Installer's Guide: Trane TEM6 Series Convertible Air Handlers
The TEM6 series air handler is designed for versatile installation in various locations including closets, utility rooms, alcoves, basements, crawl spaces, or attics. These units are suitable for air conditioning and heat pump applications, with several models available to match specific outdoor equipment requirements. Field-installed electric resistance heaters are also available. WARNING: Only qualified personnel should install and service this equipment. Improper installation or servicing by unqualified individuals can result in death or serious injury. Always observe all precautions listed in the literature and on equipment tags, stickers, and labels. WARNING: HAZARDOUS VOLTAGE! Disconnect all electric power, including remote disconnects, before servicing. Follow proper lockout/tagout procedures to prevent accidental energization. CAUTION: GROUNDING REQUIRED! Ensure all grounding devices are inspected and properly reconnected. All parts capable of conducting electrical current must be grounded. WARNING: LIVE ELECTRICAL COMPONENTS! Follow all electrical safety precautions when working with live components during installation, testing, servicing, or troubleshooting. WARNING: PRESSURIZED REFRIGERANT! System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. Do not use non-approved refrigerants, substitutes, or additives. CAUTION: SHARP EDGE HAZARD! Be careful of sharp edges on equipment or sheet metal cuts during installation or servicing. CAUTION: HAZARDOUS VAPORS! Avoid using the air handler during finishing phases of construction or remodeling to prevent corrosion damage from condensate forming in the presence of chlorides and fluorides from paints, varnishes, adhesives, etc. CAUTION: COIL IS PRESSURIZED! The coil is pressurized with approximately 8-12 psi dry air and factory leak-checked. Carefully release pressure by removing the rubber plug on the liquid line. Check for leaks if no pressure is released. SAFETY HAZARD! This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless supervised or instructed. WARNING: Children should be supervised to ensure they do not play with the appliance. WARNING: California Proposition 65. This product can expose you to chemicals, including lead, known to the State of California to cause cancer and birth defects or other reproductive harm. For more information, visit www.P65Warnings.ca.gov. Installation must comply with the National Electric Code (NFPA No. 90A and 90B) and any other local codes or utility requirements. These air handlers have been evaluated and are suitable for mobile home use. Condensation may occur on the air handler surface when installed in unconditioned spaces. Ensure all electrical and refrigerant line penetrations are sealed completely in such installations. The manufacturer recommends installing AHRI-approved, matched indoor and outdoor systems for maximum efficiency, optimum performance, and reliability. Carefully unpack the unit and inspect for damage. Notify the carrier immediately if damage is found. Verify the rating plate matches the ordered model number and voltage. Report any discrepancies or parts shortages to the manufacturer within 5 days. Install the air handler centrally. Ensure minimum clearances are met. A downflow sub-base may be required for electric heat applications. The unit must be installed level to ensure proper condensation drainage; a slight slope (up to 1/4 inch over width/depth) towards the drain is permissible. For closet/utility room installations, ensure adequate space for replacement and servicing (21" clearance from front). For unconditioned spaces (attics, crawl spaces), ensure sufficient air circulation to prevent moisture collection. A drain pan is mandatory under the unit in these locations or above finished ceilings. Install duct work in accordance with NFPA No. 90A and 90B, and applicable building codes. Insulate duct work as required by governing bodies. The unit has primary and auxiliary 3/4" NPT condensate drains. The primary drain must be trapped outside the unit and piped per building codes. The trap's water column height must at least equal the normal negative static pressure during operation. A greater height is advisable to account for static increases from dirty filters or start-up bounce. Do not reduce the drain line size below the pan connection. All drains must pitch downward at a minimum of 1/4" per foot. If a cleanout Tee is used, the standpipe must be sealed/capped. If a vent Tee is used, it must be downstream from the trap. Diagram Description: A diagram shows a U-shaped condensate trap. 'A' indicates the water column height, equal to the system's negative static pressure. 'C' indicates a dimension that should be at least twice the maximum negative static pressure. Insulate the primary drain line to prevent sweating where dew point temperatures may be encountered. Size external refrigerant piping according to the outdoor equipment manufacturer's instructions. All units are shipped with an internally-checked, non-bleed TXV designed for AC or heat pump operation. Some outdoor models may require a start assist kit. The unit features a variable speed motor with a direct drive blower wheel for adjustable airflow. Factory settings are provided for cooling and heating. Performance tables are available for additional airflow settings. Always disconnect power before making adjustments. CAUTION: EQUIPMENT DAMAGE! Failure to follow this procedure may result in equipment damage. Disconnect power before changing dip switch positions. Blower speed is controlled by the ECM Fan Control. An 8-dip switch bank adjusts airflow for outdoor unit size (tons), cooling/heating airflow, and fan off-delay options. Refer to the Airflow Label on the unit or Blower Performance Tables for correct settings. Diagram Description (Figure 1): The ECM Fan Control shows a CFM Selection Light and DIP Switches. Diagram Description (Figure 2): The DIP Switches are labeled for Cooling Airflow (SW1-SW4), Fan Off Delay Options (SW5-SW6), and Auxiliary Heat Speeds (SW7-SW8). Indoor Blower Timing: Leave dip switches 5 and 6 in their factory-shipped positions during initial system startup and checkout. Adjust as needed afterward. (a) Default setting. (b) Enhanced Mode provides gradual blower speed changes for improved comfort, quietness, and potential energy savings. Diagram Description (Figure 3): A graph illustrates blower operation (CFM) over time for Enhanced Mode, showing ramping up and down of fan speed during compressor operation and heating/cooling cycles. Consult all unit and outdoor equipment wiring diagrams for compatibility and specific requirements. Field wiring must comply with the latest National Electric Code (NFPA No. 70) and local codes. Check unit rating plates for voltage, minimum circuit ampacity (MCA), and maximum overcurrent protection (MOP). Use only 75°C minimum copper conductors, sized per code. The unit is shipped wired for 230/240V AC, 60Hz, 1 Phase. For 208V operation, adjust the low voltage transformer per the wiring diagram. Class 2 low voltage control wiring must be separated from power wiring unless appropriate Class 1 wire is used. Use 18 AWG (105°C minimum) color-coded wire for low voltage control wiring; use 16 AWG for lengths over 100 ft. Ensure separation between control and power wiring. Wiring Diagram Descriptions: Notes for wiring diagrams: Use wirenuts for pigtail connections. Cap all unused wires. For BK enabled comfort control, do not connect Y1 or Y2 at the air handler and cut the jumper between R and BK on the control board. For systems with multiple stages of electric heat, jumper W1 and W2 together if the comfort control has only one stage of heat. An air filter must be installed before the evaporator coil to protect internal components. Consult the filter manufacturer for proper sizing and maximum velocity requirements. Air filters must meet UL 900 test requirements. Select a thermostat compatible with single-stage heating/cooling and electric heat. Install the thermostat on an inside wall, away from drafts, lights, or heat sources, in a location with sufficient air circulation. Cooling (Cooling only): Thermostat R-G energizes the blower via ECM control. Thermostat R-Y energizes the outdoor unit compressor and condenser fan. Cooling (Heat pump): Thermostat R-G energizes the blower. Thermostat R-Y energizes the outdoor unit compressor and fan. Thermostat R-O energizes the reversing valve for cooling. Heating (Heat pump): Thermostat R-G energizes the blower. Thermostat R-Y energizes the outdoor unit compressor and fan. Reversing valve is not energized for heating. If temperature drops, R-W circuit energizes electric heat contactors. Heating (Electric heat only): Thermostat R-G energizes the blower. Thermostat R-W energizes heating contactors. Ensure thermostat is set to bring on the blower with electric heat. Defrost: Connect the X2 (black) wire from the outdoor unit to W1 or W2 at the indoor unit for supplemental heat during defrost, preventing cold air discharge. Ensure proper performance by operating and charging the system according to the outdoor unit's Service Facts document. Review the checkout list provided in this document upon completion of installation. Inspect, clean, or replace system air filters monthly. Ensure access panels are replaced and secured before operation. Schedule annual professional servicing, including inspection of electrical and refrigerant components, and cleaning of heat transfer surfaces. The blower motor is permanently lubricated. The following tables detail airflow performance (CFM, Watts) for various models and settings under different external static pressures. (a) Factory Default Setting (a) Factory Default Setting (a) Factory Default Setting (a) Factory Default Setting (a) Factory Default Setting (a) Factory Default Setting (a) Factory Default Setting. (b) Airflow must not exceed 1800 cfm in horizontal right, horizontal left, and downflow applications due to condensate blowoff. The 5 ton high tap shall not be used in these applications. (a) Factory Default Setting * = Motor Amps. (a) MCA and MOP for circuit 1 includes motor amps. * = Motor Amps. (a) MCA and MOP for circuit 1 includes motor amps. * = Motor Amps. (a) MCA and MOP for circuit 1 includes motor amps. * = Motor Amps. (a) MCA and MOP for circuit 1 includes motor amps. TEM6A0B24H21SC, TEM6A0B30H21SC See following tables for heater application: - Pressure Drop for Electrical Heaters - Minimum Heating Airflow Matrix (on unit nameplates) TEM6A0C36H31SC, TEM6A0C42H41SC See following tables for heater application: - Pressure Drop for Electrical Heaters - Minimum Heating Airflow Matrix (on unit nameplates) TEM6A0C48H41SC, TEM6B0C60H51SA See following tables for heater application: - Pressure Drop for Electrical Heaters - Minimum Heating Airflow Matrix (on unit nameplates) System Matched with: All other matches must be charged per the nameplate charging instructions. Follow these steps to install the air handler in a downflow configuration: Follow these steps to install the air handler in a horizontal right configuration: The final phase of installation involves system checkout. Confirm all requirements have been met: Trane and American Standard create comfortable, energy-efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com. The manufacturer has a policy of continuous data improvement and reserves the right to change design and specifications without notice. This document is printed using environmentally conscious practices.Safety Warnings
Installation Requirements
Features
Standard Features
Optional Accessories
Installation Instructions
1. Unpacking
2. Location
3. Duct Work
4. Condensate Drain
5. Refrigerant Piping
6. Metering Device
7. Blower
8. Airflow Adjustment
Switch Settings Selection Nominal Airflow 5 -- OFF, 6 -- OFF NONE SAME 5 -- ON, 6 -- OFF 1.5 MINUTES 100% (a) 5 -- OFF, 6 -- ON 3 MINUTES 50% 5 -- ON, 6 -- ON ENHANCED (b) 50%-100% 9. Wiring
10. Air Filter
11. Thermostat
12. Sequence of Operation
13. Operational and Checkout Procedures
14. Maintenance
Performance and Electrical Data
Air Flow Performance
OUTDOOR UNIT SIZE (TONS) SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9 1.5 LOW 353 CFM/ton ON ON OFF ON CFM: 533, 497, 461, 425, 390
Watts: 52, 78, 104, 130, 157NORMAL 401 CFM/ton ON ON OFF OFF CFM: 611, 580, 548, 517, 486
Watts: 65, 95, 125, 155, 185HIGH 451 CFM/ton ON ON ON OFF CFM: 684, 668, 644, 611, 570
Watts: 81, 115, 148, 182, 2152 LOW 343 CFM/ton OFF ON OFF ON CFM: 687, 672, 648, 614, 571
Watts: 82, 115, 149, 182, 215NORMAL 390 CFM/ton OFF ON OFF OFF CFM: 789, 798, 780, 735, 663
Watts: 104, 145, 183, 216, 246HIGH 439 CFM/ton OFF ON ON OFF CFM: 884, 887, 882, 845, 751
Watts: 135, 177, 230, 274, 2902.5 LOW 300 CFM/ton ON OFF OFF ON CFM: 752, 749, 729, 691, 636
Watts: 92, 123, 167, 211, 241NORMAL (a) 340 CFM/ton ON OFF OFF OFF CFM: 859, 861, 863, 830, 727
Watts: 128, 172, 211, 242, 268HIGH 383 CFM/ton ON OFF ON OFF CFM: 963, 973, 995, 967, 844
Watts: 172, 223, 263, 291, 308OUTDOOR UNIT SIZE (TONS) SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9 1.5 LOW 394 CFM/ton ON ON OFF ON CFM: 599, 571, 539, 502, 462
Watts: 58, 88, 117, 146, 175NORMAL 448 CFM/ton ON ON OFF OFF CFM: 680, 665, 641, 610, 572
Watts: 72, 109, 145, 178, 209HIGH 493 CFM/ton ON ON ON OFF CFM: 748, 746, 682, 545, 326
Watts: 89, 118, 163, 208, 2402 LOW 393 CFM/ton OFF ON OFF ON CFM: 785, 790, 773, 735, 674
Watts: 97, 128, 175, 223, 253NORMAL 446 CFM/ton OFF ON OFF OFF CFM: 904, 902, 912, 894, 809
Watts: 131, 179, 219, 253, 281HIGH 491 CFM/ton OFF ON ON OFF CFM: 980, 972, 990, 974, 863
Watts: 167, 216, 268, 308, 3242.5 LOW 350 CFM/ton ON OFF OFF ON CFM: 866, 870, 866, 833, 750
Watts: 125, 162, 215, 263, 286NORMAL (a) 398 CFM/ton ON OFF OFF OFF CFM: 995, 988, 1005, 986, 872
Watts: 171, 222, 271, 309, 325HIGH 437 CFM/ton ON OFF ON OFF CFM: 1099, 1086, 1098, 1065, 918
Watts: 220, 274, 328, 362, 3533 LOW 310 CFM/ton OFF OFF OFF ON CFM: 913, 947, 962, 938, 883
Watts: 119, 172, 233, 297, 364NORMAL (a) 330 CFM/ton OFF OFF OFF OFF CFM: 967, 1004, 1022, 1000, 947
Watts: 138, 194, 258, 326, 397OUTDOOR UNIT SIZE (TONS) SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9 1.5 LOW 353 CFM/ton ON ON OFF ON CFM: 533, 497, 461, 425, 390
Watts: 52, 78, 104, 130, 157NORMAL 401 CFM/ton ON ON OFF OFF CFM: 611, 580, 548, 517, 486
Watts: 65, 95, 125, 155, 185HIGH 451 CFM/ton ON ON ON OFF CFM: 684, 668, 644, 611, 570
Watts: 81, 115, 148, 182, 2152 LOW 343 CFM/ton OFF ON OFF ON CFM: 687, 672, 648, 614, 571
Watts: 82, 115, 149, 182, 215NORMAL 390 CFM/ton OFF ON OFF OFF CFM: 789, 798, 780, 735, 663
Watts: 104, 145, 183, 216, 246HIGH 439 CFM/ton OFF ON ON OFF CFM: 884, 887, 882, 845, 751
Watts: 135, 177, 230, 274, 2902.5 LOW 300 CFM/ton ON OFF OFF ON CFM: 752, 749, 729, 691, 636
Watts: 92, 123, 167, 211, 241NORMAL 340 CFM/ton ON OFF OFF OFF CFM: 859, 861, 863, 830, 727
Watts: 128, 172, 211, 242, 268HIGH 383 CFM/ton ON OFF ON OFF CFM: 963, 973, 995, 967, 844
Watts: 172, 223, 263, 291, 3083 LOW 310 CFM/ton OFF OFF OFF ON CFM: 913, 947, 962, 938, 883
Watts: 119, 172, 233, 297, 364NORMAL (a) 330 CFM/ton OFF OFF OFF OFF CFM: 967, 1004, 1022, 1000, 947
Watts: 138, 194, 258, 326, 397OUTDOOR UNIT SIZE (TONS) SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9 1.5 LOW 394 CFM/ton ON ON OFF ON CFM: 599, 571, 539, 502, 462
Watts: 58, 88, 117, 146, 175NORMAL 448 CFM/ton ON ON OFF OFF CFM: 680, 665, 641, 610, 572
Watts: 72, 109, 145, 178, 209HIGH 493 CFM/ton ON ON ON OFF CFM: 748, 746, 682, 545, 326
Watts: 89, 118, 163, 208, 2402 LOW 393 CFM/ton OFF ON OFF ON CFM: 785, 790, 773, 735, 674
Watts: 97, 128, 175, 223, 253NORMAL 446 CFM/ton OFF ON OFF OFF CFM: 904, 902, 912, 894, 809
Watts: 131, 179, 219, 253, 281HIGH 491 CFM/ton OFF ON ON OFF CFM: 980, 972, 990, 974, 863
Watts: 167, 216, 268, 308, 3242.5 LOW 350 CFM/ton ON OFF OFF ON CFM: 866, 870, 866, 833, 750
Watts: 125, 162, 215, 263, 286NORMAL 398 CFM/ton ON OFF OFF OFF CFM: 995, 988, 1005, 986, 872
Watts: 171, 222, 271, 309, 325HIGH 437 CFM/ton ON OFF ON OFF CFM: 1099, 1086, 1098, 1065, 918
Watts: 220, 274, 328, 362, 3533 LOW 325 CFM/ton OFF OFF OFF ON CFM: 953, 990, 1007, 985, 931
Watts: 133, 188, 251, 318, 389NORMAL (a) 346 CFM/ton OFF OFF OFF OFF CFM: 1010, 1049, 1066, 1047, 1000
Watts: 154, 212, 279, 350, 426OUTDOOR UNIT SIZE (TONS) SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9 2.5 LOW 300 CFM/ton ON ON OFF ON CFM: 761, 755, 719, 654, 560
Watts: 63, 98, 131, 163, 193NORMAL 341 CFM/ton ON ON OFF OFF CFM: 862, 861, 834, 781, 700
Watts: 82, 120, 158, 196, 235HIGH 384 CFM/ton ON ON ON OFF CFM: 962, 963, 948, 915, 863
Watts: 106, 147, 190, 234, 2793 LOW 319 CFM/ton OFF ON OFF ON CFM: 961, 962, 947, 914, 862
Watts: 106, 147, 189, 233, 279NORMAL 363 CFM/ton OFF ON OFF OFF CFM: 1092, 1093, 1082, 1060, 1026
Watts: 146, 192, 240, 288, 337HIGH 408 CFM/ton OFF ON ON OFF CFM: 1231, 1231, 1221, 1203, 1175
Watts: 196, 249, 301, 353, 4043.5 LOW 315 CFM/ton ON OFF OFF ON CFM: 1104, 1105, 1094, 1072, 1039
Watts: 150, 197, 245, 293, 343NORMAL 357 CFM/ton ON OFF OFF OFF CFM: 1258, 1258, 1248, 1229, 1201
Watts: 209, 263, 317, 369, 421HIGH 402 CFM/ton ON OFF ON OFF CFM: 1418, 1415, 1401, 1379, 1348
Watts: 286, 347, 406, 462, 5164 LOW 308 CFM/ton OFF OFF OFF ON CFM: 1238, 1238, 1229, 1210, 1182
Watts: 199, 253, 306, 357, 408NORMAL (a) 350 CFM/ton OFF OFF OFF OFF CFM: 1412, 1410, 1398, 1378, 1349
Watts: 282, 344, 404, 462, 517HIGH 394 CFM/ton OFF OFF ON OFF CFM: 1570, 1528, 1473, 1406, 1326
Watts: 393, 436, 466, 483, 488OUTDOOR UNIT SIZE (TONS) SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9 2.5 LOW 341 CFM/ton ON ON OFF ON CFM: 860, 863, 838, 788, 707
Watts: 77, 115, 154, 193, 232NORMAL 379 CFM/ton ON ON OFF OFF CFM: 949, 953, 937, 906, 852
Watts: 98, 138, 180, 224, 269HIGH 417 CFM/ton ON ON ON OFF CFM: 1042, 1046, 1036, 1015, 980
Watts: 122, 166, 212, 259, 3083 LOW 381 CFM/ton OFF ON OFF ON CFM: 1147, 1149, 1141, 1123, 1094
Watts: 154, 203, 253, 303, 353NORMAL 424 CFM/ton OFF ON OFF OFF CFM: 1277, 1279, 1272, 1255, 1228
Watts: 204, 259, 314, 368, 421HIGH 466 CFM/ton OFF ON ON OFF CFM: 1409, 1409, 1401, 1384, 1357
Watts: 260, 323, 383, 442, 5003.5 LOW 348 CFM/ton ON OFF OFF ON CFM: 1222, 1224, 1216, 1200, 1174
Watts: 180, 232, 285, 336, 388NORMAL 386 CFM/ton ON OFF OFF OFF CFM: 1361, 1362, 1354, 1337, 1310
Watts: 240, 300, 358, 415, 471HIGH 425 CFM/ton ON OFF ON OFF CFM: 1497, 1478, 1449, 1408, 1356
Watts: 316, 372, 420, 461, 4944 LOW 338 CFM/ton OFF OFF OFF ON CFM: 1360, 1361, 1353, 1336, 1309
Watts: 239, 299, 358, 415, 470NORMAL (a) 375 CFM/ton OFF OFF OFF OFF CFM: 1511, 1489, 1456, 1412, 1355
Watts: 325, 380, 426, 464, 493HIGH 413 CFM/ton OFF OFF ON OFF CFM: 1659, 1605, 1535, 1450, 1349
Watts: 420, 463, 488, 494, 483OUTDOOR UNIT SIZE (TONS) SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9 3 LOW 324 CFM/ton ON ON OFF ON CFM: 991, 985, 974, 984, 994
Watts: 89, 133, 186, 237, 303NORMAL 368 CFM/ton ON ON OFF OFF CFM: 1120, 1119, 1110, 1116, 1122
Watts: 118, 167, 224, 279, 333HIGH 423 CFM/ton ON ON ON OFF CFM: 1282, 1286, 1281, 1280, 1282
Watts: 162, 219, 280, 343, 4023.5 LOW 314 CFM/ton OFF ON OFF ON CFM: 1116, 1114, 1105, 1111, 1117
Watts: 117, 165, 222, 277, 331NORMAL 357 CFM/ton OFF ON OFF OFF CFM: 1263, 1266, 1261, 1261, 1263
Watts: 156, 212, 273, 334, 392HIGH 411 CFM/ton OFF ON ON OFF CFM: 1449, 1458, 1456, 1449, 1447
Watts: 218, 287, 352, 421, 4964 LOW 298 CFM/ton ON OFF OFF ON CFM: 1207, 1208, 1201, 1203, 1207
Watts: 140, 193, 252, 311, 366NORMAL 339 CFM/ton ON OFF OFF OFF CFM: 1368, 1374, 1370, 1367, 1367
Watts: 190, 252, 315, 381, 448HIGH 389 CFM/ton ON OFF ON OFF CFM: 1564, 1577, 1577, 1567, 1561
Watts: 264, 343, 411, 484, 5705 LOW 305 CFM/ton OFF OFF OFF ON CFM: 1534, 1545, 1545, 1536, 1531
Watts: 251, 328, 394, 467, 550NORMAL (a) 347 CFM/ton OFF OFF OFF OFF CFM: 1740, 1758, 1762, 1745, 1734
Watts: 344, 444, 518, 594, 684HIGH (b) 399 CFM/ton OFF OFF ON OFF CFM: 1995, 2022, 2030, 2005, 1987
Watts: 484, 629, 717, 783, 828OUTDOOR UNIT SIZE (TONS) SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9 3 LOW 360 CFM/ton ON ON OFF ON CFM: 1097, 1094, 1086, 1092, 1099
Watts: 112, 160, 216, 271, 326NORMAL 400 CFM/ton ON ON OFF OFF CFM: 1215, 1216, 1210, 1211, 1215
Watts: 142, 196, 255, 314, 369HIGH 440 CFM/ton ON ON ON OFF CFM: 1333, 1338, 1333, 1331, 1332
Watts: 178, 238, 300, 365, 4283.5 LOW 348 CFM/ton OFF ON OFF ON CFM: 1232, 1234, 1228, 1229, 1233
Watts: 147, 202, 261, 322, 377NORMAL 387 CFM/ton OFF ON OFF OFF CFM: 1366, 1373, 1369, 1366, 1365
Watts: 189, 252, 314, 381, 447HIGH 426 CFM/ton OFF ON ON OFF CFM: 1500, 1511, 1510, 1502, 1498
Watts: 238, 311, 377, 449, 5294 LOW 338 CFM/ton ON OFF OFF ON CFM: 1364, 1370, 1366, 1363, 1363
Watts: 188, 251, 313, 379, 446NORMAL 375 CFM/ton ON OFF OFF OFF CFM: 1509, 1520, 1519, 1511, 1506
Watts: 241, 315, 382, 453, 535HIGH 413 CFM/ton ON OFF ON OFF CFM: 1659, 1674, 1676, 1662, 1654
Watts: 305, 395, 466, 541, 6325 LOW 326 CFM/ton OFF OFF OFF ON CFM: 1637, 1652, 1653, 1641, 1632
Watts: 295, 383, 453, 528, 618NORMAL (a) 362 CFM/ton OFF OFF OFF OFF CFM: 1814, 1834, 1839, 1820, 1807
Watts: 381, 493, 570, 645, 730HIGH 398 CFM/ton OFF OFF ON OFF CFM: 1990, 2017, 2025, 2000, 1982
Watts: 481, 625, 713, 779, 826Heater Model No. No. of Circuits/Phases 240 Volt 208 Volt Capacity kW BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection Capacity kW BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection No Heater BAYHTR1504BRK
BAYHTR1504LUG1/1 3.84 13100 16.0 23 30 2.88 9800 13.8 20 BAYHTR1505BRK
BAYHTR1505LUG1/1 4.80 16400 20.0 28 35 3.60 12300 17.3 25 BAYHTR1508BRK
BAYHTR1508LUG1/1 7.68 26200 32.0 43 55 5.76 19700 27.7 40 BAYHTR1510BRK
BAYHTR1510LUG1/1 9.60 32800 40.0 53 75 7.20 24600 34.6 50 BAYHTR1517BRK Circuit 1 (a) 2/1 9.60 32800 40.0 53 75 7.20 24600 34.6 50 BAYHTR1517BRK Circuit 2 4.80 16400 20.0 25 35 3.60 12300 17.3 25 BAYHTR3510LUG 1/3 9.60 32800 23.1 32 45 7.20 24600 20.0 30 BAYHTR3517LUG 1/3 14.40 49100 34.6 46 60 10.80 36900 30.0 40 Heater Model No. No. of Circuits/Phases 240 Volt 208 Volt Capacity kW BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection Capacity kW BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection No Heater BAYHTR1504BRK
BAYHTR1504LUG1/1 3.84 13100 16.0 25 30 2.88 9800 13.8 23 BAYHTR1505BRK
BAYHTR1505LUG1/1 4.80 16400 20.0 30 40 3.60 12300 17.3 27 BAYHTR1508BRK
BAYHTR1508LUG1/1 7.68 26200 32.0 45 60 5.76 19700 27.7 40 BAYHTR1510BRK
BAYHTR1510LUG1/1 9.60 32800 40.0 55 75 7.20 24600 34.6 49 BAYHTR1517BRK Circuit 1 (a) 2/1 9.60 32800 40.0 55 75 7.20 24600 34.6 49 BAYHTR1517BRK Circuit 2 4.80 16400 20.0 25 35 3.60 12300 17.3 25 BAYHTR3510LUG 1/3 9.60 32800 23.1 34 45 7.20 24600 20.0 30 BAYHTR3517LUG 1/3 14.40 49100 34.6 48 60 10.80 36900 30.0 42 Heater Model No. No. of Circuits/Phases 240 Volt 208 Volt Capacity kW BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection Capacity kW BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection No Heater BAYHTR1504BRK
BAYHTR1504LUG1/1 3.84 13100 16.0 25 30 2.88 9800 13.8 23 BAYHTR1505BRK
BAYHTR1505LUG1/1 4.80 16400 20.0 30 40 3.60 12300 17.3 27 BAYHTR1508BRK
BAYHTR1508LUG1/1 7.68 26200 32.0 45 60 5.76 19700 27.7 40 BAYHTR1510BRK
BAYHTR1510LUG1/1 9.60 32800 40.0 55 75 7.20 24600 34.6 49 BAYHTR1517BRK Circuit 1 (a) 2/1 9.60 32800 40.0 55 75 7.20 24600 34.6 49 BAYHTR1517BRK Circuit 2 4.80 16400 20.0 25 35 3.60 12300 17.3 25 BAYHTR1523BRK Circuit 1 (a) 2/1 9.60 32800 40.0 55 75 7.20 24600 34.6 49 BAYHTR1523BRK Circuit 2 9.60 32800 40.0 50 75 7.20 24600 34.6 45 BAYHTR3510LUG 1/3 9.60 32800 23.1 34 45 7.20 24600 20.0 30 BAYHTR3517LUG 1/3 14.40 49100 34.6 48 60 10.80 36900 30.0 42 Heater Model No. No. of Circuits/Phases 240 Volt 208 Volt Capacity kW BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection Capacity kW BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection No Heater BAYHTR1504BRK
BAYHTR1504LUG1/1 3.84 13100 16.0 29 15 2.88 9800 13.8 26 BAYHTR1505BRK
BAYHTR1505LUG1/1 4.80 16400 20.0 34 35 3.60 12300 17.3 30 BAYHTR1508BRK
BAYHTR1508LUG1/1 7.68 26200 32.0 49 50 5.76 19700 27.7 43 BAYHTR1510BRK
BAYHTR1510LUG1/1 9.60 32800 40.0 59 60 7.20 24600 34.6 52 BAYHTR1517BRK Circuit 1 (a) 2/1 9.60 32800 40.0 59 75 7.20 24600 34.6 52 BAYHTR1517BRK Circuit 2 4.80 16400 20.0 25 35 3.60 12300 17.3 27 BAYHTR1523BRK Circuit 1 (a) 2/1 9.60 32800 40.0 59 75 7.20 24600 34.6 52 BAYHTR1523BRK Circuit 2 9.60 32800 40.0 50 75 7.20 24600 34.6 43 BAYHTR1525BRK Circuit 1 (a) 4/1 6.00 20500 25.0 40 40 4.50 15400 21.6 36 BAYHTR1525BRK Circuit 2 6.00 20500 25.0 31 35 4.50 15400 21.6 27 BAYHTR1525BRK Circuit 3 6.00 20500 25.0 31 35 4.50 15400 21.6 27 BAYHTR1525BRK Circuit 4 6.00 20500 25.0 31 35 4.50 15400 21.6 27 BAYHTR3510LUG 1/3 9.60 32800 23.1 36 35 4.50 15400 21.6 27 BAYHTR3517LUG 1/3 14.40 49100 34.6 51 60 10.80 36900 30.0 45 Minimum Airflow CFM
Heater With Heat Pump Without Heat Pump BAYHTR1504BRK, BAYHTR1504LUG 660 600 BAYHTR1505BRK, BAYHTR1505LUG 780 600 BAYHTR1508BRK, BAYHTR1508LUG 780 600 BAYHTR1510BRK, BAYHTR1510LUG 1050 850 BAYHTR1517BRK 780 600 BAYHTR3510LUG 900 850 BAYHTR3517LUG Heater With Heat Pump Without Heat Pump BAYHTR1504BRK, BAYHTR1504LUG 875 675 BAYHTR1505BRK, BAYHTR1505LUG 950 820 BAYHTR1508BRK, BAYHTR1508LUG 1000 820 BAYHTR1510BRK, BAYHTR1510LUG 1000 820 BAYHTR1517BRK 875 820 BAYHTR3510LUG 1000 950 BAYHTR3517LUG 1300 1140 BAYHTR1523BRK Heater With Heat Pump Without Heat Pump BAYHTR1504BRK, BAYHTR1504LUG 1200 975 BAYHTR1505BRK, BAYHTR1505LUG 1350 975 BAYHTR1508BRK, BAYHTR1508LUG 1350 975 BAYHTR1510BRK, BAYHTR1510LUG 1365 975 BAYHTR1517BRK 1300 1120 BAYHTR3510LUG 1365 1300 BAYHTR3517LUG 1810 1505 BAYHTR1523BRK BAYHTR1525BRK Airflow Performance with Auxiliary Heat
Airflow Settings Dip Switch Settings Nominal Airflow Switch 7 Switch 8 Low ON ON 601 Med-Lo OFF ON 661 Med-Hi ON OFF 781 High OFF OFF 973 Airflow Settings Dip Switch Settings Nominal Airflow Switch 7 Switch 8 Low ON ON 696 Med-Lo OFF ON 825 Med-Hi ON OFF 1150 High OFF OFF 1298 Airflow Settings Dip Switch Settings Nominal Airflow Switch 7 Switch 8 Low ON ON 1000 Med-Lo OFF ON 1130 Med-Hi ON OFF 1354 High OFF OFF 1596 Heater Pressure Drop Table
Airflow CFM Air Pressure Drop -- Inches W.G. 1 Rack 2 Racks 3 Racks 4 Racks 1800 0.02 0.04 0.06 0.14 1700 0.02 0.04 0.06 0.14 1600 0.02 0.04 0.06 0.13 1500 0.02 0.04 0.06 0.12 1400 0.02 0.04 0.06 0.12 1300 0.02 0.04 0.05 0.11 1200 0.01 0.04 0.05 0.10 1100 0.01 0.03 0.05 0.09 1000 0.01 0.03 0.04 0.09 900 0.01 0.03 0.04 0.08 800 0.01 0.03 0.03 700 0.01 0.02 0.02 600 0.01 0.02 Heater Model No. of Racks BAYHTR1504 1 BAYHTR1505 1 BAYHTR1508 2 BAYHTR1510 2 BAYHTR1517 3 BAYHTR3510 3 BAYHTR3517 3 BAYHTR1523 4 BAYHTR1525 4 Subcooling Adjustment
Indoor Unit Model No. Outdoor Unit Size Outdoor Model No. Subcooling TEM6A0C36H31 16 SEER HP -- 2 ton 4TWR6024H1000A 13 Degrees TEM6A0B24H21 15 SEER HP -- 2 ton 4TWX6024H1000A 14 Degrees TEM6A0B30H21 15 SEER HP -- 2 ton 4A6H6024H1000A 14 Degrees TEM6A0B30H21 4TWR5024G1000A TEM6A0C36H31 4A6H5024G1000A TEM6A0C42H41 15 SEER HP -- 3 ton 4TWR5036G1000A 4A6H5036G1000A OD Equipment Sub-Cooling Charge Specification For AHRI Rated Performance Up Flow / Horizontal Down Flow AC UNIT 3.5 Tons OD Name Plate OD Name Plate HP UNIT = 4 and 5 Tons OD Name Plate OD Name Plate + 4 Degrees Coil Conversion Instructions
Downflow Configuration
Horizontal Right Configuration
Checkout Procedures
About Trane