User Manual for Mircom models including: FA-300 Series LCD Fire Alarm Control Panel, FA-300 Series, LCD Fire Alarm Control Panel, Alarm Control Panel

LT-954 FA-300 userguide LCD.book

janderson

Click here to download

Mircom LT-954 FA-300 LCD Userguide (English) - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications


File Info : application/pdf, 20 Pages, 1.68MB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676764210
FA-300 Series
LCD Fire Alarm Control Panel

Advanced Life Safety Solutions

System Normal 10:36AM WED 2003-10-01

SYSTEM RESET

A.C. ON ALARM SUPV TRBL CPU FAIL

SIGNAL

SILENCE

1

2 ABC

3

ENTER

DEF

FIRE DRILL
LAMP TEST

4 GHI
7 PQR

5 JKL
8 STU

6 MNO

MENU

9

CANCEL

WXY

BUZZER

SILENCE

*

0

#

INFO

YZ

FA-300 SERIES Fire Alarm Control Panel

Installation and Operation Manual
firealarmresources.com

LT-954 Rev. 1 February 2017

firealarmresources.com

Table of Contents

1.0
1.1 1.2
2.0
3.0
3.1 3.2 3.3 3.4 3.5 3.6
4.0
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8
5.0
5.1 5.1
6.0
6.1 6.2 6.3 6.3.1 6.3.2 6.3.3 6.3.4 6.3.5 6.3.6 6.3.7
7.0

Introduction

5

About this Manual .......................................................................................................... 5 Technical Support .......................................................................................................... 5

Main Display

6

The Buzzer and LED Indicators

7

Buzzer ............................................................................................................................ 7 A.C. On LED .................................................................................................................. 7 Alarm LED ...................................................................................................................... 7 Supervisory LED ............................................................................................................ 7 Trouble LED ................................................................................................................... 7 CPU Fail LED ................................................................................................................. 7

Main Display Buttons

8

SYSTEM RESET ........................................................................................................... 8 SIGNAL SILENCE ......................................................................................................... 8 FIRE DRILL .................................................................................................................... 8 LAMP TEST ................................................................................................................... 8 BUZZER SILENCE ........................................................................................................ 8 The Up and Down Arrow Buttons .................................................................................. 8 INFO .............................................................................................................................. 9 ENTER, MENU, and CANCEL ....................................................................................... 9

Disconnecting and Reconnecting a Circuit (Zone)

10

To Disconnect (Bypass) a Circuit ................................................................................... 10 To Reconnect (Unbypass) a Circuit ............................................................................... 11

Understanding On-screen Messages

12

Example 1 (detection circuit) .......................................................................................... 12 Example 2 (indicating circuit): ........................................................................................ 12 Common Messages ....................................................................................................... 13 AC Power Fail ................................................................................................................ 13 Battery Trouble .............................................................................................................. 13 Ground Fault .................................................................................................................. 14 RAU num mismatch ....................................................................................................... 14 4Wire Pwr. Supply ......................................................................................................... 15 Supervised Aux-supply .................................................................................................. 15 City tie Polarity reversal - PR-300/Relay module ........................................................... 16

Glossary
firealarmresources.com

18
3 (20)

List of Figures
Figure 1 Main Display ................................................................................................................... 6 Figure 2 LED Indicators ................................................................................................................ 7 Figure 3 Verified Alarm Example .................................................................................................. 12 Figure 4 Silenceable Signal Example ........................................................................................... 13 Figure 5 AC Power Fail ................................................................................................................ 13 Figure 6 Battery Trouble ............................................................................................................... 14 Figure 7 Ground Fault .................................................................................................................. 14 Figure 8 RAU num mismatch ....................................................................................................... 15 Figure 9 4Wire Pwr. Supply .......................................................................................................... 15 Figure 10 Aux. Power Supply ......................................................................................................... 16 Figure 11 CtyTie/RM312 missing ................................................................................................... 16 Figure 12 City Tie trouble ............................................................................................................... 17
4 (20)
firealarmresources.com

1.0 Introduction

1.1 About this Manual

This user guide provides information on the main indicators and controls of the FA-300 Fire Alarm Control Panel. Specifically, with this manual you will learn about:
· What the LEDs on the main display indicate · What the buttons on the main display do · What certain common LCD screen messages mean
Refer to the Glossary on page 18 for an explanation of terms used in this manual.
1.2 Technical Support

For all technical support inquiries, please contact Mircom's Technical Support Department between 8 A.M. and 5 P.M. (EDT) Monday through Friday, excluding holidays.

Local Phone: 905-695-3535 Toll-Free Phone: 1-888-449-3535

Local Fax: 905-660-4113

Toll-Free Fax: 1-888-660-4113

Email: techsupport@mircom.com

5 (20)
firealarmresources.com

2.0

Main Display
Figure 1 shows the LCD display, LED indicators, and control buttons locations.

System Normal 18:01 MON 2003-04-05

SYSTEM RESET
SIGNAL SILENCE
FIRE DRILL
BUZZER SILENCE
LAMP TEST

A.C. ON

ALARM

SUPV

TRBL

CPU FAIL

1
4 GHI
7 PRS
*

2 ABC
5 JKL
8 TUV
0 QZ

3 DEF
6 MNO
9 WXY
#

ENTER MENU CANCEL INFO

Figure 1 Main Display
The main display panel on the fire alarm control board consists of: · Five LED indicators (located just below the LCD screen) · Five buttons (left edge of display) · 16 program buttons (right part of display)
LED indicators may be amber, red, or green, and may illuminate continuously (steady), or at one of two flash rates:
· Fast flash (supervisory): 120 flashes per minute · Trouble flash: 20 flashes per minutes

6 (20)
firealarmresources.com

3.0

The Buzzer and LED Indicators

A.C. ON

ALARM

SUPV

TRBL

CPU FAIL

Figure 2 LED Indicators
3.1 Buzzer
The buzzer sounds if there is a fire alarm, a supervisory alarm, or a trouble in the fire alarm system. It turns off if the condition causing the buzzer to sound is cleared or if the BUZZER SILENCE button is pressed.
3.2 A.C. On LED
The green A.C. On LED illuminates steadily as long as the main power is above minimum level. The indicator turns off when the level falls below the minimum level and the panel switches to standby (battery) power.
3.3 Alarm LED
The red Alarm LED illuminates steadily when there is a fire alarm. This indicator will remain on until the system is reset.
3.4 Supervisory LED
The amber Supervisory LED illuminates at the fast flash rate when there is a supervisory alarm in the fire alarm system. For non-latching supervisory alarms, the SUPV LED will turn off when the condition causing the alarm goes away. For latching supervisory alarms, this LED remains on until the panel is reset.
3.5 Trouble LED
The Trouble LED flashes amber at the trouble flash rate when the panel detects any trouble condition. For non-latching trouble conditions, the Trouble LED turns off when the condition causing the alarm goes away. For latching trouble conditions, the LED remains on until the panel is reset.
3.6 CPU Fail LED
The CPU Fail LED flashes amber at the trouble flash rate to indicate a microprocessor failure on the main board.

7 (20)
firealarmresources.com

4.0 Main Display Buttons
4.1 SYSTEM RESET

SYSTEM RESET

The SYSTEM RESET button resets the fire alarm control panel and all circuits.

4.2 SIGNAL SILENCE

SIGNAL SILENCE

Pressing the SIGNAL SILENCE button when the panel is in alarm deactivates any silenceable signal devices in the fire alarm system. Non-silenceable signal devices are unaffected. If you press the SIGNAL SILENCE button a second time, or if there is a subsequent alarm, the signals will re-sound. If the panel has been configured with a signal silence inhibit timer, this button will not work until the timer expires. This button also does not work if you have pressed the FIRE DRILL button.

4.3 FIRE DRILL

FIRE DRILL

Pressing the FIRE DRILL button simulates a fire alarm by activating the fire alarm signals without transmitting an alarm to the central station. To cancel the fire drill, press the button again. If the fire alarm system goes into a real alarm while you are performing a fire drill, this button will not turn off the signals or operate any programmed relays.

4.4 LAMP TEST

LAMP TEST

Pressing and holding the LAMP TEST button causes all the front panel LEDs to illuminate. The screen displays the software version and the buzzer sounds. Use this button to test that the LCD display and all LEDs on the main display are working. If you hold the LAMP TEST button for more than ten seconds, the common trouble is activated.

4.5 BUZZER SILENCE

BUZZER SILENCE

Pressing the BUZZER SILENCE button while the buzzer is sounding silences the buzzer. The buzzer will resound if there is a subsequent event. Pressing the button when the buzzer is not sounding has no effect.

4.6 The Up and Down Arrow Buttons

8 (20)

2 ABC
8 TUV

Use these buttons to scroll through any events listed on the screen. The up arrow moves to the next listed condition and the down arrow moves to the previously listed condition.

firealarmresources.com

Main Display Buttons

4.7 INFO

Press the INFO button while the there is a message on the screen to view

INFO

additional information.

4.8 ENTER, MENU, and CANCEL
The ENTER, MENU, and CANCEL buttons are used by technicians to program the fire alarm control panel.

9 (20)
firealarmresources.com

5.0

Disconnecting and Reconnecting a Circuit (Zone)
You can disconnect and reconnect detection and signal circuits (zones) from the panel using the bypass options in the menu.
To select the bypass options, you must be in the Command Menu. To enter the Command Menu, press MENU. MENU

5.1 To Disconnect (Bypass) a Circuit

Step 1: Enter your passcode

Enter the passcode

1. Enter your passcode. 2. Press ENTER. ENTER

Step 2: Select the Bypass menu

- Bypass Det Zone -

1. Use the up and down arrow buttons 2

8

ABC

TUV

to scroll down to "Bypass Det Ckt" or "Bypass NAC

Ckt".

 2. Press ENTER. ENTER

3. Use the up and down arrow buttons to select the circuit that you want to disconnect.

4. Press ENTER. ENTER

Step 3: Select BYPASSED

Zone-1 [ ] BYPASSED

1. Use the up and down arrow buttons 2

8

ABC

TUV

to scroll the cursor to "Bypassed".

2. Use the right arrow button 6 to change the
MNO



selection to "X". The "X" indicates that the option is selected.

3. Press ENTER. ENTER

4. Press CANCEL CANCEL twice to return to the main menu.

If you have disconnected (bypassed) a circuit, a trouble message appears on the display and disappears when the circuit is reconnected.

10 (20)
firealarmresources.com

Disconnecting and Reconnecting a Circuit (Zone)

5.1 To Reconnect (Unbypass) a Circuit

Step 1: Enter your passcode

Enter the passcode

1. Press MENU. 2. Enter your passcode.
3. Press ENTER. ENTER

Step 2: Select the Bypass menu

- Unbypass Det Zone -



1. Use the up and down arrow buttons 2

8

ABC

TUV

to scroll down to "Bypass Det Ckt" or "Bypass NAC

Ckt".

2. Press ENTER. ENTER 3. Use the up and down arrow buttons to select the
circuit you want to reconnect.
4. Press ENTER. ENTER

Step 3: Select UNBYPASSED

1. Use the up and down arrow buttons 2

8

ABC

TUV

to scroll the cursor to "Unbypassed".

Zone-1 [ ] UNBYPASSED



2. Use the right arrow button 6 to change the
MNO
selection to "X". The "X" indicates that the option is selected.
3. Press ENTER. ENTER

4. Press CANCEL CANCEL twice to return to the main menu.

11 (20)
firealarmresources.com

6.0
i

Understanding On-screen Messages
The screen of the fire alarm control panel displays messages regarding system events. System events display on the screen in a queue. Events in this queue are listed on the screen in order of priority: alarms are of highest priority, followed by supervisory, trouble, and monitor conditions. If the same type of event happens more than once (for example, two trouble conditions occur) they will be listed in the order of the most recent event to the least recent event. If an alarm, supervisory, or trouble condition occurs, their respective LED will flash.

Scroll through the events by using the 2 and 8 arrow buttons. If you need more

ABC

TUV

information about a displayed event, press . INFO

Note: For monitor events, the display shows the word BUILDING.

6.1 Example 1 (detection circuit)

Figure 3 indicates that event 1 of 9 is an open trouble at the East Lobby Entrance. When INFO is pressed, the screen shows that the process type is a verified alarm on Z-01 and the
event occurred on Tuesday April 4, 2003 at 18:01.

ZONE M essage

Process Type

P h y s ic a l Zone No.

EAST LOBBY ENTRANCE

OPEN TRB

01/09

EVENT type

EVENT 01 of 09

"INFO" Key

VERIFIED ALARM Z-01 18:01 TUE 2003-04-04

TIM E

DATE

Figure 3 Verified Alarm Example
6.2 Example 2 (indicating circuit):
Figure 4 indicates that event 2 of 9 is a short trouble at the East Wing Lobby. When INFO is pressed, the screen shows that the process type is silenceable on NAC-1 and the event occurred on Tuesday February 2, 2003 at 18:01.

12 (20)
firealarmresources.com

Understanding On-screen Messages

ZZOONNEE MMeessssaaggee

PP rroocceessss TTyyppee

PPhhyyssicicaal l ZZoonneeNNoo. .

EAST WING LOBBY

SHORT TRB

02/09

EE VVEENNTT Metyspseage

EEVVEE NNTT 0022 ooff 0099

""ININFFOO ""KKeyey

SILENCE-ABLE NAC-1 18:01 TUE 2003-02-02

TTIIMMEE

DDAATTEE

Figure 4 Silenceable Signal Example
6.3 Common Messages
Common system messages are outlined below.
6.3.1 AC Power Fail
The "AC Power Fail" message indicates that the power has dropped below the minimum level and the system is running on backup battery power. The trouble is removed when the power returns to the normal value.

Trouble Type

AC Power Fail Active

1/ 1

EVENT 01 of 01

Trouble code

Trouble Info

"INFO" Key

Trb:0x03 Info:0x0004 00:07 SAT 2000-01-01

T IM E

DATE

Figure 5 AC Power Fail
6.3.2 Battery Trouble
The "Battery Trouble" message indicates that the battery voltage has dropped below the minimum value. The trouble is restored when the voltage returns to the normal value.

13 (20)
firealarmresources.com

Understanding On-screen Messages

Trouble Type

Battery Trouble

Active

1/ 1

EVENT 01 of 01

Trouble code

Trouble Info

"INFO" Key

Trb:0x03 Info:0x0008 00:07 SAT 2000-01-01

TIM E

DATE

Figure 6 Battery Trouble

i

Note: The trouble code is a reference code for trained service personnel only.

6.3.3 Ground Fault
The "Ground Fault" message indicates that there is a short in the electrical connection between the metal chassis of the panel and the earth.

Trouble Type

Ground Fault Active

1/ 1
EVENT 01 of 01

Trouble code

Trouble Info

"INFO" Key

Trb:0x03 Info:0x0001 00:07 SAT 2000-01-01

TIM E

DATE

Figure 7 Ground Fault
6.3.4 RAU num mismatch
The "RAU num mismatch" message can display for one of two reasons: either the main panel and annunciator failed to communicate with each other or an unconfigured remote annunciator is communicating with the main panel. In both the cases, the following trouble message is displayed:

14 (20)
firealarmresources.com

Understanding On-screen Messages

Trouble Type

RAU num mismatch

trouble

1/ 1

EVENT 01 of 09

Trouble code

Trouble info

"INFO" Key

Trb:0x03 Info:0x0001 11:45 SAT 2003-02-03

T IM E

DATE

Figure 8 RAU num mismatch

i

Note: The trouble code is a reference code for trained service personnel only.

6.3.5 4Wire Pwr. Supply

The "4Wire Pwr. Supply" message indicates that the panel has detected a short on a four-wire smoke supply the power is cut off and a trouble message is generated. Press System Reset

SYSTEM RESET

to restore the power the system. If the short is removed, the panel will return to normal;

otherwise the trouble message will stay.

Trouble Type

4Wire Pwr. Supply

short

1/ 1

EVENT 01 of 01

Trouble code

Trouble Info

"INFO" Key

Trb:0x03 Info:0x0001 00:07 SAT 2000-01-01

T IM E

DATE

Figure 9 4Wire Pwr. Supply

6.3.6 Supervised Aux-supply

The "Aux. Power Supply" message indicates that the panel has detected a short on the

auxiliary power supply (battery backup) and has cut it off. Press System Reset

SYSTEM RESET

to

restore the power the system. If the short is removed, the panel will return to normal; otherwise the trouble message will stay.

15 (20)
firealarmresources.com

Understanding On-screen Messages

Trouble Type

Aux. Power Supply

short

1/ 1

EVENT 01 of 01

Trouble code

Trouble Info

"INFO" Key

Trb:0x03 Info:0x0001 00:07 SAT 2000-01-01

TIM E

DATE

Figure 10 Aux. Power Supply

i

Note: The trouble code is a reference code for trained service personnel only.

6.3.7 City tie Polarity reversal - PR-300/Relay module
The "CtyTie/RM312 missing" message below indicates that the city tie, polarity reversal module or the relay module is not plugged in.

Trouble Type

CtyTie/RM312 missing

Active

1/ 1

EVENT 01 of 01

Trouble code

Trouble Info

"INFO" Key

Trb:0x03 Info:0x0001 00:07 SAT 2000-01-01

TIM E

DATE

Figure 11 CtyTie/RM312 missing
The "City Tie trouble" message below indicates that the panel detects an open on the city tie output.

16 (20)
firealarmresources.com

Understanding On-screen Messages

Trouble Type

City Tie trouble

Active

1/ 1

EVENT 01 of 01

Trouble code

Trouble Info

"INFO" Key

Trb:0x03 Info:0x0001 00:07 SAT 2000-01-01

T IM E

DATE

Figure 12 City Tie trouble

i

Note: The trouble code is a reference code for trained service personnel only.

17 (20)
firealarmresources.com

7.0 Glossary
Alarm Condition
Occurs when devices such as detectors, pull stations, or sprinklers are activated. In a single stage system, this condition activates all signaling devices throughout the building. In a two stage system, this condition activates an alert signal and the General Alarm timer.
Circuits
Refers to an actual electrical interface and is classified as initiating (detection), indicating (signal), or relay. The terms "circuit" and "zone" are often used interchangeably in the fire alarm industry.
Fast Flash Rate
An LED flashes at 120 flashes per minute to indicate a supervisory alarm.
Indicating Circuit
A circuit in a fire alarm system that is connected to audible or visual signaling devices.
Initiating Circuit
A circuit in a fire alarm system that is connected to detectors, pull stations, sprinklers, or water flow switches.
Latching Circuit
A circuit that, when activated, causes a condition on the panel that cannot be cleared until the panel is reset.
LED
The light-emitting diodes (LEDs) of the FA-300 are colored either amber, red, or green. When lit, LEDs provide information about the status of the panel.
Monitor Condition
Occurs when dampers open or close, when supply and return fans are running, etc.
Non-latching Circuit
A circuit that, when activated, causes a condition on the panel that is cleared once the circuit is deactivated. This term is used to describe supervisory and trouble circuits.
18 (20)
firealarmresources.com

Glossary
Non-Silenceable Circuit
A signal circuit that cannot be silenced by pressing the SIGNAL SILENCE button.
Relay Circuit
A circuit in a fire alarm system that connects relay devices (for example, fan damper relays).
Remote Annunciator
A device that visually indicates, either by LCD or LEDs, the floor or zone where the alarm originated.
Silenceable Circuit
A signal circuit that can be silenced by pressing the SIGNAL SILENCE button.
Supervisory Condition
Occurs when the system detects open circuits, short circuits, and grounds. A supervisory condition is one that would interfere with the operation of the fire alarm system.
Trouble Condition
Occurs when an abnormal condition such as a problem in the wiring, battery or power circuits exists in the fire alarm system.
Trouble Flash Rate
An LED flashes at 20 flashes per minute to indicate a trouble condition.
Walk Test
A test performed by a technician to ensure that each detection device is connected to the panel and working properly.
Zone
A fire alarm protected area that consists of at least one circuit. The terms "circuit" and "zone" are often used interchangeably in the fire alarm industry. 19
19 (20)
firealarmresources.com

20

© Mircom 2017 Printed in Canada Subject to change without prior notice
www.mircomgroup.com

TECHNICAL SUPPORT North America Tel: (888) Mircom5
(888) 647-2665 International Tel: (905) 647-2665

U.S.A 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Tel: (888) 660-4655 (905) 660-4655 Fax: (905) 660-4113

firealarmresources.com

CANADA - Main Office 25 Interchange Way Vaughan, ON L4K 5W3 Tel: (888) 660-4655 (905) 660-4655 Fax: (905) 660-4113



References

Acrobat Distiller 15.0 (Windows)