Drywall Grid Systems: Hanging & Framing Flat Ceilings
Inspiring Great Spaces®
Armstrong CEILING SOLUTIONS
Work Smarter
Eliminate the labor-intensive cutting, tying, and spacing of track and channel framing. Armstrong's Drywall Grid Systems are engineered with rout locations and cross tees to maintain precise module spacing. Main beams feature 51 rout locations and cross tees are available in 50", 26", and 14" lengths to accommodate Type F fixtures without field modifications or accessories. Pre-notched main beams simplify curved drywall installations.
Our Drywall Systems are manufactured to meet or exceed ASTM standards and code requirements, and are engineered to provide economical alternatives to stud and track construction.
The vertical load carrying capacity for main beam and cross tee members is determined in accordance with ASTM test method E3090. Suspended ceiling systems constructed of screw-attached gypsum board panels may be installed in accordance with ASTM C1858 and are exempt from code prescribed requirements of acoustical or lay-in panel ceilings. This standard practice is limited to framing that supports a single level ceiling and is surrounded by and attached to laterally braced walls or soffits.
Drywall Grid Systems: Code Compliance You Can Trust
Meets:
- ASTM C1858
- ASTM C635
- ASTM C645
- ASTM C754
- ASTM C840
- ASTM E3090
- ICC Evaluation Service Report ESR-1289
- City of LA - RR 25348
- IBC categories D, E, and F single layer drywall ceilings
- Miami-Dade County, Florida impact testing NOA No. 14-1204.05 - 10/07/2019
- Miami-Dade County, Florida wind uplift NOA No. 15-0127.04 - 03/17/2020
Consult local codes for specific requirements.
Performance
- PeakForm® patented profile increases strength and stability for improved performance during installation.
- SuperLock™ main beam clip is engineered for a strong secure connection and fast accurate alignment, confirmed with an audible click; easy to remove and relocate.
- ScrewStop™ reverse hem prevents screw spinoff on 1-1/2" wide face.
Components
Main Beams
| Item Number | Length | Dimension | Face Height | Profile | Load | Duty | Fire Rated | Routs | Load Test Data (Lbs/LF) | Perspective | ||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| L/240 Simple Span | L/360 Simple Span | |||||||||||
| HD8906 / HD8906G90 | 144" | 1-1/2" x 1-11/16" | Heavy Duty | Yes | 51 routs - starting 2-1/4" from each end+ | 143.00 | 57.30 | 28.14 | 95.5 | 43.19 | 18.66 | [Image of main beam] |
| HD8906HRC | ||||||||||||
| HD8906IIC | 144" | 1-1/2" x 1-11/16" | Heavy Duty | Yes | 51 routs - starting 2-1/4" from each end+ | 143.00 | 57.30 | 28.14 | 95.5 | 43.19 | 18.66 | [Image of main beam] |
| HD890610 | 120" | 1-1/2" x 1-11/16" | Heavy Duty | Yes | 51 routs - starting 2-1/4" from each end+ | 143.00 | 57.30 | 28.14 | 95.5 | 43.19 | 18.66 | [Image of main beam] |
Metric
| Item Number | Length | Dimension | Face Height | Profile | Load | Fire Rated | Routs | Hanger Spacing (KG/LM) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 600mm | 900mm | 1200mm | 600mm | 900mm | 1200mm | ||||||||
| HD7940 | 3600mm | 30mm x 38mm | Yes | 200mm O.C. | 150.0 | 68.3 | 29.34 | 100.0 | 45.35 | 19.56 | |||
| 7940G | 3600mm | 30mm x 38mm | Yes | 150mm O.C. - starting 75mm from each end+ | 114.0 | 51.92 | 22.40 | 76.39 | 34.61 | 14.93 |
+ Type F fixture compatible
Cross Tees
| Item Number | Length | Dimension | Face Height | Profile | Fire Rated | Routs | Load Test Data (Lbs/LF) | Perspective | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| L/240 Simple Span | L/360 Simple Span | ||||||||||||
| 2' | 3' | 4' | 2' | 3' | 4' | ||||||||
| XL8965 / XL8965HRC | 72" | 1-1/2" x 1-1/2" | Yes | 6 routs - starting 24" from each end+ | 6.87 | 4.58 | [Image of cross tee] | ||||||
| XL8947P / XL8947PG90 | 50" | 1-1/2" x 1-1/2" | Yes | 8 routs - starting 10" from each end+ | 19.5 | 12.79 | [Image of cross tee] | ||||||
| XL8945P / XL8945PG90 / XL8945HRC | 48" | 1-1/2" x 1-1/2" | Yes | 9 routs center rout and starting 10" from each end+ | 22.5 | 14.27 | [Image of cross tee] | ||||||
| XL7936G90 | 36" | 1-1/2" x 1-1/2" | No | 50.00 | 31.33 | [Image of cross tee] | |||||||
| XL8926 / XL8926G90 | 24" | 1-1/2" x 1-1/2" | Yes | 3 routs center rout and 10" from each end+ | 158.0 | 90.25 | [Image of cross tee] |
Metric
| Item Number | Length | Dimension | Face Height | Profile | Fire Rated | Routs | Load Total Data (KG/LM) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| L/240 | L/360 | L/240 | L/360 | L/240 | L/360 | |||||||
| XL7961 | 1600mm | 30mm x 38mm | Yes | 800mm center of tee | 10.25 @ 6' | 6.84 @ 6' | 15.15 @ 1600mm | 10.18 @ 1600mm | ||||
| XL7930 | 1200mm | 30mm x 38mm | Yes | 450mm, 600mm, 750mm | 22.4 @ 4' | 14.93 @ 4' | 33.33 @ 1200mm | 22.22 @ 1200mm | ||||
| XL7925 | 900mm | 30mm x 38mm | No | none | 51.92 @ 3' | 34.61 @ 3' | 77.26 @ 900mm | 51.51 @ 900mm |
NOTE: All items available in High Recycled Content (HRC) as special order.
Molding
| Item Number | Length | Description | Profile | Perspective |
|---|---|---|---|---|
| 7858 | 144" | Reverse Angle Molding nominal 1-9/16" x 15/16" | [Image of molding profile] | [Image of molding perspective] |
| KAM10 | 120" | Knurled Angle Molding nominal 1-1/4" x 1-1/4" | [Image of molding profile] | [Image of molding perspective] |
| KAM12 / KAM12G90 / KAM12HRC | 144" | Knurled Angle Molding nominal 1-1/4" x 1-1/4" | [Image of molding profile] | [Image of molding perspective] |
| KAM1510 / KAM1512 / KAM151020 / KAM151020EQ | 120" / 144" | Knurled Angle Molding nominal 1-1/2" x 1-1/2" (25 ga.; 20 ga.; 22 ga.) | [Image of molding profile] | [Image of molding perspective] |
| KAM21020 / KAM21025 / KAM21020EQ | 120" / 144" | Knurled Angle Molding nominal 2" x 2" (20 ga.; 25 ga.; 22 ga.) | [Image of molding profile] | [Image of molding perspective] |
| LAM12 / LAM12G90 / LAM12HRC | 144" | Locking Angle Molding nominal 1-1/4" x 1-1/4" | [Image of molding profile] | [Image of molding perspective] |
| LAM151220E | 144" | 1-1/2" x 1-1/2" | [Image of molding profile] | [Image of molding perspective] |
| SC151220EQ / SC151225 | 148" | SimpleCurve™ Knurled Angle Molding (12' x 1.5" - 20 ga.; 12' x 1.5" - 25 ga.) | [Image of molding profile] | [Image of molding perspective] |
| SC21220EQ / SC21225 | 148" | SimpleCurve™ Knurled Angle Molding (12' x 2" - 20 ga.; 12' x 2" - 25 ga.) | [Image of molding profile] | [Image of molding perspective] |
NOTE: All items available in High Recycled Content (HRC) as special order.
[Diagram showing SimpleCurve™ Knurled Angle Molding used with 5/8" Gypsum Board]
Corrosion Prevention
Corrosion prevention is an essential factor in the economical utilization of galvanized sheet metal for ceiling suspension systems. Armstrong Ceilings provides G40 for standard construction per ASTM C645. When conditions include exposure to extreme moisture and salt water, G90 is available per ASTM A653.
Material: Commercial-quality cold rolled hot dipped galvanized steel
| Item Number | Length/Item | Description | Face Dimension | Flange Height | Profile | Perspective |
|---|---|---|---|---|---|---|
| 7901 | 120" | Shadow Reveal Molding | 3/8" shadow reveal | 9/16" | 1-1/4" | [Image of molding] |
| 7902 | 120" | Shadow Reveal Molding | 3/8" shadow reveal | 15/16" | 1-1/4" | [Image of molding] |
| 7903 | 120" | Inverted T Molding | 1" inverted T | 1-1/2" | [Image of molding] | |
| 7904 / 7904PF* | 120" | Flush Transition Molding | 15/16" horizontal | 15/16" | 1-1/4" | [Image of molding] |
| 7905 / 7905PF* | 120" | Flush Transition Molding | 9/16" horizontal | 9/16" | 1-1/4" | [Image of molding] |
| 7906 | 120" | F Molding | 120" vertical transition | 1/2" | 1-7/16" | [Image of molding] |
| 7907 | 120" | Tegular Transition Molding | 9/16" horizontal | 9/16" | 1-1/4" | [Image of molding] |
| 7908 | 120" | Tegular Transition Molding | 15/16" horizontal | 15/16" | 1-1/4" | [Image of molding] |
| 7909 | 15/16" 1" Step Transition Molding | 15/16" horizontal | 15/16" | 1-7/8" | [Image of molding] | |
| 7910 | 9/16" 1" Step Transition Molding | 9/16" horizontal | 9/16" | 1-7/8" | [Image of molding] | |
| 7911 | 9/16" | Shadow Reveal Transition Molding | 3/8" x 1/4" shadow reveal | 9/16" | 1-1/8" | [Image of molding] |
| 7912 | 15/16" | Shadow Reveal Transition Molding | 3/8" x 1/4" shadow reveal | 15/16" | 1-1/4" | [Image of molding] |
* 7904PF and 7905PF feature protective film on the acoustical wall angle flange for faster, easier finishing.
Axiom® Trim
Axiom Drywall Transitions
| Item Number | Length/Item | Description | Dimensions | Perspective |
|---|---|---|---|---|
| AXTRVESTR | Straight Transition for Vector® Ceiling | 120 x 2-9/16 x 1-11/16" | [Diagram: Axiom - Transitions with Vector® panel to drywall perimeter] | |
| AXTRTECUR | Curved Transition for Tegular | 120 x 2-9/16 x 1-11/16" | [Diagram: Axiom - Transitions with Tegular panel to drywall perimeter] | |
| AXTR2STR | 2" Straight Transition | 120 x 2 x 1-1/2" | [Diagram: Acoustical-to-Drywall] | |
| AXTR2CUR | 2" Curved Transition | 120 x 2 x 1-1/2" | [Diagram: Drywall-to-Drywall] | |
| AXTR4STR | 4" Straight Transition | 120 x 4 x 1-1/2" | [Diagram: Acoustical-to-Drywall] | |
| AXTR4CUR | 4" Curved Transition | 120 x 4 x 1-1/2" | [Diagram: Drywall-to-Drywall] | |
| AXTR6STR | 6" Straight Transition | 120 x 6 x 1-1/2" | [Diagram: Acoustical-to-Drywall] | |
| AXTR6CUR | 6" Curved Transition | 120 x 6 x 1-1/2" | [Diagram: Drywall-to-Drywall] | |
| AXTR8STR | 8" Straight Transition | 120 x 8 x 1-1/2" | [Diagram: Acoustical-to-Drywall] | |
| AXBTSTR | Drywall Bottom Trim | 120 x 1-1/8 x 27/32" | [Diagram: Drywall Bottom Trim] |
Accessories
| Item Number | Description | Perspective |
|---|---|---|
| AX4SPLICEB | Splice Plate | [Image of splice plate] |
| AXTBC | T-Bar Connector Clip | [Image of clip] |
Axiom One-Piece Drywall Trim
*For use with 5/8" drywall only
Material: Commercial-quality extruded aluminum alloy 6063
| Item Number | Length/Item | Description | Perspective |
|---|---|---|---|
| AX1PC2STR | 2.5" One-Piece Straight Drywall Trim | [Diagram: HANGER WIRE, DGS, AXTBC, 2-9/16", One-Piece Drywall Trim, 5/8" Drywall] | |
| AX1PC2CUR | 2.5" One-Piece Curved Drywall Trim | [Diagram: HANGER WIRE, DGS, AXTBC, 2-9/16", One-Piece Drywall Trim, 5/8" Drywall] | |
| AX1PC4STR | 4" One-Piece Straight Drywall Trim | [Diagram: HANGER WIRE, DGS, AXTBC, 4", One-Piece Drywall Trim, 5/8" Drywall] | |
| AX1PC4CUR | 4" One-Piece Curved Drywall Trim | [Diagram: HANGER WIRE, DGS, AXTBC, 4", One-Piece Drywall Trim, 5/8" Drywall] | |
| AX1PC6STR | 6" One-Piece Straight Drywall Trim | [Diagram: HANGER WIRE, DGS, AXTBC, 6", One-Piece Drywall Trim, 5/8" Drywall] | |
| AX1PC6CUR | 6" One-Piece Curved Drywall Trim | [Diagram: HANGER WIRE, DGS, AXTBC, 6", One-Piece Drywall Trim, 5/8" Drywall] |
Axiom® Building Perimeter System
Axiom Pocket with Face Plate to Drywall Transition
[Diagram showing Axiom Pocket with Face Plate to Drywall Transition, including components like Optional Stud, 3-Sided Perimeter Pocket, Foam Gasket, HVAC Boot, Splice Plate, Armstrong® Drywall Grid Cross Tee, Window, 2" Closure Clip, Interlocking Spline, Slotted Face Plate, T-Bar Connection Clip, Drywall Taping Flange, Hanger Wire, 5/8" Thick Drywall, Armstrong® Drywall Grid Main Beam]
| Item Number | Length/Item | Description | Perspective |
|---|---|---|---|
| AXP355LC | 3-Sided Lutron Compatible Shade Pocket with Connection to Extension/Face Plate Piece | [Image of pocket] | |
| AXPCC2 | 2" Shade Closure Clip | [Image of clip] | |
| AXPCC3 | 3" Shade Closure Clip | [Image of clip] | |
| AXPDFP4DTSLA / AXPDFP4DTSLB | 4" Axiom Perimeter Face Plate with Drywall Flange - 2 Slot Pattern / 1 Slot Pattern | [Image of face plate] | |
| AXPDFP7DT / AXPDFP7DTSLA / AXPDFP7DTSLB | 7" Axiom Perimeter Face Plate with Drywall Flange - Unslotted / 2 Slot Pattern / 1 Slot Pattern | [Image of face plate] |
Rout Locations
Imperial
| HD8906 (HRC)/HD890610* | [Diagram showing rout locations for HD8906/HD890610, indicating 51 routs starting 2" from end, and length of 144" or 120"] | ||||||
| HD8906IIC | [Diagram showing rout locations for HD8906IIC, indicating 51 routs starting 2" from end, and length of 144"] | ||||||
| XL8965 (HRC) (Type F Compatible) | [Diagram showing rout locations for XL8965, indicating 51 routs starting 2" from end, and length of 72"] | ||||||
| XL8947P (Type F Compatible) | [Diagram showing rout locations for XL8947P, indicating routs at 26" and 50", and lengths of 50"] | ||||||
| XL8945HRC/XL8945P (Type F Compatible) | [Diagram showing rout locations for XL8945HRC/XL8945P, indicating routs at 10", 12", 24", 48", and lengths of 48"] | ||||||
Metric
| XL7936G90 | [Diagram showing rout locations for XL7936G90, indicating 18 routs @ 200mm O.C. starting 100mm from end, and length of 3600mm] | ||||||
| XL8926 | [Diagram showing rout locations for XL8926, indicating 24 routs @ 150mm O.C. starting 75mm from end, and length of 3600mm] | ||||||
| HD7940 | [Diagram showing rout locations for HD7940, indicating 16 routs @ 200mm O.C. starting 100mm from end, and length of 3600mm] | ||||||
| 7940G | [Diagram showing rout locations for 7940G, indicating 24 routs @ 150mm O.C. starting 75mm from end, and length of 3600mm] | ||||||
| XL7961 | [Diagram showing rout locations for XL7961, indicating routs at 800mm and 1600mm, and length of 1600mm] | ||||||
| XL7930 | [Diagram showing rout locations for XL7930, indicating routs at 450mm, 600mm, 750mm, and 1200mm] | ||||||
| XL7925 | [Diagram showing rout locations for XL7925, indicating routs at 600mm and 900mm] | ||||||
| XL7920 | [Diagram showing rout locations for XL7920, indicating routs at 600mm] | ||||||
Accessories
Drywall Grid Accessories
A variety of drywall grid accessories are available to provide problem-solving solutions that save time, labor, and money. For a complete list of accessories, request submittal BPCS-3082.
| Item Number | Quantity | Description | Perspective | Application |
|---|---|---|---|---|
| DWACS | 100 | Drywall Attachment Clip facilitates transition from drywall to acoustical ceiling; locks under bulb of grid section to prevent upward movement and provide secure attachment surface on one side of exposed grid. | [Image of DWACS] | [Image of DWACS application] |
| DW30C, DW45C, DW60C, DW90C | 250 | 30-, 45-, 60-, and 90-degree Drywall Angle Clips are used to create positive and secure angles for drywall and ceiling installations on either main beams or cross tees. | [Images of DW30C, DW45C, DW60C, DW90C] | [Image of angle clip application] |
| TT10 | 30 | Partition Top Trim is used to finish the top of a drywall partition for a continuous drywall/acoustical ceiling interface. | [Image of TT10] | [Image of TT10 application] |
| DW58LT | 125 | DW58LT - Transition Clip for 5/8" Drywall with Locking Tabs; facilitates transition from drywall to acoustical ceiling; one-sided hold down clip; eliminates need for drywall bead. Locking tabs provide secure location for Drywall Grid System tees. | [Image of DW58LT] | [Image of DW58LT application] |
| DW50LT | 125 | DW50LT - Transition Clip for 1/2" Drywall with Locking Tabs; facilitates transition from drywall to acoustical ceiling; one-sided hold down clip; eliminates the need for a drywall bead. Locking tabs provide secure location for Drywall Grid System tees. | [Image of DW50LT] | [Image of DW50LT application] |
| IIC | 36 | Impact Isolation Clip for use with HD8906IIC drywall grid main beam. Provides up to 8 points of IIC improvement to ensure your project meets IBC requirements. | [Image of IIC clip] | [Image of IIC clip application] |
| MBSC2 | 200 | Main Beam Spacer Clip (2" in length) is used to space two parallel main beams 2" O.C. for air supply or return. | [Image of MBSC2] | [Image of MBSC2 application] |
| GSC9, GSC12, GSC16 | 100 | Adjustable Grid Spacer Clip is used to space two parallel main beams for light fixtures, air diffusers, etc.; allows for 1/4" adjustments with three different clips. | [Images of GSC clips] | [Image of GSC clip application] |
Drywall Grid Accessories (continued)
| Item Number | Quantity | Description | Perspective | Application |
|---|---|---|---|---|
| XTAC | 100 | Cross Tee Adapter Clip is used to attach field-cut cross tees to main beams. | [Image of XTAC] | [Image of XTAC application] |
| DDC | 250 | Double Drywall Clip is used to hang suspension system below existing 1-1/2" grid face, transferring weight directly to hanger wire; may be used to preserve the fire rating of an existing ceiling and to support heavy accessories; allows for double layer of 5/8" gypsum board. | [Image of DDC] | [Image of DDC application] |
| DLCC | 250 | Direct Load Ceiling Clip is used to hang suspension system below existing 15/16" grid face, transferring weight directly to hanger wire; may be used to preserve the fire rating of an existing ceiling and to support heavy accessories. | [Image of DLCC] | [Image of DLCC application] |
| DWC | 250 | Drywall Clip allows for a second ceiling to be installed below a drywall ceiling; attach through installed drywall to supporting structure. | [Image of DWC] | [Image of DWC application] |
| MBAC | 70 | Main Beam Adapter Clip attaches to web of suspension system section; provides larger surface for screw attachments; used as a hold down clip for thin material (metal or plastic lay-in panels); fastens drywall track to underside of exposed suspension system with lay-in panels, leaving suspension system face free of screw holes. | [Image of MBAC] | [Image of MBAC application] |
System Framing
Hanging & Framing
The grid system is comprised of main beams and cross tees that are suspended by hanger wires to the structural deck. Sections of main beams lock together end-to-end while cross tees span between the main beams. The ends of the main beams and cross tees rest on the wall channel or angle molding that run around the perimeter of the space.
[Diagram illustrating hanging and framing with main beams, cross tees, hanger wires, wall channel/angle molding, and gypsum wall board. Includes labels for KAM - Knurled Angle Molding, and a note about 107 lbs. Pull Out and 372 lbs. Shear with 25 gauge Pan Head Streaker.]
Squaring Up the System
Once you've hung your first two main beams and border cross tees, install two full cross tees between the main beams in line with the first two border cross tees. To square up the system, simply measure across the diagonals of the opening. The measurements will be the same if the grid is square. If the grid is not square, shorten one of the main beams until the diagonals are equal.
[Diagram illustrating squaring up the system by measuring diagonals A and B.]
Type F Fixtures
Hanging & Framing
Type F fixtures, access panels, and air diffusers require a full 12", 24", or 48" opening dimension. The Armstrong Drywall Grid System main beams and cross tees have additional routs in the web to accommodate this larger opening for type F fixtures. Using our 14", 26", 50", and 72" cross tees, type F fixtures fit perfectly without field cutting or special accessories.
When installing type F fixtures parallel to the main beams, use a 72" and 48" cross tee for easy placement of fixtures without field modifications.
When installing fixtures perpendicular to the main beams, use 72" cross tees for virtually limitless fixture placement.
[Diagram showing main beams at 48" O.C. with placement of XL8947P, HD8906, XL8925, XL8947P, XL8965, XL8925, XL8947P, HD8906.]
[Diagram showing main beams at 72" O.C. with placement of XL8925, XL8965, XL8947P, HD8906, XL8925, XL8965, XL8947P, HD8906.]
| Item No. | Description | Fixture Length | |
|---|---|---|---|
| DGSLLTK24 | 2' Linear Light Trim Kit | 24" x 4" | [Diagram: LCBDGS4 Connector Bracket install 2' from each end and 4' O.C., Hanger Wire, DGS Main Beam, DGS Cross Tee, Taping Flange, DGSLL Aluminum Extrusion] |
| DGSLLTK30 | 2'-6" Linear Light Trim Kit | 30" x 4" | |
| DGSLLTK48 | 4' Linear Light Trim Kit | 48" x 4" | |
| DGSLLTK60 | 5' Linear Light Trim Kit | 60" x 4" | |
| DGSLLTK72 | 6' Linear Light Trim Kit | 72" x 4" | |
| DGSLLTK90 | 7'6" Linear Light Trim Kit | 90" x 4" | |
| DGSLLTK96 | 8' Linear Light Trim Kit | 96" x 4" | |
| DGSLLTK120 | 10' Linear Light Trim Kit | 120" x 4" | |
| DGSLLTKCON | 10' Continuous Linear Light Trim Kit | 10' |
Linear Light Trim Kits designed to work with 5/8" drywall
Suspended Drywall Grid Systems
Suspended Drywall Grid System Details
[Diagram showing a layout of a suspended drywall grid system with numbered components.]
1. Butt Joint
5. Type F Fixture
9. Access Door
[Diagram showing a detail of a Butt Joint with Hanger Wire and Gypsum Board.]
[Diagram showing a detail of a Type F Fixture.]
[Diagram showing a detail of an Access Door.]
[Diagram showing details of various components: 2. Expansion Joint*, 3. Wood Trim, 4. Control Joint, 6. Air Bar, 7. High Hat Fixture, 8. Vertical Brace, 10. Securing a Single Cross Tee, 11. Channel and Angle Molding, 12. Angle Clip. Includes labels for MBSC2 Main Beam Spacer Clip, DW90C, DW60C, DW45C, DW30C, XTAC, DDC, Main Beam, Cross Tee, Drywall Screws, Expansion Joint*, Edge Bead, Screw, Wood Trim, Hanger Wire, Angle Molding, Steel Stud, Main Beam, Hanger Wire, Channel Molding, Steel Stud.]
[Diagram showing details of various components: 13. Triple Layer with Security Lath, 14. Double Layer with Security Lath, 15. Double Hung Ceiling, 16. Transition, 17. Axiom® Perimeter Trim, 18. Alternate Finishes, 19. Drywall Vertical, 20. Surface Mount Fixture, 21. Triple Layer with Sound Isolators, 22. HD8906 with IIC Clip. Includes labels for Hanger Wire, Exposed Tee Grid System, Angle Molding, Cross Tee, Acoustical Panel, Gypsum Board, Steel Stud, Drywall Grid System, Drywall Screw, Axiom® - Classic, 5/8" Gypsum Wall Board, Axiom® Drywall Bottom Trim, AXTBC, Axiom - Profiled (Convex), Drywall Screw, DDC, Hanger Wire, Main Beam, Sound Isolator by Others, Plywood or Gypsum Board, Gypsum Board, Surface Mount Light Fixture (Screwed to Main Beam), Hanger Wire, IIC Clip.]
Wire Loading
Hanging & Framing
9 Gauge Wire Breaking Strength and Technical Data
- 9 Gauge Wire
- Diameter: .148"
- Galvanized Steel
- 645 lbs. Maximum Safe Wire Load
- 3 Turns in 3" Per ASTM C636
- 450 lbs. Pullout - Hanger Wire Hole
12 Gauge Wire Breaking Strength and Technical Data
- 12 Gauge Wire
- Diameter: .105"
- Galvanized Steel
- 275 lbs. Maximum Safe Wire Load
- 3 Turns in 3" Per ASTM C636
- 500 lbs. Pullout - Hanger Wire Hole
[Diagram illustrating wire loading with 9 gauge and 12 gauge wire specifications.]
Counter Splayed Wires
Objects in the plenum may obstruct placement of vertical hanger wires and require splayed wires to support the load. When this occurs, a second counter splayed wire must be added. Install counter splayed wires at an angle equal and opposite to the first wire, but not greater than 45° from vertical. The load capacity of the main beam remains unchanged (refer to ASTM C636).
[Diagram illustrating counter splayed wires at 45°, 30°, and 15° angles. Includes a note: "If counter splayed wires are at unequal angles, refer to a local engineer or code official for approval."]
Yoke Wire Hung Ceilings
Hanging & Framing
Another method to install hanger wires around an object in the plenum is to utilize a single or double yoke wire technique. Rule: To form the 45-degree angle, the vertical location of the tension ring is always half the distance of the span at the structure.
Single Yoke
[Diagram illustrating single yoke wire technique with 8' span, 4' vertical drop, and 45° angle. Includes 5/8" Type USS Flat Washer or Equivalent.]
Double Yoke
[Diagram illustrating double yoke wire technique with 12' span, 6' vertical drop, and 45° angle. Includes 5/8" Type USS Flat Washer or Equivalent. Includes notes: "Maintain wire spacing at a maximum 4' O.C."]
Trapeze Supported Loads
Hanging & Framing
Installing a trapeze is a technique to support multiple hanger wires under obstructions, such as trunk lines, cable trays, or other objects in the plenum. In some cases, the trapeze may affect the ceiling height and must be kept small. In other cases, steel studs may be used to span the distance required.
[Diagram illustrating trapeze supported loads with HVAC DUCT, Duct Strap, Cable Trays, Elec. Conduit/Water Lines, Telephone Lines, Trapeze Support Independent of Equipment, Main Beam, Acoustical or Drywall Ceilings, and 4' O.C. spacing.]
Double Hung Ceilings
Hanging & Framing
A suspended ceiling not only carries the load of the applied finish, but can also act as a load carrying structure or membrane that supports another ceiling at a lower level. The DDC clip is used at hanger wire locations to allow for connecting the second and even third ceiling. This method of hanging and framing is used in multi-layer ceilings with long vertical drops – eliminating the use of long stud drops.
[Diagram illustrating double hung ceilings with DDC clips, Main Beam, Hanger Wires, Drywall Grid System, Wall Angle, Partition Wall, Sound Isolator, Double Layer Gypsum Wall Board, Steel Stud, DW45C.]
Gusset Hung Ceiling
[Diagram illustrating gusset hung ceiling with 2" x 6" Wood Block, Wire Clip or Eye Screw into Wood Block, Plumbing TW Wire Cable, Loading at Top of Wall in Wood Block, Electricity, Security, etc., #9 Wire 500 lbs., DWC Clip.]
Triple Hung Ceilings
Hanging & Framing
[Diagram illustrating triple hung ceilings with Drywall Grid System, Insulation, DDC Clip, Pipe Chase, Duct, Drywall Grid System, Drywall Grid System, DW45C, Channel Molding, Drywall Main Beam, Drywall Main Beam, DDC, Channel Molding, DW90C, Roof Deck, Bar Joist, Gypsum Board, Steel Stud. Labeled as 1st, 2nd, 3rd levels.]
Exterior Wind Load Data
Exterior Wind Load Ceiling Design for North America
[Table detailing Exterior Wind Load Ceiling Design for North America, including Plenum Height, Velocity Pressure, Design Pressure, Post Size, Post Gauge, Sheathing Membrane Substrate, Compression Post, Main Beam, Cross Tee, Hanger Wire Spacing, Tee Length, and Compression Post Load.]
NOTE: For building heights over 20 feet, refer to ASCE 7-10 Chapter 6 Wind Loads.
UL® Fire Resistive
Hanging & Framing
[Table detailing UL® Fire Resistive Floor/Ceiling Drywall Assemblies and Wood Deck/Ceiling Drywall Assemblies, including Deck Construction Type, UL® Design Number, Concrete Thickness, # Drywall Layers, Minimum Drywall Thickness, Maximum Fixture Penetration, Maximum Duct Penetration, and Drywall Grid System.]
[Table detailing UL® Fire Resistive Roof/Ceiling Drywall Assemblies, including Deck Construction Type, UL Design Number, Concrete Thickness, # Drywall Layers, Minimum Drywall Thickness, Maximum Fixture Penetration, Maximum Duct Penetration, and Drywall Grid System.]
Armstrong® Drywall "Design To Fit" Items XL7936G90 and XL8965 cannot be used as part of a UL Fire Resistive Design.
DFR 8000 - UL Designation, Fire Guard™ Drywall Grid System.
For fire-rated assemblies, use Type C gypsum board as noted in the UL fire-rated assembly designs.
Fire Rated Expansion Joint
[Diagram showing a fire expansion notch and a collapsed fire expansion notch.]
Load Data
Main Beam - Technical Load Test Data
[Table showing Main Beam Technical Load Test Data for Imperial and Metric units, including Simple Span loads.]
Cross Tees - Technical Load Test Data
[Table showing Cross Tees Technical Load Test Data for Imperial and Metric units, including Simple Span loads.]
NOTE: Allowable loads tested per ASTM C635 for deflection limited to L/360 and complies with ASTM C645 for deflection limited to L/240. See standards for additional information.
Membrane Load Values
[Table showing Membrane Load Values for Imperial and Metric units, including Maximum Load in lbs./ft.2 at Hanger Wire/Cross Tee Spacing and Maximum Load in kg/lm² at Hanger Wire/Cross Tee Spacing.]
Basic Products
Basic Products Used on Suspension Systems
[Table listing basic products used on suspension systems, including Material, Weight Lbs/SF, Maximum Main Beam Spacing, Maximum Cross Tee Spacing, Maximum Wire Spacing, and Load on Wire.]
NOTES: All framing on the exterior should be 16" O.C. or less.
Some manufacturers make 1/2" gypsum board with special core to span 24" framing on interior ceiling installations (available on request).
All steel product on exterior made from G90 galvanized finish.
Data based on manufacturer's published data.
Use lower RPM (1,000-2,500) screw gun to install cement board screws with intermittent pressure.
Control Joints
Please refer to ASTM C840, Section 20.3.3 to 20.4 for Control Joint Requirements.
[Diagram illustrating a control joint.]
Expansion Joints
Ceiling expansion joints are installed to separate the metal suspension system when expansion joints occur in buildings or when metal changes direction. Expansion joints are required to separate a system in T-, H-, I-, and U-, or circle-shaped buildings to eliminate cracking from expansion.
[Diagram illustrating an expansion joint.]
Sound Control
Hanging & Framing
The IBC uses two sound classes to measure sound isolation performance in building construction: Sound Transmission Class (STC) – sound transmitted through the air such as voices and music. Impact Insulation Class (IIC) – sound transmitted through the building structure such as foot traffic and objects dropped on the floor. A rating of 50 or above for both STC and IIC sound tests will satisfy the IBC's minimum requirements.
Understanding Sound Control Ratings
| STC/IIC Ratings | Description | Changes in STC/IIC Ratings | Description |
|---|---|---|---|
| 55 | Excellent | +/-1 | Almost perceptible |
| 50 | Loud speech barely audible | +/-3 | Just perceptible |
| 45 | Some loud speech audible - not understood | +/-5 | Clearly Perceptible |
| 30 | Loud speech audible - well understood | +/-10 | Twice (or half) as loud |
| 25 | Regular speech audible and understood through walls |
Satisfy IBC requirements with a rating of 50 or above for STC and IIC sound tests - without two layers of drywall using Armstrong® Drywall Grid.
Traditional Assembly - Field Tested Data
| Traditional Assembly | Building Structure | STC | IIC |
|---|---|---|---|
| 1-1/2" Black Iron / 7/8" Channel, 3-1/2" Batt Insulation, 5/8" Gypsum | Bare Concrete Base | 55 | 48 |
| 3" Concrete Slab, Fluted Steel Decking, 8" Bar Joist, 24" O.C. | 44 |
Armstrong® Standard Drywall Grid Assembly - Field Tested Data
| Item Number | Armstrong Assembly | Building Structure | STC | IIC |
|---|---|---|---|---|
| HD8906 / XL8945 | 12' Main Beam / 4' Cross Tee, 3-1/2" Batt Insulation, 5/8" Gypsum | 6" Thick Concrete: 3500psi, Bare Concrete Base | 55 | 47 |
| 3" Concrete Slab, Fluted Steel Decking, 8" Bar Joist, 24" O.C. | 47 |
Armstrong® IIC Drywall Grid Assembly - Field Tested Data
| Item Number | Armstrong Assembly | Building Structure | STC | IIC |
|---|---|---|---|---|
| HD8906IIC / XL8945 / IIC Clip | 12' Main Beam / 4' Cross Tee, IIC Clip, 3-1/2" Batt Insulation, 5/8" Gypsum | 6" Thick Slab Concrete Base with Vinyl Sheet Flooring | 57 | 66 |
[Diagram showing Armstrong® IIC Drywall Grid Assembly with HD8906IIC 12' Main Beam, XL8945 4' DGS Tee (Wires 4' O.C.), 3-1/2" Batt Insulation, Ceiling - One Layer 5/8" Gypsum, and IIC Clip.]
Estimating
Estimating Material
[Table showing Area of ceiling completed by one carton (SF) for various grid components and spacing.]
Example calculation based on 5,100 SF ceiling:
Main beam at 48" O.C.: 5,100 SF x .25 = 1,275 LF. 1,275 LF ÷ 144 LF/Ctn = 9 cartons needed
Cross tee at 16" O.C.: 5,100 SF x .76 = 3,876 LF. 3,876 LF ÷ 144 LF/Ctn = 27 cartons needed
[Table showing Estimating Lineal Feet of Grid Based on Square Footage of Ceiling for various O.C. Spacing of Component.]