Operation Manual
EE23
Humidity/Temperature Sensor
BA_EE23_B2_e // v1.1 // technical data are subject to change // 194768
 11 04-23729418 04-23724011 Emailsales@jetec.com.tw

E+E Elektronik Ges.m.b.H. doesn't accept warranty and liability claims neither upon this publication nor in case of improper treatment of the described products.
The document may contain technical inaccuracies and typographical errors. The content will be revised on a regular basis. These changes will be implemented in later versions. The described products can be improved and changed at any time without prior notice.
© Copyright E+E Elektronik Ges.m.b.H. All rights reserved.
EMC note USA (FCC):
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
EMC note Canada (ICES-003):
CAN ICES-3 (A) / NMB-3 (A)

CONTENT
1 General .................................................................................................................................................4 1.1 Explanation of Symbols.................................................................................................................................4 1.2 Safety Instructions.........................................................................................................................................4
1.2.1 General Safety Instructions..................................................................................................................................4 1.2.2 Safety Instructions for the Alarm Output Module with Voltage >50 V .................................................................. 4 1.2.3 Safety Instructions for the Integrated Power Supply (Option AM3)...................................................................... 4 1.3 Environmental Aspects ..................................................................................................................................5
2 Scope of Supply ..................................................................................................................................5
3 Operating Components ......................................................................................................................6 3.1 Electronics Board for Model T1, T2, T4 and T6.............................................................................................6 3.2 Display for Model T1, T2, T4 and T6 .............................................................................................................7 3.3 Electronic Board for Model T5 .......................................................................................................................8 3.4 Display for Model T5 .....................................................................................................................................9
4 Installation .........................................................................................................................................10 4.1 Mounting the Enclosure...............................................................................................................................10 4.2 Mounting the Sensing Probe .......................................................................................................................11 4.3 Electrical Connection...................................................................................................................................12 4.4 Connection Versions ...................................................................................................................................12
5 Calibration / Adjustment ...................................................................................................................14 5.1 Definitions....................................................................................................................................................14 5.2 Adjustment of EE23 Model T1, T2, T4 and T6 .......................................................................................... 14
5.2.1 2-Point RH Adjustment Procedure / T Adjustment Procedure............................................................................ 14 5.2.2 1-Point RH Adjustment Procedure / T Adjustment Procedure ........................................................................... 15 5.2.3 Return to Factory Calibration ............................................................................................................................. 15 5.3 Adjustment of the EE23 Model T5 via the USB Service Interface...............................................................16
6 Maintenance.......................................................................................................................................16
7 Troubleshooting ................................................................................................................................16 7.1 Fuse Replacement for Option AM3 .............................................................................................................16
8 Accessories and Spare Parts ..........................................................................................................17
9 Technical Data ...................................................................................................................................18 9.1 Operating Range Humidity Sensor..............................................................................................................19

1 General
This operation manual is part of the scope of supply and serves for ensuring proper handling and optimal functioning of the device. The operation manual shall be read before commissioning the equipment and it shall be provided to all staff involved in transport, installation, operation, maintenance and repair.
The operation manual may not be used for the purposes of competition without the written consent of E+E Elektronik® and may not be forwarded to third parties. Copies may be made for internal purposes. All information, technical data and diagrams included in these instructions are based on the information available at the time of writing.
1.1 Explanation of Symbols
This symbol indicates safety information. It is essential that all safety information is strictly observed. Failure to comply with this information can lead to personal injuries or damage to property. E+E Elektronik® assumes no liability if this happens.
This symbol indicates instructions. The instructions shall be observed in order to reach optimal performance of the device.
1.2 Safety Instructions
1.2.1 General Safety Instructions
· Avoid any unnecessary mechanical stress and inappropriate use. · Replace the filter cap with utmost care, so that the filter cap does not touch the sensing elements of
the sensing head at any time. · Do never touch the sensing elements. · For sensor cleaning and filter cap replacement please see "Cleaning instructions" at www.epluse.com. · Installation, electrical connection, maintenance and commissioning shall be performed by qualified
personnel only.
1.2.2 Safety Instructions for the Alarm Output Module with Voltage >50 V (not available for model T5 with remote probe up to 180 °C (356 °F))
· The alarm output module must be separated from the screw terminals by the partition plate (see picture).
· The enclosure must be properly closed before power on. · Power off the device before opening the enclosure.
1.2.3 Safety Instructions for the Integrated Power Supply (Option AM3)
· The back cover and the middle (active) part of the EE23 with metal enclosure must be grounded during operation.
· The E23 enclosure must be properly closed before power on. · Power off the device before opening the enclosure.

4

Operating manual EE23 humidity / temperature sensor

1.3 Environmental Aspects
Products from E+E Elektronik® are developed and manufactured observing of all relevant requirements with respect to environment protection. Please observe local regulations for the device disposal.
For disposal, the individual components of the device must be separated according to local recycling regulations. The electronics shall be disposed of correctly as electronics waste.

2 Scope of Supply

EE23 according to ordering guide Operation manual in English Inspection certificate according to DIN EN 10204 ­ 3.1 Allen key 3.0 Mating cable connector for integrated power supply Mating cable connector RSC 5/7 M16 cable gland

Included in all versions
x x x
except AM3, E4

According to ordering guide
only for metal enclosure AM3 AM3 / E4

Operating manual EE23 humidity / temperature sensor

5

3 Operating Components
3.1 Electronics Board for Model T1, T2, T4 and T6

Fig. 1 Electronics board model T1, T2, T4 and T6
1. Jumpers: Selection of the output signal and output range
voltage output

current output

2. Display: Connectors for the optional display
3. Status LEDs D1 (red) - continuously on during the calibration routine
- one short flash confirms reset to factory calibration
D2 (green) - flashes during normal operation - continuously on indicates sensor damage
4. Push-Buttons The S1 and S2 push buttons are used for the EE23 adjustment as well as for returning to the factory calibration (see Calibration / Adjustment).
5. Level / Hysteresis Potentiometers for setting the threshold / hysteresis (available with alarm module only)

6

Operating manual EE23 humidity / temperature sensor

3.2 Display for Model T1, T2, T4 and T6
The display is plugged into the connectors on the electronics board and it can easily be replaced. For upgrading an EE23 originally without display please see "Replacement parts / accessories".

12 3

4

5 6

Fig. 2 Display description T1, T2, T4 and T6

1. CAL Indicates that the device in calibration/adjustment mode

2. > <

>:

indicates measured value above the alarm threshold (with alarm module only).

visual feedback when depressing the S1 push button (Fig. 1)

<:

indicates measured value below the alarm threshold (with alarm module only).

visual feedback when depressing the S2 push button (Fig. 1)

3. SET Indication for EE23 with optional alarm output

4. Td / Tf Dew point temperature / frost point temperature

5. °C / °F Unit for temperature (T) and dew point temperature (Td) and frost point temperature (Tf)

6. %RH Unit for relative humidity (RH)

Operating manual EE23 humidity / temperature sensor

7

3.3 Electronic Board for Model T5
T5 = remote probe up to 180 °C (356 °F)

1. Display

3. Interface Fig. 3 Electronics board model T5

2. Status LEDs

1. Display: Connectors for the optional display
2. Status LEDs: Green LED flashing --> Supply voltage applied / Microprocessor is active
Red LED constantly lit --> Error category 1 = non-critical error, can be solved by the user flashing --> Error category 2 = critical error, return the device for service
Blue LED constantly lit --> analogue output is set to voltage.
Orange LED constantly lit --> analogue output is set to current.
3. Interface: USB-Interface for service use

8

Operating manual EE23 humidity / temperature sensor

3.4 Display for Model T5

Fig. 4

Display description T5 1. Measurand

RH Relative humidity

T Temperature

h

Enthalpy

r

Mixture ratio

dv Absolute humidity

Tw Wet-bulb temperature

Td Dew-point temperature

e

Water vapour partial pressure

Tab. 1 Mesurand selection

2. Units

SI

US

%

%

°C

°F

kJ/kg ftlbf/lb

g/kg

gr/lb

g/m³

gr/ft

°C

°F

°C

°F

mbar psi

3. Mesurand selection
Press the  or  button to select the measurand to be displayed.

Error description

Error code (display)

Short circuit - on voltage output 11)

Short circuit - on voltage output 21)

ERROR: 01

Short circuit - on both voltage outputs*

Current loop open - output 1

Current loop open - output 2

ERROR: 02

Current loop open - both outputs

RH sensor dirty

ERROR: 03

ERROR: 05

Hardware error

ERROR: 06

ERROR: 08

Temperature measurement failure

ERROR: 07

Humidity measurement failure

ERROR: 09 ERROR: 10

1) not available with 0 - 1 V output

2) see "Cleaning Instructions" at www.epluse.com/ee23

Error category

Recommended action

Check wiring of outputs

1 Check wiring of outputs

Clean the sensor2)

2

Return the faulty unit for service

Tab. 2 Description of error messages on the display

Operating manual EE23 humidity / temperature sensor

9

4 Installation

4.1 Mounting the Enclosure

1. Only for model T2 (duct mounting). Drill the hole for inserting the probe into the duct wall,Fig. 7 on page 11. The relevant position of top left mounting screw of the back cover with respect to the probe center:

Metal enclosure:

x = 28.5 mm (1.1") y = 37.5 mm (1.5")

Polycarbonate enclosure: x = 20.5 mm (0.8") y = 25.4 mm (1")

2. Fix the back cover of EE23 onto the wall / panel using 4 screws (diameter max. 4.2 mm (0.2") ; not included in the scope of supply).

The device shall be mounted with the cable glands pointing downwards or horizontal.

3. Wire the terminals inside the back cover according to ,,Fig. 10 Connection diagram" on Page 12.

4. Insert the middle (active) part into the back cover. By this the connection pins of the middle part will plug into the terminals of the back cover and thus realize the electrical connection.

5. Place the front cover onto the middle part and close tight the enclosure using the four screws included in the scope of supply.
Drilling for round holes:

Drilling for long holes:

Fig. 5 Mounting of metal enclosure
116 (4.5")

50.8 (2")

Fig. 6 Mounting of polycarbonat enclosure 10

Operating manual EE23 humidity / temperature sensor

For the wall mount model the probe must point downwards. For the duct mount model the probe must point either horizontally or downwards.

Ø12 (0.5")

X Ø14 (0.6")

Y
(0.5Ø1"1)3

Ø12 (0.5")

Fig. 7 T1 Wall mount

T2 Duct mount

Mounting onto DIN rails EE23 with polycarbonate enclosure can be mounted also on DIN rails with the bracket HA010203 (not included in the scope of supply, see "spare parts / accessories").

4.2 Mounting the Sensing Probe
Whenever possible place the entire probe inside the space to be monitored.
In case of mounting the probe into a partition wall, it is of paramount importance for accurate measurement to avoid T gradients along the probe. In case of large T difference between the two sides of the wall, it is highly recommended to insert the probe completely (up to the cable outlet) into the wall. Should this not be possible, place a thermal isolation layer on the part of the probe outside the wall (on the cable side).
For probe mounting into a partition wall use the mounting flanges HA010201 for probe diameter 12 mm and HA010208 for probe diameter 5 mm. Neither the mounting flanges nor the EE23 probes are pressure rated and as such they are not appropriate for pressure tight mounting. For pressure tight requirements please see www.epluse.com for appropriate products such as EE310.

Ø46 (1.8") Ø12 (0.5")

37 (1.5")

Fig. 8 Mounting flange HA010201

Mounting flange HA010208

Operating manual EE23 humidity / temperature sensor

11

For applications where condensation is likely to happen, certain ways of mounting are required. · For probe hanging onto its cable from the ceiling, use the drip water protection HA010503 (not inclu-
ded in the scope of supply, see "spare parts / accessories"). This protects the probe and the sensing head against water dripping along the cable. · For horizontal mounted probe, a drip water point should be made just before the probe.

13 (0.51")

stainless steel mounting flange

drip water loop

Fig. 9

horizontal Mounting the sensing probe

4.3 Electrical Connection

Poouwtpeurtsaunpdpslyuapnpdlyoutputs

drip water protection

34 (1.3")

85 (3.3")
hanging onto the probe cable

alAarlamrmouotuptuptut

Relais status for RH < threshold

Power supply

Fig. 10 Connection diagram

4.4 Connection Versions

standard

option E4

option AM3

1) Two M16x1.5 cable glands (one of them mounted onto the enclosure) 2) Power supply + analogue outputs: cable connector, 5-poles, straight M12 (Lumberg RKC 5/7) 3) Analogue output: cable connector, 5-poles, straight M12 (Lumberg RKC 5/7) 4) AC power supply: cable connector, 3-poles, straight (7/8-16UN)

12

Operating manual EE23 humidity / temperature sensor

Pin assignment for option E4 (with supply 8...35 V DC / 12...30 V AC)

plug for supply and analogue output (front view)

43 1 52

Description: V+ GND GND OUT1 OUT2

Pins: 5 4 3 2 1

Pin assignment for option AM3 (integrated supply unit for 100...240 VAC)

plug for analogue outputs (front view)

43 1 52

Description: GND OUT1 OUT1

Pins: 3 2 1

plug for 100-240 V metal enclosure (front view)

Description: grounding (PE) phase (L1) neutral wire (N)

Pins: 1 2 3

plug for 100-240 V polycarbonate enclosure (front view)

Description: phase (L1) neutral wire (N)

Pins: 1 3

External diameter of supply cable: 10-12 mm (0.39-0.47") Maximum wire cross section for connecting cable: 1.5 mm² (AWG 16)
The protection of the supply cable against excess current and short-circuit must be designated to a wire cross section of 0.8 mm² (AWG 18) (6A fuse).
The back cover and the middle part of the metal enclosure must be grounded during operation!

Operating manual EE23 humidity / temperature sensor

13

5 Calibration / Adjustment

5.1 Definitions

Calibration The calibration documents the accuracy of a measurement device. The device under test (specimen) is compared with the reference and the deviations are documented in a calibration certificate. During the calibration, the specimen is not changed or improved in any way.

Adjustment The adjustment improves the measurement accuracy of a device. The specimen is compared with the reference and brought in line with it. An adjustment can be followed by a calibration which documents the accuracy of the adjusted specimen.

For general calibration / adjustment guidelines and for the choice of humidity reference devices please see "Calibration Instructions" at www.epluse.com/ee23

The 2-point adjustment is recommended for best accuracy over a wide RH and / or T range.

Always start the 2-point adjustment with the lower adjustment point RH_low / T_low, followed by the higher adjustment point RH_high / T_high.

The span between the two adjustment points must be:

|RH_high ­ RH_low| > 30 % RH

|T_high ­ T_low|

> 30 °C (54 °F)

The 1-point adjustment should be used only when the RH and/or T range of interest is rather narrow. The RH resp. T adjustment point should be ideally in the middle of the range of interest.

Example: In a climate controlled environment with 40 % < RH < 60 % and 15 °C < T < 25 °C (59 °F < T < 77 °F), 1-point adjustment shall be performed at 50 % RH and 20 °C (68 °F).

1-point adjustment leads to very good accuracy within the range of main interest at the cost of the accuracy beyond this range.

5.2 Adjustment of EE23 Model T1, T2, T4 and T6 via Push Buttons on the Electronics Board
5.2.1 2-Point RH Adjustment Procedure / T Adjustment Procedure
1. For a RH humidity adjustment set the jumper to CALRH / for a temperature adjustment set the jumper to CAL T.
First point adjustment 2. Allow for the probe to stabilize at RH_low / T_low for min. 30 minutes.
3. Press BUTTONS2 for min. 3 seconds to start the adjustment procedure for the first point. The LED ,,D1" illuminates and ,,CAL<" appears on the LC display.
4. Press BUTTONS1 (up) and S2 (down) to adjust the measured value in steps of 0.1 % / 0.1 °C up or down to match the reference value. The change is indicated on the display (if available) or can be measured at the analogue output.
5. Press BUTTON S1 for min. 3 seconds to store adjusted value and end the first point adjustment. or

14

Operating manual EE23 humidity / temperature sensor

Press BUTTON S2 for min. 3 seconds to exit adjustment procedure without storing the adjusted value.
In both cases the LED ,,D1" and the symbol ,,CAL<" on the LC display are deactivated.
Second point adjustment 6. Allow for the probe to stabilize at the desired RH_high / T_high for min. 30 minutes.
7. Press BUTTON S1 for min. 3 seconds to start the adjustment procedure for the second point. The LED ,,D1" illuminates and ,,CAL>" appears on the LC display.
8. Press BUTTON S1 (up) and S2 (down) to adjust the measured value in steps of 0.1 % / 0.1 degC up or down to match the reference value. The change is indicated on the display (if available) or can be measured at the analogue output.
9. Press BUTTON S1 for min. 3 seconds to store adjusted value and end the first point adjustment. or Press BUTTON S2 for min. 3 seconds to exit adjustment procedure without storing the adjusted value.
In both cases the LED ,,D1" and the symbol ,,CAL>" on the LC display are deactivated.
5.2.2 1-Point RH Adjustment Procedure / T Adjustment Procedure
1. For a RH humidity adjustment set the jumper to CALRH / for a temperature adjustment set the jumper to CALT.
2. Allow for the probe to stabilize at the desired RH / T for min. 30 minutes.
3. For adjustment point > 50 % RH / in the upper half of the T output scale): press BUTTONS1 for min. 3 seconds to start the procedure. The LED ,,D1" illuminates and ,,CAL<" appears on the LC display. or For adjustment point < 50 % RH / in the lower half of the T output scale): press BUTTONS2 for min. 3 seconds to start the procedure. The LED ,,D1" illuminates and ,,CAL>" appears on the LC display.
4. Press BUTTONS1 (up) and S2 (down) to adjust the measured value in steps of 0.1 % / 0.1 °C up or down to match the reference value. The change is indicated on the display (if available) or can be measured at the analogue output.
5. Press BUTTONS1 for min. 3 seconds to store adjusted value and end the first point adjustment. or Press BUTTONS2 for min. 3 seconds to exit adjustment procedure without storing the adjusted value.
In both cases the LED ,,D1" and the symbol ,,CAL" on the LC display are deactivated.
5.2.3 Return to Factory Calibration
To return to RH or T factory calibration set first the jumper to RH or to T respectively.
During normal measuring mode (i.e. not during the adjustment procedure. LED D1 shall be off, the display shall not show "CAL") pressing BUTTONS1 and S2 together for min 5 seconds. The return to factory calibration is confirmed by a short flash of the LED ,,D1".

Operating manual EE23 humidity / temperature sensor

15

5.3 Adjustment of the EE23 Model T5 via the USB Service Interface
1. Download and install the EE-PCS Product Configuration Software from www.epluse.com/configurator 2. Connect the USB service interface of EE23-T5 to the PC. 3. Start the EE-PCS software. 4. Select the desired adjustment mode and follow the instructions of the EE-PCS.

6 Maintenance
When employed in dusty, polluted environment:
· The filter cap shall be replaced as needed with an E+E original one. A polluted filter cap causes longer response time of the device.
· For cleaning of the sensing head please see "Cleaning Instructions" at www.epluse.com/ee23.
7 Troubleshooting
See status LEDs at ,,3 Operating Components" on Page 6 and error messages on the display at ,,3.4 Display for Model T5" on Page 9.

7.1 Fuse Replacement for Option AM3

If the green LED on the PCB is not flashing with the supply voltage switched on check the fuse and replace if required.

Fuse secondary: 250 mA / T UL248-14

Recommended replacement types:

Series: MSTU 250 Manufacturer: Schurter

Series: 374

Manufacturer: Littelfuse

Order No.: 0034.7109 Order No.: 374 0250

Fig. 11 Fuse replacement

16

Operating manual EE23 humidity / temperature sensor

8 Accessories and Spare Parts
Description - Filter caps - External power supply unit - Display + housing cover in metal
for T1, T2, T4 and T6 for T5 - Display + housing cover in polycarbonate for T1, T2, T4 and T6 for T5 - Mounting flange for probe diameter 12 mm - Mounting flange 5mm (for model T6 only) - Bracket for plastic enclosure - for installation onto mounting rails - Drip water protection - Calibration set (see data sheet ,,Calibration Kit") - Radiation shield

Order Code HA0101xx V03
D03M-EE23 D05M-EE23T5
D03P-EE23 D05P-EE23T5 HA010201 HA010208 HA010203 HA010503 HA0104xx HA010502

Operating manual EE23 humidity / temperature sensor

17

9 Technical Data

Measurands

Relative Humidity

Working range

0...100 % RH

Accuracy1 (including hysteresis, non-linearity and repeatability, traceable to intern. standards, administrated by NIST, PTB, BEV...)

EE23-T1/T2/T4/T5

EE23-T6

-15...40 °C (5...104 °F)

90 % RH

± (1.3 + 0.3 %*mv) % RH

± (1.8 + 0,3 %*mv) % RH

-15...40 °C (5...104 °F)

>90 % RH

± 2.3 % RH

± 2.8 % RH

-25...70 °C (-13...158 °F)

± (1.4 + 1 %*mv) % RH

± (1.9 + 1%*mv) % RH

-40...180 °C (-40...356 °F)

± (1.5 + 1.5 %*mv) % RH

-

Temperature dependence electronics

typ. ± 0.015 % RH/°C

Response time t90 with metal grid filter at 20 °C (68 °F) Temperature

< 15 sec.

Probe working range

EE23-T1

-40...60 °C (-40...140 °F)

EE23-T2/T6

-40...80 °C (-40...176 °F)

EE23-T4

-40...120 °C (-40...248 °F)

EE23-T5

-40...180 °C (-40...356 °F)

Accuracy

°C

EE23-T1/T2/T4/T5

°C

EE23-T6

°C

°C

Temperature dependence of electronics Output Scale Span
from

Humidity Temperature Dew point temperature Frost point temperature

RH 0 T -40 (-40) Td -40 (-40) Tf -40 (-40)

typ. 0.002 °C/°C

EE23-T1 100
60 (140) 60 (140)
0 (32)

up to

EE23-T2/T6

EE23-T4

100

100

80 (176)

120 (248)

80 (176)

100 (212)

0 (32)

0 (32)

EE23-T5 100 180 (356) 100 (212)
0 (32)

units
% RH °C (°F) °C (°F) °C (°F)

Outputs
General Supply voltage for 0 -1 V / 0 - 5 V outputs for 0 - 10 V / 0 - 20 mA / 4-20 mA outputs
Current consumption for voltage output for DC supply for AC supply
Current consumption for current output for DC supply for AC supply
Enclosure / protection class Cable gland Electrical connection Working temperature range of electronics Working temperature range with display Storage temperature range CE compatibility according
Alarm Module2) Output
Setting range Setting accuracy

0 - 1 V 0 - 5 / 0 - 10 V 0 - 20 mA / 4 - 20 mA

-0.5 mA < IL < 0.5 mA -1 mA < IL < 1 mA RL < 470 Ohm

10.5 - 35 V DC or 12 - 28 V AC 15.0 - 35 V DC or 15 - 28 V AC 100...240 V AC, 50/60 Hz supply module (optional)

 25 mA (with alarm module  35 mA)  45 mAeff (with alarm module  70 mAeff)
 55 mA (with alarm module  65 mA)  100 mAeff (with alarm module  120 mAeff) PC or Al Si 9 Cu 3 / IP65; NEMA 4 M16x1.5 cable Ø 4.5 - 10 mm (0.18 - 0.39") screw terminals max. 1.5 mm² (AWG 16) -40...60 °C (-40...140 °F) -30...60 °C (-22...140 °F) -40...60 °C (-40...140 °F) EN61326-1 EN61326-2-3 ICES-003 ClassB Industrial Environment FCC Part15 ClassB

SPDT-Switch max. 250 V AC/8 A or 28 V DC/8A

threshold

hysteresis

10...95 % RH

3...15 % RH

± 3 % RH

1) The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) only for models T1, T2, T4 and T6.

18

Operating manual EE23 humidity / temperature sensor

Relative humidity [%RH]

9.1 Operating Range Humidity Sensor
Temperature [degC]
The gray area shows the allowed measurement range for the humidity sensor. Operation beyond this range does not destroy the sensing element, but the specified measurement accuracy cannot be guaranteed.

Operating manual EE23 humidity / temperature sensor