Metasys Integrator Liebert Application Application Note

Johnson Controls, Inc.

lntroduction 3 Cable Connections 15 Metasys Integrator ...

Application Note Issue Date May 25, 2004 Metasys Integrator Liebert Application lntroduction 3 Application Details 3 Component Requirements 10

PDF preview unavailable. Download the PDF instead.

6295370
Application Note Issue Date

May 25, 2004

Metasys Integrator® Liebert® Application

lntroduction

3

Application Details

3

Component Requirements

10

Vendor Contact Information

12

Design Considerations

13

Cable Connections

15

Cable Pinouts

15

Connecting to SiteLink/NIC Modules

17

Connecting the Cable

19

Metasys Integrator Unit Setup

21

Point Mapping Tables

26

Deluxe System/3 (MCCI Configuration)

26

Small Systems Controller (MCCI Configuration)

28

Liebert ECA2 Level 0

29

Liebert ECA2 Level 10 and Level 15

30

Liebert DCLAN Environmental Unit Level 0 and Level 0 with On/Off Control

(L00, L0A, and LSM)

31

Liebert DCLAN Environmental Unit Small Systems Control (L0B)

32

Liebert DCLAN Environmental Unit Level 2, 3, 10, and 15 (L02, L03, L10,

L1A, and LAM)

32

Liebert DCLAN Chiller - CW1, CW2, and CW3

34

Liebert DCLAN Chiller with Econocoil - CE1, CE2, and CE3

35

Liebert DCLAN Power Conditioning Unit

36

Liebert DCLAN UPS Series 300 and 600

37

Liebert DCLAN Series 600 Static Control Cabinet (SCC)

38

Liebert DCLAN Contact Closure Module (CCM)

39

Liebert SiteLink/NIC CCM Function Block

40

© 2004 Johnson Controls, Inc. Code No. LIT-6295370

1
www.johnsoncontrols.com

Liebert SiteLink/NIC CSE Function Block

41

Liebert SiteLink/NIC CSU Function Block

42

Liebert SiteLink/NIC EDS Function Block

43

Liebert SiteLink/NIC L00 Function Block

45

Liebert SiteLink/NIC L0B Function Block

46

Liebert SiteLink/NIC L10 Function Block

47

Liebert SiteLink/NIC LAM and MM2 Function Blocks

49

Liebert SiteLink/NIC LSM Function Block

51

Liebert SiteLink/NIC MM4 Function Block

52

Liebert SiteLink/NIC MMS Function Block

54

Liebert SiteLink/NIC NPower IMP Function Block

55

Liebert SiteLink/NIC PMP Function Block

57

Liebert SiteLink/NIC RAC Function Block

58

Liebert SiteLink/NIC SC4 Function Block

59

Liebert SiteLink/NIC SCC Function Block

61

Liebert SiteLink/NIC SM3 Function Block

62

Liebert SiteLink/NIC SM4 Function Block

63

Liebert SiteLink/NIC SMS Function Block

65

Liebert SiteLink/NIC THM Function Block

66

Liebert SiteLink/NIC VCF Function Block

67

Liebert SiteLink/NIC VCM Function Block

68

Liebert SiteLink/NIC WDU Function Block

69

Metasys Network Setup

70

Mapping to a CS Object

70

Custom Integration

74

2 Metasys Integrator Liebert Application Application Note

lntroduction

Application Details

This document explains Metasys Integrator® Liebert® applications. Use this document with the Metasys Integrator unit technical bulletins on the Johnson Controls® Product Information site (http://cgproducts.johnsoncontrols.com System Manuals > Integration > Metasys Integrator), which provide information on installing and commissioning the Metasys Integrator unit. For information on Liebert equipment, see Liebert documentation (obtainable from a Liebert representative).
Note: If you are using a Universal Packaging Module (UPM) enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures for this application note.
The Metasys Integrator unit allows Liebert equipment to become an integral part of the Metasys® and Metasys Companion Networks. After a Liebert Multi-Channel Communications Interface (MCCI), Environmental Communication Adapter (ECA2), DCLAN BMS, SiteLinkTM Module, or Open Comms Network Interface Card (NIC) is connected to a Metasys or Companion Network via the Metasys Integrator unit, each of its Information Gathering Modules (IGMs) has access to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, alarm notification, trend, and totalization.
IGMs maintain Liebert environmental systems to provide precise control of temperature, humidity, filtration, and distribution for heat generating equipment.
The Metasys Integrator unit supports applications for many, but not all, SiteLink function blocks. With a Liebert SiteLink module configured for Modbus RTU protocol and downloaded with the appropriate SiteLink function block, the Metasys Integrator unit can communicate with most Liebert products.
Liebert equipment equipped with a Liebert OpenComms Network Interface Card use the SiteLink vendor tables.

IMPORTANT:

For a complete list of products, controllers, and function blocks, see the Liebert Web site (www.liebert.com).

Metasys Integrator Liebert Application Application Note 3

You must verify that the product you want to integrate uses a function block that is listed in this document. Table 1 lists examples of products that are supported by the Metasys Integrator unit.

Table 1: Liebert SiteLink Products Supported by Metasys Integrator Unit

Product Names

Controller Name or Identification

Environmental Products

CSU3000

Chiller

CSU3000 with Econocoil®

Chiller with Econocoil

Deluxe SystemTM 3

Level 0

Levels 3, 10

Levels 15, Advanced Microprocessor, Advanced with Graphics

Levels 0 with On/Off Control, and Standard Microprocessor

Challenger 3

Level 0

Challenger 3000

Standard Microprocessor

Advanced Microprocessor, Advanced with Graphics

DataMate

Small System Controller

Industrial Cooling Series

Standard Microprocessor, Advanced Microprocessor

Level 10

LogicoolTM

Level 0

Mini-Mate

Small System Controller

Mini-Mate 2

MM2

Mini-Mate Plus

Small System Controller

Modular Plus

Level 1

Level 10

Liebert Monitoring Modules

LDS750 and LDS1000 Water Detection LDS750 and LDS1000

RAC2-8 Autochangeover

RAC2-8

CCM200 Contact Closure Module

CCM200

VSM100 Voltage Sensing Module

VSM100

CSM100 Current Sensing Module

CSM100

Temperature/Humidity Module

THM100

RCM8 Contact Closure Module

RCM8

Continued on next page . . .

4 Metasys Integrator Liebert Application Application Note

Product Names (Cont.)

Controller Name or Identification

Power Products

Static Transfer Switch PDU

Single Output Breaker, Prior to 1/99

Datawave®

Power Monitoring Panel

Voltage Current Frequency Monitoring Panel

Precision Power Center

Power Monitoring Panel

Voltage Current Monitoring Panel

MPU4000

Voltage Current Frequency Monitoring Panel

AP301/302 Single Module UPS

SM3

Early Series 300/500/600 Single Module SMS UPS

Early Series 500/600 System Control Cabinet

SCC

Early Series 500/600 Multi-Module UPS MMS

Series 600 Single Module UPS with Extended Protocol

SM4

Series 600 Multi-Module UPS with Extended Protocol

MM4

Series 600 System Control Cabinet

SC4

with Extended Protocol

Npower® Single Module UPS

IMP

Metasys Integrator Liebert Application Application Note 5

With the Liebert MCCI, the Metasys Integrator unit supports seven Liebert IGMs:

· Deluxe System 3/Level 0

· Deluxe System 3/Level 1

· Deluxe System 3/Level 2

· Deluxe System 3/Level 3

· Deluxe System 3/Level 10

· Deluxe System 3/Level 15

· Small Systems Controller (SSC)

With the Liebert ECA2, the Metasys Integrator unit supports three IGMs:

· Deluxe System 3/Level 0

· Deluxe System 3/Level 10

· Deluxe System 3/Level 15

With Liebert DCLAN, the Metasys Integrator unit communicates with the following devices:

· Environmental Unit Level 0 · Power Conditioning Unit Type

and Level 0 with On/Off

PMP with IGM, VCMP with

Control (L00, L0A, and LSM) IGM

· Environmental Unit Small Systems Control (L0B)
· Environmental Unit Level 2, 3, 10, and 15 (L02, L03, L10, L1A, and LAM)
· Chiller (CW1, CW2, and CW3)

· UPS Series 300* and 600-Type Single Module System (SMS), Multi Module System (MMS), and Static Control Cabinet (SCC)
· Contact Closure Module (CCM)
· Chiller with Econocoil (CE1, CE2, and CE3)

*Series 300 with optional SiteScan® Interface Card.

The MCCI or ECA2 connects to the Metasys Integrator unit through the RS-232 Bus. Once connected, it is the interface between Liebert equipment and non Liebert devices (such as the Metasys Integrator unit). The Metasys Integrator unit allows status information and commands to be transmitted between the Liebert devices and the Metasys or Companion Network.

Each Metasys Integrator vendor port can connect to one MCCI or ECA2. Each MCCI can connect up to 24 Liebert IGMs on 24 individual RS-422 lines. Each ECA2 can connect to two Liebert IGMs on two individual RS-422 lines.

6 Metasys Integrator Liebert Application Application Note

The Liebert DC100 can be used in place of the MCCI. The DC100 must be configured to use the MCCI protocol on Port 2, using SS25 software Version 1.05B or later. (The DC100 and MCCI are no longer available from Liebert.) The DCLAN BMS protocol can be used as an interface to monitor and control Environmental Units, chillers, power conditioning units, Uninterruptible Power Supplies (UPSs), and Contact Closure Modules. Liebert SiteLink modules provide a communication link between third-party Modbus devices and Liebert manufactured devices. The Liebert SiteLink-DC12i module has 12 ports. Each port may be connected to a Liebert device. A SiteLink-DC4i module has 4 ports. The OpenComms Network Interface Card has one port and is connected to one Liebert device. The SiteLink module (via downloaded Function Blocks) polls each device connected to it and stores the information in registers that a Modbus device can access. SiteLink modules can also be configured to communicate via DCLAN BMS protocol. Liebert OpenComms Network Interface Cards communicate with Modbus devices via their third-party interface port (2-wire RS-485). This port is connected via an RS-485 converter to a vendor port on the Metasys Integrator unit. Modbus RTU protocol (9600, N, 8, 1 standard) is used for communication with the OpenComms NIC. Figure 1 shows a Metasys Network with the Metasys Integrator unit connected to one MCCI in a star configuration. Figure 2 shows a Metasys Network with a Metasys Integrator unit connected to one DCLAN BMS, which can be connected to 12 control modules such as DC12-422 and DC12-485. For more information about DCLAN configurations, see Configuration Guide-Intermediate by Liebert Corporation. Figure 3 and Figure 4 show Metasys Companion and Liebert integration.
Metasys Integrator Liebert Application Application Note 7

N1 LAN

Standard NCU

RS-232 (50 ft maximum)
Metasys Integrator

MCCI with 24 RS-422
Ports

RS-422 (Belden Cable 3280 ft maximum)

Del ux e Sys tem/3

Del ux e Sys tem/3

Del ux e Sys tem/3

Del ux e Sys tem/3

Del ux e Sys tem/3

UNT N2 Bus

Deluxe System/3

Small System Controller

liebert1

Note: If you use a UPM enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures for this application note.

Figure 1: Liebert and Metasys System Integration

NCM300

Liebert

RS-232 SiteLink

:

DC12I

(50 ft maximum) (or DC4I)

:

Liebert Device 1
Liebert Device 2 : :

UNT N2 Bus

Metasys Integrator
(30 ft maximum) RS-232

DCLAN

Liebert

Liebert Device 12
Liebert DC12, DC4, DC12i, or DC4i

Note:

liebert8
If you use a UPM enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note.

Figure 2: Liebert DCLAN BMS and Metasys System Integration

8 Metasys Integrator Liebert Application Application Note

Panel Unit

Workstation

RS-232 (50 ft maximum)

um p
Metasys Integrator

MCCI with 24 RS-422
Ports

RS-422 (Belden Cable 3280 ft maximum)

Del ux e Sys tem/3

Del ux e Sys tem/3

Del ux e Sys tem/3

Del ux e Sys tem/3

Del ux e Sys tem/3

UNT

N2 Bus

Deluxe System/3

Small System Controller

Note:

Note: A PC version and converter may be substituted for the Panel unit.
liebcomp
If you use a UPM enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note.

Figure 3: Liebert MCCI and Metasys Companion Integration

Panel Unit

Workstation

RS-232 (50 ft maximum)

um p
Metasys Integrator

ECA2
Del ux e Sys tem/3

RS-422 (Belden Cable 3280 ft maximum)
Del ux e Sys tem/3

UNT

Note:

N2 Bus

Deluxe System/3

Note: A PC version and converter may be substituted for the Panel unit.

liebcom2
If you use a UPM enclosure, you must install the Metasys Integrator unit 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note.

Figure 4: Liebert ECA2 and Metasys Companion Integration

Metasys Integrator Liebert Application Application Note 9

Component Requirements

To integrate Liebert equipment, you need the following components:
· properly installed Liebert devices
· RS-232 cable (for connecting the MCCI, ECA2, DCLAN, or SiteLink module to the Metasys Integrator unit)
Note: If connecting a single Metasys Integrator unit to multiple SiteLink modules via the Modbus RTU protocol interface (that is standalone SiteLink modules that are not part of a DCLAN Network), additional RS-232 cables, RS-485 cables, and RS-485/232 converters are needed. See Cable Connections in this document for more information. Connection to one or more OpenComms Network Interface Cards also require a RS-485/232 Converter.
· Metasys Integrator unit
· N2 Bus (for connecting the Metasys Integrator unit to the Metasys or Companion Network)
· portable Personal Computer (PC) for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit and for running diagnostics
· cable for connecting portable PC to the Metasys Integrator unit
· the correct vendor communication table (.VCT file) to download into the Metasys Integrator unit (supplied on Metasys Integrator CD-ROM)
This document describes the RS-232 cable and the vendor communication tables. Liebert documentation describes its equipment. The remaining components are described in the Metasys Integrator unit technical on the Johnson Controls Product Information site (http://cgproducts.johnsoncontrols.com System Manuals > Integration > Metasys Integrator).

Metasys Release Requirements

To integrate Liebert equipment into the Metasys Network, you need: · Metasys Operator Workstation (OWS) software Release 6.0 or later · Metasys Integrator unit software/firmware Release 9.3 or later

Metasys Companion Release Requirements

To integrate Liebert equipment into the Metasys Companion Network, you need:
· Metasys Companion Release 5.0 or later
· Metasys Integrator unit software/firmware Release 9.3 or later

10 Metasys Integrator Liebert Application Application Note

Vendor Component Requirements

Integration between the Metasys Integrator unit and Liebert has been tested with the equipment listed in Table 2. Changes to this equipment or integration of Liebert products not discussed in this document requires additional software development and testing by Systems Products. For information on integrating other products, refer to the Custom Integration section of this document.

Table 2: Liebert Part and Software Version Numbers

Liebert Product

Part Number

Firmware Version Number

Multi-Channel Communications 129443G1 Interface

Revision 2.08

DC100

DC100BMS

MCCI Card, Revision 2.08

Deluxe System 3/Level 0

N/A**

Lev0 or Lev0A

Deluxe System 3/Level 1*

N/A**

Lev1

Deluxe System 3/Level 2

N/A**

Lev2 or Lev2A

Deluxe System 3/Level 3

N/A**

Lev2 or Lev2A

Deluxe System 3/Level 10

N/A**

Lev2 or Lev2A

Deluxe System 3/Level 15

N/A**

Lev2A

Single Module NPower UPS

N/A***

N/A

Small Systems Controller

N/A**

Lev0B

Environmental Communication 4D14081G1

1

Adapter (ECA2)

DCLAN BMS Data Concentrator DCLAN BMS for Local Area Network (LAN)

Revision 2.0

DC1 IGM Interface Module

DC1

--

DC4-422 IGM Interface Module DC4-422

N/A

DC12-422 IGM Interface Module DC12-422

N/A

SiteLink DC4i-422 IGM Interface SiteLink-DC4i

N/A

Module

SiteLink DC12i-422 IGM Interface SiteLink-DC12i N/A Module

OpenComms Network Interface OpenComms NIC N/A Card

REPOPT RS-485/232 Converter REPOPT

N/A

* The System 3/Level 1 IGM requires a Liebert Retrofit Kit with a Liebert Protocol Converter (Part Number KIT-0101).

** Part number varies according to the system in which the System/3 controller is mounted.

*** Requires an OpenComms NIC or SiteScan® Optional Module.

Metasys Integrator Liebert Application Application Note 11

DCLAN
The DCLAN BMS database is factory configured by Liebert. Only databases configured by a Liebert factory are supported. Obtain the following information from the Liebert representative:
· the address of each DCLAN BMS, which is configured with units to be monitored by the Metasys Integrator unit
· the DCLAN BMS database address of each unit, which includes the unit type (for example: DCLAN BMS Addresses 101 and 102 configured for an environmental unit type LAM)
Note: Every CMnet device uses two sequential DCLAN addresses. Liebert supports a maximum of fifty devices per DCLAN BMS.
To use SiteLink modules within a DCLAN system, the Liebert representative must configure SiteLink modules for DCLAN communication. DCLAN DC4 and DC12 drivers must be Version 4.7 or later.

SiteLink/OpenComms NIC
The Liebert representative must supply a Liebert Site Survey, which indicates which function blocks (for example, L00, PMP, EDS, etc.) are involved in the integration. The function blocks correspond to the three-character acronym associated with the name of each Metasys Integrator unit application for Liebert SiteLink.
To communicate directly to SiteLink/NIC modules, the Liebert representative must configure each SiteLink/NIC module to communicate via Modbus RTU protocol. The representative must also supply the Modbus address and port numbers for each Liebert device.

Vendor Contact Information

Liebert P.O. Box 29186 1050 Dearborn Drive Columbus, OH 43085
www.liebert.com
Site Application Engineering: Phone: 800-222-5877

12 Metasys Integrator Liebert Application Application Note

Design Considerations

When integrating Liebert equipment, consider the following:
· Make sure all Liebert equipment is set up, started, and running properly before attempting to integrate with the Metasys or Companion Network. (The Liebert representative is responsible for operation of Liebert equipment.)

MCCI/ECA2

· If an environmental unit is commanded off at the local controller, it cannot be turned on remotely.
· The MCCI/ECA2 baud rate is fixed at 9600 baud.
· The RS-232 port jumper settings on the MCCI should be set to DCE. (The Liebert representative is responsible for setting jumper settings on the MCCI.)
Note: The DCE jumper pins are on the lower MCCI board and are labeled DTE/DCE.
· Cable distance between the master MCCI or ECA2 and the last IGM can be a maximum of 3280 feet. (The Liebert representative is responsible for proper configuration of Liebert equipment.)
· Set the DIP switches on SW1 of the ECA2 as follows: 1=On, 2=On, 3=Off, 4=On, 5 (not used), 6=Off, 7=Off, 8=Off. Set SW2 on the ECA2 to Terminal.

DCLAN

· Liebert representatives must configure the DCLAN Network correctly.
· The DCLAN BMS must be configured so that echo is off.
· The default baud rate for the Metasys Integrator unit connection to a DCLAN Network is 9600 baud.

SiteLink Module/ OpenComms NIC

· Liebert representatives must configure each SiteLink/NIC module correctly. If the SiteLink module is directly connected to the Metasys Integrator unit, it must be downloaded with the function blocks and module drivers configured for Modbus. If connected to a DCLAN, it must be downloaded with the function blocks and module drivers configured for DCLAN.
· OpenComms NIC modules must be configured for Modbus RTU communication and a unique Modbus Subordinate Address assigned.
· The default baud rate for the Metasys Integrator unit connection to a SiteLink/NIC module is 9600 baud. The SiteLink module can also be configured for 38400 baud.
· If the SiteLink module supports automatic alarm reset, the auto-restore timer must be set as shown in Table 3 to ensure all hardware-latched alarms are reported.

Metasys Integrator Liebert Application Application Note 13

Table 3: SiteLink Auto-Restore Timer Settings

Number of SiteLink Modules Number of Minutes Number of Minutes

Connected to One Metasys Needed for SiteLink Needed for DCLAN

Integrator Port

Configuration

Configuration

1

1

2

2 to 6

2

4

7 to 10*

3

6

* We do not recommend more than 10 modules be connected to one port because of performance considerations.

· The Liebert representative is responsible for configuring the SiteLink module for setpoints and unit on/off control. If a SiteScan system is connected to the SiteLink module along with the Metasys Integrator unit, only one system is allowed to update setpoints (Analog Outputs [AOs]) and the unit on/off control.

14 Metasys Integrator Liebert Application Application Note

Cable Connections

Cable Pinouts
MCCI
ECA2

Use the following cable pinouts for the RS-232 connection between the Metasys Integrator unit and the Liebert MCCI:

Vendor Port A or B on Metasys Integrator

RS-232 Port MCCI
(set to DCE)

DB-9 Female

Signal Pin

RD

2

TD

3

DTR 4

GND 5

RTS 7

CTS 8

RS-232 (50 ft maximum)

DB-25 Male
Pin Signal
3 RD 2 TD 20 DTR 7 GND 4 RTS 5 CTS
liebert2

Figure 5: Cable Pinouts (MCCI)

Use the following cable pinouts for the RS-232 connection between the Metasys Integrator unit and the Liebert ECA2:

Vendor Port A or B on Metasys Integrator

RS-232 Port ECA2

DB-9 Female

Signal Pin

RD

2

TD

3

RTS 7

CTS 8

GND 5

RS-232 (50 ft maximum)

DB-25 Female
Pin Signal
2 TD 3 RD 5 CTS 4 RTS 7 GND
liebert6

Figure 6: Cable Pinouts (ECA2)

Metasys Integrator Liebert Application Application Note 15

DC100 DCLAN

Use the following cable pinouts for the RS-232 connection between the Metasys Integrator unit and the Liebert DC100:

Vendor Port A or B on Metasys Integrator

RS-232 Port DC100 Port 2
(DTE)

DB-9 Female

DB-25 Female

Signal Pin

RD

2

TD

3

DTR 4

GND 5

RTS 7

CTS 8

RS-232 (50 ft maximum)

Pin Signal
2 TD 3 RD 20 DTR 7 GND 4 RTS 5 CTS
liebert5

Figure 7: Cable Pinouts (DC100 Port 2)

Use the following cable pinouts for the RS-232 connection between the Metasys Integrator unit and the Liebert DCLAN Port 1. Use a DB-9 female to DB-9 female null modem to connect the Metasys Integrator unit to the Liebert DCLAN Port 2.

Vendor Port A or B on Metasys Integrator

RS-232 Port 1 DCLAN

DB-9 Female

Signal Pin

DCD 1

RD

2

TD

3

DTR 4

GND 5

RS-232 (50 ft maximum)

DB-25 Female
Pin Signal
8 DCD 2 TD 3 RD 20 DTR 7 GND
liebert7

Figure 8: Cable Pinouts (DCLAN)

16 Metasys Integrator Liebert Application Application Note

Connecting to SiteLink/NIC Modules
Direct RS-232 Connection
RS-485 Connection

Use the following cable pinout for the RS-232 connection between the Metasys Integrator unit and a single Liebert SiteLink module:

Vendor Port A or B on Metasys Integrator

RS-232 Port on SiteLink (DTE)

DB-9 Female

DB-9 Female

Signal Pin

RD

2

TD

3

GND 5

P2 or P3 on Panel

RS-232 (50 ft maximum)

Pin Signal
3 2 RD 5 GND Third Party Interface Port
Liebert9

Figure 9: Cable Pinouts for Single SiteLink Module

Use Figures 10 through 12 to wire multiple SiteLink/OpenComms NIC modules using Liebert REPOPT RS-232 to RS-485 Converters:

Vendor Port A or B on Metasys Integrator

Liebert REPOPT RS-232 to RS-485
Converter

DB-9 Female

DB-9 Female

Signal Pin

RD

2

TD

3

GND 5

P2 or P3 on Panel

RS-232 (50 ft maximum)

Pin Signal
3 2 RD 5 GND
RS-232 Connector
Lieb11

Figure 10: Cable Pinout for Liebert REPOPT RS-232 to RS-485 Converter

Metasys Integrator Liebert Application Application Note 17

REPOPT RS-232 to RS-485
Converter

RS-485

(4000 ft maximum) RS-485

Daisy-chained REPOPTs

Liebert12
Figure 11: RS-485 Network of REPOPTs

REPOPT RS-232 to RS-485
Converter
DB-9 Female

RS 232 Connector on SiteLink Module
DB-9 Female

Signal Pin

RD

2

TD

3

GND 5

RS-232 Connector on Daisy-chained REPOPT

RS-232 (50 ft maximum)

Pin Signal 3 2 RD 5 GND
Liebert13

Figure 12: Null Modem Cable from Liebert REPOPT to SiteLink Module

18 Metasys Integrator Liebert Application Application Note

Connecting the Cable

Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the other end of the cable to the RS-232 port on the MCCI, DC100, ECA2, DCLAN or SiteLink module.

Metasys Integrator
Vendor Port A or B

RS-232

Liebert MCCI. ECA2, DC100, DCLAN,
or SiteLink
RS-232 Port

Connection to Multiple SiteLink Modules

Liebert3
Figure 13: Port-to-Port Connection

Metasys RS-232 Liebert

Integrator

REPOPT

RS-485

Liebert RS-232 Liebert

REPOPT

SiteLink

Liebert

RS-232 Liebert

REPOPT

SiteLink

Liebert15
Figure 14: Connecting Metasys Integrator Unit to Multiple SiteLink Modules

Metasys Integrator Liebert Application Application Note 19

Connecting Metasys Integrator Unit to OpenComms Network Interface Cards

Metasys Integrator
Unit

RS-232

Liebert REPOPT

RS-485

OpenComms Network
Interface Card

OpenComms Network
Interface Card
Liebert15a
Figure 15: Connecting Metasys Integrator Unit to OpenComms Network Interface Card

20 Metasys Integrator Liebert Application Application Note

Metasys Integrator Unit Setup

To set up the Metasys Integrator unit, use a portable PC connected to Metasys Integrator Terminal Port. Metasys Integrator unit setup involves:
· downloading the correct vendor communication table (.VCT file)
· setting up the ports
· assigning network addresses to the controllers
Tables 4 through 7 provide setup information specific to Liebert applications. For detailed procedures, see the Metasys Integrator unit technical bulletins on the Johnson Controls Product Information site (http://cgproducts.johnsoncontrols.com System Manuals > Integration > Metasys Integrator).

Table 4: Metasys Integrator Unit Setup for Liebert MCCI Applications
Vendor Communication Table (.VCT File)

System 3/Level 0 and 1

LI_LEV0.VCT

System 3/Level 2, 3, 10, and 15

LI_LEV2.VCT

System 3/Level 10 and 15 with On/Off Control

LI_LEV2A.VCT

Small Systems Controller

LI_SSC.VCT

Port Setup

Baud Rate

9600

Word Length

8

Stop Bits

1

Parity

None

Interface

RS-232

Network Setup

Vendor Address

Port Number (1-24)

Timeout Value

4000 ms

Poll Delay

0 ms

Performance Guide

System 3/Environmental Units

8 seconds

Small Systems Controller

8 seconds

Metasys Integrator Liebert Application Application Note 21

Table 5: Metasys Integrator Unit Setup for Liebert ECA2 Applications

Vendor Communication Table (.VCT File)

Environmental Communication Adapter LI_ECA2.VCT (ECA2) Level 0

Environmental Communication Adapter LIECA210.VCT (ECA2) Levels 10 and 15

Port Setup

Baud Rate

9600

Word Length

8

Stop Bits

1

Parity

None

Interface

RS-232

Network Setup

Vendor Address

Channel (1-2)

Timeout Value

4000 ms

Poll Delay

0 ms

Performance Guide

ECA2 Environmental Communication Adapter

8 seconds

22 Metasys Integrator Liebert Application Application Note

Table 6: Metasys Integrator Unit Setup for Liebert DCLAN Applications

Vendor Communication Table (.VCT File)

Environmental Units

Level 00 (L00)

LIDCLL00.VCT

Small Systems Control (L0B)

LIDCLL0B.VCT

Level 02 (L02) and Level 03 (L03)

LIDCLL02.VCT

Level 0 with On/Off Control (L0A) and

Standard Microprocessor (LSM)

LIDCLL0A.VCT

Level 10 without On/Off Control (L10) LIDCLL10.VCT

Level 10 with On/Off Control (L1A) and Level 15 with On/Off Control (LAM) LIDCLL1A.VCT

Chillers

Single Module (CW1)

LIDCLCW1.VCT

Two Module (CW2)

LIDCLCW2.VCT

Three Module (CW3)

LIDCLCW3.VCT

Chillers with Econocoil-Single Module LIDCLCE1.VCT (CE1)

Chillers with Econocoil-Two Module LIDCLCE2.VCT (CE2)

Chillers with Econocoil-Three Module LIDCLCE3.VCT (CE3)

Power Conditioning Units

Power Monitoring Panel (PMP)

LIDCLPMP.VCT

UPS

Series 300 and 600 Single Module System (SMS)

LIDCLSMS.VCT

Series 600 Multi Module System (MMS) LIDCLMMS.VCT

Series 600 Static Control Cabinet (SCC)

LIDCLSCC.VCT

Contact Closure Module (CCM)

LIDCLCCM.VCT

Port Setup

Baud Rate

9600

Word Length

8

Stop Bits

1

Parity

None

Interface

RS-232

Continued on next page . . .

Metasys Integrator Liebert Application Application Note 23

Network Setup (Cont.)

Vendor Address

D,aaa*

where D is:

the address of the DCLAN (`1' - `9', `A' - `Z', or `a' - `y');

where aaa is: the DCLAN configured address (101 - 199); each unit uses two consecutive DCLAN addresses**, only the first address is entered.

For example, to address the first DCLAN device in DCLAN 1, enter 1,101.

Timeout Value

1000 ms

Poll Delay

0 ms

Performance Guide

DCLAN BMS Units

2 seconds

* The comma (,) between D and aaa of the Vendor Address is a required delimiter, which must be included in the vendor address.

** For the latest information on obtaining addressing information, please refer to The Advisor. It may be displayed or printed as needed.

24 Metasys Integrator Liebert Application Application Note

Table 7: Metasys Integrator Unit Setup for Liebert SiteLink/NIC Applications

Vendor Communication Table (.VCT)

CCM Function Block

LiSL_CCM.VCT

CSE Function Block

LiSL_CSE.VCT

CSU Function Block

LiSL_CSU.VCT

EDS Function Block IMP Function Block

LiSL_EDS.VCT LiSL_IMP.VCT

L00 Function Block L0B Function Block L10 Function Block LAM Function Block LSM Function Block MM4 Function Block MMS Function Block PMP Function Block RAC Function Block SC4 Function Block SCC Function Block SM3 Function Block SM4 Function Block SMS Function Block THM Function Block VCF Function Block VCM Function Block WDU Function Block

LiSL_L00.VCT LiSL_L0B.VCT LiSL_L10.VCT LiSL_LAM.VCT LiSL_LSM.VCT LiSL_MM4.VCT LiSL_MMS.VCT LiSL_PMP.VCT LiSL_RAC.VCT LiSL_SC4.VCT LiSL_SCC.VCT LiSL_SM3.VCT LiSL_SM4.VCT LiSL_SMS.VCT LiSL_THM.VCT LiSL_VCF.VCT LiSL_VCM.VCT LiSL_WDU.VCT

Port Configuration

Baud Rate

9600 (38400 also can be used if the SiteLink module is configured for it.)

Word Length

8

Stop Bits

1

Parity

None

Interface

RS-232

Network Configuration

Vendor Address

<Modbus Address>, <Port #> (for example, 3, 12)

SiteLink Modbus Address 1-255, Port 1-12

NIC Modbus Address 1-255, Port 1

For example: If the SiteLink Modbus address is 3, and the IGM is connected to Port 12, enter 3,12. If NIC Modbus address is 4, enter 4, 1

Note: <Modbus Address> defaults to 3.

Timeout Value

500 ms

Poll Delay

50 ms

Retries

3

Approximate Scan Time (for a single Metasys Integrator device)

SiteLink/NIC Modbus

1 second

Metasys Integrator Liebert Application Application Note 25

Point Mapping Tables

Deluxe System/3 (MCCI Configuration)
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Percent Heating point is AI3.

Use the following point mapping tables to map Metasys objects to the Liebert Deluxe System/3 IGMs. Table 8 applies to System/3 Levels 0, 1, 2, 3, 10, and 15.

Table 8: Deluxe System/3 (MCCI Configuration)
NPT1 NPA2 Unit Description

AI

1

DegF Temperature

AI

2

%RH Humidity

AI

3

AI

4

AI

5

AI

6

% Step % Step

Percent Heating Stages Heating Percent Cooling Stages Cooling

AO

1

DegF Temperature Setpoint (40 to 85)

AO

2

DegF Temperature Tolerance (1 to 5)

AO

3

AO

4

%RH Humidity Setpoint (40 to 60) %RH Humidity Tolerance (1 to 10)

BI

1

Cooling

0-Heat, 1-Cool

BI

2

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI 22
BI 23
BI 24

Glycol Humidifying Dehumidifying High Head Pressure Compressor 1 High Head Pressure Compressor 2 Loss of Airflow Standby Glycol Pump On Water Under Floor Change Filters High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm High Water in Humidifier Pan No Water in Humidifier Pan Compressor #1 Overload Compressor #2 Overload Main Fan Overload Manual Override Smoke Detected Loss of Water Flow Standby Unit On Low Suction Pressure

0-Off, 1-On 0-Off, 1-On 0-Off, 1-On 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm

1 Network Point Type

2 Network Point Address

Continued on next page . . .

26 Metasys Integrator Liebert Application Application Note

NPT1 NPA2 Unit Description (Cont.)

BI

25

Short Cycle Alarm

0-Normal, 1-Alarm

BI

26

Loss of Power Alarm

0-Normal, 1-Alarm

BI

27

Local Alarm 1

0-Normal, 1-Alarm

BI

28

BI

29

BI

30

BI

31

BO

1

BO

2

BD

1

BD

2

Local Alarm 2
User Alarm 1
User Alarm 2
Alarm Condition Exists Reset All Alarms3 Unit Mode4 Unit Start Status4 Local Command Status4

0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-Normal, 1-Alarm 0-N/A, 1-Reset 0-Off, 1-On 0-Off, 1-On 0-Off, 1-On

1 Network Point Type

2 Network Point Address

3 The Reset All Alarms command has no effect on the System/3 Level 10. If you want to reset alarms on the Level 10, reset them directly on the System/3 controller panel. Do not map these points to Companion Binary Output (BO) points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object's Definition and Focus window is disabled.

4 Available only on units that include start/stop control.

Metasys Integrator Liebert Application Application Note 27

Small Systems Controller (MCCI Configuration)
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Percent Heating point is AI3.

Table 9: Small Systems Controller (MCCI Configuration)
NPT1 NPA2 Unit Description

AI

1

DegF Temperature

AI

2

%RH Humidity

AI

3

%

Percent Heating

AI

4

AI

5

AI

6

Step % Step

Stages Heating Percent Cooling Stages Cooling

BI

1

Coolon

0-Heat,

1-Cool

BI

2

Glyavail

0-Off,

1-On

BI

3

Humidifying

0-Off,

1-On

BI

4

Dehumidifying

0-Off,

1-On

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI

22

BI

23

BI

24

BI

BI

25

BI

26

BI

27

BI

28

BI

29

BI

30

31

BO

1

High Head Pressure Compressor 1 High Head Pressure Compressor 2 Loss Of Airflow Standby Glycol Pump On Water Under Floor Change Filters High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm High Water In Humidifier Pan No Water In Humidifier Pan Compressor 1 Overload Compressor 2 Overload Main Fan Overload Manual Override Smoke Detected Loss Of Water Flow Standby Unit On Low Suction Pressure Short Cycle Alarm Loss Of Power Alarm Local Alarm 1 Local Alarm 2 User Alarm 1 User Alarm 2 Alarm Condition Exists Reset Alarms3

0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-Normal, 0-N/A,

1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Reset

1 Network Point Type

2 Network Point Address

3 Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object's Definition and Focus window is disabled.

28 Metasys Integrator Liebert Application Application Note

Liebert ECA2 Level 0
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity Reading point is AI2.

Table 10: Liebert ECA2 Level 0
NPT1 NPA2 Unit Description

AI

1

DegF Temperature Reading

AI

2

% RH Humidity Reading

AI

3

AI

4

% Step

Percent Heating/Cooling Stages Heating/Cooling

AO 1

DegF Temperature Setpoint

40-85

AO 2

DegF Temperature Sensitivity

1-5

AO 3 AO 4

% RH Humidity Setpoint % RH Humidity Sensitivity

40-60 1-10

BI

1

Cooling

0-Heat, 1-Cool

BI

2

Glycol

0-Off, 1-On

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI 21
BI 22
BI 23
BI 24
BI

BI

25

BI

26

27

BO 1

Humidifying Dehumidifying High Head Pressure Compressor 1 High Head Pressure Compressor 2 Loss Of Airflow Standby Glycol Pump On Water Under Floor Change Filters High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm High Water In Humidifier Pan No Water In Humidifier Pan Compressor 1 Overload Compressor 2 Overload Main Fan Overload Manual Override On Smoke Detected Loss Of Water Flow Standby Unit On Low Suction Pressure Short Cycle Alarm Loss Of Power Alarm Alarm Present Reset All Alarms3

0-Off, 0-Off, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-N/A,

1-On 1-On 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Reset

BO 2

Unit Mode

0-Off, 1-On

1 Network Point Type

2 Network Point Address

3 Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object's Definition and Focus window is disabled.

Metasys Integrator Liebert Application Application Note 29

Liebert ECA2 Level 10 and Level 15
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity Reading point is AI2.

Table 11: Liebert ECA2 Level 10 and Level 15
NPT1 NPA2 Unit Description

AI

1

DegF Temperature Reading

AI

2

%RH Humidity Reading

AI

3

%

Percent Heating/Cooling

AI

4

Step Stages Heating/Cooling

AI

5

Hours Compressor 1 Run Hours

AI

6

Hours Compressor 2 Run Hours

AI

7

Hours Glycol Hours

AO

1

DegF Temperature Setpoint

AO

2

DegF Temperature Sensitivity

AO

3

%RH Humidity Setpoint

AO

4

%RH Humidity Sensitivity

AO

5

DegF High Temperature Alarm Setpoint

AO

6

DegF Low Temperature Alarm Setpoint

AO

7

%RH High Humidity Alarm Setpoint

AO

8

%RH Low Humidity Alarm Setpoint

BI

1

Cooling

BI

2

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI

22

BI

23

BI

24

BI

BI

25

BI

26

27

Glycol Humidifying Dehumidifying High Head Pressure Compressor 1 High Head Pressure Compressor 2 Loss Of Airflow Standby Glycol Pump On Water Under Floor Change Filters High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm High Water In Humidifier Pan No Water In Humidifier Pan Compressor 1 Overload Compressor 2 Overload Main Fan Overload Manual Override On Smoke Detected Loss Of Water Flow Standby Unit On Low Suction Pressure Short Cycle Alarm Loss Of Power Alarm Alarm Present

1 Network Point Type

2 Network Point Address

Continued on next page . . .

40-85 1-5 40-60 1-10 40-85 40-85 40-60 40-60 0-Heat, 1-Cool 0-Off, 1-On 0-Off, 1-On 0-Off, 1-On 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm

30 Metasys Integrator Liebert Application Application Note

NPT1 (Cont.)
BO

NPA2
1

Unit

Description
Reset All Alarms3

0-N/A, 1-Reset

BO

2

Unit Mode

0-Off, 1-On

1 Network Point Type

2 Network Point Address

3 Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object's Definition and Focus window is disabled.

Liebert DCLAN Environmental Unit Level 0 and Level 0 with On/Off Control (L00, L0A, and LSM)
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity Reading point is AI3.

Table 12: Liebert DCLAN Environmental Unit Level 0 and

Level 0 with On/Off Control (L00, L0A, and LSM)
NPT1 NPA2 Unit Description

AI

1

DegF Temperature Reading (F)

AI

2

DegC Temperature Reading (C)

AI

3

%RH Humidity Reading

AO 1

DegF Temperature Setpoint (F)

35-95

AO 2

DegC Temperature Setpoint (C)

1-35

AO 3

Deg Temperature Tolerance Setpoint

1-10

AO

4

AO

5

%RH Humidity Setpoint %RH Humidity Tolerance Setpoint

35-65 1-10

BI

1

Alarm Present

0-No, 1-Alarm

BI

2

Humidifying On

0-Off, 1-On

BI

3

Dehumidifying On

0-Off, 1-On

BI

4

BI

5

Cooling On Heating On

0-Off, 1-On 0-Off, 1-On

BD 1

High Temperature

0-Ok, 1-Alarm

BD 2

Low Temperature

0-Ok, 1-Alarm

BD 3

High Humidity

0-Ok, 1-Alarm

BD

4

BD

5

BD

6

BD

7

BD

8

BO 1

Low Humidity Loss Of Air Flow Water Under Floor Change Filters High Head Pressure Unit Run3

0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Off,

1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-On

1 Network Point Type

2 Network Point Address

3 Only for L0A

Metasys Integrator Liebert Application Application Note 31

Liebert DCLAN Environmental Unit Small Systems Control (L0B)
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity point is AI3.

Table 13: Liebert DCLAN Environmental Unit Small Systems
Control (L0B)
NPT1 NPA2 Unit Description

AI

1

DegF Temperature (F)

AI

2

DegC Temperature (C)

AI

3

%RH Humidity

BI

1

Alarm Present

0-No, 1-Alarm

BD

1

High Temperature

0-Ok, 1-Alarm

2

Low Temperature

0-Ok, 1-Alarm

3

High Humidity

0-Ok, 1-Alarm

4

Low Humidity

0-Ok, 1-Alarm

BO

1

Unit Run

0-Off, 1-On

1 Network Point Type

2 Network Point Address

Liebert DCLAN Environmental Unit Level 2, 3, 10, and 15 (L02, L03, L10, L1A, and LAM)
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity point is AI3.

Table 14: Liebert DCLAN Environmental Unit Level 2, 3, 10,

and 15 (L02, L03, L10, L1A, and LAM)
NPT1 NPA2 Unit Description

AI

1

Deg Temperature Reading (F)

AI

2

Deg Temperature Reading (C)

AI

3

%RH Humidity

AO

1

Deg Temperature Setpoint (F)

35-95

AO

2

Deg Temperature Setpoint (C)

1-35

AO

3

Deg Temperature Tolerance Setpoint

1-10

AO

4

%RH Humidity Setpoint

35-65

AO

5

%RH Humidity Tolerance Setpoint

1-10

AO

6

DegF High Temperature Alarm Setpoint (F)

30-90

AO

7

DegF High Temperature Alarm Setpoint (C)

-1-32

AO

8

DegF Low Temperature Alarm Setpoint (F)

30-90

AO

9

Deg F Low Temperature Alarm Setpoint (C)

-1-32

AO

10

%RH High Humidity Alarm Setpoint

AO

11

%RH Low Humidity Alarm Setpoint

AO

12

Min Auto Restart Delay Setpoint

AO

13

Min CW Flush Cycle Setpoint3

35-65 30-90
0-99 0-99

1 Network Point Type

2 Network Point Address

3 Available only for Level 02 and 03.

Continued on next page . . .

32 Metasys Integrator Liebert Application Application Note

NPT1 NPA2 Unit Description

BI

1

Alarm Present

0-No, 1-Alarm

BI

2

Humidifying On

0-Off, 1-On

BI

3

Dehumidifying On

0-Off, 1-On

BI

4

BI

5

Cooling On Heating On

0-Off, 1-On 0-Off, 1-On

BD

1

High Temperature

0-Ok, 1-Alarm

BD

2

Low Temperature

0-Ok, 1-Alarm

BD

3

BD

4

BD

5

BD

6

BD

7

BD

8

BD

9

BD

10

BD

11

BD

12

BD

13

BD

14

BD

15

BD

16

BD

17

BD

18

BD

19

BD

20

BD

21

BD 22
BD 23
BD

24

BO

1

BO

2

High Humidity Low Humidity Loss Of Air Flow Water Under Floor Change Filters High Head Pressure 1 High Head Pressure 2 High Water Humidifier Pan Manual Override Customer Alarm 1 Customer Alarm 2 Standby Glycol Pump On Compressor 1 Overloaded Compressor 2 Overloaded Main Fan Overloaded Smoke Detected Loss Of Water Flow Standby Unit On Low Suction Pressure Short Cycle Loss Of Power Low Water Humidifier Pan3 Alarm Reset5 Unit Run4

0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-N/A, 0-Off,

1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Reset 1-On

1 Network Point Type

2 Network Point Address

3 Available only for Level 02 and 03.

4 Available only for devices which have on/off control.

5 Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object's Definition and Focus window is disabled.

Metasys Integrator Liebert Application Application Note 33

Liebert DCLAN Chiller - CW1, CW2, and CW3
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Module 3 Start point is BI8.

Table 15: Liebert DCLAN Chiller - CW1, CW2, and CW3
NPT1 NPA2 Unit Description

BI

1

Alarm Present

0-No, 1-Alarm

BI

2

Module 1 Start

0-Off, 1-On

BI

3

Module 1 Pump On

0-Off, 1-On

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

Module 1 Cooling On Module 2 Start3 Module 2 Pump On3 Module 2 Cooling On3 Module 3 Start4 Module 3 Pump On4 Module 3 Cooling On4

0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off,

1-On 1-On 1-On 1-On 1-On 1-On 1-On

BD 1

High Head Pressure Module 1

0-Ok, 1-Alarm

BD 2

No Water Flow Module 1

0-Ok, 1-Alarm

BD 3

High Water Temperature Module 1

0-Ok, 1-Alarm

BD

4

BD

5

BD

6

BD

7

BD

8

BD

9

BD

10

BD

11

BD

12

BD

13

BD

14

BD

15

Low Water Temperature Module 1
No Power Module 1 High Head Pressure Module 23 No Water Flow Module 23 High Water Temperature Module 23 Low Water Temperature Module 23 No Power Module 23 High Head Pressure Module 34 No Water Flow Module 34 High Water Temperature Module 34 Low Water Temperature Module 34 No Power Module 34

0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok,

1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm

1 Network Point Type

2 Network Point Address

3 Available for CW2 (two module unit) or CW3 (three module unit).

4 Available for CW3.

34 Metasys Integrator Liebert Application Application Note

Liebert DCLAN Chiller with Econocoil CE1, CE2, and CE3
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Module 2 Start point is BI6.

Table 16: Liebert DCLAN Chiller with Econocoil CE1, CE2,

and CE3
NPT1 NPA2 Unit Description

BI

1

Alarm Present

0-No, 1-Alarm

BI

2

Module 1 Start

0-Off, 1-On

BI

3

Module 1 Pump On

0-Off, 1-On

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

Module 1 Cooling On
Module 1 Econocoil Operating Module 2 Start3 Module 2 Pump On3 Module 2 Cooling On3
Module 2 Econocoil Operating Module 3 Start4 Module 3 Pump On4 Module 3 Cooling On4
Module 3 Econocoil Operating

0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off,

1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On

BD

1

High Head Pressure Module 1

0-Ok, 1-Alarm

BD

2

No Water Flow Module 1

0-Ok, 1-Alarm

BD

3

High Water Temperature Module 1

0-Ok, 1-Alarm

BD

4

BD

5

BD

6

BD

7

BD

8

BD

9

BD

10

BD

11

BD

12

BD

13

BD

14

BD

15

Low Water Temperature Module 1
No Power Module 1 High Head Pressure Module 23 No Water Flow Module 23 High Water Temperature Module 23 Low Water Temperature Module 23 No Power Module 23 High Head Pressure Module 34 No Water Flow Module 34 High Water Temperature Module 34 Low Water Temperature Module 34 No Power Module 34

0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok,

1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm

1 Network Point Type

2 Network Point Address

3 Available for CE2 (two-module unit) or CE3 (three-module unit).

4 Available for CE3.

Metasys Integrator Liebert Application Application Note 35

Liebert DCLAN Power Conditioning Unit
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Frequency point is AI14.

Table 17: Liebert DCLAN Power Conditioning Unit - Type PMP

with IGM, VCMP with IGM
NPT1 NPA2 Unit Description

AI

1

Volt

Volts Out X-Y

AI

2

Volt

Volts Out Y-Z

AI

3

Volt

Volts Out Z-X

AI

4

Volt

Volts Out X-N

AI

5

Volt

Volts Out Y-N

AI

6

Volt

Volts Out Z-N

AI

7

Amps Amps Out X

AI

8

Amps Amps Out Y

AI

9

Amps Amps Out Z

AI

10

Amps Ground Current

AI

11

Amps Neutral Current

AI

12

kV

kVA

AI

13

kW

kW

AI

14

Hz

Frequency

AI

15

%

% Capacity Phase X

AI

16

%

% Capacity Phase Y

AI

17

%

% Capacity Phase Z

BI

1

Alarm Present

0-No, 1-Alarm

BD

1

Transformer Over Temperature

0-Ok, 1-Alarm

BD

2

Frequency Deviation

0-Ok, 1-Alarm

BD

3

Ground Over Current

0-Ok, 1-Alarm

BD

4

Output Over Current

0-Ok, 1-Alarm

BD

5

BD

6

BD

7

BD

8

BD

9

BD

10

BD

11

BD

12

BD

13

BD

14

BD

15

BD

16

BD

17

BO

1

Output Over Voltage Output Under Voltage Ground System Fault Water Under Floor Security Alarm Phase Rotation Datawave Over Temperature Emergency Shutdown Unit In Bypass Customer Alarm 1 Customer Alarm 2 Local Alarm Ground Failure Alarm Reset3

0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-Ok, 1-Alarm 0-N/A, 1-Reset

1 Network Point Type

2 Network Point Address

3 Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object's Definition and Focus window is disabled.

36 Metasys Integrator Liebert Application Application Note

Liebert DCLAN UPS Series 300 and 600
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Frequency point is AI12.

Table 18: Liebert DCLAN UPS Series 300* and 600 - Type

Single Module System (SMS) and Multi Module System (MMS)
NPT1 NPA2 Unit Description

AI

1

Volt

Volts Out A-B

AI

2

Volt

Volts Out B-C

AI

3

Volt

Volts Out C-A

AI

4

Volt

Volts Out A-N

AI

5

Volt

Volts Out B-N

AI

6

Volt

Volts Out C-N

AI

7

Amps Amps Out A

AI

8

Amps Amps Out B

AI

9

Amps Amps Out C

AI

10

kV

KVA

AI

11

kW

kW

AI

12

Hz

Frequency

AI

13

%

% Capacity Phase A

AI

14

%

% Capacity Phase B

AI

15

%

% Capacity Phase C

AI

16

Amps Battery Current

AI

17

Volt

DC Bus Voltage

AI

18

Volt

Input Volts Phase A-B

AI

19

Volt

Input Volts Phase B-C

AI

20

Volt

Input Volts Phase C-A

BI

1

Alarm Present

0-No, 1-Alarm

BD

1

Output Overload

0-Ok, 1-Alarm

BD

2

Load On Bypass

0-Ok, 1-Alarm

BD

3

Static Switch Disabled

0-Ok, 1-Alarm

BD

4

BD

5

BD

6

BD

7

BD

8

BD

9

BD

10

BD

11

BO

1

Emergency Power Off Module Cooling Failure Ambient Over Temperature Battery Discharging Low Battery Reserve Battery Disconnect Fuse Cleared Control Power Failure4 Alarm Reset3

0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-N/A,

1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Reset

1 Network Point Type

2 Network Point Address

3 Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object's Definition and Focus window is disabled.

4 Not available on MMS.

* Series 300 with optional SiteScan Interface Card

Metasys Integrator Liebert Application Application Note 37

Liebert DCLAN Series 600 Static Control Cabinet (SCC)
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Frequency point is AI12.

Table 19: Liebert DCLAN Series 600 Static Control Cabinet (SCC)
NPT1 NPA2 Unit Description

AI

1

Volt

Volts Out A-B

AI

2

Volt

Volts Out B-C

AI

3

Volt

Volts Out C-A

AI

4

Volt

Volts Out A-N

AI

5

Volt

Volts Out B-N

AI

6

Volt

Volts Out C-N

AI

7

Amp Amps Out A

AI

8

Amp Amps Out B

AI

9

Amp Amps Out C

AI

10

kV

KVA

AI

11

kW

kW

AI

12

Hz

Frequency

AI

13

%

% Capacity Phase A

AI

14

%

% Capacity Phase B

AI

15

%

% Capacity Phase C

AI

16

Volt

Bypass Voltage Phase A-B

AI

17

Volt

Bypass Voltage Phase B-C

AI

18

Volt

Bypass Voltage Phase C-A

BI

1

Alarm Present

0-No, 1-Alarm

BD

1

Output Overload

0-Ok, 1-Alarm

BD

2

Emergency Power Off

0-Ok, 1-Alarm

BD

3

Load on Bypass

0-Ok, 1-Alarm

BD

4

BD

5

BD

6

BD

7

BD

8

BD

9

BD

10

BD

11

BO

1

Static Switch Disabled System Output Out of Limits Module 1 Alarm Module 2 Alarm Module 3 Alarm Module 4 Alarm Module 5 Alarm Module 6 Alarm Alarm Reset3

0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-N/A,

1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Reset

1 Network Point Type

2 Network Point Address

3 Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object's Definition and Focus window is disabled.

38 Metasys Integrator Liebert Application Application Note

Liebert DCLAN Contact Closure Module (CCM)
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Input Contact 1 point is BI1.

Table 20: Liebert DCLAN Contact Closure Module (CCM)
NPT1 NPA2 Unit Description

BI

1

Input Contact 1

0-Off, 1-On

BI

2

Input Contact 2

0-Off, 1-On

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI

22

BI

23

BI

24

BI

BI

25

BI

26

BI

27

BI

28

BI

29

BI

30

BI

31

32

Input Contact 3 Input Contact 4 Input Contact 5 Input Contact 6 Input Contact 7 Input Contact 8 Input Contact 9 Input Contact 10 Input Contact 11 Input Contact 12 Input Contact 13 Input Contact 14 Input Contact 15 Input Contact 16 Input Contact 17 Input Contact 18 Input Contact 19 Input Contact 20 Input Contact 21 Input Contact 22 Input Contact 23 Input Contact 24 Input Contact 25 Input Contact 26 Input Contact 27 Input Contact 28 Input Contact 29 Input Contact 30 Input Contact 31 Input Contact 32

0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off,

1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On

Alarm Flags

0-Ok, 1-Alarm

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

Metasys Integrator Liebert Application Application Note 39

Liebert SiteLink/NIC CCM Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Input Contact 1 point is BI1.

Table 21: Liebert SiteLink/NIC CCM Function Block
NPT1 NPA2 Unit Description

BI

1

Input Contact 1

0-Open, 1-Closed

BI

2

Input Contact 2

0-Open, 1-Closed

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI

22

BI

23

BI

BI

24

BI

25

BI

26

BI

27

BI

28

BI

29

BI

30

BI

31

32

Input Contact 3 Input Contact 4 Input Contact 5 Input Contact 6 Input Contact 7 Input Contact 8 Input Contact 9 Input Contact 10 Input Contact 11 Input Contact 12 Input Contact 13 Input Contact 14 Input Contact 15 Input Contact 16 Input Contact 17 Input Contact 18 Input Contact 19 Input Contact 20 Input Contact 21 Input Contact 22 Input Contact 23 Input Contact 24 Input Contact 25 Input Contact 26 Input Contact 27 Input Contact 28 Input Contact 29 Input Contact 30 Input Contact 31 Input Contact 32

0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed 0-Open, 1-Closed

Alarm Flags

0-Ok, 1-Alarm

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

40 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC CSE Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Module 1 Start/Stop point is BI1.

Table 22: Liebert SiteLink/NIC CSE Function Block
NPT1 NPA2 Unit Description

AI

1

#

Number of Modules

BI

1

Module 1 Start/Stop

0-Stop, 1-Start

BI

2

Module 1 Pump On/Off

0-Off, 1-On

BI

3

Module 1 Cool On/Off

0-Off, 1-On

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

Module 2 Start/Stop Module 2 Pump On/Off Module 2 Cool On/Off Module 3 Start/Stop Module 3 Pump On/Off Module 3 Cool On/Off Module 1 Econocycle On/Off Module 2 Econocycle On/Off Module 3 Econocycle On/Off System Econocycle On/Off Alarm Present

0-Stop, 1-Start 0-Off, 1-On 0-Off, 1-On 0-Stop, 1-Start 0-Off, 1-On 0-Off, 1-On 0-Off, 1-On 0-Off, 1-On 0-Off, 1-On 0-Off, 1-On 0-No, 1-Yes

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI

22

BI

23

BI

BI

24

BI

25

BI

26

BI

27

BI

28

BI

29

BI

30

31

Alarm Flags Local Alarm 1 Local Alarm 2 Module 1 High Head Pressure Module 2 High Head Pressure Module 3 High Head Pressure Module 1 No Water Flow Module 2 No Water Flow Module 3 No Water Flow Module 1 High Water Temp Module 2 High Water Temp Module 3 High Water Temp Module 1 Low Water Temp Module 2 Low Water Temp Module 3 Low Water Temp Module 1 No Power Other Mod Module 2 No Power Other Mod Module 3 No Power Other Mod

0-Ok, 1-Alarm

Alarm Flags

0-Ok, 1-Alarm

BD

1

Loss of Communication

1 Network Point Type

2 Network Point Address

Metasys Integrator Liebert Application Application Note 41

Liebert SiteLink/NIC CSU Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Module 1 Start/Stop point is BI1.

Table 23: Liebert SiteLink/NIC CSU Function Block
NPT1 NPA2 Unit Description

AI

1

#

Number of Modules

BI

1

Module 1 Start/Stop

0-Stop,

BI

2

Module 1 Pump On/Off

0-Off,

BI

3

Module 1 Cool On/Off

0-Off,

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

Module 2 Start/Stop Module 2 Pump On/Off Module 2 Cool On/Off Module 3 Start/Stop Module 3 Pump On/Off Module 3 Cool On/Off Alarm Present

0-Stop, 0-Off, 0-Off, 0-Stop, 0-Off, 0-Off, 0-No,

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI

22

BI

23

BI

BI

24

BI

25

BI

26

BI

27

BI

28

BI

29

30

Alarm Flags Local Alarm 1 Local Alarm 2 Module 1 High Head Pressure Module 2 High Head Pressure Module 3 High Head Pressure Module 1 No Water Flow Module 2 No Water Flow Module 3 No Water Flow Module 1 High Water Temp Module 2 High Water Temp Module 3 High Water Temp Module 1 Low Water Temp Module 2 Low Water Temp Module 3 Low Water Temp Module 1 No Power Other Mod Module 2 No Power Other Mod Module 3 No Power Other Mod Module 1 Liquid Detected Module 2 Liquid Detected Module 3 Liquid Detected

0-Ok,

Alarm Flags

0-Ok,

BD

1

Loss of Communication

1 Network Point Type

2 Network Point Address

1-Start 1-On 1-On 1-Start 1-On 1-On 1-Start 1-On 1-On 1-Yes 1-Alarm
1-Alarm

42 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC EDS Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the kW point is AI17.

Table 24: Liebert SiteLink/NIC EDS Function Block
NPT1 NPA2 Unit Description

AI

1

#

Transfer Count

AI

2

Volt

Source 1 Volts A-B

AI

3

Volt

Source 1 Volts B-C

AI

4

Volt

Source 1 Volts C-A

AI

5

Amps Source 1 Amps A

AI

6

Amps Source 1 Amps B

AI

7

Amps Source 1 Amps C

AI

8

Hz

Source 1 Freq

AI

9

Volt

Source 2 Volts A-B

AI

10

Volt

Source 2 Volts B-C

AI

11

Volt

Source 2 Volts C-A

AI

12

Amps Source 2 Amps A

AI

13

Amps Source 2 Amps B

AI

14

Amps Source 2 Amps C

AI

15

Hz

Source 2 Freq

AI

16

kVA

KVA

AI

17

kW

kW

AI

18

Sec

Auto Transfer Time

AI

19

%

Nominal Voltage Deviation

AI

20

Deg

Phase Differential Limit

AI

21

Hz

Frequency Deviation

BI

1

Preferred Source

0-Scr2, 1-Src1

BI

2

BI

3

BI

4

Load On Source 1 or 2 Auto-Transfer Enabled Alarm Present

0-Scr2, 1-Src1 0-Disabl, 1-Enable 0-No, 1-Yes

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI

22

Alarm Flags Logic Failure Equip Overtemp Power Supply 1 Fault Source 1 Overvoltage Source 1 Undervoltage Source 2 Overvoltage Source 2 Undervoltage Source 1 Overload Shorted SCR 1 Shorted SCR 2 Open SCR 1 Open SCR 2 Fan Failure Source 2 Overload Power Supply 2 Fault Freq Deviation Transfer Inhibit Auto Retransfer Primed

0-Ok 1-Alarm

1 Network Point Type

2 Network Point Address

Continued on next page . . .

Metasys Integrator Liebert Application Application Note 43

NPT1 NPA2 Unit (Cont.)

Description

BI

23

Out of Sync

BI

24

Source 1 Failure

BI

25

Source 2 Failure

BI

26

BI

27

BI

28

BI

29

BI

30

BI

31

BI

32

BI

33

BI

34

BI

35

BI

36

BI

37

BI

38

BI

39

BI

40

BI

41

BI

42

Retransfer Failure Overload Control Fuse 1 Blown Control Fuse 2 Blown Source 1 CB 1 Open Source 2 CB 2 Open Output CB 3 Open Custom Alarm 1 Custom Alarm 2 Bypass CB4 Closed Bypass CB5 Closed Custom Alarm 3 Custom Alarm 4 Custom Alarm 5 Custom Alarm 6 Custom Alarm 7 Custom Alarm 8

Alarm Flags

BD

1

Loss of Communication

1 Network Point Type

2 Network Point Address

0-Ok 1-Alarm

44 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC L00 Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Temperature point is AI1.

Table 25: Liebert SiteLink/NIC L00 Function Block
NPT1 NPA2 Unit Description

AI

1

Deg

Temperature

AI

2

%RH Humidity

AI

3

AI

4

AI

5

AI

6

AI

7

AI

8

Step % Deg %RH Deg %RH

Stages % Capacity Temperature Tolerance Humidity Tolerance Temperature Setpoint Humidity Setpoint

AO 1

DegF Temperature Setpoint

(40 to 90)

AO 2

%RH Humidity Setpoint

(20 to 80)

AO 3 AO 4 AO 5

DegC DegF %RH

Temperature Setpoint DegC Temperature Tolerance Setpoint Humidity Tolerance Setpoint

(5 to 32) (1 to 10) (1 to 10)

BI

1

Cooling

0-Off, 1-On

BI

2

Heating

0-Off, 1-On

BI

3

BI

4

BI

5

BI

6

Humidification Dehumidification Econ-O-Cycle Alarm Present

0-Off, 0-Off, 0-Off, 0-No,

1-On 1-On 1-On 1-Yes

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

Alarm Flags High Head Pressure 1 High Head Pressure 2 Loss Of Airflow Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Custom Alarm 1

0-Ok, 1-Alarm

Alarm Flags

0-Ok, 1-Alarm

BD 1

Loss Of Communication

1 Network Point Type

2 Network Point Address

Metasys Integrator Liebert Application Application Note 45

Liebert SiteLink/NIC L0B Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Temperature point is AI1.

Table 26: Liebert SiteLink/NIC L0B Function Block
NPT1 NPA2 Unit Description

AI

1

Deg Temperature

AI

2

%RH Humidity

AI

3

AI

4

Step %

Stages % Capacity

BI

1

Cooling

0-Off,

BI

2

Heating

0-Off,

BI

3

BI

4

BI

5

BI

6

BI

7

Humidification Dehumidification Econ-O-Cycle Alarm Present Unit Run

0-Off, 0-Off, 0-Off, 0-No, 0-Off,

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

Alarm Flags High Temperature Low Temperature High Humidity Low Humidity Unit Turned Off Locally Unit Turned Off Remotely
Temperature Scale

0-Ok, 0-DegF,

BO 1

Unit Run (Last Command)

0-Off,

Alarm Flags

0-Ok,

BD

1

Loss of Communication

1 Network Point Type

2 Network Point Address

1-On 1-On 1-On 1-On 1-On 1-Yes 1-On 1-Alarm
1-DegC 1-On 1-Alarm

46 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC L10 Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Temperature point is AI1.

Table 27: Liebert SiteLink/NIC L10 Function Block
NPT1 NPA2 Unit Description

AI

1

Deg Temperature

AI

2

%RH Humidity

AI

3

Step Stages

AI

4

%

% Capacity

AI

5

Deg Temperature Tolerance

AI

6

%RH Humidity Tolerance

AI

7

Deg Temperature Setpoint

AI

8

%RH Humidity Setpoint

AO

1

DegF Temperature Setpoint

(40 to 90)

AO

2

%RH Humidity Setpoint

(20 to 80)

AO

3

AO

4

AO

5

DegC DegF %RH

Temperature Setpoint DegC Temperature Tolerance Setpoint Humidity Tolerance Setpoint

(5 to 32) (1 to 10) (1 to 10)

1 Network Point Type

2 Network Point Address

Continued on next page . . .

Metasys Integrator Liebert Application Application Note 47

NPT1 NPA2 Unit Description (Cont.)

BI

1

Cooling

BI

2

Heating

BI

3

Humidification

BI

4

BI

5

BI

6

Dehumidification Econ-O-Cycle Alarm Present

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI 21
BI 22
BI

BI

23

BI

24

BI

25

BI

26

BI

27

BI

28

BI

29

BI

30

BI

31

BI

32

33

Alarm Flags High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycool Unit On Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem No Water in Humidifier Pan Compressor 1 Overload Compressor 2 Overload Main Fan Overload Manual Override Smoke Detected Loss of Water Standby Unit On Low Suction Pressure Short Cycle Loss of Power Inverter on Bypass Standby Fan On Emergency Power Off Local Alarm 1 Local Alarm 2

Alarm Flags

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-No, 0-Ok,

1-On 1-On 1-On 1-On 1-On 1-Yes 1-Alarm

0-Ok, 1-Alarm

48 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC LAM and MM2 Function Blocks
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Temperature point is AI1.

Table 28: Liebert SiteLink/NIC LAM and MM2 Function Blocks
NPT1 NPA2 Unit Description

AI

1

Deg Temperature

AI

2

%RH Humidity

AI

3

Step Stages

AI

4

%

% Capacity

AI

5

Deg Temperature Tolerance

AI

6

%RH Humidity Tolerance

AI

7

Deg High Temp Setpoint*

AI

8

Deg Low Temp Setpoint*

AI

9

%RH High Humidity Setpoint*

AI

10

%RH Low Humidity Setpoint*

AI

11

Deg Temperature Setpoint

AI

12

%RH Humidity Setpoint

AO

1

DegF Temperature Setpoint

(40 to 90)

AO

2

%RH Humidity Setpoint

(20 to 80)

AO

3

AO

4

AO

5

DegC DegF %RH

Temperature Setpoint DegC Temperature Tolerance Setpoint Humidity Tolerance Setpoint

(5 to 32) (1 to 10) (1 to 30)

1 Network Point Type

2 Network Point Address

* If the corresponding alarm is disabled at the SiteLink/NIC module, the setpoint has a 0 value.

Continued on next page . . .

Metasys Integrator Liebert Application Application Note 49

NPT1 NPA2 Unit Description (Cont.)

BI

1

Cooling

BI

2

Heating

BI

3

Humidification

BI

4

BI

5

BI

6

BI

7

Dehumidification Econ-O-Cycle Alarm Present Unit Run

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI 21
BI 22
BI

BI

23

BI

24

BI

25

BI

26

BI

27

BI

28

BI

29

BI

30

BI

31

BI

32

BI

33

BI

34

BI

35

36

Alarm Flags High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycool Unit On Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem No Water in Humidifier Pan Compressor 1 Overload Compressor 2 Overload Main Fan Overload Manual Override Smoke Detected Loss of Water Standby Unit On Low Suction Pressure Short Cycle Loss of Power Inverter on Bypass Standby Fan On Emergency Power Off Local Alarm 1 Local Alarm 2 Unit Turned Off Locally Unit Turned Off Remotely

BO

1

Unit Run (Last Commanded)

Alarm Flags

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-No, 0-Off, 0-Ok,

1-On 1-On 1-On 1-On 1-On 1-Yes 1-On 1-Alarm

0-Off, 0-Ok,

1-On 1-Alarm

50 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC LSM Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Temperature point is AI1.

Table 29: Liebert SiteLink/NIC LSM Function Block
NPT1 NPA2 Unit Description

AI

1

Deg Temperature

AI

2

%RH Humidity

AI

3

AI

4

AI

5

AI

6

AI

7

AI

8

Step % Deg %RH Deg %RH

Stages % Capacity Temperature Tolerance Humidity Tolerance Temp Setpoint Humidity Setpoint

AO

1

DegF Temperature Setpoint

(40 to 90)

AO

2

%RH Humidity Setpoint

(20 to 80)

AO

3

AO

4

AO

5

DegC DegF %RH

Temperature Setpoint DegC Temperature Tolerance Setpoint Humidity Tolerance Setpoint

(5 to 32) (1 to 10) (1 to 10)

BI

1

Cooling

0-Off, 1-On

BI

2

Heating

0-Off, 1-On

BI

3

BI

4

BI

5

BI

6

BI

7

Humidification Dehumidification Econ-O-Cycle Alarm Present Unit Run

0-Off, 0-Off, 0-Off, 0-No, 0-Off,

1-On 1-On 1-On 1-Yes 1-On

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

Alarm Flags High Head Pressure 1 High Head Pressure 2 Loss of Airflow Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Custom Alarm 1 Unit Turned Off Locally Unit Turned Off Remotely

0-Ok, 1-Alarm

BO

1

Unit Run (Last Commanded)

0-Off, 1-On

Alarm Flags

0-Ok, 1-Alarm

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

Metasys Integrator Liebert Application Application Note 51

Liebert SiteLink/NIC MM4 Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the kW point is AI13.

Table 30: Liebert SiteLink/NIC MM4 Function Block
NPT1 NPA2 Unit Description

AI

1

Volt Input Volts A-B

AI

2

Volt Input Volts B-C

AI

3

Volt Input Volts C-A

AI

4

Volt Output Volts A-B

AI

5

Volt Output Volts B-C

AI

6

Volt Output Volts C-A

AI

7

Amps Output Amps A

AI

8

Amps Output Amps B

AI

9

Amps Output Amps C

AI

10

Volt DC Bus Voltage

AI

11

Amps Battery Current

AI

12

kVA KVA

AI

13

kW kW

AI

14

Hz

Critical Bus Frequency

AI

15

%

% Capacity A

AI

16

%

% Capacity B

AI

17

%

% Capacity C

AI

18

Amps Input Amps A

AI

19

Amps Input Amps B

AI

20

Amps Input Amps C

1 Network Point Type

2 Network Point Address

Continued on next page . . .

52 Metasys Integrator Liebert Application Application Note

NPT1 NPA2 Unit Description (Cont.)

BI

1

Alarm Present

Alarm Flags

BI

2

Battery Discharge

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI 21
BI 22
BI

BI

23

BI

24

BI

25

26

Input Failure Hardware Shutdown DC Ground Fault Input CB Open Output CB Open DC Cap Fuse Blown Low Battery Reserve Output Overload Rectifier Fuse Blown Emergency Power Off Ambient Overtemperature Battery Disconnected Control Power Failure Overload Shutdown Inverter Fault Input Current Unbalance Inverter Out of Sync Reverse Power Low Battery Shutdown DC Overvoltage Shutdown Battery Cycle Buffer Full Equipment Overtemperature Blower/Fan Failure Overtemperature Shutdown

Alarm Flags

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

0-No, 0-Ok

1-Yes 1-Alarm

0-Ok 1-Alarm

Metasys Integrator Liebert Application Application Note 53

Liebert SiteLink/NIC MMS Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the kW point is AI16.

Table 31: Liebert SiteLink/NIC MMS Function Block
NPT1 NPA2 Unit Description

AI

1

Volt

Input Volts A-B

AI

2

Volt

Input Volts B-C

AI

3

Volt

Input Volts C-A

AI

4

Volt

Output Volts A-B

AI

5

Volt

Output Volts B-C

AI

6

Volt

Output Volts C-A

AI

7

Volt

Output Volts A-N

AI

8

Volt

Output Volts B-N

AI

9

Volt

Output Volts C-N

AI

10

Amps Output Amps A

AI

11

Amps Output Amps B

AI

12

Amps Output Amps C

AI

13

Volt

DC Bus Voltage

AI

14

Amps Battery Current

AI

15

kVA

kVA

AI

16

kW

kW

AI

17

Hz

Output Frequency

AI

18

%

% Capacity A

AI

19

%

% Capacity B

AI

20

%

% Capacity C

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok

BI

2

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

Battery Discharge Low Battery Reserve Output Overload Fuse Cleared Ambient Overtemperature Battery Grounded Battery Disconnected Module Cooling Control Power Failure Overload Shutdown

Alarm Flags

0-Ok

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-Yes 1-Alarm
1-Alarm

54 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC NPower IMP Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Battery Temperature is AI9.

Table 32: Liebert SiteLink/NIC NPower IMP Function Block
NPT1 NPA2 Unit Description

AI

1

Volt

Input Volts A-B

AI

2

Volt

Input Volts B-C

AI

3

Volt

Input Volts C-A

AI

4

Volt

Bypass Volts A-B

AI

5

Volt

Bypass Volts B-C

AI

6

Volt

Bypass Volts C-A

AI

7

Volt

Battery Volts

AI

8

Amps Battery Current

AI

9

C

Battery Temperature

AI

10

Volt

Output Volts A-B

AI

11

Volt

Output Volts B-C

AI

12

Volts Output Volts C-A

AI

13

Amps Output Current A

AI

14

Amps Output Current B

AI

15

Amps Output Current C

AI

16

kVA

Output kVA A

AI

17

kVA

Output kVA B

AI

18

kVA

Output kVA C

AI

19

kW

Output kW A

AI

20

kW

Output kW B

AI

21

kW

Output kW C

AI

22

Hz

Output Frequency

AI

23

%max Rated kVA Percent

AI

24

%max Rated kW Percent

1 Network Point Type

2 Network Point Address

Continued on next page . . .

Metasys Integrator Liebert Application Application Note 55

NPT1 NPA2 Unit (Cont.)

Description

BI

1

Communications

BI

2

Battery Fuse Failure

BI

3

Battery Low Transfer

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI 22
BI 23
BI

BI

24

BI

25

BI

26

BI

27

BI

28

BI

29

BI

30

BI

31

BI

32

BI

33

BI

34

BI

35

BI

36

BI

37

BI

38

BI

39

BI

40

BI

41

BI

42

DC Overvoltage Transient Input Phase Rotation Error Rectifier Fuse Failure Bypass Frequency Error Bypass Overload Shutdown Bypass Phase Rotation Error Inverter Overload Transfer Inverter Fuse Failure Output Overvolt Transfer Output Undervolt Transfer SBS SCR Open SBS SCR Shorted Inverter Current Limit Transfer Overtemp CB Trip Battery Ground Fault CB Trip Power Supply Fail EPO Shutdown Rectifier Fail Inverter Fail Hardware Shutdown Battery Discharging Input Current Imbalance Input Line Failure Input Undervoltage Input Overvoltage Input Overcurrent Battery CB Open Bypass Sync Error Bypass Volts Out of Tolerance Bypass Line Failure Inverter Current Limit Output Over/Under Frequency Inverter Overload Excessive Auto Re-Transfers Overtemp Warning Fan Failure SBS Unable Inverter Off by User Low Battery Warning

BI

43

Battery Test Fail User Shutdown

BI

44

Load on Bypass

45

Input Contact

1 Network Point Type

2 Network Point Address

56 Metasys Integrator Liebert Application Application Note

0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok, 0-Ok,

1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm
1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm 1-Alarm

Liebert SiteLink/NIC PMP Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the kW point is AI16.

Table 33: Liebert SiteLink/NIC PMP Function Block
NPT1 NPA2 Unit Description

AI

1

Volt Input Volts A-B

AI

2

Volt Input Volts B-C

AI

3

Volt Input Volts C-A

AI

4

Volt Output Volts A-B

AI

5

Volt Output Volts B-C

AI

6

Volt Output Volts C-A

AI

7

Volt Output Volts A-N

AI

8

Volt Output Volts B-N

AI

9

Volt Output Volts C-N

AI

10

Amps Output Amps A

AI

11

Amps Output Amps B

AI

12

Amps Output Amps C

AI

13

Amps Ground Current

AI

14

Amps Neutral Current

AI

15

kVA kVA

AI

16

kW kW

AI

17

Hz

Output Freq

AI

18

%

% Capacity A

AI

19

%

% Capacity B

AI

20

%

% Capacity C

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BI

2

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

Output Undervoltage Output Overvoltage Output Overcurrent Frequency Deviation Ground Overcurrent Transformer Overtemp Ground Fault Ground Failure Liquid Detected Security Alarm Phase Rotation/Loss Datawave Overtemp Emergency Shutdown Load On Bypass Local Alarm Custom Alarm 1 Custom Alarm 2

Alarm Flags

0-Ok,

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-Yes 1-Alarm
1-Alarm

Metasys Integrator Liebert Application Application Note 57

Liebert SiteLink/NIC RAC Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Unit 1 On/Off point is BI1.

Table 34: Liebert SiteLink/NIC RAC Function Block
NPT1 NPA2 Unit Description

BI

1

Unit 1 On/Off

0-Off,

BI

2

Unit 2 On/Off

0-Off,

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

Unit 3 On/Off Unit 4 On/Off Unit 5 On/Off Unit 6 On/Off Unit 7 On/Off Unit 8 On/Off Alarm Present

0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-Off, 0-No,

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI

20

BI

21

BI

22

BI

BI

23

24

Alarm Flags Unit 1 Common Alarm Unit 2 Common Alarm Unit 3 Common Alarm Unit 4 Common Alarm Unit 5 Common Alarm Unit 6 Common Alarm Unit 7 Common Alarm Unit 8 Common Alarm Emergency Power Operation EPO All Units High Temperature Low Temperature High Humidity Low Humidity Manual Override

0-Ok,

Alarm Flags

0-Ok,

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-On 1-Yes 1-Alarm
1-Alarm

58 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC SC4 Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the kW point is AI11.

Table 35: Liebert SiteLink/NIC SC4 Function Block
NPT1 NPA2 Unit Description

AI

1

Volt Input Volts A-B

AI

2

Volt Input Volts B-C

AI

3

Volt Input Volts C-A

AI

4

Volt Output Volts A-B

AI

5

Volt Output Volts B-C

AI

6

Volt Output Bolts C-A

AI

7

Amps Output Amps A

AI

8

Amps Output Amps B

AI

9

Amps Output Amps C

AI

10

kVA KVA

AI

11

kW kW

AI

12

Hz

Critical Bus Frequency

AI

13

%

% Capacity A

AI

14

%

% Capacity B

AI

15

%

% Capacity C

AI

16

Volt Bypass Volts A-B

AI

17

Volt Bypass Volts B-C

AI

18

Volt Bypass Volts C-A

AI

19

Hz

Output Frequency

AI

20

Hz

Bypass Frequency

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BI

2

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

BI

18

BI

19

BI 20
BI 21
BI 22
BI 23

Output Undervoltage Output Overvoltage Frequency Deviation Bypass CB Open Output CB Open Static SW Disconnected Output Overload Emergency Power Off Load On Bypass Static Switch Disabled Control Power Failure Module 1Summary Alarm Module 2 Summary Alarm Module 3 Summary Alarm Module 4 Summary Alarm Module 5 Summary Alarm Module 6 Summary Alarm Bypass Not Available Not OK to Transfer Bypass Ph. Rotation Error Manual Reset/Transfer Auto Retransfer Primed

1 Network Point Type

2 Network Point Address

Continued on next page . . .

1-Yes 1-Alarm

Metasys Integrator Liebert Application Application Note 59

NPT1 NPA2 Unit Description (Cont.)

BI

24

Overload Transfer

BI

25

Module 1 Offline

BI

26

Module 2 Offline

BI

27

Module 3 Offline

BI

28

BI

29

BI

30

BI

31

BI

32

BI

33

BI

34

BI

35

BI

36

BI

37

BI

38

Module 4 Offline Module 5 Offline Module 6 Offline Custom Alarm 1 Custom Alarm 2 Custom Alarm 3 Custom Alarm 4 Custom Alarm 5 Custom Alarm 6 Custom Alarm 7 Custom Alarm 8

Alarm Flags

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

0-Ok, 1-Alarm

60 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC SCC Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the kW point is AI14.

Table 36: Liebert SiteLink/NIC SCC Function Block
NPT1 NPA2 Unit Description

AI

1

Volt Input Volts A-B

AI

2

Volt Input Volts B-C

AI

3

Volt Input Volts C-A

AI

4

Volt Output Volts A-B

AI

5

Volt Output Volts B-C

AI

6

Volt Output Volts C-A

AI

7

Volt Output Volts A-N

AI

8

Volt Output Volts B-N

AI

9

Volt Output Volts C-N

AI

10

Amps Output Amps A

AI

11

Amps Output Amps B

AI

12

Amps Output Amps C

AI

13

kVA KVA

AI

14

kW kW

AI

15

Hz

Output Frequency

AI

16

%

% Capacity A

AI

17

%

% Capacity B

AI

18

%

% Capacity C

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BI

2

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

Output Overload Emergency Power Off Load On Bypass Static Switch Disabled Output Out of Limits Module 1 Summary Alarm Module 2 Summary Alarm Module 3 Summary Alarm Module 4 Summary Alarm Module 5 Summary Alarm Module 6 Summary Alarm

Alarm Flags

0-Ok,

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-Yes 1-Alarm
1-Alarm

Metasys Integrator Liebert Application Application Note 61

Liebert SiteLink/NIC SM3 Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Output Frequency point is AI14.

Table 37: Liebert SiteLink/NIC SM3 Function Block
NPT1 NPA2 Unit Description

AI

1

Volt Input Volts A-N

AI

2

Volt Input Volts B-N

AI

3

Volt Input Volts C-N

AI

4

Volt Output Volts A-N

AI

5

Volt Output Volts B-N

AI

6

Volt Output Volts C-N

AI

7

Amps Output Amps A

AI

8

Amps Output Amps B

AI

9

Amps Output Amps C

AI

10

Volt DC Bus Voltage

AI

11

Amps DC Bus Current

AI

12

kVA kVA

AI

13

kW

kW

AI

14

Hz

Output Frequency

AI

15

%

% Capacity A

AI

16

%

% Capacity B

AI

17

%

% Capacity C

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BI

2

Battery Discharge

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

Low Battery Reserve Output Overload Fuse Cleared Emergency Power Off Ambient Overtemperature Load On Bypass Static Switch Disabled Battery Disconnected Module Cooling Failure Control Power Failure Overload Shutdown

Alarm Flags

0-Ok,

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-Yes 1-Alarm
1-Alarm

62 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC SM4 Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Input Amps A point is AI21.

Table 38: Liebert SiteLink/NIC SM4 Function Block
NPT1 NPA2 Unit Description

AI

1

Volt Input Volts A-B

AI

2

Volt Input Volts B-C

AI

3

AI

4

AI

5

AI

6

AI

7

AI

8

AI

9

AI

10

AI

11

AI

12

AI

13

AI

14

AI

15

AI

16

AI

17

AI

18

AI

19

AI

20

AI

21

AI

22

AI

23

AI

24

Volt Volt Volt Volt Amps Amps Amps Volt Amps kVA kW Hz % % % Volt Volt Volt Amps Amps Amps Hz

Input Volts C-A Output Volts A-B Output Volts B-C Output Volts C-A Output Amps A Output Amps B Output Amps C DC Bus Voltage Battery Current kVA kW Critical Bus Frequency % Capacity A % Capacity B % Capacity C Bypass Volts A-B Bypass Volts B-C Bypass Volts C-A Input Amps A Input Amps B Input Amps C Bypass Frequency

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BI

2

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

BI

14

BI

15

BI

16

BI

17

B

18

BI

19

Output Undervoltage Output Overvoltage Battery Discharge Freq Deviation Input Failure Hardware Shutdown DC Ground Fault Input CB Open Bypass CB Open Output CB Open Static SW Disconnected DC Cap Fuse Blown Low Battery Reserve Output Overload Rectifier Fuse Blown Emergency Power Off Ambient Overtemperature Load On Bypass

1 Network Point Type

2 Network Point Address

Continued on next page . . .

1-Yes 1-Alarm

Metasys Integrator Liebert Application Application Note 63

NPT1 NPA2 (Cont.)

BI

20

BI

21

BI

22

BI

23

BI

24

BI

25

BI

26

BI

27

BI

28

BI

29

BI

30

BI

31

BI

32

BI

33

BI

34

BI

35

BI

36

BI

37

BI

38

BI

39

BI

40

BI

41

BI

42

BI

43

BI

44

BI

45

Unit

BD

1

1 Network Point Type

2 Network Point Address

Description
Static Switch Disabled Battery Disconnected Control Power Failure Inverter Fault Input Current Unbalance Bypass Not Available Not OK to Transfer Bypass Ph. Rotation Error Manual Reset/Transfer Auto Retransfer Primed Overload Transfer Reverse Power Low Battery Shutdown DC Overvoltage Shutdown Battery Cycle Buffer Full Equip Overtemp Blower/Fan Failure Overtemp Shutdown Custom Alarm 1 Custom Alarm 2 Custom Alarm 3 Custom Alarm 4 Custom Alarm 5 Custom Alarm 6 Custom Alarm 7 Custom Alarm 8 Alarm Flags Loss of Communications

0-Ok, 1-Alarm

64 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC SMS Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Output Frequency point is AI17.

Table 39: Liebert SiteLink/NIC SMS Function Block
NPT1 NPA2 Unit Description

AI

1

Volt

Bypass Volts A-B

AI

2

Volt

Bypass Volts B-C

AI

3

Volt

Bypass Volts C-A

AI

4

Volt

Output Volts A-B

AI

5

Volt

Output Volts B-C

AI

6

Volt

Output Volts C-A

AI

7

Volt

Output Volts A-N

AI

8

Volt

Output Volts B-N

AI

9

Volt

Output Volts C-N

AI

10

Amps Output Amps A

AI

11

Amps Output Amps B

AI

12

Amps Output Amps C

AI

13

Volt

DC Bus Voltage

AI

14

Amps DC Bus Current

AI

15

kVA

kVA

AI

16

kW

kW

AI

17

Hz

Output Frequency

AI

18

%

% Capacity A

AI

19

%

% Capacity B

AI

20

%

% Capacity C

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BI

2

BI

3

BI

4

BI

5

BI

6

BI

7

BI

8

BI

9

BI

10

BI

11

BI

12

BI

13

Battery Discharge Low Battery Reserve Output Overload Fuse Cleared Emergency Power Off Ambient Overtemperature Load On Bypass Static Switch Disabled Battery Disconnected Module Cooling Failure Control Power Failure Overload Shutdown

Alarm Flags

0-Ok,

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-Yes 1-Alarm
1-Alarm

Metasys Integrator Liebert Application Application Note 65

Liebert SiteLink/NIC THM Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the No. 1 Temperature point is AI1.

Table 40: Liebert SiteLink/NIC THM Function Block
NPT1 NPA2 Unit Description

AI

1

Deg

#1 - Temperature

AI

2

%RH #1 - Humidity

AI

3

Deg

#2 - Temperature

AI

4

%RH #2 - Humidity

AI

5

Deg

#3 - Temperature

AI

6

%RH #3 - Humidity

AI

7

Deg

#4 - Temperature

AI

8

%RH #4 - Humidity

AI

9

Deg

#5 - Temperature

AI

10

%RH #5 - Humidity

AI

11

Deg

#6 - Temperature

AI

12

%RH #6 - Humidity

AI

13

Deg

#7 - Temperature

AI

14

%RH #7 - Humidity

AI

15

Deg

#8 - Temperature

AI

16

%RH #8 - Humidity

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-Yes 1-Alarm

66 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC VCF Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Alarm Present point is BI1.

Table 41: Liebert SiteLink/NIC VCF Function Block
NPT1 NPA2 Unit Description

AI

1

Volt Output Volts X-Y

AI

2

Volt Output Volts Y-Z

AI

3

Volt Output Volts Z-X

AI

4

Volt Output Volts X-N

AI

5

Volt Output Volts Y-N

AI

6

Volt Output Volts Z-N

AI

7

Amps Output Amps A

AI

8

Amps Output Amps B

AI

9

Amps Output Amps C

AI

10

Amps Ground Current

AI

11

Amps Neutral Current

AI

12

kVA kVA

AI

13

Hz

Frequency

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BI

2

Output Undervoltage

BI

3

BI

4

BI

5

BI

6

Output Overvoltage Transformer Overtemp Local Alarm 1 Local Alarm 2

Alarm Flags

0-Ok,

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-Yes 1-Alarm
1-Alarm

Metasys Integrator Liebert Application Application Note 67

Liebert SiteLink/NIC VCM Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Alarm Present point is BI1.

Table 42: Liebert SiteLink/NIC VCM Function Block
NPT1 NPA2 Unit Description

AI

1

Volt Output Volts X-Y

AI

2

Volt Output Volts Y-Z

AI

3

AI

4

AI

5

AI

6

AI

7

AI

8

AI

9

AI

10

AI

11

AI

12

Volt Volt Volt Volt Amps Amps Amps Amps Amps kVA

Output Volts Z-X Output Volts X-N Output Volts Y-N Output Volts Z-N Output Amps A Output Amps B Output Amps C Ground Current Neutral Current kVA

BI

1

Alarm Present

0-No,

Alarm Flags

0-Ok,

BI

2

Output Undervoltage

BI

3

BI

4

BI

5

BI

6

Output Overvoltage Transformer Overtemp Local Alarm 1 Local Alarm 2

Alarm Flags

0-Ok,

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

1-Yes 1-Alarm
1-Alarm

68 Metasys Integrator Liebert Application Application Note

Liebert SiteLink/NIC WDU Function Block
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Distance point is AI1.

Table 43: Liebert SiteLink/NIC WDU Function Block
NPT1 NPA2 Unit Description

AI

1

#

Distance

BI

1

Units

0-Meters, 1-Feet

BI

2

Alarm Present

0-No, 1-Yes

Alarm Flags

0-Ok, 1-Alarm

BI

3

BI

4

Cable Fault Liquid Detected

Alarm Flags

0-Ok, 1-Alarm

BD

1

Loss of Communications

1 Network Point Type

2 Network Point Address

Metasys Integrator Liebert Application Application Note 69

Metasys Network Setup

Metasys Network Setup is described in the Metasys Integrator unit technical bulletins on the Johnson Controls Product Information site (http://cgproducts.johnsoncontrols.com System Manuals > Integration > Metasys Integrator). This section contains details specific to Liebert applications.

Mapping to a CS Object

Table 44: Software Model and CS Object Definition

Application

Software Model Display Attribute
(on Tables and Models (Recommended) CD-ROM)

NT Command Attribute
(Recommended)

DC100 or MCCI

System 3

LI_SYS3.DDL

AI1

BO1

Levels 0, 1, 2, 3, 10, and 15 Small Systems Controller

LI_SSC.DDL

Temperature AI1

Reset Alarms BO1

Temperature

Reset Alarms

ECA2

Level 0

LI_ECA2.DDL

AI1

BO1

Temperature

Reset Alarms

Levels 10 and 15

LIECA210.DDL

AI1

BO1

Temperature

Reset Alarms

DCLAN

Environmental Units

Level 00 (L00)

LIDCLL00.DDL

AI1

BO1

Small Systems Control (L0B) LIDCLL0B.DDL

Temperature AI1

Unit Run BO1

Level 02 (L02) and Level 03 (L03) Level 0 with On/Off Control (L0A) and Standard

LIDCLL02.DDL LIDCLL0A.DDL

Temperature AI1 Temperature

Unit Run BO1 Reset Alarms

Microprocessor (LSM)

Level 10 without On/Off Control (L10) Level 10 (L1A) and Level 15 (LAM) with On/Off Control

LIDCLL10.DDL LIDCLL1A.DDL

AI1 Temperature AI1 Temperature

BO1 Reset Alarms BO1 Reset Alarms

* For the NT Command attribute, use the same attribute as the Display attribute. However, since you cannot command the points, you will not be able to command the attribute. (This must be defined because the NT Command attribute cannot be null.)

Continued on next page . . .

70 Metasys Integrator Liebert Application Application Note

Application (Cont.)

Software Model (on Tables and Models CD-ROM)

Display Attribute (Recommended)

NT Command Attribute (Recommended)

Chillers

Single Module (CW1)

LIDCLCW1.DDL

BI4

BI4*

Two Module (CW2)

LIDCLCW2.DDL

Cooling On BI4

Cooling On BI4*

Three Module (CW3)

LIDCLCW3.DDL

Cooling On BI4

Cooling On BI4*

Chillers with Econocoil

Cooling On

Cooling On

Single Module (CE1)

LIDCLCE1.DDL

BI4

BI4

Two Module (CE2)

LIDCLCE2.DDL

Cooling On BI4

Cooling On BI4

Three Module (CE3)

LIDCLCE3.DDL

Cooling On BI4

Cooling On BI4

Power Conditioning Unit

Cooling On

Cooling On

Power Monitoring Panel (PMP) UPS

LIDCLPMP.DDL

AI 13 kW

BO1 Reset Alarms

Series 300 and 600 ­ Single Module System (SMS) Series 600 ­ Multi-Module System (MMS) Series 600 ­ Static Control Cabinet (SCC) NPower (IMP) UPS

LIDCLSMS.DDL LIDCLMMS.DDL LIDCLSCC.DDL LISL_IMP.DDL

AI16 Battery Current AI16 Battery Current AI1 Input Volts A-B AI8

BO1 Reset Alarms BO1 Reset Alarms BO1 Reset Alarms AI8*

Contact Closure Module (CCM) LIDCLCCM.DDL

Battery Current BI1

Battery Current BI1*

Input Contact 1

Input Contact 1

* For the NT Command attribute, use the same attribute as the Display attribute. However, since you cannot command the points, you will not be able to command the attribute. (This must be defined because the NT Command attribute cannot be null.)

Continued on next page . . .

Metasys Integrator Liebert Application Application Note 71

Application (Cont.)

Software Model (on Tables and Models CD-ROM)

Display Attribute (Recommended)

NT Command Attribute (Recommended)

SiteLink/NIC Modbus Function Blocks
CCM

LiSL_CCM.DDL

BI1 Contact 1

BI1* Contact 1

CSE

LiSL_CSE.DDL

BI1 Module 1 Start/Stop

BI1* Module 1 Start/Stop

CSU

LiSL_CSU.DDL

BI1 Module 1 Start/Stop

BI1* Module 1 Start/Stop

EDS

LiSL_EDS.DDL

AI2 Source 1 Volts A-B

AI2* Source 1 Volts A-B

LiSL_L00.DDL

AI1

AO1*

L00

Temperature

Setpoint

LiSL_L0B.DDL

AI1

BO1*

L0B

Temperature

Unit Run

LiSL_L10.DDL

AI1

AO1*

L10

Temperature

Setpoint

LAM

LiSL_LAM.DDL

AI1 Temperature

AO1* Setpoint

LSM

LiSL_LSM.DDL

AI1 Temperature

AO1* Setpoint

MM4

LiSL_MM4.DDL

AI1 Input Volts A-B

AI1* Input Volts A-B

MMS

LiSL_MMS.DDL

AI1 Input Volts A-B

AI1* Input Volts A-B

PMP

LiSL_PMP.DDL

AI1 Input Volts A-B

AI1* Input Volts A-B

RAC

LiSL_RAC.DDL

BI1 Unit 1 On/Off

BI1* Unit 1 On/Off

SC4

LiSL_SC4.DDL

AI1

AI1*

Input Volts A-B

Input Volts A-B

SCC

LiSL.SCC.DDL

AI1 Input Volts A-B

AI1* Input Volts A-B

SM3

LiSL_SM3.DDL

AI1 Input Volts A-B

AI1* Input Volts A-B

SM4

LiSL_SM4.DDL

AI1

AI1*

Input Volts A-B

Input Volts A-B

SMS

LiSL_SMS.DDL

AI4

AI4*

Output Volts A-B

Output Volts A-B

* For the NT Command attribute, use the same attribute as the Display attribute. However, since you cannot command the points, you will not be able to command the attribute. (This must be defined because the NT Command attribute cannot be null.)

Continued on next page . . .

72 Metasys Integrator Liebert Application Application Note

Application (Cont.)

Software Model (on Tables and Models CD-ROM)

Display Attribute (Recommended)

NT Command Attribute (Recommended)

SiteLink/NIC Modbus (Cont.)

THM

LiSL_THM.DDL

AI1

AI1*

#1 Temp

#1 Temp

VCF

LiSL_VCF.DDL

AI1

AI1*

VCM

LiSL_VCM.DDL

Output Volts X-Y AI1

Output Volts X-Y AI1*

WDU

LiSL_WDU.DDL

Output Volts X-Y AI1

Output Volts X-Y AI1*

Distance

Distance

* For the NT Command attribute, use the same attribute as the Display attribute. However, since you cannot command the points, you will not be able to command the attribute. (This must be defined because the NT Command attribute cannot be null.)

Metasys Integrator Liebert Application Application Note 73

Custom Integration
For information on integrating products that are not discussed in this document, first refer to the Metasys Compatible Products online list of released connectivity products. If this list does not provide the information you require, consider using the Systems Integration Services (SIS) Request Custom Engineered Solutions process to request a custom contract from System Integration Team. Access both the Metasys Compatible Products and the Request Custom Engineered Solutions process from The Advisor by performing the following steps: 1. Click on the Products Focus link, located at the top of The Advisor
home page. 2. Under Products, click on the Systems Integration Services link. 3. For the searchable database, click on Metasys Compatible Products. 4. Select Metasys Compatible Products Database. 5. Click Online Search Tool. 6. After the search in completed, return to the Systems Integration
Services home page as instructed in Steps 1-2. 7. Select Custom Engineered Solutions to view the process used for
requesting all types of SIS engineered solutions and services. 8. Select Requesting an Engineered Solution or Service. 9. Click Online Request Page. If you need further assistance, contact the Johnson Controls Field Support Center.

Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201
74 Metasys Integrator Liebert Application Application Note

www.johnsoncontrols.com Published in U.S.A.


Acrobat Distiller 6.0.1 (Windows)