Volt Polska Sinus Pro Ultra Plus 3000 12/230V Solar Inverter

Product Manual

Version: 2025.07.01

About This Manual

Purpose

This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.

Scope

This manual provides safety and installation guidelines as well as information on tools and wiring.

Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specs to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  10. Fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input to short circuit. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to the local dealer or service center for maintenance.

Product Overview

The inverter features the following components:

Diagrams illustrating the unit's front, side, and rear views with labeled components are provided.

Installation

Unpacking and Inspection

Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. The package should contain:

Preparation

Before connecting any wiring, remove the bottom cover by unscrewing three screws.

Mounting the Unit

Consider the following points before selecting the installation location:

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Battery Connection

CAUTION: For safe operation and regulatory compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table for typical amperage requirements for fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cables for battery connection. To reduce risk of injury, use the proper recommended cable, stripping length (L2), and tinning length (L1) as detailed below.

Recommended battery cable, stripping length (L2) and tinning length (L1)
ModelMaximum AmperageBattery CapacityWire SizeCable mm²L1 (mm)L2 (mm)Torque value
1500W-2470A100AH6AWG13.33182~3 Nm
2500W-24100A100AH4AWG21.153182~3 Nm
Other Models140A100AH2AWG383182~3 Nm

Please follow below steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative cables based on recommended stripping length.
  2. Connect all battery packs as units require. It's suggested to use recommended battery capacity.
  3. Insert battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Make sure polarity is correct at both the battery and the inverter/charger, and that battery cables are tightly screwed to the battery connector.

Diagrams show the battery connection for 12V, 24V, and 48V models.

WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.

CAUTION!! Do not place anything between the flat part of the inverter terminal, otherwise, overheating may occur.

CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.

CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).

AC Input/Output Connection

CAUTION!! Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over-current of AC input. The recommended spec of the AC breaker is 50A.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires
ModelGaugeTorque Value
1.5KW12AWG1.4~ 1.6Nm
2.5KW/3.5W10AWG1.4~ 1.6Nm
5.5KW8 AWG1.4~ 1.6Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open the DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor [~] first.
  4. Then, insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor [~] first.
  5. Make sure the wires are securely connected.

CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.

CAUTION: Appliances such as air conditioners require at least 2~3 minutes to restart because they need enough time to balance refrigerant gas inside their circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the air conditioner manufacturer if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger may trigger an overload fault and cut off output to protect your appliance, but this can sometimes still cause internal damage to the air conditioner.

PV Connection

CAUTION: Before connecting to PV modules, please install a separate DC circuit breaker between the inverter and PV modules.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

PV Module Cable Requirements
ModelTypical AmperageCable SizeTorque
1.5KW-3.5KW15A12 AWG1.4~1.6 Nm
5.5KW18A12 AWG1.4~1.6 Nm

PV Module Selection

When selecting proper PV modules, please consider the following parameters:

  1. Open circuit Voltage (Voc) of PV modules should not exceed the maximum PV array open circuit voltage of the inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.

Solar Charging Mode

Max PV Array Open Circuit VoltagePV Array MPPT Voltage RangeMax PV Input Current
1.5KW-3.5KW500VDC30VDC~500VDC15A
5.5KW500VDC60VDC~500VDC18A

The following tables provide recommended module configurations for 450Wp and 550Wp PV modules, considering the parameters above.

Solar Panel Specifications (450Wp)
SOLAR INPUTQty of panelsTotal input powerInverter Model
1 pcs in serial1 pcs450 W1.5KW-5.5KW
2 pcs in serial2 pcs900 W1.5KW-5.5KW
3 pcs in serial3 pcs1,350 W1.5KW-5.5KW
4 pcs in serial4 pcs1,800 W1.5KW-5.5KW
5 pcs in serial5 pcs2,250 W2.5KW-5.5KW
6 pcs in serial6 pcs2,700 W2.5KW-5.5KW
7 pcs in serial7 pcs3,150 W2.5KW-5.5KW
8 pcs in serial8 pcs3,600 W3.5KW-5.5KW
9 pcs in serial9 pcs4,050 W3.5KW-5.5KW
10 pcs in serial10 pcs4,500 W5.5KW
11 pcs in serial11 pcs4,950 W5.5KW
12 pcs in serial12 pcs5,400 W5.5KW
6 pieces in serial and 2 sets in parallel12 pcs5,400 W5.5KW
Solar Panel Specifications (550Wp)
SOLAR INPUTQty of panelsTotal input powerInverter Model
1 pcs in serial1 pcs550 W1.5KW-5.5KW
2 pcs in serial2 pcs1,150 W1.5KW-5.5KW
3 pcs in serial3 pcs1,650 W1.5KW-5.5KW
4 pcs in serial4 pcs2,200 W2.5KW-5.5KW
5 pcs in serial5 pcs2,750 W2.5KW-5.5KW
6 pcs in serial6 pcs3,300 W3.5KW-5.5KW
7 pcs in serial7 pcs3,850 W3.5KW-5.5KW
8 pcs in serial8 pcs4,400 W5.5KW
9 pcs in serial9 pcs4,950 W5.5KW
4 pieces in serial and 2 sets in parallel8 pcs4,400 W5.5KW
5 pieces in serial and 2 sets in parallel10 pcs5,500 W5.5KW

PV Module Wire Connection

Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
  3. Make sure the wires are securely connected.

Final Assembly

After connecting all wirings, put the bottom cover back by screwing two screws as shown below.

The AC output of the inverter is used to directly supply power to the connected devices in the so-called island system. It is forbidden to connect the AC output to the existing electrical system (even through differential current protection), especially to the phase, neutral N, and differential current wires. Such a connection may result in reverse voltage applied to the inverter output. Damage caused by such connection will result in loss of warranty.

If interference from the mains occurs at the 230V AC input during PSU operation, the PSU will switch to battery operation (BATTERY MODE) for the duration of such interference in order to filter out the interference. After detecting a voltage without interference at the 230V AC input, the power supply will switch back to mains operation (NORMAL WORKING). This situation may occur several times in a short time interval (e.g., 4-5 times switching within 10 seconds). This is due to an incorrect parameter of the power supply network in the form of a 50Hz frequency imbalance or an incorrect sine wave. The main reason may be heat pumps or on-grid photovoltaics plugged into the same power line (off the customer's grid). This is normal behavior of the inverter and does not in any way adversely affect the operation of the power supply itself and the devices connected to it.

Operation

Power ON/OFF

Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

Operation and Display Panel

The operation and display panel is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicator:

LED IndicatorMessages
AC/INV (Green)Solid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHG (Green)Solid On: Battery is fully charged.
Flashing: Battery is charging.
FAULT (Red)Solid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” to select setting programs. Then, press “ENTER” to confirm the selection or ESC to exit.

Setting Programs:

ProgramDescriptionSelectable optionExplanation
01
Output source priority: To configure load power source priority
Utility first (default)
01 Uti
Utility will provide power to the loads as the first priority. Solar and battery energy will provide power to the loads only when utility power is not available.
Solar first
01 SOL
Solar energy provides power to the loads as the first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time.
SBU priority
01 SBU
Utility provides power to the loads only when any one of the following conditions occurs:
- Solar energy is not available.
- Battery voltage drops to either low-level warning voltage or the setting point in program 12.
SUB priority
01 SUB
Solar energy provides power to the loads as the first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
02
Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current)
60A (default)
02 60
If selected, acceptable charging current range will be from Max. AC charging current to Max. charging current of SPEC, but it shouldn't be less than the AC charging current (program 11).
03
AC input voltage range
Appliances (default)
03 APL
If selected, acceptable AC input voltage range will be within 90-280VAC.
UPS
03 UPS
If selected, acceptable AC input voltage range will be within 170-280VAC.
Generator
03 GNE
If selected, acceptable AC input voltage range will be within 90-280VAC and compatible with generators.
Note: Because generators are unstable, the output of the inverter may be unstable too.
05
Battery type
AGM (default)
05 AGM
User-Defined
05 USE
If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
Lithium battery without communication
05 Li b
If "LIB" is selected, the battery default value is fit for lithium battery without communication battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
06
Auto restart when overload occurs
Restart disable
06 LFD
Restart enable (default)
06 LFE
07
Auto restart when over temperature occurs
Restart disable
07 LFD
Restart enable (default)
07 LFE
08
Output voltage
220V
08 220
230V (default)
08 230
240V
08 240
50Hz (default)
09 50
60Hz
09 60
10
Auto bypass
manual(default)
10 NAL
auto
10 AUTO
When selecting "auto", if the mains power is normal, it will automatically bypass, even if the switch is off.
11
Maximum utility charging current
30A (default)
11 30A
If selected, acceptable charging current range will be within 2-Max. AC charging current of SPEC.
12
Setting voltage point back to utility source when selecting “SBU priority” or “Solar first” in program 01.
48V models: 46V (default)
Setting range is from 44.0V to 57.2V for 48v model, but the max setting value must be less than the value of program 13 and the minimum setting value must be more than the value of 29.
24V models: 23V (default)
Setting range is from 22.0V to 28.6V for 24v model, but the max setting value must be less than the value of program 13 and the minimum setting value must be more than the value of 29.
12V models: 11.5V (default)
Setting range is from 11.0V to 14.3V for 12v model, but the max setting value must be less than the value of program 13 and the minimum setting value must be more than the value of 29.
13
Setting voltage point back to battery mode when selecting “SBU priority” or “Solar first” in program 01.
Battery fully charged (default)
13 FUL
48V models:
Setting range is from 48V to full (the value of program 26-0.4V), but the max setting value must be more than the value of program 12.
24V models:
Setting range is from 24V to full (the value of program 26-0.4V), but the max setting value must be more than the value of program 12.
12V models:
Setting range is from 12V to full (the value of program 13-0.4V), but the max setting value must be more than the value of program 12.
16
Charger source priority: To configure charger source priority
Solar first
16 050
Solar energy will charge battery as first priority.
Solar and Utility (default)
16 SNU
Solar energy and utility will charge battery at the same time.
Only Solar
16 050
Solar energy will be the only charger source no matter utility is available or not.
If this inverter/charger is working in Battery mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient.
18
Buzzer mode
Mode1
bU2 18 nd I
Buzzer mute
Mode2
bU2 18 nd2
The buzzer sounds when the input source changes or there is a specific warning or fault
Mode3
bU2 18 nd3
The buzzer sounds when there is a specific warning or fault
Mode4(default)
bU2 18 nd4
The buzzer sounds when there is a fault
19
Auto return to default display screen
Return to default display screen (default)
19 ESP
If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute.
Stay at latest screen
19 BEP
If selected, the display screen will stay at the latest screen the user finally switches.
20
Backlight control
Backlight on (default)
20 LON
Backlight off
20 LOF
23
Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode.
Bypass disable
23 bYd
Bypass enable(default)
23 bYE
25
Modbus ID Setting
Modbus ID Setting Range : 001(default)~247
nod 25 001
26
Bulk charging voltage (C.V voltage)
If self-defined is selected in program 5, this program can be set up. But the setting value must be more than or equal the value of program 27. Increment of each click is 0.1V.
12V models: Default 14.1V, setting range is from 12.0V to 15.5V,
24V models: Default 28.2V, setting range is from 24.0V to 30.0V,
48V models: Default 56.4V, setting range is from 48.0V to 62.0V.
27
Floating charging voltage
If self-defined is selected in program 5, this program can be set up.
12V models default setting: 13.5V
Setting range is from 12.0V to the value of program 26
24V models default setting: 27.0V
Setting range is from 24.0V to the value of program 26
48V models default setting: 54.0V
Setting range is from 48.0V to the value of program 26
29
Low DC cut-off voltage
If self-defined is selected in program 5, this program can be set up. The setting value must be less than the value of program 12. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
12V models default setting: 10.5v
Setting range is from 10.0V to 13.5V
24V models default setting: 21.0v
Setting range is from 20.0V to 27.0V
48V models default setting: 42.0V
Setting range is from 40.0V to 54.0V
32
Bulk charging time (C.V stage)
Automatically (Default):
32 AUT
If selected, inverter will judge this charging time automatically.
5 min
32 5
900 min
32 900
The setting range is from 5 min to 900 min. Increment of each click is 5 min.
33
Battery equalization
Battery equalization
33 EEN
Battery equalization disable (default)
33 DIS
If "Flooded" or “User-Defined” is selected in program 05, this program can be set up.
34
Battery equalization voltage
12V models default setting is 14.6V. Setting range is from floating voltage ~ 15.5V. Increment of each click is 0.1V.
24V models default setting is 29.2V. Setting range is from floating voltage ~ 30V. Increment of each click is 0.1V.
48V models default setting is 58.4V. Setting range is from floating voltage ~ 62V. Increment of each click is 0.1V.
35
Battery equalized time
60min (default)
35 60
Setting range is from 0 min to 900 min.
36
Battery equalized timeout
120min (default)
36 120
Setting range is from 0 min to 900 min.
37
Equalization interval
30days (default)
37 30d
Setting range is from 1 to 90 days.
39
Equalization activated immediately
Enable
39 EN
Disable (default)
39 ADS
If equalization function is enabled in program 33, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will shows “E9”. If "Disable" is selected, it will cancel equalization function until the next activated equalization time arrives based on program 37 setting. At this time, “E9” will not be shown in LCD main page.
41
Automatic activation for lithium battery. Note: This function is just available for supporting lithium battery activation models, other models are reserve setting item
ARE Y nNLDisable automatic activation (default)
ARE Y AEO
When the lithium battery is selected in Program 05 and the battery is not detected, the device automatically activates the lithium-ion battery.
If you want to automatically activate the lithium-ion battery, you must restart the device.
42
Manual activation for lithium battery. Note: This function is just available for supporting lithium battery activation models, other models are reserve setting item
nAt Y NOPDefault: disable activationWhen a lithium battery is selected in Program 05 and the battery is not detected, if you want to activate the lithium-ion battery, you can select this option.
nAt Y ACE
46
Maximum discharge current protection
ndC 46 OFFDefault OFF
Disable current discharge current protection function
ndC 46 100Only available in Single model. When utility is available, it turns to utility model and battery discharge stops after the battery discharge current exceeded the setting value. When utility is unavailable, warning occurs and battery discharge lasts after the battery discharge current exceeded the setting value. The setting range is from 20A to 500A.
48
Lithium battery activation time
48 006This feature is used to start (reactivate) a lithium battery that is completely discharged and unresponsive. In some cases, the battery needs a short activation pulse before it can start charging normally - this is what this option provides. You can set how long this pulse should last from 6 to 300 seconds. The default setting is 6 seconds, which is usually enough for most situations. The value can be increased if the device is unable to wake up the battery at the default time.

Battery Equalization

The equalization function is added to the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.

How to Apply Equalization Function

You must enable the battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function by either one of the following methods:

  1. Setting equalization interval in program 37.
  2. Active equalization immediately in program 39.

When to Equalize

In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.

Diagrams illustrate the charging stages: BULK, ABSORPTION, FLOAT, and EQUALIZE, showing voltage and time relationships.

In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage rises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived.

However, in the Equalize stage, when the battery equalized time is expired and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

Setting for Lithium Battery

Setting for lithium battery without communication

This suggestion is used for lithium battery application and to avoid lithium battery BMS protection without communication. Please finish the setting as follows:

  1. Before starting setting, you must get the battery BMS specification:
    A. Max charging voltage
    B. Max charging current
    C. Discharging protection voltage
  2. Set battery type as "LIB"
Battery Type Settings
ProgramBattery TypeDescription
05
Battery type
AGM (default)
05 AGM
User-Defined
05 USE
If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
Lithium battery without communication
05 Li b
If “LIB” is selected, the battery default value is fit for lithium battery without communication battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
  1. Set C.V voltage as Max charging voltage of BMS-0.5V.
  2. Set floating charging voltage as C.V voltage.
  3. Set Low DC cut-off voltage ≥ discharging protection voltage of BMS+2V.
  4. Set Max charging current which must be less than the Max charging current of BMS.
  5. Setting voltage point back to utility source when selecting “SBU priority” or “Solar first” in program 01. The setting value must be ≥ Low DC cut-off voltage+1V, or else the inverter will have a warning as battery voltage low.

Remark:
1. It's better to finish setting without turning on the inverter (just let the LCD show, no output).
2. When you finish setting, please restart the inverter.

Fault Reference Code

Fault CodeFault EventIcon on
01Over temperature of inverter module01- ERROR
02Over temperature of DCDC module02- ERROR
03Battery voltage is too high03- ERROR
04Over temperature of PV module04- ERROR
05Output short circuited.05- ERROR
06Output voltage is too high.06- ERROR
07Overload time out07- ERROR
08Bus voltage is too high08- ERROR
09Bus soft start failed09- ERROR
10PV over current10- ERROR
11PV over voltage11- ERROR
12DCDC over current12- ERROR
13Over current or surge13- ERROR
14Bus voltage is too low14- ERROR
15Inverter failed (Self-checking)15- ERROR
18Op current offset is too high18- ERROR
19Inverter current offset is too high19- ERROR
20DC/DC current offset is too high20- ERROR
21PV current offset is too high21- ERROR
22Output voltage is too low22- ERROR
23Inverter negative power23- ERROR

Warning Indicator

Warning CodeWarning EventAudible AlarmIcon flashing
02Temperature is too HighBeep three times every second02^
04Low batteryBeep once every second04^
07OverloadBeep once every 0.5 second07^ OVER LOAD
10Output power deratingBeep twice every 3 seconds10^
14Fan blockedNone14^
15PV energy is lowBeep twice every 3 seconds15^
19Lithium Battery communication is failedBeep once every 0.5 second19^
21Lithium Battery over currentNone21^
E9Battery equalizationNoneE9^
bPBattery is not connectedNonebP^

Specifications

Table 1 Line Mode Specifications


File Info : application/pdf, 28 Pages, 3.71MB

INVERTER MODEL1.5KW1.5KW2.5KW3.5KW5.5KW
Input Voltage WaveformSinusoidal (Utility or Generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS)
90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS);
100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionBattery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, Battery full charged )
Transfer Time10ms typical (UPS);
20ms typical (Appliances)
Output power derating:
When AC input voltage drops to 95V or 170V depending on models, the output power will be derated.

PDF preview unavailable. Download the PDF instead.

en-instrukcja-obslugi-inwerter-sinus-pro-ultra-plus-3000 2025-07-01

References

Corel PDF Engine Version 26.0.0.101 CorelDRAW 2025

Related Documents

PreviewInstrukcja Obsługi: Volt Polska Sinus Pro Ultra Plus 3000 12/230V Solar Inverter
Kompleksowa instrukcja obsługi dla inwertera solarnego Volt Polska Sinus Pro Ultra Plus 3000 12/230V. Dowiedz się o instalacji, funkcjach, specyfikacjach i rozwiązywaniu problemów dla efektywnego wykorzystania energii słonecznej.
PreviewVolt Polska SINUS PRO ULTRA-M 6500 Solar Inverter Product Manual
Comprehensive product manual for the Volt Polska SINUS PRO ULTRA-M 6500 solar inverter, detailing installation, operation, specifications, troubleshooting, and safety guidelines. Includes information on AC, DC, and PV connections, LCD settings, fault codes, and backup time tables.
PreviewVOLT GREEN BOOST PRO 4000 SINUS BYPASS Solar Inverter Product Manual
This product manual provides essential information on the VOLT GREEN BOOST PRO 4000 SINUS BYPASS solar inverter, covering its application in heating systems, key features like pure sine wave output and bypass functionality, operating principles, technical specifications, installation guidelines, and critical safety precautions. It details operating modes (STABLE and MPPT), connection procedures, and indicator explanations for efficient and safe use.
PreviewVolt Polska Sinus Pro Ultra-HV 6000/11000 Solar Inverter Product Manual
Comprehensive product manual for the Volt Polska Sinus Pro Ultra-HV 6000 and 11000 solar inverters. This guide covers installation, operation, specifications, and troubleshooting for these multi-function inverter/chargers.
PreviewVolt Polska Green Boost Pro 4000 Sinus Bypass Product Manual
Comprehensive product manual for the Volt Polska Green Boost Pro 4000 Sinus Bypass solar inverter, detailing its application, features, operating principles, installation, safety precautions, and technical specifications for efficient solar energy utilization in heating systems.
PreviewVOLT POLSKA SOL MPPT Solar Charge Controller Manual (10A/20A/30A)
Comprehensive user manual for the VOLT POLSKA SOL MPPT solar charge controller, covering installation, operation, technical specifications, safety instructions, and troubleshooting for 10A, 20A, and 30A models. Learn how to optimize your solar energy system with MPPT technology.
PreviewVolt Polska Sinus PRO E PLUS Pure Sine Wave Inverter/UPS User Manual
Comprehensive user manual for Volt Polska's Sinus PRO E PLUS series of pure sine wave inverters and UPS systems, covering product features, safety precautions, operation, technical specifications, and warranty information for models like the 900 E PLUS and 1200 E PLUS.
PreviewVOLT POLSKA SOL MPPT 10A Bluetooth Solar Charge Controller Manual
User manual for the VOLT POLSKA SOL MPPT 10A Bluetooth solar charge controller, detailing its functions, installation, operation, safety features, and technical specifications.