HZ432 TrueZONE Zone Panel Professional Installation Guide
honeywell-hz322manual HZ432 TrueZONE
Zone Panel Professional Installation Guide
69-2070-01
Installation Guide
Table of Contents
Specifications................................................................................................................................. 1 Accessories..................................................................................................................................... 2 Mounting......................................................................................................................................... 3 Wiring. ............................................................................................................................................. 4 Wiring: Heat Pump.........................................................................................................................6 Wiring: Dual Fuel............................................................................................................................8 Basic Configuration...................................................................................................................... 10 Operation...................................................................................................................................... 11 Advanced Configuration.............................................................................................................. 12 Checkout....................................................................................................................................... 13 Warranty........................................................................................................................................ 14
Need Help?
For assistance with this product please visit http://yourhome.honeywell.com or call Honeywell Zoning Hotline toll-free at 1-800-828-8367
Read and save these instructions.
® U.S. Registered Trademark. Patents pending.
Copyright © 2007 Honeywell International Inc. All rights reserved.
Input Ratings: Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more.
Current Draw: Zone Panel: 10 VA max. All VA specifications at 24 VAC.
Wiring: 18-gauge solid (not stranded) wire.
Humidity Ratings: 5% to 90% RH non-condensing.
HZ432 TrueZONE
Specifications
Temperature Ratings: Shipping: -20° to 150°F (-29° to 66°C) Operating: -40° to 165°F (-40° to 74°C)
Dimensions: See below.
Emissions: Complies with FCC Class B, part 15 requirements.
13.42 (341)
8 (203)
1.86 (47) M24797
HZ432 TrueZONE panel dimensions in in. (mm).
69-2070--01
Installation Guide
Accessories
Table 1. Recommended Thermostats.
System Non-
Programmable
Programmable
Single- TH5110D, TH3110D, TH8110U, TH6110D,
Stage T87N
TH4110D
Multi- TH5220D
TH8320U, TH8321U,
Stage
TH6220D, YTH9421C
Heat- TH5220D (2H/1C TH8320U (Up to 3H/2C)
Pump only)
TH8321U (Up to 3H/2C)
TH3210D (2H/1C TH6320U* (Up to 3H/2C)
only)
TH6220D (2H/1C only)
TH5320U* (Up to TH4210D (2H/1C only)
3H/2C)
YTH9421C* **
Note: These thermostat models all have different four-
digit suffixes. All versions of the model numbers listed
above will work with the applications they're listed for.
* Stage 3 heat needs to be controlled by the zone panel
with this model.
**This thermostat cannot put the panel into emergency
heat.
Type Zone Zone
Bypass
Table 2. Recommended Dampers. Honeywell Round Rectangular Damper Spring-open/ ARD ZD power-closed Power-open/ MARD/ For recommended power-closed RRD dampers call the
Honeywell Zoning Hotline at 1-800-828-8367. Static pres- SPRD SPRD sure regulating damper
Table 3. Maximum Dampers.*
Ambient Temp. Maximum Damper VA per Zone
100°F (38°C)
28.8
160°F (71°C)
16.8
* Use an SDCR (Slave Damper Control Relay) for addi-
tional dampers.
Maximum dampers per panel is limited by transformer
size.
Ensure transformer is large enough to power the panel
(10 VA) and dampers.
Table 4. Accessories.
Accessory
Description
40 VA transformer* 75 VA transformer
AT140A1042* AT175A1008
Discharge Air Temperature Sensor *
DATS C7735A1000*
Outdoor Air Temperature C7089U1006 Sensor
TAZ-4 SDCR
TotalZone® Add-A-ZoneTM Control Panel Slave Damper Control Relay
* Included in HZ432K kit.
69-2070--01
HZ432 TrueZONE
Mount the HZ432 TrueZONE panel near the HVAC
1
equipment; locate it on a wall, stud, roof truss, or coldair return.
SPRD BYPASS DAMPER
NOTE: The HZ432 TrueZONE panel can be mounted in any orientation; level it for appearance only.
DATS (ALTERNATE LOCATION)
TrueZONE PANEL MOUNTED ON RETURN DUCT
Mounting
ZD SERIES ZONE DAMPERS
SUPPLY DUCT
TrueZONE PANEL MOUNTED ON WALL
DATS (AT LEAST 3 FT FROM PLENUM)
FURNACE OR AIR CONDITIONER
M24738
2
Separate the zone panel cover from the base, and use the base as a template to drill mounting holes. Attach the base to the wall, stud, roof truss, or duct with appropriate screws (not included).
Use two screws for attaching to a stud or roof truss, or four screws for duct or drywall/plaster installations.
M24807
69-2070--01
Installation Guide
Wiring
CAUTION: Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning installation. Wire entire panel before applying transformer power.
Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional systems, refer to this page. For heat pump systems, see pages 6 and 7. For dual fuel systems, see pages 8 and 9. Wiring must comply with applicable codes, ordinances, and regulations. Use the following wiring diagrams to wire the zone panel to the thermostats and dampers.
Install thermostats using instructions provided with thermostats.
3
Connect thermostat to zone panel. To connect wire to the panel, strip approximately 1/4 in. of insulation and push wire into terminal. To
release wire, press the button on top of the terminal.
Rc
R
C
W
W2
Y
Y2
G
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M24808
The HZ432 offers many innovations for wire management and organization: wires can be run behind the panel, through wire channels on its sides, and attached to a wiring anchor with a cable tie.
ZONE 3 DAMPER
THERMOSTAT ZONE 4 DAMPER
M24743
Install dampers using instructions provided with dampers.
4
Connect dampers to zone panel.
NOTE: Multiple dampers can be wired in parallel.
ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED
M1 COMMON
M1
M4 OPEN
M4 M6
M6 CLOSED
R
RRD OR MARD DAMPER POWER-OPEN POWER-CLOSED
ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED
ZONE 1 DAMPER
ZONE 2 DAMPER
69-2070--01
M24920
5
Connect DATS as shown.
C7735A1000
DATS DATS
M24804
SENSOR
HZ432 TrueZONE
Wiring
6
Connect equipment as shown.
HVAC
24 VOLT TRANS.
C
R
W W2
FAN RELAY G
Y2 Y
COMPRESSOR RELAY
EQUIPMENT
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
M24809
The DS/BK terminal is used with a variable-speed fan. Connect the DS, BK, ODD, or DHUM terminal on the HVAC equipment to this terminal. When 1 zone is calling (or 25% on systems with more than 4 zones) this terminal will be de-energized of 24 VAC. This reduces blower speed on most variable speed blowers.
L1
(HOT)
R
7
Connect transformer as shown.
L2
C
DEDICATED
TRANSFORMER
POWER
R C
M24806
69-2070--01
Installation Guide
Heat Pump
Use the following diagram for wiring a 2-heat/1-cool heat pump with electric auxiliary heat. NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by heat pump thermostats. The diagram below shows a heat pump thermostat used with a heat pump system.
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
THERMOSTAT ZONE 4 DAMPER
1
AIR
2
HANDLER
24 VOLT TRANS.
C
R
EM. HEAT E
AUX. HEAT W2
FAN RELAY G Y
Rc R C E
AUX Y
G O/B
L
HEAT PUMP
C
R
Y
L1
(HOT)
R
REVERSING VALVE
L2
C
DEDICATED
TRANSFORMER
C7089U1006 OUTDOOR TEMPERATURE SENSOR
SENSORS
ACCESSORIES POWER
EQUIPMENT
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
C7735A1000 DATS
3
HZ432
HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN EM HEAT
ZONE 1 ZONE 2 ZONE 3 ZONE 4
EMERGENCY HEAT
HOME CONFIG CHECK OUT
ADJUST SETTING
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
ZONE 3 THERMOSTAT DAMPER
ZONE 2 THERMOSTAT DAMPER
ZONE 1 THERMOSTAT DAMPER
M1 COMMON RRD OR MARD DAMPER
POWER-OPEN
M4 OPEN
POWER-CLOSED
M6 CLOSED
Rc R C E AUX 1 Y
G
O/B
2
L
Rc R C E AUX Y
G O/B L
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
1
2
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
Rc R C E AUX 1 Y
G
O/B
2
L
1 ALTERNATIVELY LABELED W2 ON SOME THERMOSTATS.
2
FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, ATTACH O FOR COOL CHANGEOVER VALVES, AND ATTACH B FOR HEAT CHANGEOVER VALVES.
3 IF EQUIPMENT DOES NOT HAVE SEPARATE E AND W2 TERMINALS, JUMPER E TO W2 ON PANEL AND WIRE TO E.
M24794
Zone panel wiring--heat pump, 2-heat/1-cool with electric auxiliary heat.
69-2070--01
Use the following diagram for wiring a 3-heat/2-cool heat pump with electric stage 3 heat.
HZ432 TrueZONE
Heat Pump
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
THERMOSTAT ZONE 4 DAMPER
1
AIR 2 HANDLER
24 VOLT TRANS.
C
R
EM. HEAT E
AUX. HEAT W3
FAN RELAY G
Y2 Y
Rc R C E
AUX Y
Y2 G O/B L
HEAT PUMP
C
R
Y
L1
(HOT)
R
Y2
REVERSING VALVE
L2
C
DEDICATED
TRANSFORMER
C7089U1006 OUTDOOR TEMPERATURE SENSOR
SENSORS
ACCESSORIES POWER
EQUIPMENT
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
C7735A1000 DATS
3
HZ432
HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN EM HEAT
ZONE 1 ZONE 2 ZONE 3 ZONE 4
EMERGENCY HEAT
HOME CONFIG CHECK OUT
ADJUST SETTING
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
ZONE 3 THERMOSTAT DAMPER
ZONE 2 THERMOSTAT DAMPER
ZONE 1 THERMOSTAT DAMPER
M1 COMMON RRD OR MARD DAMPER POWER-OPEN
M4 OPEN
POWER-CLOSED
M6 CLOSED
Rc
R
C
E
AUX 1
Y
Y2
G
O/B
2
L
Rc R C E AUX Y Y2 G O/B L
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
1
2
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
Rc
R
C
E
AUX 1
Y
Y2
G
O/B
2
L
1 ALTERNATIVELY LABELED W2 ON SOME THERMOSTATS.
2 FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, ATTACH O FOR COOL CHANGEOVER VALVES, AND ATTACH B FOR HEAT CHANGEOVER VALVES.
3 IF EQUIPMENT DOES NOT HAVE SEPARATE E AND W2 TERMINALS, JUMPER E TO W2 ON PANEL AND WIRE TO E.
M24795
Zone panel wiring--heat pump, 3-heat/2-cool with electric stage 3 heat.
69-2070--01
Installation Guide
Dual Fuel
Use the following diagram for wiring a dual-fuel system with single-stage furnace and single-stage heat pump.
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
THERMOSTAT ZONE 4 DAMPER
FURNACE
24 VOLT TRANS.
C
R
W
FAN RELAY G Y
HEAT PUMP
C
R
Y
REVERSING VALVE
Rc R C E
AUX Y
Y2 G O/B L
L1
(HOT)
R
L2
C
DEDICATED
TRANSFORMER
C7089U1006 OUTDOOR TEMPERATURE SENSOR
C7735A1000 DATS
SENSORS
ACCESSORIES POWER
EQUIPMENT
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
HZ432
HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN EM HEAT
ZONE 1 ZONE 2 ZONE 3 ZONE 4
EMERGENCY HEAT
HOME CONFIG CHECK OUT
ADJUST SETTING
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
ZONE 3 THERMOSTAT DAMPER
ZONE 2 THERMOSTAT DAMPER
ZONE 1 THERMOSTAT DAMPER
M1 COMMON RRD OR MARD DAMPER POWER-OPEN
M4 OPEN
POWER-CLOSED
M6 CLOSED
Rc R C E AUX Y Y2 G O/B L
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
Rc
R
C
E
AUX
Y
Y2
G
O/B
ARD OR ZD DAMPER
L
SPRING-OPEN
POWER-CLOSED
Rc R C E AUX Y Y2 G O/B L
M24796
Zone panel wiring--dual fuel: single-stage furnace and single-stage heat pump.
69-2070--01
HZ432 TrueZONE
dual Fuel
Use the following diagram for wiring a dual-fuel system with two-stage furnace and two-stage heat pump.
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
THERMOSTAT ZONE 4 DAMPER
FURNACE
24 VOLT TRANS.
C
R
HEAT 1 W
HEAT 2 W2
FAN RELAY G
Y2 Y
HEAT PUMP
C
R
Y
Y2
REVERSING VALVE
Rc R C E
AUX Y
Y2 G O/B L
L1
(HOT)
R
L2
C
DEDICATED
TRANSFORMER
C7089U1006 OUTDOOR TEMPERATURE SENSOR
SENSORS
ACCESSORIES POWER
EQUIPMENT
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
C7735A1000 DATS
HZ432
HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN EM HEAT
ZONE 1 ZONE 2 ZONE 3 ZONE 4
EMERGENCY HEAT
HOME CONFIG CHECK OUT
ADJUST SETTING
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
ZONE 3 THERMOSTAT DAMPER
ZONE 2 THERMOSTAT DAMPER
ZONE 1 THERMOSTAT DAMPER
M1 COMMON
RRD OR MARD DAMPER POWER-OPEN
M4 OPEN
POWER-CLOSED
M6 CLOSED
Rc R C E AUX Y Y2 G O/B L
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
Rc R C E AUX Y Y2 G O/B L
ARD OR ZD DAMPER SPRING-OPEN
POWER-CLOSED
Rc R C E AUX Y Y2 G O/B L
M24793
Zone panel wiring--dual fuel: two-stage furnace and two-stage heat pump.
69-2070--01
Installation Guide
Configuration
To enter Configuration:
1
Press the Mode button (the Config LED will light up).
HOME CONFIG CHECK OUT
MODE
BACK ADJUST SETTING NEXT
M24799
Use the Back and Next buttons to navigate through the configuration
2
menus. Pressing Next enters the selected option for that menu item and advances to the next menu. Adjust settings up or down by pressing the
Adjust Setting button.
HOME CONFIG CHECK OUT
MODE
BACK ADJUST SETTING NEXT
M24810
HOME CONFIG CHECK OUT
MODE
BACK ADJUST SETTING NEXT
M24811
The flow chart below illustrates basic zone panel configuration. For additional configuration, see
3
Advanced Configuration on page 12. The label on the inside cover of the HZ432 Zone Panel also contains configuration information.
69-2070--01
M24812
10
HZ432 TrueZONE
The HZ432 TrueZONE panel contains an LED display that communicates system and zone status. The LEDs indicate the following information.
Operation
Much of this information, as well as configuration information, is listed on the label on the inside of the HZ432 cover. For users who prefer French or Spanish labels, they are provided in the 69-2070FS document. Cut them out and attach them to the inside of the HZ432 cover.
HZ432
HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN EM HEAT
ZONE 1 ZONE 2 ZONE 3 ZONE 4
LED HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2 PURGE
FAN EM HEAT
ZONE 1, 2, 3, 4
EMERGENCY HEAT
M24798
Table 5. LED Operation. Description Solid when in heat stage 1. Blinking when DATS high limit mode has been reached. Solid when in heat stage 2. Blinking when stage 2 locked out due to DATS or OT. Solid when in heat stage 3. Blinking when stage 3 locked out due to DATS or OT. Solid when in cool stage 1. Blinking when DATS low limit mode has been reached. Solid when in cool stage 2. Blinking when stage 2 locked out due to DATS. Solid when in purge (at power-up and after a call for heat or cool). Blinking when the DATS sensor has failed, or the wires are shorted or open. Will blink for 3 minutes at power-up if DATS is not present. Solid with a call for fan only. Solid when in emergency heat mode. This light does not indicate a call for heat. Emergency heat will only run when both HEAT and EM HEAT are lit. Solid green when open or opening. Solid red when closed or closing. Blinking amber when there is a damper or thermostat short circuit (circuit breaker trip).
11
69-2070--01
Installation Guide
Advanced Configuration
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 10 for instructions on using these buttons.
Table 6. Advanced Configuration.
Menu Name Heat Fan Stage 2 Timer Stage 3 Timer Purge Timer
Menu Title (LCD top line) HEAT FAN CONTROL STAGE 2 TIMER
STAGE 3 TIMER
PURGE TIME
Menu Options (LCD bottom line; defaults in bold) [HVAC] PANEL HVAC [PANEL]
[5 MIN] > < [60 MIN] [5 MIN] > [5 MIN] > < [60 MIN] [5 MIN] > [2] 3.5 5 MIN 2 [3.5] 5 MIN 2 3.5 [5] MIN
Menu option description
Fan control by HVAC Fan control by Panel 5 minutes60 minutes
5 minutes60 minutes
2.0 minutes 3.5 minutes 5.0 minutes
Purge Fan
FAN IN PURGE
[HVAC] PANEL
HVAC [PANEL]
Purge Dampers
PURGE DAMPERS [UNCHANGD] OPEN
UNCHANGD [OPEN]
Auto Changeover Delay CHANGEOVER
[15] 20 30 MIN
DELAY
15 [20] 30 MIN
15 20 [30] MIN
DATS Enabled
DISCHARGE
[NO] YES
SENSOR
NO [YES]
DATS High Limit
DAT HIGH LIMIT
[110 F] > < [180 F]
< [160 F] >
DATS Low Limit
DAT LOW LIMIT
[30 F] > < [60 F]
< [40 F] >
Multistage DATS Inhibit DAT MSTG INHIBIT [NO] YES
NO [YES]
Fan control by HVAC Fan control by Panel Dampers Unchanged Dampers All Open 15 minutes auto changeover timer 20 minutes auto changeover timer 30 minutes auto changeover timer Disabled Enabled 110 deg F180 deg F
30 deg F60 deg F
Disabled Enabled
Notes:
In heat mode, fan controlled by HVAC or turned on by panel in call for heat. Number of minutes to delay before engaging second stage. Number of minutes to delay before engaging third stage. Number of minutes panel will purge following call for heat or cool.
Fan controlled by HVAC or panel during purge.
Damper position unchanged or all dampers open during purge. Number of minutes to delay auto changeover when one zone is calling for heat and another is calling for cooling. Enables or disables DATS. If Disabled, the Multistage DATS Inhibit setting is Disabled. High temperature limit.
Low temperature limit.
Allow panel to downstage multistage equipment when near DATS high or low limit.
Dual Fuel Changeover DUALFUEL CHGOVR
[OT] MULTISTG OT [MULTISTG]
OT Temp Enabled
OT SENSOR
Multistage OT Temp Lockout
MSTG OT LOCKOUT
[NO] YES NO [YES]
[NO] YES NO [YES]
OT Balance
OT BALANCE
Temperature (Dual Fuel) TEMP
OT Trip point for multi- OT LOCKOUT
stage lockout
TEMP
[0 F] > < [50 F] < [30 F] >
[0 F] > < [50 F] < [50 F] >
Zone 1, 2, 3, 4 tstat config
LCD Contrast Adjust Save Changes Reload Defaults
ZONE 1 TSTAT ZONE 2 TSTAT ZONE 3 TSTAT ZONE 4 TSTAT LCD CONTRAST
SAVE CHANGES?
RELOAD DEFAULTS?
[CONV] > < [HTPUMP-O] > < [HTPUMP-B] >
[1] > < [10] < [5] > [NO] YES NO [YES] [NO] YES NO [YES]
Dual Fuel Changeover by OT Temp Allow panel to changeover from heat pump to
Dual Fuel Changeover by OT Temp + fossil fuel based on outdoor temperature, or
multistage call
allow multistage call to changeover panel to
fossil fuel when outdoor temperature is above
OT balance temperature setting.
Disabled Enabled
Enables or disables outdoor temperature sensor. If Disabled, the Multistage OT Temp Lockout setting is Disabled.
Disabled Enabled
When outdoor temperature is above OT Lockout temperature, locks out second or third stage (only for conventional and heat pump configurations).
0 deg F50 deg F
0 deg F50 deg F
Conventional Heat Pump O-type Heat Pump B-type
Selects the temperature at which a dual fuel configuration will change from heat pump to fossil fuel. The temp that locks out second or third stage (only for conventional and heat pump configurations, not dual fuel systems).
Configures panel for thermostat type. O Type energizes reversing valve in cool. B type energizes in heat.
Contrast value 110
Disabled Enabled Disabled Enabled
Sets LCD display contrast for ease of viewing. Lowest contrast is 1, highest contrast is 10. Saves or rejects the configuration settings.
Restores the panel's default configuration settings.
69-2070--01
12
HZ432 TrueZONE
Checkout
To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on page 10 for instructions on using these buttons.
Steps 310 cycle through heating and cooling stages and open and close dampers to verify proper operation.
Steps 1114 verify thermostat operation and correct wiring. This is done by making the thermostats call for heat or cool and viewing the active wires as displayed on the LCD screen.
Checkout Step 1. Display shows OT 2. Display shows DATS 3. Heat stages test
4. EM Heat stages test
5. Cool stages test
6. Fan Test 7. Damper 1 test 8. Damper 2 test 9. Damper 3 test 10. Damper 4 test 11. View Tstat1 inputs 12. View Tstat2 inputs 13. View Tstat3 inputs 14. View Tstat4 inputs 15. Exit checkout mode? 16. Exiting checkout mode
Table 7. Checkout.
Line 1 display Line 2 Display
OT SENSOR VAL current OT temp (dynamic)
DAT SENSOR VAL current DATS (dynamic)
TEST HEAT
[OFF] 1
OFF [1]
[OFF] 1 2
OFF [1] 2
OFF 1 [2]
[OFF] 1 2 3
OFF [1] 2 3
OFF 1 [2] 3
OFF 1 2 [3]
TEST EMERG HEAT [OFF] 1
OFF [1]
[OFF] 1 2
OFF [1] 2
OFF 1 [2]
Notes: All zone dampers open, all other relays OFF. Heat turns on (fan also turns on if configured for fan on in heat).
Emergency heat turns on (fan also turns on).
TEST COOL
TEST FAN TEST Z1 DAMPER
[OFF] 1 OFF [1] [OFF] 1 2 OFF [1] 2 OFF 1 [2] [OFF] ON OFF [ON]
[OPEN] CLOSED OPEN [CLOSED]
Cooling turns on (fan also turns on).
Fan cycles on and off. Cycles damper position with fan on.
TEST Z2 DAMPER [OPEN] CLOSED OPEN [CLOSED]
Cycles damper position with fan on.
TEST Z3 DAMPER [OPEN] CLOSED OPEN [CLOSED]
Cycles damper position with fan on.
TEST Z4 DAMPER [OPEN] CLOSED OPEN [CLOSED]
Cycles damper position with fan on.
ZONE1 STAT INPTS Displays active Tstat1 terminals
ZONE2 STAT INPTS Displays active Tstat2 terminals
ZONE3 STAT INPTS Displays active Tstat3 terminals
ZONE4 STAT INPTS Displays active Tstat4 terminals
EXIT CHECKOUT? (NEXT = EXIT)
EXITING
.
CHECKOUT
. .
. . .
. . . .
. . . . .
Tests thermostat wiring with HVAC off. Tests thermostat wiring with HVAC off. Tests thermostat wiring with HVAC off. Tests thermostat wiring with HVAC off.
13
69-2070--01
Warranty
Honeywell warrants the products in this catalog (except those parts designated on Honeywell's price lists as not covered by this warranty) to be free from defects due to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPROTM, FocusPRO®, PRO 4000, PRO 3000, LineVoltTM PRO, Digital RoundTM, and Modern RoundTM (T87K, N) Series Thermostats with a date code of 0501 or later: sixty (60) months from date of installation. CommercialPRO, PRO 2000 and PRO 1000 thermostats: twenty-four (24) months from date of installation. All other Honeywell thermostats and thermostats with a date code of 0452 or earlier: twelve (12) months from date of installation, unless specified otherwise. Honeywell Air Cleaners, Humidifiers, Ventilators, Ultraviolet Treatment and Zoning Products with a date code of 0501 or later, excluding replacement maintenance parts: sixty (60) months from date of installation. All other Honeywell indoor air quality and zoning products with a date code of 0452 or earlier: twenty-four (24) months from date of installation, unless specified otherwise. Variable frequency drive devices (VFD) and accessories: new products for thirty-six (36) months and factory refurbished drives for twelve (12) months from date of installation when start-up and commissioning is performed by Honeywell VFD Authorized and trained personnel. All VFD warranty return products must have prior authorization (Form No. 87-0284) and be returned only to the VFD Service Center in Chattanooga, TN. MS, MN and Fact Acting 2-position Direct Coupled Actuators: sixty (60) months from date of installation. The warranty period for all other products is twelve (12) months from date of installation.
If a product is defective due to workmanship or materials, is removed within the applicable warranty period, and is returned to Honeywell in accordance with the procedure described below, Honeywell will, at its option, either repair, replace or credit the customer for the purchase price of the product, in accordance with the procedure described below. This warranty extends only to persons or organizations who purchase products in this catalog for resale.
The expressed warranty above constitutes the entire warranty of Honeywell with respect to the products in this catalog and IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL HONEYWELL BE RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
35 Dynamic Drive
Golden Valley, MN 55422
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark. © 2007 Honeywell International Inc. Patents pending 69-2070--01 M.S. 07-07
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.