Important Safety Instruction
Secure the Magnetic lock body firmly to the door frame. Our electromagnetic lock is shock resistant to unlimited door closures, so it is vital to check if the electromagnetic lock is secure firmly on the top door header to prevent it from falling and causing possible injury.
Do not tighten the armature plate tight against the door.
The armature plate must remained movable to allow surface alignment with the magnet face. The Magnetic Lock will lose holding force without this floating alignment.
Do not trim the rubber washer mounted on the head of the armature center bolt. Trimming this rubber will adversely effect the operation of magnetic lock.

Settings and Wiring : EM5700 DSS PCBA

EM5700D DSS RIGHT SIDE PCBA

1234

1234

12 VDC 24 VDC

1234

1234

12 VDC 24 VDC

GB R
+
+ 12 24 12

-
C NC NO
MAG JP1

HR

RBG LED1

+ 12/ 24 V DC - 12/ 24 V DC C NC
NO
LED wiring: RED BLACK GREEN

GB R

LIGHT PANEL

HR wiring:

GREEN BLACK
RED

DSS wiring: BLACK - COM

Rated:24VDC RED - NC

0.2A max.

GREEN- NO

Figure 1

NC NO
C - 12/ 24 V DC
+ 12/ 24 V DC
LED wiring: GREEN BLACK RED

NC NO
C-
JP1 MAG

12 24 12

RBG

LED1

HR

DSS wiring: BLACK - COM Rated:24VDC RED - NC 0.2A max. GREEN- NO
Figure 2

RED BLACK GREEN

HR wiring:

V 1.0 2016

EM5700 DSS / EM5700D DSS INSTALLATION
ANOTHER QUALITY PRODUCT

Wiring Instructions For wiring installation, refer to Figure 1 and Figure 2.
The EM5700 DSS is a monitored single magnetic lock and the EM5700D DSS is a monitored double magnetic lock with 12 or 24 volt settings. Each magnetic lock has a broader light emitting diode display panel for better eye sight, The unit requires a filtered and regulated DC Power Source of correct voltage. The DC output of the power supply must NOT be connected to earth ground, but isolated to prevent shock and possible damage to the unit.
12VDC or 24VDC Power Wiring:
Remove the wiring cavity cover plate and select for the correct 12 VDC or 24 VDC wire jumper plug to be used.
These voltage shunts must be set before 12VDC or 24VDC is applied to the Electro-Magnetic Lock to prevent damage to the unit.

The (+) lead of the Power Source is connected to the RED wire and the (-) lead is connected to the BLACK wire. The operating switch or controlling contacts must be installed from the power source across the Magnetic Lock to reduce operating time of the Magnetic Lock to a minimum.

Power Input Requirements:

Power Input 12 VDC 24 VDC

EM5700 DSS 0.53 A 0.26 A

EM5700D DSS 2 × 0.53 A 2 × 0.26 A

Electro-Magnetic Lock Description:
The EM5700 DSS / EM5700D DSS magnetic lock runs on 12 or 24 V DC settings, with a built-iin Hall IC Crystal to indicate lock status (normally open or normally closed) and a Door Status Sensor (normally open) to indicate door status. With a Light panel on the magnet housing and a dry SPDT output which changes state when lock is secure. The Relay output C is short to the relay output NO when the lock is secure and C is short to NC when the lock is not secure.

Light Panel Indicators:

System Status
Power Off Power On-Door open Power On-Door close

Green light
OFF OFF ON

Red light
OFF ON OFF

Relay
De-Energized De-Energized
Energized

The Relay Contacts are rated at 24 volts at 2.0 Amps maximum. The Relay contact outputs are marked on the Printed Circuit Board.

Trouble Shooting

PROBLEM Door will not lock
Reduced holding force
Delay in door release
Light Panel status is incorrect

POSSIBLE CAUSE No DC voltage to lock
Loose wire Wrong wiring Bad physical contact between armature plate and face of magnet
Low voltage or wrong voltage setting Circuit switch is not between magnetic lock and power source Secondary diode installed across magnetic lock
Misalignment of armature plate Hall Effect Switch located in wrong position into magnetic block

SOLUTION Check power and wiring
Check for correct voltage Check wirings connection Ensure mating surfaces are clean and in proper alignment and the armature plate floats freely Check magnetic lock for low voltage or wrong voltage setting Re wire circuit switch between magnetic lock and power source
Remove this diode, voltage spike protection is on PCB.
Check alignment of armature plate Reposition Hall Effect switch, contact manufacturer for instruction

