Overview
The Carrier 50FCQ units are standard-efficiency, single-packaged heat pump units featuring Ecoblue™ Technology. They come pre-wired and pre-charged with Puron® refrigerant. Electric heat is available as a field-installed accessory. These units are fully factory tested and agency certified. They offer field-convertible supply and return openings, designed for installation on a roof curb accessory (ordered separately) or for slab mounting with horizontal duct connections. Various factory-installed options and field-installed accessories are available.
Key Features
Standard Base Unit
- Puron® (R-410A) HFC refrigerant
- SEER ratings up to 14.3 and SEER2 ratings up to 13.4
- IEER ratings up to 15.0 and heating HSPFs up to 8.2
- HSPFs up to 8.2 (COPs to 3.8)
- ASHRAE 90.1 compliant and Energy Star qualified
- Rated in accordance with AHRI Standards 210/240 (3-5 ton sizes) and 340/360 (6 ton sizes)
- Designed in accordance with Underwriters Laboratories Std 1995
- Listed by UL and UL-Canada
- Non-corrosive composite sloping design with side or center drain condensate pan, meeting ASHRAE Standard 62
- Single-stage cooling capacity control on 3-5 ton models; two-stage cooling capacity control on 6 ton models
- Standard cooling operating range: up to 115°F (46°C) and down to 40°F (4°C). Low Ambient cooling operation down to –20°F (–29°C)
- Convertible from vertical to horizontal airflow for slab mounting
- Two-inch disposable return air filters
- Thru-the-bottom power entry capability
- Single point electric connections for field-installed electric heat units
- 24-volt control circuit protected with resettable circuit breaker and 75-VA transformer
- Direct Drive - EcoBlue™ Technology indoor fan system with Vane Axial fan design and electronically commutated motor
- Totally enclosed condenser motors with permanently lubricated bearings
- State-of-the-art defrost control board, configurable for defrost cycles of 30, 60, 90, or 120 minutes
- New Unit Control Board with intuitive quick fan adjustment
- Loss of charge, high-pressure, and freeze protection switches
- Full perimeter base rail with built-in rigging adapters and fork truck slots
Cabinet Features
- Access panels with easy grip handles and replaceable no-strip screw collars
- Pre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection
- Fully insulated cabinet
- Tool-less filter access door
Refrigerant System Features
- Acutrol™ refrigerant metering system on 04-06 models, TXV on 07 size models
- Liquid line filter drier
- Scroll compressors with internal line-break overload protection
- Indoor and outdoor coils constructed of aluminum fins mechanically bonded to seamless copper tubes
- Removable gauge line plugs for reading refrigerant pressure with unit panels in place
- Four-way reversing valve operation
- Suction line accumulator standard, preventing excessive liquid flood back to the compressor during defrost cycle starts
Standard Limited Parts Warranty
- 5-year electric heater (field-installed)
- 3-year SystemVu Controller
- 5-year compressor
- 1-year parts
Performance and Electrical Data
The following sections provide fields for performance and electrical data, typically filled out during system specification or installation. The unit is certified by AHRI and meets ASHRAE standards.
Performance Data Fields
- Unit Operating Weight: [ ] lb
- Curb Weight: [ ] lb
- COOLING Net Total Capacity: [ ] Btuh
- COOLING Net Sensible Capacity: [ ] Btuh
- COOLING Compressor Power Input: [ ] kW
- HEATING (ELECTRIC) Power Input to Unit: [ ] kW
- HEATING (ELECTRIC) Integrated Capacity: [ ] Btuh
- Indoor Operating Air Temperature: [ ] °F db
- at Outdoor Air Temperature: [ ] °F
- Outdoor Air Temperature: [ ] °F (Winter Design)
- Indoor Entering: db: [ ] °F / wb: [ ] °F
- Rating at 70% R.H. Outdoors: [ ] kW Heater Selected
- Airflow: [ ] CFM
- External Static Pressure: [ ] in. wg
- Heat/Cool Ratio: [ ]
- Electrical Capacity Required: [ ] Btuh
Electrical Data Fields
- Power Supply to Unit: [ ] Volts
- Phase: [ ] Hz
- Maximum Circuit Amps: [ ]
- Maximum Overcurrent Protection (Fuse Only): [ ]
Submittal Data Fields
- Job Name: [ ]
- Location: [ ]
- Buyer PO #: [ ]
- Carrier #: [ ]
- Unit Number: [ ]
- Model Number: [ ]
- Performance Data Certified By: [ ]
- Architect: [ ]
- Engineer: [ ]
- Contractor: [ ]
- Unit Designation: [ ]
Certifications include listings by UL and UL-Canada, compliance with ASHRAE 90.1, and AHRI certification for various standards (210/240, 340/360). The Puron® refrigerant is highlighted.
Factory-Installed Options
The following options can be factory-installed on the 50FCQ units:
- Economizer with DRY BULB Sensing and Barometric Relief (Standard Leak Air Dampers or ULTRA LOW LEAK Air Dampers)
- Economizer with ENTHALPY Sensing and Barometric Relief (Standard Leak Air Dampers or ULTRA LOW LEAK Air Dampers)
- SystemVu Controls (features include multi-line display, USB port, BACnet/CCN compatibility, pressure display, LED status, conventional stat/sensor capabilities, historical data, supply air tempering, and system compatibility)
- RTU Open multi-protocol controller communication (LonWorks, MODBUS, BACnet, Johnson N2)
- Through-the-base connectors for electric conduit
- Non-fused disconnect (80A max)
- Powered 115-volt convenience outlet
- Non-powered 115-volt convenience outlet
- High static evaporator fan motor
- Return air smoke detector
- Supply air smoke detector
- Smoke detectors (return and supply air)
- Pre-coated Al/Cu condenser coil
- E-coated Al/Cu condenser coil
- E-coated Al/Cu condenser and evaporator coil
- Cu/Cu condenser coil
- Cu/Cu condenser coil and evaporator coil
- Condenser hail guard - louvered style
- CO2 sensor
- Hinged access doors
- Condensate overflow switch
Optional Warranties are also available, including up to 5 years for complete unit parts and labor.
Field-Installed Accessories
The following accessories can be installed in the field:
- Power exhaust - vertical or horizontal
- Electric heat
- Single point kit
- Two-position motorized outdoor air damper
- Manual outdoor air damper (25% or 50%)
- Roof curb - 14 inch (356 mm) tall
- Roof curb - 24 inch (610 mm) tall
- Thru-the-bottom utility connection kit
- Time Guard II compressor anti-cycle control
- Outdoor coil hail guard - louvered style
- Programmable setback thermostat
- Phase monitor (loss of phase/phase reversal)
- Condensate overflow switch
Economizer Sensors
- Single dry bulb control
- Differential dry bulb control
- Single enthalpy control
- Differential enthalpy control
- CO2 - wall mounted
- CO2 - duct mounted
Certified Dimension Print
The Certified Dimension Print provides detailed physical dimensions and layout information for the 50FCQ 04-07 series units. It includes multiple views (top, front, side, bottom, perspective) with dimensions specified in both inches and millimeters.
Key Dimensional Information:
- Views: The diagrams show top, front, side (left/right), bottom, and perspective views of the unit, illustrating component placement and overall form factor.
- Dimensions: Specific measurements are provided for overall length, width, height, and the location of various components like the fan, coils, control box, and access panels.
- Connections: Details are provided for field power supply holes (e.g., 1 3/8" DIA, 2" DIA), control wiring holes (e.g., 7/8" DIA), and condensate drain connections (e.g., 3/4"-14 NPT). A "Thru-the-Base" chart specifies required holes for different wiring configurations.
- Weight: A table lists the standard unit operating weights (without electric heat and packaging) for models 50FCQ*04 through 50FCQ*07, ranging from 467 lbs to 589 lbs. Corner weights are also detailed.
- Clearances: Minimum service clearances are specified for operating and conductive/non-conductive barrier conditions for front, left, right, back (with/without economizer), and top sides. For example, front clearance is 48 inches (1219mm) for service.
- Access Panels: Locations and types of access panels are indicated, including filter access (tool-less), indoor coil, compressor, control box, and indoor blower access panels.
Roof Curb Details
This section details the roof curb accessories designed for the 50FCQ series units, ensuring proper installation and sealing on rooftops.
Roof Curb Accessories:
- Two standard roof curb accessory heights are available: 14 inches (356 mm) and 24 inches (610 mm).
- Construction: The curbs are constructed from 18-gage steel with insulated panels (1" thick polyurethane foam).
- Dimensions: Specific dimensions for supply air and return air openings, as well as overall curb dimensions, are provided in inches and millimeters. For example, the 14-inch curb has a supply air opening of approximately 21.74" x 11.96" and a return air opening of approximately 15.19" x 11.96".
- Installation Notes: Instructions cover attaching ductwork to the curb, service clearances (4 feet on each side), and direction of airflow.
- Connection Packages: Accessory connector packages (e.g., CRBTMPWR001A01 for thru-the-curb gas, CRBTMPWR003A01 for thru-the-bottom gas) are detailed with their corresponding gas and power wiring fittings.
- Cross-section: A detailed cross-section (Section E-E) illustrates the layers of the roof curb assembly, including insulated deck panels, roofing felt, cant strip, and roofing material.