Installer's Guide: Trane TEM6 Series Convertible Air Handlers

The TEM6 series air handler is designed for versatile installation in various locations including closets, utility rooms, alcoves, basements, crawl spaces, or attics. These units are suitable for air conditioning and heat pump applications, with several models available to match specific outdoor equipment requirements. Field-installed electric resistance heaters are also available.

Safety Warnings

WARNING: Only qualified personnel should install and service this equipment. Improper installation or servicing by unqualified individuals can result in death or serious injury. Always observe all precautions listed in the literature and on equipment tags, stickers, and labels.

WARNING: HAZARDOUS VOLTAGE! Disconnect all electric power, including remote disconnects, before servicing. Follow proper lockout/tagout procedures to prevent accidental energization.

CAUTION: GROUNDING REQUIRED! Ensure all grounding devices are inspected and properly reconnected. All parts capable of conducting electrical current must be grounded.

WARNING: LIVE ELECTRICAL COMPONENTS! Follow all electrical safety precautions when working with live components during installation, testing, servicing, or troubleshooting.

WARNING: PRESSURIZED REFRIGERANT! System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. Do not use non-approved refrigerants, substitutes, or additives.

CAUTION: SHARP EDGE HAZARD! Be careful of sharp edges on equipment or sheet metal cuts during installation or servicing.

CAUTION: HAZARDOUS VAPORS! Avoid using the air handler during finishing phases of construction or remodeling to prevent corrosion damage from condensate forming in the presence of chlorides and fluorides from paints, varnishes, adhesives, etc.

CAUTION: COIL IS PRESSURIZED! The coil is pressurized with approximately 8-12 psi dry air and factory leak-checked. Carefully release pressure by removing the rubber plug on the liquid line. Check for leaks if no pressure is released.

SAFETY HAZARD! This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless supervised or instructed.

WARNING: Children should be supervised to ensure they do not play with the appliance.

WARNING: California Proposition 65. This product can expose you to chemicals, including lead, known to the State of California to cause cancer and birth defects or other reproductive harm. For more information, visit www.P65Warnings.ca.gov.

Installation Requirements

Installation must comply with the National Electric Code (NFPA No. 90A and 90B) and any other local codes or utility requirements.

These air handlers have been evaluated and are suitable for mobile home use.

Condensation may occur on the air handler surface when installed in unconditioned spaces. Ensure all electrical and refrigerant line penetrations are sealed completely in such installations.

The manufacturer recommends installing AHRI-approved, matched indoor and outdoor systems for maximum efficiency, optimum performance, and reliability.

Features

Standard Features

  • Multi-position installation: Upflow, Downflow, Horizontal Left, and Horizontal Right.
  • Painted finish on galvanized steel exterior with a fully insulated cabinet (R4.2 value).
  • Sturdy polycarbonate drain pans.
  • Factory installed drain pans shipped for upflow and horizontal left applications.
  • 208/230 VAC operation.
  • Variable-speed direct drive blower.
  • Factory installed R-410A Thermal Expansion Valve (TXV).
  • All aluminum coil.
  • Bottom return.
  • Meets minimum leakage requirements for Florida and California Building Codes.

Optional Accessories

  • 4, 5, 8, 10, 15, 20, and 25 KW single phase electric heaters (with circuit breakers or lugs).
  • Single point power entry kit (for 15 and 20 KW heaters).
  • Supply duct flange kit.
  • Downflow sub-base kits (TAYBASE185, TAYBASE235, TAYBASE260).
  • Slim fit filter box kit (BAYSF1185AAA, BAYSF1235AAA, BAYSF1265AAA).

Installation Instructions

1. Unpacking

Carefully unpack the unit and inspect for damage. Notify the carrier immediately if damage is found. Verify the rating plate matches the ordered model number and voltage. Report any discrepancies or parts shortages to the manufacturer within 5 days.

2. Location

Install the air handler centrally. Ensure minimum clearances are met. A downflow sub-base may be required for electric heat applications. The unit must be installed level to ensure proper condensation drainage; a slight slope (up to 1/4 inch over width/depth) towards the drain is permissible. For closet/utility room installations, ensure adequate space for replacement and servicing (21" clearance from front). For unconditioned spaces (attics, crawl spaces), ensure sufficient air circulation to prevent moisture collection. A drain pan is mandatory under the unit in these locations or above finished ceilings.

3. Duct Work

Install duct work in accordance with NFPA No. 90A and 90B, and applicable building codes. Insulate duct work as required by governing bodies.

4. Condensate Drain

The unit has primary and auxiliary 3/4" NPT condensate drains. The primary drain must be trapped outside the unit and piped per building codes. The trap's water column height must at least equal the normal negative static pressure during operation. A greater height is advisable to account for static increases from dirty filters or start-up bounce. Do not reduce the drain line size below the pan connection. All drains must pitch downward at a minimum of 1/4" per foot. If a cleanout Tee is used, the standpipe must be sealed/capped. If a vent Tee is used, it must be downstream from the trap.

Diagram Description: A diagram shows a U-shaped condensate trap. 'A' indicates the water column height, equal to the system's negative static pressure. 'C' indicates a dimension that should be at least twice the maximum negative static pressure.

Insulate the primary drain line to prevent sweating where dew point temperatures may be encountered.

5. Refrigerant Piping

Size external refrigerant piping according to the outdoor equipment manufacturer's instructions.

6. Metering Device

All units are shipped with an internally-checked, non-bleed TXV designed for AC or heat pump operation. Some outdoor models may require a start assist kit.

7. Blower

The unit features a variable speed motor with a direct drive blower wheel for adjustable airflow. Factory settings are provided for cooling and heating. Performance tables are available for additional airflow settings. Always disconnect power before making adjustments.

8. Airflow Adjustment

CAUTION: EQUIPMENT DAMAGE! Failure to follow this procedure may result in equipment damage. Disconnect power before changing dip switch positions.

Blower speed is controlled by the ECM Fan Control. An 8-dip switch bank adjusts airflow for outdoor unit size (tons), cooling/heating airflow, and fan off-delay options. Refer to the Airflow Label on the unit or Blower Performance Tables for correct settings.

Diagram Description (Figure 1): The ECM Fan Control shows a CFM Selection Light and DIP Switches.

Diagram Description (Figure 2): The DIP Switches are labeled for Cooling Airflow (SW1-SW4), Fan Off Delay Options (SW5-SW6), and Auxiliary Heat Speeds (SW7-SW8).

Indoor Blower Timing: Leave dip switches 5 and 6 in their factory-shipped positions during initial system startup and checkout. Adjust as needed afterward.

Table 3. Cooling Off-Delay Options
Switch SettingsSelectionNominal Airflow
5 -- OFF, 6 -- OFFNONESAME
5 -- ON, 6 -- OFF1.5 MINUTES100% (a)
5 -- OFF, 6 -- ON3 MINUTES50%
5 -- ON, 6 -- ONENHANCED (b)50%-100%

(a) Default setting. (b) Enhanced Mode provides gradual blower speed changes for improved comfort, quietness, and potential energy savings.

Diagram Description (Figure 3): A graph illustrates blower operation (CFM) over time for Enhanced Mode, showing ramping up and down of fan speed during compressor operation and heating/cooling cycles.

9. Wiring

Consult all unit and outdoor equipment wiring diagrams for compatibility and specific requirements. Field wiring must comply with the latest National Electric Code (NFPA No. 70) and local codes. Check unit rating plates for voltage, minimum circuit ampacity (MCA), and maximum overcurrent protection (MOP). Use only 75°C minimum copper conductors, sized per code. The unit is shipped wired for 230/240V AC, 60Hz, 1 Phase. For 208V operation, adjust the low voltage transformer per the wiring diagram. Class 2 low voltage control wiring must be separated from power wiring unless appropriate Class 1 wire is used. Use 18 AWG (105°C minimum) color-coded wire for low voltage control wiring; use 16 AWG for lengths over 100 ft. Ensure separation between control and power wiring.

Wiring Diagram Descriptions:

  • Single Stage, Cooling Only: Thermostat R to Air Handler R; Thermostat G to Air Handler G; Thermostat Y to Air Handler Y1; Thermostat W1 to Air Handler W1; Thermostat W2 to Air Handler W2. Outdoor unit connections are Y, G, O, B.
  • Single Stage, HP: Thermostat R to Air Handler R; Thermostat G to Air Handler G; Thermostat Y to Air Handler Y1; Thermostat W1 to Air Handler W1; Thermostat W2 to Air Handler W2 (Optional). Outdoor unit connections are Y, G, O, X2, B.
  • 2 Stage, 2 Step, Cooling Only: Thermostat R to Air Handler R; Thermostat G to Air Handler G; Thermostat Y1 to Air Handler Y1; Thermostat Y2 to Air Handler Y2; Thermostat W1 to Air Handler W1; Thermostat W2 to Air Handler W2. Outdoor unit connections are Y1, Y2, G, B.
  • 2 Stage, 2 Step, HP: Thermostat R to Air Handler R; Thermostat G to Air Handler G; Thermostat Y1 to Air Handler Y1; Thermostat Y2 to Air Handler Y2; Thermostat W1 to Air Handler W1; Thermostat W2 to Air Handler W2 (Optional). Outdoor unit connections are Y1, Y2, G, O, X2, B.

Notes for wiring diagrams: Use wirenuts for pigtail connections. Cap all unused wires. For BK enabled comfort control, do not connect Y1 or Y2 at the air handler and cut the jumper between R and BK on the control board. For systems with multiple stages of electric heat, jumper W1 and W2 together if the comfort control has only one stage of heat.

10. Air Filter

An air filter must be installed before the evaporator coil to protect internal components. Consult the filter manufacturer for proper sizing and maximum velocity requirements. Air filters must meet UL 900 test requirements.

11. Thermostat

Select a thermostat compatible with single-stage heating/cooling and electric heat. Install the thermostat on an inside wall, away from drafts, lights, or heat sources, in a location with sufficient air circulation.

12. Sequence of Operation

Cooling (Cooling only): Thermostat R-G energizes the blower via ECM control. Thermostat R-Y energizes the outdoor unit compressor and condenser fan.

Cooling (Heat pump): Thermostat R-G energizes the blower. Thermostat R-Y energizes the outdoor unit compressor and fan. Thermostat R-O energizes the reversing valve for cooling.

Heating (Heat pump): Thermostat R-G energizes the blower. Thermostat R-Y energizes the outdoor unit compressor and fan. Reversing valve is not energized for heating. If temperature drops, R-W circuit energizes electric heat contactors.

Heating (Electric heat only): Thermostat R-G energizes the blower. Thermostat R-W energizes heating contactors. Ensure thermostat is set to bring on the blower with electric heat.

Defrost: Connect the X2 (black) wire from the outdoor unit to W1 or W2 at the indoor unit for supplemental heat during defrost, preventing cold air discharge.

13. Operational and Checkout Procedures

Ensure proper performance by operating and charging the system according to the outdoor unit's Service Facts document. Review the checkout list provided in this document upon completion of installation.

14. Maintenance

Inspect, clean, or replace system air filters monthly. Ensure access panels are replaced and secured before operation. Schedule annual professional servicing, including inspection of electrical and refrigerant components, and cleaning of heat transfer surfaces. The blower motor is permanently lubricated.

Performance and Electrical Data

Air Flow Performance

The following tables detail airflow performance (CFM, Watts) for various models and settings under different external static pressures.

Table 4. TEM6A0B24H21SC COOLING AIRFLOW PERFORMANCE
OUTDOOR UNIT SIZE (TONS)SPEED SETTINGAIRFLOW SETTINGDIP SWITCH SETTINGEXTERNAL STATIC PRESSURE
SW1SW2SW3SW40.10.30.50.70.9
1.5LOW353 CFM/tonONONOFFONCFM: 533, 497, 461, 425, 390
Watts: 52, 78, 104, 130, 157
NORMAL401 CFM/tonONONOFFOFFCFM: 611, 580, 548, 517, 486
Watts: 65, 95, 125, 155, 185
HIGH451 CFM/tonONONONOFFCFM: 684, 668, 644, 611, 570
Watts: 81, 115, 148, 182, 215
2LOW343 CFM/tonOFFONOFFONCFM: 687, 672, 648, 614, 571
Watts: 82, 115, 149, 182, 215
NORMAL390 CFM/tonOFFONOFFOFFCFM: 789, 798, 780, 735, 663
Watts: 104, 145, 183, 216, 246
HIGH439 CFM/tonOFFONONOFFCFM: 884, 887, 882, 845, 751
Watts: 135, 177, 230, 274, 290
2.5LOW300 CFM/tonONOFFOFFONCFM: 752, 749, 729, 691, 636
Watts: 92, 123, 167, 211, 241
NORMAL (a)340 CFM/tonONOFFOFFOFFCFM: 859, 861, 863, 830, 727
Watts: 128, 172, 211, 242, 268
HIGH383 CFM/tonONOFFONOFFCFM: 963, 973, 995, 967, 844
Watts: 172, 223, 263, 291, 308

(a) Factory Default Setting

Table 5. TEM6A0B24H21SC HEATING AIRFLOW PERFORMANCE
OUTDOOR UNIT SIZE (TONS)SPEED SETTINGAIRFLOW SETTINGDIP SWITCH SETTINGEXTERNAL STATIC PRESSURE
SW1SW2SW3SW40.10.30.50.70.9
1.5LOW394 CFM/tonONONOFFONCFM: 599, 571, 539, 502, 462
Watts: 58, 88, 117, 146, 175
NORMAL448 CFM/tonONONOFFOFFCFM: 680, 665, 641, 610, 572
Watts: 72, 109, 145, 178, 209
HIGH493 CFM/tonONONONOFFCFM: 748, 746, 682, 545, 326
Watts: 89, 118, 163, 208, 240
2LOW393 CFM/tonOFFONOFFONCFM: 785, 790, 773, 735, 674
Watts: 97, 128, 175, 223, 253
NORMAL446 CFM/tonOFFONOFFOFFCFM: 904, 902, 912, 894, 809
Watts: 131, 179, 219, 253, 281
HIGH491 CFM/tonOFFONONOFFCFM: 980, 972, 990, 974, 863
Watts: 167, 216, 268, 308, 324
2.5LOW350 CFM/tonONOFFOFFONCFM: 866, 870, 866, 833, 750
Watts: 125, 162, 215, 263, 286
NORMAL (a)398 CFM/tonONOFFOFFOFFCFM: 995, 988, 1005, 986, 872
Watts: 171, 222, 271, 309, 325
HIGH437 CFM/tonONOFFONOFFCFM: 1099, 1086, 1098, 1065, 918
Watts: 220, 274, 328, 362, 353
3LOW310 CFM/tonOFFOFFOFFONCFM: 913, 947, 962, 938, 883
Watts: 119, 172, 233, 297, 364
NORMAL (a)330 CFM/tonOFFOFFOFFOFFCFM: 967, 1004, 1022, 1000, 947
Watts: 138, 194, 258, 326, 397

(a) Factory Default Setting

Table 6. TEM6A0B30H21SC COOLING AIRFLOW PERFORMANCE
OUTDOOR UNIT SIZE (TONS)SPEED SETTINGAIRFLOW SETTINGDIP SWITCH SETTINGEXTERNAL STATIC PRESSURE
SW1SW2SW3SW40.10.30.50.70.9
1.5LOW353 CFM/tonONONOFFONCFM: 533, 497, 461, 425, 390
Watts: 52, 78, 104, 130, 157
NORMAL401 CFM/tonONONOFFOFFCFM: 611, 580, 548, 517, 486
Watts: 65, 95, 125, 155, 185
HIGH451 CFM/tonONONONOFFCFM: 684, 668, 644, 611, 570
Watts: 81, 115, 148, 182, 215
2LOW343 CFM/tonOFFONOFFONCFM: 687, 672, 648, 614, 571
Watts: 82, 115, 149, 182, 215
NORMAL390 CFM/tonOFFONOFFOFFCFM: 789, 798, 780, 735, 663
Watts: 104, 145, 183, 216, 246
HIGH439 CFM/tonOFFONONOFFCFM: 884, 887, 882, 845, 751
Watts: 135, 177, 230, 274, 290
2.5LOW300 CFM/tonONOFFOFFONCFM: 752, 749, 729, 691, 636
Watts: 92, 123, 167, 211, 241
NORMAL340 CFM/tonONOFFOFFOFFCFM: 859, 861, 863, 830, 727
Watts: 128, 172, 211, 242, 268
HIGH383 CFM/tonONOFFONOFFCFM: 963, 973, 995, 967, 844
Watts: 172, 223, 263, 291, 308
3LOW310 CFM/tonOFFOFFOFFONCFM: 913, 947, 962, 938, 883
Watts: 119, 172, 233, 297, 364
NORMAL (a)330 CFM/tonOFFOFFOFFOFFCFM: 967, 1004, 1022, 1000, 947
Watts: 138, 194, 258, 326, 397

(a) Factory Default Setting

Table 7. TEM6A0B30H21SC HEATING AIRFLOW PERFORMANCE
OUTDOOR UNIT SIZE (TONS)SPEED SETTINGAIRFLOW SETTINGDIP SWITCH SETTINGEXTERNAL STATIC PRESSURE
SW1SW2SW3SW40.10.30.50.70.9
1.5LOW394 CFM/tonONONOFFONCFM: 599, 571, 539, 502, 462
Watts: 58, 88, 117, 146, 175
NORMAL448 CFM/tonONONOFFOFFCFM: 680, 665, 641, 610, 572
Watts: 72, 109, 145, 178, 209
HIGH493 CFM/tonONONONOFFCFM: 748, 746, 682, 545, 326
Watts: 89, 118, 163, 208, 240
2LOW393 CFM/tonOFFONOFFONCFM: 785, 790, 773, 735, 674
Watts: 97, 128, 175, 223, 253
NORMAL446 CFM/tonOFFONOFFOFFCFM: 904, 902, 912, 894, 809
Watts: 131, 179, 219, 253, 281
HIGH491 CFM/tonOFFONONOFFCFM: 980, 972, 990, 974, 863
Watts: 167, 216, 268, 308, 324
2.5LOW350 CFM/tonONOFFOFFONCFM: 866, 870, 866, 833, 750
Watts: 125, 162, 215, 263, 286
NORMAL398 CFM/tonONOFFOFFOFFCFM: 995, 988, 1005, 986, 872
Watts: 171, 222, 271, 309, 325
HIGH437 CFM/tonONOFFONOFFCFM: 1099, 1086, 1098, 1065, 918
Watts: 220, 274, 328, 362, 353
3LOW325 CFM/tonOFFOFFOFFONCFM: 953, 990, 1007, 985, 931
Watts: 133, 188, 251, 318, 389
NORMAL (a)346 CFM/tonOFFOFFOFFOFFCFM: 1010, 1049, 1066, 1047, 1000
Watts: 154, 212, 279, 350, 426

(a) Factory Default Setting

Table 8. TEM6A0C36H31SC, TEM6A0C42H41SC COOLING AIRFLOW PERFORMANCE
OUTDOOR UNIT SIZE (TONS)SPEED SETTINGAIRFLOW SETTINGDIP SWITCH SETTINGEXTERNAL STATIC PRESSURE
SW1SW2SW3SW40.10.30.50.70.9
2.5LOW300 CFM/tonONONOFFONCFM: 761, 755, 719, 654, 560
Watts: 63, 98, 131, 163, 193
NORMAL341 CFM/tonONONOFFOFFCFM: 862, 861, 834, 781, 700
Watts: 82, 120, 158, 196, 235
HIGH384 CFM/tonONONONOFFCFM: 962, 963, 948, 915, 863
Watts: 106, 147, 190, 234, 279
3LOW319 CFM/tonOFFONOFFONCFM: 961, 962, 947, 914, 862
Watts: 106, 147, 189, 233, 279
NORMAL363 CFM/tonOFFONOFFOFFCFM: 1092, 1093, 1082, 1060, 1026
Watts: 146, 192, 240, 288, 337
HIGH408 CFM/tonOFFONONOFFCFM: 1231, 1231, 1221, 1203, 1175
Watts: 196, 249, 301, 353, 404
3.5LOW315 CFM/tonONOFFOFFONCFM: 1104, 1105, 1094, 1072, 1039
Watts: 150, 197, 245, 293, 343
NORMAL357 CFM/tonONOFFOFFOFFCFM: 1258, 1258, 1248, 1229, 1201
Watts: 209, 263, 317, 369, 421
HIGH402 CFM/tonONOFFONOFFCFM: 1418, 1415, 1401, 1379, 1348
Watts: 286, 347, 406, 462, 516
4LOW308 CFM/tonOFFOFFOFFONCFM: 1238, 1238, 1229, 1210, 1182
Watts: 199, 253, 306, 357, 408
NORMAL (a)350 CFM/tonOFFOFFOFFOFFCFM: 1412, 1410, 1398, 1378, 1349
Watts: 282, 344, 404, 462, 517
HIGH394 CFM/tonOFFOFFONOFFCFM: 1570, 1528, 1473, 1406, 1326
Watts: 393, 436, 466, 483, 488

(a) Factory Default Setting

Table 9. TEM6A0C36H31SC, TEM6A0C42H41SC HEATING AIRFLOW PERFORMANCE
OUTDOOR UNIT SIZE (TONS)SPEED SETTINGAIRFLOW SETTINGDIP SWITCH SETTINGEXTERNAL STATIC PRESSURE
SW1SW2SW3SW40.10.30.50.70.9
2.5LOW341 CFM/tonONONOFFONCFM: 860, 863, 838, 788, 707
Watts: 77, 115, 154, 193, 232
NORMAL379 CFM/tonONONOFFOFFCFM: 949, 953, 937, 906, 852
Watts: 98, 138, 180, 224, 269
HIGH417 CFM/tonONONONOFFCFM: 1042, 1046, 1036, 1015, 980
Watts: 122, 166, 212, 259, 308
3LOW381 CFM/tonOFFONOFFONCFM: 1147, 1149, 1141, 1123, 1094
Watts: 154, 203, 253, 303, 353
NORMAL424 CFM/tonOFFONOFFOFFCFM: 1277, 1279, 1272, 1255, 1228
Watts: 204, 259, 314, 368, 421
HIGH466 CFM/tonOFFONONOFFCFM: 1409, 1409, 1401, 1384, 1357
Watts: 260, 323, 383, 442, 500
3.5LOW348 CFM/tonONOFFOFFONCFM: 1222, 1224, 1216, 1200, 1174
Watts: 180, 232, 285, 336, 388
NORMAL386 CFM/tonONOFFOFFOFFCFM: 1361, 1362, 1354, 1337, 1310
Watts: 240, 300, 358, 415, 471
HIGH425 CFM/tonONOFFONOFFCFM: 1497, 1478, 1449, 1408, 1356
Watts: 316, 372, 420, 461, 494
4LOW338 CFM/tonOFFOFFOFFONCFM: 1360, 1361, 1353, 1336, 1309
Watts: 239, 299, 358, 415, 470
NORMAL (a)375 CFM/tonOFFOFFOFFOFFCFM: 1511, 1489, 1456, 1412, 1355
Watts: 325, 380, 426, 464, 493
HIGH413 CFM/tonOFFOFFONOFFCFM: 1659, 1605, 1535, 1450, 1349
Watts: 420, 463, 488, 494, 483

(a) Factory Default Setting

Table 10. TEM6A0C48H41SC, TEM6B0C60H51SA COOLING AIRFLOW PERFORMANCE
OUTDOOR UNIT SIZE (TONS)SPEED SETTINGAIRFLOW SETTINGDIP SWITCH SETTINGEXTERNAL STATIC PRESSURE
SW1SW2SW3SW40.10.30.50.70.9
3LOW324 CFM/tonONONOFFONCFM: 991, 985, 974, 984, 994
Watts: 89, 133, 186, 237, 303
NORMAL368 CFM/tonONONOFFOFFCFM: 1120, 1119, 1110, 1116, 1122
Watts: 118, 167, 224, 279, 333
HIGH423 CFM/tonONONONOFFCFM: 1282, 1286, 1281, 1280, 1282
Watts: 162, 219, 280, 343, 402
3.5LOW314 CFM/tonOFFONOFFONCFM: 1116, 1114, 1105, 1111, 1117
Watts: 117, 165, 222, 277, 331
NORMAL357 CFM/tonOFFONOFFOFFCFM: 1263, 1266, 1261, 1261, 1263
Watts: 156, 212, 273, 334, 392
HIGH411 CFM/tonOFFONONOFFCFM: 1449, 1458, 1456, 1449, 1447
Watts: 218, 287, 352, 421, 496
4LOW298 CFM/tonONOFFOFFONCFM: 1207, 1208, 1201, 1203, 1207
Watts: 140, 193, 252, 311, 366
NORMAL339 CFM/tonONOFFOFFOFFCFM: 1368, 1374, 1370, 1367, 1367
Watts: 190, 252, 315, 381, 448
HIGH389 CFM/tonONOFFONOFFCFM: 1564, 1577, 1577, 1567, 1561
Watts: 264, 343, 411, 484, 570
5LOW305 CFM/tonOFFOFFOFFONCFM: 1534, 1545, 1545, 1536, 1531
Watts: 251, 328, 394, 467, 550
NORMAL (a)347 CFM/tonOFFOFFOFFOFFCFM: 1740, 1758, 1762, 1745, 1734
Watts: 344, 444, 518, 594, 684
HIGH (b)399 CFM/tonOFFOFFONOFFCFM: 1995, 2022, 2030, 2005, 1987
Watts: 484, 629, 717, 783, 828

(a) Factory Default Setting. (b) Airflow must not exceed 1800 cfm in horizontal right, horizontal left, and downflow applications due to condensate blowoff. The 5 ton high tap shall not be used in these applications.

Table 11. TEM6A0C48H41SC, TEM6B0C60H51SA HEATING AIRFLOW PERFORMANCE
OUTDOOR UNIT SIZE (TONS)SPEED SETTINGAIRFLOW SETTINGDIP SWITCH SETTINGEXTERNAL STATIC PRESSURE
SW1SW2SW3SW40.10.30.50.70.9
3LOW360 CFM/tonONONOFFONCFM: 1097, 1094, 1086, 1092, 1099
Watts: 112, 160, 216, 271, 326
NORMAL400 CFM/tonONONOFFOFFCFM: 1215, 1216, 1210, 1211, 1215
Watts: 142, 196, 255, 314, 369
HIGH440 CFM/tonONONONOFFCFM: 1333, 1338, 1333, 1331, 1332
Watts: 178, 238, 300, 365, 428
3.5LOW348 CFM/tonOFFONOFFONCFM: 1232, 1234, 1228, 1229, 1233
Watts: 147, 202, 261, 322, 377
NORMAL387 CFM/tonOFFONOFFOFFCFM: 1366, 1373, 1369, 1366, 1365
Watts: 189, 252, 314, 381, 447
HIGH426 CFM/tonOFFONONOFFCFM: 1500, 1511, 1510, 1502, 1498
Watts: 238, 311, 377, 449, 529
4LOW338 CFM/tonONOFFOFFONCFM: 1364, 1370, 1366, 1363, 1363
Watts: 188, 251, 313, 379, 446
NORMAL375 CFM/tonONOFFOFFOFFCFM: 1509, 1520, 1519, 1511, 1506
Watts: 241, 315, 382, 453, 535
HIGH413 CFM/tonONOFFONOFFCFM: 1659, 1674, 1676, 1662, 1654
Watts: 305, 395, 466, 541, 632
5LOW326 CFM/tonOFFOFFOFFONCFM: 1637, 1652, 1653, 1641, 1632
Watts: 295, 383, 453, 528, 618
NORMAL (a)362 CFM/tonOFFOFFOFFOFFCFM: 1814, 1834, 1839, 1820, 1807
Watts: 381, 493, 570, 645, 730
HIGH398 CFM/tonOFFOFFONOFFCFM: 1990, 2017, 2025, 2000, 1982
Watts: 481, 625, 713, 779, 826

(a) Factory Default Setting

Table 12. TEM6A0B24H21SC HEATER DATA
Heater Model No.No. of Circuits/Phases240 Volt208 Volt
Capacity kW BTUHHeater Amps per CircuitMinimum Circuit AmpacityMaximum Overload ProtectionCapacity kW BTUHHeater Amps per CircuitMinimum Circuit AmpacityMaximum Overload Protection
No Heater
BAYHTR1504BRK
BAYHTR1504LUG
1/13.84 1310016.023302.88 980013.820
BAYHTR1505BRK
BAYHTR1505LUG
1/14.80 1640020.028353.60 1230017.325
BAYHTR1508BRK
BAYHTR1508LUG
1/17.68 2620032.043555.76 1970027.740
BAYHTR1510BRK
BAYHTR1510LUG
1/19.60 3280040.053757.20 2460034.650
BAYHTR1517BRK Circuit 1 (a)2/19.60 3280040.053757.20 2460034.650
BAYHTR1517BRK Circuit 24.80 1640020.025353.60 1230017.325
BAYHTR3510LUG1/39.60 3280023.132457.20 2460020.030
BAYHTR3517LUG1/314.40 4910034.6466010.80 3690030.040

* = Motor Amps. (a) MCA and MOP for circuit 1 includes motor amps.

Table 13. TEM6A0B30H21SC HEATER DATA
Heater Model No.No. of Circuits/Phases240 Volt208 Volt
Capacity kW BTUHHeater Amps per CircuitMinimum Circuit AmpacityMaximum Overload ProtectionCapacity kW BTUHHeater Amps per CircuitMinimum Circuit AmpacityMaximum Overload Protection
No Heater
BAYHTR1504BRK
BAYHTR1504LUG
1/13.84 1310016.025302.88 980013.823
BAYHTR1505BRK
BAYHTR1505LUG
1/14.80 1640020.030403.60 1230017.327
BAYHTR1508BRK
BAYHTR1508LUG
1/17.68 2620032.045605.76 1970027.740
BAYHTR1510BRK
BAYHTR1510LUG
1/19.60 3280040.055757.20 2460034.649
BAYHTR1517BRK Circuit 1 (a)2/19.60 3280040.055757.20 2460034.649
BAYHTR1517BRK Circuit 24.80 1640020.025353.60 1230017.325
BAYHTR3510LUG1/39.60 3280023.134457.20 2460020.030
BAYHTR3517LUG1/314.40 4910034.6486010.80 3690030.042

* = Motor Amps. (a) MCA and MOP for circuit 1 includes motor amps.

Table 14. TEM6A0C36H31SC, TEM6A0C42H41SC HEATER DATA
Heater Model No.No. of Circuits/Phases240 Volt208 Volt
Capacity kW BTUHHeater Amps per CircuitMinimum Circuit AmpacityMaximum Overload ProtectionCapacity kW BTUHHeater Amps per CircuitMinimum Circuit AmpacityMaximum Overload Protection
No Heater
BAYHTR1504BRK
BAYHTR1504LUG
1/13.84 1310016.025302.88 980013.823
BAYHTR1505BRK
BAYHTR1505LUG
1/14.80 1640020.030403.60 1230017.327
BAYHTR1508BRK
BAYHTR1508LUG
1/17.68 2620032.045605.76 1970027.740
BAYHTR1510BRK
BAYHTR1510LUG
1/19.60 3280040.055757.20 2460034.649
BAYHTR1517BRK Circuit 1 (a)2/19.60 3280040.055757.20 2460034.649
BAYHTR1517BRK Circuit 24.80 1640020.025353.60 1230017.325
BAYHTR1523BRK Circuit 1 (a)2/19.60 3280040.055757.20 2460034.649
BAYHTR1523BRK Circuit 29.60 3280040.050757.20 2460034.645
BAYHTR3510LUG1/39.60 3280023.134457.20 2460020.030
BAYHTR3517LUG1/314.40 4910034.6486010.80 3690030.042

* = Motor Amps. (a) MCA and MOP for circuit 1 includes motor amps.

Table 15. TEM6A0C48H41SC, TEM6B0C60H51SA HEATER DATA
Heater Model No.No. of Circuits/Phases240 Volt208 Volt
Capacity kW BTUHHeater Amps per CircuitMinimum Circuit AmpacityMaximum Overload ProtectionCapacity kW BTUHHeater Amps per CircuitMinimum Circuit AmpacityMaximum Overload Protection
No Heater
BAYHTR1504BRK
BAYHTR1504LUG
1/13.84 1310016.029152.88 980013.826
BAYHTR1505BRK
BAYHTR1505LUG
1/14.80 1640020.034353.60 1230017.330
BAYHTR1508BRK
BAYHTR1508LUG
1/17.68 2620032.049505.76 1970027.743
BAYHTR1510BRK
BAYHTR1510LUG
1/19.60 3280040.059607.20 2460034.652
BAYHTR1517BRK Circuit 1 (a)2/19.60 3280040.059757.20 2460034.652
BAYHTR1517BRK Circuit 24.80 1640020.025353.60 1230017.327
BAYHTR1523BRK Circuit 1 (a)2/19.60 3280040.059757.20 2460034.652
BAYHTR1523BRK Circuit 29.60 3280040.050757.20 2460034.643
BAYHTR1525BRK Circuit 1 (a)4/16.00 2050025.040404.50 1540021.636
BAYHTR1525BRK Circuit 26.00 2050025.031354.50 1540021.627
BAYHTR1525BRK Circuit 36.00 2050025.031354.50 1540021.627
BAYHTR1525BRK Circuit 46.00 2050025.031354.50 1540021.627
BAYHTR3510LUG1/39.60 3280023.136354.50 1540021.627
BAYHTR3517LUG1/314.40 4910034.6516010.80 3690030.045

* = Motor Amps. (a) MCA and MOP for circuit 1 includes motor amps.

Minimum Airflow CFM

TEM6A0B24H21SC, TEM6A0B30H21SC Minimum Heater Airflow CFM
HeaterWith Heat PumpWithout Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG660600
BAYHTR1505BRK, BAYHTR1505LUG780600
BAYHTR1508BRK, BAYHTR1508LUG780600
BAYHTR1510BRK, BAYHTR1510LUG1050850
BAYHTR1517BRK780600
BAYHTR3510LUG900850
BAYHTR3517LUG
TEM6A0C36H31SC, TEM6A0C42H41SC Minimum Heater Airflow CFM
HeaterWith Heat PumpWithout Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG875675
BAYHTR1505BRK, BAYHTR1505LUG950820
BAYHTR1508BRK, BAYHTR1508LUG1000820
BAYHTR1510BRK, BAYHTR1510LUG1000820
BAYHTR1517BRK875820
BAYHTR3510LUG1000950
BAYHTR3517LUG13001140
BAYHTR1523BRK
TEM6A0C48H41SC, TEM6B0C60H51SA Minimum Heater Airflow CFM
HeaterWith Heat PumpWithout Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG1200975
BAYHTR1505BRK, BAYHTR1505LUG1350975
BAYHTR1508BRK, BAYHTR1508LUG1350975
BAYHTR1510BRK, BAYHTR1510LUG1365975
BAYHTR1517BRK13001120
BAYHTR3510LUG13651300
BAYHTR3517LUG18101505
BAYHTR1523BRK
BAYHTR1525BRK

Airflow Performance with Auxiliary Heat

TEM6A0B24H21SC, TEM6A0B30H21SC

Airflow SettingsDip Switch SettingsNominal Airflow
Switch 7Switch 8
LowONON601
Med-LoOFFON661
Med-HiONOFF781
HighOFFOFF973

See following tables for heater application: - Pressure Drop for Electrical Heaters - Minimum Heating Airflow Matrix (on unit nameplates)

TEM6A0C36H31SC, TEM6A0C42H41SC

Airflow SettingsDip Switch SettingsNominal Airflow
Switch 7Switch 8
LowONON696
Med-LoOFFON825
Med-HiONOFF1150
HighOFFOFF1298

See following tables for heater application: - Pressure Drop for Electrical Heaters - Minimum Heating Airflow Matrix (on unit nameplates)

TEM6A0C48H41SC, TEM6B0C60H51SA

Airflow SettingsDip Switch SettingsNominal Airflow
Switch 7Switch 8
LowONON1000
Med-LoOFFON1130
Med-HiONOFF1354
HighOFFOFF1596

See following tables for heater application: - Pressure Drop for Electrical Heaters - Minimum Heating Airflow Matrix (on unit nameplates)

Heater Pressure Drop Table

Airflow CFMAir Pressure Drop -- Inches W.G.
1 Rack2 Racks3 Racks4 Racks
18000.020.040.060.14
17000.020.040.060.14
16000.020.040.060.13
15000.020.040.060.12
14000.020.040.060.12
13000.020.040.050.11
12000.010.040.050.10
11000.010.030.050.09
10000.010.030.040.09
9000.010.030.040.08
8000.010.030.03
7000.010.020.02
6000.010.02
Heater Racks
Heater ModelNo. of Racks
BAYHTR15041
BAYHTR15051
BAYHTR15082
BAYHTR15102
BAYHTR15173
BAYHTR35103
BAYHTR35173
BAYHTR15234
BAYHTR15254

Subcooling Adjustment

System Matched with:

Indoor Unit Model No.Outdoor Unit SizeOutdoor Model No.Subcooling
TEM6A0C36H3116 SEER HP -- 2 ton4TWR6024H1000A13 Degrees
TEM6A0B24H2115 SEER HP -- 2 ton4TWX6024H1000A14 Degrees
TEM6A0B30H2115 SEER HP -- 2 ton4A6H6024H1000A14 Degrees
TEM6A0B30H214TWR5024G1000A
TEM6A0C36H314A6H5024G1000A
TEM6A0C42H4115 SEER HP -- 3 ton4TWR5036G1000A
4A6H5036G1000A

All other matches must be charged per the nameplate charging instructions.

Subcooling Adjustment for TEM6A0C48H41 & TEM6B0C60H51
OD EquipmentSub-Cooling Charge Specification For AHRI Rated Performance
Up Flow / HorizontalDown Flow
AC UNIT 3.5 TonsOD Name PlateOD Name Plate
HP UNIT = 4 and 5 TonsOD Name PlateOD Name Plate + 4 Degrees

Coil Conversion Instructions

Downflow Configuration

Follow these steps to install the air handler in a downflow configuration:

  1. Remove the front panels from the air handler. The coil and line set panel do not need to be separated.
  2. Remove fasteners on both sides of the coil.
  3. Remove the two screws holding the center horizontal bracket and rotate it out of place. Retain parts.
  4. Slide the coil assembly out. Remove and discard the horizontal drain pan.
  5. On both sides of the cabinet, remove the screws holding the coil support brackets. Retain these screws and brackets for later use. Seal the holes to prevent air leakage.
  6. Rotate and lift the two coil support brackets to remove them from the front slots in the cabinet.
  7. Rotate the unit into the downflow orientation.
  8. Pre-drill two clearance holes in the cabinet at dimples located below where the screws for the coil support brackets were removed (one hole per side).
  9. Replace the center horizontal bracket removed in Step 3, using the retained screws.
  10. Place coil support brackets into the lower set of slots and rotate into place. Push downward to lock them in place.
  11. Secure each bracket with a screw that was previously removed.
  12. Slide the coil assembly back into the air handler cabinet.
  13. Remove the appropriate knockout for the condensate piping.
  14. Replace all panels.

Horizontal Right Configuration

Follow these steps to install the air handler in a horizontal right configuration:

  1. Remove the front panels from the air handler. The coil and line set panel do not need to be separated.
  2. Remove the fasteners on both sides of the coil. Retain the coil retaining brackets and screws.
  3. Remove the two screws holding the center horizontal bracket and rotate it out of place. Retain parts.
  4. Note the horizontal drain pan orientation (up/down).
  5. Slide the coil assembly out.
  6. For Horizontal Right applications on some models, the top panel assembly of the coil must be rotated for proper condensate management. Locate the snap tab feature on the top baffle. On the right side of the top baffle, position a flathead tip underneath the top baffle flange and pivot the screwdriver downward to release the front tab. Repeat for the right rear tab to release the top baffle assembly from the coil.
  7. Rotate the top baffle assembly 180 degrees and snap all four corner tabs to lock it in place.
  8. Remove the left side water diverter brackets and screws and reinstall them on the right side. Note: Coil slabs and mount hole locations vary by tonnage; consult illustrations for correct mounting positions. Water diverter brackets are not symmetrical.
  9. Relocate the horizontal drain pan from the left side of the coil to the right side.
  10. Remove the drain pan support bracket (do not discard). Remove the two drain plugs from the front of the drain pan and insert them into the drains at the rear of the drain pan.
  11. Reinstall the drain pan support bracket. The bracket should be located between the two drain plugs.
  12. Slide the coil assembly back into the air handler cabinet, ensuring the coil corner locks under the tab in the side bracket to support the coil weight horizontally.
  13. Replace the center horizontal bracket using the screws removed earlier.
  14. Replace the two coil retaining brackets removed previously.
  15. Replace all panels.

Checkout Procedures

The final phase of installation involves system checkout. Confirm all requirements have been met:

  • All wiring connections are tight and properly secured.
  • Voltage and running current are within limits.
  • All refrigerant lines (internal and external) are isolated, secure, and not in direct contact with each other or structure.
  • All braze connections have been checked for leaks. A vacuum of 350 microns confirms the refrigeration system is leak-free and dry.
  • Final unit inspection to confirm factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other or any component when the unit runs.
  • Ductwork is sealed and insulated.
  • All drain lines are clear with joints properly sealed. Pour water into the drain pan to confirm proper drainage and prime the drain trap.
  • Supply registers and return grilles are open and unobstructed, and the air filter is installed.
  • Indoor blower and outdoor fan are operating smoothly and without obstruction.
  • Indoor blower motor is set on the correct speed setting to deliver the required CFM. Blower and fan set screws are tight.
  • Cover panels are in place and properly tightened.
  • For gas heating systems, manifold pressure has been checked and all gas line connections are tight and leak-free.
  • For gas heating systems, flue gas is properly vented.
  • System functions safely and properly in all modes.
  • The owner has been instructed on system use and provided with the manual.

About Trane

Trane and American Standard create comfortable, energy-efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.

The manufacturer has a policy of continuous data improvement and reserves the right to change design and specifications without notice. This document is printed using environmentally conscious practices.

Models: 2 to 5 Ton Convertible Air Handlers, 2 to 5 Ton Air Handlers, Convertible Air Handlers, Air Handlers, TEM6A0B24H21SC, TEM6A0B30H21SC, TEM6A0C36H31SC, TEM6A0C42H41SC, TEM6A0C48H41SC, TEM6B0C60H51SA

File Info : application/pdf, 32 Pages, 29.66MB

PDF preview unavailable. Download the PDF instead.

18-GF74D1-1R-EN 07182022

References

PDFlib PDI 9.0.6 (C /Win64)

Related Documents

PreviewTrane TEM8 Series Air Handler: Installation, Operation, and Maintenance Guide
Comprehensive guide for installing, operating, and maintaining Trane's TEM8 series communicating and 24-volt convertible air handlers (2-5 tons). Covers safety, installation procedures, sequence of operation, electrical data, and troubleshooting.
PreviewTrane 5TEM4 Series Convertible Air Handlers: Product Data and Specifications
Detailed product data, specifications, features, and optional equipment for Trane's 5TEM4 series 2-5 ton convertible air handlers. Includes electrical data, performance tables, and dimensional information.
PreviewTrane TEM6 Convertible Air Handler Installer's Guide
Comprehensive installer's guide for Trane TEM6 series convertible air handlers, covering installation, wiring, safety precautions, performance data, and maintenance for 2-5 ton models.
PreviewTrane A4AH4E30A1B 2.5 Ton Convertible Air Handler Submittal and Specifications
Detailed submittal, outline drawing, product specifications, performance data, and features for the Trane A4AH4E30A1B 2.5 Ton Convertible Air Handler, including dimensional data, electrical specifications, and airflow performance.
PreviewTrane A5AHV Series Variable Speed Convertible Air Handler Submittal
Submittal document for the Trane A5AHV Series Variable Speed Convertible Air Handler, 1.5 - 2.5 Ton Operation. Includes product specifications, dimensions, airflow performance, and electrical data.
PreviewTrane A4AH4E60B1C30A 5.0 Ton Convertible Air Handler Specifications and Submittal
Detailed specifications, outline drawing, and electrical data for the Trane A4AH4E60B1C30A 5.0 Ton Convertible Air Handler. Includes performance tables and features.
PreviewTrane Convertible Air Handler Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Trane's A5AHC series convertible air handlers, covering safety, technical specifications, and troubleshooting.
PreviewTrane Convertible Air Handlers 2-5 Ton Product Data
Comprehensive product data, features, specifications, and electrical information for Trane's 2-5 Ton Convertible Air Handlers (5TEM4 series), including installation details and optional equipment.