HGR41EW Series Three Phase easywire® Multifunction DIN Rail Energy Meter (MID Certified)

Brand: Hager

Product Description

The HGR41EW series is part of the easywire® family of meters, designed to save up to 90% installation time compared to standard meter and current transformer installations. This MID approved DIN rail mounted multifunction energy meter is suitable for monitoring energy consumption and other electrical parameters in industrial and commercial applications. It is certified for billing purposes and features a high-efficiency white backlit LCD display for clear indication of measured values in all light conditions. Push-buttons on the front allow user access to the required display pages.

The meter is available in two versions:

  • With single pulse output and RS485 Modbus communication
  • With single pulse output and Mbus communication

The unit is housed in a compact four-module width housing suitable for DIN rail mounting.

Displayed Parameters

ParameterDescription
Voltage - L-L, L-N and averageVoltage measurements
Current - per phase and averageCurrent measurements
Power Factor - per phase and averagePower factor measurements
FrequencySystem frequency
Power - Active, Reactive and Apparent (per phase and total)Power consumption breakdown
Power Max. demand - Active and apparent powerPeak power demand
Energy - Active, reactive and apparent (total)Total energy consumption

Technical Specifications

Display

Display TypeLCD, high definition with white back-light
Digit height6.35mm (displayed parameter)
Page scrollingManual by front key / or auto scroll mode

Displayed Parameters and Accuracies

ParameterAccuracy
Voltage0.5% of full scale
Current0.5% of full scale
Frequency0.1% of full scale (L-N >20V)
Power factor1% of unity
Active power1%
Reactive power1%
Apparent power1%
Active EnergyClass 1, Class B (IEC/EN62053-21, IEC/EN50470)
Reactive EnergyClass 2 (IEC/EN62053-23)
Energy maximum display9999999
Resolution0.01K, 0.1K, 1K, 0.01M, 0.1M (depending on CT ratio & VT ratio)

Programming

Parameters can be changed using the programming menu. Note: Once Programming Mode is entered, values in red will be locked out after 15 minutes. No further adjustment is possible without returning to the factory.

Programmable Parameters:

  • CT Primary current
  • VT primary voltage
  • VT secondary voltage
  • Communication address
  • Communication speed (Baud)
  • Communication Parity
  • Communication number of stop bits
  • Back-light time-out period
  • Demand period (for integration)
  • Pulse duration
  • Pulse output (kWh)
  • Reset to Factory Default
  • Reset Energy and Maximum Demand
  • Reset Active Energy
  • Reset Reactive Energy
  • Reset Apparent Energy
  • Reset Maximum Current
  • Reset Maximum Active Power
  • Reset Minimum Active Power
  • Reset Maximum Reactive Power
  • Reset Minimum Reactive Power
  • Reset Maximum Apparent Power

Programming access: Password protected (user selectable)

Memory retention: Non volatile memory

Input Specifications

ConnectionThree phase four wire
Input voltage range3 x 100...240V (L - N), 3 x 173...415V (L - L)
Voltage Rated Burden<8VA
Nominal current inputeasywire® - 1A (330mV)
Max current (Imax)easywire® - 1.2A (396mV)
Current Rated BurdenN/A - easywire® input
Starting current2mA (0.66mV)
Short time overcurrent30 x Imax to IEC/EN62053-21 + 23
Impulse voltage withstand6kV 1.2/50µS 0.5J
AC voltage withstand4kV 50Hz for 1 min
CT primary current5...6000A
VT primary voltage100...600V
Frequency50Hz
Current distortion factorAccording to IEC/EN50470

Auxiliary Supply

Voltage rangeSelf supplied from measuring input
Operating frequencySee input section
Power consumptionSee input section

Outputs

Energy pulses

Number of pulse outputs1
Pulse output functionkWh
Pulse output type1
Pulse output Max. current100mA
Pulse output voltage range5...27VDC
Pulse duration100ms...2s
Pulse resolution0.01K, 0.1K, 1K, 0.01M, 0.1M (depending on CT ratio & VT ratio)

Communication - Modbus Version

Communication typeRS485
Communication protocolModbus
Address1...255
Number of bits8bits
ParityNone, odd, even
Baud rate300, 600, 1200, 2400, 4800, 9600, 19200
Required response time to request<100ms
Number of meters connected on the bus32 (up to 255 with RS485 repeater)
Max distance from Master device500M

Insulation

Installation categoryIII
Pollution degree2
Insulation voltage rating300V (L-N)

Environmental Conditions

Reference temperature23°C ±2°C
Specified temperature operating range-10°C...+55°C
Storage temperature-20°C...+75°C
Relative humidity0...85%, non condensing
Mechanical environmentM1
Electromagnetic environmentE2

Mechanical

Housing4 module DIN 43880
MountingSnap-on 35mm rail
Tamper sealingMeter housing (by means of a tamper evident seal). Sealable terminal covers.
Housing materialSelf-extinguishing polycarbonate (UL94 V-0)
Protection degree (IEC/EN60529)IP20 (terminals), IP54 (front of housing)
Weight<210g

Termination

Current input terminal typeRJ45
Max. wire sizeN/A
Voltage input terminal typePluggable terminal block - Screw clamp type
Max. wire size2.5mm²
Voltage output terminal typePluggable terminal block - Screw clamp type
Max. wire size2.5mm²
Communication output (RS485 and Pulse)Pluggable terminal block - Screw clamp type
Max. wire size1.5mm²

Conformity

Electromagnetic compatibilityIEC/EN61326-1, IEC/EN55011 Class A, IEC/EN61000-4-2, -3, -4, -5, -6, -8, -11
Accuracy and functionalityIEC/EN50470-1/3
SafetyIEC/EN50470-1/3, IEC/EN62053-21, IEC/EN62053-23, DIRECTIVE 2014/32/EU, IEC/EN61010, IEC/EN62053-31

Visuals and Diagrams

Product Image

A front view of the HGR41EW energy meter is displayed. It features a high-definition white backlit LCD screen showing '243.2' and '138.3' with units 'A' and 'kWh' respectively. Below the screen are buttons and indicator LEDs. The meter is compact, designed for DIN rail mounting, and includes '[MID Certified]' and '[CE Marked]' markings.

Wiring Diagram

The wiring diagram illustrates a '3 Phase 4 Wire - 1 CT' connection. It shows connections for LINE (L1, L2, L3, N) and LOAD (L1, L2, L3, N). Terminal blocks are labeled for CT Input (RS485, NC, PULSE OUTPUT), Voltage Input (V1, V2, V3, N), and Voltage Output (N, V1, V2, V3). A note specifies fuse types (Class CC UL type, fast acting 600V, Max. 3A) and that actual rating depends on system design.

Dimensions

The dimensions diagram shows the meter's physical size. Key measurements are: Height 118.5mm, Width 70mm, Depth 66mm, and a mounting depth of 45mm. The overall width is 4 modules.

Model Selection

CommunicationsPart Number
RS485 Modbus and Single Pulse kWh OutputHGR41EWC
Mbus and Single Pulse kWh OutputHGR41EWMB

PDF preview unavailable. Download the PDF instead.

HAGER DATA SHEET HGR41EWC MID 03 09 19 Adobe PDF Library 15.0 Adobe InDesign 14.0 (Macintosh)

Related Documents

PreviewHager UKCA Declaration of Conformity for JK Series Electrical Enclosures and Accessories
Official UKCA Declaration of Conformity from Hager Group for their JK TPN DBO, Extension Boxes, Dinrail, and related accessories, confirming compliance with UK legislation and standards.
PreviewHager XEVA205 TIC/CHP Card: Installation and Technical Specifications
This document provides detailed installation instructions, functional descriptions, and technical specifications for the Hager XEVA205 TIC/CHP card, a gateway for energy meter data exchange with Hager charging stations. It covers safety precautions, connection methods for various meter types, CHP function integration, and system compatibility.
PreviewHager Meter Enclosure Installation Guide for 125/250A Models JKD1125MID, JKD2250MID
Instruction leaflet for installing Hager's 125/250A meter enclosures (models JKD1125MID, JKD2250MID). Covers cable fitting, connections, and gland plate mounting with torque specifications.
PreviewHager univers N Mounting Instructions for U96N/UG31N1 and U97N
Detailed installation guide for Hager's univers N electrical enclosure system, covering models U96N/UG31N1 and U97N. Provides step-by-step instructions, required tools, torque specifications, and safety warnings for proper mounting and assembly.
PreviewHager DR96S Din Rail Board - Technical Data Sheet
Comprehensive technical data sheet for the Hager DR96S Din rail board. Details include dimensions, capacity (96 modules), materials (Steel, RAL 9010), safety ratings (IP40, IK05), and installation specifications for this surface-mounted electrical enclosure.
PreviewHager IU42/D 3 Module DIN Rail Box Plain Door - Technical Specifications
Technical specifications for the Hager IU42/D, a 3 Module DIN Rail Box with a Plain Door. Details include dimensions, materials, safety features, and installation information.
PreviewHager Surge Protection Kit JK 250A Type II Installation Guide
User instructions and installation guide for the Hager JK202SPD Surge Protection Kit 250A Type II, detailing parts, connections, and safety precautions for electrical installations.
PreviewHager Krachtgroep 3-polig+nul 16A B-kar (MBN616E) - Technische Specificaties
Gedetailleerde productinformatie over de Hager MBN616E krachtgroep: een 3-polige+nul installatieautomaat met 16A, B-karakteristiek, 6 kA afschakelvermogen, geschikt voor 3-fase installaties.