APC Back-UPS RS 500 User Guide

Installation, Troubleshooting

EALFSON, APC-MGE, Home and Business Networks

APC Back-UPS RS 500 User Guide

PDF preview unavailable. Download the PDF instead.

files?p File Name=ABRE-7QEJYZ R0 EN &p Doc Ref=SPD ABRE-7QEJYZ EN&p enDocType=User guide
Back-UPS® RS 500
BR500CI-RS User Guide

1Connect Equipment Battery Backup Surge Protection

Place the Back-UPS to avoid:
­ Direct sunlight ­ Excessive heat ­ Excessive humidity or contact with fluids

These outlets are powered whenever the Back-UPS is switched ON. During a power outage, or other utility problems (brownouts, over-voltages), these outlets will be powered for a limited time by the Back-UPS. Plug the computer and monitor into these two outlets.
Connect AC Power Cord

ON/OFF and LED Status Indicator

Plug the Back-UPS power cord into a wall outlet, not a surge protector or power strip. The outlet should be near the equipment and easily accessible.

Battery backup and surge protected outlets

bu054a

2 Connect the Battery and Turn the Unit ON Connect the battery to the UPS before use. To connect the battery:
 Pull the top of the battery connector lever out of the unit, until the lever is horizontal.  Push the battery connector lever completely into the unit, until the end of the lever is flush with the rear panel. Press ON/OFF to turn on the unit. A single short beep, and the green "Power On" indicator confirms that the Back-UPS is on and ready to provide protection. The Back-UPS should charge for at least 10 hours to ensure sufficient runtime. The unit is being charged whenever it is connected to utility power, whether the unit is turned ON or OFF.

bu053a

3 Adjusting Transfer Voltage and Sensitivity Settings

Status Indicators
The Back-UPS indicates its operating status using a combination of visual and audible indicators.

Power On LED

Buzzer

Condition

Automatic Voltage Regulation boosts the utility voltage when it drops below safe levels. This allows the equipment plugged into the unit to operate during low voltage conditions, conserving the battery power in the event of a power outage.
The Back-UPS will switch to battery power if the input voltage level becomes too low for the Automatic Voltage Regulation to compensate, or if the utility power is distorted.
If the Back-UPS switches to battery power too frequently or too infrequently, adjust the transfer voltage and sensitivity settings:
1. Ensure the Back-UPS is off. Plug it into utility power.
2. Press and hold ON/OFF until the LED repeatedly flashes. The unit is now in Program Mode.
3. Release the button. The LED will flash once, twice, or three times per second, indicating the current setting. See Transfer Voltage and Sensitivity Settings.
4. Press ON/OFF within two seconds to change the setting. Each time the button is pressed, the LED will flash at a different rate: once, twice, or three times per second, indicating the new setting. Continue pressing the button until the desired setting is reached. If the button is not pressed within five seconds, the Back-UPS will exit the Program Mode.
5.To exit Program Mode, release the button and wait for the LED to stop flashing.

On On (Off during 4 beeps) Flashing Flashing Off
Off
On
Flashing
Off

Off

On-line - Back-UPS is supplying conditioned utility power

to the connected equipment

4 beeps repeated On-Battery - Back-UPS is supplying battery power every 30 seconds

Rapid Beeping

Low Battery Warning - The Back-UPS has 1.5 minutes of

(every 1/2 second) remaining battery power

Constant tone

Bad Battery Detected - Battery needs to be charged, or is at end of life. (See Battery Replacement.)

Short beep every 4 seconds

Low Battery Shutdown - During On Battery operation the battery power was almost completely exhausted, and the Back-UPS is waiting for utility power to return to normal

Constant Tone

On Battery Overload - Connected equipment requires more power than provided by the Back-UPS battery. Unplug devices one at a time to remove overload, if not corrected Contact APC Technical Support

Constant Tone

On Line Overload - The power drawn by the connected equipment exceeds the power capacity of the Battery Backup

Chirp every 2 seconds

Charger Warning -Back-UPS has experienced an internal problem, but continues to power the load. Contact APC Technical Support

Constant Tone

Charger Fault - Back-UPS has an internal problem, and is no longer powering the load. Contact APC Technical Support

Transfer Voltage and Sensitivity Settings

LED Flashing

Transfer Voltage Setting

Input Voltage Range
(For Utility Operation)

Once per second

Low

155 - 280

Twice per second Three times per second

Medium (factory default)
High

160 -280 165 - 270

Usage
The Back-UPS will switch to battery power less often. Use with equipment that is not sensitive to low or high level voltage levels or minor voltage waveform distortions. Default, use in normal conditions.
The Back-UPS will switch to battery power during any small fluctuation in voltage. Use with equipment that is sensitive to low or high level voltage levels or minor voltage waveform distortions.

990-3333B-006 © 2009 American Power Conversion Corp.

APC, Back-UPS and PowerChute are registered trademarks of American Power Conversion Corp. All other trademarks are property of their respective owners.

Troubleshooting

Problem Back-UPS will not turn on.

Probable Cause Circuit Breaker has tripped.

Connected equipment loses power.

Utility power is not available at the wall outlet.
The Back-UPS is overloaded.

The Back-UPS has exhausted its available battery power.

The equipment connected to the Back-UPS does not accept the step-approximated sine waveform from the unit.

The Back-UPS may require service.

The ON/OFF button is lit, and the unit is beeping four times every 30 seconds, or it is emitting a constant tone.

The unit is using battery.

The On/Off button flashes once per second, and the Back-UPS beeps once per second at the same time.

Battery capacity is low (there is about 2 minutes of use remaining).

Inadequate runtime.

The battery is not fully charged.

The battery is near the end of useful life.

Solution
Reduce the amount of equipment plugged into the "Battery Backup + Surge Protection" outlets. Reset the circuit breaker by pushing it back in. Ensure the fuse or circuit breaker for the wall outlet is okay, and the wall switch controlling the wall outlet (if any) is in the ON position. Ensure the equipment plugged into the outlets of the unit are not overloading the capacity of the unit. Try disconnecting some of the equipment one device at a time, and see if the problem continues. The unit can only operate on battery power for a limited amount of time. The unit will eventually turn off when the available battery power has been used. Allow the unit to recharge for 10 hours before continuing to use the unit. The output waveform is designed for computers and computer-related equipment. It is not designed for use with motor-type equipment.
Contact APC Technical Support for further troubleshooting. The unit is operating normally and using battery power. Save any current work, turn off all equipment, and turn the unit OFF. Once normal power is restored, turn the unit back ON, and turn on all equipment.
The unit is about to shut down due to a low battery charge condition! When the unit beeps once every second, the battery has about 2 minutes of power remaining. Immediately power down your computer, and turn the unit OFF. When power returns to normal, the unit will recharge the battery. Allow the unit to charge by leaving it plugged in, and switched on for 10 hours. As a battery ages, the amount of runtime available will decrease. Batteries also age prematurely if the unit is placed near excessive heat. If the battery will not charge, the Back-UPS is no longer operable.

Specifications

Input
Output
Protection and Filter Battery
Physical

Voltage

230 Vac nominal

Frequency

45-65 Hz

Brownout Transfer

160 ±8% VAC, typical

Over-voltage Transfer 280 VAC, typical

UPS Capacity (total)

500 VA / 300 W

Voltage On Battery

230 Vac rms (step-approximated sine wave)

Frequency - On Battery 50 Hz ±1 Hz, 60 Hz ±1 Hz

Transfer Time

50 Hz: 6ms typical, 10ms maximum 60 Hz: 5ms typical, 8ms maximum

AC Surge Protection

Full time, 273 joules

AC Input

Re-settable circuit breaker

Type

Maintenance free

Average Life

2 - 5 years depending on the number of discharge cycles and environmental temperature

Typical Recharge Time 10 Hours

Net Weight

5.1 kg

Dimensions (H x W x D) Operating Temperature Storage Temperature

18.55 cm (H) x 11.5 cm (W) x 21.3 cm (D) 0 oC to 40 oC (32 oF to 104 oF) -15 oC to 45 oC (5 oF to 113 oF)

Operating Relative Humidity

0 to 95% non-condensing

Operating Elevation

0 to 3000 m (0 to 10,000 ft)

Battery Replacement
The battery in the Back-UPS 500 is not user-replaceable. Contact APC Sales and Technical Support for a list of authorized service centers near you.
Warranty
The standard warranty is 2 years from the date of purchase. The APC standard procedure is to replace the original unit with a factory reconditioned unit. APC will ship the replacement unit once the defective unit is received by the repair department or cross-ship upon the provision of a valid credit card number. The customer pays for shipping to APC, and APC pays ground freight transportation costs back to the customer. Customers who must have the original unit back due to assigned asset tags and set depreciation schedules must declare such a need at first contact with APC Technical Support.

Service
Please DO NOT RETURN Back-UPS to the place of purchase under any circumstances. 1. Consult the Troubleshooting section to eliminate common problems. 2. If you still have problems or questions, please contact APC via the internet or at one of the phone numbers listed below. 3. Before contacting APC, please be sure to record the date purchased, UPS model, and serial number (on bottom of unit). 4. Be prepared to troubleshoot the problem over the telephone with a Technical Support Representative. If this is not successful, the representative will issue a Return Material Authorization Number (RMA#) and a shipping address. 5. Pack the unit in its original packaging. If the original packaging is not available, ask APC Technical Support about obtaining a new set. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty (insuring the package for full value is recommended). 6. Write the RMA# on the outside of the package. 7. Return the unit by insured carrier to the address given to you by APC Technical Support.

APC Worldwide Customer Support

Technical Support

http://www.apc.com/support

Internet

http://www.apc.com

Worldwide

+1 800 555 2725

Russian Federation Kenya South Africa Nigeria Middle East

(8)(800) 200 2722 +254 735 555502 0861272877 and +27 11 465 2583 00234 8065094820 and 00234 181 6129 +97145094790 and +97145094791

Back-UPS® RS 500
  BR500CI-RS

1      

 Back-UPS, :
­     ­      ­     

 

        Back-UPS.          ( , )            Back-UPS.        .

 ./.  

    

   Back-UPS   ,           .           .

bu054a

       

2          .   :            ,       .        ,        .
    ON/OFF (./.).
    Back-UPS         ,     «Power On» ( .).
     Back-UPS        10 .
         ,    .

bu053a

3     

           .   ,   ,      ,        .
      ,        ,     , Back-UPS     .
 Back-UPS          ,       :
1. ,  Back-UPS .    .
2.     ON/OFF (./.),      .      .
3.  .      ,      ,   . .      .
4.      ON/ OFF (./.)      .           : ,      ,   .    ,      .         , Back-UPS    .
5.     ,    ,     .

 

 Back-UPS            .

  



.

.

. (.  4  ) 


4     30 
   ( 1/2 )
  

.

    4 

.

  

.  .

  
  2 
  


  -- Back-UPS      
   -- Back-UPS    
     --  1,5     Back-UPS
   --       -     (.  .)
  -   --      «  »     ,  Back-UPS          
     --     ,    Back-UPS.      .    ,      APC
    -- ,   ,    
   --  Back-UPS   ,    .      APC
   --  Back-UPS   ,   .      APC

     

  

  

  
(   )



    

155­280

    

160­280

(  )

    

165­270

Back-UPS        .   ,             .
     .
Back-UPS           .   ,            .

990-3333B-006 © 2009 American Power Conversion Corp.

APC, Back-UPS  PowerChute      American Power Conversion Corp.        .

   



 



Back-UPS  .

  .

     «  +    ».    ,    .

   ,       

 .

,    ( ),   , .

   Back-UPS . .

,  ,    ,     .    ,    ,  ,   .

Back-UPS    .

         .      ,  .        10 .

  Back-UPS

        

  

.        

- .

  

.

 Back-UPS 

        

 .   APC.

 ON/OFF (./.)   .        .  

     30 

,      .   

   

  ,     .

  .

 «On/Off» (./.)

  

        ( 

      Back-UPS

2 ).

   

    .

   -    !        ,  ,       2  .      .    ,   .

  .    .   ,      10 .

    .

         .  ,    ,       .    ,  Back-UPS    .

 





230   , 



45­65 

   

160 ±8 %   , 

   280   , 



  ()

500 /300 

   « » 230    ( ) (-   )

   « »

50  ±1 , 60  ±1 

 

50 : 6  -- , 10  --  60 : 5  -- , 8  -- 

       , 273 



      

 

  

  

2­5           

  

10 

     ( x  x )
   

5,1 
18,55  () x 11,5  () x 21,3  ()  0 oC  40 oC ( 32 oF  104 oF)  -15 oC  45 oC ( 5 oF  113 oF)

    0­95 %   

       0  3000  ( 0  10000 ) 

 
 Back-UPS 500      .         APC       .

   2    .   APC      ,   .  APC     ,                .      APC,            . ,              ,            APC.


       Back-UPS   .
1.        «   ».
2.     - ,     APC        ,  .
3.     APC ,    ,      (   ).
4.              .    ,        ( RMA)   .
5.     .      ,          .         .     . ,    ,      (,     ).
6.          .
7.      ,      APC.

   APC

    

http://www.apc.com/support http://www.apc.com +1 800 555 2725

  (8)(800) 200 2722



+254 735 555502



0861272877  +27 11 465 2583



00234 8065094820  00234 181 6129

 

+97145094790  +97145094791


Acrobat Distiller 7.0.5 (Windows)