 factor system 1 control room sensor syst 2 control room sensor syst 3 factor system 3 control room sensor syst 4
Room sensors to control the room temperature can be activated here.
Caution
A slow heat-releasing heating system, such as for example, underfloor heating, may not be suitable for control using the heat pump's room sensor.
Here you can set a factor (a numerical value) that determines how much an over or sub normal temperature (the difference between the desired and actual room temperature) in the room is to affect the supply temperature to the climate system. A higher value gives a greater and faster change of the heating curve's set offset.
NOTE
Too high a set value for "factor system" can (depending on your climate system) produce an unstable room temperature.
If several climate systems are installed the above settings can be made for the relevant systems.
44
Chapter 3 | F730 at your service
NIBE F730
Menu 1.9.6
fan return time
speed 1-4 Setting range: 1 99 h Default value: 4 h
speed 1 speed 2 speed 3 speed 4
fan return time1.9.6
hrs hrs hrs hrs
Menu 1.9.7
Here you select the return time for temporary speed change (speed 1-4) on the ventilation in menu 1.2. Return time is the time it takes before ventilation speed returns to normal.
own curve
supply temperature Setting range: 0 80 °C
own curve 1.9.7
flow line temp. at -30 °C
°C
flow line temp. at -20 °C
°C
flow line temp. at -10 °C
°C
flow line temp. at 0 °C
°C
flow line temp. at 10 °C
°C
flow line temp. at 20 °C
°C
You can create your own heating curve here, if there are special requirements, by setting the desired supply temperatures for different outdoor temperatures.
Caution
Curve 0 in menu 1.9.1 must be selected for own curve to apply.
Chapter 3 | F730 at your service
NIBE F730 45
Menu 1.9.8
point offset
outdoor temp. point Setting range: -40 30 °C Default value: 0 °C
change in curve Setting range: -10 10 °C Default value: 0 °C
point offset 1.9.8
outdoor temp. point
°C
change in curve
°C
flow temperature °C
outdoor temp. °C
Select a change in the heating curve at a certain outdoor temperature here. One step is usually enough to change the room temperature by one degree, but in some cases several steps may be required. The heat curve is affected at ± 5 °C from set outdoor temp. point. It is important that the correct heating curve is selected so that the room temperature is experienced as even.
TIP
If it is cold in the house, at, for example -2 °C, "outdoor temp. point" is set to "-2" and "change in curve" is increased until the desired room temperature is maintained.
Caution
Wait 24 hours before making a new setting, so that the room temperature has time to stabilise.
46
Chapter 3 | F730 at your service
NIBE F730
Menu 1.9.9
night cooling
start temp. exhaust air Setting range: 20 30 °C Default value: 25 °C
min diff. outdoor-exhaust Setting range: 3 10 °C Default value: 6 °C
night cooling1.9.9
night cooling
start temp. exhaust air
°C
min diff. outdoor-exhaust
°C
Activate night cooling here.
When the temperature in the house is high and the outdoor temperature is lower, a cooling effect can be obtained by forcing the ventilation.
If the temperature difference between the exhaust air and the outdoor air temperature is greater than the set value ("min diff. outdoor-exhaust") and the exhaust air temperature is higher than the set value ("start temp. exhaust air") run the ventilation at speed 4 until one of the conditions is no longer met.
Caution
Night cooling can only be activated when house heating has been deactivated. This is done in menu 4.2.
Chapter 3 | F730 at your service
NIBE F730 47
Menu 2.1
Set the hot water capacity
Overview
Sub-menus
For the menu HOT WATER there are several sub-menus. Status information for the relevant menu can be found on the display to the right of the menus.
temporary lux Activation of temporary increase in the hot water temperature. Status information displays "off" or what length of time of the temporary temperature increase remains.
HOT WATER 2
temporary lux comfort mode scheduling advanced
off economy
active
comfort mode Setting hot water comfort. The status information displays what mode is selected, "economy", "normal" or "luxury".
scheduling Scheduling hot water comfort. The status information "set" appears if you have set scheduling but it is not currently active, "holiday setting" appears if holiday setting is active at the same time as scheduling (when the holiday function is prioritised), "active" appears if any part of scheduling is active, otherwise "off" appears.
advanced Setting periodic increase in the hot water temperature.
temporary lux
Setting range: 3, 6 and 12 hours and mode "off" and "one time increase"
Default value: "off"
off one time increase 3 hrs
6 hrs
12 hrs
temporary lux2.1
When hot water requirement has temporarily increased this menu can be used to select an increase in the hot water temperature to lux mode for a selectable time.
48
Chapter 3 | F730 at your service
NIBE F730
Menu 2.2
Caution
If comfort mode "luxury" is selected in menu 2.2 no further increase can be carried out.
The function is activated immediately when a time period is selected and confirmed using the OK button. The remaining time for the selected setting is shown to the right. When the time has run out F730 returns to the mode set in menu 2.2. Select "off" to switch off temporary lux .
comfort mode
Setting range: economy, normal, luxury
Default value: normal
economy normal luxury
comfort mode2.2
The difference between the selectable modes is the temperature of the hot tap water. Higher temperature means that the hot water lasts longer.
economy: This mode gives less hot water than the others, but is more economical. This mode can be used in smaller households with a small hot water requirement.
normal: Normal mode gives a larger amount of hot water and is suitable for most households.
luxury: Lux mode gives the greatest possible amount of hot water. In this mode, the immersion heater, as well as the compressor, is used to heat hot water, which may increase operating costs.
Chapter 3 | F730 at your service
NIBE F730 49
Menu 2.3
scheduling
What hot water comfort the heat
Activated
Schedule
pump is to work with can be scheduled
SCHEDULING HOT WATER
here for up to two different time periods per day.
Scheduling is activated/deactivated by ticking/unticking"activated". Set times are not affected at deactivation.
schedule 1 schedule 2
activated
all mon tues
normal
Schedule: The schedule to be changed
wed thur
is selected here.
fri
Activated: Scheduling for the selected
sat sun
period is activated here. Set times are
not affected at deactivation.
Day
Time period
Adjusting
2.3
Conflict
Day: Select which day or days of the week the schedule is to apply to here. To remove the scheduling for a particular day, the time for that day must be reset by setting the start time to the same as the stop time. If the line "all" is used, all days in the period are set for these times.
Time period: The start and stop time for the selected day for scheduling are selected here.
Adjusting: Set the hot water comfort that is to apply during scheduling here.
Conflict: If two settings conflict with each other a red exclamation mark is displayed.
TIP
If you wish to set similar scheduling for every day of the week start by filling in "all" and then changing the desired days.
TIP
Set the stop time earlier than the start time so that the period extends beyond midnight. Scheduling then stops at the set stop time the day after.
Scheduling always starts on the date that the start time is set for.
50
Chapter 3 | F730 at your service
NIBE F730
Menu 2.9
advanced
Menu advanced has orange text and is intended for the advanced user. This menu has several sub-menus.
advanced 2.9
periodic increase hot water recirc.
Menu 2.9.1
periodic increase
period Setting range: 1 - 90 days Default value: 14 days
start time Setting range: 00:00 - 23:00 Default value: 00:00
periodic increase 2.9.1
activated period start time
Next periodic increase
days
To prevent bacterial growth in the water heater, the compressor and the immersion heater can increase the hot water temperature for a short time at regular intervals.
The length of time between increases can be selected here. The time can be set between 1 and 90 days. Factory setting is 14 days. Tick/untick "activated" to start/switch off the function.
Chapter 3 | F730 at your service
NIBE F730 51
Menu 2.9.2
hot water recirc.
operating time Setting range: 1 - 60 min Default value: 60 min
downtime Setting range: 0 - 60 min Default value: 0 min
hot water recirc. 2.9.2
operating time
min
downtime
min
period 1 period 2 period 3
Set the hot water circulation for up to three periods per day here. During the set periods the hot water circulation pump will run according to the settings above.
"operating time" decide how long the hot water circulation pump must run per operating instance.
"downtime" decide how long the hot water circulation pump must be stationary between operating instances.
52
Chapter 3 | F730 at your service
NIBE F730
Menu 3.1
Get information
Overview
Sub-menus
For the menu INFO there are several sub-menus. No settings can be made in these menus, they just display information. Status information for the relevant menu can be found on the display to the right of the menus.
service info shows temperature levels and settings in the installation.
compressor info shows operating times, number of starts etc for the compressor in the heat pump.
service info compressor info add. heat info alarm log indoor temp. log
INFO 3
runs off
add. heat info displays information about the additional heat's operating times etc.
alarm log displays the latest alarm and information about the heat pump when the alarm occurred.
indoor temp. log the average temperature indoors week by week during the past year.
service info
Information about the heat pump's actual operating status (e.g. current temperatures etc.) can be obtained here. No changes can be made.
The information is on several pages. Turn the control knob to scroll between the pages.
Symbols in this menu:
Compressor
Heating
Addition
Hot water
Circulation pump, climate system
Ventilation
Chapter 3 | F730 at your service
NIBE F730 53
Menu 3.2
compressor info
Information about the compressor's operating status and statistics can be obtained here. No changes can be made.
The information is on several pages. Turn the control knob to scroll between the pages.
status: number of starts: total operating time: - of which hot water: time factor: - of which hot water:
compressor info 3.2
initiating hrs hrs
Menu 3.3
add. heat info
Information about the additional heat's settings, operating status and statistics can be obtained here. No changes can be made.
The information is on several pages. Turn the control knob to scroll between the pages.
status: time factor:
add. heat info3.3 off
54
Chapter 3 | F730 at your service
NIBE F730
Menu 3.4
alarm log
To facilitate fault-finding the heat pump operating status at alarm alerts is stored here. You can see information for the 10 most recent alarms.
To view the run status in the event of an alarm, mark the alarm and press the OK button.
alarm log 3.4
TB alarm LP alarm Sensor flt:BT6 Sens flt:BT20 Sensor flt:BT2 Sensor flt:BT1
Temperature limiter alarm(52)
outdoor temp. heat medium flow heat medium return hot water charging condenser out operating time op. mode
alarm log 3.4
-5.6 °C 30.5 °C 25.0 °C 49.0 °C
6.2 °C 30 min
off
Information about an alarm.
Chapter 3 | F730 at your service
NIBE F730 55
Menu 3.5
indoor temp. log
Here you can see the average temperature indoors week by week during the past year. The dotted line indicates the annual average temperature.
The average outdoor temperature is only shown if a room temperature sensor/room unit is installed. Otherwise, the exhaust air temperature is shown.
exhaust air °C
indoor temp. log3.5
week
To read off an average
temperature 1. Turn the control knob so that the ring on the shaft with the week
number is marked.
2. Press the OK button.
3. Follow the grey line up to the graph and out to the left to read off the average indoor temperature at the selected week.
4. You can now select to take read outs for different weeks by turning the control knob to the right or left and read off the average temperature.
5. Press the OK or Back button to exit read off mode.
56
Chapter 3 | F730 at your service
NIBE F730
Menu 4.1
Adjust the heat pump
Overview
Sub-menus
For the menu HEAT PUMP there are several sub-menus. Status information for the relevant menu can be found on the display to the right of the menus.
plus functions Settings applying to any installed extra functions in the heating system.
HEAT PUMP 4
plus functions op. mode my icons time & date language / language
auto svenska
op. mode Activation of manual or
holiday setting
off
automatic operating mode. The status
information shows the selected oper-
ating mode.
my icons Settings regarding which icons in the heat pump's user interface that are to appear in the slot when the door is closed.
time & date Setting current time and date.
language Select the language for the display here. The status information shows the selected language.
holiday setting Vacation scheduling heating, hot water and ventilation. Status information "set" is displayed if you set a vacation schedule but it is not active at the moment, "active" is displayed if any part of the vacation schedule is active, otherwise it displays " off".
advanced Setting heat pump work mode.
plus functions
Settings for any additional functions installed in F730 can be made in the sub menus.
plus functions4.1
internet sms
Chapter 3 | F730 at your service
NIBE F730 57
Menu 4.1.3
internet
Here you make settings for connecting F730 to the internet.
NOTE
For these functions to work the network cable must be connected.
internet4.1.3
nibe uplink tcp/ip settings proxy settings
Menu 4.1.3.1
Uplink
Here you can manage the installation's connection to Uplink (http://www.nibeuplink.com) and see the number of users connected to the installation via the internet.
A connected user has a user account in Uplink , which has been given permission to control and/or monitor your installation.
nibe uplink 4.1.3.1
serial number connection string number of users
request new connection string switch off all users
Request new connection string
To connect a user account on Uplink to your installation, you must request a unique connection code.
1. Mark "request new connection string" and press the OK button. 2. The installation now communicates with Uplink to create a connection
code.
3. When a connection string has been received, it is shown in this menu at "connection string" and is valid for 60 minutes.
Disconnect all users 1. Mark "switch off all users" and press the OK button.
2. The installation now communicates with Uplink to release your installation from all users connected via the internet.
NOTE
After disconnecting all users none of them can monitor or control your installation via Uplink without requesting a new connection string.
58
Chapter 3 | F730 at your service
NIBE F730
Menu 4.1.3.8
tcp/ip settings
You can set TCP/IP settings for your installation here.
tcp/ip settings4.1.3.8
Automatic setting (DHCP)
1. Tick "automatic". The installation now receives the TCP/IP settings using DHCP.
automatic
ip-address net mask gateway dns
2. Mark "confirm" and press the OK button.
confirm
reset
Manual setting 1. Untick "automatic", you now have access to several setting options.
2. Mark "ip-address" and press the OK button.
3. Enter the correct details via the virtual keypad.
4. Mark "OK" and press the OK button.
5. Repeat 1 - 3 for "net mask", "gateway" and "dns".
6. Mark "confirm" and press the OK button.
Caution
The installation cannot connect to the internet without the correct TCP/IP settings. If unsure about applicable settings use the automatic mode or contact your network administrator (or similar) for further information.
TIP
All settings made since opening the menu can be reset by marking "reset" and pressing the OK button.
Menu 4.1.3.9
proxy settings
You can set proxy settings for your installation here.
Proxy settings are used to give connection information to a intermediate server (proxy server) between the installation and Internet. These settings are primarily used when the installation connects to the Internet via a company network. The installation supports proxy authentication of the HTTP Basic and HTTP Digest type.
use proxy server port user name password
confirm
proxy settings 4.1.3.9 reset
Chapter 3 | F730 at your service
NIBE F730 59
If unsure about applicable settings, contact your network administrator (or similar) for further information.
Setting 1. Tick "use proxy" if you do not want to use a proxy. 2. Mark "server" and press the OK button. 3. Enter the correct details via the virtual keypad. 4. Mark "OK" and press the OK button. 5. Repeat 1 - 3 for "port", "user name" and "password". 6. Mark "confirm" and press the OK button.
TIP
All settings made since opening the menu can be reset by marking "reset" and pressing the OK button.
Menu 4.1.4
sms (accessory is required)
Make settings for the accessory SMS 40 here.
Add the mobile numbers that are to have access to change and receive status information from the heat pump. Mobile numbers must include country code e.g. +46 XXXXXXXX.
If you want to receive an SMS message in the event of the alarm mark the box to the right of the telephone number.
phone number
sms 4.1.4 alarm receiver
NOTE Telephone numbers provided must be able to receive SMS messages.
60
Chapter 3 | F730 at your service
NIBE F730
Menu 4.1.5
SG Ready
This function can only be used in mains networks that support the "SG Ready"-standard .
SG Ready 4.1.5
Make settings for the function "SG Ready" here.
affect room temperature
affect room temperature
affect hot water
Here you set whether room temperature should be affected when activating "SG Ready".
With low price mode on "SG Ready" the parallel offset for the indoor temperature is increased by "+1". If a room sensor is installed and activated, the desired room temperature is instead increased by 1 °C.
With over capacity mode on "SG Ready" the parallel offset for the indoor temperature is increased by "+2". If a room sensor is installed and activated, the desired room temperature is instead increased by 2 °C.
affect hot water
Here you set whether the temperature of the hot water should be affected when activating "SG Ready".
With low price mode on "SG Ready" the stop temperature of the hot water is set as high as possible at only compressor operation (immersion heater not permitted).
With over capacity mode of "SG Ready" the hot water is set to "luxury" (immersion heater permitted).
NOTE The function must be connected and activated in your F730.
Chapter 3 | F730 at your service
NIBE F730 61
Menu 4.1.6
Smart price adaptionTM
area
In this menu you state where the heat pump is located and how great a role the electricity price should play. The greater the value, the greater the effect the electricity price has and the possible savings are larger, but at the same time there is an increased risk of affecting comfort.
smart price adaption 4.1.6
activated price of electricity overview area affect room temperature affect hot water
price of electricity overview
Here you can obtain information on how the electricity price varies over up to three days.
affect room temperature Setting range: 1 - 10 Factory setting: 5
affect hot water Setting range: 1 - 4 Factory setting: 2
Smart price adaptionTM moves the heat pump's consumption over 24 hours to periods with the cheapest electricity tariff, which gives savings for hourly rate based electricity contracts. The function is based on hourly rates for the next 24 hours being retrieved via Uplink and therefore an internet connection and an account for Uplink are required.
Deselect "activated" to switch off Smart price adaptionTM.
62
Chapter 3 | F730 at your service
NIBE F730
Menu 4.1.7
smart home (accessory is required)
When you have a smart home system that can speak to Uplink, by activating the smart home function in this menu you can control the F730 via an app.
By allowing connected units to communicate with Uplink, your heating system becomes a natural part of your homesmart home and gives you the opportunity to optimise the operation.
smart home control system. 1
Caution
The smart home function requires Uplink in order to work.
smart home 4.1.7
Chapter 3 | F730 at your service
NIBE F730 63
Menu 4.1.10
solar electricity
affect room temperature Setting range: on/off Factory setting: off
affect hot water Setting range: on/off Factory setting: off
SOLAR ELECTRICITY 4.1.10
affect room temperature affect hot water
Menu 4.2
This is where you set which part of your climate system (room temperature, hot water temperature) is to be affected by EME 20 or EME 10. F730 switches automatically between differpeownetr operating modes, depeAnding on how much electricity the solar panels are producing. A sun icon appears in the main menu when electricity production is active, and when the solar panels are producing more electricity than F730 requires, the climate system is affected in line with the selected settings.
op. mode
op. mode Setting range: auto, manual, add. heat only Default value: auto
functions Setting range: compressor, addition, heating
auto manual add. heat only
op. mode 4.2
The heat pump operating mode is usually set to "auto". It is also possible to set the heat pump to "add. heat only", but only when an addition is used, or "manual" and select yourself what functions are to be permitted.
Change the operating mode by marking the desired mode and pressing the OK button. When an operating mode is selected, it shows what is permitted in the heat pump (crossed out = not permitted) and selectable alternatives to the right. To select selectable functions that are permitted or not, mark the function using the control knob and press the OK button.
64
Chapter 3 | F730 at your service
NIBE F730
Operating mode auto In this operating mode the heat pump automatically selects what functions are permitted.
Operating mode manual In this operating mode you can select what functions are permitted. You cannot deselect "compressor" in manual mode.
Operating mode add. heat only In this operating mode the compressor is not active, only additional heat is used.
Caution
If you choose mode "add. heat only" the compressor is deselected and there is a higher operating cost.
Functions "compressor" is that which produces heating and hot water for the accommodation. If "compressor" is deselected, a symbol in the main menu on the heat pump symbol is displayed. You cannot deselect "compressor" in manual mode. "addition" is what helps the compressor to heat the accommodation and/or the hot water when it cannot manage the whole requirement alone. "heating" means that you get heat in the accommodation. You can deselect the function when you do not wish to have heating running.
Caution
If you deselect "addition" it may mean that insufficient hot water and/or heating in the accommodation is achieved.
Menu 4.3
my icons
You can select what icons should be visible when the door to F730 is closed. You can select up to 3 icons. If you select more, the ones you selected first will disappear. The icons are displayed in the order you selected them.
my icons 4.3 outdoor/indoor temperature hot water temperature analog clock digital clock
Chapter 3 | F730 at your service
NIBE F730 65
Menu 4.4
time & date
Set time and date, display mode and time zone here.
TIP
Time and date are set automatically if the heat pump is connected to Uplink. To obtain the correct time, the time zone must be set.
time
date
day month year
time & date4.4
24 h 12 h
Menu 4.6
language
Choose the language that you want the information to be displayed in here.
language 4.6
Menu 4.7
holiday setting
To reduce energy consumption during a holiday you can schedule a reduction in heating, ventilation and hot water temperature.
If a room sensor is installed and activated, the desired room temperature (°C) is set during the time period. This setting applies to all climate systems with room sensors.
activated
start date stop date heating hot water comfort ventilation
holiday setting4.7
0 economy
normal
If a room sensor is not activated, the desired offset of the heating curve is set. One step is usually enough to change the room temperature by one degree, but in some cases several steps may be required. This setting applies to all climate systems without room sensors.
Vacation scheduling starts at 00:00 on the start date and stops at 23:59 on the stop date.
66
Chapter 3 | F730 at your service
NIBE F730
TIP Complete holiday setting about a day before your return so that room temperature and hot water have time to regain usual levels.
TIP Set the vacation setting in advance and activate just before departure in order to maintain the comfort.
Caution If you choose to switch off hot water production during the vacation "periodic increase" (preventing bacterial growth) are blocked during this time. "periodic increase" started in conjunction with the vacation setting being completed.
Caution If the exhaust air temperature falls below 6 °C, the compressor is blocked and electric additional heat is permitted. Heat is not recovered from the exhaust air when the compressor is blocked.
Caution In installations with water heaters without an immersion heater connected to F730"hot water comfort" should not be set to "off" when holiday setting is activated.
Menu 4.9
advanced
Menu advanced has orange text and is intended for the advanced user. This menu has several sub-menus.
advanced 4.9
op. prioritisation
auto mode setting
degree minute setting
factory setting user
schedule blocking
off
Chapter 3 | F730 at your service
NIBE F730 67
Menu 4.9.1
op. prioritisation
op. prioritisation Setting range: 0 to 180 min Default value: 30 min
op. prioritisation 4.9.1
hot water
min
heating
min
Menu 4.9.2
Choose here how long the heat pump should work with each requirement if there are two requirements at the same time. If there is only one requirement the heat pump only works with that requirement.
The indicator marks where in the cycle the heat pump is.
If 0 minutes is selected it means that requirement is not prioritised, but will only be activated when there is no other requirement.
auto mode setting
stop heating Setting range: -20 40 °C Default values: 17
stop additional heat Setting range: -25 40 °C Factory setting: 10
filtering time Setting range: 0 48 h Default value: 24 h
auto mode setting4.9.2
stop heating
°C
stop additional heat
°C
filtering time
hrs
When the operating mode is set to "auto", the heat pump selects when start and stop of additional heat and heat production is permitted, dependent on the average outdoor temperature.
Select the average outdoor temperatures in this menu.
68
Chapter 3 | F730 at your service
NIBE F730
Menu 4.9.3
Caution It cannot be set "stop additional heat" higher than "stop heating".
You can also set the time over which (filtering time) the average temperature is calculated. If you select 0, the present outdoor temperature is used.
degree minute setting
current value Setting range: -3000 3000
start compressor Setting range: -1000 -30 Default value: -60
start diff additional heat Setting range: 100 2000 Factory setting: 700
diff. between additional steps Setting range: 0 1000 Factory setting: 50
degree minute setting4.9.3
current value
DM
start compressor
DM
start diff additional heat
DM
diff. between additional steps
DM
Degree minutes are a measurement of the current heating requirement in the house and determine when the compressor respectively additional heat will start/stop.
Caution
Higher value on "start compressor" gives more compressor starts, which increase wear on the compressor. Too low value can give uneven indoor temperatures.
Chapter 3 | F730 at your service
NIBE F730 69
Menu 4.9.4
factory setting user
All settings that are available to the user (including advanced menus) can be reset to default values here.
Caution
After factory setting, personal settings such as heating curves, ventilation etc must be reset.
factory setting user 4.9.4
Do you want to reset all user settings to factory settings?
no
yes
Menu 4.9.5
schedule blocking
The compressor can be scheduled to be blocked for up to two different time periods here.
Activated
Schedule
schedule blocking 4.9.5
schedule 1 schedule 2
When scheduling is active the actual blocking symbol in the main menu on the heat pump symbol is displayed.
Schedule: The period to be changed is selected here.
Activated: Scheduling for the selected period is activated here. Set times are not affected at deactivation.
activated
all mon tues wed thur fri sat sun
Day: Select which day or days of the Day
Time period
Blocking
Conflict
week the schedule is to apply to here.
To remove the scheduling for a particular day, the time for that day must
be reset by setting the start time to the same as the stop time. If the line
"all" is used, all days in the period are set for these times.
Time period: The start and stop time for the selected day for scheduling are selected here.
Blocking: The desired blocking is selected here.
Conflict: If two settings conflict with each other a red exclamation mark is displayed.
Blocking the compressor.
Blocking additional heat.
70
Chapter 3 | F730 at your service
NIBE F730
TIP If you wish to set similar scheduling for every day of the week start by filling in "all" and then changing the desired days.
TIP Set the stop time earlier than the start time so that the period extends beyond midnight. Scheduling then stops at the set stop time the day after. Scheduling always starts on the date that the start time is set for.
Caution Long term blocking can cause reduced comfort and operating economy.
Chapter 3 | F730 at your service
NIBE F730 71
4 Disturbances in comfort
In most cases, the heat pump notes operational interference (operational interference can lead to disturbance in comfort) and indicates this with alarms and shows action instructions in the display.
Info-menu
All the heat pump measurement values are gathered under menu 3.1 in the heat pump menu system. Looking through the values in this menu can often simplify finding the fault source. See page 53 for more information about menu 3.1.
Manage alarm
In the event of an alarm, some kind of malfunction has occurred, which is indicated by the status lamp changing from green continuously to red continuously. In addition, an alarm bell appears in the information window.
Alarm
Low pressure alarm alarm
info / action reset alarm
In the event of an alarm with a red
aid mode
status lamp a malfunction has oc-
curred that the heat pump cannot
remedy itself. In the display, by turning the control knob and pressing the
OK button, you can see the type of alarm it is and reset it. You can also
choose to set the heat pump to aid mode.
info / action Here you can read what the alarm means and receive tips on what you can do to correct the problem that caused the alarm.
reset alarm In many cases, it is sufficient to select "reset alarm" in order for the product to revert to normal operation. If a green light comes on after selecting "reset alarm", the alarm has been remedied. If a red light is still visible and a menu called "alarm" is visible in the display, the problem that caused the alarm remains. If the alarm disappears and then returns, contact your installer.
aid mode "aid mode" is a type of emergency mode. This means that the heat pump produces heat and/or hot water despite there being some kind of problem. This can mean that the heat pump's compressor is not running. In this case the immersion heater produces heat and/or hot water.
72
Chapter 4 | Disturbances in comfort
NIBE F730
Caution
Selecting "aid mode" is not the same as correcting the problem that caused the alarm. The status lamp will therefore continue to be red.
If the alarm does not reset, contact your installer for suitable remedial action.
NOTE
Always state the product's serial number (14 digits) when reporting a fault.
Troubleshooting
If the operational interference is not shown in the display the following tips can be used:
Basic actions
Start by checking the following possible fault sources: The switch's position.
Group and main fuses of the accommodation.
Earth-fault breaker.
Low hot water temperature or a lack of hot water
Closed or throttled externally mounted filler valve for the water heater. Open the valve.
Heat pump in incorrect operating mode. Enter menu 4.2. If mode "auto" is selected, select a higher value on "stop additional heat" in menu 4.9.2. If mode "manual" is selected, select "addition".
Large hot water consumption. Wait until the hot water has heated up. Temporarily increased hot water capacity (temporary lux) can be activated in menu 2.1.
Too low hot water setting. Enter menu 2.2 and select a higher comfort mode.
Too low or no operating prioritisation of hot water. Enter menu 4.9.1 and increase the time for when hot water is to be prioritised. Note that if the time for hot water is increased, the time for heating production is reduced, which can give lower/uneven room temperatures.
Filter blocked.
Chapter 4 | Disturbances in comfort
NIBE F730 73
Clean or replace filter (see page 23).
Low room temperature
Closed thermostats in several rooms. See section "Saving tips" on page 28 and menu 1.1 on page 31 for more detailed information about how to best set the thermostats.
Heat pump in incorrect operating mode. Enter menu 4.2. If mode "auto" is selected, select a higher value on "stop heating" in menu 4.9.2. If mode "manual" is selected, select "heating". If this is not enough, select "addition".
Too low set value on the automatic heating control. Enter menu 1.1 "temperature" and adjust the offset heating curve up. If the room temperature is only low in cold weather the curve slope in menu 1.9.1 "heating curve" needs adjusting up.
Too low or no operating prioritisation of heat. Enter menu 4.9.1 and increase the time for when heating is to be prioritised. Note that if the time for heating is increased the time for hot water production is reduced, which can give smaller amounts of hot water.
"comfort mode" "luxury" selected in combination with large hot water outlet. Enter menu 2.2 and select "economy" or "normal".
"Holiday mode" activated in menu 4.7. Enter menu 4.7 and select "Off".
External switch for changing the room heating activated. Check any external switches.
Air in the heating system. Vent the heating system.
Filter blocked. Clean or replace filter (see page 23).
High room temperature
Too high set value on the automatic heating control. Enter menu 1.1 (temperature) and reduce the offset heating curve. If the room temperature is only high in cold weather the curve slope in menu 1.9.1 "heating curve" needs adjusting down.
External switch for changing the room heating activated. Check any external switches.
74
Chapter 4 | Disturbances in comfort
NIBE F730
Low system pressure
Not enough water in the heating system. Top up the water in the heating system.
Low or a lack of ventilation
Filter blocked. Clean or replace filter (see page 23).
The ventilation is not adjusted. Order ventilation adjustment.
Exhaust air device blocked or throttled down too much. Check and clean the exhaust air devices (see page 23).
Fan speed in reduced mode. Enter menu 1.2 and select "normal".
External switch for changing the fan speed activated. Check any external switches.
High or distracting ventilation
Filter blocked. Clean or replace filter (see page 23).
The ventilation is not adjusted. Order ventilation adjustment.
Fan speed in forced mode. Enter menu 1.2 and select "normal".
External switch for changing the fan speed activated. Check any external switches.
The compressor does not start
There is no heating requirement. The heat pump does not call on heating nor hot water. The heat pump defrosts.
Compressor blocked due to the temperature conditions. Wait until the temperature is within the product's working range.
Minimum time between compressor starts has not been reached. Wait 30 minutes and then check if the compressor has started.
Alarm tripped. Follow the display instructions.
Chapter 4 | Disturbances in comfort
NIBE F730 75
5 Technical data
Detailed technical specifications for this product can be found in the installation manual (nibe.eu).
76
Chapter 5 | Technical data
NIBE F730
6 Glossary
Additional heat
The additional heat is the heat produced in addition to the heat supplied by the compressor in your heat pump. Additional heaters can be for example, immersion heater, electric heater, gas/oil/pellet/wood burner or district heating.
Calculated flow line temperature
The temperature that the heat pump calculates that the heating system requires for an optimum accommodation temperature. The colder the outdoor temperature, the higher the calculated supply temperature.
Circulation pump
Pump that circulates liquid in a pipe system.
Climate system
Climate systems can also be called heating systems. The building is heated using radiators, under floor coils or convector fans.
Compressor
Compresses the gas state refrigerant. When the refrigerant is compressed, the pressure and the temperature increase.
Condenser
Heat exchanger where the hot gas state refrigerant condenses (cooled and becomes a liquid) and releases heat energy to the house heating and hot water systems.
Disturbances in comfort
Disturbances in comfort are undesirable changes to the hot water/indoor comfort, for example when the temperature of the hot water is too low or if the indoor temperature is not at the desired level. A malfunction in the heat pump can sometimes be noticed in the form of a disturbance in comfort. In most cases, the heat pump notes operational interference and indicates this with alarms and shows instructions in the display.
Domestic hot water
The water one showers in for example.
Chapter 6 | Glossary
NIBE F730 77
Electrical addition
This is the electricity that, for example, an immersion heater produces when the compressor's output is not sufficient to fulfil the property's heating demand.
Emergency mode
A mode that can be selected using the switch in the event of a fault, which means that the compressor stops. When the heat pump is in emergency mode, the building is heated using an immersion heater. Hot water is not produced.
Evaporator
Heat exchanger where the refrigerant evaporates by retrieving heat energy from the air which then cools.
Exhaust air
The air that comes from the exhaust air device in the various rooms of the accommodation, to F730.
Exhaust air devices
Vents, usually in the ceiling, in the kitchen/bathroom/clothes closet where the air is drawn in to be forwarded to F730.
Expansion valve
Valve that reduces the pressure of the refrigerant, whereupon the temperature of the refrigerant drops.
Expansion vessel
Vessel with fluid with the task of equalising the pressure in the system.
Extract air
The air that the heat pump has retrieved heat from and which has therefore been cooled. This air is blown out of the building.
Filtering time
Indicates the time the average outdoor temperature is calculated on.
Flow pipe
The line in which the heated water is transported from the heat pump out to the house heating system (radiators/heating coils).
78
Chapter 6 | Glossary
NIBE F730
Heat exchanger
Device that transfers heat energy from one medium to another without mixing mediums. Examples of different heat exchangers are evaporators and condensers.
Heat factor
Measurement of how much heat energy the heat pump gives off in relation to the electric energy it needs to operate. Another term for this is COP.
Heating curve
The heating curve determines which heat the heat pump is to produce depending on the temperature outdoors. If a high value is selected, this tells the heat pump that it must produce a lot of heat when it is cold outdoors in order to achieve a warm indoor temperature.
Heating medium
Hot liquid, usually normal water, which is sent from the heat pump to the house climate system and makes the accommodation warm. The heating medium also heats the hot water.
Heating medium side
Pipes to the house's climate system make up the heating medium side.
Outdoor air
Outdoor air routed into the heat pump.
Outdoor air damper
Intake for outdoor air.
Outside sensor
A sensor that is located outdoors. This sensor tells the heat pump how hot it is outdoors.
Pressostat
Pressure switch that triggers an alarm and/or stops the compressor if nonpermitted pressures occur in the system. A high pressure pressostat trips if the condensing pressure is too great. A low pressure pressostat trips if the evaporation pressure is too low.
Radiator
Another word for heating element. They must be filled with water in order to be used with F730.
Chapter 6 | Glossary
NIBE F730 79
Refrigerant
Substance that circulates around a closed circuit in the heat pump and that, through pressure changes, evaporates and condenses. During evaporation, the refrigerant absorbs heating energy and when condensing gives off heating energy.
Return pipe
The line in which the water is transported back to the heat pump from the house heating system (radiators/heating coils).
Return temp
The temperature of the water that returns to the heat pump after releasing the heat energy to the radiators/heating coils.
Room sensor
A sensor that is located indoors. This sensor tells the heat pump how hot it is indoors.
Safety valve
A valve that opens and releases a small amount of liquid if the pressure is too high.
Supply temperature
The temperature of the heated water that the heat pump sends out to the heating system. The colder the outdoor temperature, the higher the supply line temperature becomes.
Water heater
Container where domestic water is heated. Is located inside the heat pump, but an extra hot water heater can be installed in the event of large hot water requirements.
80
Chapter 6 | Glossary
NIBE F730
7 Item register
A Adjust the heat pump, 57 Alarm, 72
B Back button, 13
C Contact with F730, 12
Display unit, 12 Menu system, 15 Control knob, 13
D Display, 12 Display unit, 12
Back button, 13 Control knob, 13 Display, 12 OK button, 13 Status lamp, 13 Switch, 13 Disturbances in comfort, 72 Alarm, 72 Manage alarm, 72 Troubleshooting, 73
F F730 An excellent choice, 9 F730 at your service, 31
Adjust the heat pump, 57 Get information, 53 Set the hot water capacity, 48 Set the indoor climate, 31
G Get information, 53 Glossary, 77
H Heat pump function, 11 Help menu, 21
I Important information
F730 An excellent choice, 9 Installation data, 4 Serial number, 7 Warranty information, 7
Chapter 7 | Item register
Installation data, 4
M Maintenance of F730, 22
Regular checks, 22 Saving tips, 28 Manage alarm, 72 Menu system, 15 Help menu, 21 Operation, 17 Scroll through the windows, 21 Selecting menu, 17 Selecting options, 18 Setting a value, 19 Use the virtual keyboard, 20
O OK button, 13 Operation, 17
P Power consumption, 28
R Regular checks, 22
S Saving tips, 28
Power consumption, 28 Scroll through the windows, 21 Selecting menu, 17 Selecting options, 18 Serial number, 7 Set the hot water capacity, 48 Set the indoor climate, 31 Setting a value, 19 Status lamp, 13 Switch, 13
T Technical data, 76 The heat pump the heart of the house, 10 Troubleshooting, 73
U Use the virtual keyboard, 20
W Warranty information, 7
NIBE F730 81
WS name: Anna WS version: a2 (working edition) Publish date: 2018-01-15 12:46
NIBE Energy Systems Ltd 3C Broom Business Park Bridge Way Chesterfield S41 9QG Phone 0845 095 1200 Fax 0845 095 1201 info @ nibe.co.uk w w w.nib e.co.uk
431388
pdftk 2.02 - www tk.com itext-paulo-155 (itextpdf.sf.net-lowagie.com)